CVAMC Lightning Risk Assessment Data JMEdit.pdf

PDF 79 KB Posted

Attached to
Z2DA--T2 DB 442-22-004 Add Lightning Protection to campus (VA-22-00068380)
Solicitation number
36C25922R0089
Issued by

About this file

This document contains a lightning risk assessment and related federal contract opportunity for lightning protection system installation. The risk assessment evaluates fourteen buildings and site structures on the Cheyenne VA Medical Center campus and recommends installation of lightning protection systems. The related federal contract opportunity is a solicitation to procure design, installation, testing and commissioning services for lightning protection systems on the identified buildings and structures. Relevant locations include the RRTP, CLC, buildings A, B, C, 45, CA, CX, AR, the MRI building, building 11, warehouses 12 and 13, the switchgear building 31, photovoltaic canopies, a fueling station and oxygen storage tank. The solicitation is designated Z2DA-T2 DB 442-22-004 and is issued by the Department of Veterans Affairs Veterans Health Administration VISN 19 for lightning protection system installation in response to recommendations from a 2019 facility condition assessment.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Building

No.

Building Name Year Built Floor SqFt Length Width

Height (Roof

Peak) from

Finished

Grade

Max.

Chimney/Towe r Height

(beyond peak roof height)

Notes related to column

'I'

Lightning

Ground

Flash

Density

(flsh/km2/y r)

Material

Type

Roof

Material

Type

Structural

Contents

Structural

Occupancy

Lightning

Consequence

Lightning

Protection

System

Recommended?

1-A/1-B Cowboy 1932 Bsmt 29,782 65'-6" 8' flight pattern beacon for airforce/airport 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Difficult to

Evacuate / Risk of Panic

Continuity of

Services Required, No environmental hazard

YES

1F 34,280

2F 27,890

3F 26,410

4F 19,705

1-C Douglas Fir 1958 Bsmt 13,250 39' 15'

2 way radio antenna anchored to side of masonry builidng extending approximately 15' above highest peak 1.5 Nonmetallic Nonmetallic

High Value and

Moderately

Combustible

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

1F 14,165

2F 12,620

1-CA Buffalo 1990 Bsmt 28,530 50' 30'

2 way radio antenna anchored to side of masonry building extending approximately 30' above highest peak, apparently was struck by lightning 7 years ago according to Facilities Technician 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

1F 46,180

2F 32,450

3F 14,790

1-CX Arrowhead (PT/Specialty) 2006 1F 5,270 40' 8' antenna 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

2F 4,840

Cheyenne VAMC Lightning Risk Assessment Data

1-AR Arrowhead (Primary Care) 2012 1F 24,440 40' 8' antenna 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

1-CLC Community Living Center 2019 1F 12,000 35' 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

1-MRI MRI Building 2017 1F 4,070 16' 3' mechanical Equipment 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

Bldg 45 Douglas Fir (VBA) 1995 1F 11,340 23' 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

RRTP RRTP 2016 1F 14,580 20' 1' vents 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials

Normally

Occupied

Continuity of

Services Required, No environmental hazard

YES

376,592

4 Offices 1932 Bsmt 1,085 60' 65' 20' 2' vents 1.5 Nonmetallic Nonmetallic

Standard

Value, Non-combustible

Normally

Occupied

Continuity of

Services Not

Required, No environmental hazard

OPTIONAL

1F 3,960

2F 1,620

5 Offices 1952 Bsmt 1,430 25 80 16' 1' vents 1.5 Nonmetallic Nonmetallic

Standard

Value, Non-combustible

Normally

Occupied

Continuity of

Services Not

Required, No environmental hazard

OPTIONAL

1F 2,030

6 Offices 1932 Bsmt 1,040 30 40 20' 2' vents 1.5 Nonmetallic Nonmetallic

Standard

Value, Non-combustible

Normally

Occupied

Continuity of

Services Not

Required, No environmental hazard

OPTIONAL

1F 1,200

7 Offices 1932 Bsmt 2,200 35' 35' 24' 2' vents 1.5 Nonmetallic Nonmetallic

Standard

Value, Non-combustible

Normally

Occupied

Continuity of

Services Not

Required, No environmental hazard

OPTIONAL

Bldg 1 Total

1F 1,460

2F 910

8 Offices 1932 Bsmt 620 30' 35' 16' 1' vents 1.5 Nonmetallic Nonmetallic

Standard

Value, Non-combustible

Normally

Occupied

Continuity of

Services Not

Required, No environmental hazard

OPTIONAL

1F 1,100

11 Offices 1932 1F 3,780 100' 44' 37' 2' vents 1.5 Nonmetallic Nonmetallic

Standard

Value, Non-combustible

Normally

Occupied

Continuity of

Services Not

Required, No environmental hazard

YES

2F 3,350

12 Warehouse 1932 Bsmt 6,400 100' 50' 25' 10' site light approximately 3' from face of roof fascia/gutters 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials Unoccupied

Continuity of

Services Required, No environmental hazard

YES

1F 5,930

13 Boiler Plant 1932 Bsmt 6,650 67' 40' 33' 10' site light approximately 3' from face of roof fascia/gutters 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials Unoccupied

Continuity of

Services Required, No environmental hazard

YES

1F 3,000

Grounds Shop Insulated

Metal Bldg 2009? 1F 3,790 60 50 12' 4' exhaust stack 1.5 Metallic Metallic

Exceptional

Value, Flammable

Materials Unoccupied

Continuity of

Services Not

Required, No environmental hazard

OPTIONAL

31 Switchgear 2005? 1F 615 30 20 12 1' antenna 1.5 Nonmetallic Nonmetallic

Exceptional

Value, Flammable

Materials Unoccupied

Continuity of

Services Required, No environmental hazard

YES

52,170

428,762Site Total