2012_00409_Final_Vol2_Part1.pdf
PDF 9 MB Posted
- Attached to
- Operation of Gainesville Job Corps Center
- Solicitation number
- DOL-ETA-15-R-00047
About this file
Attachment J-9 Facility Survey - Facility Planning Report Vol 2
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Gainesville
Job Corps Center Gainesville, FL
Facility Planning Report Volume II
Supporting Data
Final June 2013
Department of Labor/ Office of Job Corps
22Gainesville Job Corps Center
Gainesville
Job Corps Center Gainesville, FL
Facility Planning Report Volume II
Supporting Data
Final June 2013
Students mingling behind Building 1
33 Gainesville Job Corps Center
CONTENTS
GAINESVILLE JOB CORPS CENTER
FACILITY PLANNING REPORT
VOLUME I - Planning Strategy
• Existing Site Plan
• Center Statistics
INTRODUCTION
• Purpose
• Report Contents
EXECUTIVE SUMMARY
A. EXISTING CONDITIONS
• Background
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Ownership
• Facility Assessment by Function
• Energy Issues
• Environmental Issues
• Sustainability
• Accessibility Standards
• Health and Life Safety Issues
• Summary of Defi ciencies
B. RECOMMENDATIONS
• Status of the Previous (PY09) Plan
• Signifi cant Issues
• PY 12 Plan Overview
• Summary of Proposed Projects
• Proposed Site Plan
• Implementation Plan
• Summary of National Projects
• Project Data Sheets
C. PLANNING ANALYSIS
• Purpose
• Planning Objectives and Assumptions
• Space Utilization Analysis
• Federal Real Property Asset Management
• Mission Dependency Site Plan
• Defi ciency Analysis
• Facility Condition Summary Report
• Building Condition by Function
• Building Condition Site Plan
VOLUME II - Supporting Data
• Vicinity Map
• Location Map
• Existing Site Plan
D. DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Energy Management Report
• Environmental Management
Asbestos Report Radon Report
• Site Descriptions
• Building Descriptions
E. DEFICIENCIES
F. CORRESPONDENCE AND REPORTS
• Center Review Meeting Minutes
• Survey Brief
• RA and Student Facility Feedback Questionnaire
• Life Safety Defi ciencies Transmittal and List
• O & M Defi ciency List
• Active Warranty Report
• FRPC Performance Measures Matrix
44Gainesville Job Corps Center
55 Gainesville Job Corps Center
66Gainesville Job Corps Center
77 Gainesville Job Corps Center
D Descriptions
BUILDINGS AND STRUCTURES
00409 GAINESVILLE 06/19/2013
1Page: of Date:
0001 - ADMIN/ED/REC/DORM/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0014 - GATE HOUSE
0015 - SIA TECH
0016 - CAREER TRANSITION BLDG.
0021 - MAINTENANCE/STORAGE
0024 - VOCATIONAL STORAGE
0027 - GYMNASIUM
0029 - SIA TECH CHARTER SCHOOL
0030 - WOMEN'S DORMITORY
0031 - RECREATION
0039 - SIA TECH (MODULAR UNIT)
0011 - FLAMMABLE STORAGE
0025 - BIOHAZARD STORAGE
0026 - AUTOMOTIVE REPAIR SHED
0028 - PAVILION
0033 - STORAGE
0034 - STORAGE
0035A - GAZEBO
0035B - GAZEBO
0035C - GAZEBO
0036 - STORAGE SHED - POLE SHED
Name GSF
100,400 23,280
1,600 1,790 1,160 8,800
10,850 3,080
26,470 10,470 2,150
2,770
1,600
Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active Active
StatusType
Building Building Building Building Building Building Building Building Building Building Building Building Structure Structure Structure Structure Structure Structure Structure Structure Structure Structure
Use Group Built Flrs Const
Residential, B Assembly, Bu Business Business Business Storage Storage Assembly Business Residential Assembly Business Storage Storage Factory/Ind.
Assembly Storage Storage Assembly Assembly Assembly Storage
Fair Good Good Good Good Good Good Good Good Good Good Good
Good Good Fair Fair Fair
Good Good Good Fair
ConditionAsset Number
0040900002 0040900003 0040900018 0040900007 0040900019 0040900022 0040900025 0040900028 0040900030 0040900031 0040900032 0040908096 0040900015 0040900026 0040900027 0040900029 0040900034 0040908091 0040908092 0040908097 0040908098 0040908093
12 190,650
10 6,488
22 197,138
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/19/2013
Space Utilization By Function 00409 Gainesville Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 315 Non Residents 35
350Total Students
(315)
(350)
(350)
DIFFERENCE
31,500
24,040
6,300
43,110
58,520
6,454
Lounge Other Shower/Toilet Sleeping excl. SPD( rooms; beds) Storage
Academic (350) Non-Academic
20 -- Auto Repair Tech/Helper + 20 -- Carpentry + 20 -- Culinary Arts + 24 -- Facilities Maint. and Const. + 20 -- Medical Assistant 20 -- Medical Office Support 30 -- Nursing Assistant + 60 -- Office Administration 20 -- Painting + 40 -- Security Services 20 -- Solar Energy Installer +
Vocational Theory (154)
Dining (2 Servings) Food Preparation Food Storage
6,900 4,100 4,910
26,480
12,352 10,700
3,490 7,010 2,318 4,480 1,560
2,250 2,430 3,520 1,630 3,100
2,830
2,849 2,350 1,255
3,150
3,780 22,680
1,890
3,500 3,500
1,500 1,500 1,200 1,800
1,200 2,700 1,500 1,400 1,500
1,540
2,800 2,100 1,400
3,750
1,130 3,800 -1,170
8,852 7,200
1,990 5,510 1,118 2,680
1,050 -270
2,020
1,600
1,290
-145
Vocations
11,610
34,480
06/19/2013
Space Utilization By Function 00409 Gainesville Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 269.1 94,185 146,226
(350)
(350)
(350)
(350)
(0)
DIFFERENCE
190,650
0.77
TOTAL GSF
NET TO GROSS RATIO
16,275
2,070
7,000
22,660
3,850
4,040
7,017
Aerobics/Exercise Arts & Crafts Gymnasium Learning Resource Center/Library Miscellaneous Recreation Multipurpose Room Music Hall Pool Hall Snack Bar T.V. Room Weight Room Women's Exercise Room
Medical/Dental
Administration
Operations & Maintenance Warehouse
Vacant
5.91
1,160 9,100
1,305 7,090
1,015
3,850
4,040
3,617 3,400
2,070
2,800 4,200
1,780
-2,960
-800
RESIDENT
NON-RESIDENT
(315)
(35) 15
50 15,750
6,385
1,780
-2,960
52,041
Net Square Footage By Building Date: 06/19/2013 Page: 1
Center: GAINESVILLE (00409) of 5
HOUSING
Sleeping excl. SPD
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
10,280 16,200
1,700 5,200
2,540 2,370
2,100 2,000
0030 - WOMEN'S DORMITORY
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0030 - WOMEN'S DORMITORY
0030 - WOMEN'S DORMITORY
0030 - WOMEN'S DORMITORY
0001 - ADMIN/ED/REC/DORM/VOC
0030 - WOMEN'S DORMITORY
0001 - ADMIN/ED/REC/DORM/VOC
Bldg Name Actual NSF Difference
26,480
6,900
4,910
4,100
Sub Total: 43,110
22,680
3,150
1,890
3,780
31,500
3,800
3,750
-1,170
1,130
4,100
( 315
11,610 rooms; beds rooms; beds
Page: 2
Center: GAINESVILLE (00409) of 5
EDUCATION
Academic
Vocational Theory (154)
Carpentry
Culinary Arts
Painting
Facilities Maint. and Const.
Medical Assistant
Security Services
Non-Academic
Solar Energy Installer
Nursing Assistant
Function Suggested
NSF
1,100
1,420 3,510 1,440 1,984
1,950
3,230 3,780
2,318
1,590 1,930
1,600 2,880
1,560
1,630
5,860 1,495 1,010
3,100
2,250
0029 - SIA TECH CHARTER SCHOOL
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0029 - SIA TECH CHARTER SCHOOL
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0039 - SIA TECH (MODULAR UNIT)
0015 - SIA TECH
0001 - ADMIN/ED/REC/DORM/VOC
0029 - SIA TECH CHARTER SCHOOL
0001 - ADMIN/ED/REC/DORM/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0024 - VOCATIONAL STORAGE
0002 - FOOD SERV/MED/DENTAL/VOC
0024 - VOCATIONAL STORAGE
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0024 - VOCATIONAL STORAGE
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0015 - SIA TECH
0001 - ADMIN/ED/REC/DORM/VOC
0016 - CAREER TRANSITION BLDG.
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
Bldg Name Actual NSF Difference
12,352
2,830
7,010
2,318
3,520
4,480
1,560
1,630
10,700
3,100
2,250
3,500
1,540
1,500
1,200
1,500
1,800
1,400
3,500
1,500
1,200
8,852
1,290
5,510
1,118
2,020
2,680
7,200
1,600
1,050
( 350 )
Page: 3
Center: GAINESVILLE (00409) of 5
EDUCATION
FOOD SERVICE
Office Administration
Medical Office Support
Auto Repair Tech/Helper
Dining (2 Servings)
Food Preparation
Food Storage
Function Suggested
NSF
2,430
3,490
2,849
2,350
1,255
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
Bldg Name Actual NSF Difference
2,430
3,490
2,849
2,350
1,255
Sub Total:
Sub Total:
58,520
6,454
2,700
1,500
2,800
2,100
1,400
24,040
6,300
-270
1,990
-145
( 350
34,480
Page: 4
Center: GAINESVILLE (00409) of 5
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
Multipurpose Room
Snack Bar
Arts & Crafts
Gymnasium
Weight Room
Miscellaneous Recreation
Pool Hall
Aerobics/Exercise
Music Hall
T.V. Room
Women's Exercise Room
Learning Resource Center/Libr
Medical/Dental
Administration
Function Suggested
NSF
4,220 2,870
1,160
9,100
1,015
3,850
3,590
0001 - ADMIN/ED/REC/DORM/VOC
0031 - RECREATION
0031 - RECREATION
0031 - RECREATION
0027 - GYMNASIUM
0031 - RECREATION
0031 - RECREATION
0027 - GYMNASIUM
0031 - RECREATION
0031 - RECREATION
0031 - RECREATION
0031 - RECREATION
0031 - RECREATION
0031 - RECREATION
0002 - FOOD SERV/MED/DENTAL/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0014 - GATE HOUSE
Bldg Name Actual NSF Difference
7,090
1,160
9,100
1,305
1,015
3,850
4,040
Sub Total:
Sub Total:
Sub Total:
22,660
3,850
4,040
2,070
7,000
16,275
2,070
7,000
1,780
-2,960
6,385
1,780
-2,960
Page: 5
Center: GAINESVILLE (00409) of 5
STORAGE/SUPPORT
VACANT
Warehouse
Operations & Maintenance
Vacant
Function Suggested
NSF
3,400
1,750 1,040
0001 - ADMIN/ED/REC/DORM/VOC
0001 - ADMIN/ED/REC/DORM/VOC
0021 - MAINTENANCE/STORAGE
0002 - FOOD SERV/MED/DENTAL/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0001 - ADMIN/ED/REC/DORM/VOC
Bldg Name Actual NSF Difference
3,400
3,617
Sub Total:
Sub Total:
7,017
4,200
2,800
7,000
-800
Energy Management Report Center: GAINESVILLE (00409)
Page: 1 Date: 06/19/2013 of 3
CENTER ENERGY DATA
None
ENERGY CONSUMPTION ASSESSMENT
44% 67,455
94,612 119,762
ENERGY USE BY FUEL TYPE
Energy Audit :
Date of Audit :
Electric Company :
Percent Change since Baseline Year :
Natural Gas Company :
Property Status :
N/A
Gainesville Regional Utilities Gainesville Regional Utilities
Federally Owned (DOL)
3,015,297 10,288=
Total 12,860
MBtu
MBtu
Total $373,911 MBtu/ $29.076
BTU/GSF
BTU/GSF
BTU/GSF
Electricity
Natural Gas kWh
2,495 MCF = 2,572 MBtu
$349,616 $0.116= kWhElectricity
Natural Gas $24,295 = $9.737 MCF
ENERGY COST BY FUEL TYPE
COMMENTS
2002 Data Estimated, No report submitted EMCs -
1. Sealing windows
2. O&M Filters
3. Up grading to HiE motors & lights on R/R
WATER CONSUMPTION ASSESSMENT
Percent Reduction Compared to Goal:
1,000 Gallons
1,000 Gallons
FY 2012 Energy Goal:
Energy Goals are being met. Keep up the Good Work to further Reduce Energy Usage.
FY 2012 Energy Consumption:
Note: The Federal Government has set a goal of 3% Energy Consumption reduction per year in EO 13423.
14,270 12,843 17,617
- 37%
Further Reduction in Water Usage is needed to meet Water Reduction Goals.
Note:
FY 2012 Goal:
FY 2012 Water Consumption:
1,000 Gallons
FY 2003 Energy Baseline:
FY 2007 Baseline:
The Federal Government has set a goal of 2% Water Consumption reduction per year in EO 13423 compared to the FY 2007 Baseline.
Page: 2 of 3
Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.
1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:
a. Turn it down (lights, heating & cooling),
b. Turn it off (lights, computers, other equipment),
c. Keep it tight (close doors and windows, use window blinds)
2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:
a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.
b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.
c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.
d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.
e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.
f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.
g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.
h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.
i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.
Page: 3 of 3
j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.
k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.
l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.
m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.
n. Caulk and fill cracks around doors and windows to reduce costly air leaks.
o. When replacing broken glass, use high transmittance, low heat gain windows.
p. Make sure automatic door closers are functioning properly to avoid drafts.
3. Buy energy efficient, buy EnergyStar (www.energystar.gov).
a. Buy EnergyStar appliances and equipment.
b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).
c. Replace broken thermostats with EnergyStar labeled programmable products.
d. Replace broken exit signs with EnergyStar LED exit signs.
Environmental Management Report
Page: 1 Date: 06/19/2013 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Buildings 21, 25
Antifreeze, organic solvent Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Boone Waste, Inc.
Yes Organic solvent (2 gals/month)
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service
Safety Kleen, Inc.
Yes Yes
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
11/10/1993 Friable/Non-Friable Archie Brown 01/01/1999 No No N/A Yes Yes
ID Fuel Type Capacity Location Overfill
Prevention Secondary Containment
Petroleum - Diesel Fuel
Petroleum - Waste Oil
Near Building 21
Near Building 26
No
No
Yes
Yes
Tank Status Active
Active
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 06/19/2013Center : Gainesville (00409) Page: 1 of 1
Wall Finishes Plumbing (Bldg) Floor Finishes Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Interior Finish Roof Repair/Replacement Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg)
Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Plumbing (Bldg) Floor Finishes
Bldg System
Bldg System
Black mastic on FG Wall Panels Pipe insulation Floor tile and mastic Pipe insulation Pipe insulation Pipe insulation Pipe insulation Pipe insulation Pipe insulation Pipe insulation Black mastic on wall panels Transite roof substrate Pipe insulation Pipe insulation Pipe insulation
Tank insulation Pipe insulation, pre-cast Pipe fitting insulation Asphalt pipe wrap (cork) Asphalt pipe wrap (fiberglass) Pipe insulation Floor tile and mastic
Category Description
Category Description
Sq. Ft.
Lin. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Sq. Ft.
Location
Location
Unit
Unit
Quantity
Quantity
GED Mechanical Room Main Mechanical room Throughout Electronic/Rec. area Main Mechanical rm Wing 5 Laundry room Administration Classrooms area Administration Laundry room Class./Voc./Rec.
Loading Dock Class./Voc./Rec.
Rooftop AHU GED Mechanical room
Boiler room Boiler room Boiler room Boiler room Boiler room Boiler room Throughout
76500
12000
Building :
Building :
0001 - ADMIN/ED/REC/DORM/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
Radon
Page: 1 of 1
0001 - ADMIN/ED/REC/DORM/VOC
0002 - FOOD SERV/MED/DENTAL/VOC
0014 - GATE HOUSE
0015 - SIA TECH
0016 - CAREER TRANSITION BLDG.
0021 - MAINTENANCE/STORAGE
0024 - VOCATIONAL STORAGE
0027 - GYMNASIUM
0029 - SIA TECH CHARTER SCHOOL
0030 - WOMEN'S DORMITORY
0031 - RECREATION
0039 - SIA TECH (MODULAR UNIT)
Bldg Name
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
06/06/1990
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
N/A
No
No
No
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
GAINESVILLE
Page: 1 Date: 06/19/2013 of 4
Comments:
Paving Type for Roads & Parking
The wide sidewalk on the north side of building one is prone to standing water.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing. The fence and a gate are at the north side separating the campus from the public road.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoIndividualGainesville Regional Utilities (GRU)Public Water Authority
None 0None
The center is provided with two master water meters, located within the property line. One meter is located at the southwest corner of Female Dormitory Building 30. The other water meter is located on the south of Vocational Building 24.
Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 5None Municipal
The nearest City of Gainesville fire station is two miles away from the center and the emergency response time is about five minutes.
Number of Deficiencies = 1
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures12 10Flat
Surrounding
Outdoor Recreation
Light Industrial
Basketball, Soft/Baseball Retention Pond
GSA Vehicle Parking
Storage Area
Chain Link
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
Yes
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Fair
Fencing
Other Features
Page: 2 Date: 06/19/2013 of 4
Comments:
Sewage Treatment Flow
Center sanitary system discharges waste into the city sanitary sewer system operated by the City of Gainesville Regional Utilities.
Center
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: The Gainesville Regional Utilities (GRU) supplies natural gas for cooking, heating and domestic hot water. An underground distribution system is connected to four gas meters at the center. One meter is located adjacent to Pavilion Structure 28. Another meter is located at the northeast corner of Gymnasium Building 27. A third meter is on the south of women's dormitory Building 30. One water meter is located south of Vocational Storage Building 24.
Gainesville Regional Utilities
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
System Capacity Adequate System Condition
Yes Fair
4. Storm Water System
Drain Type On-Site Storm Water Management
Underground/Surface Runoff Retention Pond
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Comments: There are storm water drains and two retention pounds near Buildings 30 and 31 that collect storm water. Each pond has a fountain to prevent water stagnation.
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
6. Central Plant: None
Page: 3 Date: 06/19/2013 of 4
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Gainesville Regional Utilities
The primary 12.47/7.2 kV overhead service is brought from power lines along the center southern perimeter. The primary metered service is installed on a power pole between Gymnasium Building 27 and Recreation Building 31.
The secondary distributions to buildings on the center are underground via pole, platform and pad-mounted, step-down transformers. Buildings 1 and 30 are provided with 277/480V services and step-down transformers for 120/208V. A 55 kW, 120/208V standby generator located in the electrical/mechanical room in Building 1 provides backup power for emergenlcy lights in Buildings 1 & 2 via an automatic transfer switch (ATS) and emergency distribution panel located in each of the respective buildings. Buildings 30 and 31 have a lightning system installed on the roof.
Pole,Pad and Platform Utility, Center
Utility, Center Utility, Center
No
Comments:
Telephone Company
On-site Line Owner
AT&T provides main telephone lines to the center which terminate in the telephone communication main closet (MC) located next to the security office in Building 1. The server and LAN/WAN networks are located in the nearby computer room. The telephone system and data/communication system are supported by two 2 KVA portable UPS modules which buffer the power surges and drops in the line voltage, and will maintain the power requirement of the systems up to 20 minutes before an automated shut down. The fire alarm control panels in buildings on center are connected to the central fire alarm control/annunciator panel located in the Building 1 mail room. The center security system consists of pole-mounted and building-mounted CCTV cameras, multi-display black & white monitor and electric gate operator. The CCTV cameras and electric gate operator are monitored and controlled from the security office in Gate House Building 14. Satellite dish is provided at the dormitory, dining, and other recreational facilities.
AT&T
Maint. Responsibility
Center Center
Camera, CCTV Monitor, Electric Gate Operator
12.47/7.2 kV, 3-Phase, 4 Wire
120/208 & 277/480V, 3-Phase, 4 WireUnderground & Overhead
OverheadPrimary Service
Secondary Service
Distribution Characteristics
9. Electrical (Communication/Alarm/Security)
7. Electrical (Service)
No
Central
VOIP
System Capacity Adequate System Condition
GoodYes
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
Natural Gas
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building None
Time Clock Time Clock Photocell, Time Clock Photocell, Time Clock None
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center Utility, Center Yes Good
Comments: The utility company owns and maintains lights that are mounted on power poles. The center owns and maintains all building-mounted exterior lights.
ATS MTS
Yes No
Number of Deficiencies = 5
Fire Alarm Security
Metering Master
Page: 4 Date: 06/19/2013 of 4
ACCESSIBILITY
Yes
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
01/01/1978
01/01/1978
Center
Center
Active
Active
Aboveground
Aboveground
Near Building 21
Near Building 26
No
No
Petroleum - Diesel Fuel
Petroleum - Waste Oil
STORAGE TANKS
TypeStatus Location Owner Fuel Type Capacity (Gallons) Install Date
Earthquake Risk
Low Low MediumHigh MediumIBC High
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
ID
Reg.
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X
Good Fair Poor
The soil on the property is contaminated. The nature and extent of the contamination is not fully known. Contamination is also present on contiguous property. A large portion of the east undeveloped area has wetlands. The fair rating of the site is exacerbated by the indeterminate schedule of the FL EPA's testing and evaluation program. There have been conflicting assertions of responsibility among Federal, State, and Local agencies with regard to the originating miscreants. In 2010 an agreement was reached that would allow limited digging for center projects provided the soil is tested first. No digging can be performed without permission. In addition, no portion of the center grounds can be excessed without having that portion of the site cleaned up first.
HISTORIC PRESERVATION
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Equip/Veh Fueling
Waste Oil
Purpose
Active Energy Use Reduction Program
Active Water Use Reduction Program
Approximate or Measured Waste Recycled
Use of School Dude or CMMS for Preventative Maintenance
Green Purchasing Policy Practiced
Site Stormwater Absorption Measures in Place
Center has Onsite Renewable Energy (PV or Wind)
Center has a Chartered Green Committee & Roster
Center Uses Green Cleaning Practices
SUSTAINABILITY
NO
NO
NO
NO
NO
NO
NO
NO
Building Descriptions and Utilities
BUILDING 1 - ADMIN/ED/REC/DORM/VOC
Building Descriptions
Page: 1 of 61
Building: 0001 - ADMIN/ED/REC/DORM/VOC
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry/Steel Steel
CMU Masonry EIFS
Wall Roof Rigid Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential, Business, 100,400 71,148 1 Owned 1955 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material
Asbestos: Yes
The roof drains and gravel around said drains were installed in 2006. The building also has gutters and downspouts at the north side. New significant leaks appeared throughout the building after several storms in 2009 and 2010. The roof has many recent tar pitch patches. The roof life is based on visual observations and condition of the roof during the PY12 Facility Survey.
Drainage Year Life
Remaining Type Area Served
Coal Tar Roof Membrane Interior Roof Drains 1998 2 Flat Entire Building
Comments:
3. Roof
Entire Building
Area Served
Page: 2 of 61
Building: 0001 - ADMIN/ED/REC/DORM/VOC
Comments: The windows in the male dorm wings of this building need to be replaced.
INTERIOR FINISH
Carpet Ceramic Tile Concrete Quarry Tile Vinyl Tile
Ceramic Tile Drywall Exposed Structure Stucco Vinyl Wallcovering Wood Paneling
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Metal Ladder Metal Stairs Ramp
Comments: The building has a metal stair at the loading dock. Also, there is a metal ladder in the main mechanical room to access the roof. Concrete ramps are from the independent dormitory wings to ground. The building lacks adequate ready access to the very large attic above the main level.
Metal Overhead - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame
Awning Unit - Aluminum Frame; Double Glazing; Double Hung - Aluminum Frame; Double Glazing;
Fixed - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Glass Block Glazing;
Hopper - Aluminum Frame; Double Glazing; Skylight - Aluminum Frame; Plexiglass Glazing;
Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Number of Deficiencies = 1
Exterior Doors5. Number of Deficiencies = 1
Windows6. Number of Deficiencies = 1
Floors1. Asbestos: Yes Number of Deficiencies = 1
Interior Walls2. Asbestos: Yes
3.
Interior Doors4. Number of Deficiencies = 2
Ceilings
Page: 3 of 61
Building: 0001 - ADMIN/ED/REC/DORM/VOC
Mechanical
Mechanical
Mechanical
Mechanical
Dust Collection
Toilet/Shower
Laundry
Shop Area
Equipment Room
Shop Area
Comments:
Comments:
Comments:
Comments:
Comments:
Roof-mounted exhaust fans ventilate the toilet/showers in male dormitory wing 1 through 5 and toilet serving painting shop. The typical units are Loren Cook models 165C4B, 1/3 HP, 120C3B, 1/4 HP, 120C11D, 1/6 HP and 150C4B, 1/3 HP.
Wall-mounted exhaust fans ventilate the laundries in male dormitory wings 1 and 5.
Roof-mounted exhaust fans (Loren Cook models 402C9B, 2 HP and 150C10D, 1/3 HP) ventilate the painting and carpentry shops.
Wall-mounted exhaust fans ventilate the facilities maintenance room and transformer room.
A dust collector ventilates the carpentry shop. The unit is a Vibraclean with a 3.3 HP motor.
Ventilation Area ServedExhaust Ventilation
Number of Deficiencies = 5
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Four rooftop air-handling units (RTU-1 through 4) with steam heating coils provide heating and outdoor air to multiple VAV boxes with electric resistance reheat coils located in the male dormitory, recreation, and education areas. The typical unit is a Trane model TSCA050GCBOCAAOBAMO. Two Cleaver Brooks gas-fired steam boilers provide steam to the rooftop units and a portion of the steam is converted into hot water in a shell and tube heat exchanger and piped to Building 2. One stand-by boiler is a model CB 100-60, 2,511 MBH gas input, 2070 Lbs steam/hour output, 2009 MBH output, built in 12/05/80. The other boiler is a model CFH-700-60-15ST, S/N 16020006010017, 2,363 MBH gas input, built in 2012. These boilers are located in the north mechanical room.
A horizontal air-handling unit (AHU-6) with steam heating coils provides heating and outdoor air to the administration office area. The unit is a Trane model MCCA006BAJ0, located in the west mechanical/electrical room. A Cleaver Brooks gas-fired steam boiler model CFH-700-60-15ST, S/N 16020006010017, 2,363 MBH gas input, built in 2012, also provides steam to the air-handling unit.
Two rooftop-packaged heat pump units with supplemental electric resistance heating coils provide heating and outdoor air to the offices and classrooms in the painting and carpentry shops. The unit serving the painting shop is a Trane model WCD075C300BC, S/N N49101249D, R-22 refrigerant, built in 12/1998 with a 7.5-ton capacity. The unit serving the carpentry shop is a Trane model WCD120B300EB, S/N N48102241D, R-22 refrigerant, built in 12/1998 with a 10-ton capacity.
Six split-system heat pump units with supplemental electric resistance heating coils (8.0 kW) provide heating to the administrative spaces at the front of the building. The typical indoor air-handling units are Goodman models AR60-10 and ARUF363616BA. The typical outdoor heat pump units are Goodman model CK60-1AB, R-22 refrigerant, 60 MBH capacity, and GSH1303614C, R-22 refrigerant, 36 MBH capacity. These are located on-grade at the front of the building.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1. Number of Deficiencies = 1
Gas-Fired Steam Boiler
Gas-Fired Steam Boiler
Packaged Heat Pump (Air
Source)
Split Heat Pump (Air
Source)
Variable Air Volume
Single Duct
Single Duct
Single Duct
Four-Pipe
Four-Pipe
None
Refrigerant
Direct Digital Controls (DDC)
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
Mechanical
None
None
None
None
Entire Building
Classrooms and Offices
Classrooms and Offices
Offices
Ventilation2. Number of Deficiencies = 5
Page: 4 of 61
Building: 0001 - ADMIN/ED/REC/DORM/VOC
Chiller
Chiller
Packaged Direct
Expansion (Air Source)
Split Heat Pump (Air
Source)
Split Direct Expansion (Air
Source)
Variable Air Volume
Single Duct
Single Duct
Single Duct
Fan Coil
Four-Pipe
Four-Pipe
None
Refrigerant
Refrigerant
Direct Digital Controls
Electric
Electric
Electric
Electric
Mechanical
Mechanical
Mechanical
Mechanical
Natural
None
None
None
None
None
Dorm Rooms
Classrooms and Offices
Classrooms and Offices
Offices
Electronic Equipment
Room
Four rooftop air-handling units (RTU-1 through 4) with chilled water coils provide cooling and outdoor air to multiple VAV boxes with electric resistance reheat coils located in the male dormitory, recreation, and education areas. The typical unit is a Trane model TSCA050GCBOCAAOBAMO. Two Trane rotary chillers provide chilled water to the rooftop units. The typical chiller is a Trane model RTUA1284YEO1X3DOVN, S/N U00L05203 and U00L05204, R-22 refrigerant and a 125-ton capacity.
These are located in the north mechanical/electrical room. The four associated air-cooled condensing units reject heat from the chillers and are located on the roof. The typical unit is a Carrier model 09DE- 064---5 with a 64-ton heat rejection capacity.
A horizontal air-handling unit (AHU-6) with chilled water coils provides cooling and outdoor air to the administration office area. The unit is a Trane model MCCA006BAJ0, located in the west mechanical/electrical room. Two Trane rotary chillers also provide chilled water to a horizontal air-handling unit. The typical chiller is a Trane model RTUA1284YEO1X3DOVN, S/N U00L05203 and U00L05204, R-22 refrigerant and a 125-ton capacity. These are located in the north mechanical/electrical room. The four associated air-cooled condensing units reject heat from the chillers and are located on the roof. The typical unit is a Carrier model 09DE-064---5 with a 64-ton heat rejection capacity.
Two rooftop-packaged heat pump units provide DX-cooling and outdoor air to the offices and classrooms in the painting and carpentry shops. The unit serving the painting shop is a Trane model WCD075C300BC, S/N N49101249D, R-22 refrigerant, built in 12/1998 with a 7.5-ton cooling capacity.
The unit serving the carpentry shop is a Trane model WCD120B300EB, S/N N48102241D, R-22 refrigerant, built in 12/1998 with a 10-ton cooling capacity.
Six split-system heat pump units with DX-cooling coils mounted on the discharge provide cooling to the administrative spaces at the front of the building. The typical indoor air-handling units are Goodman models AR60-10 and ARUF363616BA. The typical outdoor heat pump units are Goodman model CK60-1AB, R-22 refrigerant, 5-ton cooling capacity and GSH1303614C, R-22 refrigerant, 3-ton cooling capacity. These are located on-grade at the front of the building.
A split-system provides cooling to the computer server room 227. The outdoor condensing unit is an EMI model SCC18DF0000AA0A (roof-mounted, R-22 refrigerant) and provides 1.5-ton cooling to an indoor ceiling-mounted ductless evaporative unit.
Comments:
Comments:
Comments:
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Number of Deficiencies = 2Air Conditioning
Page: 5 of 61
Building: 0001 - ADMIN/ED/REC/DORM/VOC
A Lochinvar gas-fired water heater (model CFN0500, S/N J938275, 500 MBH gas input, 515 GPH recovery) and associated Richmond Engineering hot water storage tank (model 7889A, 250-gallon capacity) provides domestic hot water to the male dormitory wings 4 and 5. These are located in the facilities maintenance room. The hot water loop has an in-line B&G circulating pump. A Raypak gas-fired water boiler (model W1-0962, S/N 0105182345, 961.7 MBH gas input, 78 SQ. FT. heating surface) and associated 800-gallon Reco hot water storage tank provides domestic hot water to the male dormitory wings 1 through 3. These are located in the equipment closet accessible from the advance solar shop. The hot water loop has an in-line B&G model HQC56A17D58F, 1.5 HP circulating pump. In addition, a 30-gallon capacity A. O. Smith electric water heater (model ELJF30T917, S/N GF005840432, 4.5 kW) provides domestic hot water to the education spaces. It is located in the west janitor's closet.
Comments:
Cast-Iron None Cast-Iron
Electric Water Cooler Emergency Eye Wash & Shower Hose Bibb Kitchen Sink Lavatory Mop Sink Multi-Compartment Sink Portable Bottled Water Cooler Shower Sink Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
Wet None ABC Type Fire Extinguisher
Comments: A dry sprinkler system is provided at the loading dock.
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING Number of Deficiencies = 3
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 5
Fuel Distribution4.
Number of Deficiencies = 1FIRE PROTECTION
Page: 6 of 61
Building: 0001 - ADMIN/ED/REC/DORM/VOC
Comments: Service is brought from a 2000 kVA pad-mounted transformer located in the back of the building. Service terminates in a 3000A, 277/480V, 3-phase, 4 wire switchboard in the electrical/mechanical room. The switchboard serves the building's HVAC equipment and feeds several step-down transformers which provide 120/208V 3-phase, 4 wire system for this building and Buildings 16, 29 and 39. The switchboard has an integrated voltage transient surge suppression (TVSS) device. There is a 55 kW, 120/208V, 3-phase, 4 wire generator located in the electrical/mechanical room. The generator provides backup power for emergency lights in this building and Building 2 via a 225A and 50A automatic transfer switch (ATS) located in Buildings 1 and 2 respectively.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution.
Comments: In addition to surface-mounted emergency lights with self-contained battery packs, there are selected lights throughout the building which are connected to the stand-by generator.
High Intensity Discharge (HID)
Comments: Exterior building-mounted light fixtures are controlled by time clock and photocell.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Classrooms
Sleeping Rooms
Recreation
Toilets
Storage Rooms
Corridors & Stairs
Conference Rooms
Equipment Rooms (Elec/Mech)
Shower
Maintenance Shop
Vocational
Laundry Room
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Switchboard 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELECTRICAL SERVICES Number of Deficiencies = 6
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 3
Emergency /Exit Lighting3.
LIGHTING
Page: 7 of 61
Building: 0001 - ADMIN/ED/REC/DORM/VOC
FIRE ALARM
Comments: The central fire alarm control panel is a Simplex 4100 series, located adjacent to the security office. A central annunciator panel is located in Gate House Building 14.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Connected to Main System None Connected to Main System Satellite Dish
Telephone Security Public Address Television
Number of Deficiencies = 2
GENERAL BUILDING CONDITION
Rating
Comments:
X Good Fair Poor
Roof leaks are repaired, but roof is at the end of useful service life. Interiors in the independent dormitory are worn and deteriorated. Previously repaired drains are subject to back-up. The mechanical equipment is somewhat aged and has control issues. An aggregate fix that would address energy costs and reduced maintenence would be costly.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Good Exterior: Fair Interior: Fair Mechanical: Fair Electrical: Good
This building has been recommended for renovation in the Long Range Development Plan.
RENOVATION RECOMMENDATION
Type Location None None
Comments: There are no CO detectors in this building. It is required by DOL Directive Information Notice 12-27 and
NFPA 720, 2012.
CARBON MONOXIDE DETECTION
BUILDING 2 - FOOD SERV/MED/DENTAL/VOC
Page: 8 of 61
Building: 0002 - FOOD SERV/MED/DENTAL/VOC
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Steel
CMU Masonry EIFS
Wall Roof Batt Rigid
Metal Overhead - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Assembly, Business 23,280 19,279 1 Owned 1955 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
Yes
Yes
Yes
Yes
Yes
Yes
N/A
N/A
No
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
EPDM Gutters and Downspouts 2006 13 Flat Entire Building
3. Roof
Page: 9 of 61
Building: 0002 - FOOD SERV/MED/DENTAL/VOC
INTERIOR FINISH
Carpet Ceramic Tile Concrete Terrazzo Vinyl Tile
CMU Ceramic Tile Drywall Vinyl Wallcovering Wood Paneling
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Ramp
Comments: There is a concrete ramp at the second egress door from the dining room.
Awning Units - Steel Frame; Double Glazing; Fixed - Aluminum Frame; Glass Block Glazing;
Fixed - Steel Frame; Single Glazing; Sliding - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Number of Deficiencies = 1
Windows6.
Floors1. Asbestos: Yes
Interior Walls2. Number of Deficiencies = 1
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A shell-and-tube, steam to hot water heat exchanger and pump located in the Building 1 north mechanical room, provides hot water for space heating in Building 2. Two horizontal VAV air-handling units (AHU-2-1 and 2-2) and VAV boxes with 2-pipe heating coils provide heating and outdoor air to the building. The unit (AHU-2-1, 7,000 CFM, 7.5 HP fan motor) serving the food service area is a Trane model MCCA014BAJ0C0, located in the north mechanical room near culinary arts dining room. The unit (AHU-2-2, 10,500 CFM, 10 HP fan motor) serving the medical/dental area is a Trane model MCCA021GAV0ABC0, located in the medical/dental mechanical room.
Comments:
HVAC
Heat1.
Gas-Fired Steam Boiler
Variable Air Volume
Four-Pipe Direct Digital Control (DDC)
Mechanical None Entire Building
Page: 10 of 61
Building: 0002 - FOOD SERV/MED/DENTAL/VOC
Mechanical
Mechanical
Mechanical
Kitchen
Toilet/Shower
Shop Area
Comments:
Comments:
Comments:
Roof-mounted centrifugal exhaust fans and make-up air units ventilate the kitchen, culinary arts kitchen and dishwasher hoods.
Ceiling and roof-mounted exhaust fans ventilate the toilet/shower rooms.
Wall-mounted exhaust fans ventilate the mechanical equipment room and auto mechanics shop.
Ventilation Area Served
Chiller Variable Air Volume
Two-Pipe Direct Digital Control (DDC)
Mechanical None Entire Building
Exhaust Ventilation
Two horizontal VAV air-handling units (AHU-2-1 and 2-2) with chilled water coils provide cooling and outdoor air to multiple VAV boxes with hot water reheat coils located in the food service and medical/dental areas. The unit serving the food service area is a Trane (model MCCA014BAJ0C0, 7,000 CFM, 7.5 HP fan motor) located in the north mechanical room near culinary arts dining room.
The unit serving the medical/dental area is a Trane (model MCCA021GAV0ABC0, 10,500 CFM, 10 HP fan motor) located in the medical/dental mechanical room. A Trane rotary chiller, model RTUA080AYE01R3DOVN, located in the southeast mechanical room, provides chilled water for cooling. The associated air-cooled condensing unit is a Trane model RTCA080G0E00A300N with an 80-ton heat rejection capacity. It is located on-grade outside the mechanical room.
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Air Conditioning
Page: 11 of 61
Building: 0002 - FOOD SERV/MED/DENTAL/VOC
Two 100-gallon capacity Lochinvar gas-fired water heaters (model CNR199-100-DF9, 200 MBH input and 193.9 GPH recovery) provide domestic hot water to the building except the auto mechanics shop.
These are located in the southeast mechanical room. Kitchen beverage dispensing service and icemaker are provided with a domestic cold water filtration system. In addition, a 19-gallon capacity State electric water heater (model ES620S0MSK, S/N 0820A017046, 2.5 kW) provides domestic hot water to the auto mechanics shop. It is located in the female toilet located on the northwest corner of the building.
Comments:
Cast-Iron Outdoor None
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Kitchen Sink Lavatory Mop Sink Multi-Compartment Sink Portable Bottled Water Cooler Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
Wet None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING Number of Deficiencies = 3
Water Distribution1.
Sanitary Distribution2. Number of Deficiencies = 2
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Number of Deficiencies = 2FIRE PROTECTION
Location UL300 Compliance Status Main kitchen and culinary arts kitchen. Compliant
Comments: The main kitchen hood is provided with a Kidde wet fire suppression system (model WHDR-400L) with an automatic gas shut-off valve and a shunt-trip for electric cooking equipment under the hoods. The culinary arts kitchen hood is provided with a Pyro-Chem wet fire suppression system (model PCL-350) with an automatic gas shut-off valve and a shunt-trip for electric cooking equipment under the hoods.
Both fire suppression systems meet the requirement of standard UL-300.
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 12 of 61
Building: 0002 - FOOD SERV/MED/DENTAL/VOC
Comments: Service is brought from a 300 kVA platform-mounted transformer located just outside the main mechanical room. Service terminates in a 1200A, 120/208V, 3-phase, 4 wire switchboard located in the mechanical room. A transient voltage surge suppression (TVSS) device is installed next to the switchboard. There is a 50A automatic transfer switch (ATS) and a 100A MLO emergency panel that are connected to the 55 kW generator located in Building 1.
FIRE ALARM
Comments: The fire alarm system components in this building are connected to the main fire alarm control panel located in Building 1.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Duct Smoke Detector Flow Switch Heat Detector Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Comments: In addition to surface-mounted emergency lights with self-contained battery packs, there are selected lights throughout the building which are connected to the 55 kW stand-by generator.
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T12 - Fluorescent
T8 - Fluorescent
Classrooms
Offices
Food Preparation
Corridors & Stairs
Medical/Dental
Toilets
Vocational
Dishwashing
Equipment Rooms (Elec/Mech)
Wards (Patient)
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Switchboard 120/208V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
ELEC…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .