CVAMC Lightning Risk Assessment Data JMEdit.pdf
PDF 79 KB Posted
- Solicitation number
- 36C25922R0089
About this file
This document contains a lightning risk assessment and related federal contract opportunity for lightning protection system installation. The risk assessment evaluates fourteen buildings and site structures on the Cheyenne VA Medical Center campus and recommends installation of lightning protection systems. The related federal contract opportunity is a solicitation to procure design, installation, testing and commissioning services for lightning protection systems on the identified buildings and structures. Relevant locations include the RRTP, CLC, buildings A, B, C, 45, CA, CX, AR, the MRI building, building 11, warehouses 12 and 13, the switchgear building 31, photovoltaic canopies, a fueling station and oxygen storage tank. The solicitation is designated Z2DA-T2 DB 442-22-004 and is issued by the Department of Veterans Affairs Veterans Health Administration VISN 19 for lightning protection system installation in response to recommendations from a 2019 facility condition assessment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25922R0089 0001.docx | DOCX document | |
| Site Specific Lightning Protection Specifications - updated.pdf | ||
| 3-10-2021 - Past Performance Questionnaire.docx | DOCX document | |
| 36C25922R0089_1.docx | DOCX document | |
| Cheyenne_VAMC_LRA.pdf | ||
| Site Specific Lightning Protection Specifications.docx | DOCX document | |
| NEW - Calculation Worksheet for Self-Performed and Subcontracted Work.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Building
No.
Building Name Year Built Floor SqFt Length Width
Height (Roof
Peak) from
Finished
Grade
Max.
Chimney/Towe r Height
(beyond peak roof height)
Notes related to column
'I'
Lightning
Ground
Flash
Density
(flsh/km2/y r)
Material
Type
Roof
Material
Type
Structural
Contents
Structural
Occupancy
Lightning
Consequence
Lightning
Protection
System
Recommended?
1-A/1-B Cowboy 1932 Bsmt 29,782 65'-6" 8' flight pattern beacon for airforce/airport 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Difficult to
Evacuate / Risk of Panic
Continuity of
Services Required, No environmental hazard
YES
1F 34,280
2F 27,890
3F 26,410
4F 19,705
1-C Douglas Fir 1958 Bsmt 13,250 39' 15'
2 way radio antenna anchored to side of masonry builidng extending approximately 15' above highest peak 1.5 Nonmetallic Nonmetallic
High Value and
Moderately
Combustible
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
1F 14,165
2F 12,620
1-CA Buffalo 1990 Bsmt 28,530 50' 30'
2 way radio antenna anchored to side of masonry building extending approximately 30' above highest peak, apparently was struck by lightning 7 years ago according to Facilities Technician 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
1F 46,180
2F 32,450
3F 14,790
1-CX Arrowhead (PT/Specialty) 2006 1F 5,270 40' 8' antenna 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
2F 4,840
Cheyenne VAMC Lightning Risk Assessment Data
1-AR Arrowhead (Primary Care) 2012 1F 24,440 40' 8' antenna 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
1-CLC Community Living Center 2019 1F 12,000 35' 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
1-MRI MRI Building 2017 1F 4,070 16' 3' mechanical Equipment 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
Bldg 45 Douglas Fir (VBA) 1995 1F 11,340 23' 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
RRTP RRTP 2016 1F 14,580 20' 1' vents 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials
Normally
Occupied
Continuity of
Services Required, No environmental hazard
YES
376,592
4 Offices 1932 Bsmt 1,085 60' 65' 20' 2' vents 1.5 Nonmetallic Nonmetallic
Standard
Value, Non-combustible
Normally
Occupied
Continuity of
Services Not
Required, No environmental hazard
OPTIONAL
1F 3,960
2F 1,620
5 Offices 1952 Bsmt 1,430 25 80 16' 1' vents 1.5 Nonmetallic Nonmetallic
Standard
Value, Non-combustible
Normally
Occupied
Continuity of
Services Not
Required, No environmental hazard
OPTIONAL
1F 2,030
6 Offices 1932 Bsmt 1,040 30 40 20' 2' vents 1.5 Nonmetallic Nonmetallic
Standard
Value, Non-combustible
Normally
Occupied
Continuity of
Services Not
Required, No environmental hazard
OPTIONAL
1F 1,200
7 Offices 1932 Bsmt 2,200 35' 35' 24' 2' vents 1.5 Nonmetallic Nonmetallic
Standard
Value, Non-combustible
Normally
Occupied
Continuity of
Services Not
Required, No environmental hazard
OPTIONAL
Bldg 1 Total
1F 1,460
2F 910
8 Offices 1932 Bsmt 620 30' 35' 16' 1' vents 1.5 Nonmetallic Nonmetallic
Standard
Value, Non-combustible
Normally
Occupied
Continuity of
Services Not
Required, No environmental hazard
OPTIONAL
1F 1,100
11 Offices 1932 1F 3,780 100' 44' 37' 2' vents 1.5 Nonmetallic Nonmetallic
Standard
Value, Non-combustible
Normally
Occupied
Continuity of
Services Not
Required, No environmental hazard
YES
2F 3,350
12 Warehouse 1932 Bsmt 6,400 100' 50' 25' 10' site light approximately 3' from face of roof fascia/gutters 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials Unoccupied
Continuity of
Services Required, No environmental hazard
YES
1F 5,930
13 Boiler Plant 1932 Bsmt 6,650 67' 40' 33' 10' site light approximately 3' from face of roof fascia/gutters 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials Unoccupied
Continuity of
Services Required, No environmental hazard
YES
1F 3,000
Grounds Shop Insulated
Metal Bldg 2009? 1F 3,790 60 50 12' 4' exhaust stack 1.5 Metallic Metallic
Exceptional
Value, Flammable
Materials Unoccupied
Continuity of
Services Not
Required, No environmental hazard
OPTIONAL
31 Switchgear 2005? 1F 615 30 20 12 1' antenna 1.5 Nonmetallic Nonmetallic
Exceptional
Value, Flammable
Materials Unoccupied
Continuity of
Services Required, No environmental hazard
YES
52,170
428,762Site Total
Outbuilding Total