The provided file is a comprehensive architectural and engineering construction document set for the Lewis County Rainier Tenant Improvement project, involving the Lewis County Facilities Department located in Chehalis, Washington. The project encompasses improvements to two buildings at 351 NW North Street, with work focused on renovating interior spaces, upgrading exterior facades, and implementing site improvements including sidewalks, parking, and landscaping. The project will be constructed under the jurisdiction of the City of Chehalis Building & Planning Department and follows the 2015 International Building Code and associated Washington State amendments.
The construction documents detail extensive renovations including mechanical, electrical, plumbing, and architectural upgrades for a total building area of approximately 11,840 square feet for Building 1 and 5,029 square feet for Building 2. The project involves a complete interior tenant improvement for Building 1, featuring offices, conference rooms, restrooms, and support spaces, with Building 2 receiving primarily exterior facade upgrades. Key design elements include a variable refrigerant flow (VRF) mechanical system, energy-efficient lighting with daylight harvesting controls, new storefront systems, and comprehensive electrical and telecommunications infrastructure upgrades. The documents indicate a focus on accessibility, energy efficiency, and creating a modern, functional workspace for Lewis County's Community Development department.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A-251
BUILDING SECTION DESIGNATION
SHEET NUMBER WHERE SECTION APPEARS
WALL SECTION DESIGNATION
SHEET NUMBER WHERE SECTION APPEARS
SHEET NUMBER WHERE DETAIL APPEARS
DETAIL NUMBER
INTERIOR ELEVATION NUMBER(S) DESIGNATION
DIRECTION IN ROOM (FILLED ARROW)
SHEET NUMBER WHERE ELEVATION(S) APPEARS
4 2
EXTERIOR ELEVATION DESIGNATION
SHEET NUMBER WHERE ELEVATION APPEARS
LEWIS COUNTY FACILITIES DEPARTMENT
PROJECT LOCATION
AUTHORITY HAVING JURISDICTION
351 NW NORTH STREET
CHEHALIS, WA 98532
DOUG CAREY
CONTACT EMAIL: DOUG.CAREY@LEWISCOUNTY
WA.GOV
PHONE #: (360) 740-1337
COUNTY SITE PARKING
CHEHALIS, WA 98532
DOUG CAREY
CONTACT EMAIL: DOUG.CAREY@LEWISCOUNTY
WA.GOV
PHONE #: (360) 740-1337
CITY OF CHEHALIS BUILDING & PLANNING
DEPARTMENT
1321 S MARKET BLVD
CHEHALIS, WA 98532
CONTACT PERSON: CHELBI BROWNE
CONTACT EMAIL: CBROWNE@CI.CHEHALIS.WA.US
PHONE# (360) 748-0271
ARCHITECT
KMB ARCHITECTS
906 COLUMBIA STREET SW, SUITE 400
OLYMPIA, WASHINGTON 98501
JAMES HILL, RA- PRINCIPAL
360.352.8883
CIVIL
ELECTRICAL
RB ENGINEER
91 SW 13TH STREET
CHEHALIS, WA 98532
CONTACT: ROBERT BALMELLI, PE
EMAIL: ROBERT@RBENGINEERS.COM
PHONE #: (360) 740-8919
HARGIS
1201 THIRD AVENUE, STE 600
SEATTLE, WA 98101
CONTACT: ERIK STEARNS
EMAIL: ERIK.STEARNS@HARGIS.BIZ
PHONE #: (206) 448-3376
LOCATION OF PROJECT
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SAFETY IN THE AREA OF WORK IN
ACCORDANCE WITH ALL SAFETY CODES AND REQUIREMENTS.
2. KEEP ALL AREAS UNDER CONSTRUCTION CLEAN OF DEBRIS CAUSED BY THIS
SCOPE OF WORK. STORE CONSTRUCTION MATERIALS AND EQUIPMENT IN
DESIGNATED AREAS.
3. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING THE SITE CONDITIONS AND
THE PLANS AND TO NOTIFY THE OWNER'S REP / ARCHITECT OF ANY ERRORS OR
OMISSIONS PRIOR TO THE START OF CONSTRUCTION.
4. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT FOR CLARIFICATION WHERE
NECESSARY.
5. CONTRACTOR SHALL OBTAIN ALL PERMITS REQUIRED BY LOCAL AND STATE
GOVERNING AUTHORITIES.
6. ALL WORK SHALL MEET THE STANDARDS AND SPECIFICATIONS OF THE LOCAL AND
STATE GOVERNING AUTHORITIES. REFERENCE CODES, STANDARDS AND
AMENDMENTS SHALL BE THE EDITION MOST RECENTLY ADOPTED OR IN USE IN THE
JURISDICTION.
7. CONTRACTOR SHALL VERIFY ALL DIMENSIONS IN FIELD AND SHALL COORDINATE
INSTALLATION OF ALL MATERIAL AND/OR EQUIPMENT WHOSE DIMENSIONS ARE
FIXED.
8. CONTRACTOR SHALL COORDINATE THE WORK OF ALL TRADES REQUIRED TO
PERFORM THE WORK. WHERE INSTALLATION AND/OR CONNECTION OF EQUIPMENT
IS NOT SPECIFIED AND WHERE SUCH CONNECTION AND/OR INSTALLATION IS
REQUIRED FOR A COMPLETE AND OPERABLE FACILITY, THE CONTRACTOR SHALL
BE HELD RESPONSIBLE FOR SUCH INSTALLATION AND/OR CONNECTION.
9. CONTRACTOR SHALL BEAR ALL EXPENSE OF REPAIR OR REPLACEMENT OF
UTILITIES OR OTHER PROPERTY DAMAGED BY OPERATIONS IN CONJUNCTION WITH
THE EXECUTION OF THIS WORK.
10. NO PORTION OF THE WORK REQUIRING A SHOP DRAWING OR SAMPLE SUBMISSION
SHALL BE COMMENCED UNTIL THE SUBMISSION HAS BEEN APPROVED BY THE
ARCHITECT. ALL SUCH PORTIONS OF THE WORK SHALL BE IN ACCORDANCE WITH
APPROVED SHOP DRAWINGS AND SAMPLE.
11. ALL SUBCONTRACTORS ARE RESPONSIBLE FOR REVIEWING ENTIRE SET OF
DRAWINGS AND BRINGING ANY DISCREPANCIES TO CONTRACTOR'S AND
ARCHITECT'S NOTICE DURING BIDDING.
THIS PROJECT INCORPORATES SITE IMPROVEMENTS TO THE
RAINIER BLOCK BUILDINGS ADJACENT SITE AND DEVELOPMENT OF
IMPROVEMENTS TO SIDEWALKS, SITE PARKING AND LANDSCAPING.
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
/1
/2
:5
9:
P M
01-13-2023
CONFORMED SET
GI001
COVER SHEET
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
LEWIS COUNTY RAINIER TI IMPROVEMENTS
LEWIS COUNTY FACILITIES DEPARTMENT
351 NW NORTH STREET, CHEHALIS, WA 98532
J2037C
SCALE: N. T. S.
AREA MAP
SCALE: 1" = 400'-0"
VICINITY MAP
SHEET INDEXDESIGN TEAM - SHEET
DRAWING SYMBOLS
PROJECT INFORMATION
LOCATION OF PROJECT
PROJECT DESCRIPTION GENERAL NOTES
GENERAL
GI001 COVER SHEET
GI002 COVER SHEET
GI201 GENERAL CODE INFORMATION
GI301 AIR BARRIER
MECHANICAL
M-001 MECHANICAL LEGEND & NOTES
M-002 MECHANICAL SCHEDULES
M-003 MECHANICAL SCHEDULES
M-101 FLOOR PLAN BLDG 1- DEMOLITION
M-201 FOUNDATION PLAN BLDG 1- PLUMBING
M-301 FLOOR PLAN BLDG 1 - PLUMBING
M-302 PLUMBING DETAILS
M-401 FLOOR PLAN BLDG 1 - HVAC
M-402 HVAC DETAILS
M-403 HVAC DETAILS
M-404 HVAC DETAILS
ARCHITECTURAL
A-101 REFERENCE FLOOR PLAN
A-121 ENLARGED FLOOR PLAN - BLDG 1
A-121D DIMENSION PLAN - BLDG 1
A-122 ENLARGED FLOOR PLAN - BLDG 2
A-122D DIMENSION PLAN - BLDG 2
A-151 LEVEL 1- REFERENCE REFLECTED CEILING PLAN
A-152 LEVEL 1 - ENLARGED REFLECTED CEILING PLAN - BLDG 1
A-153 LEVEL 1 - ENLARGED REFLECTED CEILING PLAN - BLDG 2
A-161 REFERENCE ROOF PLAN
A-162 ENLARGED ROOF PLAN - BLDG 1
A-163 ENLARGED ROOF PLAN - BLDG 2
A-201 EXTERIOR ELEVATIONS
A-202 EXTERIOR ELEVATIONS
A-250 ENLARGED FLOOR PLANS & INTERIOR ELEVATIONS
A-251 ENLARGED FLOOR PLANS & INTERIOR ELEVATIONS
A-252 ENLARGED FLOOR PLANS & INTERIOR ELEVATIONS
A-254 ENLARGED FLOOR PLANS & INTERIOR ELEVATIONS
A-255 ENLARGED FLOOR PLANS & INTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-302 BUILDING SECTIONS
A-311 WALL SECTIONS
A-501 EXTERIOR WALL TYPES
A-502 INTERIOR WALL TYPES
A-511 FOUNDATION DETAILS
A-521 EXTERIOR DETAILS
A-522 EXTERIOR DETAILS
A-541 DOOR & WINDOW DETAILS
A-542 DOOR & WINDOW DETAILS
A-550 STOREFRONT DETAILS
A-551 STOREFRONT DETAILS
A-552 STOREFRONT DETAILS
A-553 STOREFRONT DETAILS
A-561 CEILING DETAILS
A-571 ROOF DETAILS
A-572 ROOF DETAILS
A-573 ROOF DETAILS
A-574 ROOF DETAILS
A-575 ROOF DETAILS
A-576 ROOF DETAILS
A-577 ROOF DETAILS
A-581 FRONT RECEPTION DESK & CASEWORK DETAILS
A-582 FRONT RECEPTION DESK & CASEWORK DETAILS
A-583 CASEWORK DETAILS
A-584 CASEWORK DETAILS
A-585 INTERIOR DETAILS
A-601 DOOR SCHEDULE
A-611 EXTERIOR OPENINGS- STOREFRONTS
A-612 EXTERIOR OPENINGS - STOREFRONTS
A-621 FINISH PLAN AND SCHEDULE
ELECTRICAL
E0.01 ELECTRICAL LEGEND AND DRAWING INDEX
E0.02 ELECTRICAL NOTES AND ABBREVIATIONS
E0.03 TELECOM AND LOW VOLTAGE SCHEDULES
E0.04 ELECTRICAL SCHEDULES
E0.05 ELECTRICAL SCHEDULES
E0.06 ELECTRICAL SCHEDULES
ED1.01 ELECTRICAL DEMOLITION SITE PLAN
ED3.01 POWER DEMOLITION FLOOR PLAN - BLDG 1
ED6.01 TELECOM DEMOLITION FLOOR PLAN - BLDG 1
ED7.01 ELECTRICAL DEMOLITION ELEVATIONS
ED9.01 ELECTRICAL ONE-LINE DIAGRAM - DEMOLITION
E1.01 ELECTRICAL SITE PLAN
E1.01a SITE PLAN - LIGHTING CONTROL ZONE PLAN
E2.00 LIGHTING CONTROL ZONE NETWORK MAP FLOOR PLAN
E2.01a LIGHTING CONTROL ZONE FLOOR PLAN - BLDG 1
E2.02 LIGHTING FLOOR PLAN - BLDG 2
E3.01 POWER FLOOR PLAN - BLDG 1
E3.02 POWER FLOOR PLAN - BLDG 2
E4.01 MECHANICAL POWER FLOOR PLAN - BLDG 1
E5.01 FIRE ALARM FLOOR PLAN - BLDG 1
E6.01 TELECOM FLOOR PLAN - BLDG 1
E6.02 TELECOM FLOOR PLAN - BLDG 2
E7.01 ELECTRICAL ENLARGED PLANS AND DETAILS
E7.02 ELECTRICAL DETAILS
E7.03 ELECTRICAL DETAILS
E7.04 ELECTRICAL DETAILS
E8.01 ENLARGED TELECOM DETAILS
E8.02 TELECOM DETAILS
E8.03 TELECOM DETAILS
E8.04 TELECOM DETAILS
E8.05 TELECOM DETAILS
E8.06 TELECOM DETAILS
E9.01 ELECTRICAL ONE-LINE DIAGRAM
E10.01 PANEL SCHEDULES
E10.02 PANEL SCHEDULES
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
/1
/2
:5
9:
P M
01-13-2023
CONFORMED SET
GI002
COVER SHEET
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
LEWIS COUNTY RAINIER TI IMPROVEMENTS
LEWIS COUNTY FACILITIES DEPARTMENT
351 NW NORTH STREET, CHEHALIS, WA 98532
J2037C
DRAWING ABBREVIATIONS
& AND
∠ ANGLE
@ AT
Ø DIAMETER
' FOOT (FEET)
" INCH
d PENNY (NAILS)
# POUNDS
⅊ PLATE or PROPERTY LINE
AB ANCHOR BOLT
ABV ABOVE
ACT ACOUSTIC CEILING TILE
AC ARCHITECTURAL CONCRETE
A/C ASPHALTIC CONCRETE
ACM ALUMINUM COMPOSITE METAL (PANELS)
AD AREA DRAIN
ADD ADDENDUM
ADJ ADJUSTABLE
AF ACCESS FLOOR
AFF ABOVE FINISH FLOOR
AFP ACOUSTICAL FIBERGLASS PANEL
AFG ABOVE FINISH GRADE
AGG AGGREGATE
AHU AIR HANDLING UNIT
ALT ALTERNATE
AMT AMOUNT
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ASSY ASSEMBLY
AUTO AUTOMATIC
BC BOTTOM OF CURB
BD BOARD
BFF BELOW FINISH FLOOR
INT INTERIOR
INV INVERT
JB JUNCTION BOX
JST JOIST
JT JOINT
L LENGTH
LAM LAMINATE
LAV LAVATORY
LB POUND OR LAG BOLT
LF LINEAR FOOT OR FEET
LH LEFT HAND
LIN LINOLEUM
LIN LINOLEUM
LL LIVE LOAD
LT LIGHT
LVR LOUVER
LYRS LAYERS
M METRIC/METER
MACH MACHINE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MI MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MRG MOISTURE RESISTANT GYPSUM BOARD
MTD MOUNTED
UNFIN UNFINISHED
UON UNLESS OTHERWISE NOTED
V VOLTAGE
V VALVE
VB VAPOR BARRIER
VENT VENTILATION
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VTR VENT TO ROOF
W WEST
W/ WITH
WD WOOD
WDN WINDOW
WLD WELD(ED)
WOM WALK OFF MAT
W/O WITHOUT
WP WATERPROOFING
WSCT WAINSCOT
WT WEIGHT
WTR WATER
XFRMR TRANSFORMER
YD YARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM OR BENCH MARK
BO BOTTOM OF
BOD BOTTOM OF DEK
BOR BOTTOM OF REVEAL
BOT BOTTOM
BRG BEARING
BR BRICK
BV BRICK VANEER
CAB CABINETRY
CB CATCH BASIN
CEM CEMENT
CG CORNER GUARD
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
COV PL COVER PLATE
CPT CARPET
CT CERAMIC TILE
CTR CENTER
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DN DOWN
DR DOOR
DRN DRAIN
DS DOWNSPOUT
DT DOUBLE TREE
DWG DRAWING
E EAST
(E) EXISTING
EB EXPANSION BOLT
EJ EXPANSION JOINT
ELEC ELECTRICAL
ELEV ELEVATION
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EP EPOXY PAINT
ENAM ENAMEL
EQ EQUAL
EQUIP EQUIPMENT
EXH EXHAUST
EXT EXTERIOR
FA FIRE ALARM
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FIN FINISH
FLR FLOOR
FLUOR FLUORESCENT
FO FACE OF
FOF FACE OF FINISH
FOH FRONT OF HOUSE
FOC FACE OF CONCRETE
FOM FACE OF MASONARY
FOS FACE OF STUDS
FPRF FIREPROOFING
FR FIRE RESITIVE
FT FEET or FOOT
FTG FOOTING
FV FEILD VERIFY
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GL GLASS
GLB GLULAM BEAM
GRD GRADE
GND GROUND
GWB GYPSUM WALL BOARD
HB HOSE BIB
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HNDRL HANDRAIL
HORIZ HORIZONTAL
HR HOUR
HSTL HOLLOW STEEL
HT HEIGHT
HTG HEATING
HTR HEATER
HV HOSE VALVE
HVAC HEATING, VENTILATING & AIR CONDITIONING
ID INSIDE DIAMETER / DIMENSION
IN INCH
INCL INCLUDED
INFO INFORMATION
INSUL INSULATION
MTL METAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NS NON-SHRINK
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER / DIMENSION
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OPNG OPENING
OPP OPPOSITE
OPT OPTIONAL
ORIG ORIGINAL
OVHD OVERHEAD
OV OVERFLOW DRAIN
PAV PAVERS
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PERF PERFORATED
P/L PROPERTY LINE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PNL PANEL
PRELIM PRELIMINARY
PSI POUNDS PER SQUARE INCH
P PAINT
PT PRESSURE TREATED
PTD PAINTED
QT QUARRY TILE
QTR QUARTER
R RISER
R- THERMAL RESISTANCE
RA RETURN AIR
RAD RADIUS
RB RUBBER BASE
RD ROOF DRAIN
REC RECESSED
RE: REFERENCE
REF REFRIGERATOR
REINF REINFORCE(D)(MENT)(ING)
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RFL REFLECTED
RM ROOM
RND ROUND
RO ROUGH OPENING
RQMT REQUIREMENT(S)
RV ROOF VENT
R/W RIGHT OF WAY
RWF RESILIENT WOOD FLOOR
S SOUTH
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SHTHG SHEATHING
SHT SHEET
SIM SIMILAR
SJ SEISMIC JOINT
SLR SEALER
SOG SLAB ON GRADE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
ST STREET
STN STAIN(ED)
STAG STAGGERED
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SURF SURFACE
SUSP SUSPENDED
SWS SEE WALL SECTIONS
SYM SYMMETRICAL
SYS SYSTEM
T TILE
THR THREAD
TEMP TEMPORARY
TEMP GL TEMPERED GLASS
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
THK THICK
THRSH THRESHOLD
THRU THROUGH
T/M TO MATCH
T/M TO MATCH
TO TOP OF
TOC TOP OF CONCRETE OR CURB
TOS TOP OF STEEL
TOT TOTAL
TYP TYPICAL
Project Name: Lewis County Community Development Tenant Improvement
Address: 351 NW NORTH STREET, CHEHALIS, WA 98532
Jurisdiction: City of Chehalis Department of Building and Planning
Codes Referenced:
International Building Code (IBC): 2015 Edition International Mechanical Code (IMC): 2015 Edition Uniform Plumbing Code (UPC): 2015 Edition International Fire Code (UFC): 2015 Edition National Electric Code (NFPA 70) 2017 Edition; RCW 19.28 Accessible & Usable Buildings &
Facilities (ICC/ANSI A117.1) 2009 Edition Washington State Building Code (IBC): WAC 51-50 Washington State Mechanical Code (IMC): WAC 51-52 Washington State Fire Code (IFC): WAC 51-54A Washington State Energy Code (WSEC): WAC 51-11C Washington State Department of Health WAC 246-322
All Amendments, Supplements, Modifications, Exclusions, Exceptions, And Additions To The Codes Listed Above As Adopted By The Washington State Building Code Council RCW 19.27 And WAC Title 51.
Local Amendments To The Above Listed Codes And Local Ordinances As Adopted By The Authority Having Jurisdiction: City of Chehalis.
City of Chehalis Design Requirements
1. Design Wind Speed: 85 mph basic (Vasd) + 110 mph (Vult).
2. Wind Exposure: “B”
3. Seismic Design Category: D1
4. Ground and Roof Snow Load: 25 psf
Deferred Submittals:
Type I Hood Shop Drawings Type II Hood Shop Drawings
Fire Sprinklers:
Building 1: None Required / None Provided Building 2: None Required / None Provided
Occupancies (Chapters 3 and 4):
Building 1 - B (Business) Occupancy Building 2 - B (Business) Occupancy (NO WORK ON INTERIOR)
Occupancy Separation Requirements (Chapter 3 and Section 508):
Building 1: None Building 2: None (NO WORK ON INTERIOR)
Special Occupancy Requirements (Chapter 4):
N/A
Types Of Construction (Chapters 5 and 6):
Building 1: III-B Building 2: IV (NO WORK ON INTERIOR)
Incidental Uses (Chapter 5 and Section 509):
Building 1: N/A Building 2: N/A (NO WORK ON INTERIOR)
Fire Walls / Separate Code Buildings / Area Separations For Allowable Area (Chapters 5 and 7):
Number of Stories Allowed (Chapter 5 and Table 504.4):
For _B Occupancy in Const’n Type _III-B (NS) = _3_; Actual = _1_(Existing)
For B Occupancy in Const’n Type _IV (NS) = _5_; Actual = _1_(Existing)
Building Height (Chapter 5, Table 504.3):
For B Occupancy in Const’n Type _III-B_(NS) = 55 feet; Actual = 19 feet
For B Occupancy in Const’n Type _IV_(NS) = 65 feet; Actual = 26 feet (Existing)
Actual Area: Building 1: 11,391 SF (IBC Floor Area - Not including exterior wall thickness) 11,840 SF (Including Exterior Wall Thickness)
Building 2: 4,742 SF (IBC Floor Area - Not including exterior wall thickness) 5,029 SF (Including Exterior Wall Thickness)
(EXISTING AREA, NO INTERIOR WORK)
Allowable Area: Building 1 Single Occupancy Allowable Area:
For B Occupancy in Construction Type _III-B (NS): 19,000 SF
Building 2: (NO INTERIOR WORK) For B Occupancy in Construction Type _IV (NS): 36,000 SF (EXISTING AREA, NO INTERIOR WORK)
Actual Area of Building 1 = 11,840 SF, therefore OK.
Actual Area of Building 2 = 5,029, (EXISTING AREA, NO INTERIOR WORK)
Fire Resistive Requirements (Chapters 6 and 7, Table 601):
Rating (hours):
Building Element Bldg 1 Bldg. 2 Structural Frame (Table 601): 1 X Floors & Floor Ceilings (Table 601): X X Roofs & Roof Ceilings (Table 601): X X Exterior Bearing Walls (Table 601): 1 X Interior Bearing Walls (Table 601): N/A N/A Exterior Non-Bearing Walls (Table 602): 0 0 Interior Non-Bearing Walls (Table 601): 0 0 Shafts (Section 713): N/A N/A Exit Access Stairways and Ramps (Section 1019): N/A N/A Corridors (Section 1020): N/A N/A Fire Walls (Section 706): N/A N/A Fire Barriers (Section 707): N/A N/A Fire Partitions (Section 708): N/A N/A Smoke Barriers (Section 709): N/A N/A Horizontal Assemblies (Section 711): N/A N/A Vertical Openings (Section 712): Sealed with an approved material Shaft Enclosures (Section 713): N/A N/A
Exit Requirements:
Code Occupant Load Calculation For Exiting Design (1004):
Maximum Floor Area Allowance Per Occupant: 100 (B Business Area Function @ 1/100) Total Design Occupant Load: 160 (Maximum Occupant Load)
Maximum Exit Travel Distance ( 123'
Exit Passageways (Section 1023): None
Horizontal Exits (Section 1025): None
172 SF
312 SF
192 SF255 SF
96 SFTOILET
96 SF
96 SF
TOILET
TOILET
TOILET
68 SF
76 SF
734 SF
107 SF
597 SF
200 SF
832 SF
CONFERENCE ROOM
NOXIOUS WEEDS OFFICE
OFFICEHALL
OPEN OFFICE
TLTHALL
VEST.
TENANT
IMPROVEMENT
UNDER
SEPARATE
PERMIT
FACADE
UPGRADES
ONLY THIS
BUILDING
100 3
DIRECTOR'S
OFFICE
OFFICE
MANAGER
100 3
CONFERENCE
15 22 100 2
PLAN
REVIEW
15 40
LOBBY/
WAITING
15 37
CONFERENCE
ROOM
EXECUTIVE
OFFICE
100 2
RESTROOM
101-A
OPEN
WORKSPACE
100 40
BREAKROOM
15 17
SUPPLIES100 3
300 1
WORKROOM
MUD
ROOM
STORAGE
100 3
100 1
LACTATION
300 1
CUSTODIAN
100 2
OFFICE
100 2
OFFICE
100 2
OFFICE
FEC
FEC
FEC
FEC
FEC
17 OCCUPANTS
WIDTH REQUIRED = 4.25"
WIDTH PROVIDED = 32"
25 OCCUPANTS
WIDTH REQUIRED = 6.25"
WIDTH PROVIDED = 32"
63 OCCUPANTS
WIDTH REQUIRED = 15.75"
WIDTH PROVIDED = 64"
63 OCCUPANTS
WIDTH REQUIRED = 15.75"
WIDTH PROVIDED = 64"
126 OCCUPANTS
WIDTH REQUIRED = 31"
WIDTH PROVIDED = 64"
25 OCCUPANTS
WIDTH REQUIRED = 6.25"
WIDTH PROVIDED = 32"
4 OCCUPANTS
WIDTH REQUIRED = .8"
WIDTH PROVIDED = 32"
18 OCCUPANTS
WIDTH REQUIRED = 4.5"
WIDTH PROVIDED = 64"
TOILET
FEC
FEC
50 4
300 1
ELEC/MECH.
1 OCCUPANTS
WIDTH REQUIRED = .2"
WIDTH PROVIDED = 32"
OFFICE
MICRO
ROOM
PREP
ROOM
100 2
6 OCCUPANTS
WIDTH REQUIRED = 1.5"
WIDTH PROVIDED = 32"
300 1
100 1
602 SF
123' EXIT T.D.
E X
IT
T
.D
71' EXIT T.D.
0'
E X
IT
T
.D
111133
76' EXIT T.D.
E X
IT
T
.D
73' EXIT T.D.
E X
IT
T
.D
78' EXIT T.D.
3'
E X
IT
T
.D
76' EXIT T.D.
TO OPEN'G
6'-11"
T O
O P
E N
IN
G
'-7
DENOTES MAXIMUM TRAVEL DISTANCE
EXIT
XXX
XXX XXX
SQUARE FOOTAGE
OCCUPANT FACTOR / OCCUPANT LOAD
1 - HOUR FIRE WALL (EXISTING)
UL U906 (2-hr Rated)
MTD: 123 LF
FEC: RECESSED FIRE EXTINGUISHER
CABINET
FE: WALL MOUNTED FIRE
EXTINGUISHER
CLASS A TYPE FE UNLESS NOTED
OTHERWISE
CODE REQUIRED SIGNAGE, AS
NOTED ON PLAN
1 - HOUR FIRE RATED STEEL COLUMN
(EXISTING) UL 263, NFPA 251, ASTM
E-119-106 (1-hr Rated)- APPLY
INTUMESCENT PAINT PER MANUF.
RECOMMENDATIONS
1 - HOUR FIRE RATED WOOD COLUMN
(EXISTING) UL X528 (1-hr Rated)- 1 1/2"
STEEL STUDS AROUND EXISTING
WOOD COLUMN WITH (2) LAYERS 5/8"
TYPE 'X' GWB
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/1
/2
:5
9:
P M
01-13-2023
CONFORMED SET
GI201
GENERAL CODE
INFORMATION
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3/32" = 1'-0"1
LEVEL ONE- CODE & EXITING PLAN
CODE FLOOR PLAN LEGEND
FD
Range
FD
FD
FD
FD
FD
FD
FD
FD
FD
1. SEAL ALL HOLES AND GAPS IN AIR BARRIER SYSTEM TO PROVIDE AN AIRTIGHT
INSTALLATION.
2. THE CONCRETE SLAB, SLAB ON GRADE IS ASSUMED TO PROVIDE ADEQUATE AIR
BARRIER PERFORMANCE. (SEAL ALL PENETRATIONS)
3. REFER TO DOOR, WINDOW AND LOUVER DETAILS FOR ADDITIONAL AIR BARRIER
SYSTEM AND WEATHER RESISTANT BARRIER DETAILS.
4. ENSURE THAT ALL AIR BARRIER SYSTEMS ARE SEALED TIGHT TO EACH OTHER AT
ALL TRANSITIONS, FENESTRATION OPENINGS AND JOINTS.
INSULATION VALUES:
THE FOLLOWING MINIMUM INSULATION VALUES SHALL BE:
1. EXTERIOR WALLS: R-21 @ 6" STEEL STUD WALLS
R-25 @ 8" STEEL STUD WALLS
R-10 CONTINOUS INSULATION @ EXTERIOR
2. EXTERIOR FURRING WALL: 2" RIGID INSULATION (R-10 MIN. AGAINST EXISTING
MASONRY WALL)
R-13 @ 3 1/2" STEEL STUD WALLS
3. EXISTING ROOF: R-49 @ RIGID INSULATION (ALL SEAMS TAPED) -
BELOW EXISTING ROOF DECK
4. NEW ROOF: R-38 @ CONT. RIGID INSULATION ABOVE DECK
5. SLAB PERIMETER: R-10 @ HEATED SLABS & FOR 24 INCHES BEYOND
EXTENTS OF CONTINUOUS AIR BARRIER SYSTEM
BUILDING 1
TOTAL VERTICAL FENESTRATION 1,330 SF
GROSS EXTERIOR WALL AREA (ABOVE GRADE) 5,914 SF
PERCENT VERTICAL FENESTRATION 23%
BUILDING 2
TOTAL VERTICAL FENESTRATION 1,650 SF
GROSS EXTERIOR WALL AREA (ABOVE GRADE) 6,412 SF
PERCENT VERTICAL FENESTRATION 26%
STOREFRONT
451UT CENTER GLAZED 4 1/2" X 2" FRAME
LOW E AND ARGON FILLED - SOLARBAN 60
GLASS U FACTOR = .24 OVERALL U FACTOR = .33
GLASS SHGC - .40 OVERALL SHGC = .36
GLASS VT = .72 OVERALL VT = .63
STOREFRONT DOORS W/ SOLARBAN 60
500T WIDE STILE (BETTER FOR ELECTRONIC HARDWARE)
500T WIDE STILE - LOW EWITH ARGON
GLASS U FACTOR= .24 OVERALL U FACTOR = .53
GLASS SHGC = .40 OVERALL SHGC = .21
GLASS VT = .72 OVERAL VT = .27
VT = VISUAL TRANSMITTANCE
UT = ULTRATHERMAL
C402.5.1.1 AIR BARRIER CONSTRUCTION. THE CONTINUOUS AIR BARRIER SHALL BE
CONSTRUCTED TO COMPLY WITH THE FOLLOWING:
1. THE AIR BARRIER SHALL BE CONTINUOUS FOR ALL ASSEMBLIES THAT ARE THE
THERMAL ENVELOPE OF THE BUILDING AND ACROSS THE JOINTS AND
ASSEMBLIES.
2. AIR BARRIER JOINTS AND SEAMS SHALL BE SEALED, INCLUDING SEALING
TRANSITIONS IN PLACES AND CHANGES IN MATERIALS. THE JOINTS AND SEALS
SHALL BE SECURELY INSTALLED IN OR ON THE JOINT FOR ITS ENTIRE LENGTH
SO AS NOT TO DISLODGE, LOOSEN OR OTHERWISE IMPAIR ITS ABILITY TO RESIST
POSITIVE AND NEGATIVE PRESSURE FROM WIND, STACK EFFECT AND
MECHANICAL VENTILATION.
3. PENETRATIONS OF THE AIR BARRIER SHALL BE CAULKED, GASKETED OR
OTHERWISE SEALED IN A MANNER COMPATIBLE WITH THE CONSTRUCTION
MATERIALS AND LOCATION. JOINTS AND SEALS ASSOCIATED WITH
PENETRATIONS SHALL BE SEALED IN THE SAME MANNER OR TAPED OR COVERED
WITH MOISTURE VAPOR-PERMEABLE WRAPPING MATERIAL. SEALING MATERIALS
SHALL BE APPROPRIATE TO THE CONSTRUCTION MATERIALS BEING SEALED AND
SHALL BE SECURELY INSTALLED AROUND THE PENETRATIONS SO AS NOT TO
DISLODGE, LOOSEN OR OTHERWISE IMPAIR THE PENETRATIONS’ ABILITY TO
RESIST POSITIVE AND NEGATIVE PRESSURE FROM WIND, STACK EFFECT, AND
MECHANICAL VENTILATION. SEALING OF CONCEALED FIRE SPRINKLERS, WHERE
REQUIRED, SHALL BE IN A MANNER THAT IS RECOMMENDED BY THE
MANUFACTURER. CAULKING OR OTHER ADHESIVE SEALANTS SHALL NOT BE USED
TO FILL VOIDS BETWEEN FIRE SPRINKLER COVER PLATES AND WALLS OR
CEILINGS.
4. RECESSED LIGHTING FIXTURES SHALL COMPLY WITH SECTION C402.5.8. WHERE
SIMILAR OBJECTS ARE INSTALLED WHICH PENETRATE THE AIR BARRIER,
PROVISIONS SHALL BE MADE TO MAINTAIN THE INTEGRITY OF THE AIR BARRIER.
5. CONSTRUCTION DOCUMENTS SHALL CONTAIN A DIAGRAM SHOWING THE
BUILDING’S PRESSURE BOUNDARY IN PLAN(S) AND SECTION(S) AND A
CALCULATION OF THE AREA OF THE PRESSURE BOUNDARY TO BE CONSIDERED
IN THE TEST.
LEV. 1-BLDG 1
0' - 0"
22 SF
22 SF
22 SF
22 SF
35 SF
30 SF
34 SF
187 SF
184 SF
74 SF
58 SF
140 SF
60 SF
140 SF
60 SF
152 SF
60 SF
141 SF
77 SF
217 SF
BLDG 1:
GROSS SF = 1,634 SF
FENESTRATIONS= 632 SF
PERCENTAGE= 38%
BLDG 2:
GROSS SF = 2,561 SF
FENESTRATIONS= 1,105 SF
PERCENTAGE= 43%
LEV. 1-BLDG 5
12' - 0 15/32"
120 SF
52 SF
46 SF31 SF38 SF
34 SF97 SF
11 SF
BLDG 1:
GROSS SF= 1,805 SF
FENESTRATION = 429 SF
PERCENTAGE= 23%
BLDG 2:
GROSS SF = 525 SF
PERCENTAGE= 0%
LEV. 1-BLDG 1
0' - 0"
42 SF
30 SF
10 SF 10 SF
42 SF
94 SF
42 SF 42 SF
39 SF
42 SF 13 SF
45 SF
31 SF
19 SF
BLDG 2:
GROSS SF= 2,048 SF
FENESTRATION = 471 SF
PERCENTAGE= 22%
BLDG 1:
GROSS SF= 1,466 SF
FENESTRATION = 204 SF
PERCENTAGE= 13%
33 SF
31 SF
20 SF
31 SF
19 SF
LEV. 1-BLDG 5
12' - 0 15/32"
LEV. 1-BLDG 1
0' - 0"
BLDG 1:
GROSS SF= 1,009 SF
FENESTRATIONS= 65 SF
PERCENTAGE= 10%
BLDG 2:
GROSS SF= 1,278 SF
FENESTRATIONS= 74 SF
PERCENTAGE= 5%
52 SF
22 SF
47 SF
13 SF 13 SF
LEV. 1-BLDG 5
12' - 0 15/32"
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/1
/2
:5
9:
P M
01-13-2023
CONFORMED SET
GI301
AIR BARRIER
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
AIR BARRIER FLOOR PLAN NOTES
AIR BARRIER FLOOR PLAN LEGEND
FENESTRATION CALCULATION
WSEC - AIR BARRIER CODE
1" = 20'-0"A
REFERENCE FLOOR PLAN - AIR BARRIER
1/16" = 1'-0"1
EXTERIOR ELEVATION - EAST - OPENING CALCULATIONS
1/16" = 1'-0"2
EXTERIOR ELEVATION - SOUTH- OPEN CALCULATIONS
1/16" = 1'-0"4
EXTERIOR ELEVATION - WEST - OPEN CALCULATIONS
1/16" = 1'-0"3
EXTERIOR ELEVATION - NORTH - OPENING CALCULATIONS
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
1 2 4 5
6 107 8 9
A
B
C
D
E
200'-11"
27'-6" 16'-9" 18'-7" 18'-7" 19'-0" 25'-0" 25'-0" 25'-0" 25'-6"
8'
-9
'-1
'-1
'-4
'-4
A-301
A-3012
A-301
A-301
A-301
A-301
A-301
A-301
VESTIBULE
PLAN REVIEW
CONFERENCE
OFFICE MANAGER
DIRECTOR'S OFFICE
OFFICE
TOILET
OFFICE
OFFICE
TOILET
TOILET
TOILET
OPEN WORK SPACE
CUSTODIAL
LACTATION
STORAGE
SHOWER
118-A
SUPPLIES
BREAK ROOM
CONFERENCE ROOM
MUD ROOM
MECH/ ELEC
WORKROOM
TOILET
NOXIOUS WEEDS OFFICE
OFFICEHALL
OPEN OFFICE
TLTHALL
TENANT
IMPROVEMENT
UNDER SEPARATE
PERMIT
LOBBY
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-101
REFERENCE FLOOR PLAN
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3/32" = 1'-0"1
REFERENCE FLOOR PLAN
1. ALL DIMENSIONS TO FACE OF CMU, FACE OF STUD OR GRIDLINES, U.N.O.
2. DOOR FRAMES TO BE 3" OFF ADJACENT PERPENDICULAR WALL, U.N.O.
FLOOR PLAN GENERAL NOTES
FD
FD
FD
FD
FD
FD
FD
FD
FD
6 107 8 9
A
B
C
D
E
A-202
EXTERIOR ELEVATION -
WEST
A-201
S im
E X
T E
R
IO
R E
L E
V A
T
IO
N
N O
R T
H
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
A-201
Sim
EXTERIOR ELEVATION -
EAST
A-202
E X
T E
R
IO
R E
L E
V A
T
IO
N
S O
U T
H
A-301
A-301
A-301
A-301
PLAN REVIEW
CONFERENCE
OFFICE MANAGER
DIRECTOR'S OFFICE
OFFICE
TOILET
OFFICE
TOILET
TOILET
TOILET
OFFICE
CUSTODIAL
LACTATION
SUPPLIES
BREAK ROOM
EXECUTIVE OFFICE
CONFERENCE ROOM
VESTIBULE
A-301
A-301
SFE33
SFE1SFE3SFE4SFE5SFE6SFE7SFE7SFE7SFE7
SFE28
SFE29
SFE32
C
100A
B
A
121B 118B113B
BS
F
E
HALL
00A
A-252
A
A-250
A
SFE34
A-250
B
A-251
A
A-251
A-252
SFE36
SFE37
SFE38
12" DIA. COLUMN
COVER, TYPICAL AT ALL
EXPOSED COLUMNS
A-302
A-302
MUD ROOM
STORAGE
MECH/ ELEC
117B
SFE41SFE41
SFE
SFE
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
DS
DS DS
DS
DS
DS
DSDSDS
DS
DS
DS
DS
TOILET
SHOWER
118-A
SFE27
LOBBY
SFE27
A-521
HIGH
A-550
LOW
A-521
HIGH
A-550
Sim
LOW
A-521
5 HIGH
A-521
LOW
A-522
A-585
TYP.
A-252
B
A-254
A-254
A-254
12A-255
SFE42
SFE43
A-255 6
A-255
A-255
A-255
A-255
A-255
A-550
A-511
A-581
A
A-581
A-581
SFE8
DS
WORKROOM
C
SFE32
SFE32
OFFICE
OFFICE
121A
A
A
123A
123B
A
A
A
A
A
128A
OPEN WORK SPACE
A
A
A
102B103A103B104A104A105A105A 104A105A
A
A
A
A
A
A
A
113A 117A 118A
A
A A
A
A
WRAP EXIST. COLUMN
AT GRADE BEAM IN 3
1//2" FURRING WALL &
ENCAPSULATE BASE
PLATE
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
8 RFI-016
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-121
ENLARGED FLOOR PLAN-
BLDG 1
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/8" = 1'-0"1
ENLARGED FLOOR PLAN - BLDG 1
1. ALL DIMENSIONS TO FACE OF CMU, FACE OF STUD OR GRIDLINES, U.N.O.
6 107 8 9
A
B
C
D
E
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
PLAN REVIEW
CONFERENCE
OFFICE MANAGER
DIRECTOR'S OFFICE
OFFICE
TOILET
OFFICE
TOILET
TOILET
TOILET
OFFICE
OPEN WORK SPACE
CUSTODIAL
LACTATION
STORAGE
SHOWER
118-A
SUPPLIES
BREAK ROOM
EXECUTIVE OFFICE
CONFERENCE ROOM
VESTIBULE
25'-0" 25'-0" 25'-0" 25'-6"
100'-6"
'-0
/2
'-0
/2
'-4
'-4
8'
-9
8'-8"
4' -1
1" 6'
-3
'-8
3' -8
'-0
4' -4
4'
-6
1' -1
1" 3'
-0
9' -0
'-5
15'-11"
9'-0" 6'-0" 3'-6" 1'-4"2'-3"4'-7" 17'-0"3'-4" 1'-6" 5'-4" 2'-10" 4'-6" 4'-7" 1'-9"3'-4" 3'-4" 3'-4" 3'-3" 3'-4" 1'-6"
7' -6
3' -3
'-4
4' -1
1" 6'
-0
4' -4
8' -8
/8
8'
-0
8' -0
8'
-0
8' -0
8'
-0
A-302
A-302
A1
A1
A2
A1
A2
A1
A1
A1
A1
A1
A1
A1
A1
A1
A2a
A1
A1
A3
A1
A3 A1
A3
A1
A1
A5
A5
TOILET
MECH/ ELEC
MUD ROOM
8'-8 1/8"
A2
EM3
ES1
EM3
EM4
EM4
EM4
EM5EM5
A1
A1
A1
EM6EM6EM6
EM4
EM4
EM4
EM1
10'-2 3/8"
'-0
T
Y P
2'-5 5/8"
6'-2 1/2"
3'-5 3/8"
3'-4 5/8"
A1
EM7
EM7
A3
A3
ABOVE
EM1 EM3
ES1
13'-7" 3'-4" 4'-3" 4'-0" 4'-5" 4'-0" 6'-1" 4'-4" 4'-7" 3'-4" 8'-4" 8'-0" 11'-11" 3'-4" 3'-9 3/8" 8'-0" 5'-3"
2' -6
8'
-1 0"
2' -6
5'
-9
/4
3'-3 1/4" 22'-2 1/4"
5' -3
/8
EXTERIOR FACE
OF STUD
EXTERIOR
FACE OF
STUD
'-8
/8
4'-9 7/8" 12'-7" 20'-2 5/8" 11'-8"
'-7
2' -3
/4
2' -3
/2
'-1
3/
4"
20'-10 3/8"
5'-7" 15'-3 3/8"
12'-7 1/4" 8'-3 1/8"
1'-11 3/4"
A2a
A1
A1
A2a
A3
35'-2" 10'-4 1/4" 12'-5 1/8" 11'-10 1/8" 8'-10 1/8" 21'-10 3/8"
'-1
1/
4"
3'-5 1/2" 2'-2"
8' -5
/2
9'
-5
/4
2' -5
/2
2' -2
2'
-5
/2
2' -2
4'
-5
/4
2' -2
5'-1 1/4"
4'-0" 3'-4 1/2"
2' -5
/2
1'-6" 9'-0"
7' -0
/4
'-6
'-2
/2
'-9
/2
'-6
'-6
7'-5 3/4" 3'-4" TYP. 9'-0"
2' -2
2'
-2
2' -5
/2
2'
-5
/2
2' -2
7' -0
1/
4"
2'-5 1/2"
2'-2"
5'-0"
1'-1 3/8"
2'-2"
2'-5 1/8"
2'-2 3/8"
9'-0" 2'-4" TYP.
3' -4
/8
'-0
'-6
5' -2
/2
7'
-8
/8
8' -9
2'-0 5/8"
3'-5"
2' -5
/2
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
6 RFI-016
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-121D
DIMENSION PLAN-BLDG 1
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/8" = 1'-0"1
DIMENSION FLOOR PLAN- BUILDING 1
1. ALL DIMENSIONS TO FACE OF CMU, FACE OF STUD OR GRIDLINES, U.N.O.
1 2 4 5
A
B
C
D
E
NOXIOUS WEEDS OFFICE
OFFICE
OPEN OFFICE
HALL
HALL
TLT
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
27'-6 3/8" 16'-8 5/8" 18'-7 1/4" 18'-7 1/4" 18'-11 1/2"
100'-5"
8'
-9
'-0
/2
'-0
/2
'-4
'-4
A-301
A-301
A-301
A-301
SFE26
TENANT
IMPROVEMENT
UNDER SEPARATE
PERMIT
A-302
A-302
SFE35
DSDS
SFE10SFE12SFE45SFE14
SFE16
DS
DS
SFE19 SFE20 SFE20 SFE21
DS
SFE21 SFE20 SFE20 SFE21 SFE24
SFE25
DS
SFE22SFE18
207A
DS
SFE18
NETWORKNETWORKNETWORK
CYBER SR.
CYBER
MANGER
207C
PROJECT
MEETING ROOM
DIRECTOR
CYBER AWARE
SERVER ROOM
STORAGE
KITCHENETTE
RESTROOM RESTROOM
DS
SFE39
A-521
207B
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
12 RFI-049
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-122
ENLARGED FLOOR PLAN -
BLDG 2
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/8" = 1'-0"1
ENLARGED FLOOR PLAN BLDG 2
1. ALL DIMENSIONS TO FACE OF CMU, FACE OF STUD OR GRIDLINES, U.N.O.
A
B
C
D
E
CONFERENCE ROOM
NOXIOUS WEEDS OFFICE
OFFICE
OPEN OFFICE
HALL
HALL TLT
VEST.
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
27'-6 3/8" 16'-8 5/8" 18'-7 1/4" 18'-7 1/4" 18'-5 1/2"
99'-11"
8'
-9
'-0
/2
'-0
/2
'-4
'-4
9' -5
TENANT
IMPROVEMENT
UNDER SEPARATE
PERMIT
A-255
A-255
STG
STG.
SIM.
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-122D
DIMENSION PLAN-BLDG 2
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/8" = 1'-0"1
DIMENSION FLOOR PLAN- BUILDING 2
1. ALL DIMENSIONS TO FACE OF CMU, FACE OF STUD OR GRIDLINES, U.N.O.
CEILING TYPES: XX TYPE
X' - X" HEIGHT
OPEN TO STRUCTURE- R-49 RIGID INSULATION APPLIED TO
UNDERSIDE OF ROOF DECK PAINTED BLACK
ACT-1 -2x2 SUSPENDED ACOUSTICAL CEILING PANEL AND
CONCEALED GRID SYSTEM
WD-1- 3/4" T & G WOOD SOFFIT OVER 7/8" HAT CHANNEL
ACT-2 -2x2 SUSPENDED ACOUSTICAL CEILING PANEL AND
CONCEALED GRID SYSTEM- BASIS OF DESIGN ARMSTRONG
WORDWORKS VECTOR
GWB OVER STEEL STUD FRAMING
MOLD/ MOISTURE RESISTANT GYPSUM BOARD OVER STEEL
STUD FRAMING
FULL HEIGHT WALL UP TO BOTTOM OF METAL DECKING AT ROOF ABOVE.
LOCATION OF EXTERIOR WALL ABOVE, BETWEEN LOWER AND UPPER ROOFS.
1. THESE GENERAL NOTES APPLY TO ALL REFLECTED CEILING PLANS.
2. CEILING HEIGHTS ARE FROM FINISH FLOOR UNO.
3. TYPICAL CEILING HEIGHT TO BE 9' - 0", UNO.
4. ALIGN SOFFITS WITH FACE OF ADJACENT WALL, UNO
5. NOT ALL LIGHTING, INCLUDING PENDANT AND WALL MOUNTED LIGHT FIXTURES,
SHOWN. SEE ELECTRICAL.
6. OTS = OPEN TO STRUCTURE. PAINT ALL EXPOSED CEILING/ROOF STRUCTURE, UNO.
7. U.N.O. - PAINT ALL GWB CEILINGS & SOFFITS PT-1 ( SEE FINISH SCHEDULE)
8. SEE DETAIL FOR TYP SUSPENDED GRID DETAIL..
9. INTERIOR WALLS ARE TYPICALLY 6" ABOVE CEILING HEIGHT SHOWN UNLESS NOTED
OTHERWISE ON ARCHITECTURAL OR STRUCTURAL DRAWINGS (i.e. SHEAR WALLS, SMOKE BARRIER WALLS, SOUND BARRIER WALLS, MECHANICAL ZONE WALLS).
10. COORDINATE LOCATION OF CEILING ACCESS DOORS WITH MECHANICAL &
ELECTRICAL CONTRACTORS.
11. PROVIDE ADDITIONAL EDGE BLOCKING, CROSS BRACING & SUSPENDED SUPPORT
WIRES OR ADDITIONAL FURRING FOR CEILING MOUNTED ITEMS (LIGHTING, ACCESS
PANELS, GRILLES, CAMERAS, ETC.)
FLAG NOTES TO REFLECTED CEILING PLAN:
OTS
MECHANICAL SUPPLY AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
MECHANICAL SUPPLY AIR GRILLE W/ 24"X24"
CEILING GRID SHROUD - REFER TO MECH. FOR
SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE W/ 24"X24"
CEILING GRID SHROUD - REFER TO MECH. FOR
SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
24"X24" RECESSED CEILING
TROFFER - REFER TO ELECT.
24"X24" RECESSED CEILING TROFFER
W/ BATTERY BACK-UP POWER - REFER
TO ELECT
12"X48" RECESSED CEILING
TROFFER - REFER TO ELECT.
12"X48" RECESSED CEILING TROFFER W/
BATTERY BACK-UP POWER - REFER TO
ELECT.
12"X48" PENDANT LIGHTING -
REFER TO ELECT.
RECESSED CAN LIGHT -
REFER TO ELECT.
RECESSED CAN LIGHT W/ BATTERY
BACK-UP - REFER TO ELECT.
RECESSED SKYLITE TUBE W/
TAMPER PROOF
CEILING ACCESS PANEL
CEILING MOUNTED ILLUMINATED
EXIT SIGN
1 2 4 5 6 107 8 9
A
B
C
D
E
NOXIOUS WEEDS OFFICE
DIRECTOR'S OFFICE
OFFICE MANAGER
CONFERENCE
PLAN REVIEW
102 VESTIBULE
CONFERENCE ROOM
EXECUTIVE OFFICE
BREAK ROOM
SUPPLIES
SHOWER
118-A
OPEN WORK SPACE
STORAGE
LACTATION
CUSTODIAL
OFFICE
OFFICE
OFFICE
TOILET
TOILET
TOILET
TOILET
TLTHALL
OPEN OFFICE
OFFICE
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
TENANT
IMPROVEMENT
UNDER SEPARATE
PERMIT
MECH/ ELEC
MUD ROOM
WORKROOM
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-151
LEVEL 1 - REFERENCE
REFLECTED CEILING PLAN
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
3/32" = 1'-0"1
REFERENCE REFLECTED CEILING PLAN
6 107 8 9
A
B
C
D
E
8' - 0"
10' - 0"
9' - 0"
9' - 4"
8' - 0"
9' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
9' - 0"
9' - 0"
9' - 0"
8' - 0"
8' - 0"
8' - 0"
8' - 0"
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
9' - 4"
DS
DS
DS DS
DS
DS
DSDSDSDS
10' - 0"
A-152
OTS
OTS
OTS
OTS
OTS
OTS
OTS
OTS
OTS
OTS
10'-10"
10'-10"
8'-6"
9'-10"
9'-10"
9'-10"
9'-10"
9' - 4"01
OTS
9' - 0"
9' - 0"
10' - 0"
CEILING TYPES: XX TYPE
X' - X" HEIGHT
OPEN TO STRUCTURE- R-49 RIGID INSULATION APPLIED TO
UNDERSIDE OF ROOF DECK PAINTED BLACK
ACT-1 -2x2 SUSPENDED ACOUSTICAL CEILING PANEL AND
CONCEALED GRID SYSTEM
WD-1- 3/4" T & G WOOD SOFFIT OVER 7/8" HAT CHANNEL
ACT-2 -2x2 SUSPENDED ACOUSTICAL CEILING PANEL AND
CONCEALED GRID SYSTEM- BASIS OF DESIGN ARMSTRONG
WORDWORKS VECTOR
GWB OVER STEEL STUD FRAMING
1. THESE GENERAL NOTES APPLY TO ALL REFLECTED CEILING PLANS.
2. CEILING HEIGHTS ARE FROM FINISH FLOOR UNO.
3. TYPICAL CEILING HEIGHT TO BE 9' - 0", UNO.
4. ALIGN SOFFITS WITH FACE OF ADJACENT WALL, UNO
5. NOT ALL LIGHTING, INCLUDING PENDANT AND WALL MOUNTED LIGHT FIXTURES,
SHOWN. SEE ELECTRICAL.
6. OTS = OPEN TO STRUCTURE. PAINT ALL EXPOSED CEILING/ROOF STRUCTURE, UNO.
7. U.N.O. - PAINT ALL GWB CEILINGS & SOFFITS PT-1 ( SEE FINISH SCHEDULE)
8. SEE DETAIL FOR TYP SUSPENDED GRID DETAIL..
9. INTERIOR WALLS ARE TYPICALLY 6" ABOVE CEILING HEIGHT SHOWN UNLESS NOTED
OTHERWISE ON ARCHITECTURAL OR STRUCTURAL DRAWINGS (i.e. SHEAR WALLS, SMOKE BARRIER WALLS, SOUND BARRIER WALLS, MECHANICAL ZONE WALLS).
10. COORDINATE LOCATION OF CEILING ACCESS DOORS WITH MECHANICAL &
ELECTRICAL CONTRACTORS.
11. PROVIDE ADDITIONAL EDGE BLOCKING, CROSS BRACING & SUSPENDED SUPPORT
WIRES OR ADDITIONAL FURRING FOR CEILING MOUNTED ITEMS (LIGHTING, ACCESS
PANELS, GRILLES, CAMERAS, ETC.)
FLAG NOTES TO REFLECTED CEILING PLAN:
OTS
MECHANICAL SUPPLY AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
MECHANICAL SUPPLY AIR GRILLE W/ 24"X24"
CEILING GRID SHROUD - REFER TO MECH. FOR
SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE W/ 24"X24"
CEILING GRID SHROUD - REFER TO MECH. FOR
SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
24"X24" RECESSED CEILING
TROFFER - REFER TO ELECT.
24"X24" RECESSED CEILING TROFFER
W/ BATTERY BACK-UP POWER - REFER
TO ELECT
12"X48" RECESSED CEILING
TROFFER - REFER TO ELECT.
12"X48" RECESSED CEILING TROFFER W/
BATTERY BACK-UP POWER - REFER TO
ELECT.
12"X48" PENDANT LIGHTING -
REFER TO ELECT.
RECESSED CAN LIGHT -
REFER TO ELECT.
RECESSED CAN LIGHT W/ BATTERY
BACK-UP - REFER TO ELECT.
RECESSED SKYLITE TUBE W/
TAMPER PROOF
CEILING ACCESS PANEL
CEILING MOUNTED ILLUMINATED
EXIT SIGN
A
16' - 6"
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-152
LEVEL 1 - ENLARGED
REFLECTED CEILING PLAN
- BLDG 1
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/8" = 1'-0"1
LEVEL 1- ENLARGED REFLECTIVE CEILING PLAN - BLDG 1
REFLECTED CEILING PLAN NOTES
1/4" = 1'-0"2
LEVEL 1 - ENLARGED RCP - -VESTIBULE
A
B
C
D
E
CONFERENCE ROOM
NOXIOUS WEEDS OFFICE
HALL
OPEN OFFICE
TLTHALL
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
TENANT
IMPROVEMENT
UNDER SEPARATE
PERMIT
DS DS
DS DSDS
10'-0"
10'-0"
8'-7"
DS
CEILING TYPES: XX TYPE
X' - X" HEIGHT
OPEN TO STRUCTURE- R-49 RIGID INSULATION APPLIED TO
UNDERSIDE OF ROOF DECK PAINTED BLACK
ACT-1 -2x2 SUSPENDED ACOUSTICAL CEILING PANEL AND
CONCEALED GRID SYSTEM
WD-1- 3/4" T & G WOOD SOFFIT OVER 7/8" HAT CHANNEL
ACT-2 -2x2 SUSPENDED ACOUSTICAL CEILING PANEL AND
CONCEALED GRID SYSTEM- BASIS OF DESIGN ARMSTRONG
WORDWORKS VECTOR
GWB OVER STEEL STUD FRAMING
1. THESE GENERAL NOTES APPLY TO ALL REFLECTED CEILING PLANS.
2. CEILING HEIGHTS ARE FROM FINISH FLOOR UNO.
3. TYPICAL CEILING HEIGHT TO BE 9' - 0", UNO.
4. ALIGN SOFFITS WITH FACE OF ADJACENT WALL, UNO
5. NOT ALL LIGHTING, INCLUDING PENDANT AND WALL MOUNTED LIGHT FIXTURES,
SHOWN. SEE ELECTRICAL.
6. OTS = OPEN TO STRUCTURE. PAINT ALL EXPOSED CEILING/ROOF STRUCTURE, UNO.
7. U.N.O. - PAINT ALL GWB CEILINGS & SOFFITS PT-1 ( SEE FINISH SCHEDULE)
8. SEE DETAIL FOR TYP SUSPENDED GRID DETAIL..
9. INTERIOR WALLS ARE TYPICALLY 6" ABOVE CEILING HEIGHT SHOWN UNLESS NOTED
OTHERWISE ON ARCHITECTURAL OR STRUCTURAL DRAWINGS (i.e. SHEAR WALLS, SMOKE BARRIER WALLS, SOUND BARRIER WALLS, MECHANICAL ZONE WALLS).
10. COORDINATE LOCATION OF CEILING ACCESS DOORS WITH MECHANICAL &
ELECTRICAL CONTRACTORS.
11. PROVIDE ADDITIONAL EDGE BLOCKING, CROSS BRACING & SUSPENDED SUPPORT
WIRES OR ADDITIONAL FURRING FOR CEILING MOUNTED ITEMS (LIGHTING, ACCESS
PANELS, GRILLES, CAMERAS, ETC.)
FLAG NOTES TO REFLECTED CEILING PLAN:
OTS
MECHANICAL SUPPLY AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
MECHANICAL SUPPLY AIR GRILLE W/ 24"X24"
CEILING GRID SHROUD - REFER TO MECH. FOR
SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE W/ 24"X24"
CEILING GRID SHROUD - REFER TO MECH. FOR
SIZE AND TYPE
MECHANICAL RETURN AIR GRILLE - REFER TO
MECH. FOR SIZE AND TYPE
24"X24" RECESSED CEILING
TROFFER - REFER TO ELECT.
24"X24" RECESSED CEILING TROFFER
W/ BATTERY BACK-UP POWER - REFER
TO ELECT
12"X48" RECESSED CEILING
TROFFER - REFER TO ELECT.
12"X48" RECESSED CEILING TROFFER W/
BATTERY BACK-UP POWER - REFER TO
ELECT.
12"X48" PENDANT LIGHTING -
REFER TO ELECT.
RECESSED CAN LIGHT -
REFER TO ELECT.
RECESSED CAN LIGHT W/ BATTERY
BACK-UP - REFER TO ELECT.
RECESSED SKYLITE TUBE W/
TAMPER PROOF
CEILING ACCESS PANEL
CEILING MOUNTED ILLUMINATED
EXIT SIGN
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
5 PR-005
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-153
LEVEL 1 - ENLARGED
REFLECTIVE CEILING PLAN
- BLDG 2
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/8" = 1'-0"1
LEVEL 1 - ENLARGED REFLECTIVE CEILING PLAN - BLDG 2
REFLECTED CEILING PLAN NOTES
1. TYPICAL CORRUGATED METAL ROOF ASSEMBLY:
CORRUGATED METAL ROOF PANELS
SYNTHETIC ROOFING UNDERLAYMENT\ICE AND WATER SHIELD / PEEL AND
STICK MEMBRANE AT EAVES, VALLEYS, ETC. PER SPEC
1/2" THICK ROOF COVERBOARD (DENSDECK OR APPROVED)
LAYER OR LAYERS OF R-38 RIGID INSULATION
PLYWOOD SHEATHING & ROOF FRAMING PER STRUCTURAL
2. TYPICAL SINGLE-PLY MEMBRANE ROOF ASSEMBLY:
60 MIL. FULLY-ADHERED SINGLE-PLY MEMBRANE OR APPROVED
ALTERNATIVE.
1/4" THICK ROOF COVER BOARD (DENS DECK OR APPROVED)
STAGGERED LAYERS OF RIGID INSULATION: THICKNESS AS REQUIRED
FOR R-38 RATING.
SELF-ADHERING VAPOR RETARDER MEMBRANE
METAL DECKING & ROOF FRAMING PER STRUCTURAL
3. AT EXISTING SINGLE PLY ROOF- PATCH AND REPAIR TO MAINTAIN
EXISTING WARRANTIES. REFER TO MANUFACTURER FOR INSTALLATION
REQUIREMENTS TO MAINTAIN EXISTING WARRANTIES.
4. PROVIDE 24 GA PRE-FINISHED METAL STEP FLASHING AT ANY SLOPING
SHINGLE INTERFACE W/ A VERTICAL SURFACE.
5. ALL ROOF DRAINS, OVERFLOW DRAINS AND RAIN LEADERS SERVING
SINGLE-PLY MEMBRANE ROOF TO BE 4" DIAMETER SIZE.
6. ALL DOWNSPOUTS SERVING GUTTERS TO BE 3" DIAMETER PVC PIPE.
7. PROVIDE FREE STANDING PIPING AND CONDUIT SUPPORTS OF UV
RESISTANT CLOSED CELL FOAM W/ 14 GAUGE MINIMUM PIPE / CONDUIT
CLAMPS
SINGLE-PLY MEMBRANE ROOFING.
CRICKET AT HIGH SIDE OF ROOF CURB OR WALL.
PIPE PENETRATION (PER MECH) - FLASH PER DETAIL 1/A-573
ROOFTOP MECHANICAL UNIT, REFER TO MECHANICAL
DRAWINGS & REFER TO DETAIL 2/A-572
PATCH OF ROOFING FLASHING TO OVERLAP EXISTING
ROOFING SYSTEM AND OVERLAP NEW PT SLOPED WOOD
BLOCKING AT PARAPET
CORRUGATED METAL ROOF PANELS, REFER TO ROOF TYPES
FOR ASSEMBLY
RD
RD
1 2 4 5
6 107 8 9
A
B
C
D
E
A-301
A-301
A-301
A-301
A-301
A-301
A-301
A-301
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
RIDGE
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-161
REFERENCE ROOF PLAN
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
ROOF PLAN NOTES
ROOF PLAN LEGEND
3/32" = 1'-0"1
REEFENCE ROOF PLAN
SINGLE-PLY MEMBRANE ROOFING.
CRICKET AT HIGH SIDE OF ROOF CURB OR WALL.
PIPE PENETRATION (PER MECH) - FLASH PER DETAIL 1/A-573
ROOFTOP MECHANICAL UNIT, REFER TO MECHANICAL
DRAWINGS & REFER TO DETAIL 2/A-572
PATCH OF ROOFING FLASHING TO OVERLAP EXISTING
ROOFING SYSTEM AND OVERLAP NEW PT SLOPED WOOD
BLOCKING AT PARAPET
CORRUGATED METAL ROOF PANELS, REFER TO ROOF TYPES
FOR ASSEMBLY
4. PROVIDE 24 GA PRE-FINISHED METAL STEP FLASHING AT ANY SLOPING `
SHINGLE INTERFACE W/ A VERTICAL SURFACE.
5. ALL ROOF DRAINS, OVERFLOW DRAINS AND RAIN LEADERS SERVING
SINGLE-PLY MEMBRANE ROOF TO BE 4" DIAMETER SIZE.
6. ALL DOWNSPOUTS SERVING GUTTERS TO BE 3" DIAMETER PVC PIPE.
7. PROVIDE FREE STANDING PIPING AND CONDUIT SUPPORTS OF UV
RESISTANT CLOSED CELL FOAM W/ 14 GAUGE MINIMUM PIPE / CONDUIT
CLAMPS
1. TYPICAL CORRUGATED METAL ROOF ASSEMBLY:
CORRUGATED METAL ROOF PANELS
SYNTHETIC ROOFING UNDERLAYMENT\ICE AND WATER SHIELD / PEEL AND
STICK MEMBRANE AT EAVES, VALLEYS, ETC. PER SPEC
1/2" THICK ROOF COVERBOARD (DENSDECK OR APPROVED)
LAYER OR LAYERS OF R-38 RIGID INSULATION
PLYWOOD SHEATHING & ROOF FRAMING PER STRUCTURAL
2. TYPICAL SINGLE-PLY MEMBRANE ROOF ASSEMBLY:
60 MIL. FULLY-ADHERED SINGLE-PLY MEMBRANE OR APPROVED
ALTERNATIVE.
1/4" THICK ROOF COVER BOARD (DENS DECK OR APPROVED)
STAGGERED LAYERS OF RIGID INSULATION: THICKNESS AS REQUIRED
FOR R-38 RATING.
SELF-ADHERING VAPOR RETARDER MEMBRANE
METAL DECKING & ROOF FRAMING PER STRUCTURAL
3. AT EXISTING SINGLE PLY ROOF- PATCH AND REPAIR TO MAINTAIN
EXISTING WARRANTIES. REFER TO MANUFACTURER FOR INSTALLATION
REQUIREMENTS TO MAINTAIN EXISTING WARRANTIES.
1- INSTALL NEW COPING AT PARAPET OVER NEW PT SLOPED WOOD PLATE
2- INSTALL NEW FLASHING AT COUNTER FLASHING AT WALL TO ROOF
6 107 8 9
A
B
C
D
E
A-301
A-301
A-301
A-301
A-301
A-301
A-302
A-302
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
N O
R T
H E
LE
V
A T
IO
N
C O
N S
T R
U C
T P
A R
A P
E T
O N
A T
R O
O F
T O
W A
LL
N E
W F
LA
S
H
IN
G
C O
U N
T E
R F
LA
S
H
IN
G
19' -5
'-1
1/ 2"
4'-0" TYP.
ROOF DRAIN &
OVERFLOW SCUPPER W
DOWNSPOUT & SPLASH
PAN
1/ 4"
:1
E/RD
E/RD
R
ID
G E
V A
LL
E
Y
VALLEY
A
LI
G N
T O
E X
IS
T
IN
G
A D
J.
H
E
IG
H T
B U
IL
D
-U P
P A
R A
P E
T
8' -0
4'-0" TYP.
4' -0
18'-10" 4'-0 3/8"
4' -0
T
Y P
7'-6" 23'-8 3/8"
4' -0
11'-6" 7'-6"
4' -0
ALIGN TO EXISTING ADJ. HEIGHT
BUILD-UP PARAPET &
VALLEY
VALLEY
A-571
A-571
A-571
A-571
A-571
A-571
A-552
Sim
LOW @ CANOPY
A-552
Sim
LOW @ CANOPY
SIM.
SIM.
SIM.
SIM.
SIM.
A-573
A-573
A-573
A-577
A-577
A-577
A-577
A-577
A-577
A-573
HIGH
A-573
HIGH
A-573
HIGH
A-573
HIGH
A-573
LOW
A-573
LOW
A-574
A-577
A-572
A-572
A-572
7 A-572
A-572
A-572
RD
ORD
RD ORD
A-577
A-577
A-577
4HIGH
A-577
Sim
LOW
A-577
Sim
LOW
HIGH
NEW CONDUCTOR HEAD &
DOWNSPOUT NOZZLE AT
EXISTING PARAPET WALL
OVERFLOW DOWNSPOUT
NOZZLE 1'-6" ABOVE BASE
OF EXISTING WALL
10'-6" TYP.
OVERFLOW DOWNSPOUT
NOZZLE 1'-6" ABOVE BASE
OF EXISTING WALL
NEW CONDUCTOR HEAD &
DOWNSPOUT NOZZLE AT
EXISTING PARAPET WALL
PATH OF ROOF &
OVERFLOW ROOF
DRAIN LEADERS
PATH OF ROOF &
OVERFLOW ROOF
DRAIN LEADERS
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
11 RFI-047
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-162
ENLARGED ROOF PLAN -
BLDG 1
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
ROOF PLAN LEGEND
ROOF PLAN NOTES
ROOF KEY NOTES
1/8" = 1'-0"1
ENLARGED ROOF PLAN BLDG 1
A
B
C
D
E
100'-5"
27'-6 3/8" 16'-8 5/8" 18'-7 1/4" 18'-7 1/4" 18'-11 1/2"
8'
-9
'-0
/2
'-0
/2
'-4
'-4
A-301
A-301
A-301
A-301
R E
F E
R T
O A
-1
R E
F E
R T
O A
-1
S
LO
P E S
LO
P
E
NEW GUTTER &
DOWNSPOUT
A-302
A-302
A-572
A-552
DS DS DS
A-576
A-576
A-576
4. PROVIDE 24 GA PRE-FINISHED METAL STEP FLASHING AT ANY SLOPING `
SHINGLE INTERFACE W/ A VERTICAL SURFACE.
5. ALL ROOF DRAINS, OVERFLOW DRAINS AND RAIN LEADERS SERVING
SINGLE-PLY MEMBRANE ROOF TO BE 4" DIAMETER SIZE.
6. ALL DOWNSPOUTS SERVING GUTTERS TO BE 3" DIAMETER PVC PIPE.
7. PROVIDE FREE STANDING PIPING AND CONDUIT SUPPORTS OF UV
RESISTANT CLOSED CELL FOAM W/ 14 GAUGE MINIMUM PIPE / CONDUIT
CLAMPS
1. TYPICAL CORRUGATED METAL ROOF ASSEMBLY:
CORRUGATED METAL ROOF PANELS
SYNTHETIC ROOFING UNDERLAYMENT\ICE AND WATER SHIELD / PEEL AND
STICK MEMBRANE AT EAVES, VALLEYS, ETC. PER SPEC
1/2" THICK ROOF COVERBOARD (DENSDECK OR APPROVED)
LAYER OR LAYERS OF R-38 RIGID INSULATION
PLYWOOD SHEATHING & ROOF FRAMING PER STRUCTURAL
2. TYPICAL SINGLE-PLY MEMBRANE ROOF ASSEMBLY:
60 MIL. FULLY-ADHERED SINGLE-PLY MEMBRANE OR APPROVED
ALTERNATIVE.
1/4" THICK ROOF COVER BOARD (DENS DECK OR APPROVED)
STAGGERED LAYERS OF RIGID INSULATION: THICKNESS AS REQUIRED
FOR R-38 RATING.
SELF-ADHERING VAPOR RETARDER MEMBRANE
METAL DECKING & ROOF FRAMING PER STRUCTURAL
3. AT EXISTING SINGLE PLY ROOF- PATCH AND REPAIR TO MAINTAIN
EXISTING WARRANTIES. REFER TO MANUFACTURER FOR INSTALLATION
REQUIREMENTS TO MAINTAIN EXISTING WARRANTIES.
1- INSTALL NEW COPING AT PARAPET OVER NEW PT SLOPED WOOD PLATE
2- INSTALL NEW FLASHING AT COUNTER FLASHING AT WALL TO ROOF
3- SIDING TO BE REMOVED FROM WALL, EXISTING PARAPET COPING TO
REMAIN, REMOVE AND RE- INSTALL AS REQUIRED
SINGLE-PLY MEMBRANE ROOFING.
30" WIDE ROOF WALK PADS - SPACE APART 4"+/- TO ALLOW
FOR DRAINAGE.
CRICKET AT HIGH SIDE OF ROOF CURB OR WALL.
VTR @ STEEP ROOF (PER MECH) - FLASH PER
PATCH OF ROOFING FLASHING TO OVERLAP EXISTING
ROOFING SYSTEM AND OVERLAP NEW PT SLOPED WOOD
BLOCKING AT PARAPET
CORRUGATED METAL ROOF PANELS, REFER TO ROOF TYPES
FOR ASSEMBLY
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
9 RFI-013
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-163
ENLARGED ROOF PLAN -
BLDG 2
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
1/8" = 1'-0"1
ENLARGED ROOF PLAN BLDG 2
ROOF PLAN NOTES
ROOF KEY NOTES
ROOF PLAN LEGEND
1. REFER TO SHEET GI101 FOR ENERGY CODE FENESTRATION SUMMARY.
HORIZONTAL WOOD SIDING OVER FURRING STRIPS
(APPLIED VERTICALLY) OVER EXISTING MASONRY WALL
EXISTING BRICK WALL - APPLY TRANSPARENT WATER
REPELLANT AFTER
CORRUGATED METAL SIDING OVER FURRING
STRIPS (APPLIED VERTICALLY) OVER EXISTING
MASONRY WALL
CMU VENEER - PAINT
CANOPY
CLEAN & SEAL EXISTING BRICK,
REPOINT DAMAGED MORTAR
JOINTS & REPAIR WHERE REQUIRED
NEW METAL PARAPET
COPING OVER PT SLOPED
WOOD PLATE
CANOPY
CORRUGATED
METAL SIDINGSTOREFRONT W/
DOOR
DOWNSPOUT
SFE26
B.O.CANOPY
10' - 0"
TOP PARAPET
BLDG 2
27' - 6 19/32"
SFE
SFE
LEV. 1-BLDG 2
2' - 0 19/32"
A-522
SFE16
SFE17
LEV. 1-BLDG 1.TI
0' - 0"
CANOPY
LEV. 1-BLDG 5
12' - 0 15/32"
BLDG 2 ROOF
20' - 10"
1245610 789 3
CORRUGATED METAL
SIDING OVER FURRING
STRIPS
UPPER ROOF W/
METAL FASCIA TRIM
CANOPY
WOOD SIDING OVER
FURRING
CANOPY
NEW METAL PARAPET
COPING OVER PT.
SLOPED WOOD PLATE
CLEAN & SEAL EXISTING BRICK,
REPOINT DAMAGED MORTAR
JOINTS & REPAIR WHERE
REQUIRED AT FRONT
ELEVATION
CAREFULLY RE-INSTALL
EXISTING METAL COPING AT
PARAPET WHERE IMPACTED
BY REMOVAL OF SIDING
STOREFRONT W/ DOOR
DOWNSPOUT
DOWNSPOUT
DOWNSPOUT
DOWNSPOUT
DOWNSPOUT
DOWNSPOUT
SFE2
SFE3 SFE4
SFE5 SFE6
SFE7 SFE7 SFE7 SFE7
TOP PARAPET
BLDG 2
27' - 6 19/32"
SFE9
SFE35
SFE11
SFE10
SFE13
SFE12
SFE11
SFE45
SFE15
SFE14
LEV. 1-BLDG 2
2' - 0 19/32"
SFE1
LEV. 1-BLDG 1
0' - 0"
BLDG 2 ROOF
20' - 10"
ACDE
NEW METAL PARAPET
COPING OVER PT.
SLOPED WOOD PLATE
CLEAN & SEAL EXISTING BRICK,
REPOINT DAMAGED MORTAR
JOINTS & REPAIR WHERE
REQUIRED AT FRONT
ELEVATION
CAREFULLY RE-INSTALL
EXISTING METAL COPING AT
PARAPET WHERE IMPACTED
BY REMOVAL OF SIDING
ADJ. PARAPET HEIGHT
INFILL PARAPET TO MATCH EXIST.NEW METAL
PARAPET COPING
OVER PT. SLOPED
WOOD PLATE
INSTALL NEW METAL FLASHING
AND COUNTERFLASHING AT
ROOF TO WALL TRANSITION
INSTALL NEW GUTTER
AT EXISTING ROOF AT
BLDG #2
TOP PARAPET
15' - 4"
906 Columbia Street SW, Suite 400
Olympia, Washington 98501
360.352.8883 architects
KMB Project #
SHEET NO.
REVISIONS:
DATE:
ORIGINAL SHEET SIZE = 24 x 36
HALF SIZE REDUCTIONS = 11 x 17
P
LO
T D
A T
E
ARCHITECT
STATE OF WASHINGTON
REGISTERED
JAMES HILL
10347
12 RFI-049
/1
/2
:5
8:
P M
01-13-2023
CONFORMED SET
A-201
EXTERIOR ELEVATIONS
LE
W
IS
C
O U
N
TY
R A
IN
IE
R T
I I M
P R
O
VE
M
EN
TS
LE
W
IS
C O
U N
TY
F
A C
IL
IT
IE
S
D
EP
A R
TM
EN
T
N W
N O
R
TH
S
TR
EE
T, C H
EH
A
LI
S
, W A
Fa ci lit ie s D ep ar tm en t
J2037C
EXTERIOR ELEVATION LEGEND
1/8" = 1'-0"1
EXTERIOR ELEVATION - NORTH
1/8" = 1'-0"2
EXTERIOR ELEVATION - EAST
1/8" = 1'-0"3
EXTERIOR ELEVATION- SOUTH @ BLDG 2
1. REFER TO SHEET GI101 FOR ENERGY CODE FENESTRATION SUMMARY.
HORIZONTAL WOOD SIDING OVER FURRING STRIPS
(APPLIED VERTICALLY) OVER…