CLCS Meyer Elementary Digital Sign bid drawings 260917.pdf
PDF 2 MB Posted
- Attached to
- RFP - Digital Signs
- Solicitation number
- RFP CROS 260000002737 1
- Issued by
- Sanilac County, Michigan
About this file
These are bid drawings for a digital sign installation project at Croswell-Lexington Community Schools' Meyer Elementary School located in Lexington, Michigan (Project No. 2026-045). The project, prepared by French Associates, Inc. and issued for bids on September 4, 2026, involves the installation of a new LED digital sign with specific architectural and electrical specifications. The digital sign features a 2-foot-0-inch height by 9-foot-0-inch width display housed in a 4-foot-8-inch by 9-foot-3-inch steel tube cabinet painted brown-blue, mounted on two 3-inch square poles with a reinforced concrete footing. The sign includes channel letters mounted individually with LED lighting, 20-inch letter height, white plexiglass face with blue and black vinyl, and a 3-foot depth. The installation is located at 7201 Lake Street, Lexington, Michigan 48450, as identified on the architectural site plan and Google reference location map. The drawings include detailed specifications for the sign structure, electrical power requirements, and panel schedules necessary for contractor execution.
The electrical work required includes installation of a new NEMA 3R weatherproof disconnect switch with final electrical connections using new conduit and wiring sized at 1-1/4 inches with pull string for data. The electrical contractor must coordinate the exact location of conduit stub-ups and power requirements with the sign manufacturer prior to rough-in work and ensure all conduit penetrations are sealed weather-tight. A new 20-ampere, 2-pole breaker must be installed in existing panel space, with all work performed in accordance with the 2023 National Electrical Code, 2023 Michigan Electrical Code, 2021 Michigan Building Code, and applicable state and local codes. The project specifications require minimum #12 AWG wiring with 3/4-inch minimum conduit, new THHN wire type, and all electrical equipment to be new unless otherwise noted. The drawings indicate coordination requirements with existing underground utilities and field verification to prevent disruption of existing systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 26045 00 1000 Advertisement for Bids (3).docx | DOCX document | |
| CLCS Frostick and Meyer Digital Signs bid specs 260917.pdf | ||
| CLCS Frostick Elementary Digital Sign bid drawings 260917.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIST OF DRAWINGS
ARCHITECTURAL
CROSWELL LEXINGTON COMMUNITY SCHOOLS
MEYER ELEMENTARY DIGITAL SIGN
LEXINGTON, MICHIGAN
2026-045
SEPTEMBER 04, 2026 BIDS
PROJECT NO.
ELECTRICAL
c FRENCH ASSOCIATES, INC.
-0
C
LC
S
- D
IG
IT
AL
S
IG
N
S
A1.01 SIGN/MESSAGE READER DETAILS
A1.10 ARCHITECTURAL SITE PLAN
E0.00 ELECTRICAL GENERAL INFORMATION
EP2.10 ELECTRICAL POWER NEW WORK PLAN
E6.00 ELECTRICAL PANEL SCHEDULE
7201 LAKE ST, LEXINGTON, MI 48450
REFERENCE LOCATION MAP
ORIGINAL DRAWINGS PRINTED IN FULL COLOR
CROSWELL-LEXINGTON
MEYER ELEMENTARY
GO PIONEERS
REINFORCED CONCRETE BASE
1'- 8"
2'- 0"
2'- 5"
3"
4"
5'- 2"
3" X 3" STEEL POLE,
SPRAYED BLACK
9'-3" 3"3"
5'-9 1/4"
ALUMINUM HANG OFF, MASK
SPRAYED BLACK WITH HP VINYL
1'- 0"
6'- 9"
1'-0"
ANCHOR BOLTS
1'-3"
LED DISPLAY
OVERALL SIZE: 2'-5" H X 9'-3" W
DISPLAY SIZE: 2'-0" H X 9'-0" W
CABINET SPECS
CABINET SIZE: 4'-8" H X 9'-3" W
CONSTRUCTION STYLE: STEEL TUBE
CABINET COLOR: BR. BLUE
LIGHTING: T8
MOUNTING: 3" SQ. POLES (X2)
FACE MATERIAL: SUB SURFACE CUT 0.125" ALUMINUM
CHANNEL LETTERS SPECS
MOUNTING: INDIVIDUAL
LED COLOR: COLOR
RETURN SPECS: 3" DEPTH, COLOR IS WHITE
FACE SPECS: WHITE PLEX COLOR WITH BLUE/ BLACK VINYL
LETTER HEIGHT: 20"
TRIM COLOR: WHITE
A1.01 A
(2) #5 BARS TOP AND BOTTOM
GRADE LINE
EL. 100'-0"
GRADE LINE
EL. 100'-0"
3'- 6"
MI
N.
REINFORCED CONCRETE
FOOTING
REFER TO B/A1.01 FOR
ADDITIONAL NOTES
KEY PLAN
KM
DJ
DJ
SIGN/MESSAGE
READER DETAILS
A1.01
ISSUE DATE ISSUED FOR
CHECKED
APPROVED
DRAWN
PROJECT
SHEET
PROJECT NUMBER
SHEET NUMBER
09/04/2026 BIDS
CLCS
MEYER
ELEMENTARY
SIGN
LEXINGTON,
MICHIGAN
2026-045
-0
C
LC
S
- D
IG
IT
AL
S
IG
NS
2851 High Meadow Circle | Suite 100 Auburn Hills | MI 48326
248.656.1377
KEY PLAN
SCALE:
DIGITAL SIGN
SECTION
3/4" = 1'-0" A
A1.01
SCALE:
DIGITAL SIGN
ELEVATION
3/4" = 1'-0" B
A1.01
SCALE:
EXISTING SIGN
N.T.S.
C
A1.01
EXISTING SIGN AND
BASE TO REMAIN
SCALE:
EXISTING
MIDDLE SCHOOL SIGN
N.T.S.
E
A1.01
EXISTING SIGN TO
ILLUSTRATE DESIGN
INTENT FOR NEW SIGNS
NEW SIGNS TO HAVE LED
DISPLAYS AS SPECIFIED
KEY PLAN
KM
DJ
DJ
ARCHITECTURAL
SITE PLAN
A1.10
ISSUE DATE ISSUED FOR
CHECKED
APPROVED
DRAWN
PROJECT
SHEET
PROJECT NUMBER
SHEET NUMBER
09/04/2026 BIDS
CLCS
MEYER
ELEMENTARY
SIGN
LEXINGTON,
MICHIGAN
2026-045
-0
C
LC
S
- D
IG
IT
AL
S
IG
NS
2851 High Meadow Circle | Suite 100 Auburn Hills | MI 48326
248.656.1377
KEY PLAN
LOCATION OF DIGITAL SIGN
SCALE:
ARCHITECTURAL
SITE PLAN
N.T.S.
A
A1.10
TBB
ABBREV.
IG ISOLATED GROUND
TELEPHONE BACKBOARD
ELECTRICAL ABBREVIATIONS
DESCRIPTION
RP
LP
RECEPTACLE PANEL
LIGHTING PANEL
AF AMPERE FUSE/AMPERE FRAME
WP
(E)
NIC
WEATHERPROOF
NOT IN CONTRACT
RMC
(R)
RIGID METALLIC CONDUIT
RELOCATED EXISTING ELECTRICAL EQUIPMENT
EXISTING ELECTRICAL EQUIPMENT OR WORK
MDP
FACP
ATS
MAIN DISTRIBUTION PANEL
FA
FLA
FIRE ALARM
FULL LOAD AMPS
FIRE ALARM CONTROL PANEL
AUTOMATIC TRANSFER SWITCH
T TRANSFORMER (REFER TO SCHEDULES FOR INFO)
MAIN CIRCUIT BREAKER
MAIN LUG ONLY
AVAILABLE INTERRUPTING CURRENT (AMPS)
NON-FUSIBLENF
MCB
MLO
AIC
GROUND FAULT CIRCUIT INTERRUPTERGFCI/GFI
DESCRIPTION
NEW EQUIPMENT DESIGNATION,
DEMOLITION KEY NOTE NUMBER 1
(I.E. EXHAUST FAN NUMBER 1)
CONSTRUCTION KEY NOTE NUMBER 1
SYMBOL
SECTION NUMBER 4
SECTION NO. 6
SECTION
SCALE: 1/4" = 1' - 0"
(ENLARGED PARTIAL PLAN SIMILAR)
DRAWING NOTATION
EXISTING SYSTEM COMPONENT TO BE REMOVED
SHEET E5.2 ON WHICH SECTION IS CUT
SHEET E5.2 ON WHICH SECTION IS
DRAWN
LIGHTING FIXTURE TAG
MOTOR - SINGLE PHASE
MOTOR - THREE PHASE
METERM
SYMBOL
POWER SYMBOL LIST
DESCRIPTION
E5.2
E5.2
NEW OR MODIFIED DEVICES OR EQUIPMENT
EXISTING DEVICES OR EQUIPMENT
GROUNDG/GRD
AFF ABOVE FINISHED FLOOR
CIRCUIT BREAKERCB
ELECTRICAL METALLIC TUBINGEMT
ELECTRIC WATER COOLEREWC
HAND-OFF-AUTOHOA
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNEMA
POLEP
TYP. TYPICAL
NEW OR MODIFIED UNDERGROUND WIRING
REMOVE AND REINSTALL(RR)
WG WIRE GUARD
COMMUNICATIONS DEVICE - WALL
PUSH BUTTON
WALL CLOCK - SINGLE FACE
WALL CLOCK AND SPEAKER UNITS
SPEAKERS
CARD READERCR
SYMBOL DESCRIPTION
AUXILIARY SYST. SYMBOL LIST
COMMUNICATIONS DEVICE - FLOOR
WALL CLOCK - DOUBLE FACE
STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS, NFPA 110
YEAR CODE
MICHIGAN BUILDING CODE
MICHIGAN ELECTRICAL CODE RULES, PART 8
LIFE SAFETY CODE, NFPA 101
ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS & FACILITIES
APPLICABLE CODES
AND REGULATIONS
MICHIGAN ENERGY CODE2019
NATIONAL ELECTRICAL CODE (NFPA 70)2023
NATIONAL FIRE ALARM AND SIGNALING CODE, NFPA 722013
COMMUNICATIONS DEVICE - 6" ABOVE COUNTER
NOTES:
1. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR BOX AND CONDUIT FOR
ALL DEVICES INDICATED.
2. LOW VOLTAGE CONTRACTOR SHALL PROVIDE EXACT SPECIFICATIONS AND
LOCATIONS OF ALL DEVICES.
CAMERA
MAGNETIC DOOR HOLDER
VSD VARIABLE SPEED DRIVE
C CONDUIT OR CEILING MOUNTED
CONDUIT DOWN
CONDUIT UP
CONTACTORC
POWER RECEPTACLE - DUPLEX TYPE
POWER RECEPTACLE - SIMPLEX TYPE
FLOOR BOX - RECESSED FLOOR TYPE
POWER RECEPTACLE - SPECIALTY TYPE
POWER RECEPTACLE - DUPLEX 6" ABOVE COUNTER
POWER RECEPTACLE - QUADRUPLEX TYPE
DISCONNECT SWITCH - NON FUSED
DISCONNECT SWITCH - FUSED
DISCONNECT SWITCH - COMB. MOTOR STARTER
ELECTRICAL PANEL - 208/240/480 VOLTS
GROUNDING BAR
GROUND
GROUNDING ROD
JUNCTION BOXJ
J JUNCTION BOX WITH HARDWIRED CONNECTION
MOTOR RATED SWITCHS
TIME CLOCKTC
SPD SURGE PROTECTION DEVICE
NOTES:
1. ALL DEVICE RATINGS/SIZES SHALL BE COORDINATED WITH PLANS AND
SCHEDULES.
A AMPERE
AMPERE TRIPAT
AWG AMERICAN WIRE GAUGE
CURRENT TRANSFORMERCT
COPPERCU
DISCONNECTDISC
DIAMETERDIA
EMERGENCY POWER OFFEPO
F FUSE
HORSEPOWERHP
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KILOWATT HOUR
MAXIMUMMAX
MINIMUMMIN
NATIONAL ELECTRICAL CODENEC
NEUTRALN/NEU
NC NORMALLY CLOSED
NO NORMALLY OPEN
OF/CI OWNER FURNISHED / CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED / OWNER INSTALLED
POWER FACTORPF
PHASEPH. OR Ø
PVC POLYVINYL CHOLRIDE (PLASTIC)
SPEC/SPECS SPECIFICATIONS
UC UNDER COUNTER
UL UNDERWRITERS LABORATORIES
UPS UNINTERRUPTIBLE POWER SUPPLY
VOLT
VA VOLT AMPERE
V
W WATT
XFMR TRANSFORMER
FEEDER SIZE TAG
(REFER TO FEEDER SCHEDULE ON THIS SHEET)
Z1 1A
SCENE SCHEDULE ID 'A'
DAYLIGHTING CONTROL
ZONE '1' (MAY NOT APPEAR ON
EVERY TAG)
LIGHTING CONTROL
SPACE TYPE '1'
LIGHTING CONTROL TAG
POWER RECEPTACLE - USB/DUPLEX COMBO. DEVICEUSB
USB UNIVERSAL SERIAL BUS
EF-1
FLOOR BOX - POKE THRU TYPE
FB
PT
POWER RECEPTACLE - DUPLEX TYPE CONTROLLED
POWER RECEPTACLE - DUPLEX TYPE EMERGENCY
POWER RECEPTACLE - QUADRUPLEX CONTROLLED
IT SLEEVE 1 1/4" TYPICAL UNLESS NOTED OTHERWISE
DOOR OPENDO
VIDEO INTERFACEVI
LA
EXISTING EQUIPMENT DESIGNATION,
(I.E. EXISTING EXHAUST FAN)(E)EF
DH
M
ISSUE DATE ISSUED FOR
CHECKED
APPROVED
DRAWN
PROJECT
SHEET
PROJECT NUMBER
SHEET NUMBER
MPH
EJZ
TJO
2851 High Meadow Circle | Suite 100 Auburn Hills | MI 48326
248.656.1377
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 029.26.17- MY
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
09/04/2026 BIDS
CLCS
MEYER
ELEMENTARY
REMODEL
LEXINGTON,
MICHIGAN
2026-050
-0
C
LC
S
ME
YE
R
EL
EM
EN
TA
RY
R
EM
OD
EL
ELECTRICAL GENERAL
INFORMATION
E0.00
DRAWING INDEX
SHT. NO. DESCRIPTION
E0.00 ELECTRICAL GENERAL INFORMATION
EP2.10 ELECTRICAL POWER NEW WORK PLAN
E6.00 ELECTRICAL PANEL SCHEDULES
POWER GENERAL NOTES
A
THESE DRAWINGS ARE DIAGRAMMATIC AND REPRESENT THE GENERAL EXTENT
OF THE WORK TO BE PERFORMED. PROVIDE AND EXECUTE ALL POWER SYSTEMS
PER ENGINEER'S SPECIFICATION, AND LOCAL APPLICABLE CODES INCLUDING
AMENDMENTS, BULLETINS, ETC. AS WELL AS THE STANDARDS OF INSTALLATION
AND EQUIPMENT ESTABLISHED FOR THE BUILDINGS, AND REQUIREMENTS OF
THE OWNER.
B
EXCEPT FOR CHANGES AS MAY BE SPECIFICALLY APPROVED BY THE ENGINEER OF
RECORD. IN ACCORDANCE WITH ALTERNATES OF OPTIONS AS STATED
HEREINAFTER, ALL WORK MUST BE IN FULL ACCORDANCE WITH THE INTENT OF
THE PLANS AND SPECIFICATIONS. SYSTEMS ARE TO BE COMPLETE, EFFICIENT,
AND SATISFACTORY OPERATION WHEN PROJECT IS DELIVERED TO THE OWNER.
D
CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS AND APPROVAL FROM
GOVERNING AUTHORITIES AND FILE NECESSARY FORMS, PAY ALL INSPECTION
FEES.
E
ELECTRICAL CONTRACTOR SHALL COMPLY WITH THE LATEST NATIONAL
ELECTRICAL CODE, LIFE SAFETY CODE AND APPLICABLE STATE AND LOCAL
CODES AND ORDINANCES.
F ELECTRICAL EQUIPMENT AND WIRING SHALL BE NEW AND SHALL BE FURNISHED
AND INSTALLED BY ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED.
G WIRING SHALL BE IN CONDUIT. CONDUIT SHALL BE 3/4" CONDUIT MINIMUM.
CONDUITS IN FINISHED AREAS SHALL BE CONCEALED
H
NEW WIRES SHALL BE TYPE THHN. MINIMUM SIZE SHALL BE #12 AWG, UNLESS
OTHERWISE NOTED. FINAL CONNECTIONS TO EQUIPMENT, FURNISHED AND
INSTALLED BY OTHERS, SHALL BE PROVIDED BY THIS CONTRACTOR.
POWER GENERAL NOTES
NEW LED SIGN INSTALLED BY OTHERS. ELECTRICAL CONTRACTOR SHALL
PROVIDE NEW NEMA 3R WP DISCONNECT AND FINAL ELECTRICAL CONNECTIONS
USING NEW CONDUIT AND WIRING. PROVIDE 1-1/4"C WITH PULL STRING FOR
DATA. COORDINATE EXACT LOCATION OF CONDUIT STUB-UPS AND POWER
REQUIREMENTS WITH SIGN MANUFACTURER PRIOR TO ROUGH IN.
2 COORDINATE EXACT LOCATION IN THE FIELD SUCH THAT ALL EXISTING TO
REMAIN UNDERGROUND UTILITIES ARE NOT DISRUPTED.
TRANSITION TO RIGID CONDUIT. STUB THRU WALL WITH LB FITTING 18" ABOVE
GRADE. EXACT CONDUIT PENETRATIONS TO BE COORDINATED IN THE FIELD.
SEAL ALL CONDUIT PENETRATIONS WEATHER TIGHT.
X
UNIT 'B
UNIT 'C
UNIT 'C'
UNIT 'B'
UNIT 'A
UNIT 'B
UNIT 'B'
UNIT 'A'
STAGE
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
TITLE/SMALL
GROUP
SPEECH
SPECIAL
ED
CUSTODIAL
MEDIA CENTER
WORK
STORAGE
AV
GIRLS
BOYS
CORRIDOR
VESTIBULE
SOCIAL WORKER
OFFICE
CAFETERIA
GYMNASIUM
KITCHEN
TOLIET
BOYS
LOCKER
VESTIBULE
GIRLS
LOCKER
OFFICE
FRONT
GIRLS
BOYS
BOILER
WORK
WORK
(E)CP-M
J
1 CP-M-26,28
2#8+1#8N+1#10 GND
IN 1-1/4"C
1-1/4"C FOR DATA
WITH PULLSTRING
ISSUE DATE ISSUED FOR
CHECKED
APPROVED
DRAWN
PROJECT
SHEET
PROJECT NUMBER
SHEET NUMBER
MPH
EJZ
TJO
2851 High Meadow Circle | Suite 100 Auburn Hills | MI 48326
248.656.1377
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 029.26.17- MY
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
09/04/2026 BIDS
CLCS
MEYER
ELEMENTARY
REMODEL
LEXINGTON,
MICHIGAN
2026-050
-0
C
LC
S
ME
YE
R
EL
EM
EN
TA
RY
R
EM
OD
EL
ELECTRICAL POWER
NEW WORK PLAN
EP2.10SCALE:
ELECTRICAL POWER NEW WORK PLAN
1/16" = 1'-0"
Know what's below .
Call before you dig.
AutoCAD SHX Text R
*UTILIZE EXISTING SPACES FOR NEW 20A, 2P BREAKER.
ISSUE DATE ISSUED FOR
CHECKED
APPROVED
DRAWN
PROJECT
SHEET
PROJECT NUMBER
SHEET NUMBER
MPH
EJZ
TJO
2851 High Meadow Circle | Suite 100 Auburn Hills | MI 48326
248.656.1377
UNIFIED BUILDING
SYSTEMS ENGINEERING
UBS PROJECT 029.26.17- MY
69 S. GRATIOT AVE.
MT. CLEMENS, MI 48043
09/04/2026 BIDS
CLCS
MEYER
ELEMENTARY
REMODEL
LEXINGTON,
MICHIGAN
2026-050
-0
C
LC
S
ME
YE
R
EL
EM
EN
TA
RY
R
EM
OD
EL
ELECTRICAL PANEL
SCHEDULE
E6.00
File details come from the government source that posted it. Updated .