CONSTRUCTION_PLANS_.pdf
PDF 34 MB Posted
- Attached to
- Fire Rescue Rotary Saws
- Solicitation number
- 2025-IFB-226
- Issued by
- New Haven County, Pennsylvania
About this file
The document is a set of structural engineering drawings and specifications for the Omni Hotel Port Cochere Framing Repairs project located at 155 Temple Street in New Haven, Connecticut, prepared by WSP USA Buildings Inc. The drawings, issued for permit on March 18, 2025, detail a comprehensive structural repair and renovation project focusing on concrete beam, column, and corbel repairs within a tunnel-level loading dock area. The project involves extensive demolition of existing deteriorated reinforced concrete elements, including beams, slabs, and masonry walls, followed by reconstruction using new reinforced concrete elements, waterproofing membranes, and precise connection techniques.
The structural repair documents specify detailed technical requirements for concrete work, including specific material specifications, reinforcement standards, quality assurance testing, and repair methodologies. The project includes provisions for contingency pricing to account for potential hidden structural conditions, mandates comprehensive testing and inspection protocols, and requires contractors to engage professional engineers for temporary shoring, bracing, and load analysis. The repair strategy emphasizes maintaining structural integrity, using specialized repair mortars, epoxy systems, and reinforcement techniques to restore and potentially enhance the existing structural elements. The work is intended to address deterioration and ensure the long-term stability of the loading dock and tunnel-level structural systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL DRAWING LIST
1. ALL NEW WORK AND WORK IN THE EXISTING STRUCTURE SHALL CONFORM TO THE 2022
CONNECTICUT STATE BUILDING CODE (INTERNATIONAL BUILDING CODE [IBC] 2021 AND
INTERNATIONAL EXISTING BUILDING CODE [IEBC] 2021 WITH AMENDMENTS) AND ITS APPLICABLE
REFERENCED STANDARDS (HEREIN REFERRED TO AS THE BUILDING CODE).
2. ALL REFERENCES TO THE CONTRACTOR IN THIS SET OF DRAWINGS REFER TO THE GENERAL
CONTRACTOR, CONSTRUCTION MANAGER, AND OTHER PARTY OR PARTIES RESPONSIBLE FOR
THE EXECUTION OF THE PROJECT.
3. ALL REFERENCES TO A PROFESSIONAL ENGINEER, STRUCTURAL ENGINEER, AND
GEOTECHNICAL ENGINEER IN THIS SET OF DRAWINGS REFERS TO A PROFESSIONAL ENGINEER
COMPETENT IN THE RESPECTIVE FIELD OF DESIGN WHO IS REGISTERED IN THE STATE IN
WHICH THE PROJECT IS LOCATED.
4. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND
DIMENSIONS AS THEY RELATE TO NEW CONSTRUCTION. REPORT ALL OBSERVATIONS AND ANY
DISCREPANCIES TO THE ENGINEER OF RECORD AS A REQUEST FOR INFORMATION (RFI)
BEFORE PROCEEDING WITH WORK.
5. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE FOR A SAFE AND EFFICIENT
METHOD OF SHORING AND BRACING THE STRUCTURE DURING ALL CONSTRUCTION PHASES.
ALL SHORING AND BRACING SHALL BE DESIGNED BY A PROFESSIONAL ENGINEER ENGAGED BY
THE CONTRACTOR. SUBMIT AN OUTLINE OF PROPOSED PROCEDURE AND ITS IMPACT ON THE
BUILDING STRUCTURE FOR RECORD TO THE ENGINEER OF RECORD BEFORE PROCEEDING
WITH WORK.
6. THE EVALUATION OF THE STRUCTURE TO SAFELY SUPPORT ANY AND ALL CONSTRUCTION
LOADING (E.G. EQUIPMENT LOADS, TEMPORARY LOADS FROM DEBRIS AND MATERIAL
STORAGE) IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE HAS BEEN
DESIGNED FOR PERMANENT DEAD LOAD OF 280 PSF AND LIVE LOAD OF 250 PSF. THE
CONTRACTOR SHALL ENGAGE A STRUCTURAL ENGINEER TO EVALUATE PROPOSED
CONSTRUCTION LOADING AND TO DESIGN ALL TEMPORARY BRACING AND SHORING SYSTEMS
THAT MAY BE REQUIRED DUE TO THE CONTRACTOR'S MEANS AND METHODS AND SEQUENCE
OF CONSTRUCTION.
7. WHERE DETAILS FOR SPECIFIC CONDITIONS ARE NOT SHOWN ON THESE DRAWINGS, USE
DETAILS FOR THE MOST NEARLY SIMILAR CONDITIONS SHOWN ON THE STRUCTURAL
DRAWINGS AS DETERMINED BY THE STRUCTURAL ENGINEER OF RECORD. REPORT ANY
COORDINATION ISSUES IMMEDIATELY AS AN RFI FOR REVIEW.
8. COORDINATE WITH THE EXISTING, MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE
PROTECTION SYSTEMS FOR LOCATIONS AND DIMENSIONS OF CHASES, OPENINGS, BEAM
PENETRATIONS, AND OTHER INFORMATION THAT IMPACTS STRUCTURE THAT IS NOT SHOWN
ON THESE DRAWINGS. INCLUDE ADDITIONAL FRAMING AND REINFORCEMENT FOR SUCH WORK
PER THE TYPICAL STRUCTURAL DETAILS ON THESE DRAWINGS IN BASE CONTRACT.
9. ALL WORK SHALL BE MONITORED AND INSPECTED BY AN INDEPENDENT TESTING AND
INSPECTIONS AGENCY HIRED BY THE OWNER TO CARRY OUT ALL REQUIRED TESTING AND
INSPECTION WORK. SUBMIT ALL TESTING AND INSPECTION REPORTS IN PDF FORMAT TO THE
ENGINEER OF RECORD FOR REVIEW.
10. STRUCTURAL MEMBERS SHALL NOT BE MODIFIED WITHOUT WRITTEN APPROVAL FROM THE
STRUCTURAL ENGINEER OF RECORD. ANY ANTICIPATED MODIFICATIONS TO THE
CONSTRUCTION DOCUMENTS MUST BE SUBMITTED TO THE ENGINEER OF RECORD AS AN RFI
FOR REVIEW AND COMMENT. IN THE EVENT OF A CONSTRUCTION OR FABRICATION ERROR,
THE CONTRACTOR SHALL PREPARE A SKETCH AND CALCULATIONS, PREPARED BY A
STRUCTURAL ENGINEER, DOCUMENTING THE PROPOSED CORRECTIVE ACTION AND SUBMIT IT
TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL PRIOR TO PERFORMING ANY
CORRECTIVE WORK. WSP. CANNOT CERTIFY ANY UNAUTHORIZED DEVIATIONS FROM THE
CONSTRUCTION DOCUMENTS.
11. PRIOR TO REQUESTING A SITE VISIT BY WSP FOR OBSERVATION OF A COMPLETED STAGE OF
CONSTRUCTION, THE CONTRACTOR SHALL SUBMIT A STATEMENT TO THE ENGINEER OF
RECORD THAT ALL WORK HAS BEEN COMPLETED IN CONFORMANCE WITH THE STRUCTURAL
CONTRACT DRAWINGS AND SHOP DRAWINGS WITHOUT EXCEPTION, OR HAS BEEN PERFORMED
WITH FORMAL WRITTEN EXCEPTIONS ORIGINATING FROM OR AUTHORIZED BY WSP.
12. PRIOR TO RELEASE OF THE FINAL PROJECT STATEMENT OF PROFESSIONAL OPINION TO THE
BUILDING OFFICIAL, WSP REQUIRES A LETTER FROM THE CONTRACTOR'S PROJECT EXECUTIVE
IN RESPONSIBLE CHARGE STATING THAT ALL WORK INDICATED ON THE STRUCTURAL
DRAWINGS HAS BEEN PERFORMED WITHOUT EXCEPTION OR WAS PERFORMED WITH FORMAL
WRITTEN EXCEPTIONS ORIGINATING FROM OR AUTHORIZED BY WSP. IN ADDITION, WSP
REQUIRES A LETTER FROM THE PRINCIPAL OF THE TESTING AND INSPECTIONS AGENCY
CERTIFYING THAT ALL TESTING AND INSPECTIONS WORK HAS BEEN COMPLETED IN
CONFORMANCE WITH THE PROJECT STATEMENT OF SPECIAL INSPECTIONS AND THAT ALL
STRUCTURAL NONCONFORMANCE CONDITIONS FOUND HAVE BEEN BROUGHT INTO
CONFORMANCE WITH THE PROJECT STRUCTURAL REQUIREMENTS PRIOR TO PROJECT
COMPLETION.
13. THE TRADE CONTRACTORS SHALL SUBMIT SHOP AND ERECTION DRAWINGS AS WELL AS
PRODUCT DATA (COLLECTIVELY KNOWN HEREIN AS "SHOP DRAWINGS") FOR REVIEW PRIOR TO
PROCEEDING WITH FABRICATION AND/OR CONSTRUCTION.
a. THE SHOP DRAWINGS SHALL BE PREPARED IN ACCORDANCE WITH THE LATEST EDITION OF
THE CODE OF STANDARD PRACTICE FOR EACH RESPECTIVE TRADE IN CONJUNCTION WITH
ADDITIONAL SHOP DRAWING REQUIREMENTS INDICATED ON THESE DRAWINGS.
b. ALL SHOP DRAWINGS SHALL BE FULLY DEVELOPED BY THE TRADE CONTRACTORS OR BY
AGENTS OF THE CONTRACTORS. CAD FILES, PHOTOCOPIES, OR OTHER REPRODUCTIONS
OF THE CONTRACT DRAWINGS IN WHOLE OR IN PART SHALL NOT BE USED BY THE TRADE
CONTRACTORS OR THEIR AGENTS FOR THE PREPARATION AND DEVELOPMENT OF SHOP
DRAWINGS WITHOUT THE EXPRESSED WRITTEN CONSENT OF WSP.
c. ALL SUBMITTALS SHALL BE IN UNLOCKED PDF FORMAT WITH SEARCHABLE TEXT.
14. ALL 3D VIEWS INCLUDED ON THE STRUCTURAL DRAWINGS ARE FOR REFERENCE ONLY. THE 3D
VIEWS ONLY SHOW BASIC STRUCTURAL ELEMENTS; THEY DO NOT INCLUDE DETAILS SUCH AS
EXTERIOR RAMPS AND STAIRS, SLAB AND ROOF PITCHES, OR SPECIFIC STRUCTURAL DETAILS.
REFER TO ALL PLANS, DETAIL SHEETS, AND ARCHITECTURAL DRAWINGS FOR ADDITIONAL
INFORMATION. DO NOT SCALE OFF OF THESE DRAWINGS.
15. DO NOT SCALE OFF OF THESE DRAWINGS.
16. THIS PRICING SET OF DRAWINGS IS BEING PROVIDED FOR PRELIMINARY MAJOR STRUCTURAL
PRICING PURPOSES ONLY. THESE DRAWINGS ARE NOT TO BE USED FOR CONSTRUCTION OR
BIDDING PURPOSES. WHILE THESE DRAWINGS CAN BE USED TO OBTAIN A GENERAL
UNDERSTANDING OF THE STRUCTURAL SYSTEMS INVOLVED, OMISSIONS AND
INCONSISTENCIES BETWEEN SHEETS AND BETWEEN DIFFERENT TRADES WILL EXIST.
A. GENERAL
B. EXISTING CONDITIONS
1. EXISTING CONDITIONS ON THESE DRAWINGS ARE ASSUMED BASED ON LIMITED VISUAL
OBSERVATIONS AND LASER SCANNING OF THE EXISTING STRUCTURE AND SHALL BE VERIFIED
IN THE FIELD BY THE CONTRACTOR PRIOR TO COMMENCING WITH WORK.
2. THE CONTRACTOR SHALL CARRY CONTINGENCY IN PRICING FOR DIFFERENCES IN CONDITIONS
SHOWN, INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING CONDITIONS
b. DIFFERENT FOUNDATION CONDITIONS AND/OR OBSTRUCTIONS
c. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
d. ENCOUNTERED SITE CONDITIONS.
e. ADDITIONAL FRAMING TO SUPPORT MECHANICAL EQUIPMENT, PENETRATIONS DUE FINAL
COORDINATION WITH M.E.P. AND OTHER DRAWINGS.
3. LIMITED VISUAL OBSERVATIONS OF THE EXISTING STRUCTURE WERE PERFORMED IN THE FIELD
FROM BELOW, HOWEVER, MOST OF THE EXISTING FRAMING WAS CONCEALED AND COULD NOT
BE VIEWED. THE CONTRACTOR MUST INCLUDE ADEQUATE CONTINGENCY FOR REPAIRS TO
EXISTING DAMAGED OR INADEQUATE STRUCTURAL CONDITIONS DISCOVERED DURING
CONSTRUCTION.
4. IF THE CONTRACTOR DEEMS IT NECESSARY TO MODIFY OR REMOVE ANY PORTION OF THE
EXISTING STRUCTURE IN ORDER TO PERFORM THE WORK DESCRIBED WITHIN THE CONTRACT
DOCUMENTS, THEN SUCH PORTIONS OF THE STRUCTURE SHALL BE REPAIRED OR REPLACED
WITH EQUAL MATERIALS AND DETAILS TO MATCH THE EXISTING CONDITIONS AT NO ADDITIONAL COST TO THE OWNER; THIS WORK SHALL BE INCLUDED IN THE BASE PRICE OF THE CONTRACT.
5. WHERE DISCREPANCIES BETWEEN THE DESIGN DRAWINGS AND FIELD CONDITIONS ARE
FOUND, OR EXISTING STRUCTURAL MEMBERS AND CONNECTIONS ARE FOUND TO BE DAMAGED
OR DETERIORATED TO A DIMINISHED CAPACITY AND ARE NOT SHOWN ON THESE DRAWINGS,
THE CONTRACTOR SHALL SUBMIT DETAILED SKETCHES OF THE EXISTING CONDITIONS TO THE
ARCHITECT/ENGINEER FOR REVIEW PRIOR TO COMMENCING WITH WORK. MODIFICATIONS TO
CURRENT DETAILS OR ADDITIONAL NEW DETAILS MAY BE REQUIRED BASED ON THE ACTUAL
FIELD CONDITIONS.
6. EXISTING FRAMING MEMBERS SHOWN ON THESE DRAWINGS ARE DESIGNATED BY THEIR
NOMINAL SIZE, UNLESS NOTED OTHERWISE. ACTUAL MEMBER SIZES SHALL BE VERIFIED IN THE
FIELD.
7. THE EVALUATION OF THE EXISTING STRUCTURE TO SAFELY SUPPORT ANY AND ALL
CONSTRUCTION LOADING (E.G. EQUIPMENT LOADS, TEMPORARY LOADS FROM DEBRIS AND
MATERIAL STORAGE) IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR. THE DESIGN TEAM
HAS EVALUATED THE EXISTING STRUCTURE, AFTER IMPLEMENTATION OF THE STRUCTURAL
ALTERATIONS SHOWN ON THE DRAWINGS, FOR THE PERMANENT DEAD LOADS AND UNIFORM
LIVE LOADS INDICATED ON THE STRUCTURAL DRAWINGS ACCORDING TO THE REQUIREMENTS
OF THE BUILDING CODE. THE CONTRACTOR SHALL OBTAIN COPIES OF THE ORIGINAL
STRUCTURAL DRAWINGS FOR THE BUILDING AND ANY ADDITIONS AND ALTERATIONS (IF
AVAILABLE), AND SHALL ENGAGE A LICENSED STRUCTURAL ENGINEER TO EVALUATE THE
PROPOSED CONSTRUCTION LOADING ON THE EXISTING STRUCTURE AND TO DESIGN ALL
TEMPORARY BRACING AND SHORING SYSTEMS THAT MAY BE REQUIRED DUE TO THE
CONTRACTOR'S MEANS AND METHODS AND SEQUENCE OF CONSTRUCTION.
C. ENGINEERING REQUIREMENTS FOR THE CONTRACTOR
1. THE DESIGN OF ALL ENGINEERED SYSTEMS NOTED IN THIS SECTION, INCLUDING
CONNECTIONS OF EACH SYSTEM TO THE MAIN BUILDING STRUCTURE, ARE THE
RESPONSIBILITY OF THE CONTRACTOR. ALL ENGINEERED SYSTEMS SHALL CONFORM TO THE
BUILDING CODE AND SHALL BE PERFORMED BY AN INDEPENDENT STRUCTURAL ENGINEER
ENGAGED BY THE CONTRACTOR.
2. THE FOLLOWING ENGINEERED SYSTEMS ARE REQUIRED FOR THIS PROJECT. CALCULATIONS
AND SHOP DRAWINGS, BOTH SIGNED AND STAMPED BY A PROFESSIONAL ENGINEER ENGAGED
BY THE CONTRACTOR, ARE REQUIRED TO BE SUBMITTED FOR RECORD ONLY TO THE
ARCHITECT AND ENGINEER FOR EACH RESPECTIVE ENGINEERED SYSTEM BELOW.
A. CONCRETE SHORING AND FORMWORK - SHORING AND FORMWORK SHALL BE DESIGNED
SUCH THAT ALL EFFECTED SLABS, BEAMS, GIRDERS, COLUMNS AND WALLS ARE SHORED
TO THE TUNNEL FLOOR PAVEMENT (ALIGNED WITH THE EXISTING PLENUM WALLS) OR
FOUNDATIONS, UNTIL ALL DEAD LOAD IS APPLIED TO THE SLABS, BEAMS AND GIRDERS.
B. UTILITY SUPPORT - SUPPORT OF EXISTING UTILITIES SHALL BE PROVIDED UNTIL NEW
CONCRETE HAS ACHIEVED REQUIRED DESIGN STRENGTH.
D. STRUCTURAL DEMOLITION
1. ALL DEMOLITION WORK SHALL BE IN CONFORMANCE WITH THE BUILDING CODE AND ITS
APPLICABLE REFERENCED STANDARDS.
2. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND
DIMENSIONS AS THEY RELATE TO DEMOLITION AND NEW CONSTRUCTION. WHERE
DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS ARE ENCOUNTERED,
DEMOLITION SHALL NOT PROCEED WITHOUT WRITTEN APPROVAL FROM THE
ARCHITECT/ENGINEER OF RECORD.
3. ALL BIDDERS SHALL VISIT THE SITE TO BECOME FAMILIAR WITH THE EXISTING BUILDING, RELATED ACCESS LIMITATIONS FOR PERSONNEL AND EQUIPMENT, AND OTHER POTENTIAL
CONSTRUCTION COORDINATION ISSUES. DISCREPANCIES, OMISSIONS, OR VARIATIONS FROM
CONDITIONS NOTED ON THE STRUCTURAL DRAWINGS AND IN THE SPECIFICATIONS THAT ARE
DISCOVERED DURING THE BIDDING PERIOD SHALL BE IMMEDIATELY REPORTED TO THE
ARCHITECT/ENGINEER OF RECORD AS A REQUEST FOR INFORMATION (RFI).
4. ONLY DEMOLITION OF STRUCTURAL ELEMENTS IS SHOWN ON THE STRUCTURAL CONTRACT
DRAWINGS. DEMOLITION OF ADDITIONAL NONSTRUCTURAL ELEMENTS REQUIRED TO
DEMOLISH AND REMOVE THE STRUCTURAL ELEMENTS INDICATED SHALL BE COORDINATED
WITH THE ARCHITECT. IN GENERAL, NO COLUMNS, WALLS, BRACES, OR OTHER LOAD-
BEARING VERTICAL STRUCTURAL ELEMENTS SHALL BE REMOVED AS PART OF THIS
DEMOLITION UNLESS SPECIFICALLY NOTED ON THESE DRAWINGS.
5. IT IS SOLELY THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE FOR A SAFE AND
EFFICIENT METHOD OF SHORING AND/OR BRACING THE STRUCTURE DURING ALL DEMOLITION
AND CONSTRUCTION PHASES. NOTE THAT TEMPORARY BRACING IS REQUIRED FOR ALL
COLUMNS AND WALLS TO REMAIN WHERE INTERCONNECTED FRAMING MEMBERS (SUCH AS
BEAMS, GIRDERS, DIAGONAL BRACES, OR SLABS) ARE TO BE REMOVED.
6. THE CONTRACTOR SHALL ENGAGE A STRUCTURAL ENGINEER TO PROVIDE STAMPED AND
SIGNED STRUCTURAL CALCULATIONS AND DRAWINGS FOR ALL TEMPORARY SHORING AND
BRACING SYSTEMS, AS WELL AS AN ANALYSIS OF ANY TEMPORARY LOADS THAT THE
CONTRACTOR CHOOSES TO IMPOSE UPON THE EXISTING STRUCTURE (SEE SECTION
REGARDING ENGINEERING REQUIREMENTS FOR CONTRACTOR). THE CONTRACTOR SHALL
PROVIDE ALL ADDITIONAL SHORING, FLOOR REINFORCEMENT, AND OTHER MEASURES AS
REQUIRED TO SUPPORT SUCH TEMPORARY LOADS. ALL SHORING SHALL BE PLACED
CONTINUOUS DOWN TO FOUNDATIONS. SUBMIT A DETAILED PLAN OF DEMOLITION AND
SHORING, STAMPED BY THE SAME STRUCTURAL ENGINEER, FOR RECORD.
7. DEMOLITION WORK SHALL BE PERFORMED IN SUCH A MANNER AS TO PRESERVE THE
INTEGRITY OF ALL ADJACENT STRUCTURAL AND NONSTRUCTURAL BUILDING ELEMENTS.
WHERE NECESSARY, PRECUT CONNECTIONS TO STRUCTURAL ELEMENTS TO REMAIN IN
ORDER TO AVOID DAMAGE DURING REMOVAL OF CONNECTED MEMBERS. ANY DAMAGE TO
EXISTING ELEMENTS AND FINISHES TO REMAIN SHALL BE REPAIRED BY THE CONTRACTOR AT
THEIR OWN EXPENSE.
8. WHERE EXISTING CONCRETE SLABS AND OTHER FLOOR SYSTEMS INTEGRATED WITH THE
WALL CONSTRUCTION ARE TO BE REMOVED, SAWCUT EXISTING SLABS ALL ALONG EXISTING
WALLS TO REMAIN PRIOR TO PROCEEDING WITH DEMOLITION IN ORDER TO MINIMIZE
VIBRATION TRANSMISSION THROUGH SLABS INTO WALLS DURING DEMOLITION PROCESS.
ENSURE EXISTING SLABS AND WALLS ARE ADEQUATELY SHORED AND BRACED PRIOR TO
SAWCUTTING.
E. CONTRACTOR QUALITY ASSURANCE REQUIREMENTS
1. THE CONTRACTOR SHALL COORDINATE SCHEDULE OF CONSTRUCTION TO ALLOW
FOR ALL TESTS AND INSPECTIONS TO TAKE PLACE.
2. THE FOLLOWING QUALITY ASSURANCE TESTS AND INSPECTIONS SHALL BE
PERFORMED FOR CAST-IN-PLACE CONCRETE:
a. TEST CONCRETE COMPRESSIVE STRENGTH (ASTM C31 AND C39), SLUMP
(ASTM C143), AIR CONTENT (ASTM C231 OR C173), AND TEMPERATURE (ASTM
C1064).
b. CAST AND LABORATORY CURE SIX STANDARD CYLINDER SPECIMENS FOR
EACH COMPOSITE SAMPLE AND PERFORM COMPRESSION TESTS PER
ASTM C 31/C 31M.
3. TESTING FREQUENCY: OBTAIN AT LEAST ONE SAMPLE FOR EACH 50 CU. YD. OR
FRACTION THEREOF OF EACH CONCRETE MIXTURE PLACED EACH HALF DAY.THE
FOLLOWING QUALITY ASSURANCE TESTS AND INSPECTIONS SHALL BE
PERFORMED FOR MASONRY:
a. LEVEL C QUALITY ASSURANCE PER TMS 602/ACI 530.1/ASCE 6 "SPECIFICATION
FOR MASONRY STRUCTURES".
F. CONCRETE
1. ALL CONCRETE WORK SHALL BE IN CONFORMANCE WITH THE BUILDING CODE AND ACI 318 AND
301 REQUIREMENTS. THIS SHALL INCLUDE, BUT NOT BE LIMITED TO, PROPORTIONING OF
CONCRETE MIX, CONCRETE TESTING, PLACEMENT OF CONCRETE, AND CURING PROCEDURES.
2. WHERE CONCRETE STRENGTH IS NOT SPECIFICIED, PROVIDE A MINIMUM COMPRESSIVE
STRENGTH, f'c OF 4,000PSI.
3. ALL REINFORCING STEEL SHALL CONFORM TO THE FOLLOWING MATERIAL SPECIFICATIONS:
a. REINFORCING BARS: ASTM A615 (Fy=60 KSI, MIN.)
b. WELDED WIRE REINFORCEMENT: ASTM A1064 (Fy=60 KSI, MIN.)
c. REINFORCING BARS TO BE WELDED: ASTM A615 OR ASTM A706 (Fy=60 KSI, MIN.)
d. EPOXY-COATED REINFORCING BARS: ASTM A775 OR ASTM A934
e. EPOXY-COATED WELDED WIRE REINFORCEMENT: ASTM A884
4. ALL STIRRUPS AND TIES SHALL BE CLOSED TYPE AND ALL HOOKS SHALL BE STANDARD 90°
TYPE, UNLESS OTHERWISE NOTED.
5. WHERE NO REINFORCEMENT IS INDICATED FOR CONCRETE SLABS AND WALLS, PROVIDE A
MINIMUM #4 @ 12" O.C. CONTINUOUS EACH WAY, TOP AND BOTTOM (OR EACH FACE OF WALL).
6. PROVIDE CORNER BARS AT ALL CORNERS AND INTERSECTIONS MATCHING HORIZONTAL
REINFORCEMENT WITH 2'-6" MINIMUM LAPS.
7. PROVIDE A MINIMUM OF 1-#5 SUPPORT BAR AT ALL STIRRUP BENDS WHERE PRIMARY BARS DO
NOT EXIST.
8. SET AND TIE ALL REINFORCEMENT, ANCHOR BOLTS, AND CAST-IN AND EMBEDDED ITEMS PRIOR
TO PLACING CONCRETE. SETTING OF DOWELS AND REINFORCEMENT INTO WET CONCRETE
SHALL NOT BE ALLOWED.
9. REINFORCING LAP SPLICES SHALL BE IN ACCORDANCE WITH ACI-318 FOR TENSION LAP
SPLICES, CLASS B, UNLESS NOTED OTHERWISE. SEE DRAWINGS FOR SPECIAL LAP SPLICE
INSTRUCTIONS AT FOUNDATION WALLS AND GRADE BEAM/PILE CAP INTERSECTIONS.
10. IN SLABS AND BEAMS, LAP SPLICE CONTINUOUS BOTTOM REINFORCEMENT ONLY AT SUPPORT
LOCATIONS AND CONTINUOUS TOP REINFORCEMENT ONLY AT CENTERS OF SPANS, UNLESS
NOTED OTHERWISE. PROVIDE STANDARD HOOK FOR TOP BARS AT ALL DISCONTINUOUS ENDS
AND SUPPORTS.
11. DETAILING OF REINFORCEMENT SHALL BE ACCORDING TO THE LATEST EDITION OF THE ACI 315
"MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES".
PROVIDE BAR SUPPORTS, SPACERS, AND ACCESSORIES RECOMMENDED IN THE LATEST
EDITION OF THE ACI DETAILING MANUAL, PUBLICATION SP-66. ALL ACCESSORIES IN CONTACT
WITH EXPOSED SURFACES SHALL BE PLASTIC-COATED. PROVIDE SCHEDULE OF ALL
ACCESSORIES WITH SHOP DRAWINGS FOR REVIEW.
12. CONCRETE SHALL MEET THE FOLLOWING MINIMUM PERCENTAGES OF ITS 28 DAY
COMPRESSIVE STRENGTH (f'c) PRIOR TO REMOVING FORMS AND/OR SHORES:
a. ALL CONCRETE EXCEPT AS NOTED BELOW ..................................... 40%
b. BEAM BOTTOMS (IF SHORED) .............................................................. 70%
c. FLOOR SYSTEMS .................................................................................... 80%
13. UNLESS NOTED OTHERWISE, PROVIDE REINFORCEMENT COVER PER THE TABLE AT THE END
OF THIS SECTION.
14. ALL CONCRETE SHALL BE PLACED WITHOUT HORIZONTAL CONSTRUCTION JOINTS, EXCEPT
WHERE SPECIFICALLY INDICATED. VERTICAL CONSTRUCTION JOINTS AND STOPS IN THE
CONCRETE WORK SHALL BE MADE AT MIDSPAN. ALL REINFORCEMENT SHALL BE CONTINUOUS
THROUGH VERTICAL CONSTRUCTION JOINTS.
15. PROVIDE SAWCUT JOINTS IN ALL SLABS ON GRADE USING AN EARLY-ENTRY SAW WITHIN 4
HOURS OF PLACEMENT. PROVIDE SAWCUTS @ 10'-0" O.C. MAX., UNLESS NOTED OTHERWISE.
16. PLACE ALL SLABS PER ACI 301 AND ACI 302.1 SPECIFICATIONS.
17. WHERE NECESSARY DUE TO CONGESTION OF REINFORCEMENT, CONTRACTOR SHALL PROVIDE
MECHANICAL BAR COUPLERS AND BAR TERMINATORS IN LIEU OF LAP SPLICES AND HOOKED
ENDS PER ACI REQUIREMENTS. THE CONTRACTOR SHALL INCLUDE THE COST OF SUCH
MECHANICAL ACCESSORIES IN BASE CONTRACT.
18. ALL CONCRETE TEST CYLINDERS FOR CONCRETE COMPRESSIVE TESTING SHALL BE PREPARED
PER ACI REQUIREMENTS AND APPLICABLE ASTM STANDARDS.
19. ALL CONCRETE MIX DURATION TIMES SHALL BE LESS THAN 90 MINUTES.
20. ALL CONCRETE MUST BE PLACED FROM A HEIGHT NOT GREATER THAN 4'-0" ABOVE ITS FINAL
POSITION.
21. ADDITIONAL REQUIREMENTS FOR CONCRETE EXPOSED TO VEHICULAR TRAFFIC OR WEATHER
(NOTED HEREIN AS TRAFFIC AREAS) SHALL BE AS FOLLOWS:
a. ALL TRAFFIC AREAS SHALL INCLUDE PROVISIONS FOR ADEQUATE DRAINAGE. THE SLOPE
OF SLABS SHALL BE CONSTRUCTED IN SUCH A MANNER THAT THE WATER FLOWS IN THE
DESIRED DIRECTION WITHOUT PONDING, WITH A MINIMUM SLOPE OF 2%. WATER FLOW
SHALL BE UNOBSTRUCTED BY ISLANDS, CURBS, AND OTHER FEATURES. WHERE A SLOPE
IS NOT INDICATED ON THESE DRAWINGS, AVERAGE ELEVATIONS ARE GIVEN. THE 2%
MINIMUM PITCH MUST BE MAINTAINED.
b. ALL SLAB REINFORCEMENT AT TRAFFIC AREAS SHALL BE EPOXY COATED WITH A 1 1/2"
MINIMUM COVER.
c. ALL COLUMN AND WALL REINFORCEMENT WITHIN THE TRAFFIC AREAS SHALL BE EPOXY
COATED EXCEPT REINFORCEMENT ON UNEXPOSED FACES MAY BE UNCOATED.
d. PROVIDE A CORROSION INHIBITING ADMIXTURE, GRACE DCI OR APPROVED EQUAL, 3
GALLONS PER CUBIC YARD, TO ALL CONCRETE IN TRAFFIC AREAS.
e. PROVIDE A MAXIMUM WATER/CEMENT RATIO, W/C = 0.40 FOR ALL TRAFFIC AREA CONCRETE.
f. PROVIDE A WATERPROOF HEAVY-DUTY, FLUID-APPLIED, MULTI-LAYER ELASTOMERIC
POLYURETHANE TRAFFIC-BEARING MATERIAL WITH INTEGRAL NONSKID TRAFFIC TOPPING
AT ALL ELEVATED SLABS AT TRAFFIC AREAS.
g. PROVIDE AN APPROVED CONCRETE SEALER (SIKA 701W OR APPROVED EQUAL) AT ALL
SLABS ON GRADE IN TRAFFIC AREAS.
h. PROVIDE AN APPROVED CONTINUOUS POLYURETHANE WATER-PROOFING
COATING (SIKA FLOOR 450/455 OR APPROVED EQUAL AT ALL JOINTS BETWEEN ELEVATED
SLABS AND VERTICAL SURFACES (SUCH AS CONCRETE PIERS AND CONCRETE FOUNDATION
WALLS) IN TRAFFIC AREAS.
22. SUBMIT PROPOSED MIX DESIGN OF EACH CONCRETE TYPE AND REINFORCING SHOP
DRAWINGS FOR REVIEW.
MINIMUM REINFORCEMENT COVER
CONCRETE EXPOSURE REINFORCEMENT MINIMUM COVER1
ALL ALL
ALL
SLABS AND
WALLS
NO. 6 THROUGH
NO. 18 BARS
NO. 14 AND
NO. 18 BARS
MEMBER
3 INCHES
2 INCHES
1-1/2 INCHES
CAST AGAINST AND
PERMANENTLY IN
CONTACT WITH GROUND
EXPOSED TO WEATHER
OR IN CONTACT WITH
GROUND
NOT EXPOSED TO
WEATHER OR IN
CONTACT WITH GROUND
NO. 5 BAR, W31
OR D31 WIRE,
AND SMALLER
1-1/2 INCHES
NO. 11 BAR
AND SMALLER
PRIMARY
REINFORCEMENT,
STIRRUPS, TIES,
SPIRALS, AND HOOPS
BEAMS,
COLUMNS,
PEDESTALS, AND
TENSION TIES
3/4 INCH
1-1/2 INCHES
NOTES:
1. MINIMUM COVER IS INDICATED IN THIS TABLE. SEE STRUCTURAL DETAILS FOR
LOCATIONS WHERE GREATER COVER IS REQUIRED.
G. STRUCTURAL MASONRY
1. ALL MASONRY WORK SHALL CONFORM TO THE BUILDING CODE AS WELL AS THE BUILDING
CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES (TMS 402/ACI
530/ASCE 5, AND TMS 602/ACI 530.1/ASCE 6) AND COMPANION COMMENTARIES AS WELL AS
THE STANDARDS OF THE NATIONAL CONCRETE MASONRY ASSOCIATION (NCMA). THIS SHALL
INCLUDE, BUT NOT BE LIMITED TO, ERECTION, GROUT PLACEMENT, CURING, AND WEATHER
PROTECTION.
2. ALL CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C-90 WITH THE STRENGTH OF
UNITS AND MORTAR BEING SUCH THAT THE (f'm) VALUES INDICATED ARE SATISFIED.
3. ALL MORTAR SHALL CONFORM TO ASTM C-270, TYPE (M) OR (S). ALL GROUT SHALL CONFORM TO ASTM C-476. MINIMUM COMPRESSIVE STRENGTH OF GROUT SHALL BE f'c = 3000 PSI, U.N.O.
4. MINIMUM COMPRESSIVE STRENGTH OF CONCRETE MASONRY SHALL BE f'm=1500 PSI, UNLESS
NOTED OTHERWISE.
5. ALL REINFORCING STEEL SHALL CONFORM TO THE FOLLOWING MATERIAL SPECIFICATIONS:
a. REINFORCING BARS: ASTM A615 (Fy=60 KSI, MIN.)
b. WIRE JOINT REINFORCEMENT: ASTM A951 (Fy=70 KSI, MIN.)
c. REINFORCING BARS TO BE WELDED: ASTM A615 AND A706 (Fy=60 KSI, MIN.)
6. PROVIDE GALVANIZED "LADDER TYPE" STANDARD WEIGHT (9 GA.) HORIZONTAL JOINT
REINFORCEMENT AT 16" O.C. VERTICALLY, UNLESS NOTED OTHERWISE.
7. MINIMUM CMU WALL REINFORCEMENT SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE:
A. VERTICAL REINFORCEMENT: #6 @ 24" O.C. (MAXIMUM)
B. HORIZONTAL REINFORCEMENT: (2) #4 @ 4'-0" O.C. (MAXIMUM)
8. PROVIDE ADDITIONAL CONTINUOUS BOND BEAMS WITH (2) #5 CONTINUOUS AT ALL FLOOR
LEVELS, COURSES TO RECEIVE CAST-IN OR POST-INSTALLED ANCHORS, TOPS OF ALL CMU
WALLS, AND AT MID-HEIGHT BETWEEN EACH FLOOR LEVEL. BOND BEAM VERTICAL SPACING
SHALL NOT EXCEED 4'-0" O.C., U.N.O.
9. PROVIDE ADDITIONAL VERTICAL REINFORCEMENT AT JAMBS OF ALL WALL OPENINGS, ENDS
OF WALL, AND STEEL BEAM OR ANGLE BEARING LOCATIONS. MINIMUM REINFORCEMENT
SHALL BE (2) VERTICAL BARS TO MATCH WALL REINFORCEMENT, U.N.O.
10. PROVIDE STANDARD LAP SPLICES FOR VERTICAL AND HORIZONTAL REINFORCEMENT, WITH A
SPLICE LENGTH NOT LESS THAN (48) BAR DIAMETERS. PROVIDE MECHANICAL COUPLERS,
CAPABLE OF DEVELOPING 150% OF THE TENSILE STRENGTH OF THE REINFORCING BAR, FOR
#7 AND LARGER VERTICAL REINFORCING BARS TO MINIMIZE CONGESTION OF
REINFORCEMENT WHERE MINIMUM REINFORCEMENT COVER CANNOT BE MAINTAINED.
11. PROVIDE MATCHING DOWELS INTO FOUNDATION WALLS AT ALL VERTICAL REINFORCEMENT
LOCATIONS - SEE TYPICAL DETAILS.
12. ALL BOND BEAMS, REINFORCED CELLS, AND CELLS BELOW GRADE SHALL BE GROUTED
SOLID.
13. ALL MASONRY WORK SHALL BE MONITORED AND INSPECTED BY AN INDEPENDENT TESTING
AGENCY. SUBMIT FIELD REPORTS FOR REVIEW. PROVIDE "LEVEL C" QUALITY ASSURANCE,
INCLUDING CONTINUOUS MONITORING OF GROUTING OPERATIONS AND ALL REQUIRED
PRISM TESTS, PER TMS 602/ACI 530.1/ASCE 6.
14. SUBMIT REINFORCING STEEL SHOP DRAWINGS FOR REVIEW.
ISSUED FOR PERMIT
MARCH 18, 2025
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S0.0
B2305503.000
RAB
GENERAL
STRUCTURAL
NOTES
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
S0.0 GENERAL STRUCTURAL NOTES
S1.0 EXISTING PLANS
S1.1 DEMOLITION PLANS
S1.2 NEW WORK PLANS
S2.0 SECTIONS ALONG LINE 7
S2.1 SECTIONS ALONG LINE 7
S2.2 SECTIONS ALONG LINE 7
S2.3 SECTIONS ALONG LINE 7 & CORBEL DETAILS
S3.0 SECTIONS ALONG LINE 13
S3.1 SECTIONS ALONG LINE 13
S3.2 SECTIONS ALONG LINE 13
S4.0 TYPICAL CONCRETE REPAIR DETAILS
S4.1 TYPICAL CONCRETE REPAIR DETAILS
S4.2 TYPICAL CONCRETE REPAIR DETAILS
S5.1 WATERPROOFING DETAILS
3-18-2025
ZShapiro Rectangle
ZShapiro Line
ZShapiro Line
ZShapiro Line
ZShapiro Line
ZShapiro Line
Vh
Th
S
S2.2
S2.2
S2.0
S2.1
S3.0
S3.1
S3.2
S3.2
EXIST. SIDEWALK, TYP.
EXIST. STEEL
GRATING, TYP.
EXIST. PAVEMENT
EXIST. LOADING DOCK
EXIST. CONC. COLUMN
EXIST. CMU WALL
EXIST. CONC.
COLUMN
EXIST. REINF.
CONC. WALL
'-0
'-0
EXIST. SIDEWALK
EXIST. CONC.
COLUMN
EXIST. CONC. COLUMN
'-6
/8
8'
-1
'-6
/4
'-0
'-0
/2
'-1
/4
/4
'-0
'-1
/8
'-1
/2
/8
'-9
/8
11' - 7 9/16" ±
9' - 3 9/16" ±
VARIES
PLENUM WALLS BELOW
± 2'-0" ± 2'-0"
'-6
/4
± 10 1/4"
3' - 8" ±
TOP OF MAT
FOUNDATION (BELOW)
Vh
Th
S
S2.2
S2.2
S2.0
S2.1
S3.0
S3.1
S3.2
S3.2
EXIST. REINF. CONC.
BEAMS & SLABS
EXIST. REINF. CONC.
BEAMS & SLABS
'-0
DETERIORATED
REINF. CONC.
BEAM
DETERIORATED
REINF. CONC.
BEAM
DETERIORATED
REINF. CONC. BEAM,
CORBEL & COLUMN DETERIORATED REINF.
CONC. CORBEL &
COLUMN
S2.3
_____________________ 1
S2.3
_____________________SIM.
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
NOTES REGARDING 3D VIEWS
ALL 3D VIEWS ARE FOR REFERENCE ONLY. THE 3D VIEWS ONLY SHOW
BASIC STRUCTURAL ELEMENTS; THEY DO NOT NECESSARILY INCLUDE
ALL DETAILS SUCH AS RAMPS, STAIRS, SLAB AND ROOF PITCHES, OR
SPECIFIC STRUCTURAL DETAILS. REFER TO ALL PLANS, DETAIL SHEETS,
AND OTHER DRAWINGS FOR ADDITIONAL INFORMATION. DO NOT SCALE
OFF THIS DRAWING.
ISSUED FOR PERMIT
MARCH 18, 2025
Vh
Th
S
S2.2
S2.2
S2.0
S2.1
S3.0
S3.1
S3.2
S3.2
'-0
'-0
± 16'-4"
EXIST. CONCRETE SIDEWALK
w/ STENCILED PATTERN
EXIST. CONCRETE DRIVE-THRU w/
STENCILED PATTERN
EXIST.
CURTAINWALL
SYSTEM
EXIST REINF.
CONC. COLUMN w/
ARCHITECTURAL
FINISH, TYP.
VARIES
VARIES
S2.3
EXIST. CONCRETE SIDEWALK
w/ STENCILED PATTERN
VARIES
VARIES
VARIES
S2.3
SIM.
EXIST. CONC. w/
STENCILED PATTERN
EXIST. PLAIN CONC. OVER
PLASTIC SHEETING, 1-1/2"
SAND, 1-1/2" CONC.
TOPPING SLAB
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
1/4" = 1'-0"
S1.0
B2305503.000
RAB
EXISTING PLANS
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 1/4" = 1'-0"
TUNNEL LEVEL PLAN - EXISTING
SCALE: 1/4" = 1'-0"
FIRST FLOOR FRAMING PLAN - EXISTING
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - EXISTING
N.T.S.
3D EXISTING TUNNEL LEVEL
N.T.S.
3D EXISTING FIRST FLOOR LEVEL
N.T.S.
3D VIEW AT LOADING DOCK
3-18-2025
Th
S
6 13
S2.0
S2.1
S2.2
S2.2
S3.0
S3.1
S3.2
PORTION OF CMU
WALL TO BE
DEMOLISHED TO
ALLOW FOR
COLUMN REPAIRS
PORTION OF CMU
WALL TO BE
DEMOLISHED TO
ALLOW FOR
COLUMN REPAIRS
Vh
Th
S
6 13
S2.0
_____________________ 2
S2.1
S2.2
S2.2
S3.0
S3.1
S3.2
DEMO REINF.
CONC. BEAMS
& SLABS
DEMO REINF.
CONC. BEAMS
& SLABS
DEMO EXIST.
CORBEL FLUSH
TO COL. FACE
CHIP AWAY
LOOSE CONC. @
CORBEL & COL.
S2.3
VERIFY
CONDITION OF
EXIST. BEAMS
VERIFY
CONDITION OF
EXIST. BEAMS
S2.3
_____________________SIM.
AT LEAST 12" LENGTH OF
EXIST. BEAM TOP & BTM.
REINF. TO REMAIN FOR
CONNECTION OF NEW REINF.
KEEP SLOPED WALL
AT LEAST 12" LENGTH OF
EXIST. BEAM TOP & BTM.
REINF. TO REMAIN FOR
CONNECTION OF NEW REINF.
KEEP SLOPED WALL
AT LEAST 12" LENGTH OF
EXIST. BEAM TOP & BTM.
REINF. TO REMAIN FOR
CONNECTION OF NEW REINF.
AT LEAST 12" LENGTH OF
EXIST. BEAM TOP & BTM.
REINF. TO REMAIN FOR
CONNECTION OF NEW REINF.
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
NOTES REGARDING 3D VIEWS
ALL 3D VIEWS ARE FOR REFERENCE ONLY. THE 3D VIEWS ONLY SHOW
BASIC STRUCTURAL ELEMENTS; THEY DO NOT NECESSARILY INCLUDE
ALL DETAILS SUCH AS RAMPS, STAIRS, SLAB AND ROOF PITCHES, OR
SPECIFIC STRUCTURAL DETAILS. REFER TO ALL PLANS, DETAIL SHEETS,
AND OTHER DRAWINGS FOR ADDITIONAL INFORMATION. DO NOT SCALE
OFF THIS DRAWING.
Vh
Th
S
S2.0
S2.1
S2.2
S2.2
S3.0
S3.1
S3.2
S3.2
'-0
'-0
± 16'-4"
DEMO PORTION OF SIDEWALK,
TOPPING SLAB AS REQ'D. TO
PROVIDE ACCESS FOR NEW
REINF. CONC BEAM (BELOW)
S2.3
3' - 1" ± 3' - 6" ± 3' - 6" ± 3' - 1" ±
S2.3
_____________________SIM.
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
ISSUED FOR PERMIT
MARCH 18, 2025
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
1/4" = 1'-0"
S1.1
B2305503.000
RAB
DEMOLITION
PLANS
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 1/4" = 1'-0"
TUNNEL LEVEL PLAN - DEMOLITION
SCALE: 1/4" = 1'-0"
FIRST FLOOR FRAMING PLAN - DEMOLITION
N.T.S.
3D-TUNNEL LEVEL DEMO
N.T.S.
3D-FIRST FLOOR LEVEL DEMO
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - DEMOLITION
N.T.S.
Th
S
6 13
S2.0
S2.1
S2.2
S2.2
S3.0
S3.2
S3.2
M8
M8
M8
M8
S3.1
#4 DOWELS, 12" LONG, 6"
EMBED., 24" O.C. AT
EXIST./NEW CMU WALL, TYP.
NEW CORBEL.
SEE SHEET S2.3
NEW CORBEL.
SEE SHEET S2.3
Vh
Th
S
6 13
S2.0
S2.1
S2.2
S2.2
S3.0
S3.2
S3.2
S2.3
BEAM REPAIR
T.B.D.
BEAM REPAIR
T.B.D.
S3.1
S2.3
_____________________SIM.
NEW REINF.
CONC. BEAMS.
SEE SECTIONS.
NEW REINF.
CONC. BEAMS.
SEE SECTIONS.
D x W
D x W
D x W
D x W
NEW CORBEL
BELOW
NEW CORBEL
BELOW
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
NOTES REGARDING 3D VIEWS
ALL 3D VIEWS ARE FOR REFERENCE ONLY. THE 3D VIEWS ONLY SHOW
BASIC STRUCTURAL ELEMENTS; THEY DO NOT NECESSARILY INCLUDE
ALL DETAILS SUCH AS RAMPS, STAIRS, SLAB AND ROOF PITCHES, OR
SPECIFIC STRUCTURAL DETAILS. REFER TO ALL PLANS, DETAIL SHEETS,
AND OTHER DRAWINGS FOR ADDITIONAL INFORMATION. DO NOT SCALE
OFF THIS DRAWING.
Vh
Th
S
S2.0
S2.1
S2.2
S2.2
S3.0
S3.2
S3.2
'-0
'-0
± 16'-4"
S2.3
S3.1
S2.3
_____________________SIM.
NEW PAVING &
PAVEMENT TO
MATCH EXIST.
NEW PAVING &
PAVEMENT TO
MATCH EXIST.
NEW SIDEWALK
TO MATCH EXIST.
NEW SIDEWALK
TO MATCH EXIST.
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
ISSUED FOR PERMIT
MARCH 18, 2025
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
1/4" = 1'-0"
S1.2
B2305503.000
RAB
NEW WORK
PLANS
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 1/4" = 1'-0"
TUNNEL LEVEL PLAN - NEW WORK
SCALE: 1/4" = 1'-0"
FIRST FLOOR LEVEL PLAN - NEW WORK
N.T.S.
3D-TUNNEL LEVEL REINFORCEMENT
N.T.S.
3D-FIRST FLOOR REINFORCEMENT
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - NEW WORK
NEW WALL SCHEDULE
MARK DESCRIPTION REINFORCEMENT (U.N.O.)
M8 8" CMU WALL #6 VERT. @ 24" O.C.,(2) #4 @ 48" O.C.
N.T.S.
11' - 7 9/16"± Loading Dock Level
Vh Th S
S2.2
S2.2
DETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. PLAIN CONC. OVER
PLASTIC SHEETING, 1-1/2"
SAND, 1-1/2" CONC.
TOPPING SLAB
EXIST. REINF. CONC. COLUMN
EXIST. REINF. CONC. WALL
EXIST. CONC. SIDEWALK EXIST. PAVING
EXIST. CMU WALL
DETERIORATED EXIST.
REINF. CONC. COLUMN
DETERIORATED EXIST.
REINF. CONC. CORBEL
EXIST. LOADING DOCK
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
WALL EXPANSION JOINT
EXIST. CONCRETE
SIDEWALK w/
STENCILED PATTERN
EXIST. PLENUM WALLS
S2.3
/2
11' - 7 9/16"± Loading Dock Level
Vh Th S
S2.2
S2.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
DEMO EXIST. PLAIN
CONC. PAVING
DEMO EXIST. 1 1/2" SAND
DEMO EXIST. 1 1/2"
CONC. SLAB
DEMO EXIST. CONC.
BEAMS, SLABS & REINF.
DEMO CONC.
SIDEWALK
DEMO PORTION OF
CONC. SIDEWALK
DEMO PORTION OF
CMU WALL AS REQ'D.
TO REPAIR CONC. COL.
KEEP SLOPED WALL
AT LEAST 12" LENGTH
OF EXIST BEAM TOP &
BTM. REINF. TO REMAIN
FOR CONNECTION OF
NEW REINF. 3' - 0" ±
DEMO EXIST.
CORBEL FLUSH
TO COL. FACE
AT LEAST 12" LENGTH OF
EXIST BEAM TOP & BTM.
REINF. TO REMAIN FOR
CONNECTION OF NEW REINF.
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
11' - 7 9/16"± Loading Dock Level
Vh Th S3
S2.2
S2.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
NEW PAVING TO
MATCH EXIST.
NEW COMPACTED
STONE FILL
NEW WATERPROOFING
AS PER BUILDING
ENVELOPE SPECIALIST
NEW 1 1/2" CONC. SLAB
NEW CONC. BEAMS,
SLABS & REINF. SEE
SECTIONS.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CMU
NEW CORBEL
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
S2.3
#4 DOWELS, 12" LONG, 6"
EMBED., 24" O.C. AT
EXIST./NEW CMU WALL, TYP.
3' - 0" ±
ISSUED FOR PERMIT
MARCH 18, 2025
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S2.0
B2305503.000
RAB
SECTIONS
ALONG LINE 7
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 3/8" = 1'-0"
SECTION - EXISTING
SCALE: 3/8" = 1'-0"
SECTION - DEMOLITION
SCALE: 3/8" = 1'-0"
SECTION - NEW WORK
PHOTO LOOKING AT BEAMS ALONG LINE 7
3-18-2025
ZShapiro Callout
RED LINE INDICATES 1-1/2" SAND LAYER
VhThS 1
S2.2
S2.2
DETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. REINF. CONC. SLAB
EXIST. REINF. CONC. COLUMN
EXIST. REINF. CONC. WALL
EXIST. CONC. SIDEWALKEXIST. PAVING
& CONC. SLAB
EXIST. CMU WALL
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
EXIST. PLENUM WALLS
S2.3
EXIST. CONCRETE
DRIVE-THRU w/
STENCILED PATTERN
EXIST. CONCRETE
SIDEWALK w/
STENCILED PATTERN
VhThS
S2.2
S2.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
DEMO STENCILED
CONC. PAVING.
DEMO EXIST. CONC.
BEAMS, SLABS & REINF.
DEMO PORTION
OF CONC.
SIDEWALK
DEMO PORTION OF
CONC. SIDEWALK
DEMO PORTION OF
CMU WALL AS REQ'D.
TO REPAIR CONC. COL.
AT LEAST 12" LENGTH
OF EXIST BEAM TOP &
BTM. REINF. TO REMAIN
FOR CONNECTION OF
NEW REINF.AT LEAST 12" LENGTH OF
EXIST BEAM TOP & BTM.
REINF. TO REMAIN FOR
CONNECTION OF NEW REINF.
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
VhThS
S2.2
S2.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
NEW WATERPROOFING
AS PER BUILDING
ENVELOPE SPECIALIST
NEW CONC. BEAMS,
SLABS & REINF. SEE
SECTIONS.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CMU
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
#4 DOWELS, 12" LONG, 6"
EMBED., 24" O.C. AT
EXIST./NEW CMU WALL, TYP.
ISSUED FOR PERMIT
MARCH 18, 2025
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S2.1
B2305503.000
RAB
SECTIONS
ALONG LINE 7
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 3/8" = 1'-0"
SECTION - EXISTING
SCALE: 3/8" = 1'-0"
SECTION - DEMOLITION
SCALE: 3/8" = 1'-0"
SECTION - NEW WORK
PHOTO LOOKING AT BEAMS ALONG LINE 7
3-18-2025
ZShapiro Text Box
NEW PAVING TO MATCH EXISTING
ZShapiro Text Box
NEW COMPACTED STONE FILL
ZShapiro Text Box
NEW 1 1/2" CONC SLAB
S2.0
S2.1
DETERIORATED EXIST.
REINF. CONC. BEAM
DETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. REINF.
CONC. COLUMN
EXIST. REINF.
CONC. WALL
EXIST. CONC. SIDEWALK
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
EXIST. WALL
EXPANSION JOINT
EXIST. CONC. SIDEWALK
EXIST. PLAIN CONC. OVER
PLASTIC SHEETING, 1-1/2" SAND,
1-1/2" CONC. TOPPING SLAB
EXIST. REINF.
CONC. SLAB
/4
/4
EXIST. PAVING
& CONC. SLAB
S2.3
SIM.
EXIST. CONC. w/
STENCILED PATTERN
S2.0
S2.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DEMO PORTION OF
SIDEWALK, CONC. PAVING,
SAND, ETC. AS REQ'D. TO
PROVIDE ACCESS FOR NEW
REINF. CONC BEAM (BELOW)
DEMO EXIST. REINF.
CONC. BEAM. AT ENDS OF
BEAMS AT LEAST 12"
LENGTH OF EXIST. BEAM
TOP & BTM. REINF. TO
REMAIN FOR CONNECTION
OF NEW REINF., TYP.
S2.3
SIM.
11' - 7 9/16"± Loading Dock Level
S2.0
S2.1
DETERIORATED EXIST.
REINF. CONC. BEAM
DETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. CMU WALL
EXIST. LOADING DOCK
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DETERIORATED EXIST.
REINF. CONC. CORBEL
EXIST. CONC. SIDEWALK
EXIST. PLAIN CONC. OVER
PLASTIC SHEETING, 1-1/2" SAND,
1-1/2" CONC. TOPPING SLAB
EXIST. REINF.
CONC. SLAB
/2
± 1' - 0 3/4"
2'
S2.3
1SIM.
O.H.
EXIST. PAVING &
CONC. SLAB
EXIST. CONCRETE PAVEMENT
w/ STENCILED PATTERN
11' - 7 9/16"± Loading Dock Level
S2.0
S2.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DEMO PORTION OF SIDEWALK,
CONC. PAVEMENT, SAND, ETC.
AS REQ'D. TO PROVIDE ACCESS
FOR NEW REINF. CONC BEAM
(BELOW)
DEMO EXIST. REINF.
CONC. BEAM. AT
ENDS OF BEAMS AT
LEAST 12" LENGTH
OF EXIST. BEAM
TOP & BTM. REINF.
TO REMAIN FOR
CONNECTION OF
NEW REINF., TYP.
DEMO EXIST. REINF.
CONC. CORBEL
FLUSH TO COL. FACE
S2.3
2SIM.
O.H.
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
S2.0
S2.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
SIM.
NEW REINF.
CONC. BEAMS
NEW PAVING,
STONE FILL, ETC.
11' - 7 9/16"± Loading Dock Level
S2.0
_____________________3
S2.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
3SIM.
O.H.
S2.3
NEW REINF.
CONC. BEAMS
NEW REINF.
CONC. CORBEL
NEW PAVING,
STONE FILL, ETC.
ISSUED FOR PERMIT
MARCH 18, 2025
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S2.2
B2305503.000
RAB
SECTIONS
ALONG LINE 7
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 3/8" = 1'-0"
SECTION - EXISTING
SCALE: 3/8" = 1'-0"
SECTION - DEMOLITION
SCALE: 3/8" = 1'-0"
SECTION - EXISTING
SCALE: 3/8" = 1'-0"
SECTION - DEMOLITION
SECTIONS ALONG LINE VH
SECTIONS ADJACENT TO LINE TH
SCALE: 3/8" = 1'-0"
SECTION - NEW WORK
SCALE: 3/8" = 1'-0"
SECTION - NEW WORK
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
0"
EXIST. (2) #9
EXIST. #3 TIES
(SPACING VARIES)
EXIST. (3) #9
± 1' - 0"± 1' - 0"
/2
EXIST. #5@24" O.C.
(V.I.F.)
EXIST. #5@8" O.C.
EXIST. #4@12" O.C.
EXIST. REINF. SIZES &
QUANTITIES UNKNOWN
IN THESE BEAMS
EXIST. PLAIN CONC. OVER
PLASTIC SHEETING, 1-1/2" SAND,
1-1/2" CONC. TOPPING SLAB
EXIST. CONC. w/
STENCILED PATTERN
EXIST. EXPANSION JOINT
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DEMO PORTION OF
SIDEWALK, CONC. PAVING,
SAND, ETC. AS REQ'D. TO
PROVIDE ACCESS FOR NEW
REINF. CONC. BEAMS (BELOW)
DEMO EXIST. CONC.
BEAM & REINF.
DEMO EXIST.
SLAB, BEAM &
REINF.
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
(2) #9 CONT.
(2) #5 CONT. MID-DEPTH
(4) #9 CONT.
18"12"
#3 TIES @ 9" O.C. FOR 36"
EA. END, @ 12" O.C. FOR
REMAINING SPAN LENGTH
#4@12" O.C. @ MID-
DEPTH OF EXIST. SLAB
w/ 6" EMBED. EA. END
EXPANSION JOINT MATERIAL
(2) #9 CONT.
(2) #5 CONT. MID-DEPTH
(3) #9 CONT.
#3 TIES @ 9" O.C. FOR 36"
EA. END, @ 12" O.C. FOR
REMAINING SPAN LENGTH
#5 BENT BARS @ 8" O.C. w/ 9"
EMBED. INTO EXIST. BEAM
18"
16"
6"
#3@12" O.C. @ MID-
DEPTH OF EXIST. SLAB
w/ 6" EMBED. EA. END
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
S2.3
13"
S2.3
S2.3
EXIST. VERT.
REINF.
EXIST. TIES @
12" O.C.
EXIST. CORBEL
REINF.
EXIST. CORBEL
REINF.
(3) #5 BENT BARS w/ 16"
EMBED. & 25" VERT. LEG
(3) #5 BENT BARS
w/ 16" EMBED. &
STD. 180 HOOK
(6) #5 VERT. BARS
#3 TIES
/2
O.H.
24Dx12W
21Dx18W
Th
S2.3
2' - 0"
S2.3
S2.3
(3) #5 BENT BARS w/ 16"
EMBED. & 25" VERT. LEG
(3) #5 BENT BARS
w/ 16" EMBED. &
STD. 180 HOOK
(6) #5 VERT. BARS
#3 TIES
EXIST. VERT.
REINF.
EXIST. TIES @
12" O.C.
EXIST. CORBEL
REINF.
24Dx12W
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
Th
S2.0
13 O.H.
13"
#3 TIES
(6) #5 VERT. BARS
(3) #5 BENT BARS
w/ 16" EMBED. & 25"
VERT. LEG
EXIST. TIES
EXIST. VERT. BARS
S2.3
Th
S2.0
13 O.H.
EXIST. TIES
EXIST. VERT. BARS
#3 TIES
(6) #5 VERT. BARS
(3) #5 BENT BARS
w/ 16" EMBED. &
STD. 180 HOOK
13"
S2.3
ISSUED FOR PERMIT
MARCH 18, 2025
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S2.3
B2305503.000
RAB
SECTIONS
ALONG LINE 7 &
CORBEL
DETAILS
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 1" = 1'-0"
TYPICAL EXISTING BEAMS
SCALE: 1" = 1'-0"
TYPICAL BEAMS DEMOLITION
SCALE: 1" = 1'-0"
TYPICAL NEW BEAMS
SCALE: 1" = 1'-0"
SECTION - NEW CORBEL
SCALE: 1" = 1'-0"
ELEVATION - NEW CORBEL
DETAIL
SCALE: 1" = 1'-0"
DETAIL
SCALE: 1" = 1'-0"
3-18-2025
ZShapiro Snapshot
ZShapiro Text Box
NEW 1 1/2" CONC SLAB
ZShapiro
NEW PAVING TO MATCH EXIST.
11' - 7 9/16"± Loading Dock Level
Vh Th
S3.2
S3.2
DETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. REINF. CONC. SLAB
EXIST. REINF. CONC. COLUMN
EXIST. REINF. CONC. WALL
EXIST. CONC. SIDEWALK EXIST. PAVING
EXIST. CMU WALL
DETERIORATED EXIST.
REINF. CONC. COLUMN
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
EXIST. CONCRETE DRIVE-THRU
w/ STENCILED PATTERN
EXIST. CONCRETE
SIDEWALK w/
STENCILED PATTERN
S2.3
_____________________SIM.
11' - 7 9/16"± Loading Dock Level
Vh Th
S3.2
S3.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DEMO STENCILED
CONC. PAVING.
DEMO EXIST.
WATERPROOFING
DEMO EXIST. CONC.
BEAMS, SLABS & REINF.
DEMO CONC.
SIDEWALK
DEMO PORTION OF
CONC. SIDEWALK
DEMO PORTION OF
CMU WALL AS REQ'D.
TO REPAIR CONC. COL.
AT LEAST 12" LENGTH
OF EXIST BEAM TOP &
BTM. REINF. TO REMAIN
FOR CONNECTION OF
NEW REINF.
S2.3
_____________________SIM.
AT LEAST 12" LENGTH
OF EXIST BEAM TOP &
BTM. REINF. TO REMAIN
FOR CONNECTION OF
NEW REINF.
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
11' - 7 9/16"± Loading Dock Level
Vh Th
S3.2
S3.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
NEW WATERPROOFING AS
PER BUILDING ENVELOPE
SPECIALIST
NEW CONC. BEAMS,
SLABS & REINF. SEE
SECTIONS.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CMU
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
S2.3
_____________________SIM.
#4 DOWELS, 12" LONG, 6"
EMBED., 24" O.C. AT
EXIST./NEW CMU WALL, TYP.
ISSUED FOR PERMIT
MARCH 18, 2025
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S3.0
B2305503.000
RAB
SECTIONS
ALONG LINE 13
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 3/8" = 1'-0"
SECTION - EXISTING
SCALE: 3/8" = 1'-0"
SECTION - DEMOLITION
SCALE: 3/8" = 1'-0"
VhThS
S3.2
S3.2
DETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. REINF. CONC. SLAB
EXIST. REINF. CONC. COLUMN
EXIST. REINF. CONC. WALL
EXIST. CONC. SIDEWALKEXIST. PAVING
EXIST. CMU WALL
DETERIORATED EXIST.
REINF. CONC. COLUMN
DETERIORATED EXIST.
REINF. CONC. CORBEL
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
EXIST. CONCRETE w/
STENCILED PATTERN
EXIST. CONCRETE
SIDEWALK w/
STENCILED PATTERN
EXIST. CONCRETE
SIDEWALK w/
STENCILED PATTERN
S2.3
_____________________ SIM.
/4
VhThS
S3.2
S3.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DEMO STENCILED
CONC. PAVING.
DEMO EXIST. CONC.
BEAMS, SLABS & REINF.
DEMO CONC.
SIDEWALK
DEMO PORTION OF
CONC. SIDEWALK
DEMO PORTION OF
CMU WALL AS REQ'D.
TO REPAIR CONC. COL.
KEEP SLOPED WALL
AT LEAST 12" LENGTH
OF EXIST BEAM TOP &
BTM. REINF. TO REMAIN
FOR CONNECTION OF
NEW REINF.
DEMO EXIST.
CORBEL FLUSH
TO COL. FACE
AT LEAST 12" LENGTH OF
EXIST BEAM TOP & BTM.
REINF. TO REMAIN FOR
CONNECTION OF NEW REINF.
S2.3
_____________________ SIM.
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
ISSUED FOR PERMIT
MARCH 18, 2025
VhThS
S3.2
_____________________6
S3.2
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
_____________________ SIM.
NEW WATERPROOFING AS
PER BUILDING ENVELOPE
SPECIALIST
NEW CONC. BEAMS,
SLABS & REINF. SEE
SECTIONS.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CONC.
SIDEWALK TO
MATCH EXIST.
NEW CMU
NEW CORBEL
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
CONNECT NEW BEAM REINF.
TO EXIST. REINF. w/
MECHANICAL COUPLERS
S2.3
SIM.
#4 DOWELS, 12" LONG, 6"
EMBED., 24" O.C. AT
EXIST./NEW CMU WALL, TYP.
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S3.1
B2305503.000
RAB
SECTIONS
ALONG LINE 13
155 Temple St New Haven, CT
Omni Hotel Port Cochere Framing Repairs
03-19-2025
DJO
SCALE: 3/8" = 1'-0"
SECTION - EXISTING
SCALE: 3/8" = 1'-0"
SECTION - DEMOLITION
SCALE: 3/8" = 1'-0"
SECTION - NEW WORK
PHOTO LOOKING AT BEAMS ALONG LINE 13
3-18-2025
ZShapiro Text Box
NEW 1 1/2" CONC SLAB
ZShapiro Text Box
NEW COMPACTED STONE FILL
ZShapiro
NEW 6" THICK (MIN.) CONC. SLAB W/ 6x6-W2.9xW2.9 WWF
S3.0
S3.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DETERIORATED EXIST.
REINF. CONC. BEAM
DETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. REINF.
CONC. COLUMN
EXIST. REINF.
CONC. WALL
EXIST. CONC. SIDEWALK
EXIST. WALL
EXPANSION JOINT
EXIST. CONC. SIDEWALK
EXIST. CONCRETE DRIVE-THRU
w/ STENCILED PATTERN
EXIST. REINF.
CONC. SLAB
EXIST. PAVING
& CONC. SLAB
/4
/4
/4
S2.3
SIM.
O.H.
S3.0
S3.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
DEMO PORTION OF SIDEWALK,
CONC. SLAB, ETC. AS REQ'D. TO
PROVIDE ACCESS FOR NEW
REINF. CONC BEAMS (BELOW)
DEMO EXIST. REINF.
CONC. BEAM
S2.3
2SIM.
O.H.
S3.0
S3.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
/2
/4
± 1' - 1"
DETERIORATED EXIST.
REINF. CONC. BEAMDETERIORATED EXIST.
REINF. CONC. BEAM
EXIST. CMU WALLDETERIORATED EXIST.
REINF. CONC. CORBEL
EXIST. CONC. SIDEWALK
EXIST. CONCRETE DRIVE-THRU
w/ STENCILED PATTERN OVER
COMPACTED STONE & WATER
PROOFING MEMBRANE
EXIST. REINF.
CONC. SLAB
EXIST. PAVING &
CONC. SLAB
S2.3
SIM.
13 2
S3.0
S3.1
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S2.3
SIM.
DEMO PORTION OF SIDEWALK,
CONC. SLAB, ETC. AS REQ'D. TO
PROVIDE ACCESS FOR NEW
REINF. CONC BEAM (BELOW)
NOTES REGARDING EXISTING CONDITIONS
ALL EXISTING CONDITIONS ON THE DRAWINGS ARE ASSUMED BASED ON
LIMITED VISUAL INSPECTIONS AND LASER SCANS. THE CONTRACTOR SHALL
CARRY CONTINGENCY IN PRICING FOR DIFFERENCE IN CONDITIONS SHOWN,
INCLUDING BUT NOT LIMITED TO:
a. DIFFERENT FRAMING AND/OR FOUNDATION CONDITIONS
b. HIDDEN DAMAGE OR DETERIORATION IN STRUCTURAL MEMBERS
c. ANY DETAILS NOT FULLY DEVELOPED
S3.0
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S3.1
S2.3
3SIM.
O.H.
S3.0
26' - 8"± T.O. Tunnel ceiling slab
27' - 9"± T.O. Slab 27'-9"
S3.1
S2.3
3 SIM.
S2.3
SIM.
O.H.
ISSUED FOR PERMIT
MARCH 18, 2025
NOTES REGARDING EXISTING UTILITIES
EXISTING UTILITIES ARE NOT SHOWN FOR CLARITY. COORDINATE ALL WORK
WITH UTILITY PROVIDERS AND USERS. PROVIDE SUPPORT AS REQUIRED
FOR ALL UTILITIES. PROVIDE TEMPORARY UTILITIES AS REQUIRED.
WSP USA Buildings Inc.
1223 Mineral Spring Avenue North Providence, RI 02904
(401) 724-1771 www.wsp.com/usa
PROJECT TITLE
SHEET CONTENTS
DRAWING NO.
PROJECT NO.
DRAWN BY
SCALE
DATE
CHECKED BY
As indicated
S3.2
B2305503.000
RAB
SECTIONS
ALONG LINE 13
155 Temple…