This document package includes a floor plan drawing and specifications for a federal construction project, along with a presolicitation notice for additional environmental monitors at a Veterans Health Administration facility.
The floor plan drawing and specifications are for the replacement medical center project at the Southeast Louisiana Veterans Health Care System in New Orleans. The drawing shows the fourth floor plan for Building B2 and includes notes on partition types, door and relite schedules, references to other drawings, and other construction details. The presolicitation notice indicates the Veterans Health Administration will be issuing a request for proposal around June 4, 2021 for the installation of additional environmental monitors at the New Orleans facility, with an estimated construction cost between $500,000 and $1 million. The solicitation will be set aside for service-disabled veteran-owned small businesses, who must meet certain limitations on subcontracting and be registered and verified in federal databases to be considered for award. Interested offerors should check the beta.SAM website for the full RFP and any amendments.
View the file
Other files for this federal contract opportunity
Show all 47
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
UP
1 A I1
-B
1 A
I1
-B
PATIENT
4B163
REF:2B145
PATIENT
4B161
REF:2B145
PATIENT
4B159
REF:2B145
PATIENT
4B157
REF:2B145
PATIENT
4B152
REF:2B145
PATIENT
4B164
REF:2B145
PATIENT
4B162
REF:2B145
PATIENT
4B160
REF:2B145
PATIENT
4B158
REF:2B145
PATIENT
4B156
REF:2B145
PATIENT
4B154
REF:2B145
PATIENT
4B151
REF:2B145
PATIENT
4B150
REF:2B145
ANTE
POS
4B165B
REF:2B165B
PATIENT
POS
4B165
REF:2B145
L
K
H
M
STAIR
STB-2
EC
4B153
REF:2B153
T
4B151A
REF:2B145A
T
4B150A
REF:2B145A
T
4B154A
REF:2B145A
T
4B156A
REF:2B145A
T
4B158A
REF:2B145A
T
4B160A
REF:2B145A
T
4B162A
REF:2B145A
T
4B164A
REF:2B145A
T
4B163A
REF:2B145A
T
4B161A
REF:2B145A
T
4B159A
REF:2B145A
T
4B157A
REF:2B145A
T
4B152A
REF:2B145A
SUB-STATION
4B132H
REF:2B130A
SUB-STATION
4B132D
REF:2B130A
SUB-STATION
4B132F
REF:2B130A
T
4B167
REF:2B167
ISO T
4B165A
REF:2B145A
CC
4B165C
REF:2B155A
AISLE
4B-C03A
1AS711
F2
CC
4B155A
REF:2B155A
SOILED
4B155E
REF:2B155E
CLEAN
4B155D
REF:2B155D
MED
4B155B
REF:2B155B
NOUR
4B155F
REF:2B155F
1.8
2.5
M.1
SUPPLY
4B132A
REF:2B130B
SUB-STATION
4B132B
REF:2B130A
SUPPLY
4B132C
REF:2B130B
G.6
CR
4B167
4B156.24B154.2 4B160.24B158.2 4B162.2
4B151.2 4B159.2 4B161.2 4B163.2
4B
5.
4B
5.
4B155B 4B155E
4B153
4B -C
4B150.2
4B
0.
4B157.2
4B
7.
4B152.2
4B
4.
4B164.2
SUPPLY
4B132G
REF:2B130B
SUPPLY
4B132E
REF:2B130B
J
EQ EQ
STP
FEC
FEC
1.3 01
1.4
1AI424
A2
SIM
1AI424
F3
SIM
A_6AC
A_ 6A
C
A_8ACA_6AC
J_4CJ_4C
J_4CJ_4C
A16AB
A14AB
A16AB
A16AB
A14BA14B 01
4B
1.
4B
9.
4B
1.
4B
3.
4B
6.
4B
4.
4B
0.
4B
8.
4B
2.
4B
2.
V16AB
CORR
4B-C03
REF:2B-C03
CORR
4B-C03
J_4
4B165.2
4B
5.
4B
5D
102 102
102 102
4.9
0AI510.2
B5
0AI510.1
C4
0AI510.2
A2
0AI510.2
A5
0AI510.2
A5
0AI510.2
B5
0AI510.1
B4
4B155C
TELECOM
4B155C
REF:2B155C
4B -S
TB
-2
Q
D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
P
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
T E
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F I N
C H
O
N E
FO
O
T
TH
R
EE
Q U
A R
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
( 1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
E S
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
1AI104-B2
BLDG 1 FOURTH FLOOR PLAN - AREA B2
ML AG/DMKFebruary 29, 2012
01629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
Department of
Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
I.S.C. GROUP, INC. / IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC. / WATER FEATURE
SCALE: 1/8" = 1'-0"1
GENERAL FLOOR PLAN NOTES
SLAB OPENING - REF STRUCTURAL DWGS
ALIGN PARTITIONS
LINE OF CURTAIN WALL SILL - REF EXTERIOR SERIES DWGS.
LINE OF HOISTWAY BELOW
AIR HANDLER UNIT - REF MECHANICAL DWGS
STEEL BRACING - REF STRUCTURAL DWGS
CONCRETE HOUSEKEEPING PAD - REF STRUCTURAL DWGS
ACCORDIAN FIRE DOOR - REF DOOR SCHEDULE
: 14 92 00 PNEUMATIC TUBE STATION - REF DETAILS C4 &
C5/0AI507.
08 31 13 FLOOR VAULT DOOR - 36" X 36". REF DTL E1/0AI516
ROOF/OVERFLOW DRAIN LEADER - REF PLUMBING DWGS
ELECTRICAL PANEL - REF ELECTRICAL DWGS
MEDICAL GAS ZONE VALVE BOX/MEDICAL GAS ALARM PANEL - REF MED
GAS DWGS
SLOPE FLOORING IN SHOWER/TOILET ROOM TO FLOOR DRAIN
SLAB RECESS FOR HIGH DENSITY SHELVING TRACK. VFY RECESS
DIMENSION W/ SHELVING MANUFACTUER.
14 91 34 TRASH/LINEN CHUTE & STATION: SEE DETAILS E6/0AI507
14 91 34 TRASH/LINEN CHUTE: NO LOADING STATION
14 91 34 TRASH/LINEN CHUTE: PROVIDE SLEEVES @ LEVEL 01 FLOOR
SLAB PENETRATION - SEE DETAILS E6/0AI507
08 31 13 3-HOUR FIRE RATED ACCESS PANEL - 24" X 48".
ELECTRICAL RISERS - SEE PLAN DETS ON F5/0AI512 - REF ELEC DWGS
CONCRETE ENCASED ELECTRICAL FEEDERS ABOVE - REF STRUCTURAL &
ELEC DWGS
09 27 02 GLASS FIBER REINFORCED GYPSUM COLUMN COVER -
36" O.D. UON.
BOLD DASHED LINE INDICATES ROUTE OF STRUCTURAL EXPANSION JOINT
- REF STRUCTURAL DWGS. REFERENCE FLOOR PLAN LEGEND FOR
INTERIOR EXPANSION JOINT COVER ASSEMBLY INFORMATION.
10 11 00 MARKER BOARD REF INTERIOR ELEV SHEET NOTE 207.
10 11 00 TACK BOARD REF INTERIOR ELEV SHEET NOTE 208.
10 28 00 FOLD-DOWN BENCH
10 28 00 FOLD-DOWN SHOWER SEAT
SLAB RECESS FOR WALK-OFF GRILLE. VFY RECESS DIMENSION W/
GRILLE MANUFACTURER. SEE FLOOR FINISH PLANS FOR EXTENTS.
PLUMBING ROUGH-IN FOR FUTURE SINK - REF PLUMBING DWGS.
BENT PLATE W/ TRAFFIC COATING WRAP @ WALL BASE - REF B3/0AI516
LINE OF 2-HR RATED SHAFT ABOVE. REF DETAILS E1 & E3 SHT 0AI507
05 05 00 ACCESS LADDER
10 33 13 WIRE MESH PARTITION
05 52 13 PIPE AND TUBE RAILING
11 13 00 MANUAL DOCK LEVELER AND BUMPERS
13 44 00 MODULAR MEZZANINES INCL. STAIRS & WIRE MESH PTNS.
05 50 00 METAL GRATE CATWALK
WALL MOUNTED HAND SINK - REF PLUMBING DWGS
RECESSED EMERGENCY SHOWER AND EXPOSED STAINLESS STEEL
SHOWER HEAD - REF PLUMBING DWGS
08 39 19 FLOOD BARRIERS: FLOOD PLANK SYSTEM - REF D5/0AI511
CONC. WALLS @ L 01 ELEV SHAFTS - REF STRUCT DWGS & DTL D2/0AI507
BENT PLATE W/ PEDESTRIAN TRAFFIC COATING WRAP - REF C3/0AI516
PLENUM SYSTEM - SEE EXTERIOR DRAWINGS
CENTER PARTITION ON GRIDLINE
CENTER PARTITION ON MULLION
10 21 13 TOILET PARTITIONS
TOP OF SHAFT LID ASSEMBLY - REF DETAIL B4/0AI507
CONC CURB W/ PEDESTRIAN TRAFFIC COATING WRAP - REF D3/0AI516
LIGHTING INVERTER CABINET - REF ELEC DWGS
ELEVATOR SUMP PUMP CONTROL PANEL - REF PLUMB DWGS
100.
101.
102.
103.
104.
105.
106.
107.
108.
109.
110.
111.
112.
113.
114.
115.
116.
117.
118.
119.
120.
121.
122.
123.
124.
125.
126.
127.
128.
129.
130.
131.
132.
133.
134.
135.
136.
137.
138.
139.
140.
141.
142.
143.
144.
145.
146.
147.
148.
149.
FLOOR PLAN SHEET NOTE SERIES BEGINS WITH NOTE 100
NOT ALL SHEET NOTES APPEAR ON EVERY SHEET
1XX
1. REFER TO SHEET 0AI002 FOR PARTITION SCHEDULE AND GENERAL
PARTITION TYPE NOTES.
2. REFER TO AI400 SERIES FOR ENLARGED FLOOR PLAN VIEWS INCLUDING
MEDICAL EQUIPMENT NOT SHOWN IN AI100 SERIES PLANS.
3. REFER TO LIFESAFETY DRAWINGS (LS SERIES) FOR CAMPUS-WIDE
SCOPE OF RATED WALL CONSTRUCTION, SMOKE PARTITIONS, SUITE
DESIGNATIONS AND EXIT DISCHARGE INFORMATION.
4. PARTITION TYPES AS NOTED BY THE SYMBOL CONTINUE BETWEEN
ROOM/SPACE CORNERS OR ANY INTERSECTING PARTITION.
5. DIFFERING PARTITION TYPES SHALL ALIGN SO THAT WALL PLANES
CONTINUE UNBROKEN WITHIN/ACROSS ROOMS AND/OR SPACES.
6. UNLESS OTHERWISE NOTED, DIMENSIONS ARE TO FINISH FACE.
7. REFER TO AI600 SERIES DRAWINGS FOR DOOR & RELITE SCHEDULES.
8. DISTANCE FROM HINGE SIDE OF DOOR TO INTERSECTING STUD WALL
SHALL BE 4" UNLESS NOTED OR DETAILED OTHERWISE (MEASURED
FROM OUTSIDE OF FRAME).
9. CONTRACTOR SHALL VERIFY ALL DIMENSIONS NOTED AS "CLEAR" OR
"MIN". DIMENSIONS NOTED AS "HOLD" ARE CRITICAL TO COORDINATE
OTHER WORK (E.G. CEILING GRIDS, LIGHTING, FINISHES).
10. CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO INITIATING
CONSTRUCTION AND REPORT DISCREPENCIES TO ARCHITECT PRIOR TO
COMMENCING WORK.
11. CONTRACTOR SHALL PROVIDE ALL BLOCKING REQUIRED TO ANCHOR
ALL WALL AND CLG MOUNTED ITEMS, INCLUDING BUT NOT LIMITED TO
TOILET ROOM ACCESSORIES, MILLWORK, CASEWORK, HANDRAILS,
DOOR STOPS ETC...
12. FIRE STOPPING SYSTEMS - REFER TO SPEC SECTION 07 84 00 FOR INFO
REGARDING PENETRATIONS OF ALL RATED ASSEMBLIES (BOTH SINGLE
AND DOUBLE MEMBRANE PENETRATIONS) INCLUDING BUT NOT LIMITED
TO PENETRATIONS FOR DUCTWORK, CONDUIT, PIPING AND SUPPORT
FOR WALL MOUNTED EQUIPMENT, CABINETS AND COUNTERTOPS.
13. UP-SWING GRAB BAR IN-WALL SUPPORT - SEE DTLS C3 AND A3 SHEET
0AI506 FOR TUBE STEEL BACKING AT ALL UP-SWING GRAB BARS.
14. SEE DETAIL A3/0AI516 FOR COLUMN BASE WATERPROOFING AT
EXPOSED COLUMNS IN SERVICE BAYS & MECHANICAL ROOMS.
15. SHIELDING REQUIREMENTS - VERIFY ALL SHIELDING REQUIREMENTS
WITH FINAL EQUIPMENT SELECTIONS AND A VA APPROVED REGISTERED
PHYSICIST PRIOR TO COMMENCING WORK IN SHIELDED-ROOM AREAS.
16. HOUSEKEEPING AND COPY ROOMS - ALL PARTITIONS TO BE FULL
HEIGHT TO UNDERSIDE OF DECK/INTERSTITIAL ABOVE. SEE PARTITION
TYPE NOTES SHEET 0AI002.
FLOOR PLAN SHEET NOTES
KEY PLAN
FLOOR PLAN LEGEND
ROOM NUMBER
REFERENCE ROOM NUMBER:
REFERENCE ROOM NUMBER INDICATES ROOM TO
REFERENCE FOR TYPICAL MEDICAL EQUIPMENT LAYOUT,
INTERIOR ELEVATION TAGS, GENERAL ANNOTATION AND
DIMENSIONS UNLESS OTHERWISE NOTED.
NOT ALL SYMBOLS/NOTES APPEAR ON EVERY SHEET
WHERE SYMBOL REFERENCES ANOTHER DRAWING SERIES,
SYMBOL IS SHOWN FOR DESIGN/DIMENSIONAL COORDINATION
ONLY. REFERENCE THE ENGINEERING DRAWINGS FOR FULL
SCOPE OF DEVICE LOCATIONS & ASSOCIAITED SPECIFICATIONS.
LEAD
RF
XXXX
1X
EMI
REF:XXXX
FD
CR
FEC
FEC_20
FEW
HVC
EXX-X
LKR-XX
PB
IA
FA/PS
SEE SHIELDING DETAILS/SCHEDULES ON SHEET 0AI514
LEAD SHIELDING
RADIOFREQUENCY SHIELDING
ELECTROMAGNETIC INTERFERENCE SHIELDING
MAGNETIC SHIELDING
07 95 13 - INTERIOR EXPANSION JOINT COVER ASSEMBLY -
"XX-X" LETTER DESIGNATION INDICATES COVER TYPE PER SHEET
0AI517. REFERENCE FIRE/SMOKE RATED CONDITIONS AS
INDICATED BY ASSOCIATED PTN TYPES ON THE FLOOR PLANS.
LOCKERS: "XX" DESIGNATION INDICATES TYPE:
2A - 10 51 13 - DBL TIER METAL LOCKERS, SLOPED TOP
12"W X 15"D X 60"H
LOCKERS PAINTED TO MATCH ADJ WALL
REF DTL D2/0AI532
2A.1 - 10 51 13 - DBL TIER METAL LOCKERS, SLOPED TOP
12"W X 15"D X 60"H
LOCKERS PAINTED TO MATCH ADJ WALL
REF DTL E2/0AI532
2B - 10 51 23 - DBL TIER "Z" PLAM LOCKERS, W/ PLAM SOFFIT
12"W X 15"D X 80"H
FINISH: PLAM-10
REF DTL E2/0AI532
TOPS OF LOCKERS TO ALIGN AT 7'-0" AFF.
FOR REFERENCE ONLY - GENERAL LOCATION OF OPEN OFFICE
FURNITURE - SEE FURNITURE DWGS FOR EXACT TYPES AND
LOCATIONS.
CARD READER - REF LOW VOLTAGE DWGS
DOOR PUSH PLATE - REF LOW VOLTAGE DWGS
PANIC ALARM BUTTON - REF LOW VOLTAGE DWGS
INFORMATION ASSIST CALL BOX - REF LOW VOLTAGE DWGS
FIRE ALARM PULL STATION - REF FIRE ALARM DWGS
10 44 13 - FIRE EXTINGUISHER CABINETS
RECESSED CABINET SIZED TO HOLD 10# ABC EXTINGUISHER
RECESSED CABINET SIZED TO HOLD 20# CO2 EXTINGUISHER
WALL MOUNTED EXTINGUISHER LOCATION
FIRE DEPARTMENT HOSE VALVE CABINET - REF FIRE PROT. DWGS
FLOOR DRAIN - REF PLUMBING DWGS
WHERE DRAIN IS NOT SET IN DEPRESSED SLAB/SLOPED
FLOOR SYSTEM; SET DRAIN 1/2" BELOW FINISH FLOOR
LEVEL AND TAPER CONC. AND FLOORING TO FLUSH W/
DRAIN STRAINER IN A 2' RADIUS FROM CENTER OF DRAIN
FLOOR OUTLET - REF ELECTRICAL DWGS
FLOOR CLEAN OUT - REF PLUMBING DWGS.
MAG
FCO
DASHED OBJECTS WITH EQUIPMENT TAG INDICATE
MEDICAL/OFFICE EQUIPMENT. REFERENCE EQUIPMENT
ACTIVIATION REPORT - SEE SPECIFICATIONS SECTION
01 11 10 FOR LOCATION OF REPORT.
X1234
XX1234
DP
TOILET WITH WALL MOUNTED UP-SWING GRAB BARS
10 28 00
SEE SHEET 0AI201 FOR GRAB BAR MOUNTING
HEIGHTS AND DIMENSIONAL LAYOUT
TOILET WITH WALL MOUNTED GRAB BARS
10 28 00
SEE SHEET 0AI201 FOR GRAB BAR MOUNTING
HEIGHTS AND DIMENSIONAL LAYOUT
XXXXX
PARTITION TYPE TAG - REF PARTITION SCHEDULE SHT 0AI002
RELITE TAG - REF FRAME SCHEDULE SHEET 0AI600
DOOR TAG - REF DOOR SCHEDULES AI600 SERIES
XAI40X
A
DB
C
INTERIOR ELEVATION REFERENCE:
INTERIOR ELEVATION CALLOUT
SHEET ON WHICH ELEVATION IS DRAWN
XAI10X
XAI10Y MATCHLINE REFERENCE
CENTERLINE TAG
SPOT ELEVATIONEL: +10'-0"
DIMENSIONS SAME AS LEVEL 02 AREA B2 UON
INTERIOR BACK-UP WALL, OPENINGS, SOFFITS, ETC
AROUND PERIMETER OF BUILDING REVISED TO
COORDINATE W/ EWP-06 SKIN COST REDUCTIONS. NEW
AND/OR REVISED PLAN/SECTION/RCP DETAILS AS
INDICATED ON PLANS AND REFLECTED CEILING PLANS.
11 BULL 015A - PRE-AWARD 7/26/2013
12 BULL 015A - VE 7/26/2013
Refer to RFI 01551: Interior Wall Construction Clarification at Exterior Walls
RFI 01551.1 for Interior Wall Construction at Precast Walls
RFI 02197 - 1'-1" from back of precast to finish face of drywall