GulfportGulfport

Job Corps Center Gulfport, MS

Facility Planning ReportFacility Planning Report Volume II

Supporting Data

Fi lFinal June 2012

Department of Labor/ Office of Job Corps

22Gulfport Job Corps Center

GulfportGulfport

Job Corps Center Gulfport, MS

Facility Planning ReportFacility Planning Report Volume II

Supporting Data

Fi lFinal June 2012

View of central circulation spine between the modular buildings

33 Gulfport Job Corps Center

CONTENTS

GULFPORT JOB CORPS CENTER

FACILITY PLANNING REPORT

VOLUME I - Planning Strategy

• Existing Site Plan

• Center Statistics

INTRODUCTION

• Purpose

• Report Contents

EXECUTIVE SUMMARY

A. EXISTING CONDITIONS

• Background

• General Site Conditions

• General Building Conditions

• Preventive Maintenance

• Ownership

• Facility Assessment by Function

• Energy

• Environmental Issues

• Sustainability

• Accessibility Standards

• Completed and Current Projects Since the Last Survey

• Health and Life Safety Issues

• Summary of Defi ciencies

B. RECOMMENDATIONS

• Status of the Previous (PY08) Plan

• Signifi cant Issues

• PY 11 Plan Overview

• Summary of Proposed Projects

• Regional Projects

• Proposed Near Term Site Plan

• Proposed Long Term Site Plan

C. PLANNING ANALYSIS

• Purpose

• Planning Objectives and Assumptions

• Space Utilization Analysis

• Federal Real Property Asset Management

• Mission Dependency Site Plan

• Defi ciency Analysis

• Facility Condition Summary Report

• Building Condition by Function

• Building Condition Site Plan

VOLUME II - Supporting Data

• Vicinity Map

• Location Map

• Existing Site Plan

D. DESCRIPTIONS

• Building and Structures

• Space Utilization By Function

• NSF by Building

• Energy Report

• Environmental Management

Asbestos Report Radon Report

• Site Descriptions

• Building Descriptions

E. DEFICIENCIES

F. CORRESPONDENCE AND REPORTS

• Center Review Meeting Minutes

• Survey Brief

• RA and Student Facility Feedback Questionnaire

• Life Safety Defi ciencies Transmittal and List

• O & M Defi ciency List

• Active Warranty Report

• FRPC Performance Measures Matrix

66Gulfport Job Corps Center

44Gulfport Job Corps Center

55 Gulfport Job Corps Center

77 Gulfport Job Corps Center

D Descriptions

BUILDINGS AND STRUCTURES

00411 GULFPORT 06/22/2012

1Page: of Date:

0001 - MAIN BUILDING (VACANT)

0002 - GYMNASIUM (VACANT)

0005 - CAFETERIA (VACANT)

0008 - GUARD HOUSE

0009 - FAC. MAINT., PROPERTY WHSE.

& VOC. STORAGE

0010 - FEMALE DORMITORY

M-0001 - ADMINISTRATION MODULAR -

#1

M-0002 - ADMINISTRATION MODULAR -

#2

M-0003 - WELLNESS CENTER - #3

M-0004 - DINING/KITCHEN - CAFETERIA

- #4

M-0005 - EDUCATION - #5

M-0006 - SOFT VOCATION

M-0007 - CPP

M-0008 - SOFT VOCATION - #8

0006 - DUMPSTER SHELTER

0007 - STORAGE

Name GSF

35,520 15,000 6,820

7,211

15,607 1,440

1,440

1,440 4,464

3,024 3,024

Active Active Active Active Active

Active Active

Active

Active Active

Active Active Active Active Active Active

StatusType

Building Building Building Building Building

Building Building

Building

Building Building

Building Building Building Building Structure Structure

Use Group Built Flrs Const

Multiple Func Assembly Assembly Business Storage

Residential Business

Business

Business Assembly

Business Business Business Business Utility/Misc.

Storage

Poor Poor Poor Good Good

Good Good

Good

Good Good

Good Good Good Good Good Good

ConditionAsset Number

0041100002 0041100003 0041100006 0041108105 0041100010

0041100011 0041108095

0041108096

0041108097 0041108098

0041108099 0041108100 0041108101 0041108102 0041108104 0041108103

14 96,990

2 320

16 97,310

Buildings

Structures

Total

GSF

GSF

GSF

Summary

06/22/2012

Space Utilization By Function 00411 Gulfport Page: 1 of Date:

HOUSING

EDUCATION

FOOD SERVICE

RECREATION

MEDICAL/DENTAL

ADMINISTRATION

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

SUB TOTAL

Resident Men Resident Women Total Residents

Residents 68 Non Residents 68

136Total Students

(68)

(136)

(136)

(136)

(136)

(136)

DIFFERENCE

6,800

6,420

1,088

4,420

2,720

9,500

9,588

4,018

1,224

2,769

Lounge Other Shower/Toilet Sleeping Storage

Academic (136) Non-Academic

24 -- Electrical + 25 -- Medical Assistant 25 -- Medical Office Support 25 -- Nursing Assistant +

Dining (2 Servings)

Recreation Room

Medical/Dental

Administration

7.3

1,320

1,110 5,980

3,042 2,624

1,568

4,018

1,224

2,769

4,896

1,360 1,360

1,200

1,000

1,088

2,720

1,084

-283

1,682 1,264

-150

2,930

Vocations

RESIDENT

NON-RESIDENT

(68)

(68) 15

50 3,400 1,020

2,700

3,168

2,930

-3,930

06/22/2012

Space Utilization By Function 00411 Gulfport Page: 2 of Date:

STORAGE/SUPPORT

VACANT

SUGGESTED

NSF/

ENROLLEE

SUGGESTED

TOTAL

NSF

ACTUAL

TOTAL

NSF

TYPE OF SPACE

SUB TOTAL

SUB TOTAL

TOTAL 185.01 25,161 73,099

(136)

(0)

DIFFERENCE

96,990

0.75

TOTAL GSF

NET TO GROSS RATIO

2,720

4,395

41,115

Operations & Maintenance Warehouse

Vacant

2,000 2,395

41,115

1,088 1,632

1,675

41,115

47,938

Net Square Footage By Building Date: 06/22/2012 Page: 1

Center: GULFPORT (00411) of 2

HOUSING

EDUCATION

FOOD SERVICE

RECREATION

Sleeping

Lounge

Storage

Shower/Toilet

Other

Academic

Electrical

Medical Assistant

Non-Academic

Nursing Assistant

Medical Office Support

Dining (2 Servings)

Recreation Room

Function Suggested NSF

5,980

1,320

1,110

2,722

1,568

4,018

0010 - FEMALE DORMITORY

0010 - FEMALE DORMITORY

0010 - FEMALE DORMITORY

0010 - FEMALE DORMITORY

0010 - FEMALE DORMITORY

0010 - FEMALE DORMITORY

M-0005 - EDUCATION - #5

0009 - FAC. MAINT., PROPERTY WHSE. & VOC

M-0006 - SOFT VOCATION

M-0007 - CPP

0010 - FEMALE DORMITORY

M-0006 - SOFT VOCATION

0010 - FEMALE DORMITORY

M-0006 - SOFT VOCATION

M-0008 - SOFT VOCATION - #8

M-0006 - SOFT VOCATION

M-0004 - DINING/KITCHEN - CAFETERIA - #4

0010 - FEMALE DORMITORY

Bldg Name Actual NSF Difference

5,980

1,320

1,110

3,042

1,568

2,624

4,018

Sub Total:

Sub Total:

Sub Total:

Sub Total:

9,500

9,588

4,018

4,896

1,360

1,200

1,360

1,000

1,088

6,800

6,420

1,088

4,420

1,084

-283

1,682

1,264

-150

2,930

2,700

3,168

2,930

-3,930

Net Square Footage By Building

Page: 2

Center: GULFPORT (00411) of 2

MEDICAL/DENTAL

ADMINISTRATION

STORAGE/SUPPORT

VACANT

Medical/Dental

Administration

Warehouse

Operations & Maintenance

Vacant

Function Suggested NSF

1,224

1,224

1,224

2,395

2,000

5,080 21,835 14,200

M-0003 - WELLNESS CENTER - #3

M-0002 - ADMINISTRATION MODULAR - #2

0009 - FAC. MAINT., PROPERTY WHSE. & VOC

M-0001 - ADMINISTRATION MODULAR - #1

0008 - GUARD HOUSE

0009 - FAC. MAINT., PROPERTY WHSE. & VOC

0009 - FAC. MAINT., PROPERTY WHSE. & VOC

0005 - CAFETERIA (VACANT)

0001 - MAIN BUILDING (VACANT)

0002 - GYMNASIUM (VACANT)

Bldg Name Actual NSF Difference

1,224

2,769

2,395

2,000

41,115

Sub Total:

Sub Total:

Sub Total:

Sub Total:

1,224

2,769

4,395

41,115

2,720

1,632

1,088

2,720

2,720

41,115

1,675

41,115

Energy Management Report Center: GULFPORT (00411)

Page: 1 Date: 06/22/2012 of 3

CENTER ENERGY DATA

None

ENERGY CONSUMPTION ASSESSMENT

61% 37,672

79,899 97,438

ENERGY USE BY FUEL TYPE

Energy Audit :

Date of Audit :

Electric Company :

Percent Change since Baseline Year :

Natural Gas Company :

Property Status :

N/A

Mississippi Power Company Center Point Energy Co.

Combination of Owned & Leased

742,594 2,534=

Total 3,236

MBtu

MBtu

Total $90,584 MBtu/ $27.993

BTU/GSF

BTU/GSF

BTU/GSF

Electricity

Natural Gas kWh

681 MCF = 702 MBtu

$84,998 $0.114= kWhElectricity

Natural Gas $5,586 = $8.203 MCF

ENERGY COST BY FUEL TYPE

COMMENTS

9/22/03 Adjusted Cf for gas.

8/1/2001 New LED installed in Gym, Filters & Belts changed, Security staff check for lights & PCs 2/5/01 EMCs - PM, filters, Security turns off lights

WATER CONSUMPTION ASSESSMENT

Percent Reduction Since Baseline Year:

1,000 Gallons

1,000 Gallons

FY 2011 Energy Goal:

Energy Goals are being met. Keed up the Good Work to further Reduce Energy Usage.

FY 2011 Energy Consumption:

Note: The Federal Government has set a goal of 3% Energy Consumption Reduction per year in EO 13423.

1,893

Further Reduction in Water Usage is needed to meet Water Reduction Goals.

Note: The Federal Government has set a goal of 2% Water Consumption Reduction per year in EO 13423.

FY 2011 Goal:

FY 2011 Water Consumption:

1,000 Gallons

FY 2003 Energy Baseline:

FY 2008 Baseline:

Page: 2 of 3

Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.

1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:

a. Turn it down (lights, heating & cooling),

b. Turn it off (lights, computers, other equipment),

c. Keep it tight (close doors and windows, use window blinds)

2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:

a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.

b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.

c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.

d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.

e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.

f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.

g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.

h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.

i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.

Page: 3 of 3

j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.

k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.

l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.

m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.

n. Caulk and fill cracks around doors and windows to reduce costly air leaks.

o. When replacing broken glass, use high transmittance, low heat gain windows.

p. Make sure automatic door closers are functioning properly to avoid drafts.

3. Buy energy efficient, buy EnergyStar (www.energystar.gov).

a. Buy EnergyStar appliances and equipment.

b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).

c. Replace broken thermostats with EnergyStar labeled programmable products.

d. Replace broken exit signs with EnergyStar LED exit signs.

Environmental Management Report

Page: 1 Date: 06/22/2012 of 1

SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)

Commercial Waste Service

HAZARDOUS MATERIALS STORAGE (EPCRA)

No N/A

N/A No

PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)

N/A0

PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)

ASBESTOS AND PCB MANAGEMENT (TSCA)

AIR POLLUTION CONTROL (CAA)

N/A None

Attainment

Solid Waste Disposal :

Hazardous Waste Generator :

Hazardous Waste ID :

Generator Classification :

Hazadous Materials Storage :

Hazardous Materials ID :

HazMat Storage Area :

HazMat Spill Response Plan :

Number of Regulated USTs :

Number of Un-regulated USTs :

Local Hazardous Use Permit :

LEPC Notification :

EPA Generator ID Number :

Hazardous Waste Disposal :

RCRA Compliance

ID LocationFuel Type Capacity

Number of ASTs :

Asbestos Survey Date :

Asbestos Type :

Asbestos Coordinator :

Coordinator Training Date:

Custodial/Maintenance Training :

AHERA Regulated :

Management Plan Approval :

PCB Transformer Testing :

PCB Transformers :

PCB-Contaminated Transformers :

Transformers Labelled :

Regional Air Quality :

Permitted Air Pollution Source :

Source Description :

Waste Management, Inc.

No N/A

N/A N/A N/A

N/A

No No

Overfill Leak Corrosion

SPCC Plan Required : SPCC Plan Completed :

No N/A

04/10/1992 Friable/Non-Friable Kevin Manuel 06/12/2003 Yes No

No No

ID Fuel Type Capacity Location Overfill

Prevention Secondary ContainmentTank Status

Tank Status Prevention/Detection

Asbestos-Containing Materials Inventory

Date: 06/22/2012Center : Gulfport (00411) Page: 1 of 1

Floor Finishes Ceiling Finishes Heating

Ceiling Finishes

Ceiling Finishes Roof Repair/Replacement Windows

Bldg System

Bldg System

Bldg System

Mastic beneath 12x12 tile Asbestos cement board Pipe fitting insulation

Asbestos cement board

Asbestos cement board Roof flashing Window caulking

Category Description

Category Description

Category Description

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Sq. Ft.

Lin. Ft.

Lin. Ft.

Location

Location

Location

Unit

Unit

Unit

Quantity

Quantity

Quantity

!st and 2nd floors 2nd floor Throughout

Under roof decking

Under roof decking Exterior of building Dining area

35000

12750

12500

Building :

Building :

Building :

0001 - MAIN BUILDING (VACANT)

0002 - GYMNASIUM (VACANT)

0005 - CAFETERIA (VACANT)

Radon

Page: 1 of 1

0001 - MAIN BUILDING (VACANT)

0002 - GYMNASIUM (VACANT)

0005 - CAFETERIA (VACANT)

0008 - GUARD HOUSE

0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STO

0010 - FEMALE DORMITORY

M-0001 - ADMINISTRATION MODULAR - #1

M-0002 - ADMINISTRATION MODULAR - #2

M-0003 - WELLNESS CENTER - #3

M-0004 - DINING/KITCHEN - CAFETERIA - #4

M-0005 - EDUCATION - #5

M-0006 - SOFT VOCATION

M-0007 - CPP

M-0008 - SOFT VOCATION - #8

Bldg Name

06/06/1990

06/06/1990

06/06/1990

Test Date

Yes

Yes

Yes

No

N/A

No

No

No

No

No

No

No

No

No

Radon Testing

< 4 pCi

< 4 pCi

< 4 pCi

Test Result

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

Mitigation Mitigation Date

RADON EXPLANATORY NOTES

The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than

4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.

Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;

(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.

Site Description Gulfport

Aerial view of Gulfport Job Corps CenterAerial view of Gulfport Job Corps Center

Page: 1 Date: 06/22/2012 of 4

Comments:

Paving Type for Roads & Parking

The courtyard has brick pavers.

Paving Type for Sidewalks

Asphalt Concrete

Comments:

Topography Buildings and Structures

Center is fully enclosed by fencing. A significant portion of the site is fenced off to prevent entry to Buildings 1, 2, and 5 which have sustained severe storm damage from Hurricane Katrina in 2005 and are deteriorated. These buildings and site areas were not assessed as part of the January 2012 Facility Survey.

The site is very tight with limited room for expansion.

ROADS, PARKING & SIDEWALKS

Water Source Water Authority Service Meter On-Site Treatment Plant

1. Water System

Treatment Type Storage Type Storage Capacity(Gallons)

NoMasterCity of Gulfport Water DepartmentPublic Water Authority

None 0None

Comments:

Fire Hydrants On-Site Water Supply Storage Capacity

(Gallons) Pressure Source FD Response Time (Minutes)

Yes 0 10None Municipal

The nearest fire station is Gulfport City Fire Department. There are two other fire stations located 10 miles away from the center.

Number of Deficiencies = 1SITE FEATURES

UTILITIES

2. Fire Protection System

Buildings Structures14 2Flat

Surrounding

Outdoor Recreation

Residential

Field

Front

Sides and Rear

Wrought Iron

Chain Link

Location Type

Maintenance Responsibility System Capacity Adequate System Condition

Utility Utility Yes Good

Separate Loop

No

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility Utility Yes Good

Ownership

Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good

Fencing

Other Features

Page: 2 Date: 06/22/2012 of 4

Sewage Treatment Flow

Utility

Publicly Owned Treatment Works

Utility

Gravity

Maintenance ResponsibilityOwnership

Comments: Center Point Energy Co. is the natural gas supplier.

Center Point Energy Co.

3. Sanitary Sewer System/ Sewage Treatment Plant

5. Fuel Distribution System

System Capacity Adequate System Condition

Yes Good

4. Storm Water System Number of Deficiencies = 1

Drain Type On-Site Storm Water Management

Underground N/A

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Center Yes GoodCenter

Gas Company Metering

Master

Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility Utility Yes Good

6. Central Plant: None

Page: 3 Date: 06/22/2012 of 4

Comments:

Electric Company PCB Trans.

Transformer Mounting Transformer Ownership

Systems Ownership Maintenance Responsibility

Mississippi Power Company

Overhead primary lines enter the site from 21st Street. The primary system is radial and is distributed on the center overhead and underground. The primary conductors dip underground at the power pole located near Gate House Building 8 to serve a 1000 kVA pad-mounted transformer providing for Modular Buildings M-0001 through M-0008 and at the power pole also located along 21st Street to serve a 500 kVA transformer providing for Dormitory Building B-10. The overhead primary lines continue to a 3x25 kVA pole-mounted transformer bank providing for Maintenance Building B-9. Modular Buildings M-0001 through M-0008 and Maintenance Building B-9 are provided with 120/208V, 3-phase, 4 wire services. The only 480/277V, 3-phase, 4 wire secondary service is provided to Dormitory Building 10. Buildings 9 and 10 have separate secondary utility meters, Modular Buildings M-0001 through M-0008 are measured as a zone. Modular Buildings M-0001, 02, 03, 05 and 06 are served from a 1000A MCB distribution panelboard and Modular Buildings M-0007, 8, and 4 are served from a 1200A MCB distribution panelboard, both located along the south exterior wall of Module M-0002. There are 2 motorized sliding gates (each motor 1.2 HP, 1-phase) at the entrance to the main center area and 3 motorized sliding gates at the remote parking (one gate currently in use) operated from Gate House Building 8. The gate facing 21st Street and the gate at the remote parking area stay open during normal business hours and are closed after hours. There is an air phone at the main center entrance (near Gate House Building 8) and the speaker at the power pole located on the centers side of the gate for after hours visitors.

Pole and Pad Utility

Utility Utility

No

22.86/13.20 kV, 3-Phase 4-wire

480/277 Volt, and 120/208 Volt, 3-Phase, 4 WireOverhead & Underground

Overhead & UndergroundPrimary Service

Secondary Service

Distribution Characteristics

Number of Deficiencies = 37. Electrical (Service)

Transformer Maint Resp

Utility

System Capacity Adequate System Condition

Yes Good

Generator

None

8. Electrical (Site Lighting)

Roadways Parking Walkways Building Outdoor Sports

Mounting

Control

Pole Pole Pole Building None

Photocell Photocell Photocell Photocell, Time Clock None

System Ownership Maintenance Responsibility System Capacity Adequate System Condition

Utility, Center Utility, Center Yes Good

Comments: Wall-mounted metal-halide fixtures at Modular Buildings M-0001 through M-0008 are controlled by a wall-mounted photocell located at the south wall of Administration Module M-0002. Wall-mounted lighting at Building 10 is controlled by time clock and roof-mounted photocell. Wall-mounted lighting at Building 9 is controlled by time clock.

Pole-mounted lighting (HPS flood and cobra-head lights) mounted on the utility poles, belonging to and maintained by the utility, are controlled by fixture-mounted photocells. There are no dedicated sport lights. The basketball hoop and surrounded area are illuminated by the wall-mounted and pole-mounted street lights. Modular Building lights are fed from a 100A MLO panel located at the south exterior wall of Modular Building M-0002. The panel is fed from a 1200A (modular) distribution panel.

ATS MTS

No No

Number of Deficiencies = 1

Metering Individual

Page: 4 Date: 06/22/2012 of 4

ACCESSIBILITY

Yes

NoNoYesNo

Nationally Registered Site

Site Eligible for National Register

Located in Historic District

Archaeological Significance

Comments:

Telephone Company

On-site Line Owner

Overhead telephone lines dip underground at the power utility pole. (3) T1 communication lines, two for the internet and one for the VoIP enter the main server closet (MC) at Adm. Module M-0001. The MC is provided with

(3) routers Cisco 3800 series, a Cisco 6500 series switch utilized for phone and internet connectivity, (2) voice gateway units for Fax connection and a Blue Coat Proxy for security and WAN optimization. The equipment is connected to a UPS back-up system (Smart UPS 10kW) that provides power in case of an outage. Other buildings on the campus are connected to the MC by fiber (GCC 6F 62.5) for both data & voice communications.

Connections for data outlets in the buildings are provided by CAT 5E cable. The fire alarm (FA) system on center consists of stand-alone units. The required periodic FA system inspection was conducted by Fire Protection Security Safety Corp. ((228) 575-6275; fax-(228) 575-6273)) March 19, 2012. A CCTV system consists of 17 exterior and interior, building & pole mounted security cameras and a color monitor located at the security office at Dormitory Building 10. At Building B-10 there are 6 interior security cameras (a dome and a bullet security camera in each wing corridor, dome cameras, one in the laundry and one in the commons area), and 3 exterior security cameras (pentax zoom and bullet at the east exterior wall and pentax zoom at the entrance to the front porch).

There are 8 exterior security cameras throughout the center: two bullet cameras on Building 9, three at Modular Buildings M-0006, 5 and 4, pole-mounted pentax zoom camera located SE of the dorm, a pole-mounted bullet camera locater at the back of Modular M-0008 and a pole-mounted camera located at the remote parking lot.

Local cable is provided in Building 10 and in Modules M-0001 & 3. Magnetic door alarm provided at the west wing door at the dorm is monitored from the RA office. The panel is connected to all doors; the alarm at the east door was removed.

AT&T

Maint. Responsibility

Center Center

Surveillance CCTV with exterior and interior cameras and a monitor, door alarms

Earthquake Risk

Low Medium LowLow LowIBC Medium

LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest

Fire

Accessible Parking: Accessible Slope:

Yes

Curb Cuts:

Yes

Ramps:

YesYes

Site Accessible Route:

GENERAL SITE CONDITION

Rating X Good Fair Poor

A significant portion of the site is fenced off to prevent entry to Buildings 1, 2, and 5 which have sustained severe storm damage from Hurricane Katrina in 2005 and are deteriorated. These buildings and site areas were not assessed as part of the January 2012 Facility Survey.

HISTORIC PRESERVATION

9. Electrical (Communication/Alarm/Security)

NATURAL HAZARDS

The site condition is not impacting the functional use of the facilities.

The site condition IS impacting the functional use of the facilities.

The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.

Yes

Stand-Alone

VOIP

System Capacity Adequate System Condition

GoodYes

Number of Deficiencies = 1

STORAGE TANKS: None

Fire Alarm Security

Building Descriptions and Utilities

BUILDING 1 MAIN BUILDINGBUILDING 1 - MAIN BUILDING

Building Descriptions

Page: 1 of 64

Building: 0001 - MAIN BUILDING (VACANT)

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel

Brick Masonry

Wall Roof Unknown Rigid

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Multiple Functions 35,520 21,835 2 Leased 1952 Unevaluated

Comments: The building has sustained severe storm damage from Hurricane Katrina in 2005. It is deteriorated and fenced off to prevent entry and was not assessed as part of the January 2012 Facility Survey. The information provided below is from the February 2004 Facility Survey:

Building is accessible at the main entrance on the south, the two east side entrances and at the double doors to the maintenance area on the north side. The building is not accessible from the two west side entrances. Corridor is not accessible between the three tiers. Second floor classrooms are not accessible.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

No

Yes

No

No

No

Yes

Yes

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material Drainage Year Life

Remaining Type Area Served

Built-up Roofing Gutters and Downspouts 1999 10 Flat Entire Building

3. Roof

Entire Building

Area Served

Page: 2 of 64

Building: 0001 - MAIN BUILDING (VACANT)

INTERIOR FINISH

Carpet Ceramic Tile Concrete Vinyl Tile

Ceramic Tile Drywall Exposed Structure Plaster Wood Paneling

Wood Unit - Wood Frame

Comments: The doors have vision panels.

VERTICAL CIRCULATION

Concrete Stairs

Comments: Six interior concrete stairs and one exterior steel stair. Both the ground and second floor have three tiers. The tiers are connected by a central corridor which has a stair consisting of 6 steps to transition the level change between tiers. The floors are connected by two stairs on the west side of the building adjacent to the transitioning stairs that connect the tiers.

Metal Unit - Metal Frame

Double Hung - Aluminum Frame; Double Glazing; Fixed - Steel Frame; Single Glazing;

Hopper - Steel Frame; Single Glazing;

Acoustical Tile Gypsum Board

Exterior Doors5.

Windows6.

Floors1. Asbestos: Yes

Interior Walls2.

3. Asbestos: Yes

Interior Doors4.

Ceilings

Page: 3 of 64

Building: 0001 - MAIN BUILDING (VACANT)

Mechanical/Natural Restroom

Comments: Wall mounted exhaust fans ventilate the main mechanical and electrical rooms. A fan located near the roof circulates room air in the maintenance storage room.

Ventilation Area Served

Chiller Units

Chiller

Fan Coil

Single Duct

Four-Pipe

Four-Pipe

Electric

Electric

Mechanical - Natural

Mechanical

None

None

Classrooms and Offices

Medical/Dental

Exhaust Ventilation

The air cooled chillers serve the entire building except for the maintenance/logistic areas. Ceiling mounted, chilled water, fan coil units cool the classrooms, offices and corridors. Floor mounted, chilled water, fan coils cool the outdoor entrances of the building.

A chilled water air handling unit (AHU) located in a small equipment room cools the interior rooms of the medical/dental area.

Comments:

Comments:

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Ceiling mounted, hot water, fan coil units heat the classrooms, offices and corridors. Floor mounted, hot water fan coils heat the outdoor entrances and the perimeter rooms of the medical/dental area.

A hot water air handling unit (AHU) located in a small equipment room heats the interior rooms of the medical/dental area.

Gas fired unit heaters heat the maintenance storage rooms and shops.

Comments:

Comments:

Comments:

HVAC

Heat1. Asbestos: Yes

Gas-Fired Hot Water Boiler

Gas-Fired Hot Water Boiler

Gas-Fired

Fan Coil

Single Duct

Unit Heater

Four-Pipe

Four-Pipe

None

Electric

Electric

Electric

Mechanical - Natural

Mechanical

Natural

None

None

None

Classrooms and Offices

Medical/Dental

Storage

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

3. Air Conditioning

Page: 4 of 64

Building: 0001 - MAIN BUILDING (VACANT)

A gas-fired domestic water heater provides hot water to the medical/dental area. 8 electric water heaters, one per toilet, provide hot water to the toilet rooms. 1 electric water heater provides heat to the medical assistant classroom.

Comments:

Cast Iron None Cast Iron

Dental Sink Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Service Sink Shower/Bathtub Urinal Water Closet (Flush Valve) Water Closet (Tank)

Gas (Natural)

Wet Wet ABC Type Fire Extinguisher

Comments: Each of the three (3) janitor closets is equipped with a sprinkler head supplied from the domestic water system. The rest of the building is not sprinklered. Code required fire extinguishers, ABC type, inspected recently, operable and properly tagged are located throughout the building.

Comments: The switchgear size is 1800A with a 500 KVA step-down transformer, providing the 120/208 Volt, 3-phase, 4-wire system.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

High Intensity Discharge (HID)

Main Disconnect Switch 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, Switches

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

LIGHTING

Page: 5 of 64

Building: 0001 - MAIN BUILDING (VACANT)

FIRE ALARM

Comments: The fire alarm panel is a Fire Control Instrument 7200 Series control/annunciator panel, located in the electrical room and the remote control annunciator is located in the first floor corridor. Also, a central annunciator panel is located in the facility manager's office.

Comments: Public phones are provided for students.

Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm

Connected to Main System Closed Circuit TV Connected to Main System None

Telephone Security Public Address Television

Comments: The recorded footcandle level includes natural light contribution.

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

T8 - Fluorescent

Offices

Classrooms

Medical/Dental

Storage/Warehouse-Active

Area Recommended Level

Recorded Level Light Type

Battery Backup Battery Backup

Emergency Exit

GENERAL BUILDING CONDITION

Rating

Comments:

X

Good Fair Poor

The facility has sustained severe storm damage, is vacant and is deteriorating.

Interior Lighting2.

Emergency /Exit Lighting3.

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas No NoNo

BUILDING UTILITY METERING

Structure: Poor Exterior: Poor Interior: Poor Mechanical: Poor Electrical: Poor

BUILDING 2 GYMNASIUMBUILDING 2 - GYMNASIUM

Page: 6 of 64

Building: 0002 - GYMNASIUM (VACANT)

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel

Brick Masonry

Wall Roof None Rigid

Metal Unit - Metal Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Assembly 15,000 14,200 1 Leased 1952 Unevaluated

Comments: The building has sustained severe storm damage from Hurricane Katrina in 2005. It is deteriorated and fenced off to prevent entry and was not assessed as part of the January 2012 Facility Survey.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

No

No

Yes

No

Yes

N/A

No

No

No

N/A

No

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material Drainage Year Life

Remaining Type Area Served

Built-up Roofing Gutters and Downspouts 1999 10 Flat Entire Building

3. Roof

Page: 7 of 64

Building: 0002 - GYMNASIUM (VACANT)

Comments: There are also glass block assemblies on the mezzanine and in the gymnasium.

INTERIOR FINISH

Ceramic Tile Concrete Wood

Comments: There is parquet flooring in the gymnasium.

Ceramic Tile Drywall

Metal Unit - Metal Frame Wood Unit - Wood Frame

VERTICAL CIRCULATION

Concrete Stairs

Comments: There are wood stairs to the mezzanine and concrete stairs to the basement.

Awning Unit - Steel Frame; Single Glazing; Hopper - Steel Frame; Single Glazing;

Acoustical Tile Exposed structure Gypsum Board

Windows6.

Floors1.

Interior Walls2.

3. Asbestos: Yes

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

The packaged gas-fired HVAC unit located on grade at the east wall heats the gymnasium and mezzanine areas.

Two gas-fired furnaces heat the counselor and security manager's offices, the mezzanine and the women in community service (WICS) office. They are located in small equipment rooms adjacent on the upper levels of the mezzanine.

A gas-fired unit heater heats the arts and crafts room.

Comments:

Comments:

Comments:

HVAC

Heat1.

Packaged Gas- Fired Furnace

Gas-Fired Furnace

Gas-Fired unit Heater

Single Duct

Single Duct

Unit Ventilator

None

None

None

Electric

Electric

Electric

Mechanical - Natural

Mechanical - Natural

Mechanical - Natural

Economizer

None

None

Recreation Area

Offices

Classrooms

Page: 8 of 64

Building: 0002 - GYMNASIUM (VACANT)

Mechanical Restroom

Comments: A wall mounted exhaust fan ventilates the weight room. Another wall mounted exhaust fan ventilates the kiln room.

The gas-fired domestic water heater does not work and has not been repaired or replaced. There is no domestic hot water supply in this building.

Comments:

Cast-Iron None None

Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Service Sink Water Closet (Flush Valve)

Gas (Natural)

Ventilation Area Served

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Air-cooled Packaged Unit

Split Direct Expansion (Air

Cooled)

Direct Expansion Refrigerant

Single Duct

Single Duct

Window Unit

None

Refrigerant

None

Electric

Electric

Electric

Mechanical - Natural

Natural

Mechanical - Natural

Economizer

None

None

Gymnasium

Offices

Classrooms and Offices

PLUMBING

Exhaust Ventilation

An air-cooled, packaged HVAC unit located on grade at the east wall, cools the gymnasium and bleacher areas.

Two, split system, air cooled HVAC units cool the counselor and security manager's offices, the mezzanine and the women in community service (WICS) office. They are located in small equipment rooms on the upper levels of the mezzanine.

Window air conditioning units serve the security office, aerobic and female weight room, computer room, recreation supervisor's office, arts and crafts room, and storage room (the former snack bar room.).

Comments:

Comments:

Comments:

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

Page: 9 of 64

Building: 0002 - GYMNASIUM (VACANT)

N/A None ABC Type Fire Extinguisher

Comments: Code required fire extinguishers, ABC type, recently inspected and operable and properly tagged are located in the building.

Comments: The panelboard located in this building is fed from Building 1.

FIRE ALARM

Comments: The fire alarm panel is a Fire Control Instrument, SNAC, control panel, and is connected to the central annunciator panel located in the facility manager's office in Building 1.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control Panel Duct Smoke Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm

Connected to Main System None None None

Telephone Security Public Address Television

Comments: The recorded footcandle level includes natural light contribution.

Fluorescent

High Intensity Discharge (HID)

T12 - Fluorescent

T12 - Fluorescent

Recreation

Offices

Storage/Warehouse-Active

Area Recommended Level

Recorded Level Light Type

Battery Backup Battery Backup

Main Disconnect Switch 120/208V, 3-Phase, 4-Wire Panelboard Receptacles, GFCI, Switches

Sprinkler System Stand Pipe System Fire Suppression

Emergency Exit

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

COMMUNICATION

Electric Water Gas No NoNo

Page: 10 of 64

Building: 0002 - GYMNASIUM (VACANT)

GENERAL BUILDING CONDITION

Rating

Comments:

X

Good Fair Poor

The facility has sustained severe storm damage, is vacant and is deteriorating.

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

BUILDING 5 CAFETERIABUILDING 5 - CAFETERIA

Page: 11 of 64

Building: 0005 - CAFETERIA (VACANT)

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Structural Steel Steel

Brick Masonry

Wall Roof None Rigid

Metal Unit - Metal Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Assembly 6,820 5,080 1 Leased 1952 Unevaluated

Comments: The building has sustained severe storm damage from Hurricane Katrina in 2005. It is deteriorated and fenced off to prevent entry and was not assessed as part of the January 2012 Facility Survey.

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

No

No

Yes

No

Yes

Yes

Yes

No

N/A

No

N/A

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material

Asbestos: Yes

Drainage Year Life

Remaining Type Area Served

Built-up Roofing Gutters and Downspouts 2003 19 Flat Entire Building

3. Roof

Page: 12 of 64

Building: 0005 - CAFETERIA (VACANT)

INTERIOR FINISH

Ceramic Tile Concrete Quarry Tile Vinyl Tile

Exposed Structure Plaster

Metal Unit - Metal Frame

Mechanical Kitchen

Comments: Roof mounted exhaust fans exhaust the kitchen and dishwasher hoods. The packaged HVAC units supply make up air to the hoods. A wall mounted exhaust fan ventilates the large dry food storage room. Fly fans at dining and kitchen exterior doors prevent insects from entering the rooms.

Ventilation Area Served

VERTICAL CIRCULATION

None

Comments: There are two concrete steps at the northwest entrance and a 6" concrete curb at the southeast entrance that must be negotiated to enter the building.

Awning Units - Steel Frame; Single Glazing; Fixed - Steel Frame; Single Glazing;

Acoustical Tile Plaster

Exhaust Ventilation

Windows6. Asbestos: Yes

Floors1.

Interior Walls2.

3. Asbestos: Yes

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Two large, packaged, gas fired and air cooled HVAC units, located on grade heat the dining room and kitchen.

Comments:

HVAC

Heat1.

Gas-Fired Furnace

Single Duct None Electric Mechanical Economizer Dining Hall

Ventilation2.

Page: 13 of 64

Building: 0005 - CAFETERIA (VACANT)

Comments:

Cast-Iron Outdoor Cast-Iron

A contractor services the interceptor and removes the grease on a regular basis.

Hose Bibb Lavatory Sink Urinal Water Closet (Flush Valve)

Gas (Natural)

None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Dry Chemical

Comments: There is a wet chemical, fire suppression system in the kitchen hood above the grills and ovens. Code required fire extinguishers, type ABC in the dining room and food storage room and type K in the kitchen, were recently inspected, are operable and are properly tagged.

Copper Copper Gas-Fired None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Direct Expansion Refrigerant

Unit Package None Electric Mechanical - Natural

Economizer Dining Hall

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Two large, 20 tons estimated, packaged, gas fired and air cooled HVAC units, located on grade cool the dining room and kitchen.

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

3. Air Conditioning

Location UL300 Compliance Status Unknown

Comments: The kitchen was not accessible during the January 2012 Facility Survey.The kitchen equipment has not been inspected since August 2005 (Hurricane Katrina).

UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION

Page: 14 of 64

Building: 0005 - CAFETERIA (VACANT)

Comments: The service entrance size is 400A.

FIRE ALARM

Comments: The fire alarm panel is a Fire Control Instrument SNAC control panel. The panel is connected to the central annunciator panel located in the facility manager's office in Building 1.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control Panel Duct Smoke Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm

Connected to Main System None None None

Telephone Security Public Address Television

Comments: The recorded footcandle level includes natural light contribution. Lighting fixtures in the cafeteria are a mix of fluorescent and incandescent.

High Intensity Discharge (HID)

T12 - Fluorescent

T12 - Fluorescent

T12 - Fluorescent

Food Preparation

Storage/Warehouse-Active

Offices

Area Recommended Level

Recorded Level Light Type

Battery Backup Battery Backup

Main Disconnect Switch 120/208V, 3-Phase, 4-Wire Panelboard Receptacles, Switches, None

Emergency Exit

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

COMMUNICATION

Electric Water Gas No NoNo

Page: 15 of 64

Building: 0005 - CAFETERIA (VACANT)

GENERAL BUILDING CONDITION

Rating

Comments:

X

Good Fair Poor

The facility has sustained severe storm damage, is vacant and is deteriorating.

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

BUILDING 8 GUARD HOUSEBUILDING 8 - GUARD HOUSE

Page: 16 of 64

Building: 0008 - GUARD HOUSE

BUILDING ENVELOPE

Foundation RoofBuilding

Wood Wood Wood

Metal Siding

Wall Roof Unknown Unknown

Metal Unit - Wood Frame

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Business 80 65 1 Owned 2012 Unevaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

No

No

N/A

N/A

N/A

No

No

N/A

N/A

N/A

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Exterior Doors5.

Material Drainage Year Life

Remaining Type Area Served

Metal Surface Run-off 2012 40 Gable Entire Building

3. Roof

Page: 17 of 64

Building: 0008 - GUARD HOUSE

INTERIOR FINISH

Vinyl Tile

Drywall

None

Natural Entire Building

Ventilation Area Served

VERTICAL CIRCULATION

None

Single Hung - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Single Glazing;

Packaged Heat Pump (Air

Source)

Through-The- Wall Unit

None Electric Natural None Entire Building

Gypsum Board

Exhaust Ventilation

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

HVAC

Heat1.

Packaged Heat Pump (Air

Source)

Through-The- Wall Unit

None Electric Natural None Entire Building

Ventilation2.

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Page: 18 of 64

Building: 0008 - GUARD HOUSE

None None None

None

None

None None ABC Type Fire Extinguisher

Comments: Service is provided from a 100A circuit breaker at the main distribution panel located at Module Building M-0002 to a 100A MCB loadcenter.

None None None None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Compact Fluorescent Fluorescent

Comments: Linear fluorescents are controlled by a light switch. CFL light fixtures are controlled by a motion sensor.

T8 - Fluorescent35Offices 50

Area Recommended Level

Recorded Level Light Type

Battery Backup Battery Backup

Main Loadcenter 120/208V, 1-Phase, 3 Wire Branch Panel Only Receptacles, Switches

Sprinkler System Stand Pipe System Fire Suppression

Emergency Exit

PLUMBING

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

ELECTRICAL SERVICES

Exterior Lighting1.

Interior Lighting2.

Emergency /Exit Lighting3.

Page: 19 of 64

Building: 0008 - GUARD HOUSE

FIRE ALARM

Comments: Intercom station is located at the security station to communicate with the intercom station at the gate.

None

Connected to Main System None None None

Telephone Security Public Address Television

GENERAL BUILDING CONDITION

Rating X Good

Fair Poor

COMMUNICATION

The facility condition is not impacting the functional use of the facility.

The facility condition IS impacting the functional use of the facility.

The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.

Electric Water Gas N/A N/AZone

Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good

BUILDING 9 FAC MAINT PROPERTY WHSE & VOC STORAGEBUILDING 9 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE

Page: 20 of 64

Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE

BUILDING ENVELOPE

Foundation RoofBuilding

Concrete Loadbearing Masonry Wood

CMU Masonry Wood Siding

Comments: The building exterior is predominately CMU but has wood siding at the gables.

Wall Roof None None

AccessibilityFeature

GSF NSF Year Built Use Group Historic Ownership#Floors

Storage 7,211 6,219 1 Owned 1996 Unevaluated

REAL ESTATE

Access to Building

Ramps

Entrance

2nd Egress

Visual Alarm

Corridor/Aisle

Rooms

Stairs

Elevator

Restrooms

Drinking Fountain

Telephone

Yes

N/A

Yes

Yes

Yes

N/A

Yes

N/A

N/A

No

Yes

N/A

ACCESSIBILITY

Structural Systems1.

Exterior Walls2.

Insulation4.

Material Drainage Year Life

Remaining Type Area Served

Asphalt Shingles

Asphalt Shingles

Gutters and Downspouts

Surface Run-off

Gable

Gable

Maintenance Shop Wing

Warehouse Wing

3. Roof

Page: 21 of 64

Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE

INTERIOR FINISH

Concrete Vinyl Tile

CMU Drywall

Wood Unit - Metal Frame Wood Unit - Wood Frame

Mechanical Restroom

Ventilation Area Served

VERTICAL CIRCULATION

None

Metal Overhead - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame

None

Acoustical Tile Gypsum Board

Exhaust Ventilation

Exterior Doors5.

Windows6.

Floors1.

Interior Walls2.

3.

Interior Doors4.

Heat Source

Heat Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

There are two air handling units (Carrier #40RM007B611GC, built 6/2003) with heaters on the discharge, one serving the maintenance shop and one serving the west wing of the building.

This is a pad-mounted packaged unit (Carrier, built 6/2009).

Comments:

Comments:

HVAC

Heat1.

Electric Resistance

Electric Resistance

Single Duct

Single Duct

None

None

Electric

Electric

Mechanical

Natural

None

None

Storage

Storage

Page: 22 of 64

Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE

A point-of use electric, domestic water heater above the restrooms' ceiling provides domestic hot water to the lavatories.

Comments:

Cast Iron None None

Hose Bibb Lavatory Water Closet (Tank)

None

None None ABC Type Fire Extinguisher

Copper Copper Electric None No

Hot Water Cold Water Water Heater Water Treatment HW Storage Tank

Grease InterceptorWaste / Vent Interior Storm

Split Direct Expansion (Air

Cooled)

Packaged Direct

Expansion (Air Source)

Single Duct

Single Duct

Refrigerant

None

Electric

Electric

Mechanical

Natural

None

None

Storage

Storage

Sprinkler System Stand Pipe System Fire Suppression

PLUMBING

Two air handling units (Carrier #40RM007B611GC, built 6/2003) provide cooling by two condensing units (Carrier, 6 ton, built 7/2003), one serving the maintenance shop and one serving the west wing of the building.

This is a pad-mounted packaged unit (Carrier, 3 ton, built 6/2009).

Comments:

Comments:

System Type

Air Distribution

Piping System

Control System

Fresh Air Intake

Energy Conservation

Measure

Area Served

Water Distribution1.

Sanitary Distribution2.

Fixtures3.

Fuel Distribution4.

FIRE PROTECTION

Page: 23 of 64

Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE

Comments: Overhead service is provided from a 3x25 kVA utility-owned, pole-mounted transformer bank located west of the building. Service enters to a 250A MCB main panelboard located on the west building exterior wall.

The secondary utility meter for this building is located adjacent to the panel. The panel serves one 100A MLO panel (from a 100A CB) located in the electrical classroom, serving the electrical classroom and the maintenance shop, and one 100A MLO loadcenter located in the maintenance shop and serving the warehouse area, two AHU units (from (2) 100A CB), two CU units (from (2) 40A CB) and one HVAC unit (from a 30A CB). The electrical classroom also houses a 100A dedicated panel utilized for the mock-up area.

FIRE ALARM

Comments: The fire alarm panel is a Gamewell 7100 series conventional fire alarm control panel, located in the maintenance shop office.

Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices

Audible Alarm Control/Annunciator Panel Exterior Audib/Visual Alarm Manual Pull Station Smoke Detector Visual Alarm

Comments: Recorded footcandle levels include natural light contribution.

Comments: Selected industrial type fluorescent lights with emergency ballasts are utilized in the electrical classroom. Battery backup emergency lights are utilized in the storage areas and in the maintenance shop.

High…