Paul_Simon_Fac_Surv_vol_2_4-16-14.pdf
PDF 4 MB Posted
- Attached to
- Operations of the Paul Simon Job Corps Center
- Solicitation number
- DOL12RA20002
About this file
Facility Planning Report Attachment 1
View the file
Other files
| File | Type | Posted |
|---|---|---|
| milesage_report_2-15-15.pdf | ||
| AMENDMENT_03.rtf | RTF text file | |
| Amendment_0002.pdf | ||
| Copy_of_Paul_Simon_Center_DOL_Comp_PY10_and_Beyond_Rev2014.xls | XLS spreadsheet | |
| Amendment_0001.pdf | ||
| Paul_Simon_MasterPropertyRpt2.pdf | ||
| Paul_Simon_Fac_Surv_vol_1_4-16-14.pdf | ||
| PS2014StaffingPlan.docx | DOCX document | |
| Paul_Simon_Center__FINAL_1-13-2015_(4)_(2).docx | DOCX document | |
| Paul_Simon_PropertySummaryRpt1.pdf | ||
| Energy_Report.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Paul Simon
Job Corps Center Chicago, IL
Facility Planning Report Volume II
Supporting Data
Final March 2013
Department of Labor/ Office of Job Corps
22Paul Simon Job Corps Center
Paul Simon
Job Corps Center Chicago, IL
Facility Planning Report Volume II
Supporting Data
Final March 2013
South Dormitory Building 5 and Cafeteria Building 2
33 Paul Simon Job Corps Center
CONTENTS
PAUL SIMON JOB CORPS CENTER
FACILITY PLANNING REPORT
VOLUME I - Planning Strategy
• Existing Site Plan
• Center Statistics
INTRODUCTION
• Purpose
• Report Contents
EXECUTIVE SUMMARY
A. EXISTING CONDITIONS
• Background
• General Site Conditions
• General Building Conditions
• Preventive Maintenance
• Ownership
• Facility Assessment by Function
• Energy
• Environmental Issues
• Sustainability
• Accessibility Standards
• Health and Life Safety Issues
• Summary of Defi ciencies
B. RECOMMENDATIONS
• Status of the Previous (PY09) Plan
• Signifi cant Issues
• PY 12 Plan Overview
• Summary of Proposed Projects
• National Projects
• Regional Projects
• Proposed Site Plan
• Implementation Plan
• Summary of National Projects
• Project Data Sheets
C. PLANNING ANALYSIS
• Purpose
• Planning Objectives and Assumptions
• Space Utilization Analysis
• Federal Real Property Asset Management
• Mission Dependency Site Plan
• Defi ciency Analysis
• Facility Condition Summary Report
• Building Condition by Function
• Building Condition Site Plan
VOLUME II - Supporting Data
• Vicinity Map
• Location Map
• Existing Site Plan
D. DESCRIPTIONS
• Buildings and Structures
• Space Utilization By Function
• NSF by Building
• Energy Management Report
• Environmental Management
Radon Report
• Site Descriptions
• Building Descriptions
E. DEFICIENCIES
F. CORRESPONDENCE AND REPORTS
• Center Review Meeting Minutes
• Survey Brief
• RA and Student Facility Feedback Questionnaire
• Life Safety Defi ciencies Transmittal and List
• O & M Defi ciency List
• Active Warranty Report
• FRPC Performance Measures Matrix
44Paul Simon Job Corps Center
55 Paul Simon Job Corps Center
Paul Sim on Job C orps C enter
77 Paul Simon Job Corps Center
D Descriptions
BUILDINGS AND STRUCTURES
00512 PAUL SIMON 03/26/2013
1Page: of Date:
0001 - ADMINISTRATION/MEDICAL-
DENTAL
0002 -CAFETERIA
0003 - WEST DORMITORY
0004 - NORTH DORMITORY
0005 - SOUTH DORMITORY
0006 - EDUCATION
0007 - PHYSICAL FITNESS
0008 - MAINTENANCE/WAREHOUSE
0009 - VOCATION
0010 - PUMP HOUSE
0011 - CHILD DEVELOPMENT CENTER
PV-1 - PAVILION
PV-2 - PAVILION
SB-1 - VOCATION/MOTOR POOL
STORAGE
SB-2 - PROPERTY STORAGE
SB-4 - VOCATIONAL STORAGE
SB-5 - PAINTING VOCATION STORAGE
Name GSF
13,447
11,937 16,110 29,644 29,644 24,245 17,348 7,440
17,860
5,200
2,384
1,500
Active
Active Active Active Active Active Active Active Active Active Active Active Active Active
Active Active Active
StatusType
Building
Building Building Building Building Building Building Building Building Building Building Structure Structure Structure
Structure Structure Structure
Use Group Built Flrs Const
Business
Assembly Residential Residential Residential Business Assembly Storage Business Utility/Misc.
Day Care Assembly Assembly Storage
Storage Storage Storage
Good
Good Good Good Good Good Good Good Good Good Good Good Good Good
Good Good Good
ConditionAsset Number
0051208144
0051208145 0051208146 0051208147 0051208148 0051208149 0051208150 0051208151 0051208152 0051208153 0051208159 0051208157 0051208158 0051208154
0051208155 0051208160 0051208161
11 173,660
6 6,492
17 180,152
Buildings
Structures
Total
GSF
GSF
GSF
Summary
03/26/2013
Space Utilization By Function 00512 Paul Simon Page: 1 of Date:
HOUSING
EDUCATION
FOOD SERVICE
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
Resident Men Resident Women Total Residents
Residents 328 Non Residents 26
354Total Students
(328)
(354)
(354)
DIFFERENCE
32,800
25,580
6,372
47,345
35,980
10,030
Lounge Other Shower/Toilet Sleeping Storage
Academic (354) Non-Academic
32 -- ACT (Off-Ctr) 20 -- Bricklayer + 40 -- Carpentry + 30 -- Computer Service Tech.
30 -- Graphic Artist 60 -- Material Handler 30 -- Nursing Assistant + 60 -- Office Administration 20 -- Painting + 30 -- Pharmacy Tech +
Vocational Theory (140)
Dining (2 Servings) Food Preparation Food Storage
6,960 5,165 6,060
27,480 1,680
6,510 6,370
3,860 3,860 1,540
3,720
2,230 3,720
1,310
4,970 2,870 2,190
3,280
3,936 23,616
1,968
3,540 3,540
1,500 3,000
1,050 3,900 1,200 2,700 1,500 1,350
1,400
2,832 2,124 1,416
3,680
2,124 3,864
-288
2,970 2,830
2,360 -90
-180 -250 -470
2,220 -400
-90
2,138
Vocations
14,545
10,400
3,658
03/26/2013
Space Utilization By Function 00512 Paul Simon Page: 2 of Date:
RECREATION
MEDICAL/DENTAL
ADMINISTRATION
STORAGE/SUPPORT
SUGGESTED
NSF/
ENROLLEE
SUGGESTED
TOTAL
NSF
ACTUAL
TOTAL
NSF
TYPE OF SPACE
SUB TOTAL
SUB TOTAL
SUB TOTAL
SUB TOTAL
TOTAL 285.23 100,972 129,509
(354)
(354)
(354)
(354)
DIFFERENCE
173,660
0.75
TOTAL GSF
NET TO GROSS RATIO
16,790
2,070
10,280
7,080
15,710
3,030
10,290
7,124
Aerobics/Exercise Arts & Crafts Canteen Computer Lab Gymnasium Meeting Room Music Hall Pool Hall Recreation Hall Recreation Office Recreation Storage Theater Women's Exercise Room
Medical/Dental
Administration Child Development Center (40)
Operations & Maintenance Warehouse
5.85
7,800
2,570
3,030
5,950 4,340
2,924 4,200
2,070
7,080 3,200
2,832 4,248
-1,130 1,140
-48
RESIDENT
NON-RESIDENT
(328)
(26) 15
50 16,400
-1,080
28,537
Net Square Footage By Building Date: 03/26/2013 Page: 1
Center: PAUL SIMON (00512) of 4
HOUSING
Sleeping
Lounge
Storage
Shower/Toilet
Other
Function Suggested
NSF
11,200 10,680
5,600
1,900 2,530 2,530
2,720 1,140 2,200
1,750 2,800
0004 - NORTH DORMITORY
0005 - SOUTH DORMITORY
0003 - WEST DORMITORY
0003 - WEST DORMITORY
0005 - SOUTH DORMITORY
0004 - NORTH DORMITORY
0003 - WEST DORMITORY
0004 - NORTH DORMITORY
0005 - SOUTH DORMITORY
0005 - SOUTH DORMITORY
0003 - WEST DORMITORY
0004 - NORTH DORMITORY
0003 - WEST DORMITORY
0004 - NORTH DORMITORY
0005 - SOUTH DORMITORY
Bldg Name Actual NSF Difference
27,480
6,960
1,680
6,060
5,165
Sub Total: 47,345
23,616
3,280
1,968
3,936
32,800
3,864
3,680
-288
2,124
5,165
( 328
14,545
Page: 2
Center: PAUL SIMON (00512) of 4
EDUCATION
Academic
Vocational Theory (140)
Carpentry
Painting
Bricklayer
Computer Service Tech.
Non-Academic
Nursing Assistant
Graphic Artist
Material Handler
Pharmacy Tech
Office Administration
Function Suggested
NSF
2,080 1,280 1,240
1,310
3,860
3,720
3,860
1,540
3,500
3,720
2,230
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0009 - VOCATION
0009 - VOCATION
0009 - VOCATION
0009 - VOCATION
0006 - EDUCATION
0006 - EDUCATION
0007 - PHYSICAL FITNESS
0006 - EDUCATION
0004 - NORTH DORMITORY
0005 - SOUTH DORMITORY
0003 - WEST DORMITORY
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0006 - EDUCATION
0009 - VOCATION
0006 - EDUCATION
0006 - EDUCATION
Bldg Name Actual NSF Difference
6,510
1,310
3,860
3,720
3,860
1,540
6,370
3,720
2,230
Sub Total: 35,980
3,540
1,400
3,000
1,500
1,500
3,540
1,200
1,050
3,900
1,350
2,700
25,580
2,970
-90
2,220
2,360
2,830
-250
-90
-180
-400
-470
( 354
10,400
Page: 3
Center: PAUL SIMON (00512) of 4
FOOD SERVICE
RECREATION
MEDICAL/DENTAL
Dining (2 Servings)
Food Preparation
Food Storage
Recreation Hall
Arts & Crafts
Gymnasium
Theater
Pool Hall
Canteen
Aerobics/Exercise
Music Hall
Meeting Room
Women's Exercise Room
Computer Lab
Recreation Storage
Recreation Office
Medical/Dental
Function Suggested
NSF
4,970
2,870
2,190
7,800
2,570
3,030
0002 -CAFETERIA
0002 -CAFETERIA
0002 -CAFETERIA
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0007 - PHYSICAL FITNESS
0001 - ADMINISTRATION/MEDICAL-DENTAL
Bldg Name Actual NSF Difference
4,970
2,870
2,190
7,800
2,570
3,030
Sub Total:
Sub Total:
Sub Total:
10,030
15,710
3,030
2,832
2,124
1,416
2,070
6,372
16,790
2,070
2,138
3,658
-1,080
Page: 4
Center: PAUL SIMON (00512) of 4
ADMINISTRATION
STORAGE/SUPPORT
Administration
Child Development Center
Warehouse
Operations & Maintenance
Function Suggested
NSF
4,840
4,340
4,200
1,610
0001 - ADMINISTRATION/MEDICAL-DENTAL
0006 - EDUCATION
0007 - PHYSICAL FITNESS
0008 - MAINTENANCE/WAREHOUSE
0011 - CHILD DEVELOPMENT CENTER
0008 - MAINTENANCE/WAREHOUSE
0010 - PUMP HOUSE
0007 - PHYSICAL FITNESS
0008 - MAINTENANCE/WAREHOUSE
Bldg Name Actual NSF Difference
5,950
4,340
4,200
2,924
Sub Total:
Sub Total:
10,290
7,124
7,080
3,200
4,248
2,832
10,280
7,080
-1,130
1,140
-48
Energy Management Report Center: PAUL SIMON (00512)
Page: 1 Date: 03/26/2013 of 3
CENTER ENERGY DATA
Deferred (new center)
ENERGY CONSUMPTION ASSESSMENT
-27% 196,193
121,761 154,128
ENERGY USE BY FUEL TYPE
Energy Audit :
Date of Audit :
Electric Company :
Percent Change since Baseline Year :
Natural Gas Company :
Property Status :
Vanguard Energy Peoples Energy
Leased
2,824,166 9,636=
Total 34,071
MBtu
MBtu
Total $250,343 MBtu/ $7.348
BTU/GSF
BTU/GSF
BTU/GSF
Electricity
Natural Gas kWh
23,700 MCF = 24,435 MBtu
$181,456 $0.064= kWhElectricity
Natural Gas $68,887 = $2.907 MCF
ENERGY COST BY FUEL TYPE
COMMENTS
Adjustments made to correct consumption history 8/5/03
The month of June was not included for the Natural gas bill.
WATER CONSUMPTION ASSESSMENT
Percent Reduction Since Baseline Year:
1,000 Gallons
1,000 Gallons
FY 2012 Energy Goal:
Further Reduction in Energy Usage is needed to meet Energy Reduction Goals.
FY 2012 Energy Consumption:
Note: The Federal Government has set a goal of 3% Energy Consumption Reduction per year in EO 13423.
9,582 8,624 10,057
- 5%
Further Reduction in Water Usage is needed to meet Water Reduction Goals.
Note: The Federal Government has set a goal of 2% Water Consumption Reduction per year in EO 13423.
FY 2012 Goal:
FY 2012 Water Consumption:
1,000 Gallons
FY 2003 Energy Baseline:
FY 2007 Baseline:
Page: 2 of 3
Implementing some of the below recommendations can save you 10% to 25% off your annual energy bill without negatively impacting comfort or productivity.
1. Your staff and students are the key to savings. Educate the students and staff on the why of energy saving - costs and environmental impacts. Encouraging them to actively participate in energy reduction is also important. Post reminders at exit doors and bulletin boards about energy conservation. Simple tips include:
a. Turn it down (lights, heating & cooling),
b. Turn it off (lights, computers, other equipment),
c. Keep it tight (close doors and windows, use window blinds)
2. Operations and Maintenance: Educate the O&M staff on the why of energy saving -costs and environmental impacts. Simple tips include:
a. Make sure that the Operations and Maintenance staff is properly trained for the equipment they operate.
b. Tune and clean HVAC: Perform seasonal cleanups on air conditioners, boilers and furnaces, and regularly clean cooling coils and drain pans. Get rooftop or outdoor condenser coils cleaned and maintain an appropriate filter changing schedule.
c. Check (or ask your HVAC contractor to check) your outside air dampers or economizers to verify proper ventilation. Make sure economizer controls function properly. Make sure automatic dampers close during unoccupied periods.
d. Restore automatic control: When troubleshooting a system, take time to figure out and repair the automatic controls. Today's quick fix is tomorrow's bad idea.
e. Reasonable set points: Try 68°F in the heating season and 75°F in the cooling season.
f. Schedule HVAC equipment and lighting: (weekdays, weekends, holidays, off-season). Make sure equipment runs only when it is needed and the buildings are occupied. When buildings are vacant (i.e. dormitories during the day with students in class), make sure all the lights in the building are off.
g. Seasonal (resets, schedules, and shutoffs): As the seasons change, adjust set points and schedules to match the system's response to the weather.
h. Lighting: Invest in an inexpensive light level meter to measure the foot-candles in spaces to determine whether or not they are over lit and lamps can be safely removed. Where four-lamp fixtures are in use, two lamps can usually be removed from every fixture or every other fixture. After lamps are removed, disconnect ballasts. Contact the Energy team at PBDewberry for suggested light levels for individual space types. Cleaning fixtures regularly increases light levels.
i. Utilize power management features for all computers and monitors to shut them off when idle for more than 15 minutes.
Page: 3 of 3
j. Have your vending machine suppliers turn off or remove light tubes from the advertising lighting in the machine. This will save about $50 per year per vending machine.
k. Save water with low flow sink aerators (0.5gpm) and low flow shower heads (1.5gpm - 2.0gpm). This will also reduce water heating energy consumption.
l. Set your water heater to 120°F. Verify by measuring at the tap. Never go below 115°F.
m. For water heaters installed in unconditioned spaces, add insulation blankets making sure that access covers, electric connection areas, and pressure relief valves are left uncovered.
n. Caulk and fill cracks around doors and windows to reduce costly air leaks.
o. When replacing broken glass, use high transmittance, low heat gain windows.
p. Make sure automatic door closers are functioning properly to avoid drafts.
3. Buy energy efficient, buy EnergyStar (www.energystar.gov).
a. Buy EnergyStar appliances and equipment.
b. Replace burned out lightbulbs with EnergyStar labeled compact fluorescent lightbulbs (CFLs).
c. Replace broken thermostats with EnergyStar labeled programmable products.
d. Replace broken exit signs with EnergyStar LED exit signs.
Environmental Management Report
Page: 1 Date: 03/26/2013 of 1
SOLID & HAZARDOUS WASTE MANAGEMENT (RCRA)
Commercial Waste Service
HAZARDOUS MATERIALS STORAGE (EPCRA)
Yes Building 8
Paint thinner, paint Yes
PETROLEUM UNDERGROUND STORAGE TANKS (RCRA)
Compliance0
PETROLEUM ABOVEGROUND STORAGE TANKS (CWA)
ASBESTOS AND PCB MANAGEMENT (TSCA)
AIR POLLUTION CONTROL (CAA)
N/A None
Non-Attainment
Solid Waste Disposal :
Hazardous Waste Generator :
Hazardous Waste ID :
Generator Classification :
Hazadous Materials Storage :
Hazardous Materials ID :
HazMat Storage Area :
HazMat Spill Response Plan :
Number of Regulated USTs :
Number of Un-regulated USTs :
Local Hazardous Use Permit :
LEPC Notification :
EPA Generator ID Number :
Hazardous Waste Disposal :
RCRA Compliance
ID LocationFuel Type Capacity
Number of ASTs :
Asbestos Survey Date :
Asbestos Type :
Asbestos Coordinator :
Coordinator Training Date:
Custodial/Maintenance Training :
AHERA Regulated :
Management Plan Approval :
PCB Transformer Testing :
PCB Transformers :
PCB-Contaminated Transformers :
Transformers Labelled :
Regional Air Quality :
Permitted Air Pollution Source :
Source Description :
National Industrial Waste Yes Paint Thinner
Conditionally Exempt Small Quantity Generator N/A Commercial Hazardous Waste Disposal Service
Total Safety
Yes Yes
Overfill Leak Corrosion
SPCC Plan Required : SPCC Plan Completed :
No N/A
No Survey Performed None
N/A N/A
Yes Yes
Ozone, PM-10
ID Fuel Type Capacity Location Overfill
Prevention Secondary ContainmentTank Status
Tank Status Prevention/Detection
Radon
Date: 03/26/2013Center : Paul Simon (00512) Page: 1 of 1
0001 - ADMINISTRATION/MEDICAL-DENTAL
0002 -CAFETERIA
0003 - WEST DORMITORY
0004 - NORTH DORMITORY
0005 - SOUTH DORMITORY
0006 - EDUCATION
0007 - PHYSICAL FITNESS
0008 - MAINTENANCE/WAREHOUSE
0009 - VOCATION
0010 - PUMP HOUSE
0011 - CHILD DEVELOPMENT CENTER
Bldg Name
11/04/2004
11/04/2004
11/04/2004
11/04/2004
11/04/2004
11/04/2004
11/04/2004
11/04/2004
11/04/2004
01/17/2007
01/17/2007
Test Date
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Radon Testing
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
< 4 pCi
Test Result
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Mitigation Mitigation Date
RADON EXPLANATORY NOTES
The US Environmental Protection Agency (EPA) has established a radon action level of 4.0 picoCuries per liter (pCi/L). Occupied buildings with radon concentrations less than 4.0 pCi/L do not require radon mitigation; un-occupied buildings, or those buildings which are occupied only infrequently for brief periods of time, also do not require radon mitigation. Occupied buildings with radon concentrations greater than
4.0 pCi/L require radon mitigation and verification of radon reductions as soon as possible, with priority given to dormitories and student recreation buildings. Occupied buildings with radon concentrations greater than 20.0 pCi/L should be considered significant radon exposure hazards, and priority for mitigation should be given to buildings with these highly elevated radon concentrations.
Radon mitigation techniques include: (1) adjustment of the building HVAC system to create a positive pressure within the building; (2) sealing of foundation wall cracks, penetrations, or other openings;
(3) sealing crawlspace openings and sump pits; (4) installing an active subslab depressurization (ASD) system.
Site Description
PAUL SIMON
View from the south loop roadView from the south loop road
Aerial viewAerial view
Page: 1 Date: 03/26/2013 of 3
Comments:
Paving Type for Roads & Parking
The south section of the loop road is deteriorated. Soil erosion and water ponding were identified east of North Dormitory Building 4 and west of South Dormitory Building 5. The staff parking at the east side gets flooded during rains.
Paving Type for Sidewalks
Asphalt Concrete
Comments:
Topography Buildings and Structures
Center is not fully enclosed by fencing.
ROADS, PARKING & SIDEWALKS
Water Source Water Authority Service Meter On-Site Treatment Plant
1. Water System
Treatment Type Storage Type Storage Capacity(Gallons)
NoMasterCity of Chicago Dept. of Water ManagemPublic Water Authority
None 0None
A water pressure booster system located in Pump House Building 10 serves the entire site.Comments:
Comments:
Fire Hydrants On-Site Water Supply Storage Capacity
(Gallons) Pressure Source FD Response Time (Minutes)
Yes 0 10None Fire Pump
A City of Chicago fire station which serves the center is about 5 miles away and has a response time of about 10 minutes.
Number of Deficiencies = 5
Number of Deficiencies = 3
SITE FEATURES
UTILITIES
2. Fire Protection System
Buildings Structures11 6Gently Sloping
Surrounding
Outdoor Recreation
Light Industrial
Basketball, Field, Soccer, Soft/Baseball High Voltage Transmission Lines, RR Tracks
All site except the east entry Chain Link
Location Type
Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Separate Loop
No
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Ownership
Roads & Parking Adequate Roads & Parking Condition Sidewalks Adequate Sidewalk Condition Yes Fair Yes Good
Number of Deficiencies = 3
Fencing
Other Features
Page: 2 Date: 03/26/2013 of 3
Sewage Treatment Flow
Utility
Publicly Owned Treatment Works
Center
Gravity
Maintenance ResponsibilityOwnership
Comments: Natural gas is supplied by Peoples Energy.
Peoples Energy
Comments:
Electric Company PCB Trans.
Transformer Mounting Transformer Ownership
Systems Ownership Maintenance Responsibility
Vanguard Energy
The 12.47 kV primary utility lines are brought to the center from power poles along Kedzie Avenue. The overhead lines transit to underground at the last pole at the corner of Kedzie Avenue and Access Drive where primary service meters are installed. The underground secondary services are distributed throughout the center via a loop of manholes and 12.47 kV:480/277V utility-owned, pad-mounted transformers located outside Buildings 1, 4, 5, 6, 7 and 11. Each building has a 208/120V, 3-phase, 4 wire system provided by a center-owned, step-down transformer located within its respective electrical room. Secondary metering is also provided at each building service entrance.
Except Child Development Center Building 11, all buildings at the center have a lightning protection system installed on the roof.
Pad Utility
Utility Utility
No
12.47 kV, 3-Phase, 3 Wire
480/277V, 3-Ph, 4 Wire and 208/120V, 3-Ph, 4 WireUnderground
UndergroundPrimary Service
Secondary Service
Distribution Characteristics
3. Sanitary Sewer System/ Sewage Treatment Plant
5. Fuel Distribution System
Number of Deficiencies = 3
System Capacity Adequate System Condition
Yes Good
4. Storm Water System Number of Deficiencies = 6
Drain Type On-Site Storm Water Management
Underground N/A
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Yes UnknownCenter
Comments: Water ponding and erosion were present east of North Dormitory Building 4 and west of South Dormitory Building
5. These conditions are attributed to a clogged drain, inadequate grading and the absence of an underground pipe to channel the storm water to an existing culvert.
Gas Company Metering
Master
Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
7. Electrical (Service)
Transformer Maint Resp
Utility
System Capacity Adequate System Condition
Yes Good
Generator
None
ATS MTS
No No
6. Central Plant: None
Metering Master
Page: 3 Date: 03/26/2013 of 3
ACCESSIBILITY
Yes
NoNoNoNo
Nationally Registered Site
Site Eligible for National Register
Located in Historic District
Archaeological Significance
Comments:
Telephone Company
On-site Line Owner
The main telephone service is brought to the center by AT&T. XO Communications provides/maintains the internal distribution system. Job Corps Data Center provides and oversees the data/communication networks. The telephone/server room is located in Administration/Medical/Dental Building 1. The building fire alarm system at the center is stand alone but remotely monitored from the security office and maintenance office. The site security system includes CCTV cameras, black and white monitors and an electric gate operator. CCTV cameras are mounted on light poles and building exteriors at strategic locations, with black and white monitors located in the security office. Additional cameras are being installed in the dormitory's interiors. The electric gate operator with card reader is installed at the northeast entrance. The gate can also be remotely controlled in the security office.
Door alarms are installed in dormitory, education and CDC buildings. A satellite dish for television programming is provided in the dormitory, cafeteria, physical fitness and education buildings.
AT&T
Maint. Responsibility
Utility Utility
CCTV Cameras, Electric Gate Operator and Door Alarms
Earthquake Risk
Low Medium LowMedium MediumIBC Low
LightningEarthquake Def. Authority Flooding Tornado Hurricane Forest
Fire
Accessible Parking: Accessible Slope:
Yes
Curb Cuts:
Yes
Ramps:
YesYes
Site Accessible Route:
GENERAL SITE CONDITION
Rating X Good Fair Poor
HISTORIC PRESERVATION
9. Electrical (Communication/Alarm/Security)
NATURAL HAZARDS
The site condition is not impacting the functional use of the facilities.
The site condition IS impacting the functional use of the facilities.
The site condition IS SIGNIFICANTLY impacting the functional use of the facilities.
Yes
Central
VOIP
System Capacity Adequate System Condition
GoodYes
8. Electrical (Site Lighting)
Roadways Parking Walkways Building Outdoor Sports
Mounting
Control
Pole Pole Pole Building Pole
Photocell Photocell, Time Clock Photocell, Time Clock Photocell, Time Clock Switch
System Ownership Maintenance Responsibility System Capacity Adequate System Condition
Center Center Yes Good
Comments: The site lighting consists of pole-mounted and building-mounted fixtures which are controlled by photocells and timers. The center owns and maintains the site lighting system.
Number of Deficiencies = 3
Number of Deficiencies = 8
STORAGE TANKS: None
Fire Alarm Security
Building Descriptions and Utilities
BUILDING 1 ADMINISTRATION/MEDICAL DENTALBUILDING 1 - ADMINISTRATION/MEDICAL-DENTAL
Building Descriptions
Page: 1 of 56
Building: 0001 - ADMINISTRATION/MEDICAL-DENTAL
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Wood Wood
Wood Shingles Wood Siding
Wall Roof Batt Batt
Metal Unit - Metal Frame Storefront - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Business 13,447 7,870 1 Owned 1999 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material Drainage Year Life
Remaining Type Area Served
Fiberglass Shingles Gutters and Downspouts 2010 48 Gable/Shed Entire Building
3. Roof
Entire Building
Area Served
Page: 2 of 56
Building: 0001 - ADMINISTRATION/MEDICAL-DENTAL
INTERIOR FINISH
Carpet Ceramic Tile Concrete Stamped Rubber Vinyl Tile
CMU Ceramic Tile Drywall Vinyl Wallcovering
Metal Rollup - Metal Frame Wood Unit - Metal Frame
Metal Overhead - Wood Frame
VERTICAL CIRCULATION
None
Casement - Aluminum Frame; Double Glazing;
Acoustical Tile Gypsum Board Plaster
Number of Deficiencies = 1
Windows6.
Floors1.
Interior Walls2. Number of Deficiencies = 1
3.
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Heating hot water is provided by two HydroTherm MR-360C-PV boilers serving two McQuay LSL-106 and one McQuay LSL-104 air handling units.
Electric cabinet unit heaters also serve mechanical rooms.
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Electric Resistance
Electric Resistance
Single Duct
Unit Heater
Baseboard
Two-Pipe
None
None
Direct Digital Controls (DDC)
Electric
Electric
Heat
Natural Means
Natural Means
None
None
None
Entire Building
Vestibules
Offices
Ceilings
Page: 3 of 56
Building: 0001 - ADMINISTRATION/MEDICAL-DENTAL
Mechanical
Mechanical
Mechanical
Restroom
Janitor's Closet
Mechanical Room
A 50 gallon A. O. S. model DEN 5210 electric water heater (6,000 Watts input) serves the administration wing. An 80 gallon State electric water heater (18 kW input) serves the medical/dental wing.
Comments:
Cast Iron None None
Electric Water Cooler Fixed Emergency Eyewash Hose Bibb Lavatory Service Sink Shower/Bathtub Sink Urinal Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Electric None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Split Direct Expansion (Air
Source)
Split Direct Expansion (Air
Source)
Single Duct
Single Duct
Refrigerant
Refrigerant
Direct Digital Control (DDC)
Electric
Mechanical
Natural
None
None
Entire Building
Electronic Equipment
Room
PLUMBING
Exhaust Ventilation
Three Carrier model CBA090FA2 and one Carrier model CBA048FB4 condensing units serve coils in the air handling units.
A Janitrol CD24-1D system provides cooling to electronic equipment in rooms 111 and 112.
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 1
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
3. Air Conditioning
Page: 4 of 56
Building: 0001 - ADMINISTRATION/MEDICAL-DENTAL
None None ABC Type Fire Extinguisher
Comments: Service is brought from a 12.47 kV:480/277V pad-mounted transformer outside to a 400A main distribution panel (MDP) with integral secondary meter, located in the electrical room. The 400A MDP also serves Pump House Building 10. A 112.5 kVA step-down transformer provides the 120/208V, 3-phase, 4 wire system for the building.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an Edwards System model EST-3 located in the main lobby.
The remote annunciator panel is located in the vestibule of the administration wing.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution.
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Medical/Dental
Wards (Patient)
Reception
Lounges
Conference Rooms
Corridors & Stairs
Toilets
Equipment Rooms (Elec/Mech)
Storage Rooms
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
FIRE PROTECTION
ELECTRICAL SERVICES
Exterior Lighting1.
Interior Lighting2.
Emergency /Exit Lighting3. Number of Deficiencies = 2
LIGHTING
Page: 5 of 56
Building: 0001 - ADMINISTRATION/MEDICAL-DENTAL
Comments: The electric gate operator and CCTV cameras are monitored and controlled from the security office.
Telephone and data/communication equipment is located in the telephone/server room in this building.
A UPS in this room provides back-up power for the communication and data equipment. A pay phone is provided in the vestibule of the administration wing.
Connected to Main System Closed Circuit TV Not Connected to Main System
None
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION Number of Deficiencies = 1
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoZone
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location None None
Comments: At the time of May 2012 Facility Survey, CO detectors were not provided. A deficiency has been added to the report.
CARBON MONOXIDE DETECTION
BUILDING 2 CAFETERIABUILDING 2 -CAFETERIA
Page: 6 of 56
Building: 0002 -CAFETERIA
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry/Wood
Wood
CMU Cement Board Siding Wood Shingles
Comments: The original horizontal wood siding on the lower half of the exterior walls was replaced with cement siding boards. The original wood shingle siding on the upper wall is original to the building.
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Assembly 11,937 10,030 1 Owned 1999 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
No
Yes
Yes
Yes
Yes
Yes
N/A
N/A
Yes
Yes
N/A
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Material
During the May 2012 Facility Survey, moderate deterioration of the roof membrane (bubbling) was observed but no roof leaks were noticed inside the building. The life expectancy of the roof is estimated based on the visual observation during the May 2012 Facility Survey.
A CTST project to enclose the loading dock was not finished. The new single ply roof installed over the existing loading dock does not have a gutter or downspouts and the membrane is delaminated.
Inadequate flashing between this roof and the shingle roof over the main building and the lack of gutter and downspouts caused water infiltration inside the building and staining of the new CMU wall enclosure.
The single ply roof was installed after the replacement of the main roof of the building causing damage to the new shingles.
Drainage Year Life
Remaining Type Area Served
Fiberglass Shingles
EPDM
Single Ply
Gutters and Downspouts
Gutters and Downspouts
Surface Run-off
Gable/Hip
Flat
Shed
Dining Hall
Kitchen
Loading Dock
Number of Deficiencies = 1
Comments:
Comments:
3. Roof
Page: 7 of 56
Building: 0002 -CAFETERIA
Wall Roof Batt/Rigid Batt
INTERIOR FINISH
Carpet Ceramic Tile Concrete Quarry Tile Vinyl Tile
CMU Ceramic Tile Drywall Wood Paneling
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Loading Dock Concrete Ramp
Metal Unit - Metal Frame Storefront - Metal Frame
Casement - Aluminum Frame; Double Glazing; Fixed - Aluminum Frame; Double Glazing;
Acoustical Tile Exposed Structure Gypsum Board
Number of Deficiencies = 1
Insulation4.
Exterior Doors5.
Windows6.
Floors1.
Interior Walls2.
3.
Interior Doors4.
Page: 8 of 56
Building: 0002 -CAFETERIA
Mechanical
Mechanical
Mechanical
Restroom
Kitchen
Janitor's Closet
Ventilation Area Served
Packaged Direct
Expansion (Air Source)
Single Duct None Direct Digital Control (DDC)
Mechanical None Entire Building
Exhaust Ventilation
A Carrier model 48EJE038 serves the kitchen. A Carrier model 48EJE034 serves the dining hall. A Carrier model PGAA18B1K6 serves the dry food storage area. All are rooftop units.
Comments:
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
A Carrier model 48EJE038 serves the kitchen. A Carrier model 48EJE034 serves the dining hall. A Carrier model PGAA18B1K6 serves the dry food storage area. All are rooftop units.
Electric cabinet unit heaters serve vestibules.
Three Industrial Air Systems units replace air exhausted by hoods. Model numbers are MD112CA000134E, MD112CA000138E, and MD112CA000138D.
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Packaged
Electric Resistance
Gas-Fired Direct
Single Duct
Unit Heater
Makeup Air Unit
None
None
None
Direct Digital Controls (DDC)
Electric
Direct Digital Control (DDC)
Mechanical
Natural
Mechanical
None
None
None
Entire Building
Vestibules
Kitchen
Ventilation2.
System Type
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Page: 9 of 56
Building: 0002 -CAFETERIA
Three Lochinvar model CNH251-100-DF9 water heaters serve this building. Each water heater has 98-gallon capacity and 227 GPH recovery with 250 MBH input.
Comments:
Cast Iron Outdoor None
Electric Water Cooler Hose Bibb Lavatory Service Sink Sink Urinal Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
None None ABC Type Fire Extinguisher, K Type Fire Extinguisher, Wet Chemical
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
Location UL300 Compliance Status Kitchen, near sink next to pull station.
Near cutting board station.
Compliant
Compliant
UL300 COMMERCIAL KITCHEN HOOD FIRE SUPPRESSION
Page: 10 of 56
Building: 0002 -CAFETERIA
Comments: Service is brought from a 12.47 kV:480/277V pad-mounted transformer located behind Gymnasium Building 7. Service terminates in an 800A MDP with integral secondary meter, located inside the cafeteria.
A 225 kVA step-down transformer provides the 120/208V, 3-phase, 4 wire system for the building. The
12.47 kV:480/277V pad-mounted transformer also serves Physical Fitness Building 7 and Maintenance/Warehouse Building 8.
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an Edwards System model EST-3 located in the vestibule. The dining hall has beam type smoke detectors.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Audible Alarm Control/Annunciator Panel Heat Detector Manual Pull Station Remote Annunciator Panel Smoke Detector Visual Alarm
Comments: Recorded footcandle levels include natural light contribution. The dining area has four large pendant-mounted decorative circular fixtures with acrylic translucent domes. Each fixture has a combination of 2- 400W HID and 8 compact fluorescent lamps providing indirect and direct illumination, respectively.
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
Offices
Food Preparation
Dining/Lunch Rooms
Dishwashing
Storage Rooms
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Locker Room
Toilets
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Emergency Exit
Number of Deficiencies = 1
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 1
Page: 11 of 56
Building: 0002 -CAFETERIA
Connected to Main System None Not Connected to Main System
Satellite Dish
Telephone Security Public Address Television
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location None None
Comments: At the time of May 2012 Facility Survey, CO detectors were not provided. A deficiency has been added to
BUILDING 3 WEST DORMITORYBUILDING 3 - WEST DORMITORY
Page: 12 of 56
Building: 0003 - WEST DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood Truss
CMU Masonry Cement Board Siding
Wall Roof Rigid Batt
Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 16,110 9,755 2 Owned 1999 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2.
Insulation4.
Exterior Doors5. Number of Deficiencies = 1
Material Drainage Year Life
Remaining Type Area Served
Fiberglass Shingles Gutters and Downspouts 2010 48 Gable Entire Building
3. Roof
Page: 13 of 56
Building: 0003 - WEST DORMITORY
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
CMU Ceramic Tile Drywall Folding Partition
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Elevator Metal Stairs Wood Stairs
Casement - Aluminum Frame; Double Glazing; Double Hung - Aluminum Frame; Double Glazing;
Fixed - Aluminum Frame; Double Glazing;
Gypsum Board
Number of Deficiencies = 4
Windows6.
Floors1. Number of Deficiencies = 1
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Dual-temperature McQuay model HSB040CN fan coils serve four-person rooms. Model HSB030CN units serve two-person rooms.
These are cabinet unit heaters.
Common areas are served by constant air volume, variable temperature McQuay model LSL114 air handling units. A HydroTherm model MR-600B-PV boiler provides heating hot water to the air handlers and dorm fan coil units.
Hot water baseboard heaters are located under lounge perimeter windows and also serve storage areas.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Electric Resistance
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Fan Coil
Unit Heater
Single Duct
Baseboard
Two-Pipe
None
Two-Pipe
Two-Pipe
Electric
Electric
Direct Digital Control (DDC)
Hand Valves
Natural
Natural
Mechanical
Natural
None
None
None
None
Dorm Rooms
Vestibules
Common Area
Common Area
Page: 14 of 56
Building: 0003 - WEST DORMITORY
Mechanical
Mechanical
Mechanical
Mechanical
Mechanical
Toilet/Shower
Laundry
Equipment Room
Janitor's Closet
Storage Rooms
Comments: Mechanical and electric equipment rooms have mechanical exhausts.
Domestic hot water is provided by two A.O. Smith model BTH 400A 976 direct vent water heaters.Comments:
Cast Iron None None
Electric Water Cooler Lavatory Service Sink Shower/Bathtub Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
Ventilation Area Served
Copper Copper Gas-Fired None No
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Chiller
Chiller
Single Duct
Fan Coil
Two-Pipe
Two-Pipe
Direct Digital Control (DDC)
Electric
Mechanical
Natural
None
None
Common Area
Dorm Rooms
PLUMBING
Exhaust Ventilation
Common areas are served by constant air volume, variable temperature McQuay model LSL114 air handling units. A McQuay model AR040E package chiller provides chilled water to the air handlers and dorm fan coil units.
Dual-temperature McQuay model HSB040CN fan coils serve four-person rooms. Model HSB030CN units serve two-person rooms.
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 2
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Water Distribution1.
Sanitary Distribution2.
Fixtures3. Number of Deficiencies = 1
Fuel Distribution4.
Page: 15 of 56
Building: 0003 - WEST DORMITORY
Dry None ABC Type Fire Extinguisher
Comments: Service is brought from a 12.47 kV:480/277V pad-mounted transformer located outside South Dormitory Building 5. Service terminates in a 400A MDP with integral secondary meter, located in West Dormitory Building 3 electrical room. A 75 kVA step-down transformer provides the 120/208V, 3-phase, 4 wire system for the building.
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
Comments: Recorded footcandle levels include natural light contribution. In addition to general lighting, each bedroom has wall-mounted reading lights above beds and task lights at study desks. The main lobby is provided with recessed-mounted compact fluorescent down lights. The two-story lounge in each dormitory wing has pendant-mounted direct/indirect HID light fixtures. Night light wall sconces with compact fluorescent lamps are installed at the entry of each bedroom.
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Sleeping Rooms
Housing Lounge
Laundry Room
Study Room
Shower
Toilets
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Storage Rooms
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
Emergency Exit
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 2
Exterior Lighting1.
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 1
Page: 16 of 56
Building: 0003 - WEST DORMITORY
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an Edwards System model EST-3 located in the foyer.
Comments: Pay phones are provided in the main lobby for student use. New CCTV cameras, being installed in the corridor and stairwells, were not operational at the time of May, 2012 Facility Survey.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Connected to Main System Magnetic Door/Alarm None Satellite Dish
Telephone Security Public Address Television
Number of Deficiencies = 1
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
COMMUNICATION
The facility condition is not impacting the functional use of the facility.
The facility condition IS impacting the functional use of the facility.
The facility condition IS SIGNIFICANTLY impacting the functional use of the facility.
Electric Water Gas No NoYes
BUILDING UTILITY METERING
Structure: Good Exterior: Good Interior: Good Mechanical: Good Electrical: Good
Type Location None None
Comments: At the time of May 2012 Facility Survey, CO detectors were not provided. A deficiency has been added to
BUILDING 4 NORTH DORMITORYBUILDING 4 - NORTH DORMITORY
Page: 17 of 56
Building: 0004 - NORTH DORMITORY
BUILDING ENVELOPE
Foundation RoofBuilding
Concrete Loadbearing Masonry Wood Truss
CMU Masonry Cement Board Siding
Wall Roof Rigid Batt
Metal Unit - Metal Frame Storefront - Storefront Frame
AccessibilityFeature
GSF NSF Year Built Use Group Historic Ownership#Floors
Residential 29,644 18,720 2 Owned 1999 Not Evaluated
REAL ESTATE
Access to Building
Ramps
Entrance
2nd Egress
Visual Alarm
Corridor/Aisle
Rooms
Stairs
Elevator
Restrooms
Drinking Fountain
Telephone
Yes
N/A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
ACCESSIBILITY
Structural Systems1.
Exterior Walls2. Number of Deficiencies = 1
Insulation4.
Exterior Doors5. Number of Deficiencies = 2
Material Drainage Year Life
Remaining Type Area Served
Fiberglass Shingles Gutters and Downspouts 2010 48 Gable Entire Building
3. Roof
Page: 18 of 56
Building: 0004 - NORTH DORMITORY
INTERIOR FINISH
Ceramic Tile Concrete Vinyl Tile
CMU Ceramic Tile Drywall Folding Partition
Metal Unit - Metal Frame Wood Unit - Metal Frame
VERTICAL CIRCULATION
Elevator Metal Stairs Wood Stairs
Casement - Aluminum Frame; Double Glazing; Double Hung - Aluminum Frame; Double Glazing;
Fixed - Aluminum Frame; Double Glazing;
Gypsum Board
Number of Deficiencies = 2
Windows6.
Floors1. Number of Deficiencies = 2
Interior Walls2.
3. Number of Deficiencies = 1
Interior Doors4.
Heat Source
Heat Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area Served
Dual-temperature McQuay model HSB040CN fan coils serve four-person rooms. Model HSB030CN units serve two-person rooms.
These are cabinet unit heaters.
Hot water baseboard heaters are located under lounge perimeter windows and also serve storage areas.
Common areas are served by constant air volume, variable temperature McQuay model LSL114 air handling units. Two HydroTherm model MR-900B-PV boilers provide heating hot water to the air handlers and dorm fan coil units.
Comments:
Comments:
Comments:
Comments:
HVAC
Heat1.
Gas-Fired Hot Water Boiler
Electric Resistance
Gas-Fired Hot Water Boiler
Gas-Fired Hot Water Boiler
Fan Coil
Unit Heater
Baseboard
Single Duct
Two-Pipe
None
Two-Pipe
Two-Pipe
Electric
Electric
Hand Valves
Direct Digital Controls (DDC)
Natural
Natural
Natural
Mechanical
None
None
None
None
Dorm Rooms
Vestibules
Common Area
Page: 19 of 56
Building: 0004 - NORTH DORMITORY
Mechanical
Mechanical
Mechanical
Mechanical
Mechanical
Toilet/Shower
Laundry
Equipment Room
Janitor's Closet
Storage Rooms
Comments: Mechanical and electric equipment rooms have mechanical exhausts.
Ventilation Area Served
Chiller
Chiller
Fan Coil
Single Duct
Two-Pipe
Two-Pipe
Electric
Direct Digital Control (DDC)
Natural
Mechanical
None
None
Dorm Rooms
Common Area
Exhaust Ventilation
Dual-temperature McQuay model HSB040CN fan coils serve four-person rooms. Model HSB030CN units serve two-person rooms.
Common areas are served by constant air volume, variable temperature McQuay model LSL114 air handling units. A McQuay model AGR080AS27 package chiller provides chilled water to the air handlers and dorm fan coil units. (Chiller has S/N 58E8135901 and two compressors, 40 HP and 50
HP).
Comments:
Comments:
Ventilation2.
System Type
Number of Deficiencies = 2
Air Distribution
Piping System
Control System
Fresh Air Intake
Energy Conservation
Measure
Area
Page: 20 of 56
Building: 0004 - NORTH DORMITORY
Domestic hot water is provided by four A.O. Smith model BTH 400A 976 direct vent water heaters.
Each water heater has a 130-gallon capacity, 465 GPH recovery, 400 MBH input, and was manufactured in 12/2007.
Comments:
Cast Iron None None
Electric Water Cooler Laundry Sink Lavatory Service Sink Shower/Bathtub Wall Hydrant Water Closet (Flush Valve)
Gas (Natural)
Wet None ABC Type Fire Extinguisher
Comments: A dry pipe sprinkler system serves the second floor and attic.
Comments: Service is brought from a 12.47 kV:480/277V pad-mounted transformer outside to a 500A main distribution panel (MDP) with integral secondary meter, located in the electrical room. A 150 kVA step-down transformer provides the 120/208V, 3-phase, 4 wire system for the building.
Copper Copper Gas-Fired None Yes
Hot Water Cold Water Water Heater Water Treatment HW Storage Tank
Grease InterceptorWaste / Vent Interior Storm
Service Entrance Electrical Characteristics Distribution Equipment Wiring Devices
High Intensity Discharge (HID)
Comments: Exterior building-mounted and surrounding area pole-mounted light fixtures are controlled by time clock and photocells.
Main Distribution Panel 277/480V, 3-Phase, 4 Wire Panelboard Receptacles, GFCI, Switches
Sprinkler System Stand Pipe System Fire Suppression
PLUMBING
Water Distribution1.
Sanitary Distribution2.
Fixtures3.
Fuel Distribution4.
FIRE PROTECTION
ELECTRICAL SERVICES Number of Deficiencies = 1
Exterior Lighting1.
Page: 21 of 56
Building: 0004 - NORTH DORMITORY
FIRE ALARM
Comments: The fire alarm control/annunciator panel is an Edwards System model EST-3 located in the vestibule.
Comments: Pay phones are provided in the main lobby for student use. Though not yet operational during the May 2012 Facility Survey, new CCTV cameras were being installed in the corridor and stairwells.
Audible Alarm Control/Annunciator Panel Duct Smoke Detector Flow Switch Manual Pull Station Smoke Detector Tamper Switch Visual Alarm
Connected to Main System Magnetic Door/Alarm None Satellite Dish
Telephone Security Public Address Television
Comments: Recorded footcandle levels include natural light contribution. In addition to general lighting, each bedroom has wall-mounted reading lights above beds and task lights at study desks. The main lobby is provided with asymmetric wall-mounted HID lights and decorative compact fluorescent wall sconces. The two-story lounge in each dormitory wing has pendant-mounted direct/indirect HID light fixtures. Night light wall sconces with compact fluorescent lamps are installed at the entry of each bedroom.
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Compact Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
T8 - Fluorescent
Offices
Sleeping Rooms
Housing Lounge
Laundry Room
Study Room
Shower
Toilets
Corridors & Stairs
Equipment Rooms (Elec/Mech)
Storage Rooms
Area Recommended Level
Recorded Level Light Type
Battery Backup Battery Backup
Emergency Exit
Number of Deficiencies = 2
Interior Lighting2. Number of Deficiencies = 1
Emergency /Exit Lighting3. Number of Deficiencies = 1
COMMUNICATION
Electric Water Gas No NoYes
BUILDING UTILITY METERING
Type Location None None
Comments: At the time of May 2012 Facility Survey, CO detectors were not provided. A deficiency has been added to
Page: 22 of 56
Building: 0004 - NORTH DORMITORY
GENERAL BUILDING CONDITION
Rating X Good
Fair Poor
The facility condition is not impacting the functional use of the…