CRFQ PSC27-03 - ADDENDUM NO. 02.PDF

PDF 1 MB Posted

Attached to
HVAC Upgrade and Ceiling Replacement
Solicitation number
CRFQ 0926 PSC2700000003 4
Issued by
Kanawha County, West Virginia

About this file

Summary

This is Addendum No. 02 to a Centralized Request for Quote (CRFQ) issued by the West Virginia Department of Administration Purchasing Division for the West Virginia Public Service Commission. The addendum modifies solicitation CRFQ PSC27-03 (version 3) for HVAC Upgrade and Ceiling Replacement work. The primary modification attaches updated and additional project plans containing revised technical documentation for the renovation project. The solicitation maintains the following key dates: a non-mandatory site visit on October 27, 2026, at 9:00 AM; vendor questions deadline of October 30, 2026, by 4:00 PM; and bid opening on November 10, 2026, at 1:30 PM. All bids are subject to the terms and conditions contained in the original solicitation and this addendum. Vendor acknowledgment of all addenda is required and must be submitted with bids to avoid potential disqualification. The procurement is located at 201 Brooks Street, Charleston, West Virginia, with the bid receiving location at the Department of Administration Purchasing Division, 2019 Washington Street East, Charleston, West Virginia. The architect of record is ZMM, Inc. Architects and Engineers (Project No. 25095).

The addendum includes comprehensive specification sections covering facility natural gas piping, water treatment for closed-loop hydronic systems, condensing boilers, wall and ceiling unit heaters, and a direct digital control (DDC) system for HVAC. The DDC system must be web-based with all controllers, software, licensing, installation, and warranty included for a minimum of three years beyond substantial completion. Bidders must be established building automation contractors with a minimum of ten years' experience, maintain an office within 100 miles of the project, be authorized distributors of specified manufacturers, and employ certified application engineers. Pre-approved contractors include Automated Logic (Premier Energy Systems), ASI Controls (RDS, Inc.), Schneider Electric (Mason & Barry), and Trane Controls. No pricing information, set-asides, incumbent data, or funding sources are specified in this addendum document.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Date Printed: Oct 23, 2026 Page: 1 FORM ID: WV-PRC-CRFQ-002 2020/05

Department of Administration Purchasing Division 2019 Washington Street East Post Office Box 50130 Charleston, WV 25305-0130

State of West Virginia Centralized Request for Quote

Construction

Proc Folder: 2076891 Reason for Modification:

Doc Description: HVAC Upgrade and Ceiling Replacement Addendum No. 02

Proc Type: Central Purchase Order

Date Issued Solicitation Closes Solicitation No Version

2026-10-23 2026-11-10 13:30 CRFQ 0926 PSC2700000003 3

BID RECEIVING LOCATION

BID CLERK

DEPARTMENT OF ADMINISTRATION

PURCHASING DIVISION

2019 WASHINGTON ST E

CHARLESTON WV 25305

US

VENDOR

Vendor Customer Code:

Vendor Name :

Address :

Street :

City :

State : Country : Zip :

Principal Contact :

Vendor Contact Phone: Extension:

FOR INFORMATION CONTACT THE BUYER

Larry D McDonnell 304-558-2063 larry.d.mcdonnell@wv.gov

Vendor Signature X FEIN# DATE

All offers subject to all terms and conditions contained in this solicitation

Date Printed: Oct 23, 2026 Page: 2 FORM ID: WV-PRC-CRFQ-002 2020/05

ADDITIONAL INFORMATION

Addendum No. 02

1. To attach the updated / additional project plans (revised technical documentation).

Please note this document may not be available at the locations listed in section 12 of the original specifications.

2. Second site visit date and time still remains October 27, 2026, at 9:00AM.

Please note this visit is a non-mandatory but attendance is highly encouraged.

3. Vendor question due date and time still remains October 30, 2026, by 4:00PM

4. Bid opening date and time still remains November 10, 2026, at 1:30PM.

No other changes

INVOICE TO SHIP TO

PUBLIC SERVICE

COMMISSION

PUBLIC SERVICE

COMMISSION

201 BROOKS ST 201 BROOKS ST

CHARLESTON WV CHARLESTON WV

US US

Line Comm Ln Desc Qty Unit Issue Unit Price Total Price 1 HVAC Upgrade and Ceiling Replacement

Comm Code Manufacturer Specification Model #

72151207

Extended Description:

See attached documentation for further details.

SCHEDULE OF EVENTS

Line Event Event Date

SOLICITATION NUMBER: CRFQ PSC27*03

Addendum Number: 02

The purpose of this addendum is to modify the solicitation identified as (“Solicitation”) to reflect the change(s) identified and described below.

Applicable Addendum Category:

[ ] Modify bid opening date and time

[ ] Modify specifications of product or service being sought

[] Attachment of vendor questions and responses

[ ] Attachment of pre-bid sign-in sheet

[ ] Correction of error

[X] Other

Description of Modification to Solicitation:

1. To attach the updated / additional project plans (revised technical documentation).

Please note this document may not be available at the locations listed in section 12 of the original specifications.

2. Second site visit date and time still remains October 27, 2026, at 9:00AM.

Please note this visit is a non-mandatory but attendance is highly encouraged.

3. Vendor question due date and time still remains October 30, 2026, by 4:00PM

4. Bid opening date and time still remains November 10, 2026, at 1:30PM.

No other changes

Additional Documentation: Documentation related to this Addendum (if any) has been included herewith as Attachment A and is specifically incorporated herein by reference.

Terms and Conditions:

1. All provisions of the Solicitation and other addenda not modified herein shall remain in full force and effect.

2. Vendor should acknowledge receipt of all addenda issued for this Solicitation by completing an Addendum Acknowledgment, a copy of which is included herewith. Failure to acknowledge addenda may result in bid disqualification. The addendum acknowledgement should be submitted with the bid to expedite document processing.

ADDENDUM ACKNOWLEDGEMENT FORM

SOLICITATION NO.: CRFQ PSC27*03

TO: Prospective Bidders

FROM: ZMM, Inc. Architects and Engineers

This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents.

ATTACH THIS ADDENDUM TO THE FRONT COVER OF THE PROJECT MANUAL AND ACKNOWLEDGE RECEIPT OF THIS ADDENDUM AS DIRECTED IN THE West Virginia Purchasing Request For Quotations (RFQ) .

PART 1 - CHANGES TO SPECIFICATIONS

A. REPLACE Table of Contents dated 10/05/26 with revised Table of Contents as attached to this Addendum.

B. ADD Specification Sections as listed in the Attachments to this Addendum.

END OF ADDENDUM

Attachments: Table of Contents (Revised) ..................................................................................... 4 pages Section 221124 “Facility Natural Gas Piping” ....................................................... 16 pages Section 232513 “Water Treatment for Closed-Loop Hydronic System” .................. 6 pages Section 235216 “Condensing Boilers” ..................................................................... 9 pages Section 238239.19 “Wall and Ceiling Unit Heaters” ............................................... 3 pages Section 250923 “Direct Digital Control (DDC) System for HVAC” ..................... 60 pages Section 250993 “Sequence of Operations for HVAC DDC”.................................. 13 pages

October 22, 2026

ADDENDUM NO. 2

RE: Renovations for Office Buildings

Public Service Commission of West Virginia Department of Administration General Services Division Charleston, West Virginia Architect’s Project No. 25095

Renovations for WV PSC Office Building

Document Description Pages

ZMM LLC Architects Engineers Renovations for WV PSC Office Building 222 Lee Street West, Charleston, West Virginia West Virginia Public Service Commission ZMM Project Number 25095 1116 Quarrier Street, Charleston, WV Date: 10/22/26 Page 1 of 4

Table of Contents (revised)– Added sections appear in italics.

Requirements

Request For Quotation, (Issued by the WV State Purchasing Division, Incorporated by Cross Reference Only) includes the following:

1. Instructions To Vendors Submitting Bids

2. General Terms and Conditions

3. Additional Terms and Conditions (Construction Contracts Only)

4. Subcontractor List Submission Form

5. Addendum Acknowledgement Form

6. Request For Quotation

7. Construction Bid Submission Review Form

8. Disclosure of Interested Parties to Contracts

9. Certification and Signature Page

Bidding Requirements

Professional Seals Advertisement For Bids Viewing Depositories for Bidding Documents

HAZMAT Release Form Bid Bond and Bid Bond Instructions Performance Bond and Instructions Labor and Materials Payment Bond and Instructions Maintenance Bond and Instructions West Virginia Drug-Free Workplace Cover Sheet and Conformance Affidavit (WV-73) Vendor Registration and Disclosure Statement Notice of Defective or Non-Conforming Work Resolution of Defective or Non-Conforming Work Notice of Non-Compliance with Project Requirements Resolution of Non-Compliance with Project Requirements Notice of Breach of Contract

Contract Forms

AIA A101 Standard Form of Agreement Between Owner and Contractor 2017 AIA A101 Exhibit A Insurance and Bonds 2017 AIA G701 Change Order 2017 AIA G702 Application and Certificate for Payment 1992 AIA G703 Continuation Sheet 1992 AIA G704 Certificate of Substantial Completion 2017

ZMM Project Number 25095 1116 Quarrier Street, Charleston, WV Date: 10/22/26 Page 2 of 4

AIA G706 Contractor’s Affidavit of Payment of Debts and Claims 1994 AIA G706A Contractor’s Affidavit of Release of Liens 1994 AIA G707 Consent of Surety to Final Payment 1994 AIA G707A Consent of Surety to Reduction in or Partial Release of Retainage 1994 AIA G709 Work Changes Proposal Request 2001 AIA G710 Architect’s Supplemental Instructions 2017 AIA G714 Construction Change Directive 2017 AIA G715 Supplemental Attachment for ACORD Certificate of Insurance 2017 AIA G716 Request For Information (RFI) 2004

Contract Conditions .

AIA A201 General Conditions of the Contract for Construction 2017 West Virginia Supplementary Conditions Sample Certificate of Liability Insurance Sample Certificate of Property Insurance Specifications

Division 01 – General Requirements .

011000 Summary 012500 Substitution Procedures Request For Substitution(After Bid) 012600 Contract Modification Procedures 012900 Payment Procedures 013100 Project Management and Coordination 013200 Construction Progress Documentation 013300 Submittal Procedures Submittal Cover Sheet Submittal Deviation Sheet 014000 Quality Requirements 014200 References 015000 Temporary Facilities and Controls 016000 Product Requirements 017300 Execution 017700 Closeout Procedures 017823 Operation and Maintenance Data 017839 Project Record Documents 017900 Demonstration and Training

Division 02 – Existing Conditions

024119 Selective Demolition

Division 03 – 04 (Not Used)

ZMM Project Number 25095 1116 Quarrier Street, Charleston, WV Date: 10/22/26 Page 3 of 4

Division 05 – Metals .

055000 Metal Fabrications

Division 06 – Wood, Plastics, and Composites

061000 Rough Carpentry

Division 07 – Thermal and Moisture Protection

075323 EPDM Membrane Roofing 076200 Sheet Metal Flashing and Trim 077100 Roofing Specialties 077200 Roof Accessories 078413 Penetration Firestopping 079200 Joint Sealants

Division 08 – Openings

083113 Access Doors and Frames

Division 09 – Finishes

092216 Non-Structural Metal Framing 092900 Gypsum Board 095113 Acoustical Panel Ceilings 099113 Exterior Painting 099123 Interior Painting

Division 10 – 14 (Not Used)

(Green Pages)

Division 20 – General Mechanical

200100 Common Work Results for General Mechanical 200523 General Duty Valves for General Mechanical Piping 200529 Hangers and Supports for General Mechanical Piping & Equip 200548 Vibration Controls for General Mechanical 200553 Identification for General Mechanical Piping & Equipment 200593 Testing, Adjusting, and Balancing for HVAC 200716 General Mechanical Equipment Insulation 200719 General Mechanical Piping Insulation

Division 21 (Not Used)

ZMM Project Number 25095 1116 Quarrier Street, Charleston, WV Date: 10/22/26 Page 4 of 4

Division 22 – Plumbing

221124 Facility Natural Gas Piping

Division 23 – Heating, Ventilating, and Air Conditioning

230100 Common Specifications – General HVAC 230130 Existing HVAC Air Distribution System Cleaning 230713 Duct Insulation 232113 Hydronic Piping 232116 Hydronic Piping Specialties 232300 Refrigerant Piping 232513 Water Treatment for Closed-Loop Hydronic System 233113 Metal Ducts 233300 Air Duct Accessories 233400 HVAC Fans 233600 Air Terminal Units 233713 Air Diffusers, Registers and Grilles 235216 Condensing Boilers 237416 Packaged, Rooftop Air-Conditioning Units 238239 Units Heaters

238239.19 Wall and Ceiling Unit Heaters

Division 25 – HVAC Controls

250923 Direct Digital Control (DDC) System for HVAC 250993 Sequence of Operations for HVAC DDC

(Yellow Pages)

Division 26 – Electrical

260519 Conductors and Cables 260523 Control-Voltage Electrical Power Cables 260529 Hangers and Supports for Electrical Systems 260533 Raceways and Boxes 260544 Sleeves and Sleeve Seals for Electrical 260553 Electrical Identification 260600 Grounding and Bonding 262416 Panelboards 262816 Enclosed Switches and Circuit Breakers

End Table of Contents

FACILITY NATURAL-GAS PIPING 221124 - 1 25095

SECTION 221124

FACILITY NATURAL-GAS PIPING

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section Includes:

1. Pipes, tubes, and fittings.

2. Piping specialties.

3. Piping and tubing joining materials.

4. Valves.

1.3 DEFINITIONS

A. Finished Spaces: Spaces other than mechanical and electrical equipment rooms, furred spaces, pipe and duct shafts, unheated spaces immediately below roof, spaces above ceilings, unexcavated spaces, crawlspaces, and tunnels.

B. Exposed, Interior Installations: Exposed to view indoors. Examples include finished occupied spaces and mechanical equipment rooms.

C. Exposed, Exterior Installations: Exposed to view outdoors or subject to outdoor ambient temperatures and weather conditions. Examples include rooftop locations.

1.4 PERFORMANCE REQUIREMENTS

A. Minimum Operating-Pressure Ratings:

1. Piping and Valves: 100 psig minimum unless otherwise indicated.

B. Natural-Gas System Pressures: Primary pressure is 0.5 psig (3.45 kPa) or less.

1.5 ACTION SUBMITTALS

A. Product Data: For each type of the following:

1. Piping specialties.

FACILITY NATURAL-GAS PIPING 221124 - 2 25095

2. Corrugated, stainless-steel tubing with associated components.

3. Valves. Include pressure rating, capacity, settings, and electrical connection data of selected models.

4. Dielectric fittings.

1.6 INFORMATIONAL SUBMITTALS

A. Coordination Drawings: Plans and details, drawn to scale, on which natural-gas piping is shown and coordinated with other installations, using input from installers of the items involved.

B. Site Survey: Plans, drawn to scale, on which natural-gas piping is shown and coordinated with other services and utilities.

C. Qualification Data: For qualified professional engineer.

D. Welding certificates.

E. Field quality-control reports.

1.7 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For pressure regulators to include in emergency, operation, and maintenance manuals.

1.8 QUALITY ASSURANCE

A. Steel Support Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

B. Pipe Welding Qualifications: Qualify procedures and operators according to ASME Boiler and Pressure Vessel Code.

1.9 DELIVERY, STORAGE, AND HANDLING

A. Handling Flammable Liquids: Remove and dispose of liquids from existing natural-gas piping according to requirements of authorities having jurisdiction.

B. Deliver pipes and tubes with factory-applied end caps. Maintain end caps through shipping, storage, and handling to prevent pipe end damage and to prevent entrance of dirt, debris, and moisture.

C. Store and handle pipes and tubes having factory-applied protective coatings to avoid damaging coating, and protect from direct sunlight.

FACILITY NATURAL-GAS PIPING 221124 - 3 25095

1.10 PROJECT CONDITIONS

A. Interruption of Existing Natural-Gas Service: Do not interrupt natural-gas service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide purging and startup of natural-gas supply according to requirements indicated:

1. Notify Architect, Construction Manager, and Owner no fewer than two days in advance of proposed interruption of natural-gas service.

2. Do not proceed with interruption of natural-gas service without Owner's written permission.

PART 2 - PRODUCTS

2.1 PIPES, TUBES, AND FITTINGS

A. Steel Pipe: ASTM A 53/A 53M, black steel, Schedule 40, Type E or S, Grade B.

1. Malleable-Iron Threaded Fittings: ASME B16.3, Class 150, standard pattern.

2. Wrought-Steel Welding Fittings: ASTM A 234/A 234M for butt welding and socket welding.

3. Unions: ASME B16.39, Class 150, malleable iron with brass-to-iron seat, ground joint, and threaded ends.

4. Forged-Steel Flanges and Flanged Fittings: ASME B16.5, minimum Class 150, including bolts, nuts, and gaskets of the following material group, end connections, and facings:

a. Material Group: 1.1.

b. End Connections: Threaded or butt welding to match pipe.

c. Lapped Face: Not permitted underground.

d. Gasket Materials: ASME B16.20, metallic, flat, asbestos free, aluminum o-rings, and spiral-wound metal gaskets.

e. Bolts and Nuts: ASME B18.2.1, carbon steel aboveground and stainless steel underground.

5. Mechanical Couplings:

a. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

1) Dresser Piping Specialties; Division of Dresser, Inc.

2) Smith-Blair, Inc.

b. Steel flanges and tube with epoxy finish.

c. Buna-nitrile seals.

d. Steel bolts, washers, and nuts.

e. Coupling shall be capable of joining PE pipe to PE pipe, steel pipe to PE pipe, or steel pipe to steel pipe.

f. Steel body couplings installed underground on plastic pipe shall be factory equipped with anode.

http://www.specagent.com/LookUp/?ulid=3307&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824941&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812126&mf=95&src=wd

FACILITY NATURAL-GAS PIPING 221124 - 4 25095

B. Corrugated, Stainless-Steel Tubing: Comply with ANSI/IAS LC 1.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. OmegaFlex, Inc.

b. Parker Hannifin Corporation; Parflex Division.

c. Titeflex.

d. Tru-Flex Metal Hose Corp.

2. Tubing: ASTM A 240/A 240M, corrugated, Series 300 stainless steel.

3. Coating: PE with flame retardant.

a. Surface-Burning Characteristics: As determined by testing identical products according to ASTM E 84 by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.

1) Flame-Spread Index: 25 or less.

2) Smoke-Developed Index: 50 or less.

4. Fittings: Copper-alloy mechanical fittings with ends made to fit and listed for use with corrugated stainless-steel tubing and capable of metal-to-metal seal without gaskets.

Include brazing socket or threaded ends complying with ASME B1.20.1.

5. Striker Plates: Steel, designed to protect tubing from penetrations.

6. Manifolds: Malleable iron or steel with factory-applied protective coating. Threaded connections shall comply with ASME B1.20.1 for pipe inlet and corrugated tubing outlets.

7. Operating-Pressure Rating: 5 psig (34.5 kPa).

C. Drawn-Temper Copper Tube: Comply with ASTM B 88, Type L (ASTM B 88M, Type B).

1. Copper Fittings: ASME B16.22, wrought copper, and streamlined pattern.

2. Bronze Flanges and Flanged Fittings: ASME B16.24, Class 150.

a. Gasket Material: ASME B16.20, metallic, flat, asbestos free, aluminum o-rings, and spiral-wound metal gaskets.

b. Bolts and Nuts: ASME B18.2.1, carbon steel or stainless steel.

3. Protective Coating for Underground Tubing: Factory-applied, extruded PE a minimum of

0.022 inch (0.56 mm) thick.

D. Annealed-Temper Copper Tube: Comply with ASTM B 88, Type L (ASTM B 88M, Type B).

1. Copper Fittings: ASME B16.22, wrought copper, and streamlined pattern.

2. Flare Fittings: Comply with ASME B16.26 and SAE J513.

a. Copper fittings with long nuts.

b. Metal-to-metal compression seal without gasket.

c. Dryseal threads complying with ASME B1.20.3.

http://www.specagent.com/LookUp/?ulid=3308&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812127&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824944&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812128&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812129&mf=95&src=wd

FACILITY NATURAL-GAS PIPING 221124 - 5 25095

3. Protective Coating for Underground Tubing: Factory-applied, extruded PE a minimum of

0.022 inch (0.56 mm) thick.

2.2 PIPING SPECIALTIES

A. Appliance Flexible Connectors:

1. Indoor, Fixed-Appliance Flexible Connectors: Comply with ANSI Z21.24.

2. Indoor, Movable-Appliance Flexible Connectors: Comply with ANSI Z21.69.

3. Outdoor, Appliance Flexible Connectors: Comply with ANSI Z21.75.

4. Corrugated stainless-steel tubing with polymer coating.

5. Operating-Pressure Rating: 0.5 psig (3.45 kPa).

6. End Fittings: Zinc-coated steel.

7. Threaded Ends: Comply with ASME B1.20.1.

8. Maximum Length: 72 inches (1830 mm.)

B. Quick-Disconnect Devices: Comply with ANSI Z21.41.

1. Copper-alloy convenience outlet and matching plug connector.

2. Nitrile seals.

3. Hand operated with automatic shutoff when disconnected.

4. For indoor or outdoor applications.

5. Adjustable, retractable restraining cable.

C. Y-Pattern Strainers:

1. Body: ASTM A 126, Class B, cast iron with bolted cover and bottom drain connection.

2. End Connections: Threaded ends for NPS 2 (DN 50) and smaller; flanged ends for

NPS 2-1/2 (DN 65) and larger.

3. Strainer Screen: 40 mesh startup strainer, and perforated stainless-steel basket with 50 percent free area.

4. CWP Rating: 125 psig (862 kPa).

D. Basket Strainers:

1. Body: ASTM A 126, Class B, high-tensile cast iron with bolted cover and bottom drain connection.

2. End Connections: Threaded ends for NPS 2 (DN 50) and smaller; flanged ends for NPS 2-1/2 (DN 65) and larger.

3. Strainer Screen: 40 mesh startup strainer, and perforated stainless-steel basket with 50 percent free area.

4. CWP Rating: 125 psig (862 kPa).

E. T-Pattern Strainers:

1. Body: Ductile or malleable iron with removable access coupling and end cap for strainer maintenance.

2. End Connections: Grooved ends.

3. Strainer Screen: 40 mesh startup strainer, and perforated stainless-steel basket with 57 percent free area.

FACILITY NATURAL-GAS PIPING 221124 - 6 25095

4. CWP Rating: 750 psig (5170 kPa).

2.3 JOINING MATERIALS

A. Joint Compound and Tape: Suitable for natural gas.

B. Welding Filler Metals: Comply with AWS D10.12/D10.12M for welding materials appropriate for wall thickness and chemical analysis of steel pipe being welded.

C. Brazing Filler Metals: Alloy with melting point greater than 1000 deg F (540 deg C) complying with AWS A5.8/A5.8M. Brazing alloys containing more than 0.05 percent phosphorus are prohibited.

2.4 MANUAL GAS SHUTOFF VALVES

A. See "Aboveground Manual Gas Shutoff Valve Schedule" Article for where each valve type is applied in various services.

B. General Requirements for Metallic Valves, NPS 2 (DN 50) and Smaller: Comply with

ASME B16.33.

1. CWP Rating: 125 psig (862 kPa).

2. Threaded Ends: Comply with ASME B1.20.1.

3. Dryseal Threads on Flare Ends: Comply with ASME B1.20.3.

4. Tamperproof Feature: Locking feature for valves indicated in "Aboveground Manual Gas

Shutoff Valve Schedule" Article.

5. Listing: Listed and labeled by an NRTL acceptable to authorities having jurisdiction for valves 1 inch (25 mm) and smaller.

6. Service Mark: Valves 1-1/4 inches (32 mm) to NPS 2 (DN 50) shall have initials "WOG" permanently marked on valve body.

C. General Requirements for Metallic Valves, NPS 2-1/2 (DN 65) and Larger: Comply with

ASME B16.38.

1. CWP Rating: 125 psig (862 kPa).

2. Flanged Ends: Comply with ASME B16.5 for steel flanges.

3. Tamperproof Feature: Locking feature for valves indicated in "Aboveground Manual Gas

Shutoff Valve Schedule" Article.

4. Service Mark: Initials "WOG" shall be permanently marked on valve body.

D. One-Piece, Bronze Ball Valve with Bronze Trim: MSS SP-110.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. BrassCraft Manufacturing Company; a Masco company.

b. Conbraco Industries, Inc.; Apollo Div.

c. Lyall, R. W. & Company, Inc.

d. McDonald, A. Y. Mfg. Co.

http://www.specagent.com/LookUp/?ulid=3312&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824951&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824953&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812134&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812135&mf=95&src=wd

FACILITY NATURAL-GAS PIPING 221124 - 7 25095

e. Perfection Corporation; a subsidiary of American Meter Company.

2. Body: Bronze, complying with ASTM B 584.

3. Ball: Chrome-plated brass.

4. Stem: Bronze; blowout proof.

5. Seats: Reinforced TFE; blowout proof.

6. Packing: Separate packnut with adjustable-stem packing threaded ends.

7. Ends: Threaded, flared, or socket as indicated in "Aboveground Manual Gas Shutoff

Valve Schedule" Article.

8. CWP Rating: 600 psig (4140 kPa).

9. Listing: Valves NPS 1 (DN 25) and smaller shall be listed and labeled by an NRTL acceptable to authorities having jurisdiction.

10. Service: Suitable for natural-gas service with "WOG" indicated on valve body.

E. Two-Piece, Full-Port, Bronze Ball Valves with Bronze Trim: MSS SP-110.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. BrassCraft Manufacturing Company; a Masco company.

b. Conbraco Industries, Inc.; Apollo Div.

c. Lyall, R. W. & Company, Inc.

d. McDonald, A. Y. Mfg. Co.

e. Perfection Corporation; a subsidiary of American Meter Company.

2. Body: Bronze, complying with ASTM B 584.

3. Ball: Chrome-plated bronze.

4. Stem: Bronze; blowout proof.

5. Seats: Reinforced TFE; blowout proof.

6. Packing: Threaded-body packnut design with adjustable-stem packing.

7. Ends: Threaded, flared, or socket as indicated in "Aboveground Manual Gas Shutoff

Valve Schedule" Article.

8. CWP Rating: 600 psig (4140 kPa).

9. Listing: Valves NPS 1 (DN 25) and smaller shall be listed and labeled by an NRTL acceptable to authorities having jurisdiction.

10. Service: Suitable for natural-gas service with "WOG" indicated on valve body.

F. Two-Piece, Regular-Port Bronze Ball Valves with Bronze Trim: MSS SP-110.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. BrassCraft Manufacturing Company; a Masco company.

b. Conbraco Industries, Inc.; Apollo Div.

c. Lyall, R. W. & Company, Inc.

d. McDonald, A. Y. Mfg. Co.

e. Perfection Corporation; a subsidiary of American Meter Company.

2. Body: Bronze, complying with ASTM B 584.

3. Ball: Chrome-plated bronze.

4. Stem: Bronze; blowout proof.

http://www.specagent.com/LookUp/?uid=123456824954&mf=95&src=wd http://www.specagent.com/LookUp/?ulid=3313&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824955&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824956&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812136&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812137&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824958&mf=95&src=wd http://www.specagent.com/LookUp/?ulid=3314&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824959&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824961&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812138&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812139&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456824962&mf=95&src=wd

FACILITY NATURAL-GAS PIPING 221124 - 8 25095

5. Seats: Reinforced TFE.

6. Packing: Threaded-body packnut design with adjustable-stem packing.

7. Ends: Threaded, flared, or socket as indicated in "Aboveground Manual Gas Shutoff

Valve Schedule" Article.

8. CWP Rating: 600 psig (4140 kPa).

9. Listing: Valves NPS 1 (DN 25) and smaller shall be listed and labeled by an NRTL acceptable to authorities having jurisdiction.

10. Service: Suitable for natural-gas service with "WOG" indicated on valve body.

G. Bronze Plug Valves: MSS SP-78.

1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. Lee Brass Company.

b. McDonald, A. Y. Mfg. Co.

2. Body: Bronze, complying with ASTM B 584.

3. Plug: Bronze.

4. Ends: Threaded, socket, or flanged as indicated in "Aboveground Manual Gas Shutoff

Valve Schedule" Article.

5. Operator: Square head or lug type with tamperproof feature where indicated.

6. Pressure Class: 125 psig (862 kPa).

7. Listing: Valves NPS 1 (DN 25) and smaller shall be listed and labeled by an NRTL acceptable to authorities having jurisdiction.

8. Service: Suitable for natural-gas service with "WOG" indicated on valve body.

2.5 DIELECTRIC FITTINGS

A. General Requirements: Assembly of copper alloy and ferrous materials with separating nonconductive insulating material. Include end connections compatible with pipes to be joined.

B. Dielectric Unions:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Capitol Manufacturing Company.

b. Central Plastics Company.

c. Hart Industries International, Inc.

d. Jomar International Ltd.

e. Matco-Norca, Inc.

f. McDonald, A. Y. Mfg. Co.

g. Watts Regulator Co.; a division of Watts Water Technologies, Inc.

h. Wilkins; a Zurn company.

2. Description:

a. Standard: ASSE 1079.

http://www.specagent.com/LookUp/?ulid=3315&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812140&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812141&mf=95&src=wd http://www.specagent.com/LookUp/?ulid=3331&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812187&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812188&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812189&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812190&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812191&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812192&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456825024&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456825028&mf=95&src=wd

FACILITY NATURAL-GAS PIPING 221124 - 9 25095

b. Pressure Rating: 250 psig (1725 kPa).

c. End Connections: Solder-joint copper alloy and threaded ferrous.

C. Dielectric Flanges:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Capitol Manufacturing Company.

b. Central Plastics Company.

c. Matco-Norca, Inc.

d. Watts Regulator Co.; a division of Watts Water Technologies, Inc.

e. Wilkins; a Zurn company.

2. Description:

a. Standard: ASSE 1079.

b. Factory-fabricated, bolted, companion-flange assembly.

c. Pressure Rating: 300 psig (2070 kPa).

d. End Connections: Solder-joint copper alloy and threaded ferrous; threaded solder-joint copper alloy and threaded ferrous.

D. Dielectric-Flange Insulating Kits:

1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:

a. Advance Products & Systems, Inc.

b. Calpico, Inc.

c. Central Plastics Company.

d. Pipeline Seal and Insulator, Inc.

2. Description:

a. Nonconducting materials for field assembly of companion flanges.

b. Pressure Rating: 150 psig (1035 kPa).

c. Gasket: Neoprene or phenolic.

d. Bolt Sleeves: Phenolic or polyethylene.

e. Washers: Phenolic with steel backing washers.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine roughing-in for natural-gas piping system to verify actual locations of piping connections before equipment installation.

http://www.specagent.com/LookUp/?ulid=3332&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812193&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812194&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812195&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456825031&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456825034&mf=95&src=wd http://www.specagent.com/LookUp/?ulid=3333&mf=04&mf=95&src=wd&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812196&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812197&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812198&mf=95&src=wd http://www.specagent.com/LookUp/?uid=123456812199&mf=95&src=wd

FACILITY NATURAL-GAS PIPING 221124 - 10 25095

B. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Close equipment shutoff valves before turning off natural gas to premises or piping section.

B. Inspect natural-gas piping according to the International Fuel Gas Code to determine that natural-gas utilization devices are turned off in piping section affected.

C. Comply with the International Fuel Gas Code requirements for prevention of accidental ignition.

3.3 INDOOR PIPING INSTALLATION

A. Comply with the International Fuel Gas Code for installation and purging of natural-gas piping.

B. Drawing plans, schematics, and diagrams indicate general location and arrangement of piping systems. Indicated locations and arrangements are used to size pipe and calculate friction loss, expansion, and other design considerations. Install piping as indicated unless deviations to layout are approved on Coordination Drawings.

C. Arrange for pipe spaces, chases, slots, sleeves, and openings in building structure during progress of construction, to allow for mechanical installations.

D. Install piping in concealed locations unless otherwise indicated and except in equipment rooms and service areas.

E. Install piping indicated to be exposed and piping in equipment rooms and service areas at right angles or parallel to building walls. Diagonal runs are prohibited unless specifically indicated otherwise.

F. Install piping above accessible ceilings to allow sufficient space for ceiling panel removal.

G. Locate valves for easy access.

H. Install natural-gas piping at uniform grade of 2 percent down toward drip and sediment traps.

I. Install piping free of sags and bends.

J. Install fittings for changes in direction and branch connections.

K. Verify final equipment locations for roughing-in.

L. Comply with requirements in Sections specifying gas-fired appliances and equipment for roughing-in requirements.

M. Drips and Sediment Traps: Install drips at points where condensate may collect, including service-meter outlets. Locate where accessible to permit cleaning and emptying. Do not install where condensate is subject to freezing.

FACILITY NATURAL-GAS PIPING 221124 - 11 25095

1. Construct drips and sediment traps using tee fitting with bottom outlet plugged or capped.

Use nipple a minimum length of 3 pipe diameters, but not less than 3 inches (75 mm) long and same size as connected pipe. Install with space below bottom of drip to remove plug or cap.

N. Conceal pipe installations in walls, pipe spaces, utility spaces, above ceilings, below grade or floors, and in floor channels unless indicated to be exposed to view.

O. Concealed Location Installations: Except as specified below, install concealed natural-gas piping and piping installed under the building in containment conduit constructed of steel pipe with welded joints as described in Part 2. Install a vent pipe from containment conduit to outdoors and terminate with weatherproof vent cap.

1. Above Accessible Ceilings: Natural-gas piping, fittings, valves, and regulators may be installed in accessible spaces without containment conduit.

2. In Floors: Install natural-gas piping with welded or brazed joints and protective coating in cast-in-place concrete floors. Cover piping to be cast in concrete slabs with minimum of 1-1/2 inches (38 mm) of concrete. Piping may not be in physical contact with other metallic structures such as reinforcing rods or electrically neutral conductors. Do not embed piping in concrete slabs containing quick-set additives or cinder aggregate.

3. In Floor Channels: Install natural-gas piping in floor channels. Channels must have cover and be open to space above cover for ventilation.

4. In Walls or Partitions: Protect tubing installed inside partitions or hollow walls from physical damage using steel striker barriers at rigid supports.

a. Exception: Tubing passing through partitions or walls does not require striker barriers.

5. Prohibited Locations:

a. Do not install natural-gas piping in or through circulating air ducts, clothes or trash chutes, chimneys or gas vents (flues), ventilating ducts, or dumbwaiter or elevator shafts.

b. Do not install natural-gas piping in solid walls or partitions.

P. Use eccentric reducer fittings to make reductions in pipe sizes. Install fittings with level side down.

Q. Connect branch piping from top or side of horizontal piping.

R. Install unions in pipes NPS 2 (DN 50) and smaller, adjacent to each valve, at final connection to each piece of equipment. Unions are not required at flanged connections.

S. Do not use natural-gas piping as grounding electrode.

T. Install strainer on inlet of each line-pressure regulator and automatic or electrically operated valve.

U. Install sleeves for piping penetrations of walls, ceilings, and floors. Comply with requirements for sleeves specified in Section 200517 "Sleeves and Sleeve Seals for General Mechanical Piping."

FACILITY NATURAL-GAS PIPING 221124 - 12 25095

V. Install sleeve seals for piping penetrations of concrete walls and slabs. Comply with requirements for sleeve seals specified in Section 200517 "Sleeves and Sleeve Seals for General Mechanical Piping."

W. Install escutcheons for piping penetrations of walls, ceilings, and floors. Comply with requirements for escutcheons specified in Section 200518 "Escutcheons for General Mechanical Piping."

3.4 VALVE INSTALLATION

A. Install manual gas shutoff valve for each gas appliance ahead of corrugated stainless-steel tubing, aluminum, or copper connector.

B. protection devices with maintenance access space adequate for servicing and testing.

C. Install anode for metallic valves in underground PE piping.

3.5 PIPING JOINT CONSTRUCTION

A. Ream ends of pipes and tubes and remove burrs.

B. Remove scale, slag, dirt, and debris from inside and outside of pipe and fittings before assembly.

C. Threaded Joints:

1. Thread pipe with tapered pipe threads complying with ASME B1.20.1.

2. Cut threads full and clean using sharp dies.

3. Ream threaded pipe ends to remove burrs and restore full inside diameter of pipe.

4. Apply appropriate tape or thread compound to external pipe threads unless dryseal threading is specified.

5. Damaged Threads: Do not use pipe or pipe fittings with threads that are corroded or damaged. Do not use pipe sections that have cracked or open welds.

D. Welded Joints:

1. Construct joints according to AWS D10.12/D10.12M, using qualified processes and welding operators.

2. Bevel plain ends of steel pipe.

3. Patch factory-applied protective coating as recommended by manufacturer at field welds and where damage to coating occurs during construction.

E. Brazed Joints: Construct joints according to AWS's "Brazing Handbook," "Pipe and Tube" Chapter.

F. Flanged Joints: Install gasket material, size, type, and thickness appropriate for natural-gas service. Install gasket concentrically positioned.

FACILITY NATURAL-GAS PIPING 221124 - 13 25095

G. Flared Joints: Cut tubing with roll cutting tool. Flare tube end with tool to result in flare dimensions complying with SAE J513. Tighten finger tight, then use wrench. Do not overtighten.

3.6 HANGER AND SUPPORT INSTALLATION

A. Install seismic restraints on piping. Comply with requirements for seismic-restraint devices specified in Section 200548 "Vibration Controls for General Mechanical."

B. Comply with requirements for pipe hangers and supports specified in Section 200529 "Hangers and Supports for General Mechanical Piping and Equipment."

C. Install hangers for horizontal steel piping with the following maximum spacing and minimum rod sizes:

1. NPS 1 (DN 25) and Smaller: Maximum span, 96 inches (2438 mm); minimum rod size, 3/8 inch (10 mm).

2. NPS 1-1/4 (DN 32): Maximum span, 108 inches (2743 mm); minimum rod size, 3/8 inch (10 mm).

3. NPS 1-1/2 and NPS 2 (DN 40 and DN 50): Maximum span, 108 inches (2743 mm);

minimum rod size, 3/8 inch (10 mm).

4. NPS 2-1/2 to NPS 3-1/2 (DN 65 to DN 90): Maximum span, 10 feet (3 m); minimum rod size, 1/2 inch (13 mm).

5. NPS 4 (DN 100) and Larger: Maximum span, 10 feet (3 m); minimum rod size, 5/8 inch (15.8 mm).

D. Install hangers for horizontal drawn-temper copper tubing with the following maximum spacing and minimum rod sizes:

1. NPS 3/8 (DN 10): Maximum span, 48 inches (1220 mm); minimum rod size, 3/8 inch (10 mm).

2. NPS 1/2 and NPS 5/8 (DN 15 and DN 18): Maximum span, 72 inches (1830 mm);

minimum rod size, 3/8 inch (10 mm).

3. NPS 3/4 and NPS 7/8 (DN 20 and DN 22): Maximum span, 84 inches (2134 mm);

minimum rod size, 3/8 inch (10 mm).

4. NPS 1 (DN 25): Maximum span, 96 inches (2440 mm); minimum rod size, 3/8 inch (10 mm).

E. Install hangers for horizontal, corrugated stainless-steel tubing with the following maximum spacing and minimum rod sizes:

1. NPS 3/8 (DN 10): Maximum span, 48 inches (1220 mm); minimum rod size, 3/8 inch (10 mm).

2. NPS 1/2 (DN 15): Maximum span, 72 inches (1830 mm); minimum rod size, 3/8 inch (10 mm).

3. NPS 3/4 (DN 20) and Larger: Maximum span, 96 inches (2440 mm); minimum rod size, 3/8 inch (10 mm).

FACILITY NATURAL-GAS PIPING 221124 - 14 25095

3.7 CONNECTIONS

A. Install natural-gas piping electrically continuous, and bonded to gas appliance equipment grounding conductor of the circuit powering the appliance according to NFPA 70.

B. Install piping adjacent to appliances to allow service and maintenance of appliances.

C. Connect piping to appliances using manual gas shutoff valves and unions. Install valve within 72 inches (1800 mm) of each gas-fired appliance and equipment. Install union between valve and appliances or equipment.

D. Sediment Traps: Install tee fitting with capped nipple in bottom to form drip, as close as practical to inlet of each appliance.

3.8 LABELING AND IDENTIFYING

A. Install detectable warning tape directly above gas piping, 12 inches (300 mm) below finished grade, except 6 inches (150 mm) below subgrade under pavements and slabs.

3.9 PAINTING

A. Comply with requirements in Section 099113 "Exterior Painting" and Section 099123 "Interior Painting" for painting interior and exterior natural-gas piping.

B. Paint exposed, exterior metal piping, valves, service regulators, service meters and meter bars, earthquake valves, and piping specialties, except components, with factory-applied paint or protective coating.

1. Alkyd System: MPI EXT 5.1D.

a. Prime Coat: Alkyd anticorrosive metal primer.

b. Intermediate Coat: Exterior alkyd enamel matching topcoat.

c. Topcoat: Exterior alkyd enamel.

d. Color: Gray.

C. Paint exposed, interior metal piping, valves, service regulators, service meters and meter bars, earthquake valves, and piping specialties, except components, with factory-applied paint or protective coating.

1. Latex Over Alkyd Primer System: MPI INT 5.1Q.

a. Prime Coat: Alkyd anticorrosive metal primer.

b. Intermediate Coat: Interior latex matching topcoat.

c. Topcoat: Interior latex.

d. Color: Gray.

D. Damage and Touchup: Repair marred and damaged factory-applied finishes with materials and by procedures to match original factory finish.

FACILITY NATURAL-GAS PIPING 221124 - 15 25095

3.10 FIELD QUALITY CONTROL

A. Perform tests and inspections.

B. Tests and Inspections:

1. Test, inspect, and purge natural gas according to the International Fuel Gas Code and authorities having jurisdiction.

C. Natural-gas piping will be considered defective if it does not pass tests and inspections.

D. Prepare test and inspection reports.

3.11 INDOOR PIPING SCHEDULE FOR SYSTEM PRESSURES LESS THAN 0.5 PSIG (3.45

kPa)

A. Aboveground, branch piping NPS 1 (DN 25) and smaller shall be one of the following:

1. Corrugated stainless-steel tubing with mechanical fittings having socket or threaded ends to match adjacent piping.

2. Annealed-temper, tin-lined copper tube with flared joints and fittings.

3. Annealed-temper, copper tube with wrought-copper fittings and brazed flared joints.

4. Aluminum tube with flared fittings and joints.

5. Steel pipe with malleable-iron fittings and threaded joints.

B. Aboveground, distribution piping shall be one of the following:

1. Steel pipe with malleable-iron fittings and threaded joints.

2. Steel pipe with wrought-steel fittings and welded joints.

3. Drawn-temper copper tube with wrought-copper fittings and brazed joints.

3.12 ABOVEGROUND MANUAL GAS SHUTOFF VALVE SCHEDULE

A. Valves for pipe sizes NPS 2 (DN 50) and smaller at service meter shall be one of the following:

1. One-piece, bronze ball valve with bronze trim.

2. Two-piece, full-port, bronze ball valves with bronze trim.

3. Bronze plug valve.

B. Valves for pipe sizes NPS 2-1/2 (DN 65) and larger at service meter shall be one of the following:

1. Two-piece, full-port, bronze ball valves with bronze trim.

2. Bronze plug valve.

3. Cast-iron, nonlubricated plug valve.

C. Distribution piping valves for pipe sizes NPS 2 (DN 50) and smaller shall be one of the following:

1. One-piece, bronze ball valve with bronze trim.

FACILITY NATURAL-GAS PIPING 221124 - 16 25095

2. Two-piece, full-port, bronze ball valves with bronze trim.

3. Bronze plug valve.

D. Distribution piping valves for pipe sizes NPS 2-1/2 (DN 65) and larger shall be one of the following:

1. Two-piece, full-port, bronze ball valves with bronze trim.

2. Bronze plug valve.

3. Cast-iron, lubricated plug valve.

E. Valves in branch piping for single appliance shall be one of the following:

1. One-piece, bronze ball valve with bronze trim.

2. Two-piece, full-port, bronze ball valves with bronze trim.

3. Bronze plug valve.

END OF SECTION

WATER TREATMENT FOR

CLOSED-LOOP HYDRONIC

SYSTEMS

232513 - 1 25095

SECTION 232513 - WATER TREATMENT FOR CLOSED-LOOP HYDRONIC SYSTEMS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes the following water treatment for closed-loop hydronic systems:

1. Manual chemical-feed equipment.

2. Chemicals.

B. Related Requirements:

1. Section 232533 "HVAC Makeup-Water Filtration Equipment" for water treatment of water softeners, RO equipment, and filtration equipment.

1.3 DEFINITIONS

A. TDS: Total dissolved solids consist of salts and other materials that combine with water as a solution.

B. TSS: Total suspended solids include both organic and inorganic solids that are suspended in the water. These solids may include silt, plankton, and industrial wastes.

1.4 ACTION SUBMITTALS

A. Product Data: Include rated capacities, operating characteristics, and furnished specialties and accessories for the following products:

1. Bypass feeders.

2. Water meters.

3. Inhibitor injection timers.

4. pH controllers.

5. Chemical solution tanks.

6. Injection pumps.

7. Chemical-treatment test equipment.

8. Chemical material safety data sheets.

9. Inhibited ethylene glycol.

10. Inhibited propylene glycol.

232513 - 2 25095

B. Shop Drawings: Pretreatment and chemical-treatment equipment, showing tanks, maintenance space required, and piping connections to hydronic systems.

1. Include plans, elevations, sections, and attachment details.

2. Include diagrams for power, signal, and control wiring.

1.5 INFORMATIONAL SUBMITTALS

A. Water-Analysis Provider Qualifications: Verification of experience and capability of HVAC water-treatment service provider.

B. Field quality-control reports.

C. Water-Treatment Program: Written sequence of operation on an annual basis for the application equipment required to achieve water quality defined in "Performance Requirements" Article.

D. Water Analysis: Illustrate water quality available at Project site.

1.6 CLOSEOUT SUBMITTALS

A. Operation and Maintenance Data: For sensors, injection pumps, and controllers to include in emergency, operation, and maintenance manuals.

1.7 QUALITY ASSURANCE

A. HVAC Water-Treatment Service Provider Qualifications: An experienced HVAC water-treatment service provider, capable of analyzing water qualities, installing water-treatment equipment, and applying water treatment as specified in this Section.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Provide all hardware, chemicals, and other material necessary to maintain HVAC water quality in all systems, as indicated in this Specification. Water quality for hydronic systems shall minimize corrosion, scale buildup, and biological growth for optimum efficiency of hydronic equipment without creating a hazard to operating personnel or the environment.

B. Base HVAC water treatment on quality of water available at Project site, hydronic system equipment material characteristics and functional performance characteristics, operating personnel capabilities, and requirements and guidelines of authorities having jurisdiction.

232513 - 3 25095

2.2 MANUAL CHEMICAL-FEED EQUIPMENT

A. Bypass Feeders: Provide steel feeders with corrosion-resistant exterior coating, minimum 3-1/2-inch (89-mm) fill opening in the top, and NPS 3/4 (DN 20) bottom inlet and top side outlet.

Provide quarter turn or threaded fill cap with gasket seal and diaphragm to lock the top on the feeder when exposed to system pressure in the vessel.

1. Capacity: 5 gal. (19 L).

2. Minimum Working Pressure: 125 psig (860 kPa).

2.3 CHEMICAL-TREATMENT TEST EQUIPMENT

A. Test Kit: Manufacturer-recommended equipment and chemicals in a wall-mounted cabinet for testing pH, corrosion inhibitors, alkalinity, hardness, and other properties recommended by manufacturer.

B. Corrosion Test-Coupon Assembly: Constructed of corrosive-resistant material, complete with piping, valves, and mild steel and copper coupons. Locate copper coupon downstream from mild steel coupon in the test-coupon assembly.

1. Two-station rack for closed-loop systems.

2.4 CHEMICALS

A. Chemicals shall be as recommended by water-treatment system manufacturer, compatible with piping system components and connected equipment, and able to attain water quality specified in "Performance Requirements" Article.

PART 3 - EXECUTION

3.1 WATER ANALYSIS

A. Perform an analysis of supply water to determine quality of water available at Project site.

3.2 INSTALLATION

A. Install chemical-application equipment on concrete bases, level and plumb. Maintain manufacturer's recommended clearances. Arrange units, so controls and devices that require servicing are accessible. Anchor chemical tanks and floor-mounting accessories to substrate.

Install all chemical application equipment within a spill-containment area without floor drain.

B. Install seismic restraints for equipment and floor-mounting accessories, and anchor to building structure. Comply with requirements in Section 230548 "Vibration and Seismic Controls for HVAC" for seismic restraints.

C. Install water-testing equipment on wall near water-chemical-application equipment.

232513 - 4 25095

D. Install interconnecting control wiring for chemical-treatment controls and sensors.

E. Mount sensors and injectors in piping circuits.

F. Bypass Feeders: Install in closed hydronic systems, including hot-water heating,, and equip with the following:

1. Install bypass feeder in a bypass circuit around circulating pumps unless indicated otherwise on Drawings.

2. Install water meter in makeup-water supply.

3. Install test-coupon assembly in bypass circuit around circulating pumps unless otherwise indicated on Drawings.

4. Install a gate or full-port ball isolation valves on inlet, outlet, and drain below the feeder inlet.

5. Install a swing check on the inlet after the isolation valve.

3.3 PIPING CONNECTIONS

A. Piping installation requirement are specified in other Sections. Drawings indicate general arrangement of piping, fittings, and specialties.

B. Where…