About this file

This is a chemicals specification document related to water treatment services for the Washington Suburban Sanitary Commission (WSSC) in Maryland. The file contains detailed chemical requirements for HVAC and biosolids treatment systems across eleven WSSC facilities. The contractor must provide comprehensive water treatment services including all necessary chemicals, supervision, labor, equipment, materials, and tools to maintain proper operating conditions across the designated systems. Sealed responses must be submitted via WSSC's eProcurement Portal at https://procurement.opengov.com/portal/wsscwater no later than 2:00 pm on Monday, August 3, 2026, with late submissions not accepted. The scope encompasses both mechanical and water systems requiring specialized chemical treatment to meet operational and regulatory standards.

The chemicals specification document outlines the specific chemical products, formulations, and quantities required for the contract performance. These specifications establish the baseline requirements and standards that bidding contractors must meet or exceed in their proposals. The document serves as a critical reference for contractors to understand the technical requirements and chemical treatment protocols necessary to successfully perform water treatment services at all eleven WSSC locations, ensuring compliance with applicable water quality and system maintenance standards.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Chemicals

1. Closed System Nitrite Program
PH9-10
Nitrite500 - 1000 ppm
2. Closed System Sulfite Program
pH9-10
SulfiteI 80 ppm
TDS3500 max
3. Steam Boiler Program
pH9-11 ppm
Sulfite30-60 ppm
P Alkalinity300-400 ppm
M Alkalinity400-600 ppm
Phosphate30-60 ppm
Iron<1 ppm
TDS2500-3000 ppm
4. Cooling Tower Program
pH8-9
Phosponates (PBTC)3-6 ppm (if used)
T Alkalinity400 ppm max
Conductivity1000-1400 mm
Chlorides80-190 ppm
Total Hardness600 ppm max
Molybdenum0.8-1.2 ppm (if used)
5. Glycol Program
pH8.5-10.5
Freezing Point0 Degrees
6. Water Softners
pH7-9
Total Hardness0-50 ppm
7. Low-pressure Steam Biolers (Piscataway Biosolids, non-HVAC)
pH9-11
Phosponates (PBTC)10-50 ppm
P Alkalinity30-500 ppm
M Alkalinity400-600 ppm
Nitrite500-2000 ppm
Chlorides100-130 ppm
Total Hardness0
Hydrazine0.05-0.10 ppm
Sulfite30-60 ppm
Chromate500-1500 ppm
Phosphorus200-900 ppm
Phosphate60 ppm
Steam Condensate PH8-10

File details come from the government source that posted it. Updated .