Chiller IFB Question and Answer B38914.docx
DOCX document 14 KB Posted
- Attached to
- IFB - IRCC - 60 Ton Chiller Rental - 1239 - JSW
- Solicitation number
- 24-426DOC-ILRIV-B-38914
- Issued by
- Fulton County, Illinois
About this file
This document is a Question and Answer document related to an Invitation for Bid (IFB) for a 60 ton chiller rental contract issued by an Illinois state agency. The IFB requests a 60 ton chiller rental, and the questions and answers address logistics such as the availability of a forklift on-site, the need for a technician for setup and startup, and details about the electrical and water connections for the chiller. The chiller will be placed on a concrete pad, and the agency will utilize their existing house pumps rather than requiring the vendor to provide a separate pump.
The pricing terms, set asides, incumbent, funding sources, and other financial details are not provided in this document. The focus is on the technical and logistical requirements for the chiller rental.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Blank IPG Active Registered Vendor Disclosure~1.docx | DOCX document | |
| Chiller IFB Question and Answer 2 B38914~1.docx | DOCX document | |
| Notice of Award Form Chiller Rental B38914~3 (1).pdf | ||
| IFB Chiller Rental B38914~2.docx | DOCX document | |
| Vendor Disclosure~1.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Chiller IFB Question and Answer B-38914
1. Do you have the forklift available on-site or would you us to arrange the forklift to offload & place the equipment on the concrete pad?
No, there is not a forklift on-site for use.
2. Do you require a technician for set up / start up & strike / off-rent?
Yes
3. Are there any space/equipment footprint restrictions we need to know about?
No Chiller:
1. Are we using the house pumps, or do you need us to provide a pump?
House pumps
2. Distance between the chiller and the Breaker/electrical supply?
Electrical service is approximately 15 feet within where the chiller will be placed.
3. What is the distance to the water connections for the supply and return hose from concrete pad placement?
Same as the electrical service.
4. Are we using the plant / system pumps or am I supplying a separate pump?
Please see answer to question one.