CHEMICAL STORAGE BUILDING PRICE TEMPLATE AMEND1.xlsx

XLSX spreadsheet 13 KB Posted

Attached to
8145--HAZARDOUS WASTE STORAGE UNIT RFQ AMEND 1
Solicitation number
36C24526Q0052
Issued by

About this file

This document is a Price Template for a Hazardous Waste Storage Building Request for Quote (RFQ) from the Department of Veterans Affairs (VA). The solicitation (36C24526Q0052) requires a fully assembled outdoor Hazardous Storage Building with specific technical requirements, including a 112 square foot design, 4-hour fire-rated walls and roof, explosion-proof features, fire suppression system, shelving, ventilation, and a moveable metal grading floor with spill containment. Key delivery specifications include destination delivery to an existing VA site pad within 200 days, with vendor responsible for offloading.

The RFQ amendment addresses vendor questions regarding installation, delivery, and site conditions, confirming that VA will be responsible for anchoring and power hookup, no fire suppression installation is required at delivery, and the delivery site has no parking, street, or placement obstacles. The RFQ close date has been extended to 11/3/25 at 12 PM EST, and the solicitation emphasizes that incomplete technical or pricing responses will be considered non-compliant. The procurement is classified under NAICS 332311 and PSC 8145, targeting a hazardous waste storage unit solution for the Veterans Health Administration's Integrated Service Network 5.

View the file

Other files

File Type Posted
36C24526Q0052_2.docx DOCX document
36C24526Q0052 AMEND 1.pdf PDF
CHEMICAL STORAGE BUILDING PRICE TEMPLATE.xlsx XLSX spreadsheet
36C24526Q0052.pdf PDF
36C24526Q0052_1.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Vendor NAME
Vendor SAM UEI
Contract Number
Manufacturer letter of authorization
Destination delivery date
ITEM NUMBERSLINSOW DESCRIPTIONVENDOR SOLUTIONMODEL NAME/NUMBERPLACE OF MANUFACTURERPRICETOTAL
0001OUTDOOR HAZARDOUS WASTE STORAGE BUILDING
0001AAsize dimensions no larger than 112 Square feet
0001ABstaff entry 60"W x 80"H Double Door with 36" Active Leaf
0001ACSump Capacity: 393 gallons
0001AD4 Hour Fire Rated, Fire Rated Walls are tested to meet ASTM E119, and FM approved for 4 Hours, Fire Rated Roof tested to meet ASTM E119 and FM Approved for 3 Hours.
0001AEMain breaker OP-100A Load Center 12 SPACE 100A NEMA 3R 120/240V to meet power requirements for container
0001AFgrounding kit/ tie down
0001AGOff load site is free and clear area to operate machinery. No powerlines, sewers or obstructions will be at pad site. No bolting, electrical hook up, or fire suppression services needed at pad site.
0001AHExplosion Proof Air Conditioner with Color Coded Thermostat Class 1, Division 2 208 Volt 15,700Btu, 230 Volt 15,700Btu (ORD)
0001AIR11 Insulation Walls, Ceiling and DLC
0001AJExplosion Proof Exhaust System-335 CFM w/indicator light
0001AKExplosion Proof Emergency Shut Off Switch for Exhaust System
0001ALLED Explosion Proof Light Fixture with Light Switch Class 1 Division 2
0001AMABC Dry Chemical Fire Suppression System with Audible Alarm vendor shall provide system requirement to be operable so the VA can ensure the fire suppression system is fully functional.
0001AN14"W SHELVES WITH 2" LIP SIDES (Priced Per Linear Foot)
0001AOat least 3 tiers footage coverage length on back, left , and right walls
0001AP6 ACHs
0001AQat least one adjustable 18” W x 18H Vent with Insulated Cover
0001ARno larger than 52"W x 72"L Perforated Steel Ramp with Skid-Resistant Finish to meet container ground height.
0001ASMoveable metal grading full length flooring with spill containment with drain.
0001ATdestination delivery to Vexisting VA site pad within 200 days or sooner.
0001AUMeets intertek test, FM approved

File details come from the government source that posted it. Updated .