CVE VOR 100 pct Signed Dwgs.pdf

PDF 7 MB Posted

Attached to
Security Fence Dallas TX Federal contract opportunity
Solicitation number
6973GH-23-Q-00181
Issued by
Department of Transportation Federal Aviation Administration Franchise Acquisition Services

About this file

This set of documents includes plans and drawings for a security fence installation project at a VOR site in Dallas, Texas. The project involves installing over 3,000 linear feet of 8-foot tall chain link security fencing with barbed wire, as well as gates and signage. Drawings show the site layout and specifications, fencing and gate details, and the existing conditions. The related federal contract opportunity is solicitation number 6973GH-23-Q-00181 from the Department of Transportation Federal Aviation Administration to provide fencing and security upgrades at the Dallas VOR facility. The responsive contractor will be responsible for removal of vegetation, installation of the new fencing and gates, grounding, and additional security measures per the drawings and specifications provided.

View the file

Other files for this federal contract opportunity

Other files attached to Security Fence Dallas TX, newest first.
File Type Posted
FAA_AJWC18D_2918 CVE VOR Security Fence Specs.pdf PDF
FAA_AJWC18D_2918 CVE VOR Security Fence Specs.pdf PDF
Experience Information Form.pdf PDF
Contractor Release Form.pdf PDF
6973GH-23-Q-00181.pdf PDF
Payment Bond.pdf PDF
Performance Bond.pdf PDF
WAGE DETERMINATION.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

H

G

F

E

D

C

B

A

8 1234567

M

P lo t t e d b y

S R

V

O c v e z

.d w g

8 234567

BFEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY DATE

DRAWING NO

DESIGNED

REVIEWED BY

APPROVED

IS

U

02/21/2023

MGR: ENGINEERING - FORT WORTH

DALLAS

CVE-21005100-Z001

BCM

VOR

REFERENCE DRAWING:

PLAT OF SURVEY

-2

-z

INFRASTRUCTURE

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

IE

W

COWBOY

THIS DRAWING PRODUCED ON ASW REGION MICROSTATION SYSTEM

PROJECT ENGINEER

21005100

TX

cve-21005100-z001

2023-03-21T15:50:16-0500

FEKADU M WAKTOLA

2023-03-10T10:29:31-0600

BRITTANY ALEXIS COMER-MATHIS

CURB

EXISTING

FAA PROPERTY LINE

CHAIN LINK FENCE

EXISTING TRI-DAL REALTY

FAA PROPERTY LINE EXISTING CURB

LEAF GATE

EXISTING DOUBLE

FOR PLAT SURVEY)

(SEE SHEET CVE-21005100-Z001

1.6' W. BACK OF CURB

FOR PLAT SURVEY)

(SEE SHEET CVE-21005100-Z001

0.3'S. & 0.1W. OF FENCE CORNER

SIDEWALK

EXISTING

ADJACENT PROPERTY LINE

IN GOOD CONDITION

EXISTING FAA CHAIN LINK FENCE

IN GOOD CONDITION

EXISTING FAA CHAIN LINK FENCE

EXISTING CREEK

EXISTING FIRE HYDRANT

EXISTING POWER POLE

t t e d b

40' 0 40' 80"

SCALE: 1" = 40"

ADJ PROPERTY LINE

EXISTING CHAIN LINK FENCE

TEMPORARY CHAIN LINK FENCE

TREES/SHRUBS

REFERENCE POINT FROM SURVEY

EXISTING DOUBLE LEAF GATE

J

L

LEGEND

EXISTING GRAVEL ROAD

X

T

IN

N

'2

"W

'-9

N00°39'29"W 500'-0"'

'1

"E

.2

NOTES

1. CONTACT THE SSC MANAGER FOR SITE ACCESS.

2. CONTRACTOR TO VERIFY PROPERTY LIMITS.

3. CALL TEXAS811 BEFORE ANY TREE REMOVAL WORK IS DONE.

4. LOCATE EXISTING UTILITIES AS NEEDED. SSC STAFF WILL

LOCATE THEIR UNDERGROUND UTILITIES AT THE SITE UPON

THE CONTRACTORS REQUEST. GIVE 3 DAYS NOTICE TO THE

COR.

100% SUBMITTAL

CVE-21005100-C001

SECURITY FENCE INSTALLATION

EXISTING SITE PLAN

-c cve-21005100-c001

2023-03-21T15:49:38-0500

FEKADU M WAKTOLA

2023-03-10T10:23:41-0600

BRITTANY ALEXIS COMER-MATHIS

TO BE REMOVED

154'-0" TEMPORARY FENCE

EXISTING TRI-DAL REALTY

BE REMOVED

FENCE TO

150'-0" TEMPORARY

SHEET CVE-21005100-C003)

(SEE CHAIN LINK FENCE DETAILS ON

CENTERED ON ACCESS ROAD

DOUBLE LEAF GATE

INSTALL 24' WIDE

(SEE SHEET CVE-21005100-C003 FOR DETAILS)

FENCE WITH 1 FOOT INTRUDER GUARD

FENCE WITH A NEW 7' HIGH CHAIN LINK

INSTALL A 3,071 LF PERIMETER SECURITY

SECURE VOR

FENCE TO REMAIN TO

EXISTING FAA CHAIN LINK

FENCE TO REMAIN

EXISTING FAA CHAIN LINK

SHEET CVE-21005100-C003)

(SEE CHAIN LINK FENCE DETAILS ON

INSTALL 12' WIDE

SHEET CVE-21005100-C003/C004)

(SEE WALK GATE DETAILS ON

WALK GATE WITH EMERGENCY USE SIGN AND KNOX BOX

INSTALL 5' WIDE

ADJ PROPERTY FENCE LINE

ALL THE WAY TO

EXTEND FENCE LINE

t t e d b

CHAIN LINK FABRIC KNUCKLED

TOP AND BOTTOM WITH #9

GALVANIZED TENSION WIRE

#9 TIE WIRE 12"

C. TO C. APPROX.

33/4

13/8" O.D.

PLUNGER ROD

12' TO 24' GATE (OPENING BETWEEN POSTS)

DOUBLE LEAF

(GATE LEAF TO SWING A MINIMUM OF 100

AND A MAXIMUM OF 150 )

1'-6"

MIN.

GATE POST

4" STANDARD PIPE

(MINIMUM)

LOCATED PER PLANS

CORNER POST

OR GATE POST

x x x x x x x x

3"

5' WALK GATE

CVE-21005100-C002

SITE PLAN AND GENERAL NOTES

40' 0 40' 80"

SCALE: 1" = 40"

ADJ PROPERTY LINE

EXISTING CHAIN LINK FENCE

PROPOSED CHAIN LINK FENCE

TEMPORARY CHAIN LINK FENCE

TREES/SHRUBS

REFERENCE POINT FROM SURVEY

PROPOSED SIGN

J

LEGEND

NOTES

1. REMOVE ALL MESQUITE BRUSH/SHRUBS INSIDE CLEAR ZONE THAT WILL INTERFERE WITH

PROPER CONSTRUCTION OF THE FENCE. CONTRACTOR TO CONFIRM BRUSH REMOVAL WITH SSC

MANAGER AND SITE TECHNICIAN. FILL ANY HOLES WITH CLEAN FILL DIRT TO 80% COMPACTION

TO MATCH EXISTING GROUND PRIOR TO WORK COMMENCING.

2. INSTALL 3,071 LF 8' HIGH TOTAL SECURITY FENCE WITH 3 BARBED WIRE

TOP PER DETAILS ON SHEET CVE-21005100-C003. INSTALL (1) 12' WIDE DOUBLE

LEAF GATE AND (1) 24' WIDE DOUBLE LEAF GATE PER DETAILS ON SHEET CVE-21005100-C003.

3. INSTALL (1) 5' WALK GATE PER DETAILS ON SHEET CVE-21005100-C004 WITH 10" X 14"

EMERGENCY USE ONLY SIGN AND KNOX BOX. KNOX BOX TO BE INSTALLED PER LOCAL FIRE

DEPARTMENT REQUIREMENTS AND DIRECTIONS.

4. FOR GROUNDING: INSTALL DOUBLE LEAF GATE, WALK GATE, AND PERIMETER FENCE PER

DETAILS ON SHEET CVE-21005100-C004. FOR PORTIONS OF THE FENCE THAT ARE LOCATED

WITHIN 22 FEET OF A FACILITY EES SHALL BE BONDED TO THAT EES WITH A 4/0 AWG BARE

COPPER CONDUCTOR EXOTHERMICALLY WELDED TO A FENCE POST GROUND ROD. ALL

CONNECTIONS SHALL BE MADE AT A MAXIMUM SPACING OF 100', WITH A MINIMUM OF TWO

CONNECTIONS.

5. INSTALL (4) 12" X 18" NO PARKING TOWING ENFORCED SIGNS EVERY 300' ON EAST FENCE AS

INDICATED IN PLANS.

6. INSTALL GEOTEXTILE FABRIC, AND GRAVEL TO STERILIZE THE GROUND AGAINST PLANT GROWTH

IN THE CLEAR ZONE AS INDICATED IN PLANS.

EXISTING GRAVEL ROAD

22,000 SF CLEARZONE

FOR CREEK

INSTALL

(4) - 12" X 18"

NO PARKING TOW AWAY

SIGNS AT 300' APART

1 1 1 1

INSTALL

(1) - 10" X 14"

FOR FIRE OR EMERGENCY USE

ONLY SIGN ON WALK GATE

cve-21005100-c002

2023-03-21T15:49:45-0500

FEKADU M WAKTOLA

2023-03-10T10:28:26-0600

BRITTANY ALEXIS COMER-MATHIS

FENCE CORNER

0.3' S. & 0.1' W. OF

3.8''

GRAVEL

BCK PROPERTIES JOINT VENTURE

VOL 94039 PG 2523

(MAXIMUM)

CL CL

#9 AWG GALVANIZED

CHAIN LINK 2" MESH

3 STRANDS BARBED

TOP RAIL CONTINUOUS

PRESSED STEEL TOP

PINNED TO POST

LOCK WIRE FOR BARB WIRE

PLACED INSIDE ARM

10'-0" TO

(MAXIMUM)

CL CL

END POST

OR CORNER POST

TENSION WIRE #9

INSTALLED TO

TIE FABRIC TO TENSION

WIRE 14" O.C.; FABRIC TO

POSTS 14" O.C.MAX.

ABOVE

CROWN 1"

(TYPICAL)

GRADE

INTRUDER GUARD

OUTWARD FROM GOVERNMENT

PROPERTY

LINE POST

10'-0" TO

PULL POST

1'-0"

WIRE 4-PT. 4" C-C

1 2/3" DIAMETER

2 3/8" STANDARD PIPE

GA. WITHIN 4"

FROM THE GROUND

Y

2" MAX. OF FINISHED FIRM

SURFACE, PREFERABLE 1" OR LESS

FABRIC SHALL BE

TURNBUCKLE

(TYPICAL)

BRACE

SECURE BARBED SELVAGES

SEE SWING GATE POST DATA

BRICK OR CONCRETE

BLOCK FURNISHED

BY CONTRACTOR

1 5/8"

3/8" O

HOOK

BOLTS

12' GATE

(OPENING BETWEEN POSTS)

AND A MAXIMUM OF

GATE FRAME 1 1/2" STD. PIPE

TRUSS

RODS

130 BOTH WAYS)

NOT TO SCALE

(GATE TO SWING A MINIMUM 100

INSIDE ELEVATION CLASS "F" CHAIN LINK FENCE AND GATES

4" MAX.

AT TOP & BOTTOM

TENSION ROD

#9 GAUGE

REINFORCEMENT

#9 TIE WIRE 12"

C. TO C. APPROX.

33/4

13/8" O.D.

PLUNGER ROD

12' TO 24" GATE (OPENING BETWEEN POSTS)

DOUBLE LEAF

(GATE LEAF TO SWING A MINIMUM OF 100

AND A MAXIMUM OF 150 )

3 3/4"

OR GATE POST

LATCH FORK FORK CATCHER PADLOCK KEEPER

1 2 3

PADLOCK KEEPER

GUIDE

PLUNGE ROD

CATCH TOP HINGE

4 5 6

BOTTOM HINGE GATE CATCH BALL TOP

7 8 9

RAILS AT END RAILS AT CORNER

CHAIN LINK

CONNECTION AT CORNER

BOTTOM CORNER

AND HINGE DETAIL

2-WAY CONDITION

3 WEDGE

PINS PER

BALL TOP

TO HOLD GATE IN

OPEN POSITION

#4-AN PLUG

RIVETED TO GATE

BRACE OR

TOP RAIL

OFFSET

CUPS

STRETCHER BAR

3/4"x1/4" MIN.

STRETCHER

BAR BAND

EACH BAR

BAND (2 AT

LINE POST

STRAIGHT CUPSBRACE RAIL

BRACE OR

TOP RAILEND POST

STRAIGHT CUPS

1 5/8" O.D.

BRACE RAIL

USE FOR GATES ONLY IF INDICATED ON PLANS

14" O.C.

BAND

TENSION

TRUSS CONNECTION

AT TERMINAL POST

CONCRETE

FOOTING

3/8" DIA.

CORNER POST)

END ELEVATION

INSIDE

CHAIN LINK

FABRIC HEIGHT 84"

UNLESS OTHERWISE

NOTED

1 1/2"

BRACE BAND

STRAIGHT CUP

CONNECTION AT LINE POST

BRACE AND TENSION ROD

TIGHTENER

0'-10"

IM

BAR STRETCHER

CABLE BAND

SLOPED

FINISH

TWISTED AND BARBED SELVAGE

SURFACE

FINISHED FIRM

NOTES:

ALL METAL SHALL BE HOT DIPPED GALVANIZED.

FENCES AND GATES SHALL BE FURNISHED COMPLETE

WITH ALL NECESSARY FITTINGS.

FOR GATES - SIZES OF PIPES, SAG RODS AND

TURNBUCKLES SHALL BE MANUFACTURER'S STANDARD

WHICH ALSO MEET THE REQUIREMENTS OF THIS

DRAWING.

FENCE IS TO BE LOCATED SO THAT INTRUDER GUARD

DOES NOT OVERHANG PROPERTY LINE.

1.

2.

3.

4.

POSTS SHALL BE ROLLED OR EXTRUDED SECTIONS OR

TUBING OF STEEL OR ALUMINUM CAPABLE OF

WITHSTANDING A LATERAL FORCE OF 100 POUNDS

APPLIED AT THE TOP. ALL HOLLOW POSTS SHALL BE

CAPPED.

ALL CONCRETE SHALL BE 3000 LBS. WITH 3" SLUMP

AND 3/4" MAXIMUM SIZE AGGREGATE.

SECURITY MEASURES REQUIRE NO CLIMABLE OBJECTS

SHALL BE WITHIN 20 FEET OF THE FENCE. TREES

6.

7.

8.

5.

STANDARD PIPE SIZES INDICATED ARE NOMINAL

STANDARDS ASSOCIATION (ASA) B36.10.

OUTSIDE DIAMETER, SCHEDULE 40, PER AMERICAN

SHALL BE TRIMMED BACK OR REMOVED.

ALL FASTENING AND HINGE HARDWARE WILL BE SECURED IN

PLACE BY PEENING OR WELDING TO ALLOW PROPER

OPERATION OF OCMPONENTS BUT PREVENT DISASSEMBLY

9.

OF FENCING OR REMOVAL OF GATE. ALL POSTS AND

STRUCTURAL SUPPORTS WILL BE LOCATED IN THE INNER

SIDE OF THE FENCING.

10.

BOND THE BARBED WIRE TO THE FENCE POSTS AT

#6 STRANDED TINNED COPPER CONDUIT AND UL LISTED

BONDING CONNECTORS.

INTERVALS NO MORE THAN 100 FEET USING

x x x x x x x

5'-0"

WALK GATE DETAIL

WALK GATE STOP AND REST

DETERMINED

TO BE FIELD

CVE-21005100-C004

ON SHEET

SEE ADDITIONAL DETAILS

t t e d b

CVE-21005100-C003

CHAIN LINK FENCE DETAILS

SEE VIEWPORT ABOVE

cve-21005100-c003

2023-03-21T15:49:55-0500

FEKADU M WAKTOLA

2023-03-10T10:29:50-0600

BRITTANY ALEXIS COMER-MATHIS

NOTE 3

NOTE 4 NOTE 4

NOTE 2 NOTE 6

NOTE 1

NOTE 2

NOTE 5

CHAIN LINK FABRIC

" DIA TRUSS RODS (TYP)8

NOTE 7

NOTE 4

NOTE 6

THE FENCE

PERPENDICULAR TO

POWER LINE CROSSING

t t e d b

5'-0"

3"

CVE-21005100-C004

GATE & FENCE GROUNDING DETAILS

C004 NOT TO SCALE

DOUBLE LEAF GATE GROUNDING DETAIL

WALK GATE GROUNDING DETAILS & MISCELLANEOUS

1. INSTALL 10' X 3/4" COPPER CLAD GROUND ROD AT BOTH GATE

POSTS.

2. EXOTHERMICALLY WELD A 4/0 AWG JUMPER FROM THE GATE

FENCE POST TO THE NEAREST MAIN POST.

3. MECHANICALLY CONNECT OR WELD THE HORIZONTAL 6 AWG

CONDUCTOR TO THE FENCE POST AT ALL CORNERS, GATE

POSTS, AND AT INTERVALS NO GREATER THAN 40 FEET.

4. MECHANICALLY BOND EACH STRAND OF SECURITY WIRE TO

THE FENCE POST AT ALL CORNERS, GATE POSTS, AND AT

INTERVALS NO GREATER THAN 100 FEET.

5. INSTALL 4/0 AWG CONDUCTOR BELOW GRADE TO

INTERCONNECT BOTH SIDES.

6. CONNECT NEW EES BELOW GRADE TO EXISTING EES

AROUND THE TOWER BASE TO INTERCONNECT.

1. INSTALL 10' X 3/4" COPPER CLAD GROUND RODS AT ALL CORNERS,

GATE POSTS, AND AT INTERVALS NO GREATER THAN 100 FEET.

2. EXOTHERMICALLY WELD EACH GROUND ROD TO THE NEAREST

FENCE POST IN THE LOCATIONS STATED ABOVE. EACH GROUND

ROD SHALL BE SPACED AT LEAST 10 HORIZONTAL FEET APART.

3. MECHANICALLY CONNECT OR WELD THE HORIZONTAL 6 AWG

POSTS, AND AT INTERVALS NO GREATER THAN 100 FEET.

4. MECHANICALLY BOND EACH STRAND OF SECURITY WIRE TO

PERIMETER GROUNDING DETAIL

UL LISTED MECHANICAL CONNECTORS

EXOTHERMIC WELD

SPLIT BOLT MECHANICAL CONNECTION

6 AWG TINNED STRANDED COPPER CONDUCTOR

4/0 AWG BARE STRANDED COPPER CONDUCTOR

MECHANICALLY BOND EACH STRAND OF SECURITY WIRE TO 8.

SECTION.

LENGTH OF COPPER BRAID BETWEEN THE GATE POST AND GATE

GATE TO GATE POST BY MECHANICALLY CLAMPING AN ADEQUATE

STOPS AND CENTER REST AT 6" ABOVE GRADE. GROUND THE

GALVANIZED MATERIAL WITH PIVOT TYPE HINGES, CATCH

WALK GATE SHALL BE MADE TO MIMIC DOUBLE LEAF GATE 7.

INSTALLED ADJACENT TO THE FENCE LINE AND CONCRETE PIER.

CONDUIT SHALL EXTEND 3" ABOVE GRADE, AND SHALL BE

EXTEND ABOVE GRADE TO THE POST CONNECTIONS. THE

PROTECTION OF GROUNDING CONDUCTORS WHERE THEY

" X 15" RIGID PVC CONDUIT FOR MECHANICAL 4

INSTALL 6.

AROUND THE TOWER BASE TO INTERCONNECT.

CONNECT NEW EES BELOW GRADE TO EXISTING EES 5.

INTERCONNECT BOTH SIDES.

INSTALL 4/0 AWG CONDUCTOR BELOW GRADE TO 4.

POSTS, AND AT INTERVALS NO GREATER THAN 100 FEET.

MECHANICALLY CONNECT OR WELD THE HORIZONTAL 6 AWG 3.

FENCE POST TO THE NEAREST MAIN POST.

EXOTHERMICALLY WELD A 4/0 AWG JUMPER FROM THE GATE 2.

POSTS.

INSTALL 10' X 3/4" COPPER CLAD GROUND ROD AT EACH GATE 1.

FENCE GROUNDING AT PERPENDICULAR POWER LINE CROSSING

1. WHERE THE 4 AWG IS BEING INSTALLED, IT IS NOT

NECESSARY TO INSTALL THE 6 AWG TO BOND THE SECURITY WIRE.

2. FOR POWERLINES RUNNING PARALLEL WITH THE FENCE

AND WITHIN THE HEIGHT OF THE POWER POLES TO THE FENCE,

BOND THE FENCE WITH 4 AWG AS SHOWN IN THE FOLLOWING

LOCATIONS:

- AT A GROUND ROD THAT IS A MINIMUM OF 20' OUTSIDE

OF THE LOCATIONS WHERE THE FENCE AND POWERLINES

FIRST RUN PARALLEL.

- AT 40' INTERVALS, COINCIDING WITH THE INSTALLATION

OF GROUND RODS.

cve-21005100-c004

2023-03-21T15:50:03-0500

FEKADU M WAKTOLA

2023-03-10T10:28:44-0600

BRITTANY ALEXIS COMER-MATHIS

t t e d b

CVE VOR - DALLAS, TEXAS

T OF TRANSPO

T A

IO

IC

OF

STATES

IT

P A

TM

EN

AVIA

LA

TRAT

SI

NI

IG

LYNDON B JOHNSON FWY 635

ROYAL LANE

JOE FIELD ROAD

VICINITY MAP

PROPERTY ADDRESS:

2226 JOE FIELD ROAD

DALLAS, TX 75229

CVE-21005100-G001

COVER SHEET

-g cve-21005100-g001

2023-03-21T15:49:28-0500

FEKADU M WAKTOLA

2023-03-10T10:20:56-0600

BRITTANY ALEXIS COMER-MATHIS

File details come from the government source that posted it. Updated .