Clark Rest Area.pdf
PDF 3 MB Posted
- Solicitation number
- RFP-785-2500000200-1
- Issued by
- Carter County, Kentucky
About this file
This is a building evaluation report from the Kentucky Transportation Cabinet's Facilities Support Services Design & Construction Branch regarding the Clark County Rest Area (RA25-64E1) conducted on December 15, 2020. The inspection identified numerous deficiencies including a deteriorating asphalt roll roofing system that has reached the end of its life expectancy and is causing ceiling and wall damage throughout the facility, stained and damaged ceilings with black substance requiring testing, cracked concrete floors, outdated wall and floor tiles with damage and mismatched repairs, and deteriorating restroom partitions with worn finishes and mismatched repair parts.
The electrical system is in poor condition with multiple non-functioning outlets, broken conduits, and ongoing circuit breaker issues that require staff to keep several breakers off to prevent tripping. The vending shelter requires fascia board replacement, gutter re-hanging, and roof vent replacement. The report concludes that the facility needs comprehensive renovation, with the scope of work exceeding the threshold for single quotes. The recommendation is to request finance department approval to hire a consultant to determine estimated costs for bringing the facility up to current standards.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KENTUCKY TRANSPORTATION CABINET
FACILITIES SUPPORT SERVICES
DESIGN & CONSTRUCTION BRANCH
Clark County Rest Area
RA25-64E1
12-15-2020 RE: Building Evaluation
Site visit Clark County Rest Area with Chris Spencer and Ricky Lundsford to review the facility for improvements. Findings area as follows:
Roof: Asphalt Roll Roofing.
Condition: Material has reached its life expectances and in need of replacement. Leaks causing ceiling and wall damage throughout.
Roof
Ceilings:
Condition: Stained/damaged in several areas. There is also several areas with Black substance appearing throughout. Need to test to identify.
Above Entrance
Rest Room
Walls:
Condition: Interior walls have areas with moisture damage causing Paint to peel or flake. Areas show wear, fading and obvious patched areas.
FIRST VIEW ENTERING
East Side Corridor
End Wall Adjacent Women’s Rest Room
Tile: Walls/Floor Condition: Tile out dated. Wall tile has signs of cracking, section need re-grouted. Mis-matched patch. Floor tile holding but out dated
Concreate Floors:
Condition: Several areas have cracks.
Settlement Crack Corner Adjacent Water Fountain
Crack Entering Rest Room
Partitions:
Conditions: Out dated. Finish wearing off. Repaired with mis-matching parts/panels. Repairs remain to latches and latch catches.
Mis-matched Door
Electric:
Condition: Poor. Several outlets not working. Conduits broken. Office area staff has plug adapter in receptacle top leg does not work. Site attendant states he keeps several breaker off do to tripping.
Vending Shelter:
Condition: Needs fascia board replaced and gutter re-hung. Roof Vent replaced.
The facility needs to be re-done. The amount of work will exceed the allotted amount to acquire single quotes. Recommend to bring the facility up to date request finance to hire consultant for estimated cost.
Robert Price Construction Superintendent Project Manager Transportation Cabinet Office of Support Services Design & Construction Section 502-782-2496 502-229-9007