ChillerCompressor_Revised.doc

DOC document 51 KB Posted

Attached to
EMERGENCY REPLACE CHILLER COMPRESSOR Federal contract opportunity
Solicitation number
140G0125Q0168
Issued by
Department of the Interior US Geological Survey Office of Acquisitions and Grants

About this file

This Statement of Work (SOW) details the replacement of a chiller compressor for the U.S. Geological Survey Wetland and Aquatic Research Center (WARC) in Lafayette, LA. The project requires removing the existing failed screw compressor (Model: RTWD200F2D02A1A1AA2A1A1X1B0A1000000A700200D0) and installing a new 85-ton Trane screw compressor (Model: CHHO0M21KJ0R092AANN). The scope of work includes refrigerant removal and storage, equipment installation, system testing, leak checks, vacuum cleaning, refrigerant refilling, and a 200-hour operational test with subsequent oil change.

The related federal contract opportunity (Solicitation Number: 140G0125Q0168) is a competitive Request for Quotations (RFQ) to be issued on 07/11/2025, with written quotes due on 07/14/2025 at 10:00am MT. The anticipated contract award date is 7/15/2025. The procurement falls under NAICS code 561790 (Other Services to Buildings and Dwellings) with a size standard of $9 million. Quotes should be submitted to Mindie Dixon at mdixon@usgs.gov, and the opportunity is being managed by the Department of the Interior US Geological Survey Office of Acquisitions and Grants.

View the file

Other files for this federal contract opportunity

Other files attached to EMERGENCY REPLACE CHILLER COMPRESSOR, newest first.
File Type Posted
B08_Attachment_1_Instructions_To_Offerors.doc DOC document
Sol_140G0125Q0168.pdf PDF
Wage_Determination_2015-5185.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK

Replace Chiller Compressor

I. GENERAL INFORMATION

A.

Introduction.

Our mission statement at the USGS Wetland and Aquatic Research Center (WARC) is to provide USGS science to Louisiana, the Southeastern States, the U.S. Caribbean, and elsewhere in the world. We are also leaders in seeking new and innovative ways to meet the critical need for sound, objective scientific information that can be applied to issues of local to international concern.

USGS wishes to replace a chiller compressor compatible with the existing chiller/air handling system. The compressor is to be delivered, setup, and tested at the Wetland and Aquatic Research Center located in Lafayette, LA, 70506. Proposals shall include purchase cost of compressor as well as delivery, installation, complete setup, pressure testing, operational testing and subsequent oil change.

II. WORK REQUIREMENTS

A. Technical Requirements:

a. Existing Chiller Unit:

i. Model: RTWD200F2D02A1A1AA2A1A1X1B0A1000000A700200D0 Serial Number: U15C01614

b. Installation of new Trane Compressor:

i. Model: CHHO0M21KJ0R092AANN

ii. Serial Number: N21H01537

B. Scope of Work:

· Vendor shall provide all necessary materials and labor.

· Remove and store refrigerant to be used to restart the system after repair.

· Remove failed screw compressor.

· Provide and install new 85-ton Trane screw compressor.

· Install new equipment including dryers, oil filter, and oil as needed.

· All systems to be tested and checked for leaks.

· Charge the system with required oil amount.

· Clean out system by vacuum according to industry standards.

· Refill system with stored refrigerant.

· Perform start up with new compressor and verify chiller is working properly.

· Run for a period of 200 hour to verify all liquid and gas levels are sufficient are within the acceptable operating range.

· Following the 200-hour test, replace compressor oil and oil filter to ensure that the oil is clean.

· Vendor to return core to manufacturer for inspection.

· USGS to provide forklift as needed for compressor removal and installation.

III.

SUPPORTING INFORMATION

A.

Place of Performance:

U.S. Geological Survey

Wetland and Aquatic Research Center

700 Cajundome Boulevard

Lafayette, LA 70506

B.

In the event the contractor encounters difficulty in meeting performance requirements, or when it anticipates difficulty in complying with the contract delivery schedule or date, or whenever the contractor has knowledge that any actual or potential situation is delaying or threatens to delay the timely performance of this contract, the contractor shall immediately notify the Contracting Officer and the COTR, in writing, giving pertinent details. This data shall be informational only in character.

C.

Local Contact Information:

Will be provided at the time of award D.

CODES, STANDARDS, AND DEPARTMENTAL PUBLICATIONS. The following manuals, handbooks, industry standards and codes are incorporated by reference.

Uniform Federal Accessibility Standards

National Electrical Code

ICBO Uniform Building Code

NFPA, National Fire Codes

NFPA, 101 LIFE SAFETY CODE

NFPA 45

Uniform Plumbing Code

Uniform Mechanical Code

Underwriters Laboratories Fire Resistance Directory

Underwriters Laboratories Building Materials Directory

DOE Energy Conservation Standards 10 CFR Part 435

Construction Specifications Institute Standards

ANSI/AIHA Z9.5 2003

DOE Energy Conservation Standards 10 CFR Part 435

OSHA 29CFR 1910

All state, Federal and local building codes and requirements