Coopers Electrical Phase II - Project Drawings.pdf
PDF 20 MB Posted
- Solicitation number
- CRFQ 0310 DNR2700000006 1
- Issued by
- Pleasants County, West Virginia
About this file
This is a set of construction documents and project drawings prepared by Miller Engineering Inc. for the West Virginia Division of Natural Resources for the Coopers Rock High Voltage Repairs Phase 2 project, involving high voltage and low voltage electrical replacement at Coopers Rock State Park near Bruceton Mills, West Virginia. The project encompasses comprehensive electrical infrastructure upgrades including the installation of new poles, overhead and underground electrical distribution systems, pad-mounted transformers, and associated electrical equipment across seven designated areas (A through G) spanning approximately 4,000 linear feet. The construction documents include detailed electrical demonstration plans, electrical plans by area, enlarged plans for specific installations, electrical details for pole construction and equipment mounting, and comprehensive schedules for transformers, feeders, and fuses. The project involves installation of multiple transformers with capacities ranging from 10 to 75 kilovolt-amperes (KVA), distribution panels serving various park facilities including water treatment plants, campgrounds, restrooms, and recreational areas, and coordination with utility companies for metering and primary voltage connections.
The electrical work must be performed in accordance with the 2020 National Electrical Code and includes provisions for both copper and aluminum cable conductors in various sizes, PVC and metal conduit installations, grounding systems utilizing copper ground rods and cadweld connections, and pole-mounted safety equipment including fused cutouts, disconnects, and lightning arrestors. Key project specifications require verification of field conditions prior to bidding, coordination among all trades and subcontractors, installation of new poles generally within three feet of existing poles unless otherwise indicated, complete new system installation prior to removal of existing systems, provision of insulating sleeves or wraps on poles for safety purposes, and final coordination of fixture locations with the project owner and general contractor. The project includes removal and repurposing of existing electrical infrastructure, extension of underground conduit to multiple facility locations, and installation of 15 kilovolt cable through previously installed conduit for interstate crossing bore locations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
C000
COVER PAGE
06-29-2026
TRT
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK HIGH VOLTAGE REPAIRS
PHASE 2 - HIGH VOLTAGE & LOW VOLTAGE
ELECTRICAL REPLACEMENT
SHEET INDEX
Sheet Number Sheet Name
C000 COVER PAGE
E001 ELECTRICAL DEMO PLAN - OVERALL NORTH
E002 ELECTRICAL DEMO PLAN - OVERALL SOUTH
E003 ELECTRICAL DEMO PLAN "AREA A"
E004 ELECTRICAL DEMO PLAN "AREA B"
E005 ELECTRICAL DEMO PLAN "AREA C"
E006 ELECTRICAL DEMO PLAN "AREA D"
E007 ELECTRICAL DEMO PLAN "AREA E"
E008 ELECTRICAL DEMO PLAN "AREA F"
E009 ELECTRICAL DEMO PLAN "AREA G"
E101 ELECTRICAL PLAN "AREA A"
E102 ELECTRICAL PLAN "AREA B"
E103 ELECTRICAL PLAN "AREA C"
E104 ELECTRICAL PLAN "AREA D"
E105 ELECTRICAL PLAN "AREA E"
E106 ELECTRICAL PLAN "AREA F"
COOPERS ROCK HIGH VOLTAGE REPAIRS
PHASE 2 - MAIN PARK POWER FEED
61 COUNTY LINE DR.
BRUCETON MILLS, WV 26525
PA OFFICE:
PO BOX 42
GARARDS FORT, PA 15334
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN ROAD
MORGANTOWN, WV 26508
PH: (304) 291-2234
N O
D
E S
C R
IP
T
IO
N
D A
T E
SHEET INDEX
Sheet Number Sheet Name
E107 ELECTRICAL PLAN "AREA G"
E108 ELECTRICAL PLAN "AREA A"
E109 ELECTRICAL PLAN "AREA B"
E110 ELECTRICAL PLAN "AREA C"
E111 ELECTRICAL PLAN "AREA D"
E112 ELECTRICAL PLAN "AREA E"
E113 ELECTRICAL PLAN "AREA F"
E114 ELECTRICAL PLAN "AREA G"
E401 ENLARGED ELECTRICAL PLAN
E402 ENLARGED ELECTRICAL PLAN
E501 ELECTRICAL DETAILS
E502 ELECTRICAL DETAILS
E503 ELECTRICAL DETAILS
E504 ELECTRICAL DETAILS
E601 ELECTRICAL SCHEDULES
NOTE: ORIGINAL DOCUMENTS ARE IN COLOR
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
#8 DN POLE
#11 UP POLE
A
B
C
D
CLEAR OVERHEAD, TREES, LIMBS, AND BRUSH ONLY
GROUND TO SKY, TO 50' EACH SIDE OF CENTER LINE.
CLEAR GROUND IN ALL OF THE EXISTING RIGHT OF
WAY BRUSH, TREES, ETC. DO NOT CUT TREES
OUTSIDE THE PROPOSED RIGHT OF WAY. (TYP - ALL
UNLESS OTHERWISE DIRECTED)
1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
2. WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
3. ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
4. ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED. ALL
NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED OR
COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC WIRING.
5. PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
6. PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
7. ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
8. EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
9. TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
10. GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
11. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
12. PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
13. COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E001
ELECTRICAL DEMO
PLAN - OVERALL
NORTH
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK HIGH VOLTAGE REPAIRS
PHASE 2 - HIGH VOLTAGE & LOW VOLTAGE
ELECTRICAL REPLACEMENT
RIGHT OF WAY KEY
1" = 400'-0"
ELECTRICAL DEMO PLAN - OVERALL NORTH
N O
D
E S
C R
IP
T
IO
N
D A
T E
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
D
E F
G
1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
2. WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
3. ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
4. ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED. ALL
NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED OR
COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC WIRING.
5. PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
6. PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
7. ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
8. EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
9. TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
10. GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
11. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
12. PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
13. COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E002
ELECTRICAL DEMO
PLAN - OVERALL
SOUTH
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK HIGH VOLTAGE REPAIRS
PHASE 2 - HIGH VOLTAGE & LOW VOLTAGE
ELECTRICAL REPLACEMENT
RIGHT OF WAY KEY
1" = 400'-0"
ELECTRICAL DEMO PLAN - OVERALL SOUTH
N O
D
E S
C R
IP
T
IO
N
D A
T
#8 DN POLE
#11 UP POLE
2'
5/
344' - 9 17/32"
/3
374' - 8 3/8"
264' - 11 5/8" 291' - 7 29/32"
333' - 9 3/32"
387' - 1 3/32"
213' - 1 1 27/32"
196' - 2 9/16"
388' - 9 29/32"
216' - 8 25/32" 33' - 6 9/16"
39°39'22.00"N
79°47'21.00"W
39°39'25.07"N
79°47'18.38"W
39°39'26.24"N
79°47'14.24"W
39°39'30.63"N
79°47'14.23"W
39°39'31.02"N
79°47'10.54"W
39°39'31.11"N
79°47'6.27"W
39°39'32.46"N
79°47'1.64"W
39°39'33.33"N
79°46'59.15"W
39°39'34.37"N
79°46'57.03"W
39°39'36.38"N
79°46'52.79"W
39°39'36.44"N
79°46'50.02"W
39°39'36.44"N
79°46'49.59"W
39°39'31.17"N
79°47'17.55"W
39°39'31.27"N
79°47'22.34"W
FOR NEW RIGHT OF WAY, EXTEND THE EXISTING RIGHT
OF WAY AN ADDITIONAL 25' TO THE NORTH FOR POLES
2-9 (75' TOTAL NORTH, 50' TOTAL SOUTH OF CENTER OF
RIGHT OF WAY).
EXISTING POLE TO BE REMOVED AFTER INSTALLATION OF
NEW POLES AND NEW OVERHEAD IS ENERGIZED. WHEN
REMOVED, BUNK EXISTING POLES IN LOCATIONS ON
DRAWINGS UNLESS DESIGNATED OTHERWISE BY OWNER
POLE YARD BUNKER LOCATION (TYP)
UNDERGROUND CONDUIT BY OTHERS, (1)
CND INCLUDES NEWLY INSTALLED CABLE TO
BE RE-SERVED TO NEW POLES 8 & 11.
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E003
ELECTRICAL DEMO
PLAN "AREA A"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL DEMO PLAN - "AREA A"
RIGHT OF WAY KEY
/3
1'
1/
7'
/1
6"
1'
/8
7'
9/
39°39'6.49"N
79°47'31.88"W
39°39'10.19"N
79°47'30.52"W
39°39'13.55"N
79°47'27.79"W
39°39'16.14"N
79°47'25.74"W
39°39'19.00"N
79°47'23.43"W
39°39'22.00"N
79°47'21.00"W
POLE YARD BUNKER LOCATION (TYP)
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E004
ELECTRICAL DEMO
PLAN "AREA B"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL DEMO PLAN - "AREA B"
/3
/3
/3
/3
/3
39°38'50.08"N
79°47'38.40"W
39°38'53.77"N
79°47'37.02"W
39°38'55.69"N
79°47'36.26"W
39°38'57.25"N
79°47'35.50"W
39°38'59.41"N
79°47'34.70"W
39°39'3.19"N
79°47'33.32"W
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E005
ELECTRICAL DEMO
PLAN "AREA C"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL DEMO PLAN - "AREA C"
39°38'38.80"N
79°47'42.71"W
169'
1 7 /3
2"
173' - 0 11/32"
/1
/3
308' - 9 1/4"
322' -
1/1
6"
127' - 7 31/32" 72' -
1/3 2"
/8
/3
/3
39°38'32.20"N
79°47'55.62"W
39°38'33.30"N
79°47'53.99"W
39°38'32.07"N
79°47'52.46"W
39°38'31.49"N
79°47'45.45"W
39°38'35.73"N
79°47'43.97"W
39°38'37.32"N
79°47'40.60"W
39°38'39.29"N
79°47'37.36"W
39°38'39.57"N
79°47'35.77"W
39°38'40.04"N
79°47'35.07"W
39°38'42.53"N
79°47'41.23"W
39°38'46.22"N
79°47'39.83"W
39°38'50.08"N
79°47'38.40"W
POLE YARD BUNKER LOCATION (TYP)
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E006
ELECTRICAL DEMO
PLAN "AREA D"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL DEMO PLAN - "AREA D"
169'
1 7 /3
2"
173' - 0 11/32"
280' - 10 13/32"
424' - 0 13/32"
423' - 1 1/2"
399' - 1 9/32"
235' - 2 13/32"
468' - 10 3/16"
39°38'32.20"N
79°47'55.62"W
39°38'33.30"N
79°47'53.99"W
39°38'32.07"N
79°47'52.46"W
39°38'29.78"N
79°47'50.42"W
39°38'31.49"N
79°47'45.45"W
39°38'28.36"N
79°47'41.86"W
39°38'25.27"N
79°47'38.69"W
39°38'23.40"N
79°47'36.90"W
39°38'19.76"N
79°47'33.19"W
POLE YARD BUNKER LOCATION (TYP)
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E007
ELECTRICAL DEMO
PLAN "AREA E"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
1" = 100'-0"
ELECTRICAL DEMO PLAN - "AREA E"
N O
D
E S
C R
IP
T
IO
N
D A
T
340' - 4 17/32"
405' - 3 23/32"
7'
/3 2"
396'
17/3
2"
306' - 1 21/32"
385' - 0 5/32"
367' - 9 1/32"
169'
1 7 /3
2"
173' - 0 11/32"
280' - 10 13/32"
39°38'24.25"N
79°48'23.97"W 39°38'24.14"N
79°48'19.62"W
39°38'25.86"N
79°48'14.94"W
39°38'27.57"N
79°48'12.69"W
39°38'30.18"N
79°48'8.90"W
39°38'30.84"N
79°48'5.08"W
39°38'31.46"N
79°48'0.22"W
39°38'32.20"N
79°47'55.62"W
39°38'33.30"N
79°47'53.99"W
39°38'32.07"N
79°47'52.46"W
POLE YARD BUNKER LOCATION (TYP)
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E008
ELECTRICAL DEMO
PLAN "AREA F"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL DEMO PLAN - "AREA F"
7'
5/
337' - 11 5/8
392' - 1 1/32"
/8
' - 0
469' - 9 23/32"
336' - 2 7/8"
330' - 0 7/8"
483' - 5 1/2"
39°38'17.53"N
79°48'56.65"W
39°38'20.74"N
79°48'52.71"W
39°38'22.72"N
79°48'49.23"W
39°38'23.46"N
79°48'44.31"W
39°38'24.29"N
79°48'38.40"W
39°38'25.15"N
79°48'34.25"W
39°38'25.19"N
79°48'30.03"W
39°38'24.25"N
79°48'23.97"W
39°38'19.90"N
79°48'44.74"W
39°38'15.33"N
79°48'44.57"W
REMOVE EXISTING TRANSFORMER.
CONDUIT TO BE REPURPOSED TO 7200
UNDERGROUND, EXTEND UNDERGROUND
FROM EXISTING LV DISCONNECT LOCATION
TO AND UP NEW POLE N58, PER DETAILS.
REMOVE CONDUCTORS FROM POLE 55
TO 57 LEAVE POLES 56 AND 57 IN PLACE
FOR INSTALLATION OF FIBER BY
OTHERS.
POLE YARD BUNKER LOCATION (TYP)
EXISTING R.O.W.
DISTANCE VARIES
NEW R.O.W.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E009
ELECTRICAL DEMO
PLAN "AREA G"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL DEMO PLAN - "AREA G"
#11 UP POLE39°39'25.01"N
N12
79°47'18.34"W
39°39'26.23"N
N11
79°47'14.24"W
39°39'32.99"N
N4
79°46'59.95"W
39°39'34.58"N
N3
79°46'56.59"W
39°39'36.38"N
N2
79°46'52.79"W
39°39'36.44"N
N1
79°46'50.02"W
39°39'36.44"N
N0
79°46'49.59"W
39°39'31.27"N
N10
79°47'22.34"W
39°39'31.71"N
N5
79°47'4.12"W
39°39'30.99"N
N6
79°47'8.50"W
39°39'30.82"N
N7
79°47'11.25"W39°39'30.61"N
N8
79°47'14.12"W
39°39'31.02"N
N9
79°47'18.55"W
39°39'22.10"N
N13
79°47'20.72"W
TX-7, FUSED DISCONNECT.
REFER TO DETAIL 3 ON E503.
FOR THE BORED INTERSTATE CROSSING,
INSTALL W/ #1/0 15KV CABLE IN PREVIOUSLY
INSTALLED CONDUIT (TYP-1)
USE (2) #2/0 OVERHEAD AAC (TYP)
INSTALL ALL NEW POLES GENERALLY WITHIN 3' OF EXISTING POLES, UNLESS INDICATED
OTHERWISE. GUY POLES PER DETAILS IN ALL CHANGES OF DIRECTION. COMPLETE NEW
SYSTEM PRIOR TO REMOVAL OF THE EXISTING SYSTEM. PROVIDE POLE INSULATING
SLEEVES OR WRAPS AS REQUIRED FOR SAFETY. REVIEW QUESTIONS ON POLE LOCATIONS
WITH ENGINEER PRIOR TO START. (TYP-ALL)
INSTALL CROSSBAR ON THIS POLE AND PROVIDE (2) FUSED AIR CUTOUTS TO THE TWO UNDERGROUND CONDUCTORS. PROVIDE NON-FUSED JUMPER IN PLACE OF FUSE IN BOTH DISCONNECTS. THIS POLE TO BE CONDUCTORS IN PARALLEL, COMMON WIRE BUSS ON LOAD SIDE TO OVERHEAD CABLING.
RELOCATE PREVIOUSLY INSTALLED 15KV CABLE TO NEW POLE ON ONE OF THE TWO SWITCHES. LEAVE ONE SWITCH OPEN AS DIRECTED. COORDINATE THE SWITCHES ON EAST AND WEST OF THE POLE WITH POLE 8 AND MARK IN A MANNER VISIBLE FROM THE GROUND.
CLEAR OVERHEAD, TREES, LIMBS, AND BRUSH ONLY GROUND TO SKY, TO 50' EACH SIDE
OF CENTER LINE. CLEAR GROUND IN ALL OF THE EXISTING RIGHT OF WAY BRUSH, TREES,
ETC. DO NOT CUT TREES OUTSIDE THE PROPOSED RIGHT OF WAY. (TYP - ALL UNLESS
OTHERWISE DIRECTED)
UNDERGROUND CONDUIT BY OTHERS, (1)
CND INCLUDES NEWLY INSTALLED CABLE TO
BE RE-SERVED TO NEW POLES 8 & 11.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E101
ELECTRICAL PLAN
"AREA A"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA A"
INSTALL CROSSBAR ON THIS POLE AND PROVIDE TWO FUSED
CUTOUTS TO THE TWO UNDERGROUND CONDUCTORS. CONDUCTORS
IN PARALLEL, COMMON WIRE BUS ON LINE SIDE. RELOCATE
PREVIOUSLY INSTLLED 15KV CABLE TO NEW POLE ON ONE OF THE
TWO SWITCHES. COORDINATE THE SWITCHES ON EAST AND WEST OF
THE POLE WITH POLE 8 AND MARK IN A MANNER VISIBLE FROM THE
GROUND.
UTILITY WILL PROVIDE NEW METERING TO CONTRACTOR FOR MOUNTING ON OWNER'S
METERING POLE INSTALLED BY PROJECT. FOLLOW UTILITY REQUIREMENTS AND
DIRECTION. SLACK SPAN REQUIRED BETWEEN UTILITY OWNED AND OWNER'S FIRST POLE.
UTILITY METERING LOCATION.
SEE DETAIL 2 ON E501
39°39'22.10"N
N13
79°47'20.72"W
39°39'19.21"N
N14
79°47'23.15"W
39°39'16.21"N
N15
79°47'25.43"W
39°39'13.34"N
N16
79°47'27.98"W
39°39'10.30"N
N17
79°47'30.16"W
39°39'7.00"N
N18
79°47'31.58"W
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E102
ELECTRICAL PLAN
"AREA B"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA B"
39°39'3.71"N
N19
79°47'32.87"W
39°39'0.42"N
N20
79°47'34.22"W
39°38'57.06"N
N21
79°47'35.28"W
39°38'55.64"N
N22
79°47'36.11"W
39°38'53.74"N
N23
79°47'36.87"W
N24
39°38'47.13"N
N25
79°47'39.27"W
NEW POLE 24
39°38'50.45"N 79°47'38.06"W
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E103
ELECTRICAL PLAN
"AREA C"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA C"
39°38'31.90"N
N43
79°47'56.79"W
39°38'31.42"N
N34
79°47'45.45"W
39°38'35.71"N
N29
79°47'43.94"W
39°38'37.38"N
N30
79°47'40.65"W
N24
39°38'47.13"N
N25
79°47'39.27"W
39°38'43.85"N
N26
79°47'40.66"W
39°38'40.54"N
N27
79°47'41.94"W
39°38'37.94"N
N28
79°47'43.17"W
39°38'39.44"N
N31
79°47'37.04"W
39°38'33.60"N
N33
79°47'44.67"W
39°38'31.89"N
N42
79°47'52.76"W
NEW POLE 32
39°38'40.02"N 79°47'35.06"W
NEW POLE 24
39°38'50.45"N 79°47'38.06"W
TX-1
SECONDARY POWER
LOCATION. INCLUDE FUSED
DISCONNECT. REFER TO
DETAIL 3 ON E503.
TX-2
SECONDARY POWER
LOCATION. FUSED
DISCONNECT. REFER
TO DETAIL 3 ON E503.
FUSED CUTOUT AT THIS LOCATION
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E104
ELECTRICAL PLAN
"AREA D"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA D"
79°47'56.79"W
N41
39°38'31.42"N
N34
79°47'45.45"W
39°38'20.13"N
N39
79°47'33.56"W
39°38'33.60"N
N33
79°47'44.67"W
39°38'28.69"N
N35
79°47'42.68"W
39°38'26.01"N
N36
79°47'39.86"W
39°38'23.41"N
N37
79°47'37.01"W
39°38'21.65"N
N38
79°47'35.17"W
39°38'30.64"N
N40
79°47'48.15"W
39°38'31.89"N
N42
79°47'52.76"W
NEW POLE 41
39°38'29.58"N 79°47'50.06"W
TX-3
SECONDARY POWER LOCATION.
SEE DETAIL 2 ON E503
TX-2
SECONDARY POWER
LOCATION. FUSED
DISCONNECT. REFER
TO DETAIL 3 ON E503.
DPLN1
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E105
ELECTRICAL PLAN
"AREA E"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA E"
FUSED CUTOUT ON THIS POLE FOR TAP
FUSED CUTOUT ON
OVERLOOK LATERAL
FUSED CUTOUT ON CAMPGROUND LATERAL
INSTALL CROSSBAR AND PROVIDE (2) FUSED
CUTOUTS ON THIS POLE, ONE FOR NEW
PADMOUNT, ONE FOR EXISTING RENTAL CABINS
UNDERGROUND
39°38'24.56"N
N50
79°48'24.91"W
39°38'24.09"N
N49
79°48'20.47"W
39°38'25.32"N
N48
79°48'16.32"W
39°38'27.21"N
N47
79°48'12.61"W
39°38'31.20"N
N44
79°48'1.10"W
39°38'31.90"N
N43
79°47'56.79"W
N41
39°38'31.89"N
N42
79°47'52.76"W
39°38'30.71"N
N45
79°48'5.52"W
39°38'29.89"N
N46
79°48'9.79"W
NEW POLE 41
39°38'29.58"N 79°47'50.06"W
TX-2
SECONDARY POWER
LOCATION. FUSED
DISCONNECT. REFER
TO DETAIL 3 ON E503.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E106
ELECTRICAL PLAN
"AREA F"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA F"
39°38'23.30"N
N55
79°48'44.70"W
39°38'25.06"N
N52
79°48'33.82"W
39°38'25.04"N
N51
79°48'29.37"W
39°38'24.56"N
N50
79°48'24.91"W
39°38'15.35"N
N58
79°48'44.84"W
39°38'24.30"N
N53
79°48'38.28"W
39°38'23.81"N
N54
79°48'42.61"W
39°38'19.69"N
N56
79°48'44.96"W
39°38'17.53"N
N57
79°48'44.74"W
39°38'22.59"N
N59
79°48'49.21"W
EXISTING NEW BATHHOUSE
EXISTING UNDERGROUND ELECTRICAL CONDUIT
EXISTING OLD BATHHOUSE
TX-4
SECONDARY POWER LOCATION.
COOPER MAXISHRUB 37.5 KVA. SEE PAD
MOUNTED TRANSFORMER ON E502
TX-6
SECONDARY POWER
LOCATION. FUSED
DISCONNECT. REFER TO
DETAIL 3 ON E503.
INSTALL FUSED CUTOUT THIS LOCATION
INSTALL FUSED CUTOUT THIS LOCATION
EXTEND NEW 7200V FROM TX4 TO TX5
INSTALL FUSED CUTOUT THIS LOCATION. TAP POLE TO NEW
UNDERGROUND THROUGH EXTENDED EXISTING 3" CONDUIT TO NEW
PAD MOUNT TRANSFORMERS 4 & 5 AT BATHHOUSE AND GIFT SHOP. SEE
SHEET E401 FOR DETAILS
TX-4
TX-5, FUSED
DISCONNECT.
REFER TO DETAIL 3
ON E503.
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E107
ELECTRICAL PLAN
"AREA G"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA G"
#11 UP POLE39°39'25.01"N
N12
79°47'18.34"W
39°39'26.23"N
N11
79°47'14.24"W
39°39'32.99"N
N4
79°46'59.95"W
39°39'34.58"N
N3
79°46'56.59"W
39°39'36.38"N
N2
79°46'52.79"W
39°39'36.44"N
N1
79°46'50.02"W
39°39'36.44"N
N0
79°46'49.59"W
39°39'31.27"N
N10
79°47'22.34"W
39°39'31.71"N
N5
79°47'4.12"W
39°39'30.99"N
N6
79°47'8.50"W
39°39'30.82"N
N7
79°47'11.25"W39°39'30.61"N
N8
79°47'14.12"W
39°39'31.02"N
N9
79°47'18.55"W
39°39'22.10"N
N13
79°47'20.72"W
USE (2) #2/0 OVERHEAD AAC (TYP)
FOR THE BORED INTERSTATE CROSSING, INSTALL W/ #1/0
15KV CABLE IN PREVIOUSLY INSTALLED CONDUIT (TYP-1)
INSTALL CROSSBAR ON THIS POLE AND PROVIDE (2) FUSED AIR CUTOUTS TO THE TWO UNDERGROUND CONDUCTORS. PROVIDE NON-FUSED JUMPER IN PLACE OF FUSE IN BOTH DISCONNECTS. THIS POLE TO BE CONDUCTORS IN PARALLEL, COMMON WIRE BUSS ON LOAD SIDE TO OVERHEAD CABLING.
RELOCATE PREVIOUSLY INSTALLED 15KV CABLE TO NEW POLE ON ONE OF THE TWO SWITCHES. LEAVE ONE SWITCH OPEN AS DIRECTED. COORDINATE THE SWITCHES ON EAST AND WEST OF THE POLE WITH POLE 8 AND MARK IN A MANNER VISIBLE FROM THE GROUND.
EXISTING R.O.W.
DISTANCE VARIES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E108
ELECTRICAL PLAN
"AREA A"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA A" (TOPO)
TX-7
39°39'22.10"N
N13
79°47'20.72"W
39°39'19.21"N
N14
79°47'23.15"W
39°39'16.21"N
N15
79°47'25.43"W
39°39'13.34"N
N16
79°47'27.98"W
39°39'10.30"N
N17
79°47'30.16"W
39°39'7.00"N
N18
79°47'31.58"W
EXISTING R.O.W.
DISTANCE VARIES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E109
ELECTRICAL PLAN
"AREA B"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA B" (TOPO)
39°39'3.71"N
N19
79°47'32.87"W
39°39'0.42"N
N20
79°47'34.22"W
39°38'57.06"N
N21
79°47'35.28"W
39°38'55.64"N
N22
79°47'36.11"W
39°38'53.74"N
N23
79°47'36.87"W
39°38'50.45"N
N24
79°47'38.06"W
39°38'47.13"N
N25
79°47'39.27"W
EXISTING R.O.W.
DISTANCE VARIES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E110
ELECTRICAL PLAN
"AREA C"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA C" (TOPO)
79°47'56.79"W
39°38'31.42"N
N34
79°47'45.45"W
39°38'35.71"N
N29
79°47'43.94"W
39°38'37.38"N
N30
79°47'40.65"W
39°38'47.13"N
N25
79°47'39.27"W
39°38'43.85"N
N26
79°47'40.66"W
39°38'40.54"N
N27
79°47'41.94"W
39°38'37.94"N
N28
79°47'43.17"W
39°38'39.44"N
N31
79°47'37.04"W
39°38'40.02"N
N32
79°47'35.06"W
39°38'33.60"N
N33
79°47'44.67"W
39°38'31.89"N
N42
79°47'52.76"W
EXISTING R.O.W.
DISTANCE VARIES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E111
ELECTRICAL PLAN
"AREA D"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA D" (TOPO)
79°47'56.79"W
39°38'29.58"N
N41
79°47'50.06"W
39°38'31.42"N
N34
79°47'45.45"W
39°38'20.13"N
N39
79°47'33.56"W
39°38'33.60"N
N33
79°47'44.67"W
39°38'28.69"N
N35
79°47'42.68"W
39°38'26.01"N
N36
79°47'39.86"W
39°38'23.41"N
N37
79°47'37.01"W
39°38'21.65"N
N38
79°47'35.17"W
39°38'30.64"N
N40
79°47'48.15"W
39°38'31.89"N
N42
79°47'52.76"W
TX-3
SECONDARY POWER LOCATION.
COOPER MAXISHRUB 75 KVA. SEE
PAD MOUNTED TRANSFORMER ON
E502
DPLN1
E402
EXISTING R.O.W.
DISTANCE VARIES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E112
ELECTRICAL PLAN
"AREA E"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA E" (TOPO)
39°38'24.56"N
N50
79°48'24.91"W
39°38'24.09"N
N49
79°48'20.47"W
39°38'25.32"N
N48
79°48'16.32"W
39°38'27.21"N
N47
79°48'12.61"W
39°38'31.20"N
N44
79°48'1.10"W
39°38'31.90"N
N43
79°47'56.79"W
39°38'31.89"N
N42
79°47'52.76"W
39°38'30.71"N
N45
79°48'5.52"W
39°38'29.89"N
N46
79°48'9.79"W
EXISTING R.O.W.
DISTANCE VARIES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E113
ELECTRICAL PLAN
"AREA F"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA F" (TOPO)
39°38'23.30"N
N55
79°48'44.70"W
39°38'25.06"N
N52
79°48'33.82"W
39°38'25.04"N
N51
79°48'29.37"W
39°38'24.56"N
N50
79°48'24.91"W
39°38'15.35"N
N58
79°48'44.84"W
39°38'24.30"N
N53
79°48'38.28"W
39°38'23.81"N
N54
79°48'42.61"W
39°38'19.69"N
N56
79°48'44.96"W
39°38'17.53"N
N57
79°48'44.74"W
39°38'22.59"N
N59
79°48'49.21"W
EXISTING NEW BATHHOUSE
EXISTING OLD BATHHOUSE
TX-4
E401
TX-5
EXISTING R.O.W.
DISTANCE VARIES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E114
ELECTRICAL PLAN
"AREA G"
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 100'-0"
ELECTRICAL PLAN - "AREA G" (TOPO)
EXISTING BATHHOUSE
EXISTING BATHHOUSE
TX-4
39°38'15.35"N
N58
79°48'44.84"W
39°38'17.53"N
N57
79°48'44.74"W
DPLN2
INTERCEPT EXISTING LV CONDUIT AND REPURPOSE TO SERVE TX-4.
EXTEND NEW 3" CONDUIT PLUS SPARE FROM TX-4 TO TX-5. SEE DETAIL 2
THIS SHEET.
A B
NEW CONDUIT FROM DPLN2 TO EXISTING QUAZITE
BOX. MATCH TO EXISTING CONDUCTOR SIZE IN
QUAZITE.
(2) 2" CND
(1) 3" CND
C
SPARE 3" CND
EXISTING CND
EXISTING CND
EXISTING CND
TX-5
RE-SERVE EXISTING 200A, AND (2) 100A
FEEDERS FROM NEW PANEL SERVED BY TX4
EXTEND AND REUSE 3" CND
FOR 7200V TO NEW TX-4
TX-4
7200V DISTRIBUTION
DPLN2
240V DISTRIBUTION
NEW POLE 58
TO QUAZITE BOX THAT SERVES OLD &
NEW BATH HOUSES AND PAVILLION
TO TX-5
7200V DISTRIBUTION
TX-5
7200V DISTRIBUTION
A
B
C E
D
REPURPOSE METERING ENCLOSURE TO FEED
THROUGH VOLTAGE SUPPLY TO OVERLOOK
TRADING POST PANEL
OVERLOOK TRADING POST
EXTEND 2" CND TO REPURPOSED
METERING ENCLOSURE
1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
2. WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
3. ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
4. ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED. ALL
NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED OR
COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC WIRING.
5. PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
6. PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
7. ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
8. EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
9. TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
10. GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
11. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
12. PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
13. COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E401
ENLARGED
ELECTRICAL PLAN
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 50'-0"
ENLARGED ELECTRICAL PLAN - OVERLOOK AREA
DRAWING NOT SCALABLE
POLE 58 NEW LAYOUT
FEEDER SCHEDULE
TAG # SETS
CONDUCTOR SIZE
CONDUIT SIZE
VOLTAGE
TYPEPOWER & NEUTRAL GROUND
A 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 EXISTING MEDIUM
B 1 3 - #350 KCMIL (CU) #1/0 3" LOW
C 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 3" MEDIUM
D 1 2 - 2/0 (AAC) #6 NA MEDIUM
E 1 3 - #2/0 (CU) #4 2" LOW
F 1 2 - #1/0 (CU) #6 EXISTING PHASE 1 MEDIUM
G 1 3 - #400 KCMIL (CU) #1/0 3" LOW
FUSE SCHEDULE
FUSE TAG VOLTAGE (V) FUSE HOLDER SERIES / FUSE MODEL NUMBER
A 7200 HX OPEN TYPE T / 40T
B 7200 HX OPEN TYPE T / 30T
C 7200 HX OPEN TYPE T / 25T
D 7200 HX OPEN TYPE T / 20T
E 7200 HX OPEN TYPE T / 15T
F 7200 XFMR BAY-O-NET / 6A
G 7200 XFMR BAY-O-NET / 25A
H 7200 XFMR BAY-O-NET / 15A
J 7200 XFMR BAY-O-NET / 12A
A
39°38'23.41"N
N37
79°47'37.01"W
39°38'21.65"N
N38
79°47'35.17"W
TX-3 SECONDARY POWER
LOCATION. SEE DETAIL 2 ON E503.
DPLN1
CAMPGROUND STORE
CAMPGROUND BATHHOUSE
N39 39°38'20.13"N 79°47'33.56"W
G
E
NEW POLE 39
TX-3
7200V DISTRIBUTION
DPLN1
240V DISTRIBUTION
EXTEND NEW UNDERGROUND
TO EXISTING BATHHOUSE
EXTEND AND INTERCEPT CONDUIT
THAT FEEDS EXISTING RENTAL CABINS.
EXTEND NEW UNDERGROUND TO
EXISTING CAMPGROUND OFFICE PANEL.
EXTEND AND INTERCEPT CND TO WATER TREATMENT PLANT.
EXTEND AND INTERCEPT CND TO CAMPGROUND POWER DIST. PANEL.
NOTE: WHERE INTERCEPTING CONDUIT, MATCH EXISTING
CONDUIT SIZE AND CONDUCTOR SIZE. VERIFY IN FIELD. (TYP)
REMOVE AND REPLACE SIDEWALK TO ALLOW FOR
CONDUIT TRENCHING TO CAMPGROUND BATHHOUSE.
D
DE
G
C
E
1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES
OR SPECIAL CONDITIONS. ALL WALL MOUNTED DEVICES ARE
FINAL HEIGHT BY. ARCH.
2. WIRING AND CONDUIT OR MC CABLE SHALL BE REQUIRED FOR
ALL OUTLETS AND DEVICES. FOLLOW INDICATED CIRCUITS
NUMBERS AND PANEL DESIGNATION. OBTAIN PRIOR APPROVAL
OF ENGINEER FOR DEVIATIONS.
3. ALL 15A AND 20A, 115V AND 120V RECEPTACLES LOCATED IN
DWELLING UNITS SHALL BE TAMPER RESISTANT.
4. ALTHOUGH ALL BRANCH CIRCUIT WIRING IS NOT SHOWN, IT IS
THE INTENT OF THESE DOCUMENTS THAT A COMPLETE
BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED. ALL
NEUTRALS SHALL BE FULL CAPACITY. THE USE OF SHARED OR
COMMON NEUTRALS IS PROHIBITED ON ALL ELECTRIC WIRING.
5. PROVIDE CONTROL AND FIRE ALARM WIRE AS NECESSARY TO
INSTALL ALL SYSTEMS DEVICES AND PANELS FOR COMPLETE
SYSTEMS. FINAL CONNECTION TO PERMANTLY MOUNTED
EQUIPMENT IS PART OF THE ELECTRICAL SCOPE OF THIS
PROJECT.
6. PROVIDE TEL/DATA AND CAT5 AS INDICATED. REVIEW DATA,
SWITCH, RECEPTACLE, ETC LOCATIONS AND HEIGHTS WITH
OWNER PRIOR TO INSTALLATION.
7. ALL INTERIOR WIRING SHALL BE THHN/THWN IN METAL CONDUIT
OR MC CABLE. MAX OF 3'-0" OF FLEXIBLE CONDUIT MAY BE
USED FOR FINAL EQUIPMENT TERMINATIONS.
8. EXTERIOR WIRING IS TO BE THHN/THWN IN PVC CONDUIT. MAX.
OF 3'-0" OF FLEXIBLE METALLIC SEATITLE CONDUIT MAY BE
USED TO EXTERIOR EQUIPMENT.
9. TV AND TELEPHONE CABLING SHALL BE INSTALLED FROM
LOCATIONS INDICATED ON DRAWINGS TO DEMARC LOCATION.
COORDINATE FINAL DEMARC LOCATIONS w/ TV AND
TELEPHONE COMPANY.
10. GROUP AND TRAIN ALL TEL/DATA AND CABLE TV CABLE.
SUPPORT FROM STRUCTURE.
11. VERIFY ALL FIELD CONDITIONS AND MEASUREMENTS PRIOR TO
BIDDING. COORDINATE ALL WORK WITH OTHER TRADES.
COORDINATE ALL CEILING MOUNTED DEVICES WITH ALL OTHER
TRADES PRIOR TO INSTALLATION.
12. PERFORM ALL WORK IN ACCORDANCE WITH 2020 NEC.
13. COORDINATE FINAL FIXTURE LOCATIONS WITH OWNER AND
GENERAL CONTRACTOR PRIOR TO INSTALLATION OF CEILING.
FINAL COORDINATION OF SCOPE OF WORK , DIMENSIONS,
FIXTURE PLACEMENT, ROUTINGS, ETC IS THE RESPONSIBILITY
OF THE GENERAL CONTRACTOR AND ALL SUB-CONTRACTORS
PRIOR TO BIDDING.
ELECTRICAL NOTES
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E402
ENLARGED
ELECTRICAL PLAN
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
1" = 50'-0"
ENLARGED ELECTRICAL PLAN - CAMPGROUND
DRAWING NOT SCALABLE
POLE 39 NEW LAYOUT
FEEDER SCHEDULE
TAG # SETS
CONDUCTOR SIZE
CONDUIT SIZE
VOLTAGE
TYPEPOWER & NEUTRAL GROUND
A 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 EXISTING MEDIUM
B 1 3 - #350 KCMIL (CU) #1/0 3" LOW
C 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 3" MEDIUM
D 1 2 - 2/0 (AAC) #6 NA MEDIUM
E 1 3 - #2/0 (CU) #4 2" LOW
F 1 2 - #1/0 (CU) #6 EXISTING PHASE 1 MEDIUM
G 1 3 - #400 KCMIL (CU) #1/0 3" LOW
FUSE SCHEDULE
FUSE TAG VOLTAGE (V) FUSE HOLDER SERIES / FUSE MODEL NUMBER
A 7200 HX OPEN TYPE T / 40T
B 7200 HX OPEN TYPE T / 30T
C 7200 HX OPEN TYPE T / 25T
D 7200 HX OPEN TYPE T / 20T
E 7200 HX OPEN TYPE T / 15T
F 7200 XFMR BAY-O-NET / 6A
G 7200 XFMR BAY-O-NET / 25A
H 7200 XFMR BAY-O-NET / 15A
J 7200 XFMR BAY-O-NET / 12A
CUT AND REPLACE CONCRETE SIDEWALK
FOR NEW CONDUIT TRENCHING
8" X 7' DOUBLE HELIX ANCHOR
W/ 8,000 FT/LB TORQUE
ROTBLOC UTILITY POLEWRAP. START AT
BUTT AND END 2" - 4" ABOVE GROUND
LEVEL. ATTACH W/ 1-1/4 STAINLESS
STAPLES, OVERLAP 12" ON EACH TURN.
CUSTOM POLE TAG
NOTE: BOND ALL METAL PARTS TO GROUND
COPPER POLE BONDING
PLATE( BURNDY 000038595504)
1: OHIO BRASS PSPT 552 INSULATOR
2: 24" PINTOP, CHANCE MODEL PSC2060874P
3: #6 BARE SOLID GROUND WIRE W/ 3/4" CABLE GUARD (GALVANIZED
STEEL TO 8', THEN PVC), COPPER COATED 1-1/4" STAPLE EVERY 5'
4: 3/4" GALV THROUGHBOLT. CLEVIS AND INSULATOR.
POLE BURIED 6'-6"
45'/3 POLE
6'
0"
COMPRESSION CONNECTOR (TYP)
THROUGH BOLT
STRAIN CLAMP
SLACK SPAN
METERING CT
FROM POWER CO
TO STATE PARK
NOTE: FOLLOW ALL POLE
INSTALLATION DETAILS
FUSED CUTOUT BY PROJECT,
COORDINATE W/ UTILITY
15KV POLY PIN TOP INSULATOR
BOND ALL METAL HARDWARE
USE EXTENDED "L" BRACKET OFF THE POLE TO TRIP SAVER.
TRIP SAVER II IN 200A LOAD BREAK
CUTOUT HOLDER. MOUNTING
HEIGHT 21' AFG TO CENTER.
HORIZONTAL PIN
STANDOFF BRACKET.
NEUTRAL CONNECTS TO
REARWARD STANDOFF BRACKET
(3) 3/4" X 10' GROUND RODS. 6' SPACING (3) 3/4" X 10' GROUND
RODS. 6' SPACING
#6 GRN
45.00°
DOWN POLEUP POLE
TRIP SAVER II CUTOUT-MOUNTED RECLOSER
CHANCE STANDOFF BRACKET (1SBH20H1)
CHANCE STANDOFF BRACKET (1SBH27H1)
15.00°
DOWN POLE
UP POLE
TO NEUTRAL CONNECTION
TO PARK TO UTILITY
PRIMARY VOLTAGE
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E501
ELECTRICAL DETAILS
06-29-2026
TRT
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
DRAWING NOT SCALABLE
15 KV AND BELOW SINGLE PHASE LINE POLE (TYP-ALL)
DRAWING NOT SCALABLE
METERING POINT & OWNER'S DISCONNECT DETAIL
DRAWING NOT SCALABLE
HORIZONTAL STANDOFF BRACKET POLE DETAIL
BACK GUY
LINE GUY
LINE GUY
BACK GUY
45.00°
8' FULL ROUND GUY
MARKER, YELLOW.
HUBBEL 96FRPE
CLASS 3 POLE
XFMR
#2 CONCENTRIC NEUTRAL
CABLE W/ TERMINATION
CROSSBAR
CONTINUOUS GALVANIZED STEEL CABLE GUARD UP
THE POLE. 3" P80 PVC CONDUIT UP THE POLE 10'
AGL.
SECONDARY CONDUIT AS INDICATED
GROUND ROD
24"
GRAVEL OR
COMPACTED
EARTH(10" - 12")
RURAL PAD MOUNT XFMR. SEE
PLANS FOR KVA.
NOTE: FOLLOW ALL POLE INSTALLATION DETAILS
FIBERGLASS GROUND SLEEVE
8KV LIGHTNING ARRESTOR
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E502
ELECTRICAL DETAILS
06-29-2026
TRT
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
DRAWING NOT SCALABLE
GUY DETAIL GREATER THAN 10 DEG. DIR. CHANGE
DRAWING NOT SCALABLE
GUY DETAIL LESS THAN 10 DEG. DIR. CHANGE
1/4" = 1'-0"
DOUBLE GUY ANCHOR DETAIL (TYP-ALL)
DRAWING NOT SCALABLE
PAD MOUNTED TRANSFORMER DETAIL
NEW POLE 8
NEW POLE 11
FROM POWER
COMPANY
NEW POLE 10
NEW POLE 29
NEW POLE 32
TX-1
10 KVA
NEW POLE 39
TX-3
75 KVA
NEW POLE 34
NEW POLE 42
TX-2
10 KVA
NEW POLE 58
TX-4
37.5 KVA
TX-6
10 KVA
TX-5
15 KVA
ALL ALUMINUM CABLE (AAC)
NEW POLE 55
NEW POLE 59
D
A C
D
TX-7
10 KVA
C C
C
RE-USE EXISTING UNDERGROUND CND
F
TO EXISTING RENTAL CABINS
A B C
F
F
D
D
D
F
D
D
E
G
J
H
D
F
D
FUSE (TYP)
FEEDER (TYP)
D D D
PANEL
4' - 0"
2"X12" TREATED BOARD (TYP)
4"Ø GALVANIZED POST (TYP)
INSTALL POST IN 10" SONOTUBE & FILL
WITH 3,500 PSI CONCRETE.
ARRANGE ELECTRICAL EQUIPMENT AS NEEDED IN FIELD.
TRANSFORMER
FIBERGLASS GROUND SLEEVE
GRAVEL OR
COMPACTED
EARTH(10" - 12")
6"Ø GALVANIZED
POST (TYP)
INSTALL POST IN 10" SONOTUBE & FILL WITH 3,500 PSI CONCRETE.
FUSED
DISCONNECT
TO UTILITY POLE
TO LOAD
TRANSFORMER
2"X12" TREATED BOARD (TYP)
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E503
ELECTRICAL DETAILS
06-29-2026
TRT
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
DRAWING NOT SCALABLE
ELECTRICAL LAYOUT
FEEDER SCHEDULE
TAG # SETS
CONDUCTOR SIZE
CONDUIT SIZE
VOLTAGE
TYPEPOWER & NEUTRAL GROUND
A 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 EXISTING MEDIUM
B 1 3 - #350 KCMIL (CU) #1/0 3" LOW
C 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 3" MEDIUM
D 1 2 - 2/0 (AAC) #6 NA MEDIUM
E 1 3 - #2/0 (CU) #4 2" LOW
F 1 2 - #1/0 (CU) #6 EXISTING PHASE 1 MEDIUM
G 1 3 - #400 KCMIL (CU) #1/0 3" LOW
DRAWING NOT SCALABLE
ELECTRIC POWER BACKBOARD - GENERAL
DRAWING NOT SCALABLE
ELECTRIC POWER BACKBOARD - TO RECONNECTION POINTS
FUSE SCHEDULE
FUSE TAG VOLTAGE (V) FUSE HOLDER SERIES / FUSE MODEL NUMBER
A 7200 HX OPEN TYPE T / 40T
B 7200 HX OPEN TYPE T / 30T
C 7200 HX OPEN TYPE T / 25T
D 7200 HX OPEN TYPE T / 20T
E 7200 HX OPEN TYPE T / 15T
F 7200 XFMR BAY-O-NET / 6A
G 7200 XFMR BAY-O-NET / 25A
H 7200 XFMR BAY-O-NET / 15A
J 7200 XFMR BAY-O-NET / 12A
A A
POWER CO. POLE
#6 BARE CU
CAD WELD (TYP)
TX-7
1Ø
7200V/240V
10KVA
NEMA 3R
C
CONDUCTOR BY UTILITY
METERING POLE
FIRST POLE DNR
#1/0 BARE CU
CAD WELD (TYP)
3/4" X 10' CU GRN ROD (TYP)
#6 BARE CU
CAD WELD (TYP)
TX-1
1Ø
7200V/240V
10KVA
NEMA 3R
C
#6 BARE CU
CAD WELD (TYP)
TX-3
1Ø
7200V/240V
75KVA
NEMA 3R
C
#6 BARE CU
CAD WELD (TYP)
3/4" X 10' CU
GRN ROD (TYP)
TX-2
1Ø
7200V/240V
10KVA
NEMA 3R
C
#6 BARE CU
CAD WELD (TYP)
TX-4
1Ø
7200V/240V
37.5KVA
NEMA 3R
A
#6 BARE CU
CAD WELD (TYP)
TX-5
1Ø
7200V/240V
15KVA
NEMA 3R
C
D D D D D D
3/4" X 10' CU
GRN ROD (TYP)
3/4" X 10' CU
GRN ROD (TYP)
3/4" X 10' CU
GRN ROD (TYP)
3/4" X 10' CU
GRN ROD (TYP)
3/4" X 10' CU
GRN ROD (TYP)
#6 BARE CU
CAD WELD (TYP)
TX-7
1Ø
7200V/240V
10KVA
NEMA 3R
A
3/4" X 10' CU
GRN ROD (TYP)
D
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E504
ELECTRICAL DETAILS
06-29-2026
TRT
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
DRAWING NOT SCALABLE
SERVICE ONE-LINE
FEEDER SCHEDULE
TAG # SETS
CONDUCTOR SIZE
CONDUIT SIZE
VOLTAGE
TYPEPOWER & NEUTRAL GROUND
A 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 EXISTING MEDIUM
B 1 3 - #350 KCMIL (CU) #1/0 3" LOW
C 1 2 - #1/0 (CU) (133% INSULATION)(CONCENTRIC NEUTRAL) #6 3" MEDIUM
D 1 2 - 2/0 (AAC) #6 NA MEDIUM
E 1 3 - #2/0 (CU) #4 2" LOW
F 1 2 - #1/0 (CU) #6 EXISTING PHASE 1 MEDIUM
G 1 3 - #400 KCMIL (CU) #1/0 3" LOW
PA OFFICE:
429 LAUREL RUN ROAD
CARMICHAELS, PA 15320
PH: (724) 966-5655
WV OFFICE:
54 WEST RUN RD.
MORGANTOWN, WV 26508
PH: (304) 291-2234
SHEET NAME:
MILLER ENGINEERING INC.
COPY RIGHT:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
BCM
SEAL:
CONSULTANT:
PROJECT NAME:
PROJECT OWNER:
PROJECT STATUS:
PROJECT NUMBER:
ORIGINAL PAGE SIZE: 22x34
E601
ELECTRICAL
SCHEDULES
06-29-2026
BCM
BCM
26002
CONSTRUCTION
DOCUMENTS
WEST VIRGINIA
DIVISION OF
NATURAL
RESOURCES
COOPERS ROCK
HIGH VOLTAGE
REPAIRS PHASE
2 - HIGH VOLTAGE &
LOW VOLTAGE
ELECTRICAL
REPLACEMENT
N O
D
E S
C R
IP
T
IO
N
D A
T E
TRANSFORMER SCHEDULE
TAG MANUFACTURER MODEL PHASES
VOLTAGES
KVA LOCATION SERVES
PRIMARY SECONDARY
TX-1 EATON COOPER MAXISHRUB 1 7200 240 10.0 WATER PLANT EXISTING PANEL
TX-2 EATON COOPER MAXISHRUB 1 7200 240 10.0 RESERVOIR PUMPHOUSE EXISTING PANEL
TX-3 EATON COOPER MAXISHRUB 1 7200 240 75.0 CAMPGROUND DPLN1
TX-4 EATON COOPER MAXISHRUB 1 7200 240 37.5 RESTROOM AREAS DPLN2
TX-5 EATON COOPER MAXISHRUB 1 7200 240 15.0 CLIFFSIDE SHOP EXISTING PANEL
TX-6 EATON COOPER MAXISHRUB 1 7200 240 10.0 RHOD. CAMPGROUND EXISTING DISCONNECT
TX-7 EATON COOPER MAXISHRUB 1 7200 240 10.0 TROUT LAKE NEW DISCONNECT
SLOTS 13, 14, 15, 16, 17, 18, 19, 20 IS 1 BREAKER
SLOTS 21, 22, 23, 24, 25, 26, 27, 28 IS 1 BREAKER
Notes:
29 30 27 28 25 26 23 24 21 22 19 20 17 18 15 16 13 14 11 12 9 10 7 ... 8
BATH HOUSE 400 A 2
2 400 A CAMPGROUND PANEL
3 ... 4
WATER TREATMENT PLANT 200 A 2
2 200 A CAMPGROUND OFFICE
CKT Circuit Description Trip Poles Poles Trip Circuit Description CKT
ENCLOSURE: NEMA 3R Outdoor MAIN TYPE: MCB
WIRES: 3 MAIN: 600 A
VOLTS: 120/240 Single PHASES: 1
Branch Panel: DPLN1
SLOTS 21, 22, 23, 24 IS A FEED THROUGH LUG SECTION
SLOTS 25, 26, 27, 28, 29, 30 IS A BLANK COVER
Notes:
29 COVER -- 1 ... 1 -- COVER 30
27 COVER -- 1 ... 1 -- COVER 28
25 COVER -- 1 ... 1 -- COVER 26
23 ... 24
THROUGH FEED BATH HOUSE 1 -- 2
2 -- THROUGH FEED BATH HOUSE 2
19 20 17 18 15 16 13 14 11 12 9 10 7 8 5 6 3 ... 4
PAVILION PANEL 100 A 2
... 2
CKT Circuit Description Trip Poles Poles Trip Circuit Description CKT
ENCLOSURE: NEMA 3R Outdoor MAIN TYPE: MCB
WIRES: 3 MAIN: 300 A
VOLTS: 120/240 Single PHASES: 1
Branch Panel: DPLN2