GulfportGulfport
Job Corps Center Gulfport, MS
Facility Planning ReportFacility Planning Report Volume II
Supporting Data
Fi lFinal June 2012
Department of Labor/ Office of Job Corps
22Gulfport Job Corps Center
GulfportGulfport
Job Corps Center Gulfport, MS
Facility Planning ReportFacility Planning Report Volume II
Supporting Data
Fi lFinal June 2012
View of central circulation spine between the modular buildings
33 Gulfport Job Corps Center
CONTENTS
GULFPORT JOB CORPS CENTER
FACILITY PLANNING REPORT
VOLUME I - Planning Strategy
• Existing Site Plan
• Center Statistics
INTRODUCTION
• Purpose
• Report Contents
EXECUTIVE SUMMARY
A. EXISTING CONDITIONS
• Background
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Ownership
• Facility Assessment by Function
• Energy
• Environmental Issues
• Sustainability
• Accessibility Standards
• Completed and Current Projects Since the Last Survey
• Health and Life Safety Issues
• Summary of Defi ciencies
B. RECOMMENDATIONS
• Status of the Previous (PY08) Plan
• Signifi cant Issues
• PY 11 Plan Overview
• Summary of Proposed Projects
• Regional Projects
• Proposed Near Term Site Plan
• Proposed Long Term Site Plan
C. PLANNING ANALYSIS
• Purpose
• Planning Objectives and Assumptions
• Space Utilization Analysis
• Federal Real Property Asset Management
• Mission Dependency Site Plan
• Defi ciency Analysis
• Facility Condition Summary Report
• Building Condition by Function
• Building Condition Site Plan
VOLUME II - Supporting Data
• Vicinity Map
• Location Map
• Existing Site Plan
D. DESCRIPTIONS
• Building and Structures
• Space Utilization By Function
• NSF by Building
• Energy Report
• Environmental Management
Asbestos Report Radon Report
• Site Descriptions
• Building Descriptions
E. DEFICIENCIES
F. CORRESPONDENCE AND REPORTS
• Center Review Meeting Minutes
• Survey Brief
• RA and Student Facility Feedback Questionnaire
• Life Safety Defi ciencies Transmittal and List
• O & M Defi ciency List
• Active Warranty Report
• FRPC Performance Measures Matrix
66Gulfport Job Corps Center
44Gulfport Job Corps Center
55 Gulfport Job Corps Center
77 Gulfport Job Corps Center
D Descriptions
BUILDINGS AND STRUCTURES
00411 GULFPORT 06/22/2012
1Page: of Date:
0001 - MAIN BUILDING (VACANT)
0002 - GYMNASIUM (VACANT)
0005 - CAFETERIA (VACANT)
0008 - GUARD HOUSE
0009 - FAC. MAINT., PROPERTY WHSE.
& VOC. STORAGE
0010 - FEMALE DORMITORY
M-0001 - ADMINISTRATION MODULAR -
#1
M-0002 - ADMINISTRATION MODULAR -
#2
M-0003 - WELLNESS CENTER - #3
M-0004 - DINING/KITCHEN - CAFETERIA
- #4
M-0005 - EDUCATION - #5
M-0006 - SOFT VOCATION
M-0007 - CPP
M-0008 - SOFT VOCATION - #8
0006 - DUMPSTER SHELTER
0007 - STORAGE
Name GSF
35,520 15,000 6,820
7,211
15,607 1,440
1,440
1,440 4,464
3,024 3,024
Active Active Active Active Active
Active Active
Active
Active Active
Active Active Active Active Active Active
StatusType
Building Building Building Building Building
Building Building
Building
Building Building
Building Building Building Building Structure Structure
Use Group Built Flrs Const
Multiple Func Assembly Assembly Business Storage
Residential Business
Business
Business Assembly
Business Business Business Business Utility/Misc.
Storage
Poor Poor Poor Good Good
Good Good
Good
Good Good
Good Good Good Good Good Good
ConditionAsset Number
0041100002 0041100003 0041100006 0041108105 0041100010
0041100011 0041108095
0041108096
0041108097 0041108098
0041108099 0041108100 0041108101 0041108102 0041108104 0041108103
14 96,990
2 320
16 97,310
Buildings
Structures
Total
GSF
GSF
GSF
Summary
06/22/2012
Space Utilization By Function 00411 Gulfport Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 68 Non Residents 68
136Total Students
(68)
(136)
(136)
(136)
(136)
(136)
DIFFERENCE
6,800
6,420
1,088
4,420
2,720
9,500
9,588
4,018
1,224
2,769
Lounge Other Shower/Toilet Sleeping Storage
Academic (136) Non-Academic
24 -- Electrical + 25 -- Medical Assistant 25 -- Medical Office Support 25 -- Nursing Assistant +
Dining (2 Servings)
Recreation Room
Medical/Dental
Administration
7.3
1,320
1,110 5,980
3,042 2,624
1,568
4,018
1,224
2,769
4,896
1,360 1,360
1,200
1,000
1,088
2,720
1,084
-283
1,682 1,264
-150
2,930
Vocations
RESIDENT
NON-RESIDENT
(68)
(68) 15
50 3,400 1,020
2,700
3,168
2,930
-3,930
06/22/2012
Space Utilization By Function 00411 Gulfport Page: 2 of Date:
STORAGE/SUPPORT
VACANT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
TOTAL 185.01 25,161 73,099
(136)
(0)
DIFFERENCE
96,990
0.75
TOTAL GSF
NET TO GROSS RATIO
2,720
4,395
41,115
Operations & Maintenance Warehouse
Vacant
2,000 2,395
41,115
1,088 1,632
1,675
41,115
47,938
Net Square Footage By Building Date: 06/22/2012 Page: 1
Center: GULFPORT (00411) of 2
HOUSING
EDUCATION
FOOD SERVICE
RECREATION
Sleeping
Lounge
Storage
Shower/Toilet
Other
Academic
Electrical
Medical Assistant
Non-Academic
Nursing Assistant
Medical Office Support
Dining (2 Servings)
Recreation Room
Function Suggested NSF
5,980
1,320
1,110
2,722
1,568
4,018
0010 - FEMALE DORMITORY
0010 - FEMALE DORMITORY
0010 - FEMALE DORMITORY
0010 - FEMALE DORMITORY
0010 - FEMALE DORMITORY
0010 - FEMALE DORMITORY
M-0005 - EDUCATION - #5
0009 - FAC. MAINT., PROPERTY WHSE. & VOC
M-0006 - SOFT VOCATION
M-0007 - CPP
0010 - FEMALE DORMITORY
M-0006 - SOFT VOCATION
0010 - FEMALE DORMITORY
M-0006 - SOFT VOCATION
M-0008 - SOFT VOCATION - #8
M-0006 - SOFT VOCATION
M-0004 - DINING/KITCHEN - CAFETERIA - #4
0010 - FEMALE DORMITORY
Bldg Name Actual NSF Difference
5,980
1,320
1,110
3,042
1,568
2,624
4,018
Sub Total:
Sub Total:
Sub Total:
Sub Total:
9,500
9,588
4,018
4,896
1,360
1,200
1,360
1,000
1,088
6,800
6,420
1,088
4,420
1,084
-283
1,682
1,264
-150
2,930
2,700
3,168
2,930
-3,930
Net Square Footage By Building
Page: 2
Center: GULFPORT (00411) of 2
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
VACANT
Medical/Dental
Administration
Warehouse
Operations & Maintenance
Vacant
Function Suggested NSF
1,224
1,224
1,224
2,395
2,000
5,080 21,835 14,200
M-0003 - WELLNESS CENTER - #3
M-0002 - ADMINISTRATION MODULAR - #2
0009 - FAC. MAINT., PROPERTY WHSE. & VOC
M-0001 - ADMINISTRATION MODULAR - #1
0008 - GUARD HOUSE
0009 - FAC. MAINT., PROPERTY WHSE. & VOC
0009 - FAC. MAINT., PROPERTY WHSE. & VOC
0005 - CAFETERIA (VACANT)
0001 - MAIN BUILDING (VACANT)
0002 - GYMNASIUM (VACANT)
Bldg Name Actual NSF Difference
1,224
2,769
2,395
2,000
41,115
Sub Total:
Sub Total:
Sub Total:
Sub Total:
1,224
2,769
4,395
41,115
2,720
1,632
1,088
2,720
2,720
41,115
1,675
41,115
Energy Management Report Center: GULFPORT (00411)
Page: 1 Date: 06/22/2012 of 3
CENTER ENERGY DATA
None
ENERGY CONSUMPTION ASSESSMENT
61% 37,672
79,899 97,438
ENERGY USE BY FUEL TYPE
Energy Audit :
Date of Audit :
Electric Company :
Percent Change since Baseline Year :
Natural Gas Company :
Property Status :
N/A
Mississippi Power Company Center Point Energy Co.
Combination of Owned & Leased
742,594 2,534=
Total 3,236
MBtu
MBtu
Total $90,584 MBtu/ $27.993
BTU/GSF
BTU/GSF
BTU/GSF
Electricity
Natural Gas kWh
681 MCF = 702 MBtu
$84,998 $0.114= kWhElectricity
Natural Gas $5,586 = $8.203 MCF
ENERGY COST BY FUEL TYPE
COMMENTS
9/22/03 Adjusted Cf for gas.
8/1/2001 New LED installed in Gym, Filters & Belts changed, Security staff check for lights & PCs 2/5/01 EMCs - PM, filters, Security turns off lights
WATER CONSUMPTION ASSESSMENT
Percent Reduction Since Baseline Year:
1,000 Gallons
1,000 Gallons
FY 2011 Energy Goal:
Energy Goals are being met. Keed up the Good Work to further Reduce Energy Usage.
FY 2011 Energy Consumption:
Note: The Federal Government has set a goal of 3% Energy Consumption Reduction per year in EO 13423.
1,893
Further Reduction in Water Usage is needed to meet Water Reduction Goals.
Note: The Federal Government has set a goal of 2% Water Consumption Reduction per year in EO 13423.
FY 2011 Goal:
FY 2011 Water Consumption:
1,000 Gallons
FY 2003 Energy Baseline:
FY 2008 Baseline:
Page: 2 of 3
Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.
1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:
a. Turn it down (lights, heating & cooling),
b. Turn it off (lights, computers, other equipment),
c. Keep it tight (close doors and windows, use window blinds)
2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:
a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.
b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.
c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.
d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.
e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.
f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.
g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.
h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.
i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.
Page: 3 of 3
j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.
k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.
l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.
m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.
n. Caulk and fill cracks around doors and windows to reduce costly air leaks.
o. When replacing broken glass, use high transmittance, low heat gain windows.
p. Make sure automatic door closers are functioning properly to avoid drafts.
3. Buy energy efficient, buy EnergyStar (www.energystar.gov).
a. Buy EnergyStar appliances and equipment.
b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).
c. Replace broken thermostats with EnergyStar labeled programmable products.
d. Replace broken exit signs with EnergyStar LED exit signs.
Environmental Management Report
Page: 1 Date: 06/22/2012 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
No N/A
N/A No
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
N/A0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
Waste Management, Inc.
No N/A
N/A N/A N/A
N/A
No No
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
04/10/1992 Friable/Non-Friable Kevin Manuel 06/12/2003 Yes No
No No
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Asbestos-Containing Materials Inventory
Date: 06/22/2012Center : Gulfport (00411) Page: 1 of 1
Floor Finishes Ceiling Finishes Heating
Ceiling Finishes
Ceiling Finishes Roof Repair/Replacement Windows
Bldg System
Bldg System
Bldg System
Mastic beneath 12x12 tile Asbestos cement board Pipe fitting insulation
Asbestos cement board
Asbestos cement board Roof flashing Window caulking
Category Description
Category Description
Category Description
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Sq. Ft.
Lin. Ft.
Lin. Ft.
Location
Location
Location
Unit
Unit
Unit
Quantity
Quantity
Quantity
!st and 2nd floors 2nd floor Throughout
Under roof decking
Under roof decking Exterior of building Dining area
35000
12750
12500
Building :
Building :
Building :
0001 - MAIN BUILDING (VACANT)
0002 - GYMNASIUM (VACANT)
0005 - CAFETERIA (VACANT)
Radon
Page: 1 of 1
0001 - MAIN BUILDING (VACANT)
0002 - GYMNASIUM (VACANT)
0005 - CAFETERIA (VACANT)
0008 - GUARD HOUSE
0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STO
0010 - FEMALE DORMITORY
M-0001 - ADMINISTRATION MODULAR - #1
M-0002 - ADMINISTRATION MODULAR - #2
M-0003 - WELLNESS CENTER - #3
M-0004 - DINING/KITCHEN - CAFETERIA - #4
M-0005 - EDUCATION - #5
M-0006 - SOFT VOCATION
M-0007 - CPP
M-0008 - SOFT VOCATION - #8
Bldg Name
06/06/1990
06/06/1990
06/06/1990
Test Date
Yes
Yes
Yes
No
N/A
No
No
No
No
No
No
No
No
No
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description Gulfport
Aerial view of Gulfport Job Corps CenterAerial view of Gulfport Job Corps Center
Page: 1 Date: 06/22/2012 of 4
Comments:
Paving Type for Roads & Parking
The courtyard has brick pavers.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is fully enclosed by fencing. A significant portion of the site is fenced off to prevent entry to Buildings 1, 2, and 5 which have sustained severe storm damage from Hurricane Katrina in 2005 and are deteriorated. These buildings and site areas were not assessed as part of the January 2012 Facility Survey.
The site is very tight with limited room for expansion.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterCity of Gulfport Water DepartmentPublic Water Authority
None 0None
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 10None Municipal
The nearest fire station is Gulfport City Fire Department. There are two other fire stations located 10 miles away from the center.
Number of Deficiencies = 1SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures14 2Flat
Surrounding
Outdoor Recreation
Residential
Field
Front
Sides and Rear
Wrought Iron
Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Good Yes Good
Fencing
Other Features
Page: 2 Date: 06/22/2012 of 4
Sewage Treatment Flow
Utility
Publicly Owned Treatment Works
Utility
Gravity
Maintenance ResponsibilityOwnership
Comments: Center Point Energy Co. is the natural gas supplier.
Center Point Energy Co.
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 1
Drain Type On-Site Storm Water Management
Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes GoodCenter
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility Utility Yes Good
6. Central Plant: None
Page: 3 Date: 06/22/2012 of 4
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Mississippi Power Company
Overhead primary lines enter the site from 21st Street. The primary system is radial and is distributed on the center overhead and underground. The primary conductors dip underground at the power pole located near Gate House Building 8 to serve a 1000 kVA pad-mounted transformer providing for Modular Buildings M-0001 through M-0008 and at the power pole also located along 21st Street to serve a 500 kVA transformer providing for Dormitory Building B-10. The overhead primary lines continue to a 3x25 kVA pole-mounted transformer bank providing for Maintenance Building B-9. Modular Buildings M-0001 through M-0008 and Maintenance Building B-9 are provided with 120/208V, 3-phase, 4 wire services. The only 480/277V, 3-phase, 4 wire secondary service is provided to Dormitory Building 10. Buildings 9 and 10 have separate secondary utility meters, Modular Buildings M-0001 through M-0008 are measured as a zone. Modular Buildings M-0001, 02, 03, 05 and 06 are served from a 1000A MCB distribution panelboard and Modular Buildings M-0007, 8, and 4 are served from a 1200A MCB distribution panelboard, both located along the south exterior wall of Module M-0002. There are 2 motorized sliding gates (each motor 1.2 HP, 1-phase) at the entrance to the main center area and 3 motorized sliding gates at the remote parking (one gate currently in use) operated from Gate House Building 8. The gate facing 21st Street and the gate at the remote parking area stay open during normal business hours and are closed after hours. There is an air phone at the main center entrance (near Gate House Building 8) and the speaker at the power pole located on the centers side of the gate for after hours visitors.
Pole and Pad Utility
Utility Utility
No
22.86/13.20 kV, 3-Phase 4-wire
480/277 Volt, and 120/208 Volt, 3-Phase, 4 WireOverhead & Underground
Overhead & UndergroundPrimary Service
Secondary Service
Distribution Characteristics
Number of Deficiencies = 37. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
None
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building None
Photocell Photocell Photocell Photocell, Time Clock None
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Utility, Center Utility, Center Yes Good
Comments: Wall-mounted metal-halide fixtures at Modular Buildings M-0001 through M-0008 are controlled by a wall-mounted photocell located at the south wall of Administration Module M-0002. Wall-mounted lighting at Building 10 is controlled by time clock and roof-mounted photocell. Wall-mounted lighting at Building 9 is controlled by time clock.
Pole-mounted lighting (HPS flood and cobra-head lights) mounted on the utility poles, belonging to and maintained by the utility, are controlled by fixture-mounted photocells. There are no dedicated sport lights. The basketball hoop and surrounded area are illuminated by the wall-mounted and pole-mounted street lights. Modular Building lights are fed from a 100A MLO panel located at the south exterior wall of Modular Building M-0002. The panel is fed from a 1200A (modular) distribution panel.
ATS MTS
No No
Number of Deficiencies = 1
Metering Individual
Page: 4 Date: 06/22/2012 of 4
ACCESSIBILITY
Yes
NoNoYesNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Comments:
Telephone Company
On-site Line Owner
Overhead telephone lines dip underground at the power utility pole. (3) T1 communication lines, two for the internet and one for the VoIP enter the main server closet (MC) at Adm. Module M-0001. The MC is provided with
(3) routers Cisco 3800 series, a Cisco 6500 series switch utilized for phone and internet connectivity, (2) voice gateway units for Fax connection and a Blue Coat Proxy for security and WAN optimization. The equipment is connected to a UPS back-up system (Smart UPS 10kW) that provides power in case of an outage. Other buildings on the campus are connected to the MC by fiber (GCC 6F 62.5) for both data & voice communications.
Connections for data outlets in the buildings are provided by CAT 5E cable. The fire alarm (FA) system on center consists of stand-alone units. The required periodic FA system inspection was conducted by Fire Protection Security Safety Corp. ((228) 575-6275; fax-(228) 575-6273)) March 19, 2012. A CCTV system consists of 17 exterior and interior, building & pole mounted security cameras and a color monitor located at the security office at Dormitory Building 10. At Building B-10 there are 6 interior security cameras (a dome and a bullet security camera in each wing corridor, dome cameras, one in the laundry and one in the commons area), and 3 exterior security cameras (pentax zoom and bullet at the east exterior wall and pentax zoom at the entrance to the front porch).
There are 8 exterior security cameras throughout the center: two bullet cameras on Building 9, three at Modular Buildings M-0006, 5 and 4, pole-mounted pentax zoom camera located SE of the dorm, a pole-mounted bullet camera locater at the back of Modular M-0008 and a pole-mounted camera located at the remote parking lot.
Local cable is provided in Building 10 and in Modules M-0001 & 3. Magnetic door alarm provided at the west wing door at the dorm is monitored from the RA office. The panel is connected to all doors; the alarm at the east door was removed.
AT&T
Maint. Responsibility
Center Center
Surveillance CCTV with exterior and interior cameras and a monitor, door alarms
Earthquake Risk
Low Medium LowLow LowIBC Medium
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
A significant portion of the site is fenced off to prevent entry to Buildings 1, 2, and 5 which have sustained severe storm damage from Hurricane Katrina in 2005 and are deteriorated. These buildings and site areas were not assessed as part of the January 2012 Facility Survey.
HISTORIC PRESERVATION
9. Electrical (Communication/Alarm/Security)
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Yes
Stand-Alone
VOIP
System Capacity Adequate System Condition
GoodYes
Number of Deficiencies = 1
STORAGE TANKS: None
Fire Alarm Security
Building Descriptions and Utilities
BUILDING 1 MAIN BUILDINGBUILDING 1 - MAIN BUILDING
Building Descriptions
Page: 1 of 64
Building: 0001 - MAIN BUILDING (VACANT)
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry
Wall Roof Unknown Rigid
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Multiple Functions 35,520 21,835 2 Leased 1952 Unevaluated
Comments: The building has sustained severe storm damage from Hurricane Katrina in 2005. It is deteriorated and fenced off to prevent entry and was not assessed as part of the January 2012 Facility Survey. The information provided below is from the February 2004 Facility Survey:
Building is accessible at the main entrance on the south, the two east side entrances and at the double doors to the maintenance area on the north side. The building is not accessible from the two west side entrances. Corridor is not accessible between the three tiers. Second floor classrooms are not accessible.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
No
Yes
No
No
No
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material Drainage Year Life
Remaining Type Area Served
Built-up Roofing Gutters and Downspouts 1999 10 Flat Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 64
Building: 0001 - MAIN BUILDING (VACANT)
INTERIOR FINISH
Carpet Ceramic Tile Concrete Vinyl Tile
Ceramic Tile Drywall Exposed Structure Plaster Wood Paneling
Wood Unit - Wood Frame
Comments: The doors have vision panels.
VERTICAL CIRCULATION
Concrete Stairs
Comments: Six interior concrete stairs and one exterior steel stair. Both the ground and second floor have three tiers. The tiers are connected by a central corridor which has a stair consisting of 6 steps to transition the level change between tiers. The floors are connected by two stairs on the west side of the building adjacent to the transitioning stairs that connect the tiers.
Metal Unit - Metal Frame
Double Hung - Aluminum Frame; Double Glazing; Fixed - Steel Frame; Single Glazing;
Hopper - Steel Frame; Single Glazing;
Acoustical Tile Gypsum Board
Exterior Doors5.
Windows6.
Floors1. Asbestos: Yes
Interior Walls2.
3. Asbestos: Yes
Interior Doors4.
Ceilings
Page: 3 of 64
Building: 0001 - MAIN BUILDING (VACANT)
Mechanical/Natural Restroom
Comments: Wall mounted exhaust fans ventilate the main mechanical and electrical rooms. A fan located near the roof circulates room air in the maintenance storage room.
Ventilation Area Served
Chiller Units
Chiller
Fan Coil
Single Duct
Four-Pipe
Four-Pipe
Electric
Electric
Mechanical - Natural
Mechanical
None
None
Classrooms and Offices
Medical/Dental
Exhaust Ventilation
The air cooled chillers serve the entire building except for the maintenance/logistic areas. Ceiling mounted, chilled water, fan coil units cool the classrooms, offices and corridors. Floor mounted, chilled water, fan coils cool the outdoor entrances of the building.
A chilled water air handling unit (AHU) located in a small equipment room cools the interior rooms of the medical/dental area.
Comments:
Comments:
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Ceiling mounted, hot water, fan coil units heat the classrooms, offices and corridors. Floor mounted, hot water fan coils heat the outdoor entrances and the perimeter rooms of the medical/dental area.
A hot water air handling unit (AHU) located in a small equipment room heats the interior rooms of the medical/dental area.
Gas fired unit heaters heat the maintenance storage rooms and shops.
Comments:
Comments:
Comments:
HVAC
Heat1. Asbestos: Yes
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Gas-Fired
Fan Coil
Single Duct
Unit Heater
Four-Pipe
Four-Pipe
None
Electric
Electric
Electric
Mechanical - Natural
Mechanical
Natural
None
None
None
Classrooms and Offices
Medical/Dental
Storage
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
3. Air Conditioning
Page: 4 of 64
Building: 0001 - MAIN BUILDING (VACANT)
A gas-fired domestic water heater provides hot water to the medical/dental area. 8 electric water heaters, one per toilet, provide hot water to the toilet rooms. 1 electric water heater provides heat to the medical assistant classroom.
Comments:
Cast Iron None Cast Iron
Dental Sink Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Service Sink Shower/Bathtub Urinal Water Closet (Flush Valve) Water Closet (Tank)
Gas (Natural)
Wet Wet ABC Type Fire Extinguisher
Comments: Each of the three (3) janitor closets is equipped with a sprinkler head supplied from the domestic water system. The rest of the building is not sprinklered. Code required fire extinguishers, ABC type, inspected recently, operable and properly tagged are located throughout the building.
Comments: The switchgear size is 1800A with a 500 KVA step-down transformer, providing the 120/208 Volt, 3-phase, 4-wire system.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Main Disconnect Switch 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
LIGHTING
Page: 5 of 64
Building: 0001 - MAIN BUILDING (VACANT)
FIRE ALARM
Comments: The fire alarm panel is a Fire Control Instrument 7200 Series control/annunciator panel, located in the electrical room and the remote control annunciator is located in the first floor corridor. Also, a central annunciator panel is located in the facility manager's office.
Comments: Public phones are provided for students.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Connected to Main System Closed Circuit TV Connected to Main System None
Telephone Security Public Address Television
Comments: The recorded footcandle level includes natural light contribution.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Classrooms
Medical/Dental
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
GENERAL BUILDING CONDITION
Rating
Comments:
X
Good Fair Poor
The facility has sustained severe storm damage, is vacant and is deteriorating.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoNo
BUILDING UTILITY METERING
Structure: Poor Exterior: Poor Interior: Poor Mechanical: Poor Electrical: Poor
BUILDING 2 GYMNASIUMBUILDING 2 - GYMNASIUM
Page: 6 of 64
Building: 0002 - GYMNASIUM (VACANT)
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry
Wall Roof None Rigid
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Assembly 15,000 14,200 1 Leased 1952 Unevaluated
Comments: The building has sustained severe storm damage from Hurricane Katrina in 2005. It is deteriorated and fenced off to prevent entry and was not assessed as part of the January 2012 Facility Survey.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
Yes
No
Yes
N/A
No
No
No
N/A
No
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Built-up Roofing Gutters and Downspouts 1999 10 Flat Entire Building
3. Roof
Page: 7 of 64
Building: 0002 - GYMNASIUM (VACANT)
Comments: There are also glass block assemblies on the mezzanine and in the gymnasium.
INTERIOR FINISH
Ceramic Tile Concrete Wood
Comments: There is parquet flooring in the gymnasium.
Ceramic Tile Drywall
Metal Unit - Metal Frame Wood Unit - Wood Frame
VERTICAL CIRCULATION
Concrete Stairs
Comments: There are wood stairs to the mezzanine and concrete stairs to the basement.
Awning Unit - Steel Frame; Single Glazing; Hopper - Steel Frame; Single Glazing;
Acoustical Tile Exposed structure Gypsum Board
Windows6.
Floors1.
Interior Walls2.
3. Asbestos: Yes
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
The packaged gas-fired HVAC unit located on grade at the east wall heats the gymnasium and mezzanine areas.
Two gas-fired furnaces heat the counselor and security manager's offices, the mezzanine and the women in community service (WICS) office. They are located in small equipment rooms adjacent on the upper levels of the mezzanine.
A gas-fired unit heater heats the arts and crafts room.
Comments:
Comments:
Comments:
HVAC
Heat1.
Packaged Gas- Fired Furnace
Gas-Fired Furnace
Gas-Fired unit Heater
Single Duct
Single Duct
Unit Ventilator
None
None
None
Electric
Electric
Electric
Mechanical - Natural
Mechanical - Natural
Mechanical - Natural
Economizer
None
None
Recreation Area
Offices
Classrooms
Page: 8 of 64
Building: 0002 - GYMNASIUM (VACANT)
Mechanical Restroom
Comments: A wall mounted exhaust fan ventilates the weight room. Another wall mounted exhaust fan ventilates the kiln room.
The gas-fired domestic water heater does not work and has not been repaired or replaced. There is no domestic hot water supply in this building.
Comments:
Cast-Iron None None
Electric Water Cooler Hose Bibb Kitchen Sink Lavatory Service Sink Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Air-cooled Packaged Unit
Split Direct Expansion (Air
Cooled)
Direct Expansion Refrigerant
Single Duct
Single Duct
Window Unit
None
Refrigerant
None
Electric
Electric
Electric
Mechanical - Natural
Natural
Mechanical - Natural
Economizer
None
None
Gymnasium
Offices
Classrooms and Offices
PLUMBING
Exhaust Ventilation
An air-cooled, packaged HVAC unit located on grade at the east wall, cools the gymnasium and bleacher areas.
Two, split system, air cooled HVAC units cool the counselor and security manager's offices, the mezzanine and the women in community service (WICS) office. They are located in small equipment rooms on the upper levels of the mezzanine.
Window air conditioning units serve the security office, aerobic and female weight room, computer room, recreation supervisor's office, arts and crafts room, and storage room (the former snack bar room.).
Comments:
Comments:
Comments:
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
Page: 9 of 64
Building: 0002 - GYMNASIUM (VACANT)
N/A None ABC Type Fire Extinguisher
Comments: Code required fire extinguishers, ABC type, recently inspected and operable and properly tagged are located in the building.
Comments: The panelboard located in this building is fed from Building 1.
FIRE ALARM
Comments: The fire alarm panel is a Fire Control Instrument, SNAC, control panel, and is connected to the central annunciator panel located in the facility manager's office in Building 1.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control Panel Duct Smoke Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Connected to Main System None None None
Telephone Security Public Address Television
Comments: The recorded footcandle level includes natural light contribution.
Fluorescent
High Intensity Discharge (HID)
T12 - Fluorescent
T12 - Fluorescent
Recreation
Offices
Storage/Warehouse-Active
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Disconnect Switch 120/208V, 3-Phase, 4-Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Electric Water Gas No NoNo
Page: 10 of 64
Building: 0002 - GYMNASIUM (VACANT)
GENERAL BUILDING CONDITION
Rating
Comments:
X
Good Fair Poor
The facility has sustained severe storm damage, is vacant and is deteriorating.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
BUILDING 5 CAFETERIABUILDING 5 - CAFETERIA
Page: 11 of 64
Building: 0005 - CAFETERIA (VACANT)
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Structural Steel Steel
Brick Masonry
Wall Roof None Rigid
Metal Unit - Metal Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Assembly 6,820 5,080 1 Leased 1952 Unevaluated
Comments: The building has sustained severe storm damage from Hurricane Katrina in 2005. It is deteriorated and fenced off to prevent entry and was not assessed as part of the January 2012 Facility Survey.
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
No
No
Yes
No
Yes
Yes
Yes
No
N/A
No
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material
Asbestos: Yes
Drainage Year Life
Remaining Type Area Served
Built-up Roofing Gutters and Downspouts 2003 19 Flat Entire Building
3. Roof
Page: 12 of 64
Building: 0005 - CAFETERIA (VACANT)
INTERIOR FINISH
Ceramic Tile Concrete Quarry Tile Vinyl Tile
Exposed Structure Plaster
Metal Unit - Metal Frame
Mechanical Kitchen
Comments: Roof mounted exhaust fans exhaust the kitchen and dishwasher hoods. The packaged HVAC units supply make up air to the hoods. A wall mounted exhaust fan ventilates the large dry food storage room. Fly fans at dining and kitchen exterior doors prevent insects from entering the rooms.
Ventilation Area Served
VERTICAL CIRCULATION
None
Comments: There are two concrete steps at the northwest entrance and a 6" concrete curb at the southeast entrance that must be negotiated to enter the building.
Awning Units - Steel Frame; Single Glazing; Fixed - Steel Frame; Single Glazing;
Acoustical Tile Plaster
Exhaust Ventilation
Windows6. Asbestos: Yes
Floors1.
Interior Walls2.
3. Asbestos: Yes
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Two large, packaged, gas fired and air cooled HVAC units, located on grade heat the dining room and kitchen.
Comments:
HVAC
Heat1.
Gas-Fired Furnace
Single Duct None Electric Mechanical Economizer Dining Hall
Ventilation2.
Page: 13 of 64
Building: 0005 - CAFETERIA (VACANT)
Comments:
Cast-Iron Outdoor Cast-Iron
A contractor services the interceptor and removes the grease on a regular basis.
Hose Bibb Lavatory Sink Urinal Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Dry Chemical
Comments: There is a wet chemical, fire suppression system in the kitchen hood above the grills and ovens. Code required fire extinguishers, type ABC in the dining room and food storage room and type K in the kitchen, were recently inspected, are operable and are properly tagged.
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Direct Expansion Refrigerant
Unit Package None Electric Mechanical - Natural
Economizer Dining Hall
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Two large, 20 tons estimated, packaged, gas fired and air cooled HVAC units, located on grade cool the dining room and kitchen.
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
3. Air Conditioning
Location UL300 Compliance Status Unknown
Comments: The kitchen was not accessible during the January 2012 Facility Survey.The kitchen equipment has not been inspected since August 2005 (Hurricane Katrina).
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 14 of 64
Building: 0005 - CAFETERIA (VACANT)
Comments: The service entrance size is 400A.
FIRE ALARM
Comments: The fire alarm panel is a Fire Control Instrument SNAC control panel. The panel is connected to the central annunciator panel located in the facility manager's office in Building 1.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control Panel Duct Smoke Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Connected to Main System None None None
Telephone Security Public Address Television
Comments: The recorded footcandle level includes natural light contribution. Lighting fixtures in the cafeteria are a mix of fluorescent and incandescent.
High Intensity Discharge (HID)
T12 - Fluorescent
T12 - Fluorescent
T12 - Fluorescent
Food Preparation
Storage/Warehouse-Active
Offices
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Disconnect Switch 120/208V, 3-Phase, 4-Wire Panelboard Receptacles, Switches, None
Emergency Exit
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
COMMUNICATION
Electric Water Gas No NoNo
Page: 15 of 64
Building: 0005 - CAFETERIA (VACANT)
GENERAL BUILDING CONDITION
Rating
Comments:
X
Good Fair Poor
The facility has sustained severe storm damage, is vacant and is deteriorating.
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
BUILDING 8 GUARD HOUSEBUILDING 8 - GUARD HOUSE
Page: 16 of 64
Building: 0008 - GUARD HOUSE
BUILDING ENVELOPE
Foundation RoofBuilding
Wood Wood Wood
Metal Siding
Wall Roof Unknown Unknown
Metal Unit - Wood Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 80 65 1 Owned 2012 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
No
No
N/A
N/A
N/A
No
No
N/A
N/A
N/A
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5.
Material Drainage Year Life
Remaining Type Area Served
Metal Surface Run-off 2012 40 Gable Entire Building
3. Roof
Page: 17 of 64
Building: 0008 - GUARD HOUSE
INTERIOR FINISH
Vinyl Tile
Drywall
None
Natural Entire Building
Ventilation Area Served
VERTICAL CIRCULATION
None
Single Hung - Aluminum Frame; Double Glazing; Single Hung - Aluminum Frame; Single Glazing;
Packaged Heat Pump (Air
Source)
Through-The- Wall Unit
None Electric Natural None Entire Building
Gypsum Board
Exhaust Ventilation
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
HVAC
Heat1.
Packaged Heat Pump (Air
Source)
Through-The- Wall Unit
None Electric Natural None Entire Building
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 18 of 64
Building: 0008 - GUARD HOUSE
None None None
None
None
None None ABC Type Fire Extinguisher
Comments: Service is provided from a 100A circuit breaker at the main distribution panel located at Module Building M-0002 to a 100A MCB loadcenter.
None None None None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Compact Fluorescent Fluorescent
Comments: Linear fluorescents are controlled by a light switch. CFL light fixtures are controlled by a motion sensor.
T8 - Fluorescent35Offices 50
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Loadcenter 120/208V, 1-Phase, 3 Wire Branch Panel Only Receptacles, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3.
Page: 19 of 64
Building: 0008 - GUARD HOUSE
FIRE ALARM
Comments: Intercom station is located at the security station to communicate with the intercom station at the gate.
None
Connected to Main System None None None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas N/A N/AZone
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
BUILDING 9 FAC MAINT PROPERTY WHSE & VOC STORAGEBUILDING 9 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE
Page: 20 of 64
Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood
CMU Masonry Wood Siding
Comments: The building exterior is predominately CMU but has wood siding at the gables.
Wall Roof None None
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Storage 7,211 6,219 1 Owned 1996 Unevaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
N/A
Yes
N/A
N/A
No
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Material Drainage Year Life
Remaining Type Area Served
Asphalt Shingles
Asphalt Shingles
Gutters and Downspouts
Surface Run-off
Gable
Gable
Maintenance Shop Wing
Warehouse Wing
3. Roof
Page: 21 of 64
Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE
INTERIOR FINISH
Concrete Vinyl Tile
CMU Drywall
Wood Unit - Metal Frame Wood Unit - Wood Frame
Mechanical Restroom
Ventilation Area Served
VERTICAL CIRCULATION
None
Metal Overhead - Metal Frame Metal Unit - Metal Frame Storefront - Storefront Frame
None
Acoustical Tile Gypsum Board
Exhaust Ventilation
Exterior Doors5.
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
There are two air handling units (Carrier #40RM007B611GC, built 6/2003) with heaters on the discharge, one serving the maintenance shop and one serving the west wing of the building.
This is a pad-mounted packaged unit (Carrier, built 6/2009).
Comments:
Comments:
HVAC
Heat1.
Electric Resistance
Electric Resistance
Single Duct
Single Duct
None
None
Electric
Electric
Mechanical
Natural
None
None
Storage
Storage
Page: 22 of 64
Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE
A point-of use electric, domestic water heater above the restrooms' ceiling provides domestic hot water to the lavatories.
Comments:
Cast Iron None None
Hose Bibb Lavatory Water Closet (Tank)
None
None None ABC Type Fire Extinguisher
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Cooled)
Packaged Direct
Expansion (Air Source)
Single Duct
Single Duct
Refrigerant
None
Electric
Electric
Mechanical
Natural
None
None
Storage
Storage
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Two air handling units (Carrier #40RM007B611GC, built 6/2003) provide cooling by two condensing units (Carrier, 6 ton, built 7/2003), one serving the maintenance shop and one serving the west wing of the building.
This is a pad-mounted packaged unit (Carrier, 3 ton, built 6/2009).
Comments:
Comments:
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
Page: 23 of 64
Building: 0009 - FAC. MAINT., PROPERTY WHSE. & VOC. STORAGE
Comments: Overhead service is provided from a 3x25 kVA utility-owned, pole-mounted transformer bank located west of the building. Service enters to a 250A MCB main panelboard located on the west building exterior wall.
The secondary utility meter for this building is located adjacent to the panel. The panel serves one 100A MLO panel (from a 100A CB) located in the electrical classroom, serving the electrical classroom and the maintenance shop, and one 100A MLO loadcenter located in the maintenance shop and serving the warehouse area, two AHU units (from (2) 100A CB), two CU units (from (2) 40A CB) and one HVAC unit (from a 30A CB). The electrical classroom also houses a 100A dedicated panel utilized for the mock-up area.
FIRE ALARM
Comments: The fire alarm panel is a Gamewell 7100 series conventional fire alarm control panel, located in the maintenance shop office.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Exterior Audib/Visual Alarm Manual Pull Station Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
Comments: Selected industrial type fluorescent lights with emergency ballasts are utilized in the electrical classroom. Battery backup emergency lights are utilized in the storage areas and in the maintenance shop.
High…