This is a comprehensive asbestos and lead-based paint survey report prepared by L.Y. Environmental, Inc. for the Fontana Unified School District regarding modular buildings at Oleander Elementary School located at 8650 Oleander Avenue, Fontana, California. The survey was conducted on April 7, 2026, by Yonan Benjamin, a Certified Asbestos Consultant and Certified Industrial Hygienist, and included bulk sampling of 66 materials from three structures (a staff restroom building and two classroom buildings designated as #33 and #34) that are slated for demolition. Samples were analyzed by Inland Asbestos Lab, an NVLAP-accredited laboratory, using EPA Method 600/R-93/116 for asbestos detection and PLM analysis. XRF lead readings were also conducted on all painted and impacted components throughout the facilities.
The survey findings indicate that all 66 bulk samples tested negative for asbestos, and all lead-based paint XRF readings registered at 0.00 mg/cm², well below the HUD and CDPH standard of 1.0 mg/cm². Materials sampled included linoleum and adhesives from restrooms, drywall and joint compounds from classroom walls, ceiling tiles, carpet adhesives, baseboards, roof materials (hot roll sheets and felt paper), roof penetration mastics, wall moisture paper, exterior piping, floor materials, and exterior asphalt pavement. The structures were found to be in intact, non-friable condition with zero percent damage across all tested materials. This survey supports the planned demolition and relocation of these modular buildings as part of the Oleander Elementary School site improvement project scheduled for commencement following the mandatory April 8, 2026, job walk.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L.Y. Environmental, Inc.
1050 Nevada Street, Suite 401, Redlands, CA 92374 • Phone (909) 3079730 • Fax (909) 3079740
April 13, 2026
Fontana Unified School District Attn: Luis E. Estrada Senior Director, Maintenance & Operations Phone: (909) 3577520 Email: Luis.Estrada@fusd.net
Summary Report: Comprehensive Asbestos & Lead Based Paint Survey 8650 Oleander Ave, Fontana, CA 92335
Oleander Elementary School
I. Introduction
L.Y. Environmental Inc., (LYEI) received a request to conduct a Comprehensive Asbestos & Lead Based Paint Survey for the property located on 8650 Oleander Ave, Fontana, California. LYEI was requested to inspect the abovementioned property for the existence of asbestos and lead containing materials and to provide a written report of findings.
II. Background
Yonan Benjamin (CAC DOSH #02/3228) of LYEI conducted the survey at the subject site on April 7, 2026. The report was reviewed and completed by Yonan Benjamin, a Certified Asbestos Consultant and Certified Industrial Hygienist with LYEI.
The structures are manufactured portables that are slated for demolition. The samples of the Floor, Ceiling, Wall Panels, Wall Moisture Paper, Exterior Pipe Drain, Exterior Floor, Roof Hot Roll Sheet, Roof Felt Paper, Roof Penetration Mastic, Wall, Baseboard, Ceiling Tile, Carpet Adhesive, and Exterior Asphalt Pavement Materials were collected. Samples were taken, all of which were analyzed by Inland Asbestos Lab located in Redlands, California, which is an NVLAP Lab (NVLAP Code 2010000; Ph: 9094355504). Asbestos Bulk samples were analyzed by PLM using EPA Method 600/R93/116, (July 1993), in accordance with 40 CFR 763, Subpart F, Appendix A (AHERA), and if applicable, the Point Count Method 600/R93/116 (1000 Point), (July 1993). The survey was conducted in accordance with CAL/OSHA, EPA AHERA and South Coast Air Quality Management District sampling protocols using nondestructive representative sampling techniques. See attached, Asbestos Bulk Sampling Field Log for materials and locations of samples collected.
In addition, XRF Niton XL #9739, Model XLp 300A, 40 mCi Cd109, readings of all impacted and painted components were taken onsite by Yonan Benjamin, Lead Inspector/Assessor, Cert.# LRC 00008161.
III. Findings/Conclusions
1Results Table Summary
Sample
Material Sampled Sample Location Quantity Analytical Results
Friability Condition Percent Damaged
L1 Linoleum (brown)
Staff Restroom “Women”
180ft2 Non Detected Non Friable Intact 0%
L1 Adhesive (yellow)
Staff Restroom “Women”
180ft2 Non Detected Non Friable Intact 0%
L2 Linoleum (brown)
Staff Restroom “Men”
180ft2 Non Detected Non Friable Intact 0%
L2 Adhesive (yellow)
Staff Restroom “Men”
180ft2 Non Detected Non Friable Intact 0%
L3 Linoleum (brown)
Staff Restroom “Handicap”
40ft2 Non Detected Non Friable Intact 0%
L3 Adhesive (yellow)
Staff Restroom “Handicap”
40ft2 Non Detected Non Friable Intact 0%
CS1 Ceiling Drywall (white, brown)
Staff Restroom “Women”
180ft2 Non Detected Non Friable Intact 0%
CS1 Ceiling Joint Compound
(white)
Staff Restroom “Women”
180ft2 Non Detected Non Friable Intact 0%
CS2 Ceiling Drywall (white, brown)
Staff Restroom “Men”
180ft2 Non Detected Non Friable Intact 0%
CS2 Ceiling Joint Compound
(white)
Staff Restroom “Men”
180ft2 Non Detected Non Friable Intact 0%
CS3 Ceiling Drywall (white, brown)
Staff Restroom “Handicap &
Closet”
70ft2 Non Detected Non Friable Intact 0%
CS3 Ceiling Joint Compound
(white)
Staff Restroom “Handicap &
Closet”
70ft2 Non Detected Non Friable Intact 0%
WP1 Wall Panels & Adhesive
(gray, brown)
Staff Restroom “Women”
180ft2 Non Detected Non Friable Intact 0%
WP2 Wall Panels & Adhesive
(gray, brown)
Staff Restroom “Men”
180ft2 Non Detected Non Friable Intact 0%
WP3 Wall Panels & Adhesive
(gray, brown)
Staff Restroom “Handicap &
Closet”
70ft2 Non Detected Non Friable Intact 0%
WMP1 Wall Moisture Paper
(brown)
Staff Restroom Building Exterior
Walls
450ft2 Non Detected Non Friable Intact 0%
WMP2 Wall Moisture Paper
(brown)
Staff Restroom Building Exterior
Walls
450ft2 Non Detected Non Friable Intact 0%
WMP3 Wall Moisture Paper
(brown)
Staff Restroom Building Exterior
Walls
450ft2 Non Detected Non Friable Intact 0%
P1 Exterior Pipe Drain (gray, black)
Staff Restroom Under E. Wall
5ft2 Non Detected Non Friable Intact 0%
P2 Exterior Pipe Drain (gray, black)
Staff Restroom Under E. Wall
5ft2 Non Detected Non Friable Intact 0%
P3 Exterior Pipe Drain (gray, black)
Staff Restroom Under E. Wall
5ft2 Non Detected Non Friable Intact 0%
FM1 Exterior Floor
Material (black)
Staff Restroom North Ramps
120ft2 Non Detected Non Friable Intact 0%
FM2 Exterior Floor Material (black)
Staff Restroom North Ramps
120ft2 Non Detected Non Friable Intact 0%
FM3 Exterior Floor Material (black)
Staff Restroom North Ramps
120ft2 Non Detected Non Friable Intact 0%
R1 Roof Hot Roll Sheet
(black)
Staff Restroom Building
550ft2 Non Detected Non Friable Intact 0%
R2 Roof Hot Roll Sheet
(black)
Staff Restroom Building
550ft2 Non Detected Non Friable Intact 0%
R3 Roof Hot Roll Sheet
(black)
Staff Restroom Building
550ft2 Non Detected Non Friable Intact 0%
FP1 Roof Felt Paper (black)
Staff Restroom Building
550ft2 Non Detected Non Friable Intact 0%
FP2 Roof Felt Paper (black)
Staff Restroom Building
550ft2 Non Detected Non Friable Intact 0%
FP3 Roof Felt Paper (black)
Staff Restroom Building
550ft2 Non Detected Non Friable Intact 0%
PM1 Roof Penetration Mastic
(white, black)
Staff Restroom Building
10ft2 Non Detected Non Friable Intact 0%
PM2 Roof Penetration Mastic
(white, black)
Staff Restroom Building
10ft2 Non Detected Non Friable Intact 0%
PM3 Roof Penetration Mastic
(white, black)
Staff Restroom Building
10ft2 Non Detected Non Friable Intact 0%
WS1 Wall Drywall (white, brown)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
WS1 Wall Plaster & Joint Compound
(white)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
WS2 Wall Drywall (white, brown)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
WS2 Wall Plaster & Joint Compound
(white)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
WS3 Wall Drywall (white, brown)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
WS3 Wall Plaster & Joint Compound
(white)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
BC1 Baseboard (black)
#34 Building 34ft2 Non Detected Non Friable Intact 0%
BC1 Adhesive (yellow)
#34 Building 34ft2 Non Detected Non Friable Intact 0%
BC2 Baseboard (black)
#34 Building 34ft2 Non Detected Non Friable Intact 0%
BC2 Adhesive (yellow)
#34 Building 34ft2 Non Detected Non Friable Intact 0%
BC3 Baseboard #34 Building 34ft2 Non Detected Non Friable Intact 0%
(black) BC3 Adhesive
(yellow) #34 Building 34ft2 Non Detected Non Friable Intact 0%
CT1 2’x4’ Ceiling Tile (white, brown)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
CT2 2’x4’ Ceiling Tile (white, brown)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
CT3 2’x4’ Ceiling Tile (white, brown)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
CA1 Carpet Adhesive (yellow)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
CA2 Carpet Adhesive (yellow)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
CA3 Carpet Adhesive (yellow)
#34 Building 600ft2 Non Detected Non Friable Intact 0%
WS4 Wall Drywall (white, brown)
#33 Building Perimeter Walls
600ft2 Non Detected Non Friable Intact 0%
WS4 Wall Joint Compound
(white)
#33 Building Perimeter Walls
600ft2 Non Detected Non Friable Intact 0%
WS5 Wall Drywall (white, brown)
#33 Building Perimeter Walls
600ft2 Non Detected Non Friable Intact 0%
WS5 Wall Joint Compound
(white)
#33 Building Perimeter Walls
600ft2 Non Detected Non Friable Intact 0%
WS6 Wall Drywall (white, brown)
#33 Building Perimeter Walls
600ft2 Non Detected Non Friable Intact 0%
WS6 Wall Joint Compound
(white)
#33 Building Perimeter Walls
600ft2 Non Detected Non Friable Intact 0%
WS7 Wall Drywall Panels
(white, brown)
#33 Building Partitions “Walls”
600ft2 Non Detected Non Friable Intact 0%
WS8 Wall Drywall Panels
(white, brown)
#33 Building Partitions “Walls”
600ft2 Non Detected Non Friable Intact 0%
WS9 Wall Drywall Panels
(white, brown)
#33 Building Partitions “Walls”
600ft2 Non Detected Non Friable Intact 0%
CT4 2’x4’ Ceiling Tile (white, brown)
#33 Building 600ft2 Non Detected Non Friable Intact 0%
CT5 2’x4’ Ceiling Tile (white, brown)
#33 Building 600ft2 Non Detected Non Friable Intact 0%
CT6 2’x4’ Ceiling Tile (white, brown)
#33 Building 600ft2 Non Detected Non Friable Intact 0%
CA4 Carpet Adhesive (yellow)
#33 Building 600ft2 Non Detected Non Friable Intact 0%
CA5 Carpet Adhesive (yellow)
#33 Building 600ft2 Non Detected Non Friable Intact 0%
CA6 Carpet Adhesive (yellow)
#33 Building 600ft2 Non Detected Non Friable Intact 0%
BC4 Baseboard (black)
#33 Building “Perimeters”
34ft2 Non Detected Non Friable Intact 0%
BC4 Adhesive (yellow)
#33 Building “Perimeters”
34ft2 Non Detected Non Friable Intact 0%
BC5 Baseboard (black)
#33 Building “Perimeters”
34ft2 Non Detected Non Friable Intact 0%
BC5 Adhesive
(yellow) #33 Building “Perimeters”
34ft2 Non Detected Non Friable Intact 0%
BC6 Baseboard (black)
#33 Building “Perimeters”
34ft2 Non Detected Non Friable Intact 0%
BC6 Adhesive (yellow)
#33 Building “Perimeters”
34ft2 Non Detected Non Friable Intact 0%
BC7 Baseboard (black)
#33 “Partition Walls”
34ft2 Non Detected Non Friable Intact 0%
BC7 Adhesive (yellow)
#33 “Partition Walls”
34ft2 Non Detected Non Friable Intact 0%
BC8 Baseboard (black)
#33 “Partition Walls”
34ft2 Non Detected Non Friable Intact 0%
BC8 Adhesive (yellow)
#33 “Partition Walls”
34ft2 Non Detected Non Friable Intact 0%
BC9 Baseboard (black)
#33 “Partition Walls”
34ft2 Non Detected Non Friable Intact 0%
BC9 Adhesive (yellow)
#33 “Partition Walls”
34ft2 Non Detected Non Friable Intact 0%
FM4 Exterior Floor Material (brown)
#33 & #34 Buildings “Ramps”
160ft2 Non Detected Non Friable Intact 0%
FM5 Exterior Floor Material (brown)
#33 & #34 Buildings “Ramps”
160ft2 Non Detected Non Friable Intact 0%
FM6 Exterior Floor Material (brown)
#33 & #34 Buildings “Ramps”
160ft2 Non Detected Non Friable Intact 0%
PA1 Exterior Asphalt Pavement
(black)
Exterior Floor Around #33, #34, Restroom
1,000ft2 Non Detected Non Friable Intact 0%
PA2 Exterior Asphalt Pavement
(black)
Exterior Floor Around #33, #34, Restroom
1,000ft2 Non Detected Non Friable Intact 0%
PA3 Exterior Asphalt Pavement
(black)
Exterior Floor Around #33, #34, Restroom
1,000ft2 Non Detected Non Friable Intact 0%
BC10 Baseboard (brown)
Staff Restroom “Handicap”
10ft2 Non Detected Non Friable Intact 0%
BC10 Adhesive (offwhite)
Staff Restroom “Handicap”
10ft2 Non Detected Non Friable Intact 0%
BC11 Baseboard (brown)
Staff Restroom “Handicap”
10ft2 Non Detected Non Friable Intact 0%
BC11 Adhesive (offwhite)
Staff Restroom “Handicap”
10ft2 Non Detected Non Friable Intact 0%
BC12 Baseboard (brown)
Staff Restroom “Handicap”
10ft2 Non Detected Non Friable Intact 0%
BC12 Adhesive (offwhite)
Staff Restroom “Handicap”
10ft2 Non Detected Non Friable Intact 0%
Asbestos
Results of the bulk sample analysis are attached to this report and showed no concentrations of asbestos in the structural materials collected and tested. See attached, Asbestos Sampling Field Log for the results and locations.
Lead Based Paint
The results of the onsite XRF readings of the painted components showed readings below the HUD & CDPH standard/guideline of 1.0 mg/cm2.
Thank you for giving L.Y. Environmental, Inc. the opportunity to participate in this investigation.
We would be happy to provide any additional services, if necessary. Should there be any questions, or if I may be of further assistance, please feel free to contact me.
Sincerely, L.Y. Environmental, Inc.
Yonan Benjamin, CIH CAC LPM Director, Indoor Air Quality and Industrial Hygiene Certified Industrial Hygienist (ABIH #7299) Certified Asbestos Consultant (DOSH #02/3228) Lead Inspector/Assessor (LRC00008161)
Attachments:
Laboratory Results for Asbestos Chain of Custody
CONDITIONS AND LIMITATIONS
L.Y. Environmental, Inc. (“LYEI”) has prepared this report for the exclusive use of its client. LYEI, in its survey’s measurements, applies approximations of the dimensional areas (square footage) it is not to be relied upon for bidding purposes.
LYEI, in performing its professional services, has applied engineering and scientific judgment that it believes is consistent with OSHA and AHERA industry standards. LYEI has inspected structures and/or contents in a good faith effort to observe pertinent detail. Due to the limitations of time, access, and other variables, certain details may have been overlooked. LYEI has relied in good faith upon the information and representations of others in the preparation of this report and the opinions expressed herein. Accordingly, LYEI accepts no responsibility for deficiencies, omissions, misrepresentations, or fraudulent acts of persons interviewed.
It is always possible that chemical and/or biological agents may be present in a building that have not been targeted for assay, have not been identified by science as a potential health threat, or are present in such small quantities or low levels that they were not detected by the sampling and/or analytical methods employed. It is also possible that variables in sample collection, such as those associated with an isolated or intermittent contaminant, the random selection of a sample location, etc., will affect analytical results. Accordingly, it cannot be determined with absolute certainty that there is no risk of exposure to some chemical and/or biological agents.
LYEI will accept no liability for any loss, injury, claim or damage arising directly or indirectly from any use or reliance on this report or the opinions expressed herein. LYEI makes no warranty, expressed or implied.
Inland Asbestos Lab, Inc.
1040 Nevada St., Suite 300, Redlands, CA 92374
(909) 219-4285 info@inlandalab.com
L.Y. Environmental, Inc. Lab Ref. No.:
Yonan Benjamin 66 Date Collected:
(909) 307-9730 Yonan Benjamin Date Received:
yonan@lyenvironmental.com Acceptable Date Analyzed:
Date Amended:
260655-06-1
CS-3 Ceiling (Drywall) - white, brown No
Staff Restroom "Handicap & Closet"
260655-06 Staff Restroom "Handicap & Closet" CS-3 Ceiling (Joint Compound) - white
No
CS-2 Ceiling (Drywall) - white, brown No
260655-05 Staff Restroom "Men"
260655-05-1 Staff Restroom "Men"
CS-2 Ceiling (Joint Compound) - white No
5 5 90
CS-1 Ceiling (Joint Compound) - white No 100
260655-04-1 Staff Restroom "Women"
CS-1 Ceiling (Drywall) - white, brown No 5 5 90
260655-04 Staff Restroom "Women"
L-1 No
Asbestos Type, %
Fiberglass
Crocidolite
2 85
260655-01 Staff Restroom "Women"
Q C
Client Sample ID Inland Sample ID
No
No
260655-02-1 Staff Restroom "Men"
260655-01-1
10 3 85
Sampler: April 8, 2026
Chrysotile
Actinolite
Cellulose
Sample Description - Color Comment
Sample Condition:
Linoleum - brown
10 3
Staff Restroom "Women"
April 9, 2026
Test Report: PLM Bulk Asbestos Analysis Analytical Method: EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials, in conjunction with EPA -- 40
CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples
Project Address: 8650 Oleander Ave., Fontana, CA 92335
Anthophyllite
Am osite
Asbestos Detected
26040655
April 8 & 9, 2026
Number of Samples:
N on-Asbestos N on-Fibrous
Synthetic Fibers
April 7, 2026
Project Name/Number: Oleander E.S. #33, #34 & Staff Restrooms Bldgs., Fontana USD
L-2 Adhesive - yellow No
Trem olite
Non-Asbestos Constituents, %
L-1 Adhesive - yellow
260655-02 Staff Restroom "Men"
L-2 Linoleum - brown
L-3 Linoleum - brown No
260655-03 Staff Restroom "Handicap" L-3 Adhesive - yellow
No 260655-03-1
5 5 90
Staff Restroom "Handicap"
8510 3 2 mailto:info@inlandalab.com
L.Y. Environmental, Inc. Lab Ref. No.:
Yonan Benjamin 66 Date Collected:
(909) 307-9730 Yonan Benjamin Date Received:
yonan@lyenvironmental.com Acceptable Date Analyzed:
Date Amended:
April 9, 2026
No 100
95 5
260655-10 Staff Restroom Bldg Ext. Walls
260655-07 Staff Restroom "Women"; no adhesive present for analysis
WP-2
Wall Panels & Adhesive - gray, brown
No 95 5
260655-08 Staff Restroom "Men"; no adhesive present for analysis
WP-1
Wall Panels & Adhesive - gray, brown
No
Staff Restroom Under E. Wall P-2 Ext. Pipe "Drain" - gray, black
No
260655-09 Staff Restroom "Handicap & Closet";
no adhesive present for analysis
P-1 Ext. Pipe "Drain" - gray, black No 100
260655-13
WP-3
Wall Panels & Adhesive - gray, brown
No
260655-16 Staff Restroom North Ramps
P-3 Ext. Pipe "Drain" - gray, black No
260655-15 Staff Restroom Under E. Wall
260655-14 Staff Restroom Under E. Wall
26040655
Number of Samples: April 7, 2026
Sampler: April 8, 2026
Sample Condition: April 8 & 9, 2026
Project Name/Number: Oleander E.S. #33, #34 & Staff Restrooms Bldgs., Fontana USD Asbestos Type, % Non-Asbestos Constituents, %
Q C
Project Address: 8650 Oleander Ave., Fontana, CA 92335 Asbestos Detected
Chrysotile
Am osite
Crocidolite
Anthophyllite
Trem olite
Actinolite
Cellulose
Fiberglass
Synthetic Fibers
N on-Asbestos N on-Fibrous
FM-3 Ext. Floor Material - black No
260655-18 Staff Restroom North Ramps
Client Sample ID Inland Sample ID
Sample Description - Color Comment
FM-2 Ext. Floor Material - black No 100
260655-17 Staff Restroom North Ramps
15 85 260655-19 Staff Restroom Bldg.
R-1 Roof "Hot Roll Sheet" - black No
FM-1 Ext. Floor Material - black No
Wall Moisture Paper - brown No 100
260655-12 Staff Restroom Bldg Ext. Walls
WMP-1 Wall Moisture Paper - brown
WMP-2 Wall Moisture Paper - brown No 100
260655-11 Staff Restroom Bldg Ext. Walls
WMP-3
(909) 307-9730 Yonan Benjamin Date Received:
yonan@lyenvironmental.com Acceptable Date Analyzed:
Date Amended:
R-2 Roof "Hot Roll Sheet" - black No 15 85
260655-20 Staff Restroom Bldg.
R-3 Roof "Hot Roll Sheet" - black
No 15 85 260655-21 Staff Restroom Bldg.
26040655
Number of Samples: April 7, 2026
Sampler: April 8, 2026
Sample Condition: April 8 & 9, 2026
April 9, 2026
260655-26
PM-1
Roof Penetration Mastic - white, black No
Project Name/Number: Oleander E.S. #33, #34 & Staff Restrooms Bldgs., Fontana USD Asbestos Type, % Non-Asbestos Constituents, %
Q C
Project Address: 8650 Oleander Ave., Fontana, CA 92335 Asbestos Detected
Chrysotile
Am osite
Crocidolite
Anthophyllite
Trem olite
Actinolite
Cellulose
Fiberglass
Synthetic Fibers
N on-Asbestos N on-Fibrous
Client Sample ID Inland Sample ID
Sample Description - Color Comment
Staff Restroom Bldg.
PM-3
Roof Penetration Mastic - white, black No
5 95
15 85
5 95 260655-27 Staff Restroom Bldg.
#34 Bldg
260655-25 Staff Restroom Bldg.
PM-2
Roof Penetration Mastic - white, black No 5 95
5 95 260655-28 #34 Bldg WS-1 Wall (Joint Compound) - white
No 100 260655-28-1
WS-1 Wall (Drywall) - white, brown No
5 95 260655-29 #34 Bldg
#34 Bldg
WS-2 Wall (Drywall) - white, brown No
260655-29-1 #34 Bldg WS-3 Wall (Drywall) - white, brown
No 5 95 260655-30
WS-2 Wall (Joint Compound) - white No
15 85 260655-22 Staff Restroom Bldg.
FP-2 Roof Felt Paper - black
No 15 85 260655-23
FP-1 Roof Felt Paper - black No
260655-24 Staff Restroom Bldg.
Staff Restroom Bldg.
FP-3 Roof Felt Paper - black
No
260655-30-1 #34 Bldg
WS-3 Wall (Joint Compound) - white No
(909) 307-9730 Yonan Benjamin Date Received:
yonan@lyenvironmental.com Acceptable Date Analyzed:
Date Amended:
260655-31-1 #34 Bldg BC-2 Baseboard - black
No 100 260655-32 #34 Bldg
BC-1 Baseboard - black No
No
Project Name/Number: Oleander E.S. #33, #34 & Staff Restrooms Bldgs., Fontana USD Asbestos Type, % Non-Asbestos Constituents, %
Q C
Project Address: 8650 Oleander Ave., Fontana, CA 92335 Asbestos Detected
Chrysotile
Am osite
Crocidolite
Anthophyllite
Trem olite
Actinolite
Cellulose
260655-31 #34 Bldg BC-1 Adhesive - yellow
No
Fiberglass
Synthetic Fibers
N on-Asbestos N on-Fibrous
Client Sample ID Inland Sample ID
Sample Description - Color Comment
#34 Bldg CT-3 2'x4' Ceiling Tile - white, brown
No
10 90
10 90 260655-36 #34 Bldg
#34 Bldg
260655-34 #34 Bldg CT-2 2'x4' Ceiling Tile - white, brown
No 10 90 260655-35
CT-1 2'x4' Ceiling Tile - white, brown
260655-37 #34 Bldg CA-2 Carpet Adhesive - yellow
No 100 260655-38
CA-1 Carpet Adhesive - yellow No
260655-39 #34 Bldg
#33 Bldg. Perimeter Walls
CA-3 Carpet Adhesive - yellow No
5 95 260655-40 #33 Bldg Perimeter Walls WS-4 Wall (Joint Compound) - white
No 100 260655-40-1
WS-4 Wall (Drywall) - white, brown No
5 95 260655-41 #33 Bldg. Perimeter Walls
WS-5 Wall (Drywall) - white, brown No
April 9, 2026
26040655
Number of Samples: April 7, 2026
Sampler: April 8, 2026
Sample Condition: April 8 & 9, 2026
260655-32-1 #34 Bldg BC-3 Baseboard - black
No 100 260655-33
BC-2 Adhesive - yellow No
260655-33-1 #34 Bldg
#34 Bldg BC-3 Adhesive - yellow
(909) 307-9730 Yonan Benjamin Date Received:
yonan@lyenvironmental.com Acceptable Date Analyzed:
Date Amended:
260655-52-1 #33 Bldg. "Perimeters"
WS-6 Wall (Joint Compound) - white No 100
260655-42-1 #33 Bldg Perimeter Walls
WS-6 Wall (Drywall) - white, brown No 5 95
260655-42 #33 Bldg Perimeter Walls
WS-5 Wall (Joint Compound) - white No 100
260655-41-1 #33 Bldg. Perimeter Walls
5 2 93 260655-43 #33 Bldg Partitions "Walls"
BC-4 Adhesive - yellow No
WS-7
Wall (Drywall Panels) - white, brown No
April 9, 2026
26040655
Number of Samples: April 7, 2026
Sampler: April 8, 2026
Sample Condition: April 8 & 9, 2026
Project Name/Number: Oleander E.S. #33, #34 & Staff Restrooms Bldgs., Fontana USD Asbestos Type, % Non-Asbestos Constituents, %
Q C
Project Address: 8650 Oleander Ave., Fontana, CA 92335 Asbestos Detected
Chrysotile
Am osite
Crocidolite
Anthophyllite
Trem olite
Actinolite
Cellulose
Fiberglass
Synthetic Fibers
N on-Asbestos N on-Fibrous
Client Sample ID Inland Sample ID
Sample Description - Color Comment
10 90 260655-48 #33 Bldg
#33 Bldg CT-6 2'x4' Ceiling Tile - white, brown
No
No 10 90
260655-49 #33 Bldg CA-5 Carpet Adhesive - yellow
No 100 260655-50
CA-4 Carpet Adhesive - yellow No
260655-51 #33 Bldg
#33 Bldg CA-6 Carpet Adhesive - yellow
No
260655-52 #33 Bldg. "Perimeters"
BC-4 Baseboard - black No
260655-47
#33 Bldg Partitions "Walls"
CT-5
2'x4' Ceiling Tile - white, brown
5 2 93 260655-44 #33 Bldg Partitions "Walls"
WS-8
Wall (Drywall Panels) - white, brown No
10 90 260655-46 #33 Bldg
2'x4' Ceiling Tile - white, brown
CT-4
5 2 93 260655-45
No
WS-9
Wall (Drywall Panels) - white, brown No
(909) 307-9730 Yonan Benjamin Date Received:
yonan@lyenvironmental.com Acceptable Date Analyzed:
Date Amended:
PA-2 Ext. Asphalt Pavement - black No 5 95
260655-62 Ext. Floor around #33, 34, Restroom
BC-6 Adhesive - yellow No 100
260655-54-1 #33 Bldg. "Perimeters"
260655-53-1 #33 Bldg. "Perimeters" BC-6 Baseboard - black
No 100 260655-54 #33 Bldg. "Perimeters"
BC-5 Baseboard - black No 100
260655-53 #33 Bldg. "Perimeters"
BC-7 Baseboard - black No 100
260655-55 #33 Bldg "Partition Walls"
260655-56-1
BC-8 Baseboard - black No
Project Name/Number: Oleander E.S. #33, #34 & Staff Restrooms Bldgs., Fontana USD Asbestos Type, % Non-Asbestos Constituents, %
Q C
Project Address: 8650 Oleander Ave., Fontana, CA 92335 Asbestos Detected
Chrysotile
Am osite
Crocidolite
BC-5 Adhesive - yellow No
BC-7 Adhesive - yellow No
April 9, 2026
26040655
Number of Samples: April 7, 2026
Sampler: April 8, 2026
Sample Condition: April 8 & 9, 2026
#33 & 34 Bldgs. "Ramps"
260655-56 #33 Bldg "Partition Walls" BC-8 Adhesive - yellow
No 100 #33 Bldg "Partition Walls"
BC-9 Baseboard - black No
BC-9 Adhesive - yellow No
260655-57 #33 Bldg "Partition Walls"
FM-5 Ext. Floor Material - brown No
260655-57-1 #33 Bldg "Partition Walls" FM-4 Ext. Floor Material - brown
No 100 260655-58
260655-61
FM-6 Ext. Floor Material - brown No
260655-59 #33 & 34 Bldgs. "Ramps"
Ext. Floor around #33, 34, Restroom
260655-60 #33 & 34 Bldgs. "Ramps" PA-1 Ext. Asphalt Pavement - black
No 5 95
260655-55-1 #33 Bldg "Partition Walls"
Anthophyllite
Trem olite
Actinolite
Cellulose
Fiberglass
Synthetic Fibers
N on-Asbestos N on-Fibrous
Client Sample ID Inland Sample ID
Sample Description - Color Comment
(909) 307-9730 Yonan Benjamin Date Received:
yonan@lyenvironmental.com Acceptable Date Analyzed:
Date Amended:
BC-11 Baseboard - brown No 100
260655-65 Staff Restroom "Handicap"
BC-10 Adhesive - off-white No 100
260655-64-1 Staff Restroom "Handicap"
BC-10 Baseboard - brown No 100
260655-64 Staff Restroom "Handicap"
PA-3 Ext. Asphalt Pavement - black No 5 95
260655-63 Ext. Floor around #33, 34, Restroom
260655-65-1 Staff Restroom "Handicap"
April 9, 2026
26040655
Number of Samples: April 7, 2026
Sampler: April 8, 2026
Sample Condition: April 8 & 9, 2026
Project Name/Number: Oleander E.S. #33, #34 & Staff Restrooms Bldgs., Fontana USD Asbestos Type, % Non-Asbestos Constituents, %
Q C
Project Address: 8650 Oleander Ave., Fontana, CA 92335 Asbestos Detected
Chrysotile
Am osite
Crocidolite
Anthophyllite
Trem olite
Actinolite
Cellulose
Fiberglass
Synthetic Fibers
N on-Asbestos N on-Fibrous
Client Sample ID Inland Sample ID
Sample Description - Color Comment
BC-11 Adhesive - off-white No
260655-66 Staff Restroom "Handicap" BC-12 Adhesive - off-white
No 100 260655-66-1
BC-12 Baseboard - brown
Staff Restroom "Handicap"
Analyst(s):
Egypt Bailey
April 9, 2026
N/A=not analyzed. The above analyses of the samples were performed in general compliance with the procedures outlined in EPA 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Materials, in conjunction with EPA -- 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples. Non-friable organically bound materials may present a problem matrix, therefore Inland Asbestos Lab, Inc. recommends gravimetric analysis. The client is responsible for interpretation and use of test results. This report relates only to the samples reported above and reflects the samples as received. Sample descriptions are generated from the client's field sampling data on the Chain of Custody. This report may not be reproduced, except in full, without written approval from Inland Asbestos Lab, Inc. and must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. Inland Asbestos Lab, Inc. bears no responsibility for client sample collection activities or analytical method limitations. The limit of detection for this analytical method is less than 1% and total sample constituents may total greater than 100% due to trace amounts. Building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample unless requested otherwise by the client. Inland Asbestos Lab, Inc. is accredited under the NIST/NVLAP (NVLAP Lab Code: 201000-0) program for bulk asbestos analysis using polarized light microscopy. Samples are within quality control criteria and met method specifications unless otherwise noted.
Estimation of uncertainty is available upon request. Please feel free to contact Inland Asbestos Lab, Inc. regarding any questions about this report.
Approved by: Julia Benjamin, Laboratory Director Approved Signatory
Date Sampling: 4/7/2026 Page 1 of 2 Children: Yes Year Built:
SAMPLE # ROOM WALL COMPONENT SUBSTRATE
PAINT
CONDITION
READING RESULT
1 Exterior of Portable Staff Restrooms A Wall Wood Intact 0.00 Negative
2 Exterior of Portable Staff Restrooms B Wall Wood Intact 0.00 Negative
3 Exterior of Portable Staff Restrooms C Wall Wood Intact 0.00 Negative
4 Exterior of Portable Staff Restrooms D Wall Wood Intact 0.00 Negative
5 Exterior of Portable Staff Restrooms Railings/Fallguards Metal Intact 0.00 Negative
6 Exterior of Portable Staff Restrooms Trim/Fascia Metal Intact 0.00 Negative
7 Ext. of Portable Staff Restroom Janitor's Closet Door Metal Intact 0.00 Negative
8 Ext. of Portable Staff Restroom Janitor's Closet Door Jamb Metal Intact 0.00 Negative
9 Ext. of Portable Staff Men's Restroom Door Metal Intact 0.00 Negative
10 Ext. of Portable Staff Men's Restroom Door Jamb Metal Intact 0.00 Negative
11 Ext. of Portable Staff Women's Restroom Door Metal Intact 0.00 Negative
12 Ext. of Portable Staff Women's Restroom Door Jamb Metal Intact 0.00 Negative
13 Interior of Portable Staff Restroom A Wall Drywall Intact 0.00 Negative
14 Interior of Portable Staff Restroom B Wall Drywall Intact 0.00 Negative
15 Interior of Portable Staff Restroom C Wall Drywall Intact 0.00 Negative
16 Interior of Portable Staff Restroom D Wall Drywall Intact 0.00 Negative
17 Interior of Portable Staff Restroom Ceiling Drywall Intact 0.00 Negative
18 Exterior of Portable Classroom 34 A Wall Wood Intact 0.00 Negative
19 Exterior of Portable Classroom 34 B Wall Wood Intact 0.00 Negative
20 Exterior of Portable Classroom 34 C Wall Wood Intact 0.00 Negative
21 Exterior of Portable Classroom 34 D Wall Wood Intact 0.00 Negative
22 Exterior of Portable Classroom 34 Railings/Fallguards Metal Intact 0.00 Negative
23 Exterior of Portable Classroom 34 Trim/Fascia Metal Intact 0.00 Negative
24 Exterior of Portable Classroom 34 Door Metal Intact 0.00 Negative
25 Exterior of Portable Classroom 34 Door Jamb Metal Intact 0.00 Negative
26 Exterior of Portable Classroom 34 Window Cage Metal Intact 0.00 Negative
27 Interior of Portable Classroom 34 A Wall Drywall Intact 0.00 Negative
28 Interior of Portable Classroom 34 B Wall Drywall Intact 0.00 Negative
29 Interior of Portable Classroom 34 C Wall Drywall Intact 0.00 Negative
Lead Inspection Sampling Log Oleander Elementary School - 8650 Oleander Ave, Fontana, CA 92335
Date Sampling: 4/7/2025 Page 2 of 2 Children: Yes Year Built:
SAMPLE # ROOM WALL COMPONENT SUBSTRATE
PAINT
CONDITION
READING RESULT
30 Interior of Portable Classroom 34 D Wall Drywall Intact 0.00 Negative
31 Interior of Portable Classroom 34 Ceiling Ceiling Tile Intact 0.00 Negative
32 Exterior of Portable Classroom 33 A Wall Wood Intact 0.00 Negative
33 Exterior of Portable Classroom 33 B Wall Wood Intact 0.00 Negative
34 Exterior of Portable Classroom 33 C Wall Wood Intact 0.00 Negative
35 Exterior of Portable Classroom 33 D Wall Wood Intact 0.00 Negative
36 Exterior of Portable Classroom 33 Railings/Fallguards Metal Intact 0.00 Negative
37 Exterior of Portable Classroom 33 Trim/Fascia Metal Intact 0.00 Negative
38 Exterior of Portable Classroom 33 Door Metal Intact 0.00 Negative
39 Exterior of Portable Classroom 33 Door Jamb Metal Intact 0.00 Negative
40 Exterior of Portable Classroom 33 Window Cage Metal Intact 0.00 Negative
41 Interior of Portable Classroom 33 A Wall Drywall Intact 0.00 Negative
42 Interior of Portable Classroom 33 B Wall Drywall Intact 0.00 Negative
43 Interior of Portable Classroom 33 C Wall Drywall Intact 0.00 Negative
44 Interior of Portable Classroom 33 D Wall Drywall Intact 0.00 Negative
45 Interior of Portable Classroom 33 Ceiling Ceiling Tile Intact 0.00 Negative
Lead Inspection Sampling Log Oleander Elementary School - 8650 Oleander Ave, Fontana, CA 92335