Charleston_Facility_Survey_Vol._2_March_2012.pdf

PDF 5 MB Posted

Attached to
Operation of Charleston Job Corps Center which includes Career Transition Services
Solicitation number
DOL-ETA-15-R-00057
Issued by

About this file

J-9 Facility Survey Volume 2

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CharlestonCharleston

Job Corps Center Charleston, WV

Facility Planning ReportFacility Planning Report Volume II

Supporting Data

Fi lFinal March 2012

Department of Labor/ Office of Job Corps

22Charleston Job Corps Center

CharlestonCharleston

Job Corps Center Charleston, WV

Facility Planning ReportFacility Planning Report Volume II

Supporting Data

Fi lFinal March 2012

Dormitories and Commons

33 Charleston Job Corps Center

CONTENTS

CHARLESTON JOB CORPS CENTER

FACILITY PLANNING REPORT

VOLUME I - Planning Strategy

• Existing Site Plan

• Center Statistics

INTRODUCTION

• Purpose

• Report Contents

EXECUTIVE SUMMARY

A. EXISTING CONDITIONS

• Background

• General Site Conditions

• General Building Conditions

• Preventive Maintenance

• Ownership

• Facility Assessment by Function

• Energy

• Environmental Issues

• Sustainability

• Accessibility Standards

• Health and Life Safety Issues

• Summary of Defi ciencies

B. RECOMMENDATIONS

• Status of the Previous (PY08) Plan

• Signifi cant Issues

• PY 11 Plan Overview

• Summary of Proposed Projects

• Regional Projects

• Proposed Site Plan Implementation Plan

• Summary of National Projects

• Project Data Sheets

C. PLANNING ANALYSIS

• Purpose

• Planning Objectives and Assumptions

• Space Utilization Analysis

• Federal Real Property Asset Management

• Mission Dependency Site Plan

• Defi ciency Analysis

• Facility Condition Summary Report

• Building Condition by Function

• Building Condition Site Plan

VOLUME II - Supporting Data

• Vicinity Map

• Location Map

• Existing Site Plan

D. DESCRIPTIONS

• Buildings and Structures

• Space Utilization By Function

• NSF by Building

• Energy Management Report

• Environmental Management

Radon Report

• Site Descriptions

• Building Descriptions

E. DEFICIENCIES

F. CORRESPONDENCE AND REPORTS

• Center Review Meeting Minutes

• Survey Brief

• RA and Student Facility Feedback Questionnaire

• Life Safety Defi ciencies Transmittal and List

• O & M Defi ciency List

• Active Warranty Report

• FRPC Performance Measures Matrix

44Charleston Job Corps Center

55 Charleston Job Corps Center

C harleston Job C orps C enter

77 Charleston Job Corps Center

D Descriptions

BUILDINGS AND STRUCTURES

00303 CHARLESTON 16-FEB-12

1Page: of 1

A - ADMIN/MEDICAL/DENTAL

B - EDUCATION

C - VOCATIONAL

D - CAFETERIA/CULINARY ARTS

E - RECREATION

F - MAINTENANCE/WAREHOUSE

G - RECEPTION/SECURITY

H - FEMALE DORMITORY

I - MALE DORMITORY

M - PUMP HOUSE

N - CARPENTRY

O - MAINTENANCE STORAGE

S - FACILITY MAINTENANCE VOCATION

STORAGE

T - PAINTING VOCATION STORAGE

L - FLAMMABLE STORAGE

P - GAZEBO

Q - GAZEBO

R - GAZEBO

U - GAZEBO

V - GREEN HOUSE

W - STORAGE

X - STORAGE

Name GSF

11,270 10,710 25,140 13,920 24,000 15,450

32,900 32,900

1,050

1,200

Active Active Active Active Active Active Active Active Active Active Active Active Active

Active Active Active Active Active Active Active Active Active

StatusType

Building Building Building Building Building Building Building Building Building Building Building Building Building

Building Structure Structure Structure Structure Structure Structure Structure Structure

Use Group Built Flrs Const

Business Business Business Assembly Assembly Storage Utility/Misc.

Residential Residential Utility/Misc.

Storage Storage Storage

Storage Storage Business Business Business Business Utility/Misc.

Storage Storage

Good Good Good Good Good Good Good Good Good Good Good Good Good

Good Good Good Good Good Good Good Good Good

ConditionAsset Number

0030300002 0030300003 0030300004 0030300005 0030300006 0030300007 0030300008 0030300009 0030300010 0030300014 0030300016 0030300015 0030300020

0030300021 0030300013 0030300017 0030300018 0030300019 0030308110 0030308111 0030308112 0030308113

14 170,746

8 3,160

22 173,906

Buildings

Structures

Total

GSF

GSF

GSF

Summary

Net Square Footage By Building Date: 02/16/2012 Page: 1Center: CHARLESTON (00303) of 4

HOUSING

Sleeping

Lounge

Storage

Shower/Toilet

Other

Function Suggested NSF

13,584 13,584

3,424 3,424

2,388 2,388

1,894 1,894

H - FEMALE DORMITORY

I - MALE DORMITORY

H - FEMALE DORMITORY

I - MALE DORMITORY

I - MALE DORMITORY

H - FEMALE DORMITORY

I - MALE DORMITORY

H - FEMALE DORMITORY

H - FEMALE DORMITORY

I - MALE DORMITORY

Bldg Name Actual NSF Difference

27,168

6,848

4,776

3,788

Sub Total: 43,054

23,904

3,320

1,992

3,984

33,200

3,264

3,528

-1,518

3,788

( 332

9,854

Page: 2Center: CHARLESTON (00303) of 4

EDUCATION

Academic

Vocational Theory (172)

Carpentry

Health Occupations

Culinary Arts

Painting

Network Cable Installer

HVAC

Facilities Maint. and Const.

Non-Academic

Business Office Technologies

Medical Office Specialist

Function Suggested NSF

1,168

2,007

2,814

1,436

1,724

1,126

2,880

2,077

3,261

1,084

2,433

1,849

1,944

B - EDUCATION

B - EDUCATION

B - EDUCATION

B - EDUCATION

D - CAFETERIA/CULINARY ARTS

C - VOCATIONAL

N - CARPENTRY

C - VOCATIONAL

C - VOCATIONAL

D - CAFETERIA/CULINARY ARTS

T - PAINTING VOCATION STORAGE

N - CARPENTRY

C - VOCATIONAL

C - VOCATIONAL

C - VOCATIONAL

S - FACILITY MAINTENANCE VOCATION STOR

C - VOCATIONAL

F - MAINTENANCE/WAREHOUSE

B - EDUCATION

B - EDUCATION

H - FEMALE DORMITORY

E - RECREATION

C - VOCATIONAL

E - RECREATION

I - MALE DORMITORY

B - EDUCATION

B - EDUCATION

C - VOCATIONAL

C - VOCATIONAL

Bldg Name Actual NSF Difference

2,692

2,392

3,154

1,436

1,724

4,346

2,077

3,825

8,544

1,944

Sub Total: 34,069

3,900

1,720

1,500

1,500

1,800

3,600

3,900

18,820

-1,208

1,654

1,436

1,724

2,846

4,644

1,944

( 390

15,249

Page: 3Center: CHARLESTON (00303) of 4

FOOD SERVICE

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

Dining (2 Servings)

Food Preparation

Food Storage

Multipurpose Room

Recreation Hall

Arts & Crafts

Gymnasium

Weight Room

Student Store

Miscellaneous Recreation

Recreation/Snack Bar

Recreation Storage

Recreation Office

Medical/Dental

Administration

Function Suggested NSF

4,026

2,421

1,296

1,565

8,235

1,048

1,082

2,715

4,480

D - CAFETERIA/CULINARY ARTS

D - CAFETERIA/CULINARY ARTS

D - CAFETERIA/CULINARY ARTS

E - RECREATION

E - RECREATION

E - RECREATION

E - RECREATION

E - RECREATION

E - RECREATION

E - RECREATION

E - RECREATION

E - RECREATION

E - RECREATION

A - ADMIN/MEDICAL/DENTAL

A - ADMIN/MEDICAL/DENTAL

G - RECEPTION/SECURITY

Bldg Name Actual NSF Difference

4,026

2,421

1,296

1,565

8,235

1,048

1,082

2,715

4,950

Sub Total:

Sub Total:

Sub Total:

Sub Total:

7,743

15,280

2,715

4,950

3,120

2,340

1,560

2,070

7,800

7,020

17,470

2,070

7,800

-264

-2,850

-2,190

-2,850

Page: 4Center: CHARLESTON (00303) of 4

STORAGE/SUPPORT

Warehouse

Operations & Maintenance

Function Suggested NSF

7,524

1,030

7,118

F - MAINTENANCE/WAREHOUSE

O - MAINTENANCE STORAGE

M - PUMP HOUSE

F - MAINTENANCE/WAREHOUSE

Bldg Name Actual NSF Difference

7,524

8,369

Sub Total: 15,893

4,680

3,120

7,800

2,844

5,249

( 390

8,093

February 16, 2012 Space Utilization By Function 00303 Charleston

Page: 1 of 2

HOUSING

EDUCATION

FOOD SERVICE

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Residents 332 Non Residents 58

390Total Students

(332)

(390)

(390)

DIFFERENCE

33,200

27,520

7,020

43,054

34,069

7,743

Lounge Other Shower/Toilet Sleeping Storage

Academic (390) Non-Academic

45 -- ACT (Off-Ctr) 0 -- Business Office Technologies 20 -- Carpentry + 30 -- Cert. Nursing Asst.

0 -- Culinary Arts + 30 -- Dental Assistants + 48 -- Facilities Maint. and Const. +

24 -- HVAC +

0 -- Health Occupations + 0 -- Medical Office Specialist 30 -- Medical Office Support 30 -- Network Cable Installer

25 -- OCT

90 -- Office Administration 20 -- Painting + 30 -- Pharmacy Tech +

Vocational Theory (172)

Dining (2 Servings) Food Preparation Food Storage

6,848 3,788 4,776

27,168

2,692 8,544

1,944 3,154

1,724

3,825 2,077 1,436

4,346

2,392

4,026 2,421 1,296

3,320

3,984 23,904

1,992

3,900 3,900

1,500 1,200

1,200 3,600 1,800

4,050 1,500 1,350

1,720

3,120 2,340 1,560

3,528

3,264 -1,518

-1,208 4,644

1,654

2,846

-264

Vocations

9,854

6,549

February 16, 2012 Space Utilization By Function 00303 Charleston

Page: 2 of 2

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

TOTAL 263.79 102,880 123,704

(390)

(390)

(390)

(390)

DIFFERENCE

170,746

0.72

TOTAL GSF

NET TO GROSS RATIO

17,470

2,070

7,800

7,800

15,280

2,715

4,950

15,893

Arts & Crafts Gymnasium Miscellaneous Recreation Multipurpose Room Recreation Hall Recreation Office Recreation Storage Recreation/Snack Bar Student Store Weight Room

Medical/Dental

Administration

Operations & Maintenance Warehouse

5.31

8,235 1,082

1,565

1,048

2,715

4,950

8,369 7,524

2,070

7,800

3,120 4,680

-2,850

5,249 2,844

RESIDENT

NON-RESIDENT

(332)

(58) 15

50 16,600

-2,190

-2,850

8,093

20,824

Energy Management Report Center: CHARLESTON (00303)

Page: 1 Date: 02/16/2012 of 3

CENTER ENERGY DATA

Deferred (new center)

ENERGY CONSUMPTION ASSESSMENT

16% 72,084 70,023 85,393

ENERGY USE BY FUEL TYPE

Energy Audit :

Date of Audit :

Electric Company :

Percent Reduction since Baseline Year :

Natural Gas Company :

Property Status :

N/A

American Electric Columbia Gas

Federally Owned (DOL)

2,300,720 7,850=

Total 12,308

MBtu

MBtu

Total $288,610 MBtu/ $23.449

BTU/GSF

BTU/GSF

BTU/GSF

Electricity

Natural Gas kWh

4,324 MCF = 4,458 MBtu

$220,990 $0.096= kWhElectricity

Natural Gas $67,620 = $15.638 MCF

ENERGY COST BY FUEL TYPE

WATER CONSUMPTION ASSESSMENT

FY 2007 Baseline:

Percent Reduction Since Baseline Year:

1,000 Gallons

1,000 Gallons

FY 2011 Energy Goal:

Further Reduction in Energy Usage is needed to meet Energy Reduction Goals.

FY 2011 Energy Consumption:

Note: The Federal Government has set a goal of 3% Energy Consumption Reduction per year in EO 13423.

8,713 8,016 7,165

18%

Water Goals are being met. Keep reducing Water Consumption.

Note: The Federal Government has set a goal of 2% Water Consumption Reduction per year in EO 13423.

FY 2011 Goal:

FY 2011 Water Consumption:

1,000 Gallons

FY 2003 Energy Baseline:

Page: 2 Date: 02/16/2012 of 3

Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.

1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:

a. Turn it down (lights, heating & cooling),

b. Turn it off (lights, computers, other equipment),

c. Keep it tight (close doors and windows, use window blinds)

2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:

a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.

b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.

c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.

d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.

e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.

f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.

g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.

h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.

i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.

Page: 3 Date: 02/16/2012 of 3

j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.

k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.

l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.

m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.

n. Caulk and fill cracks around doors and windows to reduce costly air leaks.

o. When replacing broken glass, use high transmittance, low heat gain windows.

p. Make sure automatic door closers are functioning properly to avoid drafts.

3. Buy energy efficient, buy EnergyStar (www.energystar.gov).

a. Buy EnergyStar appliances and equipment.

b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).

c. Replace broken thermostats with EnergyStar labeled programmable products.

d. Replace broken exit signs with EnergyStar LED exit signs.

Environmental Management Report

Page: 1 Date: 02/16/2012 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

Commercial Waste Service

HAZARDOUS MATERIALS STORAGE (EPCRA)

No Buildings L, N, O

Organic solvent (50 gals), propane (50 lbs), oil-based paint (100 gals) Yes

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

N/A0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

N/A None

Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazadous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

HazMat Spill Response Plan :

Number of Regulated USTs :

Number of Un-regulated USTs :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance

ID LocationFuel Type Capacity

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

AHERA Regulated :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Williams Waste Management No N/A

N/A N/A N/A

N/A

No No

Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

No N/A

No Survey Performed None N/A

N/A N/A

No Yes

ID Fuel Type Capacity Location Overfill

Prevention Secondary Containment

1 Petroleum - Diesel Fuel 100 Inside Building M Yes Yes

Tank Status Active

Tank Status Prevention/Detection

Radon

Date: Feb. 16, 2012Center : Charleston (00303) Page: 1 of 1

A - ADMIN/MEDICAL/DENTAL

B - EDUCATION

C - VOCATIONAL

D - CAFETERIA/CULINARY ARTS

E - RECREATION

F - MAINTENANCE/WAREHOUSE

G - RECEPTION/SECURITY

H - FEMALE DORMITORY

I - MALE DORMITORY

M - PUMP HOUSE

N - CARPENTRY

O - MAINTENANCE STORAGE

S - FACILITY MAINTENANCE VOCATION STORAGE

T - PAINTING VOCATION STORAGE

Bldg Name

02/14/2004

02/16/2004

02/14/2004

Test Date

Yes

No

Yes

No

No

Yes

No

No

No

N/A

N/A

N/A

N/A

N/A

Radon Testing

< 4 pCi

< 4 pCi

< 4 pCi

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.

303 Ch l t J b C C t303 Charleston Job Corps Center Site Description

View of Parking at Entrance to Center

Page: 1 Date: 02/16/2012 of 4

Comments:

Paving Type for Roads & Parking

There is a speed bump by Reception/Security Building G. There is a vehicular drive around the site perimeter.

Concrete sidewalks provide internal pedestrian circulation.

Paving Type for Sidewalks

Asphalt Concrete

Comments:

Topography Buildings and Structures

Center is not fully enclosed by fencing. There are landscape features on the student promenade. The site is partially fenced on the north side between the parking lot and vehicular drive and on the south side along the vehicular drive and baseball field. Two signs are on the access road near the center entrance. There are two metal entrance gates, one manual and one electronic.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water System

Treatment Type Storage Type Storage Capacity(Gallons)

NoMasterCity of CharlestonAmerican Water Systems

Source Water Disinfection 0None

The meter is located just west of Pump House Building M.Comments:

Comments:

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time (Minutes)

Yes 0 10None Fire Pump

The Center is served by a Peerless Pump Company duplex pump set powered by two Magnatek 7-1/2 HP, 1760 RPM motors. In the case of a power outage, the Center will be served by an emergency pump (Peerless Pump Company #4AFF11, 750 GPM at 55 PSI, 31 BHP) powered by a Clarke diesel-fueled engine. The 100 gallon fuel tank is within the building.

Number of Deficiencies = 2

SITE FEATURES

UTILITIES

2. Fire Protection System

Buildings Structures14 8Flat

Surrounding

Outdoor Recreation

Forest, Light Commercial

Basketball, Soft/Baseball Flagpoles

Entrance

Southern Boundary

Ornamental Metal

Chain Link

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Good

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good

Fencing

Other Features

Page: 2 Date: 02/16/2012 of 4

Sewage Treatment Flow

Center

Publicly Owned Treatment Works

Center

Gravity

Maintenance ResponsibilityOwnership

Comments: Each building is metered individually.

Columbia Gas

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

American Electric

The primary distribution on the center is a 12.47/7.2kV underground loop which feeds pad-mounted transformers ("Y/Y" configuration) which step the voltage down to 208/120V, 3-Phase, 4 Wire. The major buildings: A, B, C, D, E, F, H and I are separately metered by secondary meters at the buildings. Building G is sub-fed from Building D and Building M is sub-fed from Building E by zone metering at the major buildings. Buildings L and O are sub-fed from Building F by zone metering. There is one center-owned 30 kVA natural gas Kohler Power generator with a 100A automatic transfer switch (Kohler). The generator, which is located next to the cafeteria building, provides power for some refrigeration and kitchen loads, for one packaged roof top unit, for limited lighting loads, and for life safety.

Pad Utility

Utility Utility

No

12.47/7.2kV, 3-Phase

208Y/120, 3-Phase, 4 WIreUnderground

UndergroundPrimary Service

Secondary Service

Distribution Characteristics

3. Sanitary Sewer System/ Sewage Treatment Plant

5. Fuel Distribution System

Number of Deficiencies = 7

System Capacity Adequate System Condition

Yes Good

4. Storm Water System Number of Deficiencies = 9

Drain Type On-Site Storm Water Management

Surface Run-off Underground Storage

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes GoodCenter

Comments: An underground stormwater detention system, consisting of three corrugated metal pipe structures, slows stormwater run-off away from the center.

Gas Company Metering

Individual

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility Center Yes Good

7. Electrical (Service)

Transformer Maint Resp

Utility

System Capacity Adequate System Condition

Yes Good

Generator

Natural Gas

ATS MTS

Yes No

6. Central Plant: None

Metering Individual

Page: 3 Date: 02/16/2012 of 4

Comments:

Telephone Company

On-site Line Owner

Fire alarm panels of Buildings A-F, H and I and fire alarm devices in Building M are connected and monitored by a central control/annunciator panel in Security Building G. The center's fire alarm equipment was manufactured by Simplex.

The center telephone communication system is provided by the JCDC. The main data closet (MC) is located in the main electrical room in Building A. One PRI circuit is used for VoIP. Fax numbers are routed through the VoIP system using a Cisco VG224 analog/digital voice gateway. Out of 100 DID's 10 numbers are reserved for faxes.

The center also has 5 POTS lines terminated at MC in Building A, used exclusively for emergencies in the event the main system goes down.

All internet traffic is carried through (4) T1 lines split between Routers 1 and 2. Switch 1 connects Routers 1 and 2 to the network. Two dedicated T1 lines carry all Citrix traffic. Citrix traffic is separated at Router 1, located in MC in Building A. Content is filtered by the use of "Blue Coat" also connected to Switch 1 located in MC. The network consists of a fiber backbone connecting each building to Building A, Switch 1. MC in Building 1 houses Routers 1 and 2, Switch 1, Blue Coat and the VG224 (on the rack). The MC is connected to a UPS back-up system. Each switch on center has fiber connecting them to the network. Most are connected all the way back to Switch 1, however there are areas that have more than one switch and these areas are connected switch to switch using fiber between them. The computers and phones are connected by CAT5 cables to the switches in each building's mechanical/electrical rooms.

CCTV cameras are located throughout the campus inside and outside the buildings. Information from the cameras is saved in Buildings A, H, and I. Building G was provided with central monitoring capabilities. The central monitoring system is currently not operational. There is Direct TV satellite television in Buildings A, H and I.

NTelos (FiberNet)

Maint. Responsibility

Center Center

Closed Circuit TV

10/01/1997CenterActive AbovegroundInside Building M

The tank stores diesel fuel for the emergency fire pump.

NoPetroleum - Diesel Fuel

STORAGE TANKS

Comments:

TypeStatus Location Owner Fuel Type Capacity Install DateID

Reg.

9. Electrical (Communication/Alarm/Security)

Other

Purpose

Yes

Central

VOIP

System Capacity Adequate System Condition

GoodYes

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Pole Pole Building Sport Light

Time Clock Time Clock Time Clock Photocell Switch

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Center Yes Fair

Comments: The site and sports high intensity discharge lighting on center is owned and maintained by the center. Walkway lighting, provided via pole-mounted square type decorative light fixtures, is served from Buildings C, G and I and is controlled by time clocks located in the corresponding buildings. Sports lighting is manually controlled by pole-mounted key operated switches. Softball lighting (four poles with five light fixtures and two poles with two light fixtures each) is served from Building B and basketball lighting (four poles with two light fixtures each) is served from Building D. Roadway and parking lighting, provided via pole-mounted shoe-box type light fixtures, is controlled by time clock and are served from Building G, which also provides for flag pole lighting (flood uplights). Building-mounted HID wall packs and canopy-mounted recessed HID light fixtures, controlled by building-mounted photocells, are utilized for building exterior lighting.

Number of Deficiencies = 4

Number of Deficiencies = 5

Fire Alarm Security

Page: 4 Date: 02/16/2012 of 4

ACCESSIBILITY

Yes

There is a bus parking area in the main parking lot at the entry.Comments:

UnknownUnknownUnknownNo

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Earthquake Risk

Low Medium LowMedium LowIBC Low

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

Occasionally wild animals such as foxes, bears, and deer, come onto the site from the surrounding forest.Comments:

Number of Deficiencies = 2

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

YesYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X Good Fair Poor

HISTORIC PRESERVATION

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Building Descriptions and Utilities Charleston

BUILDING A ADMIN/MEDICAL/DENTALBUILDING A - ADMIN/MEDICAL/DENTAL

Building Descriptions

Page: 1 of 65

Building: A - ADMIN/MEDICAL/DENTAL

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood / Steel

CMU Masonry EIFS

Wall Roof Batt Batt

Metal Unit - Metal Frame Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Business 11,270 7,195 1 Owned 1997 Unevaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material Drainage Year Life

Remaining Type Area Served

Asphalt Shingles

EPDM

Gutters and Downspouts

Interior Roof Drains

Hip

Flat

Medical/Dental/Of fices

Storage/Lounge

Number of Deficiencies = 23. Roof

Entire Building

Area Served

Page: 2 of 65

Building: A - ADMIN/MEDICAL/DENTAL

INTERIOR FINISH

Carpet Ceramic Tile Vinyl Tile

Ceramic Tile Drywall

Metal Unit - Metal Frame Storefront - Metal Frame

Wood Unit - Metal Frame

Mechanical

Mechanical

Restroom

Janitor's Closet

Comments:

Comments:

A rooftop exhaust fan (Loren Cook #180ACE180C11D, 3/4 HP, built 1/2008) ventilates the four public restrooms. Small ceiling fans ventilate the other medical/dental restrooms.

This room is ventilated by a ceiling fan.

Ventilation Area Served

VERTICAL CIRCULATION

Metal Ladder

Comments: There is a steel ladder to access the roof.

Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;

Sliding - Aluminum Frame; Single Glazing;

Acoustical Tile Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 1

Number of Deficiencies = 1

Windows6.

Floors1. Number of Deficiencies = 1

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Five rooftop units (Trane #YCD090D3LOBE, 97.2 MBH output, built 4/1996) serve this building.

There are four serving the three entryways and one office.

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Packaged

Electric Resistance

Single Duct

Wall Heaters

None

None

Electronic

Electric

Mechanical

Natural

None

None

Entire Building

Vestibules

Ventilation2.

Ceilings

Page: 3 of 65

Building: A - ADMIN/MEDICAL/DENTAL

There are two gas-fired water heaters (Bradford-White #MITW50L6LN10, 48 gallon).Comments:

Cast Iron None Cast Iron

Electric Water Cooler Lavatory Mop Sink Multi-Compartment Sink Shower/Bathtub Sink Urinal Wall Hydrant Water Closet (Flush Valve)

Gas (Natural)

Wet None ABC Type Fire Extinguisher

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Direct

Expansion (Air Source)

Split Direct Expansion (Air

Source)

Single Duct

Fan Coil

None

Refrigerant

Direct Digital Control (DDC)

Electric

Mechanical

Natural

None

None

Entire Building

Electronic Equipment

Room

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Five rooftop units (Trane #YCD090D3LOBE, 7-1/2 ton, built 4/1996) serve this building.

This room is served by a ductless split system (Trane #T7K536, 3 ton, built 3/2004) as is the adjacent storage room (Trane #T7K518, 1-1/2 ton. built 3/2004).

Comments:

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

3. Number of Deficiencies = 1Air Conditioning

Page: 4 of 65

Building: A - ADMIN/MEDICAL/DENTAL

Comments: Underground service from a 225 kVA pad-mounted transformer (30 kV, Imp. 2.1%) located near the north building's corner is provided to a 600A main distribution panel with a 600A main circuit breaker (MCB).

The main panel is protected by a secondary MOV surge arrester (Joslyn Mfg., Surge Tech Z-650, 650V max). The main panel serves two 225A main-lug-only (MLO) two-section panels A1 and A2 (from 225A circuit breakers (CB), and 5 ACU units (from (1) 45A, (1) 40A, (2) 30A and (1) 25A CB). Panel A1 is providing for the administration wing and panel A2 for the medical/dental wing. The main distribution panel and panel A1 are located in the main electrical room. Panel A2 is located in the storage room of the dental wing. All panels are by Cutler-Hammer, built 04/96, PRL3A and PRL1 type. This building is protected by a lightning protection system. The utility meter is located at the north wall of the main electrical room. Same transformer also serves Building E.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Comments: Recorded footcandle levels include natural light contribution. Occupancy sensors are utilized throughout the administration portion of the building.

Comments: Remote head emergency light fixtures are utilized at the exterior exits, each has battery backup (Embassy, EMB-6CE 12T1, 6V Sealed Lead Acid batteries) located inside the building. The tritium gas exit signs manufactured in March 1996 have a stated life of 20 years.

High Intensity Discharge (HID)

Comments: Exterior lighting is controlled by fixture-mounted photocells. Recessed HID light fixtures are provided above the main entrances.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Compact Fluorescent

Offices

Medical/Dental

Storage Rooms

Wards (Patient)

Reception

Conference Rooms

Corridors & Stairs

Toilets

Housing Lounge

Equipment Rooms (Elec/Mech)

Mail Room

Toilets

Area Recommended Level

Recorded Level Light Type

Selected Lighting w/ Battery Tritium Gas

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES Number of Deficiencies = 3

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3. Number of Deficiencies = 1

LIGHTING

Page: 5 of 65

Building: A - ADMIN/MEDICAL/DENTAL

FIRE ALARM

Comments: The fire alarm panel is a Simplex 4020 located in the reception area. The local annunciator is a Simplex 4602-8001, located in the main vestibule. The fire alarm system is additionally monitored in Reception/Security Building G.

Comments: The center telephone communication system is provided by the JCDC to the main data closet (MC) located in the main electrical room. MC houses Routers 1 & 2, Switch 1, Blue Coat and the VG224.

UPS is used for power backup. One PRI circuit is used for VoIP. Fax numbers are also routed through the VoIP system using a Cisco VG224 analog/digital voice gateway. Out of 100 DID's a bank of 10 numbers is reserved for faxes. The center also has 5 POTS lines terminated at MC and used exclusively for emergencies. All internet traffic is carried through (4) T1 lines split between Routers 1 &

2. Switch 1 connects Routers 1 and 2 to the network. Two dedicated T1 lines carry all Citrix traffic.

Citrix traffic is separated at Router 1, located in MC in Building A. Content is filtered by the use of Blue Coat also connected to Switch 1 located in MC. The network consists of a fiber backbone connecting buildings to Building A, Switch 1. Computers & phones in the building are connected by CAT 5 cables.

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Smoke Detector Visual Alarm

Connected to Main System Magnetic Door/Alarm None Satellite Dish

Telephone Security Public Address Television

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No YesYes

BUILDING UTILITY METERING

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

BUILDING B EDUCATIONBUILDING B - EDUCATION

Page: 6 of 65

Building: B - EDUCATION

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood

CMU Masonry EIFS

Wall Roof Batt Batt

Metal Unit - Metal Frame Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Business 10,710 6,793 1 Owned 1997 Unevaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

N/A

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5. Number of Deficiencies = 2

Material Drainage Year Life

Remaining Type Area Served

Asphalt Shingles Gutters and Downspouts 1997 6 Hip Entire Building

3. Roof

Page: 7 of 65

Building: B - EDUCATION

INTERIOR FINISH

Carpet Ceramic Tile Vinyl Tile

CMU Ceramic Tile Drywall

Aluminum Storefront - Aluminum Frame Folding - Aluminum Frame

Metal Unit - Metal Frame Wood Units - Metal Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

None

Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;

Acoustical Tile Exposed Structure Gypsum Board

Exhaust Ventilation

Number of Deficiencies = 1

Windows6. Number of Deficiencies = 1

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 5

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

There are three units (two Trane #YCH120C3MOAB, 166 MBH output, 4000 CFM; and a Trane #YCH060C3LOBE, 72.9 MBH output, 2000 CFM) serving this building. All units are on grade behind the building.

There is an electric heater at each of the four entrances to the building.

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Packaged

Electric Resistance

Single Duct

Unit Heater

None

None

Electronic

Electric

Mechanical

Natural

None

None

Entire Building

Vestibules

Ventilation2. Number of Deficiencies = 1

Page: 8 of 65

Building: B - EDUCATION

The water heater (Bradford White, 48 gallon, 32 MBH output) is located in the exterior mechanical equipment room.`

Comments:

Cast Iron None None

Electric Water Cooler Lavatory Mop Sink Urinal Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Packaged Direct

Expansion (Air Source)

Single Duct None Electronic Mechanical None Entire Building

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

There are three units (two Trane #YCH120C3MOAB, 10 ton, 4000 CFM; and a Trane #YCH060C3LOBE, 5 ton, 2000 CFM) serving this building. All units are on grade behind the building.

Comments:

Number of Deficiencies = 1

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

3. Air Conditioning

Page: 9 of 65

Building: B - EDUCATION

Comments: Underground service from a 150 kVA pad-mounted transformer (30 kV, Imp. 1.9%) located just east of the building is provided to a 600A main distribution panel with a 600A main circuit breaker (MCB). The main panel is protected by a secondary MOV surge arrester (Joslyn Mfg., Surge Tech Z-650, 650V max). The main panel serves three 225A main-lug-only (MLO) panels B1, B2 and B3 (from (2) 200 and (1) 100A CB), three ACU units (from (2) 80A and (1) 35A CB) and softball field lighting (from 150A CB). Panels B2 and B3, located in the north electrical room, serve the north part of the building. Panel B1, located in the janitor closet, serves the south part of the building. All panels are by Cutler-Hammer, built 04/96, PRL3A and PRL1 type. This building is protected by a lightning protection system. The utility meter is located at the south exterior wall of the mechanical room.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Comments: Recorded footcandle levels include natural light contribution.

Comments: Remote head emergency light fixtures are utilized at the exterior exits, each has battery backup (Embassy, EMB-6CE 12T1, 6V Sealed Lead Acid batteries) located inside the building. The tritium gas exit signs manufactured in March 1996 have a stated life of 20 years.

High Intensity Discharge (HID)

Comments: Exterior lighting is controlled by fixture-mounted photocells. Recessed HID light fixtures are provided above the main entrance. The softball field lighting is controlled by pole-mounted key operated switch.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Compact Fluorescent

Classrooms

Storage Rooms

Offices

Corridors & Stairs

Toilets

Reception

Equipment Rooms (Elec/Mech)

Classrooms

Lounges

Storage Rooms

Area Recommended Level

Recorded Level Light Type

Selected Lighting w/ Battery Tritium Gas

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches

Emergency Exit

ELECTRICAL SERVICES Number of Deficiencies = 2

Exterior Lighting1.

Interior Lighting2. Number of Deficiencies = 1

Emergency /Exit Lighting3. Number of Deficiencies = 2

Page: 10 of 65

Building: B - EDUCATION

FIRE ALARM

Comments: The fire alarm panel is a Simplex 4020 located at the reception area. The local annunciator is a Simplex 4602-8001 located in the main vestibule. The fire alarm system is additionally monitored in Reception/Security Building G.

Comments: The building is connected to the center's telephone and LAN system. Building is provided with two LAN switches (two Catalyst 3560 units).

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Smoke Detector Visual Alarm

Connected to Main System Closed Circuit TV None TV with VCR

Telephone Security Public Address Television

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No YesYes

BUILDING C VOCATIONALBUILDING C - VOCATIONAL

Page: 11 of 65

Building: C - VOCATIONAL

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood / Steel

CMU Masonry EIFS

Wall Roof Batt Batt

Metal Unit - Metal Frame Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Business 25,140 19,065 2 Owned 1997 Unevaluated

Comments: A mezzanine with classrooms is over the vocational shops.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

Yes

No

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5. Number of Deficiencies = 3

Material Drainage Year Life

Remaining Type Area Served

EPDM

Asphalt Shingles

Interior Roof Drains

Gutters and Downspouts

Flat

Hip

Shop Area

Classrooms

3. Roof

Page: 12 of 65

Building: C - VOCATIONAL

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

CMU Ceramic Tile Drywall Wood Paneling

Accordion - Aluminum Frame Aluminum Storefront - Aluminum Frame

Metal Unit - Metal Frame Wood Unit - Metal Frame

VERTICAL CIRCULATION

Metal Ladder Metal Pan w/Concrete Stairs Metal Stairs

Comments: Metal stairs, some with concrete treads, provide access to shop mezzanines. There is a steel ladder to access the roof.

Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;

Acoustical Tile Exposed Structure Gypsum Board Precast Concrete Panel

Number of Deficiencies = 2

Windows6.

Floors1.

Interior Walls2.

3. Number of Deficiencies = 1

Interior Doors4. Number of Deficiencies = 6

Page: 13 of 65

Building: C - VOCATIONAL

Mechanical

Mechanical

Shop Area

Restroom

Ventilation Area Served

Packaged Direct

Expansion (Air Source)

Single Duct None Electronic Mechanical None Classrooms

Exhaust Ventilation

The classrooms and common areas served by six roof-top units (Trane #YCD120C3MOAB, 10 ton;

#YCD090D3HOBE, 165 MBH output; #YCD060C3LOBE, 5 ton; #YCD048C3LOBE, 4 ton;

#YCD036C3LOBE, 3 ton, all built between 1/1996 and 5/1996; and #YCD030F1NOBJ, 2-1/2 ton, built 4/2005) half with mechanical outdoor intake.

Comments:

Number of Deficiencies = 1

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

The classrooms and common areas served by six roof-top units (Trane #YCD120C3MOAB, 165 MBH output; #YCD090D3HOBE, 165 MBH output; #YCD060C3LOBE, 72.9 MBH output; #YCD048C3LOBE,

72.9 MBH outout; #YCD036C3LOBE, 64.8 MBH output, all built between 1/1996 and 5/1996; and #YCD030F1NOBJ, 48 MBH output, built 4/2005) half with mechanical outdoor intake.

These are located in tool storage rooms. There are also electric wall heaters at the main entrances to the building.

There are two heating and ventilating units that serve the shop ares; one unit is manufactured by DeVilbiss (model number not available) and the other unit is manufactured by Reznor (model number not available)

Comments:

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Packaged

Gas-Fired

Electric Resistance

Gas-Fired Packaged

Single Duct

Unit Heater

Unit Heater

Makeup Air Unit

None

None

None

None

Electronic

Electric

Electric

Electric

Mechanical

Natural

Natural

Mechanical

None

None

None

None

Classrooms

Shop Area

Storage

Shop Area

Ventilation2.

System Type

Number of Deficiencies = 4

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Page: 14 of 65

Building: C - VOCATIONAL

There are two water heaters (Bradford-White #MITW50L6BN12, 48 gallon and a Lochinor #DUN051G, 50 gallon; both 32 MBH output).

Comments:

Cast Iron None None

Electric Water Cooler Fixed Emergency Eyewash Lavatory Shower/Bathtub Urinal Wall Hydrant Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher

Comments: Underground service from a pad-mounted transformer is provided to a 1200A main distribution panel with a 1200A main circuit breaker (MCB). The main panel is protected by a secondary MOV surge arrester (Joslyn Mfg., Surge Tech Z-650, 650V max). The main panel serves a 400A main-lug-only (MLO) panel (from 300A CB) located in the j-closet & serving the south wing, a 400A MCB panel (400A CB) located in the former welding/current painting shop, four 225A MCB panels ((4) 225A CB) serving each of four hard vocational shops, a two-section 225A MLO panel (200A) located in the main el. room and serving north wing, a 100A panel (100A CB) serving computer lab & a ACU5 unit (60A CB). A 400A MLO panel in the j-closet serves (4) ACU, (2) make-up air units & walkway lighting. All panels are by Cutler-Hammer, built 04/96, PRL4B and PRL1 type. The building is protected by a lightning protection system. The emergency power shut-off switches are provided in the shops. The utility meter is on the exterior.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

High Intensity Discharge (HID)

Comments: Exterior lighting is controlled by fixture-mounted photocells. Recessed HID light fixtures are provided above the main entrance. The walkway lighting is controlled by the time clock.

Main Distribution Panel 120/208V, 3-Phase, 4 Wire Panelboards Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3. Number of Deficiencies = 1

Fuel Distribution4.

Number of Deficiencies = 2FIRE PROTECTION

ELECTRICAL SERVICES Number of Deficiencies = 4

Exterior Lighting1.

Page: 15 of 65

Building: C - VOCATIONAL

FIRE ALARM

Comments: The fire alarm panel is a Simplex 4020 located in the manager's office. The local annunciator is a Simplex 4602-8001 located in the main vestibule area. The fire alarm system is additionally monitored in Reception/Security Building G.

Comments: The building is connected to the center's telephone and LAN system.

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Magnetic Door Holder Manual Pull Station Remote Annunciator Smoke Detector Visual Alarm

Connected to Main System Closed Circuit TV None TV with VCR

Telephone Security Public Address Television

Comments: Recorded footcandle levels include natural light contribution.

Comments: Remote head emergency light fixtures are utilized at the exterior exits, each has battery backup (Embassy, EMB-6CE 12T1, 6V Sealed Lead Acid batteries) located inside the building. The tritium gas exit signs manufactured in March 1996 have a stated life of 20 years. Emergency light fixtures with battery backup are utilized for high ceiling areas (vocation shops).

T8 - Fluorescent

High Intensity Discharge (HID)

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

High Intensity Discharge (HID)

Classrooms

Vocational

Storage Rooms

Offices

Corridors & Stairs

Toilets

Equipment Rooms (Elec/Mech)

Vocational

Area Recommended Level

Recorded Level Light Type

Selected Lighting w/ Battery Tritium Gas

Emergency Exit

Number of Deficiencies = 1

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

Interior Lighting2. Number of Deficiencies = 3

Emergency /Exit Lighting3. Number of Deficiencies = 3

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No YesYes

BUILDING D CAFETERIA/CULINARY ARTSBUILDING D - CAFETERIA/CULINARY ARTS

Page: 16 of 65

Building: D - CAFETERIA/CULINARY ARTS

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood / Steel

CMU Masonry EIFS

Wall Roof Batt Batt

Metal Unit - Metal Frame Storefront - Storefront Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Assembly 13,920 9,852 1 Owned 1997 Unevaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

Yes

Yes

No

N/A

Yes

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5. Number of Deficiencies = 3

Material Drainage Year Life

Remaining Type Area Served

EPDM

Asphalt Shingles

Interior Roof Drains

Gutters and Downspouts

Flat

Hip

Kitchen

Dining Hall

3. Roof

Page: 17 of 65

Building: D - CAFETERIA/CULINARY ARTS

INTERIOR FINISH

Carpet Ceramic Tile Concrete Quarry Tile Vinyl Tile

CMU Ceramic Tile Plaster

Aluminum Storefront - Aluminum Frame Metal Unit - Metal Frame

Wood Unit - Metal Frame

VERTICAL CIRCULATION

Concrete Stairs Metal Ladder

Comments: Concrete stairs are from grade to the loading dock. There is a steel ladder to access the roof.

Fixed - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Double Glazing;

Acoustical Tile Gypsum Board

Number of Deficiencies = 3

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4. Number of Deficiencies = 6

Page: 18 of 65

Building: D - CAFETERIA/CULINARY ARTS

Mechanical

Mechanical

Mechanical

Restroom

Kitchen

Janitor's Closet

Comments: All kitchen exhaust hoods are ventilated by roof fans (main kitchen hoods by Acme #PNU365GGP; the servery area hood by Acme #PNU245RGM and the Culinary Arts hood by an undetermined Acme model). The dishwashers are also ventilated.

Ventilation Area ServedExhaust Ventilation

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

This is a roof-mounted unit (Trane #YCD210C3L0AB, 203 MBH output, 7000 CFM, built 8/1996).

This is a roof-mounted unit (Trane #YCD180B3LDEA, 203 MBH output, 6000 CFM, built 4/2000) serving the main kitchen.

This is a roof-mounted unit (Trane #YCD120, 96 MBH output, 4000 CFM, built 8/1996) serving the Culinary Arts kitchen space.

This is a roof-mounted unit (Trane #GRCA35GDMBON, 276 MBH output, 3420 CFM @ 1" wg, built 8/1996) serving the Dining Hall servery exhaust hood.

This is a roof-mounted unit (Trane #GRAA60GDNBON, 480 MBH output, 7600 CFM, built 8/1996) serving the kitchen food preparation area exhaust hoods.

This a roof-mounted unit (Trane #GRAA40GDMBON,320 MBH output, 6000 CFM, built 8/1996) serving the Culinary Arts kitchen exhaust hood.

There is an electric wall heater at the front entrance vestibule.

Comments:

Comments:

Comments:

Comments:

Comments:

Comments:

Comments:

HVAC

Heat1.

Gas-Fired Packaged

Gas-Fired Packaged

Gas-Fired Packaged

Gas-Fired Furnace

Gas-Fired Furnace

Gas-Fired Furnace

Electric Resistance

Single Duct

Single Duct

Single Duct

Makeup Air Unit

Makeup Air Unit

Makeup Air Unit

Unit Heater

None

None

None

None

None

None

None

Electronic

Electronic

Electronic

Electronic

Electronic

Electronic

Electric

Mechanical

Mechanical

Mechanical

Mechanical

Mechanical

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .