CHEMICAL STORAGE BUILDING PRICE TEMPLATE.xlsx
XLSX spreadsheet 13 KB Posted
- Attached to
- 8145--HAZARDOUS WASTE STORAGE UNIT RFQ AMEND 1 Federal contract opportunity
- Solicitation number
- 36C24526Q0052
About this file
This is a Price Template Excel file for a Chemical Storage Building solicitation by the Department of Veterans Affairs (VA), specifically Veterans Health Administration Veterans Integrated Service Network 5. The detailed template outlines precise specifications for an outdoor hazardous waste storage building with comprehensive requirements across 20+ line items, including building dimensions, electrical systems, fire suppression, ventilation, shelving, and delivery parameters.
Key specifications include a storage building no larger than 112 square feet, 4-hour fire-rated walls and roof, explosion-proof electrical components, a 393-gallon sump capacity, ABC dry chemical fire suppression system, LED lighting, climate control features, and a moveable metal flooring with spill containment. The solicitation (36C24526Q0052) requires full destination delivery within 200 days of contract award, with vendors expected to provide a complete technical and pricing response using the attached template, with non-compliance resulting in potential disqualification.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| CHEMICAL STORAGE BUILDING PRICE TEMPLATE AMEND1.xlsx | XLSX spreadsheet | |
| 36C24526Q0052 AMEND 1.pdf | ||
| 36C24526Q0052_2.docx | DOCX document | |
| 36C24526Q0052_1.docx | DOCX document | |
| 36C24526Q0052.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Vendor NAME | |||||||
| Vendor SAM UEI | |||||||
| Contract Number | |||||||
| Manufacturer letter of authorization | |||||||
| Destination delivery date | |||||||
| ITEM NUMBER | SLIN | SOW DESCRIPTION | VENDOR SOLUTION | MODEL NAME/NUMBER | PLACE OF MANUFACTURER | PRICE | TOTAL |
| 0001 | OUTDOOR HAZARDOUS WASTE STORAGE BUILDING | ||||||
| 0001 | AA | size dimensions no larger than 112 Square feet | |||||
| 0001 | AB | staff entry 60"W x 80"H Double Door with 36" Active Leaf | |||||
| 0001 | AC | Sump Capacity: 393 gallons | |||||
| 0001 | AD | 4 Hour Fire Rated, Fire Rated Walls are tested to meet ASTM E119, and FM approved for 4 Hours, Fire Rated Roof tested to meet ASTM E119 and FM Approved for 3 Hours. | |||||
| 0001 | AE | Main breaker OP-100A Load Center 12 SPACE 100A NEMA 3R 120/240V to meet power requirements for container | |||||
| 0001 | AF | grounding kit/ tie down | |||||
| 0001 | AG | Electrical Hookup to Energize and De-Energize Equipment when Dry Chemical Suppression System | |||||
| 0001 | AH | Explosion Proof Air Conditioner with Color Coded Thermostat Class 1, Division 2 208 Volt 15,700Btu, 230 Volt 15,700Btu (ORD) | |||||
| 0001 | AI | R11 Insulation Walls, Ceiling and DLC | |||||
| 0001 | AJ | Explosion Proof Exhaust System-335 CFM w/indicator light | |||||
| 0001 | AK | Explosion Proof Emergency Shut Off Switch for Exhaust System | |||||
| 0001 | AL | LED Explosion Proof Light Fixture with Light Switch Class 1 Division 2 | |||||
| 0001 | AM | ABC Dry Chemical Fire Suppression System with Audible Alarm vendor shall provide system requirement to be operable so the VA can ensure the fire suppression system is fully functional. | |||||
| 0001 | AN | 14"W SHELVES WITH 2" LIP SIDES (Priced Per Linear Foot) | |||||
| 0001 | AO | at least 3 tiers footage coverage length on back, left , and right walls | |||||
| 0001 | AP | 6 ACHs | |||||
| 0001 | AQ | at least one adjustable 18” W x 18H Vent with Insulated Cover | |||||
| 0001 | AR | no larger than 52"W x 72"L Perforated Steel Ramp with Skid-Resistant Finish to meet container ground height. | |||||
| 0001 | AS | Moveable metal grading full length flooring with spill containment with drain. | |||||
| 0001 | AT | destination delivery to loading dock with 200 days. | |||||
| 0001 | AU | Meets intertek test, FM approved |