City_of_Beaverton_Waterline_Plans_[Schedule_B].pdf

PDF 30 MB Posted

Attached to
100315 - NW Walker Road - NW 185th Ave to NW 173rd Ave
Solicitation number
2026.011-LUT CPS
Issued by
Washington County, Oregon

About this file

This document is a comprehensive water main construction plan set prepared for the City of Beaverton Water Department and Tualatin Valley Water District (TVWD) in association with the Walker Road Phase 3 project in Washington County, Oregon. The plans detail water main improvements spanning approximately 3.8 miles from NW 185th Avenue to NW 173rd Avenue, including the installation of a 24-inch Non-Potable Transmission Line (NTLI) water main and a 12-inch ductile iron distribution main. The project encompasses multiple construction stages, beginning with Stage I temporary connections and concluding with Stage III final connections and TVWD main abandonment. The plans include 29 sheets of detailed drawings covering water main plans and profiles organized by station (STA 00+00 to STA 38+21.83), connection details, pressure reducing vault specifications, and standard construction details. Key infrastructure elements include blowoff assemblies at low points, air vacuum assemblies at high points, service lateral connections and transfers from TVWD to COB systems, dielectric isolation joints with cathodic protection measures, and coordination with existing utilities including gas, electrical, telecommunications, and sanitary sewer systems.

The project requires strict adherence to Oregon utility notification requirements and the Oregon Utility Notification Center (503-232-1978), with contractors obligated to call 48 hours before excavation using One Call (1-800-332-2344). Water main materials specified include ductile iron pipe (DIP) with various joint types (RJ, ERDIP, ERDIP-TRJ), with minimum cover depths of 36 inches for pipes 12 inches or smaller and 48 inches for larger diameters. Construction must maintain minimum separations between utilities, including 2 feet minimum between water mains and cathodically protected pipes, 8 feet minimum between water and sanitary sewer lines, and 12 inches minimum clearance from gas crossings with fiberglass sheathing for closer distances. The project design stamp is held by Dennis Kessler, P.E. (Oregon License #12836, expires 06/30/2027), with primary project contacts including Jorge Miranda (City of Beaverton Project Manager) and representatives from RH2 Engineering providing technical coordination for all water main installation specifications and field requirements.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXISTING

S D

IV

PROPOSED WATER

X+XX

XXX'

PROPOSED WATER

X+XX

XXX'

PROPOSED ROADWAY

PROFILE VIEW SYMBOLS

RPH

TON

P180

PROFILE VIEW SYMBOLS

RPH

TON

P180

PREPARATION AND DEMO SYMBOLS

X

WALKER ROAD PHASE 3 WATER MAIN

NW 185TH AVENUE TO NW 173RD AVENUE

ROADWAY COORDINATION NOTES

CALL 48 HOURS BEFORE YOU DIG

ONE CALL 1-800-332-2344

ATTENTION: OREGON LAW REQUIRES YOU TO FOLLOW RULES ADOPTED BY THE OREGON UTILITY

NOTIFICATION CENTER. THOSE RULES ARE SET FORTH IN OAR 952-001-0010 THROUGH OAR

952-001-0090. YOU MAY OBTAIN COPIES OF THE RULES BY CALLING THE CENTER AT 503-232-1978.

THESE PLANS ARE INTENDED TO DETAIL THE WATER MAIN IMPROVEMENTS FOR CITY OF

BEAVERTON WATER DEPARTMENT (COB) AND TUALATIN VALLEY WATER DISTRICT (TVWD)

ASSOCIATED WITH THE WALKER ROAD PHASE 3 NW 185TH AVENUE TO NW 173RD AVENUE PROJECT

FOR WASHINGTON COUNTY COUNTY'S DEPARTMENT OF LAND USE AND TRANSPORTATION. SEE

ROADWAY DESIGN PLANS PROVIDED BY 3J CONSULTING FOR ADDITIONAL INFORMATION.

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

G01 1 29

PROJECT LOCATION

WALKER RD.

WASHINGTON COUNTY

BEAVERTON, OR

NW

8T H

AV

E.

SW

5T H

AV

E.

W BASELINE RD.

ABBREVIATIONS

CONTACT PERSONNEL

PROJECT LOCATION MAP LEGEND

W A

TE

R

M A

IN

CO

VE

R A

ND

GE

NE

RA

L IN

FO

RM

AT

IO

N

DRAWING INDEX

SHEET NO. SHEET TITLE STATION DWG NO.

1 COVER AND GENERAL INFORMATION G01

2 CONSTRUCTION NOTES G02

3 WATER MAIN PLAN 1 STA 00+00 TO STA 05+00 W01

4 WATER MAIN PROFILE 1 STA 00+00 TO STA 05+00 W01A

5 WATER MAIN PLAN 2 STA 05+00 TO STA 10+00 W02

6 WATER MAIN PROFILE 2 STA 05+00 TO STA 10+00 W02A

7 WATER MAIN PLAN 3 STA 10+00 TO STA 15+00 W03

8 WATER MAIN PROFILE 3 STA 10+00 TO STA 15+00 W03A

9 WATER MAIN PLAN 4 STA 15+00 TO STA 20+00 W04

10 WATER MAIN PROFILE 4 STA 15+00 TO STA 20+00 W04A

11 WATER MAIN PLAN 5 STA 20+00 TO STA 25+00 W05

12 WATER MAIN PROFILE 5 STA 20+00 TO STA 25+00 W05A

13 WATER MAIN PLAN 6 STA 25+00 TO STA 30+00 W06

14 WATER MAIN PROFILE 6 STA 25+00 TO STA 30+00 W06A

15 WATER MAIN PLAN 7 STA 30+00 TO STA 35+00 W07

16 WATER MAIN PROFILE 7 STA 30+00 TO STA 35+00 W07A

17 WATER MAIN CONNECTION DETAILS W08

18 WATER MAIN CONNECTION PROFILES 1 W08A

19 WATER MAIN CONNECTION PROFILES 2 W09

20 WATER MAIN CONNECTION PROFILES 3 W09A

21 PRESSURE REDUCING VAULT DETAILS 1 W10

22 PRESSURE REDUCING VAULT DETAILS 2 W10A

23 DETAILS 1 DET01

24 DETAILS 2 DET02

25 DETAILS 3 DET03

26 DETAILS 4 DET04

27 DETAILS 5 DET05

28 DETAILS 6 DET06

29 DETAILS 7 DET07

NW

3R D

AV

E.

SURVEY NOTES CONTACT AGENCY PHONE

JORGE MIRANDA (PROJECT MANAGER) CITY OF BEAVERTON (503) 686-4358

CASEY FERGESON (DEPUTY PROJECT MANAGER)CITY OF BEAVERTON (971) 294-2997

DAVID WINSHIP (TECHNICAL ADVISOR) CITY OF BEAVERTON (503) 350-2434

TROY PIERSON (WATER) CITY OF BEAVERTON (503) 246-0223

KYLE PETTIBONE, P.E. RH2 ENGINEERING (503) 446-2816

PATRICK LAU, P.E. RH2 ENGINEERING (503) 446-5949

DENNIS KESSLER, P.E. RH2 ENGINEERING (503) 446-2905

STEPHEN CRUISE WASHINGTON COUNTY (503) 969-2789

HEIDI SPRINGER TVWD (971) 317-6775

TERRENCE WALKER AT&T/PIVOTAL COMMUNICATIONS (360) 882-4268 (125)

TODD DALLOF COMCAST (503) 519-5394

JEREMY NOBLE VERIZON (503) 723-8300

BRIAN DAVIDSON ZAYO (360) 558-4215

STEVE MONIER NW NATURAL (217) 741-4403

SCOTT BINNEY ZIPLY FIBER (503) 643-0371

JOHN GAYLORD WAVE BROADBAND (503) 302-3441

CARL HAYNES LUMEN (541) 409-2083

DEANNA KANESHIRO PORTLAND GENERAL ELECTRIC (503) 201-2713

ABANDON EXISTING COB WATER MAIN OR BRANCH OF FIRE HYDRANT PER DETAIL

COORDINATE SHUTDOWN WITH TVWD.

TRANSFER WATER SERVICE FROM TVWD (TO BE ABANDONED) TO COB WATER MAIN. PROVIDE PROPOSED WATER SERVICE AND ABANDON EXISTING SERVICE LINE WITH ABANDONMENT OF TVWD 12" MAIN, ABANDONMENT OF EXISTING WATER SERVICE AT MAIN IS NOT REQUIRED, SEE SIM. DETAIL ANY WORK TO PRIVATE SERVICE LINES, I.E. BACKSIDE OF THE METER, MUST BE PERFORMED BY A LICENSED PLUMBER.

B

PROVIDE PROTECTIVE GEOMEMBRANE SLEEVE WRAP OR SLEEVE SLIP-ON AT CROSSING OF CATHODICALLY PROTECTED PIPE, SEE MODIFIED

STANDARD DETAILS 680-4 OR 680-5.

CENTER A FULL LENGTH OF PIPE OVER SEWER CROSSING.

REPLACE SANITARY SEWER FOR AT LEAST 9' IN BOTH DIRECTIONS FROM WATER CROSSING WITH EQUAL INSIDE DIAMETER STICK OF PIPE: CLASS 52 DI, SDR 17 HDPE, OR C900 PVC. CONNECT TO EXISTING PIPE PER DETAIL

G

CAP SERVICE LINE WHERE SEVERED AT TEMPORARY/PROPOSED CONNECTION AND ABANDON WITH ABANDONMENT OF TVWD 12" MAIN.

TRANSFER WATER SERVICE FROM TVWD (ACTIVE) TO COB WATER MAIN. PROVIDE PROPOSED WATER SERVICE AND ABANDON EXISTING. ANY WORK TO PRIVATE SERVICE LINES, I.E. BACKSIDE OF THE METER, MUST BE PERFORMED BY A LICENSED PLUMBER.

B

C

WATER MAIN TO BE ABANDONED BY TVWD DURING STAGE III AFTER COB SERVICE AND MAIN TRANSFER CONNECTIONS ARE COMPLETED

ABANDON COB WATER MAIN DURING STAGE I

FIELD VERIFY AND DOCUMENT EXISTING UTILITIES LOCATIONS BEFORE STARTING WATER MAIN INSTALLATION; COORDINATE ANY NECESSARY

ALIGNMENT CHANGES WITH OWNER'S REPRESENTATIVE

ABANDON EXISTING COB WATER MAIN OR BRANCH OF FIRE HYDRANT PER DETAIL

COORDINATE SHUTDOWN WITH TVWD.

TRANSFER WATER SERVICE FROM TVWD (TO BE ABANDONED) TO COB WATER MAIN. PROVIDE PROPOSED WATER SERVICE AND ABANDON EXISTING SERVICE LINE WITH ABANDONMENT OF TVWD 12" MAIN, ABANDONMENT OF EXISTING WATER SERVICE AT MAIN IS NOT REQUIRED, SEE SIM. DETAIL ANY WORK TO PRIVATE SERVICE LINES, I.E. BACKSIDE OF THE METER, MUST BE PERFORMED BY A LICENSED PLUMBER.

B

PROVIDE PROTECTIVE GEOMEMBRANE SLEEVE WRAP OR SLEEVE SLIP-ON AT CROSSING OF CATHODICALLY PROTECTED PIPE, SEE MODIFIED

STANDARD DETAILS 680-4 OR 680-5.

CENTER A FULL LENGTH OF PIPE OVER SEWER CROSSING.

REPLACE SANITARY SEWER FOR AT LEAST 9' IN BOTH DIRECTIONS FROM WATER CROSSING WITH EQUAL INSIDE DIAMETER STICK OF PIPE: CLASS 52 DI, SDR 17 HDPE, OR C900 PVC. CONNECT TO EXISTING PIPE PER DETAIL

G

CAP SERVICE LINE WHERE SEVERED AT TEMPORARY/PROPOSED CONNECTION AND ABANDON WITH ABANDONMENT OF TVWD 12" MAIN.

TRANSFER WATER SERVICE FROM TVWD (ACTIVE) TO COB WATER MAIN. PROVIDE PROPOSED WATER SERVICE AND ABANDON EXISTING. ANY WORK TO PRIVATE SERVICE LINES, I.E. BACKSIDE OF THE METER, MUST BE PERFORMED BY A LICENSED PLUMBER.

B

C

WATER MAIN TO BE ABANDONED BY TVWD DURING STAGE III AFTER COB SERVICE AND MAIN TRANSFER CONNECTIONS ARE COMPLETED

ABANDON COB WATER MAIN DURING STAGE I

FIELD VERIFY AND DOCUMENT EXISTING UTILITIES LOCATIONS BEFORE STARTING WATER MAIN INSTALLATION; COORDINATE ANY NECESSARY

ALIGNMENT CHANGES WITH OWNER'S REPRESENTATIVE

STATION BASE LINE - NW WALKER ROAD

NUMBER

L1

C1

L2

C2

L3

C3

L4

C4

L5

C5

L6

START N,E

(687309.52,7595429.96)

(687172.33,7595655.88)

(687142.92,7595701.76)

(686522.82,7596619.59)

(686475.70,7596695.69)

(686359.91,7596900.47)

(686330.36,7596956.34)

(685995.64,7597634.65)

(685968.68,7597693.47)

(685754.52,7598198.78)

(685664.55,7598368.88)

END N,E

(687172.33,7595655.88)

(687142.92,7595701.76)

(686522.82,7596619.59)

(686475.70,7596695.69)

(686359.91,7596900.47)

(686330.36,7596956.34)

(685995.64,7597634.65)

(685968.68,7597693.47)

(685754.52,7598198.78)

(685664.55,7598368.88)

(685423.74,7598742.80)

START STA

0+00.00

2+64.31

3+18.82

14+26.48

15+16.02

17+51.27

18+14.47

25+70.88

26+35.59

31+84.41

33+77.07

END STA

2+64.31

3+18.82

14+26.48

15+16.02

17+51.27

18+14.47

25+70.88

26+35.59

31+84.41

33+77.07

38+21.83

LENGTH

264.308

54.508

1107.668

89.532

235.251

63.207

756.401

64.719

548.818

192.662

444.754

RADIUS

1125.00

1125.00

1125.00

1125.00

1125.00

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

G02 2 29

W A

TE

R

M A

IN

C

O N

S

TR

U C

TI

O

N N

O

TE

S

STANDARD KEY NOTES

GENERAL NOTES

EXISTING UTILITIES

WATER MAIN ABANDONMENT NOTES

WATER MAIN ABANDONMENT NOTES (CONTINUED)

TVWD SERVICE AND HYDRANT KILLS

WATER MAIN CONSTRUCTION NOTES

WATER MAIN PLAN AND PROFILE ALIGNMENT GENERAL NOTES

NON-BURIED WATER MAIN PIPE COATING NOTES

ALIGNMENT DEFINITION TABLE

212213

NW WALKER ROAD

NW 185TH AVENUE

T IV

IVIV

S S S

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

W

W

FUTURE 24" WATER MAIN

FUTURE 12" WATER MAIN

NW WALKER ROAD CENTERLINE ALIGNMENT,

GENERALLY THE SAME ALIGNMENT AS THE

ROADWAY PLANS "W" LINE, TYP. ALL

SHEETS, SEE DWG G02 FOR ALIGNMENT

DEFINITION TABLE

LOCATE PROPOSED 24" NTLI

WATER MAIN APPROX. 8' FROM

PROPOSED FACE OF CURB, TYP.

0 LF 100 LF

L1

C1

0+00 1+00

2+00 3+00 4+00 5+00

CONSTRUCTION KEY NOTES WATER MAIN NOTES (NTLI) WATER SERVICE NOTESWATER MAIN NOTES (DISTRIBUTION)

SEE DWG G02 FOR STANDARD KEYNOTES.

24" NTLI WATER MAIN SHALL BE DIELECTRICALLY ISOLATED, JOINT

BONDED AND PROVIDED COMPLETE WITH ANODES AND TEST

STATIONS. SEE DWG NO. DET03 AND DET04 FOR MODIFIED

STANDARD DETAILS 680-1 THRU 680-10.

SAWCUT, REMOVE, AND REPLACE ISLAND AND CURB.

STAGE III CONNECTION

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

IS REDUCED TO INSTALL IN A JOINT TRENCH, SEE DETAIL FOR

ADDITIONAL INFORMATION

12 ~

W01 3 29

W A

TE

R

M A

IN

P

LA

N

W

AS

H

IN

G

TO

N

C O

U N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

PLAN VIEW

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

VICINITY MAP

S

TA

0+

T

O S

TA

5+

N W

TH

A

V E

WALKER

ROAD N

W

R D

A V

E

WATER MAIN PROFILE

190'

200'

210'

220'

230'

190'

200'

210'

220'

230'

-415 LF -400 LF -300 LF -200 LF -100 LF 0 LF 83 LF

FUTURE 24" DI

WATER MAIN

FINISHED GRADE

PROPOSED 24" DI

WATER MAIN (NTLI), TYP. ALL

PROFILE SHEETS

CA

P

BL

OW

OF

F

ST

A:

4+

.3IE

: 2

.3

4+15

24" AND 12" WATER MAINS PROFILE VIEW

TE

E

ST

A:

4+

.5IE

: 2

.9

PROPOSED 12" DI

WATER MAIN (DISTRIBUTION),

PROJECTED ON TO 24" WATER

MAIN (NTLI) PROFILE, TYP. ALL

PROFILE SHEETS

DISTANCE ALONG PIPE

APPROX. DESIGN STATIONING

6" MIN.

TE

E, V

AL

VE

C

AP

ST

A:

4+

.5IE

: 2

.9

-0.0%

-0.0%

FUTURE 12" DI

WATER MAIN

4+98

NTLI MAIN - APPROX. 83 LF OF 24" RJ DIP

DISTRIBUTION MAIN - APPROX. 85 LF OF 12" RJ DIP

2" MIN.

2" MIN.

-1.0%

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W01A 4 29

W A

TE

R

M A

IN

P

R O

FI

LE

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

S

TA

0+

T

O S

TA

5+

212 213 214

NW WALKER ROAD

NW 183RD AVENUE

RI

CH

M

ON

D

PA

RK

IV

IV

T

IV

T

T

T

TT

IV

CS

S S

D

D

D

D

STEEL

GATE

S

E E

E E

D

E

PH5

W-1W-7 W-2-2

GAS-1

FIB-2

GAS-2

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

LOCATE PROPOSED 24" NTLI

WATER MAIN APPROX. 5' FROM

PROPOSED CURB LINE

W

100 LF 200 LF 300 LF 400 LF 500 LF

600 LF

L25+00 6+00 7+00 8+00 9+00 10+00

PH5

W-1W-7 W-2-2

GAS-1

FIB-2

GAS-2

24" NTLI WATER MAIN SHALL BE DIELECTRICALLY ISOLATED, JOINT

BONDED AND PROVIDED COMPLETE WITH ANODES AND TEST

STATIONS. SEE MODIFIED STANDARD DETAILS 680-1 THRU 680-10.

CONSTRUCTION KEY NOTES WATER MAIN NOTES (NTLI) WATER MAIN NOTES (DISTRIBUTION)

SERVICE LATERAL IS NOT ACTIVE; COORDINATE WITH TVWD TO

CONFIRM CLOSED VALVE. CUT AND ABANDON WHERE IN CONFLICT

WITH 12" AND 24" DI W.

PROVIDE DIELECTRIC ISOLATION JOINT MATCHING PIPE SIZE WITH

A 5' SPOOL (FLxPE) AT INDICATED LOCATION AND BELOW GRADE

ISOLATION JOINT TEST STATION, SEE MODIFIED STANDARD

DETAILS 680-1, 680-7, AND 680-10.

SEE DWG G02 FOR STANDARD KEYNOTES.

WATER MAIN NOTES (DISTRIBUTION)

TEMPORARY STAGE I CONNECTION, SEE DWG NO. W08 FOR

GENERALIZED DETAIL; FIELD LOCATE CONNECTION TO MINIMIZE

PROPOSED STAGE III RESTORATION AND TRAFFIC IMPACTS.

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

IS REDUCED TO INSTALL IN A JOINT TRENCH, SEE DETAIL FOR

ADDITIONAL INFORMATION

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

MAY BE REDUCED TO INSTALL IN A JOINT TRENCH; HOLD

POSITION OF 24" TRANSMISSION MAIN, SEE DETAIL FOR

ADDITIONAL REQUIREMENTS

POTHOLED GAS APPROX. 51' WEST OF SURVEY LOCATES; BOTH

LINES ARE SHOWN; VERIFY WITH CONSTRUCTION LOCATES.

W02 5 29

W A

TE

R

M A

IN

P

LA

N

W

AS

H

IN

G

TO

N

C O

U N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

PLAN VIEW

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

VICINITY MAP

S

TA

5+

T

O S

TA

0+

N W

TH

A

V E

WALKER

ROAD N

W

R D

A

200'

210'

220'

230'

190'

200'

210'

220'

230'

83 LF 100 LF 200 LF 300 LF 400 LF 500 LF 594 LF

FINISHED GRADE

EXISTING GRADE

4+98 5+15 6+15 7+15 8+15 9+15

DISTANCE ALONG PIPE

APPROX. DESIGN STATIONING

TE

E, V

AL

VE

S

DE

FL

EC

T

JO

IN

T

ST

A:

5+

.8IE

: 2

.3

TE

E

VA

LV

ES

ST

A:

5+

.0IE

: 2

.3

CR

OS

S

VA

LV

E

ST

A:

6+

.5IE

: 2

.0

12"

MIN.

-3.1% 0.0% 4.0%-1.0%

3.5%

10" CONC. ST,

TO BE REMOVED.

SEE ROADWAY PLANS

LO

CA

TE

B

LO

W

OF

F

AT

LO

W

PO

IN

T

OF

W

AT

ER

M

AI

N

HO

RZ

. B

EN

D

ST

A:

9+

.9IE

: 2

.8

HO

RZ

. B

EN

D

ST

A:

7+

.4IE

: 2

.0

HO

RZ

. B

EN

D

ST

A:

7+

.5IE

: 2

.0

0.0% 0.0%

LO

CA

TE

B

LO

W

OF

F

AT

LO

W

PO

IN

T

OF

W

AT

ER

M

AI

N

0.0%

NTLI MAIN - APPROX. 511 LF OF 24" RJ DIP

DISTRIBUTION MAIN - APPROX. 511 LF OF 12" RJ DIP

9+99

LO

CA

TE

B

LO

W

OF

F

AT

LO

W

PO

IN

T

OF

W

AT

ER

M

AI

N

12" MIN.

0.0% 0.0%0.0% 2.0% 0.0% 2.5%

HO

RZ

. B

EN

D

ST

A:

9+

.1IE

: 2

.8

24" AND 12" WATER MAINS PROFILE VIEW

RP

H

TO

N PH

GA

S-

SEE DWG G02 FOR STANDARD KEYNOTES.

DISTRIBUTION MAIN ALIGNMENT DEVIATES FROM

THE NTLI MAIN ALIGNMENT; PROFILE AND EXISTING

UTILITY CROSSINGS MAY VARYPROVIDE 6" MIN. CLEARANCE

BETWEEN COMM AND POWER

CROSSINGS AND DISTRIBUTION MAIN

ON

LY

A T

NT

LI

MA

IN

ON

LY

A T

NT

LI

MA

IN

ON

LY

A T

NT

LI

MA

IN

WATER CROSSING ONLY AT DISTRIBUTION MAIN,

PROVIDE 6" MIN. CLEARANCE BETWEEN WATER AND

DISTRIBUTION MAIN

WATER MAIN PROFILE

200'

210'

220'

200'

210'

220'

-0+25 0+00 0+15

PR

OP

. W

AT

ER

TE

E

PR

OP

. W

AT

ER

CR

OS

SI

NG

APPROX. 11 LF OF 6" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. S

TO

RM

P

VC

IE

: 2

.7±

WATER MAIN PROFILE

200'

210'

220'

200'

210'

220'

-0+15 0+00 0+25

PR

OP

. W

AT

ER

TE

E

PR

OP

. S

TO

RM

P

VC

IE

: 2

.4±

PR

OP

. W

AT

ER

CR

OS

SI

NG

APPROX. 10 LF OF 6" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

WATER MAIN PROFILE

195'

200'

210'

195'

200'

210'

-0+10 0+00 0+25

PR

OP

. S

TO

RM

P

VC

IE

: 2

.3±

PR

OP

. W

AT

ER

CR

OS

SI

NG

PR

OP

. W

AT

ER

CR

OS

SI

NG

APPROX. 15 LF OF 4" RJ DIP

6" MIN.

PR

OP

. W

AT

ER

VA

LV

E

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W02A 6 29

W A

TE

R

M A

IN

P

R O

FI

LE

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

S

TA

5+

T

O S

TA

0+

BLOWOFF PROFILE - STA 5+65 BLOWOFF PROFILE - STA 5+87 BLOWOFF PROFILE - STA 6+23

214214

NW WALKER ROAD

NW 180TH AVENUE

NW 180TH AVENUE

IV

E

E

T

C

T

SS

D

D

4' CL FENCE

PH9

PH8

FIB-4FIB-3

GAS-3

FIB-5

MA

TC

HL

IN

E

MA

TC

HL

IN

E

LOCATE PROPOSED 24" NTLI

WATER MAIN APPROX. 28' FROM

PROPOSED CURB LINE

W

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

W

FOR PROFILE,

SEE DWG NO. W09

600 LF 700 LF 800 LF 900 LF 1000 LF 1100 LF

C210+00 11+00 12+00

13+00 14+00 15+00

PH9

PH8

FIB-4FIB-3

GAS-3

FIB-5

WATER SERVICE NOTES

24" NTLI WATER MAIN SHALL BE DIELECTRICALLY ISOLATED, JOINT

BONDED AND PROVIDED COMPLETE WITH ANODES AND TEST

STATIONS. SEE MODIFIED STANDARD DETAILS 680-1 THRU 680-10.

CONSTRUCTION KEY NOTES WATER MAIN NOTES (NTLI) WATER MAIN NOTES (DISTRIBUTION) WATER MAIN NOTES (DISTRIBUTION)

SEE DWG G02 FOR STANDARD KEYNOTES.

REMOVE AND DISPOSE OF EXISTING HYDRANT AND ABANDON

HYDRANT LATERAL WITH WATER MAIN ABANDONMENT.

INSTALL SERVICE LINE IN PVC CARRIER PIPE UNDER SOUND WALL

BETWEEN SOUND WALL POSTS. ANY WORK TO PRIVATE SERVICE

LINE MUST BE PERFORMED BY A LICENSED PLUMBER.

TEMPORARY STAGE I CONNECTION (WITH 90 DEG BENDS), SEE SIM.

DWG NO. W08 FOR GENERALIZED DETAIL; FIELD LOCATE

CONNECTION TO MINIMIZE PROPOSED STAGE III RESTORATION AND

TRAFFIC IMPACTS.

TEMPORARY STAGE I SERVICE LINE CONNECTION; FIELD LOCATE

CONNECTION TO MINIMIZE PROPOSED STAGE III RESTORATION AND

TRAFFIC IMPACTS.

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

MAY BE REDUCED TO INSTALL IN A JOINT TRENCH; HOLD

POSITION OF 24" TRANSMISSION MAIN, SEE DETAIL FOR

ADDITIONAL REQUIREMENTS

FIELD VERIFY IF 4" BYPASS EXISTS, IF IT EXISTS FIELD ADJUST

CONNECTION TO BE UPSTREAM OF THE BYPASS, I.E. DO NOT

REMOVE BYPASS.

W03 7 29

W A

TE

R

M A

IN

P

LA

N

W

AS

H

IN

G

TO

N

C O

U N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

PLAN VIEW

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

VICINITY MAP

S

TA

0+

T

O S

TA

5+

N W

TH

A

V E

WALKER

ROAD N

W

R D

A

200'

210'

220'

230'

190'

200'

210'

220'

230'

600 LF 700 LF 800 LF 900 LF 1000 LF 1095 LF

EXISTING GRADE

FINISHED GRADE

10+06 11+06 12+06 13+06 14+06 15+00

DISTANCE ALONG PIPE

APPROX. DESIGN STATIONING

1.7%

12" MIN.

CR

OS

S

VA

LV

ES

ST

A:

+5 8.5

IE

: 2

.0

12" MIN.

0.0%

TE

E

VA

LV

ES

ST

A:

+1

9.1I E:

8.2

0.0% 7.0%

6"

MIN.

1.1%

NTLI MAIN - APPROX. 501 LF OF 24" RJ DIP

DISTRIBUTION MAIN - APPROX. 501 LF OF 12" RJ DIP

0.3%

3.6%

1.5% 12" MIN.

2" MIN.

24" AND 12" WATER MAINS PROFILE VIEW

12.5%

FI

B-

FI

B-

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W03A 8 29

W A

TE

R

M A

IN

P

R O

FI

LE

S

TA

0+

T O

S

TA

5+

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

209211

NW WALKER ROAD

NW 180TH AVENUE

E

E C

T

S

S

D

D

D

D D

D D

6' WOOD FENCE

6' W O

O

D FENCE

PH11

W-2

GAS-4

GAS-4.1

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MAINTAIN 8' MIN SEPARATION

BETWEEN SEWER

LOCATE PROPOSED 24" NTLI

WATER MAIN APPROX. 27.2' FROM

PROPOSED CURB LINE

6', TYP.

1100 LF

1200 LF

1300 LF

1400 LF 1500 LF 1600 LF

L3

C3

15+00 16+00

17+00 18+00 19+00 20+00

PH11

W-2

GAS-4

GAS-4.1

24" NTLI WATER MAIN SHALL BE DIELECTRICALLY ISOLATED, JOINT

BONDED AND PROVIDED COMPLETE WITH ANODES AND TEST

STATIONS. SEE MODIFIED STANDARD DETAILS 680-1 THRU 680-10.

CONSTRUCTION KEY NOTES WATER MAIN NOTES (NTLI) WATER SERVICE NOTESWATER MAIN NOTES (DISTRIBUTION)

PROVIDE DIELECTRIC ISOLATION JOINT MATCHING PIPE SIZE AT

INDICATED LOCATION AND BELOW GRADE ISOLATION JOINT TEST

STATION, SEE MODIFIED STANDARD DETAILS 680-1, 680-7, 680-10.

SEE DWG G02 FOR STANDARD KEYNOTES.

REMOVE METER BOX AND RESTORE SURFACE. INSTALL METER

BOX BEHIND CURB AND EXTEND BACKPIPE TO CONNECT AT

EXISTING METER LOCATION. ANY WORK ON THE PRIVATE SIDE OF

THE WATER SERVICE OR OUTSIDE OF THE ROW SHALL BE

PERFORMED BY A LICENSED PLUMBER AND REQUIRES A PRIVATE

PLUMBING PERMIT.

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

IS REDUCED TO INSTALL IN A JOINT TRENCH, SEE DETAIL FOR

ADDITIONAL INFORMATION

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

MAY BE REDUCED TO INSTALL IN A JOINT TRENCH; HOLD

POSITION OF 24" TRANSMISSION MAIN, SEE DETAIL FOR

ADDITIONAL REQUIREMENTS

W04 9 29

W A

TE

R

M A

IN

P

LA

N

W

AS

H

IN

G

TO

N

C O

U N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

PLAN VIEW

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

VICINITY MAP

S

TA

5+

T

O S

TA

0+

N W

TH

A

V E

WALKER

ROAD N

W

R D

A

200'

210'

220'

230'

190'

200'

210'

220'

230'

1100 LF 1200 LF 1300 LF 1400 LF 1500 LF 1595 LF

PR

OP

. S

TO

RM

P

VC

OU

TS

ID

E

TO

P

EL

: 2

.4±

EXISTING GRADE

FINISHED GRADE

15+05 16+05 17+05 18+05 19+04 19+99

DISTANCE ALONG PIPE

APPROX. DESIGN STATIONING

-5.0%

-2.3%

12" MIN.

LO

CA

TE

A

IR

V

AC

A

T

HI

GH

PO

IN

T

OF

W

AT

ER

M

AI

N

LO

CA

TE

A

IR

V

AC

A

T

HI

GH

PO

IN

T

OF

W

AT

ER

M

AI

N

DI

EL

EC

TR

IC

IS

OL

AT

IO

N

JO

IN

T

ST

A:

+9 7.2

IE

: 2

.8

1.7% 0.2% -0.8%

0.4% 0.3% -0.6%

-1.9%

-3.8%

LO

CA

TE

A

IR

V

AC

A

T

HI

GH

PO

IN

T

OF

W

AT

ER

M

AI

N

-3.6%

NTLI MAIN - APPROX. 500 LF OF 24" RJ DIP

DISTRIBUTION MAIN - APPROX. 500 LF OF 12" RJ DIP

VA

LV

E

ST

A:

+9 0.7

IE

: 2

.7

12" MIN.

12", MIN.

12" MIN.

VERIFY DEPTH OF

RELOCATED GAS

24" AND 12" WATER MAINS PROFILE VIEW

-4.1%

GA

S-

SEE DWG G02 FOR STANDARD KEYNOTES.

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W04A 10 29

W A

TE

R

M A

IN

P

R O

FI

LE

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

S

TA

5+

T

O S

TA

0+

209 185

18818

NW WALKER ROAD

NW

8T H

AV

E

CE

T

C C

S S

C

NW

C

AM

BR

AY

ST

RE

ET

PH14

PH17

PH19

PH17

W-3 W-4

W-8

GAS-5 GAS-6

GAS-7

FIB-6

FIB-7

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

W

W

W

W

LOCATE PROPOSED 24" NTLI

WATER MAIN APPROX. 11'

FROM PROPOSED CURB LINE

LOCATE PROPOSED 24" NTLI

WATER MAIN APPROX. 28.6' FROM

PROPOSED CURB LINE

PROVIDE 5' MIN.

SEPARATION

PROVIDE 5' MIN. FROM WALL OF

PROPOSED 24" WATER MAIN TO WALL

OF EXISTING 12" WATER MAIN

SAWCUT LINE, LIMITS OF WALKER

ROAD IMPROVEMENTS, TYP,

FOR PROFILE, SEE DWG NO. W09

1600 LF 1700 LF 1800 LF 1900 LF 2000 LF

2100 LF

LF

0 L

F

L420+00 21+00 22+00 23+00 24+00 25+00

PH14

PH17

PH19

PH17

W-3 W-4

W-8

GAS-5 GAS-6

GAS-7

FIB-6

FIB-7

WATER SERVICE NOTES

CONSTRUCTION KEY NOTES WATER MAIN NOTES (NTLI) WATER MAIN NOTES (DISTRIBUTION) WATER MAIN NOTES (DISTRIBUTION)

COORDINATE WITH TVWD TO ABANDON THE EXISTING 12" EAST OF NW

CAMBRAY STREET AND WEST OF NW 174TH TERRACE TO INSTALL COB

PIPELINES AND TO OBTAIN APPROVAL IF NECESSARY TO REMOVE

PORTIONS OF THE EXISTING TVWD WATER MAIN TO BE ABANDONED IN

CONFLICT WITH THE PROPOSED COB WATER MAIN.

24" NTLI WATER MAIN SHALL BE DIELECTRICALLY ISOLATED, JOINT

BONDED AND PROVIDED COMPLETE WITH ANODES AND TEST

STATIONS. SEE MODIFIED STANDARD DETAILS 680-1 THRU 680-10.

SEE DWG G02 FOR STANDARD KEYNOTES.

REMOVE AND DISPOSE OF EXISTING HYDRANT AND ABANDON

HYDRANT LATERAL WITH WATER MAIN ABANDONMENT.

INSTALL SERVICE LINE IN PVC CARRIER PIPE UNDER SOUND WALL

BETWEEN SOUND WALL POSTS. ANY WORK TO PRIVATE SERVICE

LINE MUST BE PERFORMED BY A LICENSED PLUMBER.

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

MAY BE REDUCED TO INSTALL IN A JOINT TRENCH; HOLD

POSITION OF 24" TRANSMISSION MAIN, SEE DETAIL FOR

ADDITIONAL REQUIREMENTS

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

IS REDUCED TO INSTALL IN A JOINT TRENCH, SEE DETAIL FOR

ADDITIONAL INFORMATION

REMOVE ABANDONED SERVICE METER AND BOX; ABANDON SERVICE LINE

WITH TVWD MAIN.

TEMPORARY STAGE I CONNECTION, SEE DWG NO. W08 FOR

GENERALIZED DETAIL; FIELD LOCATE CONNECTION TO MINIMIZE

PROPOSED STAGE III RESTORATION AND TRAFFIC IMPACTS.

W05 11 29

W A

TE

R

M A

IN

P

LA

N

W

AS

H

IN

G

TO

N

C O

U N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

PLAN VIEW

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

VICINITY MAP

S

TA

0+

T

O S

TA

5+

N W

TH

A

V E

WALKER

ROAD N

W

R D

A

170'

180'

190'

200'

210'

220'

170'

180'

190'

200'

210'

220'

1600 LF 1700 LF 1800 LF 1900 LF 2000 LF 2100 LF

PR

OP

. S

TO

RM

P

VC

IE

: 1

.4±

PR

OP

. S

TO

RM

P

VC

IE

: 1

.3±

EXISTING GRADE

FINISHED GRADE

20+04 21+04 22+04 23+04 24+04 25+00

DISTANCE ALONG PIPE

APPROX. DESIGN STATIONING

-5.0%

6" MIN.

HO

RZ

. B

EN

D

ST

A:

+1 9.9

IE

: 1

.9

HO

RZ

. B

EN

D

ST

A:

+7 2.4

IE

: 1

.4

12" MIN.

12"

MIN.

VE

RT

. B

EN

D, C

RO

SS

V

AL

VE

S

ST

A:

+9 6.2

IE

: 1

.3

12" MIN.

6" MIN.

HO

RZ

. B

EN

D

ST

A:

+7 4.8

IE

: 1

.7

HO

RZ

. B

EN

D

ST

A:

+2 5.5

IE

: 1

.8

PR

OP

. T

VW

D W

AT

ER

TO

P:

4.0

-5.2%

VE

RT

. B

EN

D

ST

A:

+1 4.3

IE

: 1

.5

VE

RT

. B

EN

D

ST

A:

+3 5.2

IE

: 1

.8

-4.9%

-4.1%

-22.5%

0.0% -5.2% -1.0%

-5.9%

-3.6%

-7.4%

-8.1%

-2.6%

NTLI MAIN - APPROX. 505 LF OF 24" RJ DIP

DISTRIBUTION MAIN - APPROX. 505 LF OF 12" RJ DIP

-4.3%

-6.7%

-11.6%

18" MIN.

-3.4%

-4.2%

-7.5%

18" MIN.

18" MIN.

LO

CA

TE

B

LO

W

OF

F

AT

LO

W

PO

IN

T

OF

W

AT

ER

M

AI

N

6" MIN.

-2.5%

2" MIN.

24" AND 12" WATER MAINS PROFILE VIEW

RP

H

FI

B-

SEE DWG G02 FOR STANDARD KEYNOTES.

-2.3%

172'

180'

190'

172'

180'

190'

-0+15 0+00 0+25

PR

OP

. S

TO

RM

P

VC

IE

: 1

.6±

PR

OP

. W

AT

ER

TE

E

PR

OP

. W

AT

ER

CR

OS

SI

NG

APPROX. 13 LF OF 6" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W05A 12 29

W A

TE

R

M A

IN

P

R O

FI

LE

S

TA

0+

T O

S

TA

5+

BLOWOFF PROFILE - STA 24+76

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

180185 179 179181

182183

186 NW WALKER ROAD TPTP

W

ILLO

W C

R

EEK

S

S

S

PH21

PH22

W-4 W-5

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

LOCATE PROPOSED 24" NTLI WATER

MAIN ALIGNED APPROX. 11' FROM

PROPOSED CURB LINE

PROPOSED CULVERT, SEE

ROADWAY PLANS FOR DETAILS

2100 LF

2200 LF 2300 LF 2400 LF 2500 LF 2600 LF

L5C4

25+00 26+00 27+00 28+00 29+00 30+00

PH21

PH22

W-4 W-5

24" NTLI WATER MAIN SHALL BE DIELECTRICALLY ISOLATED, JOINT

BONDED AND PROVIDED COMPLETE WITH ANODES AND TEST

STATIONS. SEE MODIFIED STANDARD DETAILS 680-1 THRU 680-10.

CONSTRUCTION KEY NOTES WATER MAIN NOTES (NTLI) WATER SERVICE NOTESWATER MAIN NOTES (DISTRIBUTION)

APPROX. EXTENT OF CELLULAR CONCRETE FILL AREA, SEE

ROADWAY PLANS FOR DETAILS. WITHIN PIPE ZONE AND BACKFILL

AREAS OF WATER MAIN TRENCH USE MATERIALS PER MODIFIED

STANDARD DETAIL 620-1; DO NOT BED OR BACKFILL WATER MAIN

PIPE ZONE WITH CELLULAR CONCRETE.

SEE DWG G02 FOR STANDARD KEYNOTES.

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

MAY BE REDUCED TO INSTALL IN A JOINT TRENCH; HOLD

POSITION OF 24" TRANSMISSION MAIN, SEE DETAIL FOR

ADDITIONAL REQUIREMENTS

PGE UTILITY PLANNED TO BE RELOCATED, VERIFY PROPOSED

LOCATION AND DEPTH

J

W06 13 29

W A

TE

R

M A

IN

P

LA

N

W

AS

H

IN

G

TO

N

C O

U N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

PLAN VIEW

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

VICINITY MAP

S

TA

5+

T

O S

TA

0+

N W

TH

A

V E

WALKER

ROAD N

W

R D

A

12" MIN.

155'

160'

170'

180'

190'

155'

160'

170'

180'

190'

2100 LF 2200 LF 2300 LF 2400 LF 2500 LF 2600 LF

OUTSIDE TOP OF CULVERT

STA:24+48.08

ELEV:170.87

12" CONC. ST,

TO BE REMOVED.

SEE ROADWAY PLANS

FINISHED GRADE

EXISTING GRADE

25+00 25+99 26+99 27+99 28+99 29+98

DISTANCE ALONG PIPE

APPROX. DESIGN STATIONING

PR

OP

. S

TO

RM

P

VC

IE

: 1

.2±

PROPOSED

CULVERT, SEE

ROADWAY

PLANS FOR

DETAILS

PR

OP

. S

TO

RM

P

VC

IE

: 1

.2±

-0.1%

TE

E

VA

LV

E

ST

A:

+8

4.7

IE

: 1

.4

0.0% 1.5%

-2.1%

-2.5%

LO

CA

TE

B

LO

W

OF

F

AT

LO

W

PO

IN

T

OF

W

AT

ER

M

AI

N

LO

CA

TE

B

LO

W

OF

F

AT

LO

W

PO

IN

T

OF

W

AT

ER

M

AI

N

-0.5%

-0.1% -1.9%

0.1%

NTLI MAIN - APPROX. 25 LF OF 24" RJ DIP

DISTRIBUTION MAIN - APPROX. 500 LF OF 12" RJ DIP

NTLI MAIN - APPROX. 144 LF OF 24" ERDIP

12" MIN.

3.3%

NTLI MAIN - APPROX. 331 LF OF 24" ERDIP-TRJ

2.0%

3.9%

24" AND 12" WATER MAINS PROFILE VIEW

APPROX. 12 LF PROPOSED ROADWAY

CELLULAR CONCRETE FILL AREA

VERIFY DEPTH IF NOT RELOCATED AS

PART OF CULVERT REPLACEMENT WORK

-2.6%

-0.4%

WATER MAIN PROFILE

165'

170'

180'

165'

170'

180'

-0+15 0+00 0+30

PR

OP

. W

AT

ER

TE

E

6" MIN.

PR

OP

. W

AT

ER

TE

E

BLOWOFF ON 24"

TRANSMISSION MAIN

SHOWN IN BACKGROUND

APPROX. 19 LF OF 4" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

VA

LV

E

APPROX. 13 LF OF 6" RJ DIP

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W06A 14 29

W A

TE

R

M A

IN

P

R O

FI

LE

S

TA

5+

T O

S

TA

0+

BLOWOFF PROFILE - STA 28+00

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

18518

186 187

NW WALKER ROAD

NW

4T H

TE

RR

AC

E

T

C

EM

T

S

NW WALKER RD

W-6

FIB-1

GAS-8

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

MA

TC

HL

IN

E

W

W

LOCATE PROPOSED 24" NTLI WATER

MAIN ALIGNED APPROX. 11' FROM

PROPOSED CURB LINE

LIMIT OF ROADWAY

IMPROVEMENTS

SAWCUT LINE, SEE

ROADWAY PLANS

LOCATE PROPOSED 24" NTLI WATER

MAIN ALIGNED APPROX. 5' FROM

PROPOSED CURB LINE

NTLI SEGMENT 1 WATER

MAINS, VERIFY LOCATION

AND ELEVATION OF

CONNECTION POINT BEFORE

STARTING WATER MAIN

CONSTRUCTION; REMOVE

TEMPORARY CAP AND

BLOW-OFF AS NECESSARY TO

MAKE CONNECTION.

2600 LF 2700 LF 2800 LF

2900 LF

3000 LF

3100 LF

C5 30+00 31+00 32+00

33+00

34+00

35+00

W-6

FIB-1

GAS-8

24" NTLI WATER MAIN SHALL BE DIELECTRICALLY ISOLATED, JOINT

BONDED AND PROVIDED COMPLETE WITH ANODES AND TEST

STATIONS. SEE MODIFIED STANDARD DETAILS 680-1 THRU 680-10.

CONSTRUCTION KEY NOTES WATER MAIN NOTES (NTLI) WATER SERVICE NOTESWATER MAIN NOTES (DISTRIBUTION)

CATCH BASIN TO BE REMOVED, SEE ROADWAY PLANS FOR

DETAILS AND COORDINATE REMOVAL WITH ROADWAY WORK

PROVIDE DIELECTRIC ISOLATION JOINT MATCHING PIPE SIZE AT

INDICATED LOCATION AND BELOW GRADE ISOLATION JOINT TEST

STATION, SEE MODIFIED STANDARD DETAILS 680-1, 680-7, 680-10.

SEE DWG G02 FOR STANDARD KEYNOTES.

SEPARATION BETWEEN TRANSMISSION AND DISTRIBUTION MAINS

MAY BE REDUCED TO INSTALL IN A JOINT TRENCH; HOLD

POSITION OF 24" TRANSMISSION MAIN, SEE DETAIL FOR

ADDITIONAL REQUIREMENTS

TEMPORARY STAGE I SERVICE LINE CONNECTION; FIELD LOCATE

CONNECTION TO MINIMIZE PROPOSED STAGE III RESTORATION AND

TRAFFIC IMPACTS.

W07 15 29

W A

TE

R

M A

IN

P

LA

N

W

AS

H

IN

G

TO

N

C O

U N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

PLAN VIEW

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

VICINITY MAP

S

TA

0+

T

O S

TA

5+

N W

TH

A

V E

WALKER

ROAD N

W

R D

A

160'

170'

180'

190'

200'

160'

170'

180'

190'

200'

2600 LF 2700 LF 2800 LF 2900 LF 3000 LF 3100 LF

FINISHED GRADE

EXISTING GRADE

29+98 30+98 31+99 33+01

DISTANCE ALONG PIPE

APPROX. DESIGN STATIONING

12"

MIN.

TE

E

VA

LV

ES

ST

A:

+6

6.5

IE

: 1

.3

12"

MIN.

6" MIN.

LO

CA

TE

A

IR

V

AC

A

T

HI

GH

PO

IN

T

OF

W

AT

ER

M

AI

N

LO

CA

TE

A

IR

V

AC

A

T

HI

GH

PO

IN

T

OF

W

AT

ER

M

AI

N

3.3%

4.5%

3.0% 0.0%

4.0%

2.5% 0.0%

NTLI MAIN - APPROX. 148 LF OF 24" RJ DIP

DISTRIBUTION MAIN - APPROX. 392 LF OF 12" RJ DIP

12" MIN.

LIMIT OF

ROADWAY

IMPROVEMENTS

NTLI MAIN - APPROX. 246 LF OF 24" ERDIP-TRJ

2.0%

2.9%

24" AND 12" WATER MAINS PROFILE VIEW

NTLI SEGMENT 1

WATER MAINS

APPROX. 23 LF

FROM CARV

TO

N

GA

S-

FI

B-

TV

W

D

CO

MB

IN

AT

IO

N

AI

R

VA

LV

E

TV

W

D

LO

CA

TE

S

ST

AT

IO

N

TV

W

D

SA

MP

LIN

G

ST

AT

IO

N

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W07A 16 29

W A

TE

R

M A

IN

P

R O

FI

LE

0" 1/2" 1"

DRAWING IS FULL SCALE WHEN

BAR MEASURES 1"

SCALE:SHOWN

S

TA

0+

T

O S

TA

5+

8" D

I W

8" D

I W

DI

W

DI

W

W08 17 29

W A

TE

R

M A

IN

C

O N

N E

C

TI

O N

D E

TA

IL

S

GENERALIZED 8" PROPOSED CONNECTION

TO EXISTING 8" WATER MAIN

EXISTING

WATERLINE PIPE PER PLAN

TEMPORARY CAP W/

BLOW-OFF AND

TESTING ASSEMBLY

AND THRUST BLOCK

ABANDON EXISTING MAIN; REMOVE

ABANDONED MAIN OR SERVICE LINE

WHERE IN NEW STREET SUBGRADE OR IN

CONFLICT WITH OTHER FACILITIES, CAP

ENDS OF PIPE REMAINING IN GROUND

STRADDLE BLOCK, FIELD LOCATE WITH

CITY APPROVAL CLEAR OF EXISTING

UTILITIES ON SAME EXISTING PIPE AS

PROPOSED CONNECTION

A) FOR CI WATER MAINS: SEE

STRADDLE THRUST BLOCKING AND TIE

RODS DETAIL ON DWG DET06

B) FOR DI WATER MAINS: SEE COB

MODIFIED STANDARD DETAIL 630-8

8" DI 45° BEND (RJxRJ), LOCATE AND ROLL TO

ACHIEVE VERTICAL AND

HORIZONTAL ALIGNMENT

BEGIN CONNECTION

TO EXISTING

8" DI 45° BEND (RJxRJ), LOCATE

AND ROLL TO ACHIEVE VERTICAL

AND HORIZONTAL ALIGNMENT

8" DI SPOOL,

LENGTH TO FIT

8" DI SPOOL,

LENGTH TO FIT

THRUST BLOCKS

AS REQUIRED

1A 7AGENERALIZED 8" PROPOSED CONNECTION

TO EXISTING 6" OR 4" WATER MAIN

FINAL CONFIGURATIONTESTING CONFIGURATION

EXISTING

WATERLINE

PIPE PER PLAN

TEMPORARY CAP

W/ BLOW-OFF AND

TESTING ASSEMBLY

AND THRUST BLOCK DI 45° BEND (RJxRJ), LOCATE AND ROLL TO

ACHIEVE VERTICAL AND

HORIZONTAL ALIGNMENT

DI 45° BEND (RJxRJ), LOCATE AND

ROLL TO ACHIEVE VERTICAL AND

HORIZONTAL ALIGNMENT

DI SPOOL,

LENGTH TO FIT

DI SPOOL,

LENGTH TO FIT

6A 11A

STRADDLE BLOCK, FIELD LOCATE WITH

CITY APPROVAL CLEAR OF EXISTING

UTILITIES ON SAME EXISTING PIPE AS

PROPOSED CONNECTION

A) FOR CI WATER MAINS: SEE STRADDLE

THRUST BLOCKING AND TIE RODS DETAIL

ON DWG DET06

B) FOR DI WATER MAINS: SEE COB

MODIFIED STANDARD DETAIL 630-8

BEGIN CONNECTION

TO EXISTING

A) FOR CI WATER MAINS:

LONG BODY SLEEVE (MJxRJ)

OR COUPLING WHERE SLEEVE

DOES NOT FIT OD OF CIP

B) FOR DI WATER MAINS:

LONG BODY SLEEVE (RJxRJ)

FINAL CONFIGURATIONTESTING CONFIGURATION

NOTE: EXISTING UTILITIES NOT SHOWN ON GENERAL

CONNECTION DETAILS. SEE PLAN AND CONNECTION

PROFILES FOR EXISTING UTILITIES AT CONNECTIONS.

DI SPOOL,

LENGTH TO FIT

DI FITTING,

PER PLAN

NOTE: EXISTING UTILITIES NOT SHOWN ON GENERAL

CONNECTION DETAILS. SEE PLAN AND CONNECTION

PROFILES FOR EXISTING UTILITIES AT CONNECTIONS.

5A

12A

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

2A

8A

9A

A) FOR CI WATER MAINS:

LONG BODY SLEEVE (MJxRJ)

OR COUPLING WHERE SLEEVE

DOES NOT FIT OD OF CIP

B) FOR DI WATER MAINS:

LONG BODY SLEEVE (RJxRJ)

GENERALIZED TEMPORARY STAGE I AND

FINAL/STATE III CONNECTION

STAGE I CONFIGURATIONEXISTING CONFIGURATION FINAL/STAGE III CONFIGURATION

PIPE PER PLAN

TEMPORARY

THRUST BLOCKING

AS REQUIRED

SIZE TO MATCH EXISTING TVWD LATERAL;

PROVIDE REDUCER AS NECESSARY

A) FOR CI WATER MAINS: LONG BODY

SLEEVE (MJxRJ) OR COUPLING WHERE

SLEEVE DOES NOT FIT OD OF CIP

B) FOR DI WATER MAINS:

LONG BODY SLEEVE (RJxRJ)

8" DI 45° BEND (RJxRJ), LOCATE AND

ROLL TO ACHIEVE VERTICAL AND

HORIZONTAL ALIGNMENT

8" DI 45° BEND (RJxRJ), LOCATE

AND ROLL TO ACHIEVE VERTICAL

AND HORIZONTAL ALIGNMENT

8" DI PIPE,

LENGTH TO FIT

EXISTING

WATERLINE

8" DI LONG BODY SLEEVE (RJxRJ), WITH SPACER RING

PIPE PER PLAN

REMOVE TEMPORARY CONNECTION AND THRUST

BLOCKING; ABANDON TVWD EXISTING MAIN AND

VALVES. REMOVE ANY SECTIONS IN CONFLICT WITH

SUBGRADE OR OTHER UTILITIES. CAP ENDS OF PIPE

REMAINING IN GROUND

ABANDON EXISTING MAIN; REMOVE

ABANDONED MAIN OR SERVICE LINE

WHERE IN NEW STREET SUBGRADE OR IN

CONFLICT WITH OTHER FACILITIES, CAP

ENDS OF PIPE REMAINING IN GROUND

ABANDON EXISTING MAIN; REMOVE

ABANDONED MAIN OR SERVICE LINE

WHERE IN NEW STREET SUBGRADE OR IN

CONFLICT WITH OTHER FACILITIES, CAP

ENDS OF PIPE REMAINING IN GROUND

COORDINATE WITH TVWD

TO CLOSE VALVE

200'

210'

220'

200'

210'

220'

-0+42 0+00 0+08

1A

EXISTING AND

FINISHED GRADE

PR

OP

. W

AT

ER

TE

E

AN

D

VA

LV

ES

PR

OP

. W

AT

ER

CR

OS

SI

NG

APPROX. 13 LF OF 8" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

2" MIN.

APPROX. 16 LF OF 8" RJ DIP

TO

N

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

WATER MAIN PROFILE

195'

200'

210'

195'

200'

210'

-0+92 0+00 0+08

FINISHED GRADEEXISTING GRADE

5A

PR

OP

. S

TO

RM

P

VC

IE

: 2

.1±

PR

OP

. W

AT

ER

CR

OS

S

VA

LV

ES

2" MIN.

2" MIN.

APPROX. 15 LF OF 6" RJ DIP

PR

OP

. W

AT

ER

RE

DU

CE

R

PR

OP

. W

AT

ER

CR

OS

SI

NG

PR

OP

. W

AT

ER

VA

LV

E

APPROX. 63 LF OF 8" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

RP

H

6"

MIN.

PROVIDE SAND CUSHION

WHERE CLEARANCE FROM

GAS MAIN IS LESS THAN 1'

2" MIN.

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

GA

S-

FI

B-

195'

200'

210'

195'

200'

210'

-0+10 0+00 0+76

PROP VAULT

PER PLAN

EXISTING GRADE

FINISHED GRADE

PR

OP

. S

TO

RM

P

VC

IE

: 2

.6±

PR

OP

. S

TO

RM

P

VC

IE

: 2

.1±

PR

OP

. W

AT

ER

CR

OS

S

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

TE

E

VA

LV

ES

PR

OP

. W

AT

ER

TE

E

VA

LV

ES

APPROX. 27 LF OF 12" RJ DIP APPROX. 23 LF

OF 12" RJ DIP

6" MIN.

PR

OP

. W

AT

ER

TE

E

VA

LV

ES

PIPE AND FITTINGS

PER DETAIL

PR

OP

. W

AT

ER

TE

E

VA

LV

ES

200'

210'

220'

200'

210'

220'

-0+10 0+00 0+60

6A SIM.

EXISTING GRADE

FINISHED GRADE

EX. VAULT

PER PLAN

PR

OP

. W

AT

ER

TE

E

VA

LV

ES

PR

OP

. W

AT

ER

CR

OS

SI

NG

12" MIN.

APPROX. 13 LF OF 8" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

APPROX. 33 LF OF 8" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

TO

N

195'

200'

210'

195'

200'

210'

-0+17 0+00 0+32

PR

OP

. W

AT

ER

CR

OS

SI

NG

PR

OP

. W

AT

ER

TE

E

6" MIN.

2A SIM.

APPROX. 9 LF OF 12" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

APPROX. 6 LF OF 12" RJ DIP

FINISHED GRADE

EXISTING GRADE

W08A 18 29

W A

TE

R

M A

IN

C

O N

N E

C

TI

O N

P R

O

FI

LE

S

CONNECTION PROFILE - STA 4+191

CONNECTION PROFILE - STA 6+715

CONNECTION PROFILE - STA 5+60 AND 5+803

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

CONNECTION PROFILE - STA 10+196

CONNECTION PROFILE - STA 4+912

180'

190'

200'

180'

190'

200'

-1+00 0+00 1+00 1+45

9A SIM.

PR

OP

. W

AT

ER

RE

DU

CE

R

PR

OP

. W

AT

ER

TE

E

PR

OP

. W

AT

ER

CR

OS

S

VA

LV

ES

6" MIN.

PR

OP

. W

AT

ER

ST

A:

0+

.3

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

VE

RT

. B

EN

D

PR

OP

. W

AT

ER

PL

UG

PR

OP

. S

TO

RM

P

VC

IE

: 1

.9±

PR

OP

. S

TO

RM

P

VC

IE

: 1

.3±

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. S

TO

RM

R

CP

IE

: 1

.1±

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

6" MIN.

APPROX. 120 LF OF 8" RJ DIPAPPROX. 66 LF OF 8" RJ DIP

12" MIN.

APPROX. 23 LF OF 6" RJ DIP

12" MIN.

6" MIN.

12" MIN.

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

TE

E

PR

OP

. W

AT

ER

VA

LV

E

RP

H

2"

MIN.

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

GA

S-

FI

B-

200'

210'

220'

200'

210'

220'

-1+30 -1+00 0+00 0+65

8A

EXISTING GRADE

FINISHED GRADE

7A

PROP. PARALLEL STORM,

SHOWN IN BACKGROUND,

CROSSING HYDRANT

PR

OP

. W

AT

ER

CR

OS

S

VA

LV

ES

PR

OP

. W

AT

ER

TE

E

PR

OP

. W

AT

ER

RE

DU

CE

R

PR

OP

. W

AT

ER

BE

ND

PR

OP

. W

AT

ER

BE

ND PR

OP

. W

AT

ER

BE

ND

PR

OP

. W

AT

ER

BE

ND

12" MIN. 3" MIN.

APPROX. 14 LF OF 8" RJ DIPAPPROX. 22 LF OF 6" RJ DIP

2.5' COVER

MIN.

PR

OP

. W

AT

ER

BE

ND

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

CR

OS

SI

NG

APPROX. 59 LF OF 8" RJ DIP APPROX. 38 LF OF 8" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

TO

N

2"

MIN.

6"

MIN.

PROVIDE SAND CUSHION

WHERE CLEARANCE FROM

GAS MAIN IS LESS THAN 1'

PR

OP

. W

AT

ER

DE

FL

EC

T

JO

IN

T

GA

S-

FI

B-

W09 19 29

W A

TE

R

M A

IN

C

O N

N E

C

TI

O N

P R

O

FI

LE

S

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

CONNECTION PROFILE - STA 22+979

CONNECTION PROFILE - STA 14+32 AND STA 14+737 8

175'

180'

190'

175'

180'

190'

-0+40 0+00 0+50

PR

OP

. W

AT

ER

CR

OS

SI

NG

PR

OP

. W

AT

ER

RE

DU

CE

R

FINISHED

GRADE

12" MIN.

11A

PR

OP

. W

AT

ER

TE

E

VA

LV

E

EXISTING

WATER,

TYP.

12A

8"

MIN.

APPROX. 16 LF OF 6" RJ DIPAPPROX. 19 LF OF 6" RJ DIP

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

VA

LV

E

PR

OP

. W

AT

ER

RE

DU

CE

R

APPROX. 22 LF OF 8" RJ DIP

TO

N

WATER MAIN PROFILE

165'

170'

180'

165'

170'

180'

-0+15 0+00 0+35

PR

OP

. W

AT

ER

CR

OS

SI

NGPR

OP

. W

AT

ER

TE

E

VA

LV

E

APPROX. 19 LF OF 6" RJ DIP

PR

OP

. S

TO

RM

P

VC

OU

TS

ID

E

TO

P

EL

: 1

.2±

6" MIN.

W09A 20 29

W A

TE

R

M A

IN

C

O N

N E

C

TI

O N

P R

O

FI

LE

S

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

CONNECTION PROFILE - STA 33+6611HYDRANT PROFILE - STA 29+85 10 12

3" AND LARGER BYPASS

PLAN

ELEVATION

4A

MAIN RUN

8"x3" PRESSURE REDUCING STATION4

PRESSURE GAUGE ASSEMBLY

W10 21 29

P R

E S

S U

R E

R E

D U

C

IN

G V

A U

LT

D

E

TA

IL

S

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

HYDRAULIC GENERATOR TAP ASSEMBLY

HYDRAULIC SUMP EJECTOR DETAIL

PLAN

ELEVATION

VAULT INSTALLATION DETAIL 4A

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

W10A 22 29

P R

E S

S U

R E

R E

D U

C

IN

G V

A U

LT

D

E

TA

IL

S

TYPE 1

PIPE PENETRATION MECHANICAL SEAL

APPLICATION MATRIX

TABLE A: PIPE SUPPORT DESIGN CRITERIA

TYPE A - FLANGE SUPPORT TYPE C - SADDLE CLAMP SUPPORT

PS1 - STANDON PIPE SUPPORT

PIPE STANCHION DETAIL

CONDUIT VAULT PENETRATION DETAIL102

WHERE SPECIFIED ON PLANS OR

REQUIRED IN THE FIELD, PROVIDE 1"

TEMPORARY THREADED TAP AND BLEED

VALVE AT PIPE CROWN TO EVACUATE AIR

DURING TESTING. AT THE CONCLUSION

OF TESTING, REMOVE BLEED VALVE AND

REPLACE WITH BRASS PLUG.

DIP, SIZE TO

MATCH MAINLINE

TAPE WRAP GALV PIPE WITH WAX TAPE SYSTEM.

WHERE SPECIFIED ON PLANS OR

REQUIRED IN THE FIELD, PROVIDE 1"

TEMPORARY THREADED TAP AND BLEED

VALVE AT PIPE CROWN TO EVACUATE AIR

DURING TESTING. AT THE CONCLUSION

OF TESTING, REMOVE BLEED VALVE AND

REPLACE WITH BRASS PLUG.

DIP, SIZE TO

MATCH MAINLINE

PLUG MUST BE BRASS OR PLASTIC

3. TAPE WRAP GALV PIPE WITH WAX TAPE SYSTEM.

WHEN ADJACENT TO A VALVE: IF ADJACENT VALVE IS A BUTTERFLY VALVE PROVIDE 2' MIN OF PIPE; IF VALVE IS A GATE VALVE AND IF VALVE LOCATION IS NOT A HIGH POINT, NO PIPE IS REQUIRED; PLUG THE GATE VALVE DIRECTLY.

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

DET01

23 29

D E

TA

IL

David A. Winship, P.E.

UTILITIES ENGINEER

1. This blowoff is to be used at low points in the water line.

2. Blowoff shall be sized at 25% of line diameter or 4 inches, whichever is larger.

3. Blowoff shown is 4 inches in diameter and shall only be used on lines with diameters of 16 inches or less.

4. For thrust restraint see City's Engineering Design Manual section 612.P.

City Of Beaverton

4" GATE VALVE

MJ x FLG

4" 45° BEND FLG

THRUST BLOCK

NOTES:

LINE SIZE MJ

TEE x 4" FLG

ROTATED

DOWN 45°

4" 90° BEND MJ

WITH MEGALUG

JOINT RESTRAINT

SEE NOTE 4

DEPARTMENT

PUBLIC WORKS

DATE DRAWN BY DRAWING NO.

2 - 13 - 07

LOW POINTS IN WATER LINES

STANDARD BLOWOFF FOR

JR - ED

CONCRETE

PIER BLOCK

MEGALUG

JOINT RESTRAINT

SEE NOTE 4

4" PLAIN END

BY FLG DI

SPOOL

4" DI SPOOL

4" BLIND

FLANGE

2'-6" Ø

MJ RETAINER

GLAND WITH

SET SCREWS

LENGTH

VARIES

3,000 PSI

CONCRETE

TYP

WATER VALVE BOX

BROOKS METER

BOX #37 WITH CI

SIDEWALK LID

SEE Beaverton Standard Dwg 615

6"

12"

12"

640-2

4' MIN.

IN UNIMPROVED AREAS METER BOX TOP SHALL BE SET 2" ABOVE GRADE.

17. PROVIDE 5LB ZINC ANODE PER DETAIL

5. FOR 6" BLOWOFF USE SAME COMPONENTS, SIZE TO 6"

B

TEE PER PLAN

EAST JORDAN FOUNDRY VALVE BOX AND COVER WITH "CITY OF BEAVERTON" CAST INTO TOP SURFACE.

19. LOCATE 5 LB ZINC ANODE 2' BELOW COPPER PIPE;

ATTACH WITH COPPER PIPE GROUNDING CLAMP

3. CORP STOP SHALL HAVE INTEGRAL ISOLATION IF WATER MAIN IS EQUAL TO OR GREATER THAN 24" DIA

CCxCTS

DETAIL 640-2

6"

OR BFV

DET02

24 29

D E

TA

IL

S

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

TEE AS SHOWN ON PLANS

6" COMPACTED CLASS B BACKFILL

6" GATE VALVE, LOCATE BY TEE EXCEPT WHERE SHOWN OTHERWISE ON PLANS.

MIN. 2'

3/4" SERVICE CONNECTION WITH

INTEGRAL ISOLATION AND ANODE

SIMILAR TO DETAIL 660-3.

3-4" CLEARANCE FROM BACK

OF CURB (WHERE APPLICABLE)

OR LARGER CONC. PIER BLOCK OR EQUIVALENT640-2

9"

5. APPROVED BACKFLOW TO BE LOCATED OUTSIDE OF RIGHT-OF-WAY/PUBLIC UTILITY EASEMENT, WHERE APPLICABLE.

6. NO WATER SERVICE LINES SHALL BE INSTALLED UNDER ANY LIDA SWALE,

DRIVEWAY, OR DRIVEWAY WINGS UNLESS APPROVED BY CITY OF BEAVERTON.

METER SETTER

BY CITY

7. PROVIDE 5LB ZINC ANODE PER

DETAIL B SIM, DWG NO. DET05.

METER BOX AND SERVICE INSTALLATION BY

CONTRACTOR - SEE SPECIFICATIONS FOR BOX SIZE.

FOR WATER MAINS EQUAL TO

OR GREATER THAN 24" DIA.,

PROVIDE ISOLATION:

(2) 2" BRASS FLANGES

ASSEMBLED AS AN INSULTING

FLANGE JOINT (INCLUDING

INSULTING: GASKET, SLEEVES,

AND WASHERS; TAPE WRAP

CIRCUMFERENCE OF FLANGES

W/ 20 MIL PVC TAPE), 2" IPTxCTS

COUPLING.

SEE NOTE 7

PLANTER STRIP

OR REPAIR BAND AS NEEDED

BASED ON PIPE CONDITION (TYP)

650-4

5.75" 3.75"

ENGRAVED LABEL,

1/4" HIGH LETTERS

CITY OF BEAVERTON TEST STATION

OR SS

METER BOX AND SERVICE

INSTALLATION BY

CONTRACTOR - SEE

SPECIFICATIONS.

METER BY CITY.

PROFILE VIEW

4"

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

DET03

25 29

D E

TA

IL

SEE INSULATING

FLANGE DETAIL.

PVC TAPE

NOTE: FOR GAS CROSSINGS

CLOSER THAN 12", INSTALL

FIBERGLASS SHEATHING MATERIAL

PROVIDED BY NW NATURAL

BETWEEN THE GAS LINE AND THE

WATER LINE (OVER THE PVC

MEMBRANE) FOR A DISTANCE OF 18"

ON EACH SIDE OF THE GAS LINE.

20 MIL PVC

NOTE: WHEN THE PIPE IS POLYETHYLENE

ENCASED THE POLYETHYLENE SHALL CONTINUE

UNDER THE GEOMEMBRANE WRAP SLEEVE WRAP.

OVERLAP 1/4 CIRCUMFERENCE

OR 6", WHICHEVER IS GREATER

PROVIDE TERMINAL BOARD,

SEE DETAIL 680-2.

NOTE: WHERE ANODES ARE

REQUIRED DO NOT INSTALL ANODES

WITHIN LIMITS OF SLEEVE WRAPPING.

A

1. FIELD LOCATE IN BIKE LANE OR BEHIND BACK OF CURB.

2. ROUTE WIRES FROM ISOLATION JOINT TO TEST STATION ALONG NEAREST LATERAL OR SERVICE, SECURE WITH DUCT TAPE EVERY 5 FT.

10' MIN. EACH SIDE

6"

3' BELOW

PIPE

ANODE

JO

IN

T

BO

ND

F

IT

TI

NG

S

VA

LV

ES

JO

IN

T

BO

ND

P

IP

E

JO

IN

TS

4.

FO

R

ER

DI

P:

JO

IN

T

BO

ND

W

IR

E

LE

NG

TH

S

HA

LL

B

E

SU

FF

IC

IE

NT

F

OR

F

UL

L

EX

TE

NS

IO

N

OF

JO

IN

T

BONDING OF DIP JOINTS AND FITTINGS

24"

OVER POLYETHYLENE ENCASEMENT

(ONLY AT LIGHT RAIL CROSSINGS)

THE FERNCO COUPLING OR SEAL SHOWN ON EACH END SHALL BE SIZED TO SPACE THE SLEEVE FROM THE WATER PIPE.

6. FOR GAS CROSSINGS CLOSER THAN 12", INSTALL FIBERGLASS SHEATHING MATERIAL PROVIDED BY NW NATURAL BETWEEN THE GAS LINE AND THE WATER LINE (OVER THE PVC SLEEVE) FOR A DISTANCE OF 18" ON EACH SIDE OF THE GAS LINE.

FOR DI PIPE (EXCEPT AT LIGHT RAIL CROSSINGS) AND WHERE A SLEEVE SLIP-ON IS NOT POSSIBLE, PROVIDE

SLEEVE WRAPPING PER STANDARD DETAIL 680-4.

DET04

26 29

D E

TA

IL

S

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

NOTES:

1. WIRE SHALL HAVE ENOUGH SLACK TO EXTEND A MIN OF 2 FT

ABOVE FINISHED GRADE AFTER FINAL PAVING.

2. FOR AN ISOLATION JOINT RUN OF NEW WATER PIPE, WIRE ON

THE UP STATION SIDE OF THE ISOLATION JOINT SHALL BE

WHITE AND WIRE ON THE DOWN STATION SIDE OF THE

ISOLATION JOINT SHALL BE BLACK.

3. COLOR CODE WIRES BY INSULATION COLOR, OR BY COLORED

TAPE OR HEAT SHRINK ON LAST 4 FT OF WIRE.

ITEM WIRE COLOR WIRE

NEW WATER MAIN WHITE 8 AWG STRANDED COPPER

WIRE

EXISTING WATER

MAIN BLACK 8 AWG STRANDED COPPER

WIRE

CASING PIPE ORANGE 8 AWG STRANDED COPPER

WIRE

GALVANIC ANODES BLUE 12 AWG SOLID COPPER WIRE

ZINC REFERENCE

CELL YELLOW 12 AWG SOLID COPPER WIRE

CP MONITORING

COUPONS PURPLE 12 AWG STRANDED COPPER

WIRE

TEST STATION TYPE & WIRE

IDENTIFICATION TABLE

REMOVE VALVE AND VALVE BOX AT

BRANCH AND INSTALL BLIND FLANGE

OR MJ PLUG AT TEE. PROVIDE

MECHANICAL RESTRAINT OR CONCRETE

BLOCKING AS REQUIRED.

EXISTING TVWD WATER

MAIN (TO REMAIN IN

SERVICE)

CUT AND REMOVE TAPPED PORTION OF

MAINLINE PIPE AND THRUST BLOCK, REBUILD

WITH DI SPOOL AND LONG BODY SLEEVES AS

REQUIRED BASED OF FIELD CONDITIONS.

PLUG PIPE THAT IS TO BE ABANDONED IN PLACE

WITH CONCRETE, TYP. EACH SEPARATE END

EXISTING BRANCH MAIN OR

HYDRANT RUN

REMOVE EXISTING PIPE

MAINLINE TEE MAINLINE TAPPING SLEEVE

3' MIN., TYP

1' MIN., TYP

ABANDONMENT AT MAINLINE - TVWD

EXTEND SERVICE LINE AND PROVIDE

CONNECTION TO EXISTING BUILDING SERVICE BY

LICENSED PLUMBER (NOT SHOWN ON PLANS)

NEW WATER METER BOX,

LOCATION TO BE APPROVED

BY OWNERS

REPRESENTATIVE. SEE

NOTES 5 AND 7

CONNECTION TO NEW COB

DUCTILE IRON WATER MAINEXISTING COB OR

TVWD WATER MAIN

EXISTING WATER SERVICE

REMOVE EXISTING

WATER METER AND

BOX

2' MIN.

NOTES:

1. RESTORE DISTURBED AREAS BEHIND CURB AND ON PRIVATE PROPERTY TO EXISTING OR BETTER CONDITION.

2. SEE CITY OF BEAVERTON STANDARD DRAWING 660-3 AND 660-5 FOR WATER SERVICE DETAILS.

3. IF SIDEWALK IS DAMAGED OR REMOVED, REPLACE ENTIRE SIDEWALK PANEL FROM SCORELINE TO SCORELINE. IF

METERS ARE SHOWN ADJACENT TO SIDEWALK LOCATE THEM IN EDGE OF REPLACED SIDEWALK PANEL.

4.REMOVE EXISTING WATER METER. PROVIDE TO OWNER FOR FINAL METER READ; THEN DISPOSE OF METER.

5. NEW WATER METER TO BE PROVIDED BY CITY OF BEAVERTON.

6. INSTALL 5LB ZINC ANODE 2' UNDER COPPER SERVICE PIPE AND CONNECT TO SERVICE PIPE WITH COPPER PIPE

GROUNDING CLAMP.

7. LOCATE NEW METER AND METER BOX TO BE WITHIN RIGHT-OF-WAY REGARDLESS IF CURRENT LOCATION IS ON

PRIVATE PROPERTY.

8. PRIVATE SIDE CONNECTION NOT SHOWN ON PLAN VIEW.

CURB OR EDGE OF

PAVEMENT

PROPERTY LINE

ABANDON EXISTING WATER

SERVICE AT MAIN PER

STANDARD DETAIL 660-1. 5LB ZINC ANODE

TYPICAL 2" AND SMALLER COPPER WATER

SERVICE REPLACEMENT PLAN

B CA

EXISTING MAIN

12' MAX.

3' MIN.

(WOOD AND/OR CONCRETE)

2" X 2 1/2" NST ADAPTER

2" X 2 1/2" NST ADAPTER

2" DISCHARGE

2" CONTROL VALVE

MIN.

12"

(CAP SIZE TO MATCH WATER MAIN SIZE)CONNECTION TO

TEMP. TEST BLOCKING

NEW WATER MAIN

TEMP. CAP (MJ) W/2" TAP (IP)

2" CONTROL VALVE

2" R.P. DEVICE

2 1/2" X 2" ADAPTER

SUPPLY HOSE

NOTES:

1) ALL FITTINGS TO BE DUCTILE IRON.

2) ALL EXCAVATION SHALL PROVIDE A MINIMUM OF 12" CLEARANCE AROUND PIPE & FITTINGS.

3) CONTRACTOR TO DETERMINE ALIGNMENT & GRADE OF EXISTING FACILITIES PRIOR TO INSTALLATION OF NEW WATER MAIN. OUTSIDE DIAMETER OF EXISTING WATER MAIN TO BE DETERMINED AT THE SAME TIME

THE CONTRACTOR EXCAVATES FOR ALIGNMENT & GRADE.

4) ALL EXCAVATION, PIPE, FITTINGS (EXCEPT AS NOTED), OTHER MATERIAL, BACKFILL, COMPACTION & STREET RESTORATION BY CONTRACTOR. ALL MATERIALS TO BE ON JOB SITE PRIOR TO SCHEDULED

SHUT-DOWN OF EXISTING WATER MAIN(S).

5) D.I. SLEEVE (MJ) TO BE INSERTED AT TIME OF CONNECTION FOR CUT INTO EXISTING WATER MAIN.

6) D.I. SLEEVE(S) FURNISHED BY CONTRACTOR FOR CUT INTO EXISTING WATER MAIN.

7) COORDINATE WITH SEWER UTILITY BEFORE DISCHARGE TO SEWERS.

8) FITTINGS & HOSE SIZE SHOWN ARE MINIMUM SIZE. USE LARGER SIZE AS NEEDED FOR 2.5 F.P.S.

FLUSHING.

TRENCH CLEARANCESD

GENERALIZED TESTING DETAILF

11UTILITY PROTECTION DETAIL

SEE NOTE

UTILITY PROTECTION NOTES:

1. PROVIDE TRENCH SHORING AS REQUIRED AND

APPROPRIATE TO EXCAVATE AND PROTECT ADJACENT

UTILITIES. CONFIRM TYPE, SIZE, AND MATERIAL OF

ADJACENT UTILITIES, AS WELL AS BEDDING AND BACKFILL

MATERIAL, AND PROVIDE APPROPRIATE PROTECTION

MEASURES.

2. TRENCH SHORING IS TO BE INSTALLED AS EXCAVATION

PROGRESSES IN A MANNER TO MINIMIZE THE AREA OF

UNSUPPORTED TRENCH AND MAINTAIN POSITIVE

PRESSURE ON THE TRENCH WALLS. LIMIT EXCAVATION

AHEAD OF INSTALLED PIPE TO TWO PIPE LENGTHS.

BACKFILL AND COMPACT AS INSTALLATION PROGRESSES IN

A MANNER THAT MINIMIZES THE AREA OF UNSUPPORTED

TRENCH.

3. TRENCH SHIELDING (TRENCH BOX) IS ACCEPTABLE AT THE

PIPE BELL LOCATION FOR PIPE INSTALLATION PROVIDED

THAT THE TRENCH WALL AHEAD OF THE TRENCH BOX IS

SUPPORTED WITH SHORING. REMOVAL OF SHORING FOR

MOVEMENT OF TRENCH BOX TO THE SUBSEQUENT PIPE

BELL LOCATION SHALL OCCUR IN A MANNER TO MINIMIZE

THE AREA OF UNSUPPORTED TRENCH.

4. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT

ALL TRENCH SHORING, SHIELDING AND SAFETY MEASURES

COMPLY TO OSHA RULES AND REGULATIONS.

5. POTHOLE AND PROTECT ADJACENT UTILITIES LOCATED

WITHIN A ANTICIPATED SKIN-TO-SKIN DISTANCE OF 2 TIMES

THE EXCAVATION LIMITS OF THE PROPOSED TRENCH, OR

MIN. 5' WHICHEVER IS GREATER.

EXCAVATION LIMITS

CONTRACTOR DESIGNED SHORING AS

REQUIRED TO PROTECT THE EXISTING AND

ADJACENT UTILITIES AND CONSTRUCT THE

PROPOSED IMPROVEMENTS, TYP.

EXISTING STORM/SEWER PIPING WITHIN TRENCH LIMITS MAY

BE CUT AND REMOVED IF ALLOWED BY OWNER'S

REPRESENTATIVE. INSTANCES WHERE THIS MAY APPLY

INCLUDE:

1) IF NECESSARY TO FACILITATE WATER MAIN INSTALLATION,

WHEN THE WATER MAIN IS GOING UNDER A EXISTING UTILITY.

2) WHERE THERE IS LESS THAN 2' OF VERTICAL SEPARATION

WHEN GOING OVER AN EXISTING UTILITY.

STORM/SEWER PIPE TO BE REPAIRED/REPLACED PER DETAIL

G/DET06. ALSO REPLACE SEWER AT LOCATIONS REQUIRED BY

DETAIL D THIS SHEET AND AS INDICATED ON THE PLANS.

SEE NOTE

EXISTING STORM/SEWER,

POTHOLE AT ALL CROSSINGS

EXISTING UTILITY

RESTORATION NOT SHOWN;

REFER TO RESTORATION

SHEETS, TYP.

PROPOSED UTILITY/

WATER MAIN

POTHOLE TO CONFIRM EXISTING BEDDING AND

BACKFILL MATERIAL AND PLAN PROTECTION OF

UTILITY ACCORDINGLY, TYP.

W

AS

H

IN

G

TO

N C

O U

N

TY

W

AL

KE

R

R O

AD

P

H

AS

E

N W

TH

A

VE

N

U E

TO

N

W

R

D A

VE

N

U E

100315

C

AD

PL

O T

ST

AM

P:

R

EV

IS

IO

N S

N O

PA

TH

12836

OREGON

EXPIRES: 06/30/2027

DENNIS KESSLER

RE

GIS

TERED PROFESSIONALENG INEER

FEB. 14, 1985

DET05

27 29

D E

TA

IL

CUT PIPE SQUARE

1' MIN FROM BREAK, TYP.

DAMAGED GRAVITY PIPE

REPAIR COUPLING, SEE NOTE 1

STAINLESS STEEL HARDWARE

REPAIRED GRAVITY PIPE (SAME MATERIAL OR OD)

NEW PIPE WITH SAME ID AS

EXISTING

SHEAR RESISTANT COUPLING

STAINLESS STEEL

HARDWARE

REPAIRED GRAVITY PIPE (DIFFERENT MATERIAL OR OD)

NEW PIPE WITH SAME ID AS EXISTING

ALIGN PIPE INVERTS, CREATE

SMOOTH TRANSITION

COUPLING ADAPTER SPECIFIED BY

MANUFACTURER FOR PIPE OD

DIFFERENCE

ALIGN PIPE INVERTS, CREATE

SMOOTH TRANSITION

MINIMIZE GAP,

1/4" MAX , TYP.

GRAVITY STORM AND SEWER REPAIR

L

PIPE DIA

4" AND 6"

8" 10" 12"

A (MIN)

12"

SIZING TABLE

54" 52" 42" 36"

H (MIN)

24" 24" 18" 18"

T (MIN)

12" 10" 8"

4" AND 6"

PIPE DIA SOFT CLAY

54" 80" 98" 120" 66"

54" 48" 48"

SANDY SILTSILT

48" 66" 78" 92"

PLAN VIEW

ELEVATION

H

T

TIE RODS

BLOCK "KEYED" INTO

UNDISTURBED SOIL.

TIE RODS

MIN. BLOCK LENGTH (L)

SOIL CONDITION

3" CLR (TYP)

A (TYP)

6" MIN

(TYP.)

18" MIN

END VIEW

#4 BAR REINFORCING

(TYP)

2' TO 10'

#4 @ 8" OC EW

#4 @ 12" OC EW

#4 @ 12" OC EW

#4 @ 10" OC EW

REINFORCING

REINFORCING

3" CLR

(TYP)

BOTH FACES

SEE NOTE 7

1. CONCRETE BLOCK SHALL BE CLASS 3000 PSI CONCRETE (MIN.) WITH 3/4" AGGREGATE AND

SLUMP OF 2"-4".

2. MAINTAIN 18" MINIMUM COVER OVER THE TOP OF BLOCK.

3. BOTTOM OF BLOCK IS TO BE ON UNDISTURBED SOIL. DO NOT INSTALL BLOCK ON PIPE JOINT.

4. TRENCH TO BE BACKFILLED WITH CRUSHED ROCK COMPACTED TO 95% DENSITY ON ALL SIDES

OF BLOCK…

This is the start of the file's text. The full file is on GovTribe.