CMS-CAO_PV-PRO-DOCS_DRAWINGS_Issue-for-Bid.pdf
PDF 6 MB Posted
- Attached to
- Bids for Photovoltaic System
- Solicitation number
- 35523
- Issued by
- Middlesex County, Connecticut
About this file
Summary of Photovoltaic System Procurement Documents
This is a set of architectural and electrical drawings and project documentation for a photovoltaic system installation at Cromwell Middle School (State Project #033-0055-N) and Central Administration Office (State Project #033-0056-BE) in Cromwell, Connecticut, managed by Newfield Construction on behalf of the Town of Cromwell. The project represents Phase 4 of 4 for a comprehensive photovoltaic system installation across multiple building rooftops. The scope includes four distinct photovoltaic arrays totaling approximately 399.75 kW DC capacity: Array #1 (105.3 kW), Array #2 (147.6 kW), Arrays #3 and #4 combined (91.85 kW). The system utilizes REC Alpha 72 Series solar modules rated at 450W, SolarEdge power optimizers, and four SolarEdge inverters (two SE110KUS units rated at 110 kW each and two SE80KUS units rated at 80 kW each). Sealed proposals for Bid Package 4.01 Photovoltaic System must be submitted to Newfield Construction at the Town of Cromwell address by 2:00 PM prevailing time on April 15, 2026. The procurement documents include detailed electrical plans, riser diagrams, roof mounting specifications, and conduit routing requirements across multiple drawing sheets.
The system design incorporates advanced electrical infrastructure with voltage drop limitations of 3 percent, 1000-volt rated DC wiring and equipment, and comprehensive grounding requirements throughout. All PV modules and power optimizers carry 25-year warranties, and all inverters meet UL1741 standards with automatic disconnect capabilities and rapid shutdown equipment. The installation requires coordination with multiple design disciplines including structural engineers, MEP consultants (DeSimone Consulting Engineers), and IT representatives for production reporting via SolarEdge monitoring systems. The project must comply with the 2022 Connecticut State Building Code, 2021 International Building Code, 2020 NFPA 70 National Electrical Code, and applicable Connecticut fire codes. Significant attention is paid to roof protection and compatibility, with specifications requiring pressure-sensitive molded walkway pads beneath ballast racks and coordination with the TPO roofing system to maintain manufacturer warranty compliance. Contractor must demonstrate conformity with roofing warranty requirements for the complete PV array installation.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. ASSEMBLIES, ITEMS AND CONDITIONS DETAILED OR OTHERWISE IDENTIFIED ON ONE DRAWING ARE APPLICABLE AND BINDING FOR IDENTICAL OR SIMILAR CONDITIONS ON ALL OTHER DRAWINGS.
2. THE SCOPE OF WORK IS DEFINED IN THE DRAWINGS AND SPECIFICATIONS; REFERENCE TO BOTH IS
REQUIRED.
3. ALL CONSTRUCTION AND WORK SHOWN ON THE COMPLETE SET OF DOCUMENTS (DRAWINGS AND
SPECIFICATIONS) IS ASSUMED TO BE NEW AND TO BE FURNISHED AND INSTALLED BY THE
CONTRACTOR, UNLESS SPECIFICALLY NOTED OTHERWISE.
4. IF A CONFLICT EXISTS WITHIN THE DOCUMENTS, THE MORE STRINGENT AND MORE COSTLY
REQUIREMENT SHALL BE ENFORCED. IF AN ITEM IS SHOWN ON THE DRAWINGS BUT NOT SPECIFIED, THE CONTRACTOR SHALL PROVIDE THE ITEM AS SHOWN, SUBJECT TO SUBMITTAL REQUIREMENTS.
CONFLICTS BETWEEN THE DRAWINGS AND SPECIFICATIONS SHOULD IMMEDIATELY BE REFERRED TO
THE ARCHITECT FOR CLARIFICATION.
5. IF A CONFLICT EXISTS BETWEEN DRAWINGS OF DIFFERENT SCALES, CONSULT THE ARCHITECT FOR
CLARIFICATION.
6. THE CONTRACTOR SHALL NOT SCALE THE DRAWINGS. WHERE A DIMENSION IS MISSING OR CANNOT
BE DETERMINED MATHEMATICALLY, CONSULT THE ARCHITECT FOR CLARIFICATION.
7. ALL DIMENSIONS ARE FINISH TO FINISH, UNLESS NOTED OTHERWISE.
8. SPACES SHOWN BUT NOT NOTED, WHICH ARE SUBSTANTIALLY SIMILAR IN USE TO SPACES NOTED AS
TYPICAL, SHALL BE CONSTRUCTED WITH THE SAME MATERIALS AND FINISHES AS THE TYPICAL
SPACE.
9. SECTIONS ILLUSTRATED ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE
REFERENCED AS WELL AS TO ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR SIMILAR
ASSEMBLIES THROUGHOUT THE PROJECT FOR WHICH SECTIONS HAVE NOT BEEN PROVIDED.
10. DETAILS NOTED AS TYPICAL SHALL APPLY TO ALL APPROPRIATE CONDITIONS EVEN IF NOT
SPECIFICALLY REFERENCED.
11. FOR WALL, FLOOR AND ROOF PENETRATIONS, SEE ELECTRICAL DRAWINGS FOR EXTENT AND
LOCATIONS. PROVIDE ALL SLEEVES, LINTELS AND SEALANTS FOR ALL WALL PENETRATIONS.
12. THE CONTRACT DOCUMENTS ARE COMPLIMENTARY; WORK FROM ALL TRADES AND DISCIPLINES SHALL BE COORDINATED BY THE CONSTRUCTION MANAGER. THE OWNER AND ARCHITECT SHALL BE
NOTIFIED IMMEDIATELY OF ANY APPARENT CONFLICTS.
13. ALL PRODUCTS AND SYSTEMS DESIGNATED AS A PARTICULAR MANUFACTURER OR BRAND SHALL
BE UNDERSTOOD AS A BASIS OF DESIGN, NOT A SOLE-SOURCE PRODUCT OR SYSTEM.
GENERAL PROJECT NOTES
PROJECT No.
Construction Manager:Owner: Civil / Site: Structural: MEP-FP:Landscape: IT/Telcom/Security: Food Service:
860-830-6548 860-953-1477 203-271-1773 860-678-0669 230-495-8270 860-632-1682 203-539-6164 203-972-1605
STATE PROJECT No: 033-0055-N & 033-0056-BE
95550.00
01/16/2026PHOTOVOLTAIC SYSTEM PROCUREMENT DOCUMENTS
CROMWELL MIDDLE SCHOOL & CENTRAL ADMINISTRATION OFFICE
STATE PROJECT #033-0055-N & 033-0056-BE (PHASE 4 OF 4)
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
CES
811 Middle Street, Middletown, CT 06457
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities
International
137 Elm Place, New Canaan, CT 06840
The Town of Cromwell Newfield Construction
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
LOCATION MAP
M A
IN
S
T
GEER ST.
S H
U N
P
IK
E R
D
C R
O M
W E
L L
A V
E
COURT ST.
C O
N N
E C
T
IC
U T
R
IV
E R
CROMWELL
MIDDLE
SCHOOL
16. BUILDING AREAS FOR GRANT CALCULATION (ENTIRE FACILITY)
BUILDING AREA (EACH FLOOR)
(AREA CALCULATED FROM INSIDE FACE OF EXTERIOR WALLS, AREA INCLUDES
HORIZONTAL PROJECTIONS)
BUILDING 1 BUILDING 2 BUILDING 3
LEVEL:
FIRST FLR 63,805 SF 11,916 SF 5,166 SF
SECOND FLR 0 SF 11,891 SF 0 SF
SUB-TOTAL63,805 SF 23,807 SF 5,166 SF
AREAS UNDER PROJECTIONS:
FIRST FLR 87 SF
TOTAL: 63,805 SF 23,894 SF 5,166 SF
GRAND TOTAL: 92,865 SF
CODE INFO
APPLICABLE CODES
2022 STATE BUILDING CODE - STATE OF CONNECTICUT
2021 INTERNATIONAL BUILDING CODE
2021 INTERNATIONAL MECHANICAL CODE
2021 INTERNATIONAL PLUMBING CODE
2021 INTERNATIONAL ENERGY CONSERVATION CODE
2021 INTERNATIONAL EXISTING BUILDING CODE
2018 CONNECTICUT STATE FIRE SAFETY CODE
2015 INTERNATIONAL FIRE CODE
2015 NFPA 101 LIFE SAFETY CODE
2015 CONNECTICUT FIRE PREVENTION CODE
2015 NFPA 1 FIRE CODE
2020 NFPA 70 NATIONAL ELECTRICAL CODE
2017 ICC / ANSI A117.1 ACCESSIBLE AND USABLE BUILDING AND FACILITIES
AMERICANS WITH DISABILITIES ACT OF 2010
LOCAL FIRE DEPARTEMNT/FIRE MARSHAL
ALL OTHER AUTHORITIES HAVING JURISDICTION
REFERENCE STANDARDS:
2013 NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
2013 NFPA 14 - STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS
2013 NFPA 20 - STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION
2015 NFPA 54 - NATIONAL FUEL GAS CODE
2013 NFPA 72 - NATIONAL FIRE ALARM AND SIGNALING CODE
DRAWING LIST
GENERAL:
G-000 COVER SHEET
SITE SOLAR PV:
SU-101 SITE UTILITY PHOTOVOLTAIC PLAN
ARCHITECTURAL:
A-104 OVERALL ROOF PLAN - PV SYSTEM
ELECTRICAL:
E-001 ELECTRICAL ABBREVIATIONS, NOTES, SYMBOLS, AND SCHEDULES
EP-113a ELECTRICAL SOLAR ROOF PLAN - AREA A EP-113b ELECTRICAL SOLAR ROOF PLAN - AREA B EP-113c ELECTRICAL SOLAR ROOF PLAN - AREA C EP-113d ELECTRICAL SOLAR ROOF PLAN - AREA D
E-505 ELECTRICAL DETAILS
E-506 ELECTRICAL DETAILS
ELECTRICAL SERVICE ENTRANCE
WITH TRANSITION TO
UNDERGROUND
UTILITY
PRIMARY
PULLBOX
UTILITY
PRIMARY
PULLBOX
APPROXIMATE
LOCATION OF THE
MAIN ELECTRICAL
ROOM 142 ON THE
FIRST FLOOR.
PRIMARY
CONDUITS
PRIMARY
CONDUITS
PRIMARY
CONDUITS
CONDUITS ENCASED
IN CONCRETE AT
THIS LOCATION
SECONDARY
CONDUITS
UTILITY TRANSFORMER
LOCATION OF THE
GENERATOR
GENERATOR FEEDER AND
CONTROL BURIED CONDUITS.
ALL HALF-TONED ITEMS ARE PART OF
AN EARLIER PHASE
REPRESENTS THE BUILDING
EXTERIOR VIEWS OF THE
MAIN ELECTRICAL ROOM.
REFER TO 2&3/SU-101 FOR
MORE INFORMATION.
LEVEL 0
-2' - 0"
LEVEL 2
12' - 7 3/4"
ROOF LEVEL
28' - 4 1/8"
LEVEL 1
0' - 0"
LEVEL 1 T.O. STL.
14' - 8"
9 10 11 12 13 14
EXISTING UTILITY METER.
METER #: 038129692
ACCOUNT #: 5169 336 0182
EXISTING
EXTERIOR
RECEPTACLE.
EXISTING EXTERIOR
SPEAKER STROBE.
EXISTING EXTERIOR
FIRE ALARM BELL.
600A/500AF, LEVER OPERATED,
FUSED DISCONNECT SWITCH. REFER
TO E-505 FOR MORE INFORMATION.
13 TERMINAL SOCKET PRODUCTION METER
WITH TEST SWITCH. REFER TO E-505 FOR
MORE INFORMATION.
METER #: TBD
ACCOUNT #: TBD
METERING TRANSFORMER
ENCLOSURE. REFER TO E-505 FOR
MORE INFORMATION.
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
As indicated
/1
/2
:0 :4
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
SITE UTILITY
PHOTOVOLTAIC
PLAN
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
SU-101
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
1" = 50'-0"
SITE UTILITY PHOTOVOLTAIC PLAN
1/8" = 1'-0"
MAIN ELECTRICAL ROOM 142 - EXTERIOR ELEVATION
MAIN ELECTRICAL ROOM 142 EXTERIOR - 3D VIEW
No. Description Date
1 Addendum #1 12/07/2023
4 Addendum #5 01/5/2024
5 Issued for Construction 01/22/2024
12 Bulletin #1 07/23/2024
15 Bulletin #4 10/17/2024
W /D
A T
S
A T
S
E
E
E
E
E
E
E
E
E
E E
E
E
E
E
E
SB
SB
SB
AB
AD
AE
AF
AI
AG
BF
BA
AC
BH
BM
BN
BK
BL
BJ
BO
BP
M
N
14 8
CC
F
I I
D
H
JJ
L
23.1
23.1
T
S
Y
Z Z
V
AA
AA
A
BQ
J.1
F.1
B
X
Q
U
P
7 6 4 2
R.1
O
19.1
19.1
AC.1
K
W
16.17.17.2
BI
BD
41.1
BC
BE
25.1
25.1
R.2
BG
E
G
16.216.818.318.8
18.9
18.9 15.1
43.1
EXISTING WALK PADS
NEW WALK PADS
003-0056 BE CENTRAL
ADMINISTION OFFICE
PROJECT
GENERAL NOTES:
1. PROVIDE PRESSURE-SENSITIVE MOLDED WALKWAY PADS
COMPATIBLE WITH EXISTING ROOFING SYSTEM BENEATH
BALLAST RACKS.
ROOF TIE-OFF
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
1/16" = 1'-0"
/1
/2
:0 :2
A
M c re v it l o c a l\ C ro m w e ll_
R
A
R C
H j.
c u lo tt a T
Z V
X Y
.r v t
OVERALL ROOF
PLAN - PV SYSTEM
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
01/16/2026
A-104
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PROCUREMENT DOCUMENTS
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
CES
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
No. Description Date
1/16" = 1'-0"
OVERALL ROOF PLAN - PV SYSTEM
INVERTER SCHEDULE
GENERAL SOLAR PV NOTES
PV SOURCE CIRCUIT NOTE
PV MODULE SCHEDULE
PV SYSTEM DESIGN CRITERIA
1. VOLTAGE DROP SHALL BE LIMITED TO 3% BETWEEN INVERTER(S) AND THE EXTERIOR AC
DISCONNECT.
2. ALL WIRING SHALL BE COPPER.
3. THE CONTRACTOR SHALL PROVIDE PROOF OF CONFORMITY TO THE ROOF WARRANTY
AS IT PERTAINS TO THE PV ARRAY IN ITS ENTIRETY.
4. ANY DEVIATION FROM THE BASIS OF DESIGN SHALL REQUIRE A REDESIGN OF THE
SYSTEM BY THE CONTRACTOR AS STIPULATED IN SPECIFICATIONS.
5. ALL DC WIRING AND EQUIPMENT SHALL BE 1000 VOLT RATED
6. EACH POWER OPTIMIZER SERIAL NUMBER SHALL BE RECORD AND ITS PHYSICAL
LOCATION SAVED WITHIN THE OWNER'S DOCUMENTATION AND AS-BUILT DRAWINGS.
THESE DRAWINGS ARE DIAGRAMMATIC TO SHOW MODULES CONNECTED TO
POWER OPTIMIZERS CONNECTED IN SERIES TO INVERTERS. PROVIDE
POSITIVE/NEGATIVE STRING CONDUCTORS. ROOF MOUNTED DC WIRING SHALL
ADHERE, IN INTENT, TO THE ROUTING SHOWN ON PLANS. FINAL ROOF MOUNTED
PV ARRAY AND CONDUIT CONFIGURATION AND ROUTING SHALL BE FULLY
COORDINATED WITH ALL OTHER INSTALLERS, BUILDING OWNERS, ARCHITECTS
AND ENGINEERS.
REC ALPHA 72 SERIES
REC450AA 72
Voc Vmp Imp IscPmax(STC)
450W
LOCATION
ROOF
MANUFACTURER
& MODEL
MANUFACTURER
& MODEL
OUTPUT
CURRENT
OUTPUT
POWER
MPPTV WARRANTY
SOLAR EDGE
SE80KUS
96.5A 80KW 1000V 25 YEARS
DESIGN CODE: 2021 INTERNATIONAL BUILDING CODE
DESIGN WIND SPEED PER ATC: 140 MPH
WIND EXPOSURE: C
RISK CATEGORY: III
GROUND SNOW LOAD: 30 PSF
53.2V 46.3V 9.72A 10.43A
INVERTER
NUMBERS
INV-3, INV-4
OPTIMIZER
SOLAR EDGE
P1101
SUPPLEMENTARY PV SYMBOLS LIST
PV MODULE MOUNTED TO RACKING SYSTEM AND CONNECTED TO
INVERTER AS NOTED.
NOTES:SYMBOLS
PHOTOVOLTAIC SYSTEM DC CIRCUIT: SHOWN TO DEPICT STRING
CONFIGURATION. LINES SHOWN UNDER PV MODULE, DESIGNATES THAT
THE MODULE IS WIRED, IN SERIES, VIA POWER OPTIMIZER, TO THE
DESIGNATED STRING AND INVERTER. PV MODULE SHALL BE CIRCUITED
PER THE PV RISER DIAGRAM DETAIL ON SHEET E-505 AND PER
SOLAREDGE REQUIREMENTS.
#, INV-#
INVERTER INPUT CIRCUIT: SHOWN TO DEPICT STRING & INVERTER WIRING
CONFIGURATION. SYMBOL INDICATES DESIGNATED STRING NUMBER AND
INVERTER NUMBER. EACH INVERTER SHALL BE CONNECTED TO SPECIFIED
NUMBER OF STRINGS AS INDICATED ON PLANS. PROVIDE EQUIPMENT FOR
STRING CONFIGURATION PER SOLAREDGE REQUIREMENTS.
INV-#
WALL MOUNTED THREE-PHASE PV INVERTER COMPRISED OF (1) SYNERGY
MANAGER AND (2) SYNERGY UNITS.
SOLAR EDGE
SE110KUS 144.75A 110KW 1000V 25 YEARSINV-1, INV-2
SOLAR EDGE
P1101 (FOR INV-2)
P960 (FOR INV-1)
1. MODULE ATTRIBUTES:
A. DIMENSIONS: 81.2"x40.0"x1.18"
B. WEIGHT: 52 LBS
C. FRONT SIDE EFFICIENCY: 21.3%
NOTE: ELECTRICAL STATISTICS ARE BASED ON STANDARD TEST CONDITIONS
(STC).
2. PV MODULES SHALL HAVE A 25 YEAR WARRANTY.
1. INVERTERS MEET UL1741 STANDARD AND PROVIDES AUTOMATIC DISCONNECT/ISOLATION FROM
THE UTILITY COMPANY WHEN UTILITY POWER IS LOST.
2. ALL INVERTERS EQUIPPED WITH RAPID SHUT-DOWN EQUIPMENT TO CONTROL ALL PV ARRAYS
AS REQUIRED.
3. REFER TO PANEL SCHEDULES AND DIAGRAMS FOR INVERTER CONNECTIONS TO SOURCE
PANELS. REFER TO PHOTOVOLTAIC PLANS FOR STRINING AND MODULE QUANTITIES.
4. PROVIDE SURGE SURPRESSION DEVICES ON ALL AC INVERTER CIRCUITS AND DC CONNECTED
CIRCUITS AS INDICATED.
5. POWER OPTIMIZERS SHALL HAVE A 25 YEAR WARRANTY.
ROOF TIE OF ANCHOR. SHOWN FOR REFERENCE ONLY.
ELECTRICAL ABBREVIATIONS
AMPERE
ALTERNATING CURRENT
FRAME AMPERAGE
ARC FAULT CIRCUIT INTERRUPTER
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPS INTERRUPTING CURRENT
ALUMINUM
TRIP AMPERAGE
AUTOMATIC TRANSFER SWITCH
AMERICAL WIRE GAUGE
BASEMENT
CONDUIT
CABLE TELEVISION
CIRCUIT BREAKER
CIRCUIT
COMPRESSOR
CONDENSATE PUMP
CURRENT TRANSFORMER
CONDENSING UNIT OR COPPER
CABINET UNIT HEATER
DRYER
DEGREE
DIAMETER
DOWN
DRAWING
EXISTING TO REMAIN
EXHAUST FAN
ELECTRICAL
ELEVATOR
EMERGENCY
ELECTRIC METALLIC TUBING
EMERGENCY PANEL
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FAHRENHEIT
FIRE ALARM
FIRE ALARM CONTROL PANEL
FOOT CANDLE
FAN COIL UNIT
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
HORSE POWER
HIGH PRESSURE SODIUM
HOUR
HERTZ
ISOLATED GROUND
INCHES
JUNCTION BOX
THOUSAND CIRCULAR MILS
KILOVOLT AMPERE
KILOWATT
MAXIMUM
MAKE-UP AIR UNIT
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOLDED CASE CIRCUIT BREAKER
MAIN FUSE
METAL HALIDE OR MANHOLE
MINIMUM
MAIN LUGS ONLY
NOT APPLICABLE
NEW DEVICE INSTALLED IN SAME LOCATION AS EXISTING REMOVED DEVICE
NATIONAL ELECTRIC CODE
NOT IN CONTRACT
NEW LOCATION OF RELOCATED DEVICE
NEW TO REPLACE EXISTING
NOT TO SCALE
POLE
PRIMARY ELECTRIC SERVCE
POWER FACTOR
PHASE
PANEL
POLYVINYL CHLORIDE CONDUIT
EXISTING TO BE REMOVED
REFRIGERATOR
RIGID GALVANIZED STEEL CONDUIT
EXISTING TO BE RELOCATED
ROOM
EXISTING TO BE REMOVED AND REPLACED WITH NEW (EXISTING
BACKBOXES, CONDUIT AND WIRING TO REMAIN)
EXISTING TO BE RELOCATED IN SAME LOCATION ON NEW SURFACE
ROOFTOP UNIT
SECONDARY ELECTRICAL SERVICE
SPECIFICATION
SWITCHBOARD
SURGE PROTECTION DEVICE
TELECOMMUNICATIONS/TELEPHONE
TELEVISION
TRANSFORMER
TYPICAL
UNIT HEATER
UNLESS OTHERWISE NOTED
VOLTS
VOLT AMPERE
VOLTS ALTERNATING CURRENT
VERIFY IN FIELD
WATT OR WIRE
WASHER
WIRE GUARD
WEATHERPROOF
A/AMP
AC
AF
AFCI
ACU
AFF
AFG
AHU
AIC
AL
AT
ATS
AWG
BSMT
C
CATV
C/B
CKT
COMP
CP
CT
CU
CUH
D
DEG.
DIA
DN
DWG
ETR
EF
ELEC
ELEV
EM
EMT
EP
EUH
EWC
EWH
F
FA
FACP
FC
FCU
G
GFCI
HP
HPS
HR
HZ
IG
IN
JB
KCMIL
KVA
KW
MAX
MAU
MCB
MCC
MCCB
MF
MH
MIN
MLO
NA
NE
NEC
NIC
NL
NR
NTS
P
PE
PF
PH
PNL
PVC
RE
REF
RGS
RL
RM
RN
RR
RTU
SE
SPEC
SWBD
SPD
TELE
TV
T/TX
TYP
UH
UON
V
VA
VAC
VIF
W
WA
WG
WP
ELECTRICAL SYMBOLS
SYMBOL DESCRIPTION
DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
SURFACE MOUNTED PANELBOARD
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
As indicated
/1
/2
:0 :3
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
ELECTRICAL
ABBREVIATIONS,
NOTES, SYMBOLS,
AND SCHEDULES
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
E-001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
No. Description Date
2 Addendum #2 12/14/2023
3 Addendum #3 12/20/2023
5 Issued for Construction 01/22/2024
43.1
444546
AI
AH
AG
AF
AE
AD
AB
ACAC.1
27 26
25.1 25
23.1 23
2241.1
BA
BB
BC
BD
A
B
C
D
E
F
F.1
G
H
I
J
J.1
K
L
M
APPROXIMATE LOCATION OF 3" SOLAR
PHOTOVOLTAIC CONDUIT STUB-UP.
CAP AND SEAL CONDUITS TO PREVENT
WATER INTRUSION.
NO PHOTOVOLTAIC
SCOPE IN THIS AREA.
9, INV-2
1, INV-1
2, INV-1
3, INV-1
4, INV-1
5, INV-1
6, INV-1
7,INV-1
PV1
PV6
PV7
PV9
PV7
PV9
ROOF DRAIN. SHOWN
FOR REFERENCE
ONLY (TYPICAL).
APPROXIMATE LOCATION
OF ROOF TIE OFF ANCHOR.
SHOWN FOR REFERENCE
ONLY (TYPICAL).
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
1/8" = 1'-0"
/1
/2
:0 :4
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
ELECTRICAL SOLAR
ROOF PLAN - AREA A
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
EP-113a
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
1/8" = 1'-0"
ELECTRICAL PHOTOVOLTAIC ROOF PLAN - AREA A
KEYNOTES - PHOTOVOLTAIC
Key Value Keynote Text
PV1 PV ARRAY #1 - AREA A: 105.3KW/DC PV ARRAY CONSISTING OF PV MODULES, POWER OPTIMIZERS, RACKING, BALLAST, BALANCE OF SYSTEM COMPONENTS, ETC. REFER TO E-505 & E-506 FOR MORE INFORMATION.
PV6 PROVIDE CONTINUATION OF ROOF MOUNTED IMC CONDUIT/FEEDERS TO PV ARRAY STRINGS.
PV7 ROOF MOUNTED HIGH VOLTAGE DC WIRING (1000V RATED DC WIRING) IN IMC CONDUIT, PROVIDE MOUNTED TO CONDUIT ROOF SUPPORTS PER ROOFING MANUFACTURER'S REQUIREMENTS. REFER TO INVERTER MOUNTING DETAILS ON SHEET E-506 FOR MORE INFORMATION ON ROOF SUPPORTS. PROVIDE PV WARNING LABELS. REFER
TO ADJACENT ROOF AREA FOR CONTINUATION.
PV9 PROVIDE CONTINUATION OF ROOF/WALL MOUNTED IMC CONDUIT/FEEDERS TO INVERTERS.
No. Description Date
43.1
BQ
BO
BN
BM
BL
BK
BH
AI
AH
AG
27 26
25.1 25
24 23.1 41.1 41 40 21
BA
BB
BC
BD
BE
BF
BG
BI
BJ
K
L
M
N
O
P
Q
R
R.2
S
T
U
V
W
X
Y
INV-1
INV-2
NO PHOTOVOLTAIC SCOPE IN
THIS AREA.
1, INV-2
2, INV-2
3, INV-2
4, INV-2
5, INV-2
6, INV-2
7, INV-2
8, INV-2
9, INV-2
1, INV-1
REFER TO 1/E-506 FOR MORE
INFORMATION. COORDINATE
MOUNTING OF INVERTERS WITH
THE OWNER AND ENGINEER
PRIOR TO ROUGH-IN.
PV9
PROVIDE 2" CONDUIT
DOWN TO THE
INTERIOR OF THE
BUILDING FOR THE
ROUTING OF RS485
CABLING TO DATA
ROOM D146.
PV10
PV7
PV2
PV6
PV9
ROOF DRAIN. SHOWN
FOR REFERENCE
ONLY (TYPICAL).
ROOF DRAIN. SHOWN
FOR REFERENCE
ONLY (TYPICAL).
APPROXIMATE LOCATION OF ROOF
TIE OFF ANCHOR. SHOWN FOR
REFERENCE ONLY (TYPICAL).
APPROXIMATE LOCATION OF DATA
ROOM D130. ON THE FIRST FLOOR.
SHOWN FOR COORDINATION AND
REFERENCE ONLY.
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
1/8" = 1'-0"
/1
/2
:0 :4
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
ELECTRICAL SOLAR
ROOF PLAN - AREA B
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
EP-113b
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
1/8" = 1'-0"
ELECTRICAL PHOTOVOLTAIC ROOF PLAN - AREA B
KEYNOTES - PHOTOVOLTAIC
Key Value Keynote Text
PV2 PV ARRAY #2 - AREA B: 147.6KW/DC PV ARRAY CONSISTING OF PV MODULES, POWER OPTIMIZERS, RACKING, BALLAST, BALANCE OF SYSTEM COMPONENTS, ETC. REFER TO E-505 & E-506 FOR MORE INFORMATION.
PV6 PROVIDE CONTINUATION OF ROOF MOUNTED IMC CONDUIT/FEEDERS TO PV ARRAY STRINGS.
PV7 ROOF MOUNTED HIGH VOLTAGE DC WIRING (1000V RATED DC WIRING) IN IMC CONDUIT, PROVIDE MOUNTED TO CONDUIT ROOF SUPPORTS PER ROOFING MANUFACTURER'S REQUIREMENTS. REFER TO INVERTER MOUNTING DETAILS ON SHEET E-506 FOR MORE INFORMATION ON ROOF SUPPORTS. PROVIDE PV WARNING LABELS. REFER
TO ADJACENT ROOF AREA FOR CONTINUATION.
PV9 PROVIDE CONTINUATION OF ROOF/WALL MOUNTED IMC CONDUIT/FEEDERS TO INVERTERS.
PV10 PROVIDE CONTINUATION OF ROOF/WALL MOUNTED IMC CONDUIT AND FEEDERS FROM INVERTERS TO PANEL "PVP." REFER TO PHOTOVOLTAIC SYSTEM RISER DIAGRAM ON SHEET E-505 FOR MORE INFORMATION.
1234566.177.17.28910111213141516
171818.91919.1
BC
BD
BE
BF
BG
BI
L
M
N
O
P
Q
R
R.2
S
T
U
V
W
X
Y
APPROXIMATE LOCATION OF 3"
SOLAR PHOTOVOLTAIC CONDUIT
STUB-UP. CAP AND SEAL
CONDUITS TO PREVENT WATER
INTRUSION.
INV-4 INV-3
3, INV-3
4, INV-3
1, INV-4
1, INV-3
2, INV-3
NO PHOTOVOLTAIC SCOPE IN THIS AREA.
APPROXIMATE LOCATION OF
MAIN ELECTRICAL ROOM 142
ON THE FIRST FLOOR.
SHOWN FOR COORDINATION
AND REFERENCE ONLY.
REFER TO 2/E-506 FOR
MORE INFORMATION.
COORDINATE MOUNTING OF
INVERTERS WITH THE
OWNER AND ENGINEER
PRIOR TO ROUGH-IN.
PV7
PV3
PV4
PV8
PV7
PV9
PV6
PV7
PV6
PV7
PROVIDE 2" CONDUIT DOWN TO
THE INTERIOR OF THE BUILDING
FOR THE ROUTING OF RS485
CABLING TO DATA ROOM D130.
PVP
PV10
PV8
ROOF DRAIN. SHOWN
FOR REFERENCE
ONLY (TYPICAL).
APPROXIMATE LOCATION OF ROOF TIE OFF ANCHOR.
SHOWN FOR REFERENCE ONLY (TYPICAL).
APPROXIMATE LOCATION OF
DATA ROOM D130. ON THE
FIRST FLOOR. SHOWN FOR
COORDINATION AND
REFERENCE ONLY.
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
1/8" = 1'-0"
/1
/2
:0 :4
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
ELECTRICAL SOLAR
ROOF PLAN - AREA C
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
EP-113c
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
1/8" = 1'-0"
ELECTRICAL PHOTOVOLTAIC ROOF PLAN - AREA C
KEYNOTES - PHOTOVOLTAIC
Key Value Keynote Text
PV3 PV ARRAY #3 - AREA C1: 32.4KW/DC PV ARRAY CONSISTING OF PV MODULES, POWER OPTIMIZERS, RACKING, BALLAST, BALANCE OF SYSTEM COMPONENTS, ETC. REFER TO E-505 & E-506 FOR MORE INFORMATION.
PV4 PV ARRAY #3 CONT. - AREA C2: 59.4KW/DC PV ARRAY CONSISTING OF PV MODULES, POWER OPTIMIZERS, RACKING, BALLAST, BALANCE OF SYSTEM COMPONENTS, ETC. REFER TO E-505 & E-506 FOR MORE
INFORMATION.
PV6 PROVIDE CONTINUATION OF ROOF MOUNTED IMC CONDUIT/FEEDERS TO PV ARRAY STRINGS.
PV7 ROOF MOUNTED HIGH VOLTAGE DC WIRING (1000V RATED DC WIRING) IN IMC CONDUIT, PROVIDE MOUNTED TO CONDUIT ROOF SUPPORTS PER ROOFING MANUFACTURER'S REQUIREMENTS. REFER TO INVERTER MOUNTING DETAILS ON SHEET E-506 FOR MORE INFORMATION ON ROOF SUPPORTS. PROVIDE PV WARNING LABELS. REFER
TO ADJACENT ROOF AREA FOR CONTINUATION.
PV8 WALL MOUNTED HIGH VOLTAGE DC WIRING (1000V RATED DC WIRING) IN IMC CONDUIT. PROVIDE PV WARNING
LABELS.
PV9 PROVIDE CONTINUATION OF ROOF/WALL MOUNTED IMC CONDUIT/FEEDERS TO INVERTERS.
PV10 PROVIDE CONTINUATION OF ROOF/WALL MOUNTED IMC CONDUIT AND FEEDERS FROM INVERTERS TO PANEL "PVP." REFER TO PHOTOVOLTAIC SYSTEM RISER DIAGRAM ON SHEET E-505 FOR MORE INFORMATION.
7.289101112131415161818.91919.1
AI
AH
BA
BB
A
B
18.3 16.8 16.2 15.1 13.8 11.8 8.1
C
D
E
F
F.1
G
H
I
J
J.1
K
L
NO PHOTOVOLTAIC SCOPE IN THIS AREA.
PV5
PV8
2, INV-4
3, INV-4
4, INV-4
5, INV-4
PV8
PV6
PV7
ROOF DRAIN. SHOWN
FOR REFERENCE
ONLY (TYPICAL).
APPROXIMATE LOCATION OF ROOF
TIE OFF ANCHOR. SHOWN FOR
REFERENCE ONLY (TYPICAL).
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
1/8" = 1'-0"
/1
/2
:0 :5
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
ELECTRICAL SOLAR
ROOF PLAN - AREA D
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
EP-113d
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
1/8" = 1'-0"
ELECTRICAL PHOTOVOLTAIC ROOF PLAN - AREA D
KEYNOTES - PHOTOVOLTAIC
Key Value Keynote Text
PV5 PV ARRAY #4 - AREA D: 54.45KW/DC PV ARRAY CONSISTING OF PV MODULES, POWER OPTIMIZERS, RACKING, BALLAST, BALANCE OF SYSTEM COMPONENTS, ETC. REFER TO E-505 & E-506 FOR MORE INFORMATION.
PV6 PROVIDE CONTINUATION OF ROOF MOUNTED IMC CONDUIT/FEEDERS TO PV ARRAY STRINGS.
PV7 ROOF MOUNTED HIGH VOLTAGE DC WIRING (1000V RATED DC WIRING) IN IMC CONDUIT, PROVIDE MOUNTED TO CONDUIT ROOF SUPPORTS PER ROOFING MANUFACTURER'S REQUIREMENTS. REFER TO INVERTER MOUNTING DETAILS ON SHEET E-506 FOR MORE INFORMATION ON ROOF SUPPORTS. PROVIDE PV WARNING LABELS. REFER
TO ADJACENT ROOF AREA FOR CONTINUATION.
PV8 WALL MOUNTED HIGH VOLTAGE DC WIRING (1000V RATED DC WIRING) IN IMC CONDUIT. PROVIDE PV WARNING
LABELS.
E1
E2
E3
E4
E6A
E7A
RACK MOUNTED SOLAR EDGE POWER OPTIMIZER P1101 (UNLESS
OTHERWISE NOTED. REFER TO INVERTER SCHEDULE FOR MORE
INFORMATION). (1) POWER OPTIMIZER SERVES (2) PV MODULES.
PROVIDE UL LISTED MOUNTING BRACKET AS REQUIRED BY SOLAR
EDGE AND RACKING MANUFACTURER. PROVIDE CONNECTOR AND
EXTENSION ADAPTORS AS REQUIRED. MOUNT POWER OPTIMIZER
PER MANUFACTURER REQUIREMENTS.
SOLAR EDGE PV INVERTER MOUNTED TO CUSTOM FABRICATED
MOUNTING STRUCTURE - REFER TO 1/E-506 FOR MORE INFORMATION.
PROVIDE SOLAREDGE RAPID SHUTDOWN KIT RS485 SPD (#SE-RS485-
SPD2-K1). PRODUCTION REPORTING: DAISY CHAIN INVERTERS TO
FORM A MASTER/SLAVE CONFIGURATION AS REQUIRED BY
SOLAREDGE FOR COMPLETE SYSTEM REPORTING, PROVIDE A
HARDWIRED MODEM KIT INCLUDING A SOLAREDGE DATA PLAN FOR
EACH MASTER INVERTER (TYP). ENSURE PRODUCTION DATA
REPORTING REMAINS OPERATIONAL FOR THE FULL SERVICE LIFE OF
THE PV ARRAY (+25 YEARS). CONFIGURE PRODUCTION REPORTING
WITH THE SCHOOL'S IT REPRESENTATIVE.
EXPOSED 1000V RATED 2#10 PV DC WIRING AND #6 GROUND WIRE
TO SOLAR EDGE POWER OPTIMIZER. CONDUCTORS SHALL BE
PROTECTED FROM PHYSICAL AND UV DAMAGE. PROVIDE CONDUIT
PROTECTION WITH APPROVED BUSHINGS WHEN EXPOSED, WHEN
CROSSING ROWS AND TO AVOID POTENTIAL DAMAGE. PROVIDE
WIRING BETWEEN ROWS IN CONDUIT. CONDUIT AND WIRING SHALL
BE INSTALLED TO LIMIT REFLECTIVE SHADING ON THE BACK SIDE
OF THE PV MODULE. WIRING AT THE PV ARRAY SHALL BE SECURED
WITH STAINLESS STEEL CLIPS AND POLYESTER COATED
STAINLESS STEEL WIRE TIES. GROUND ALL EQUIPMENT AS
REQUIRED INCLUDING RACKING, MODULE, POWER OPTIMIZERS,
JUNCTION BOXES, ETC.
REC ALPHA 72 SERIES PV MODULE MOUNTED TO PV RACKING SYSTEM
ON ROOF. REFER TO PV MODULE SCHEDULE ON SHEET E-001.
4#2/0 & 1#6G, THWN-2 IN 2"IMC CONDUIT.
E6A
E2E4
(TYP.)
E1 E1
INVERTER
SYNERGY UNIT
110KW
INVERTER
SYNERGY
MANAGER
TYPICAL PV INVERTER/STRING CONFIGURATION PER SYNERGY UNIT FOR SOLAREDGE
INVERTER SE110KUS: REFER TO PLANS AND SCHEDULES FOR QUANTITY
(TYP.)
E3
J
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
E7A
E6A
E1
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
E2E4
(TYP.) (TYP.)
E3
J
SU-1 SU-2 SU-3
KEY NOTES - PV ARRAY RISER DIAGRAM
PROVIDE 1000V RATED 2#10 DC WIRING & 1#10G, 1"IMC (INTERMEDIATE
METAL CONDUIT) TO THE ROOF MOUNTED PV ARRAY. PROVIDE ROOF
MOUNTED CONDUIT SUPPORTS THROUGHOUT; KEEP CONDUIT OFF THE
ROOF BY AT LEAST 3-1/2"C. THE CONTRACTOR MAY COMBINE MULTIPLE
STRINGS IN A SINGLE 1" CONDUIT IF THE STRINGS ARE CONNECTED TO
THE SAME INVERTER (AS INDICATED ON PLANS) AND ORIGINATE FROM
THE SAME LOCATION - NOT TO EXCEED 3 DC CIRCUITS (UP TO 6 CURRENT
CARRYING CONDUCTORS PER CONDUIT).
INVERTER
SYNERGY UNIT
INVERTER
SYNERGY UNIT
SU-1 SU-2
E1 E1
TYPICAL PV INVERTER/STRING CONFIGURATION PER SYNERGY UNIT FOR SOLAREDGE INVERTER SE80KUS:
REFER TO PLANS AND SCHEDULES FOR QUANTITY
E2E4
(TYP.) (TYP.)
E3
J
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
E1
E2E4
(TYP.) (TYP.)
E3
J
STRING 1, SU-1
STRING 2, SU-1
STRING 3, SU-1
STRING 4, SU-2
STRING 5, SU-2
STRING 6, SU-2
E2E4
(TYP.) (TYP.)
E3
J
STRING 1, SU-1
STRING 2, SU-1
STRING 3, SU-1
STRING 4, SU-2
STRING 5, SU-2
STRING 6, SU-2
STRING 7, SU-3
STRING 8, SU-3
STRING 9, SU-3
E1
80KW
INVERTER
SYNERGY
MANAGER
E7B
SOLAR EDGE PV INVERTER MOUNTED TO CUSTOM FABRICATED
MOUNTING STRUCTURE - REFER TO 2/E5.06 FOR MORE INFORMATION.
PROVIDE SOLAREDGE RAPID SHUTDOWN KIT RS485 SPD (#SE-RS485-
SPD2-K1). PRODUCTION REPORTING: DAISY CHAIN INVERTERS TO
FORM A MASTER/SLAVE CONFIGURATION AS REQUIRED BY
SOLAREDGE FOR COMPLETE SYSTEM REPORTING, PROVIDE A
HARDWIRED MODEM KIT INCLUDING A SOLAREDGE DATA PLAN FOR
EACH MASTER INVERTER (TYP). ENSURE PRODUCTION DATA
REPORTING REMAINS OPERATIONAL FOR THE FULL SERVICE LIFE OF
THE PV ARRAY (+25 YEARS). CONFIGURE PRODUCTION REPORTING
WITH THE SCHOOL'S IT REPRESENTATIVE.
E7B
E6B
E6B 4#1 & 1#6G, THWN-2 IN 2"IMC CONDUIT.
PV ARRAY RISER DIAGRAM - NOTES
1. REFER TO SHEET E-001 FOR SCHEDULES, NOTES, AND THE LABELING CHART FOR
PV SYSTEM.
ARRAYS #3 & #4
ARRAYS #1 & #2
INVERTER
SYNERGY UNIT
INVERTER
SYNERGY UNIT
A
A
UTILITY C.T.
CABINET
A
A
3000A /3P
GFPE
SPD-1
A
A
A
MAIN DISTRIBUTION SWITCHBOARD: MSB-1
3000A COPPER BUS, 480/277V, 3PH-4W.
PRE-PURCHASED
MULTI-METER
ENERGY
MONITORING
SYSTEM
LOCATED ON ROOF
MAIN ELECTRICAL ROOM 142
LINE TYPES
NEW WORK
PREVIOUS PHASE/EXISTING
1-1/2"C. TO METER.
METER SOCKET SHALL
BE PROVIDED BY EC IN
LOCATION INDICATED
ON PLANS.
FEEDERS AND CONDUITS TO
DISTRIBUTION SYSTEM.
E8A 4#250KCMIL & 1#4G, THWN-2 IN 3"IMC CONDUIT.
E8B 4#500KCMIL & 1#3G, THWN-2 IN 4"IMC CONDUIT.
E10
METERING TRANSFORMER ENCLOSURE SHALL BE: (REFER TO
EVERSOURCE PUBLISHED EQUIPMENT LIST FOR MORE INFORMATION:
https://www.eversource.com/content/docs/default-source/doing-business/connecticut-approved-meter-sockets.pdf)
• (3) CURRENT TRANSFORMERS: 600: 5, BAR TYPE, PROVIDED BY THE
UTILITY COMPANY.
• (3) VOLTAGE TRANSFORMERS: 288: 120 OR 2, 4:1, PROVIDED BY THE
UTILITY COMPANY.
E9
13 TERMINAL SOCKET PRODUCTION METER WITH TEST SWITCH SHALL BE:
(REFER TO EVERSOURCE PUBLISHED EQUIPMENT LIST FOR MORE
INFORMATION: https://www.eversource.com/content/docs/default-source/doing-business/connecticut-approved-meter-sockets.pdf)
• FORM 9S, 3Φ/4W WYE, CLASS 20.
UNDERGROUND
TO UTILITY
TRANSFORMER
(2) 4" BURIED
CONDUITS
E11
RS485 COMMUNICATION WIRE TO INVERTER. RS485 CABLE SHALL BE
SUPPORTED BY EXISTING J-HOOK SUPPORTS. INVERTER SHALL BE
CONFIGURED FOR REPORTING VIA CAT.6 HARDWIRED CONNECTION
TO SOLAR EDGE MONITORING PORTAL. CONFIGURE SOLAR EDGE
MONITORING PORTAL TO REPORT TO TOWN'S IT INFRASTRUCTURE.
COORDINATE WITH TOWN'S IT REPRESENTATIVE TO ENSURE DATA IS
AVAILABLE 24/7 TO THE TOWN FOR MONITORING AND DISPLAY.
E11
E11
A
175A
175A
125A
PVP
500A, 480Y/277V
3PH-4W. NEMA 3R
RATED (MCB)
125A
SPD-3
CONDUITS/FEEDERS
TO SOLAR
INVERTERS AS
INDICATED ON
PLANS.
PROVIDE NEW
500A, LSIG CIRCUIT
BREAKER. LOCATE
ON THE OPPOSITE
SIDE OF BUS FROM
MAIN BREAKER
PER NEC
REQUIREMENTS.
(2) SETS 4#250KCMIL
& 1#2G IN (2) 3"C.
E6A
E6B
A
M
E9
(2) SETS 4#250KCMIL
& 1#2G IN (2) 3"C.
BUILDING EXTERIOR
E6B
TO PANEL
"PVP"
TO PANEL
"PVP"
600A/500AF, LEVER
OPERATED, FUSED,
NEMA-3R DISCONNECT
SWITCH.
NOTES:
1. SPD DEVICES SHALL BEAR THE UL MARK AND SHALL BE LISTED TO THE MOST RECENT EDITION
OF UL1449.
2. SPD DEVICES SHALL BE UL LABELED WITH 20 KAI NOMINAL (ln) FOR COMPLIANCE TO UL 96a
LIGHTING PROTECTION MASTER LABEL AND NFPA 780.
3. SPD DEVICES SHALL BE UL LISTED AS TYPE 1 AND TYPE 2 DEVICES.
4. SPD DEVICES SHALL HAVE A SHORT CIRCUIT CURRENT RATING OF 200,000 A.
5. SPD DEVICES SHALL BE EQUIPPED WITH LED DIAGNOSTICS, SURGE COUNTER AND (1) SET OF
NO/NC DRY CONTACTS.
6. SPD DEVICES SHALL INCLUDE EMI/RFI FILTERING -50 dB FROM 10kHz TO 100 MHz.
SPD SCHEDULE
TYPE VOLTAGE PHASE WIRES
SURGE CURRENT RATING
(PER PHASE - A)
MOUNTING
MODES OF
PROTECTION
SPD-3 480Y/277V 3 4 100,000 INTEGRAL L-N; L-G; L-L
208Y/120V
SPD-1
SPD-2
3 4
3 4
240,000 INTEGRAL L-N; L-G; L-L
INTEGRAL L-N; L-G; L-L160,000
480Y/277V
E10
COMMERCIAL GATEWAY
SE1000-CCG-G-S1
LOCATED IN DATA
ROOM D146.
CATEGORY 6 CABLE FROM
COMMERCIAL GATEWAY TO
AVAILABLE PORT IN EXISTING RACK.
CABLE SHALL BE SUPPORTED BY
EXISTING J-HOOKS + CABLE TRAYS.
COMMERCIAL GATEWAY
SE1000-CCG-G-S1
LOCATED IN DATA
ROOM D130.
CATEGORY 6 CABLE FROM
COMMERCIAL GATEWAY TO
AVAILABLE PORT IN
EXISTING RACK. CABLE
SHALL BE SUPPORTED BY
EXISTING J-HOOKS + CABLE
TRAYS.
INVERTERS 1 & 2
INVERTERS 3 & 4
TO ADJACENT SYNERGY MANAGER
RS485 CABLE
TO ADJACENT SYNERGY
MANAGER
RS485
CABLE
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
NTS
/1
/2
:0 :5
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
ELECTRICAL
DETAILS
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
E-505
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
NTS
PHOTOVOLTAIC SYSTEM RISER DIAGRAM
INVERTER
SYNERGY UNIT
INVERTER
SYNERGY UNIT
INVERTER SYNERGY
MANAGER
SU-1 SU-2
PV SOURCE CIRCUITS
TO INVERTER
SYNERGY MANAGER
SHEET METAL ROOF SHIELD MADE FROM 8
GUAGE SHEET ALUMINUM. ROOF SHIELD
SHALL BE PITCHED 15 DEGREES AND
EXTEND 9" BEYOND THE PV INVERTER.
SHEET METAL BACK PLATE MADE FROM 8
GUAGE SHEET ALUMINUM.
PIPE PIER OR APPROVED EQUAL TO SUPPORT DC
CIRCUITS IN CONDUIT ATLEAST 3.5" ABOVE ROOF
SURFACE (TYPICAL). SUPPORT STRUCUTRE SHALL BE
COMPLIANT WITH TPO ROOF.
GALVANIZED P1000
UNISTRUT (TYPICAL).
PV INVERTER
MOUNTING STRUCTURE
CONNECTION TO
BUILDING STRUCTURE.
ROOF LEVEL (TPO)
ALL METAL CLAMPS SHALL BE
GALVANIZED STEEL. ALL
HARDWARE, NUTS, SCREWS,
BOLTS, AND FASTENERS SHALL
BE STAINLESS STEEL (TYPICAL).
SOLAREDGE SE80KUS THREE-PHASE
INVERTER. REFER TO PLANS FOR
QUANTITY AND CONFIGURATIONS.
ROOF MOUNTED DC CIRCUITS
WHERE INDICATED FOR THE
ROOF PV ARRAY.
ROOF MOUNTED AC
CIRCUITS IN CONDUIT
TO 400A FUSED
DISCONNECT.
TO 200A FUSED
DISCONNECT. SEE TYPICAL
DISCONNECT ROOF
MOUNTING DETAIL FOR
MORE INFORMATION.
INVERTER
SYNERGY UNIT
INVERTER SYNERGY
MANAGER
SU-1 SU-2 SU-3
PV SOURCE CIRCUITS
TO INVERTER
SYNERGY MANAGER
SHEET METAL ROOF SHIELD MADE FROM 8
GUAGE SHEET ALUMINUM. ROOF SHIELD
SHALL BE PITCHED 15 DEGREES AND
EXTEND 9" BEYOND THE PV INVERTER.
SHEET METAL BACK PLATE MADE FROM 8
GUAGE SHEET ALUMINUM.
PIPE PIER OR APPROVED EQUAL TO SUPPORT DC
CIRCUITS IN CONDUIT ATLEAST 3.5" ABOVE ROOF
SURFACE (TYPICAL). SUPPORT STRUCUTRE SHALL BE
COMPLIANT WITH TPO ROOF.
GALVANIZED P1000
UNISTRUT (TYPICAL).
PV INVERTER
MOUNTING STRUCTURE
CONNECTION TO
BUILDING STRUCTURE.
ROOF LEVEL (TPO)
ALL METAL CLAMPS SHALL BE
GALVANIZED STEEL. ALL
HARDWARE, NUTS, SCREWS,
BOLTS, AND FASTENERS SHALL
BE STAINLESS STEEL (TYPICAL).
SOLAREDGE SE110KUS THREE-PHASE
INVERTER. REFER TO PLANS FOR
QUANTITY AND CONFIGURATIONS.
ROOF MOUNTED DC CIRCUITS
WHERE INDICATED FOR THE
ROOF PV ARRAY.
ROOF MOUNTED AC
CIRCUITS IN CONDUIT
TO 400A FUSED
DISCONNECT.
TO 200A FUSED
DISCONNECT. SEE TYPICAL
DISCONNECT MOUNTING
DETAIL FOR MORE
INFORMATION.
INVERTER
SYNERGY UNIT
INVERTER
SYNERGY UNIT
PV MODULE FRAME WITH 5° TILT (TYPICAL).
REFER TO PV MODULE SCHEDULE ON SHEET
E-001 FOR MORE INFORMATION.
5/16" X 7/8"L HEX BOLT (TYPICAL)
TOP CLAMP (TYPICAL)
(#BX-TCL-30MM-M1)
BOTTOM/PULL CLAMP (TYPICAL)
(#BX-BCL-M1)
1' 1-1/4"
9-7/8"
BALLAST BLOCK. PROVIDE AMOUNT
OF BLOCKS PER THE STRUCTURAL
ENGINEER AND IRONRIDGE
REQUIREMENTS (TYPICAL).
TYPICAL FULL BLOCK:
- 8"X16"X4"
- 32 LBS.
GENERAL NOTES:
1. BASIS OF DESIGN IS IRONRIDGE.
2. ELECTRICAL CONTRACTOR SHALL COORDINATE EXACT MOUNT
LOCATIONS, AND QUANTITIES OF MOUNTS AND BALLAST BLOCKS
WITH THE STRUCTURAL ENGINEER AND MANUFACTURER'S
REQUIREMENTS.
BX CHASSIS 5 DEGREE
ASSEMBLY (TYPICAL)
(#BX-5D-P1)
PROVIDE MODULE BONDING JUMPER
FOR GROUNDING OF EACH MODULE
PER IRONRIDGE REQUIREMENTS.
(#BX-MB8-M1)
PROVIDE ROW BONDING JUMPER
FOR GROUNDING OF EACH ROW PER
IRONRIDGE REQUIREMENTS.
(#BX-RB38-M1)
PROVIDE PV MODULE GROUNDING
LUG PER IRONRIDGE REQUIREMENTS.
(PV-LUG-01-A1)
PROVIDE ROOF CONTACT PAD UNDER EACH BALLAST TRAY (TYPICAL). APPLY
PROFESSIONAL-GRADE ADHESIVE FOR ATTACHMENT OF ROOF CONTACT PAD TO
BALLAST TRAY. PROFESSIONAL ADHESIVE SHALL BE COMPATIBLE WITH CONTACT PAD
MATERIAL. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
CONDUIT ROOF SUPPORTS.
REFER TO TYPICAL CONDUIT
ROOF SUPPORTS DETAIL FOR
MORE INFORMATION.
ROOF
ROOF MOUNTED DC
CIRCUITS WHERE
INDICATED FOR THE
ROOF PV ARRAY.
1'6" MAX
CANTILEVERED OPEN-ENDED
IMC CONDUIT. REFER TO
PHOTOVOLTAIC RISER
DIAGRAM FOR CONDUIT
SIZES.
EQUIPMENT GROUNDING CONDUCTOR CONNECTED TO LAY-IN-LUG.
EXAMPLE PARTS (OR EQUIVALENT):
GREAVES BTL 4-DBP (IF BUSHING HAS #10 SCREWS)
GREAVES BTL 414-BDP (IF BUSHING HAS 1/4" SCREWS)
CONDUIT BONDING BUSHING. SEAL CONDUIT
ENTRY USING WEATHERPROOF METHODS
SIZED TO FIT CONDUIT DIAMETER.
TO WIRE
MANAGEMENT
UNDERNEATH PV
ARRAYS.
PV WIRING
PROVIDE TO SUPPORT DC CIRCUITS IN CONDUIT
ATLEAST 3.5" ABOVE ROOF SURFACE (TYPICAL).
SUPPORT STRUCTURE SHALL BE COMPLIANT
WITH TPO ROOF.
ROOF
ROOF MOUNTED DC CIRCUITS
WHERE INDICATED FOR THE
ROOF PV ARRAY.
SIDE VIEW OF CONDUIT
SUPPORTS. PROVIDE TO
SUPPORT DC CIRCUITS IN
CONDUIT ATLEAST 3.5"
ABOVE ROOF SURFACE
(TYPICAL). SUPPORT
STRUCTURE SHALL BE
COMPLIANT WITH TPO
ROOF.
10' MAX 2' MAX
MAXIMUM SPACING BETWEEN
CONDUIT SUPPORTS.
CONDUIT SUPPORTS SHALL BE
INSTALLED WITHIN 2 FEET OF EACH
CONDUIT BEND.
GENERAL NOTES:
1. BASIS OF DESIGN IS PIPE PIER.
2. ALL CONDUIT ROUTED ON THE ROOF SHALL BE SUPPORTED BY AT LEAST 3.5 INCHES ABOVE THE ROOF SURFACE.
3. ELECTRICAL CONTRACTOR SHALL PROVIDE A COMPLETE INSTALLATION BASED ON MANUFACTURER'S REQUIREMENTS
AND CONDUIT SIZING BASED ON THE PHOTOVOLTAIC RISER DIAGRAM.
4. ROOF MATERIAL PROTECTION:
• PROVIDE CONTACT PAD UNDER EACH CONDUIT SUPPORT (TYPICAL FOR ALL CONDUIT SUPPORTS). CONTACT PAD SHALL BE THE SAME PRODUCT USED FOR THE BALLAST TRAYS. REFER TO SPECIFICATIONS FOR CONTACT PAD
INFORMATION.
• ALTERNATE PRODUCT: "CUSTOM BOOT BASE MAT, BY PIPE PIER." APPROVED IF COMPATIBLE WITH ROOF
MATERIAL AND ACCEPTABLE BY THE ROOF MANUFACTURER.
CONDUIT ROOF SUPPORTS.
REFER TO TYPICAL
CONDUIT ROOF SUPPORTS
DETAIL FOR MORE
INFORMATION.
ROOF
ROOF MOUNTED
IMC CONDUIT.
REFER TO
PHOTOVOLTAIC
RISER DIAGRAM
FOR CONDUIT
SIZES AND ROOF
PLANS FOR
ROUTING.
NEMA4X PULLBOX. ALL OPENINGS OR CONDUIT
INSTALLATION INTO THE BOX SHALL BE
SEALED/WEATHERPROOFED.
EMT RAINTIGHT
COMPRESSION
COUPLING FOR
CONDUIT.
FLANGE AND STRUT NUT
TO FASTEN ENCLOSURE
TO SPANNING STRUT.
HEX BOLT, FENDER
WASHER, AND STRUT
NUT TO FASTEN
SPANNING STRUT TO
SPACER STRUT.
HEX BOLT AND
SERRATED FLANGE
NUT AND FENDER
WASHER.
CONDUIT ROUTING STRAP,
FASTENED TO STRUCTURE
BELOW, SUPPORT AT MAX 10'.
MOGUL L BODY SIZED TO MATCH CONDUIT
DIAMETER INDICATED IN THE PHOTOVOLTAIC
RISER DIAGRAM.
CONDUIT HANGER
STRAP FASTENED TO
STRUCTURE BELOW.
(2) SPANNING STRUTS FOR PULLBOX
MOUNTING.
PIPE PIER SUPPORTS FOR SUPPORTING
PULL BOX. (4) TOTAL, ONE PER CORNER.
GENERAL NOTES:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE ROOFING
CONTRACTOR TO DETERMINE APPROPRIATE FLASHING SLEEVE/BOOT
SIZE. DEPTH AND SPACER STRUTS SHALL BE SELECTED
ACCORDINGLY.
2. ALL CONDUIT ROUTED ON THE ROOF SHALL BE SUPPORTED BY AT
LEAST 3.5 INCHES ABOVE THE ROOF SURFACE.
3. ELECTRICAL CONTRACTOR SHALL PROVIDE A COMPLETE
INSTALLATION BASED ON MANUFACTURER'S REQUIREMENTS AND
CONDUIT SIZING BASED ON THE PHOTOVOLTAIC RISER DIAGRAM.
4. COORDINATE WITH ROOFING CONTRACTOR FOR ALL ROOF
PENETRATIONS AND SEALING TO MAINTAIN ROOF WARRANTY.
FLASHING SLEEVE,
COMPATIBLE WITH
ROOF MATERIAL.
SCALE:
SEAL
DRAWING TITLE:
PROJECT TITLE:
PROJECT No:
KEY PLAN
Owner:
Construction Manager:
Civil / Site:
Structural:
Mechanical, Electrical, Plumbing & Fire Protection:
IT/Telcom/Security:
Food Service:
Landscape:
A
B
C
D
STATE PROJECT No:
CMS 033-0055-N CAO 033-0056-BE
CES #2022575.00
As indicated
/1
/2
:0 :5
P
M C
U s e rs
\r m u n o z \D o c u m e n ts
\R
-2
.0
M
E P
C e n tr a l -
C ro m w e ll
M S rm u n o z Q
P X
F .r v t
ELECTRICAL
DETAILS
95550.00
CROMWELL MIDDLE
SCHOOL & CENTRAL
ADMINISTRATION
OFFICE
1/16/2026
E-506
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
PHOTOVOLTAIC SYSTEM
PHASE 4 OF 4
Newfield Construction
225 Newfield Avenue, Hartford, CT 06106
SLR
99 Reality Drive, Chesire, CT 06410
DeSimone Consulting Engineers
55 Church Street, 4th Flr, New Haven, CT 06510
Consulting Engineering Services, Inc.
811 Middle Street, Middletown, CT 06457
D'Agostino & Associates
1000 Lafayette Blvd., 11th Floor, Bridgeport, CT 06604
Food Service Facilities International
137 Elm Place, New Canaan, CT 06840
Richter & Cegan, Inc.
8B Canal Court, Avon, CT 06001
9 Captain James Mann Memorial Drive, Cromwell, CT 06416
The Town of Cromwell
677 Washington Blvd.
Suite 101 Stamford, CT 06901 T. +1 203 251 7400 F. +1 203 251 7474
NTS
INVERTER MOUNTING DETAIL FOR ARRAYS #3 & #4 - SE80KUS
NTS
INVERTER MOUNTING DETAIL FOR ARRAYS #1 &2 - SE110KUS
NTS
PHOTOVOLTAIC RACKING DETAIL
Notes: Total Amps: 469.1 A
Total Load: 390.00 kVA
Phase... 469.3 A 469.3 A 469.3 A
Phase Load: 130.00 kVA 130.00 kVA 130.00 kVA
17 SPACE -- 1 -- -- 1 -- SPACE 18
15 SPACE -- 1 -- -- 1 -- SPACE 16
13 SPACE -- 1 -- -- 1 -- SPACE 14
11 -- -- -- 27.00 27.00 -- -- -- 12
9 -- -- -- 27.00 27.00 -- -- -- 10
7 INV-3 125 A 3 27.00 27.00 3 125 A INV-4 8
5 -- -- -- 38.00 38.00 -- -- -- 6
3 -- -- -- 38.00 38.00 -- -- -- 4
1 INV-1 175 A 3 38.00 38.00 3 175 A INV-2 2
CKT Circuit Description Trip Poles
A B C
Poles Trip Circuit Description CKT
Enclosure: Type 3R MCB Rating / MLO: 500A MCB
Mounting: Surface Wires: 4 Bus Rating: 500 A
Supply From: MSB-1 Phases: 3 Bus Material: CU
Location: Volts: 480/277 Wye A.I.C. Rating: 22 KAIC
Branch Panel: PVP
ROOFTOP
NTS
TYPICAL CONDUIT TRANSITION/ENTRY DETAIL
NTS
TYPICAL CONDUIT SUPPORTS DETAIL
NTS
CONDUIT PENETRATION DETAIL
| G-000 PV SYSTEM - COVER SHEET |
| Sheets |
| G-006 - COVER SHEET - PV |
| A-104 OVERALL ROOF PLAN - PV SYSTEM - Copy |
| Sheets |
| A-104 - OVERALL ROOF PLAN - PV SYSTEM |
| Cromwell MS_Solar PV |
| Sheets |
| E-001 - ELECTRICAL ABBREVIATIONS, NOTES, SYMBOLS, AND SCHEDULES |
| E-505 - ELECTRICAL DETAILS |
| E-506 - ELECTRICAL DETAILS |
| EP-113a - ELECTRICAL SOLAR ROOF PLAN - AREA A |
| EP-113b - ELECTRICAL SOLAR ROOF PLAN - AREA B |
| EP-113c - ELECTRICAL SOLAR ROOF PLAN - AREA C |
| EP-113d - ELECTRICAL SOLAR ROOF PLAN - AREA D |
| SU-101 - SITE UTILITY PHOTOVOLTAIC PLAN |