This document is a Daikin Applied Technical Data Sheet for a Trailblazer® Packaged Air-Cooled Scroll Chiller, specifically for the Plymouth 35th District Courthouse project dated 4/29/2025. The chiller (Model AGZ008F) has a capacity of 141.5 tons, operates on 460 V / 60 Hz / 3 Ph power, and uses R32 refrigerant with a total refrigerant weight of 100 lbs. The unit is a standard efficiency, platform-style air-cooled scroll compressor chiller with a door-mounted display and DC fan motors.

The chiller features a fluid volume of 13.9 gallons, uses 40% ethylene glycol, and has a fluid flow range of 215.9 to 593.6 gpm. Its electrical specifications include a minimum circuit ampacity of 305 A, with recommended and maximum overcurrent protection of 350 A. The unit comes with standard warranty coverage of 1 year for entire unit parts, with an extended 4-year compressor warranty. Additional features include communication capabilities via Modbus, BACnet MS/TP, and BACnet IP, ground fault protection, and AHRI certification. The physical dimensions are 170 in length, 99 in height, and 88 in width, with a shipping weight of 6,618 lbs and an operating weight of 6,741 lbs.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TRAILBLAZER ® Packaged Air-Cooled Scroll Chiller

DST Pathfinder v16.80 Generated 4/29/2025 Page 1 of 4 www.DaikinApplied.com

Job Information Technical Data Sheet

Job Name Plymouth 35th District Courthouse Date 4/29/2025 Submitted By Derik Melo Software Version 16.80 Unit Tag CH-1 Scroll

Unit Overview

Model Number

Capacity ton

Voltage Unit Starter Type

ASHRAE 90.1 LEED Enhanced Refrigerant Management Credit

AGZ008F 141.5 460 V / 60 Hz / 3 Ph Across the Line '07, '10, '13, '16 & '19 Pass

Unit Type Platform Unit Revision Air-Cooled Scroll Compressor Chiller Standard Efficiency Packaged 00

Display Tubing

Door Mounted Display EEXV, Repl FD, Liq/Disch Shutoff, HS Relief, Suction Shutoff, HGBP

Fan Type Refrigerant Type Refrigerant Weight

DC Fan Motors / All Fans VFD - 850 RPM - DC R32 100 lb (per unit)

Compressor Approval UUNNUUNN ETL/cETL, AHRI & ASHRAE 90.1

Actual refrigerant charge depends on the final unit construction, refer to unit nameplate.

Evaporator

Evaporator Model: PPA502H206 Fluid Volume: 13.9 gal

Connection Hand: Universal, 1-Pass, Grooved, Standard Head Connection Size: 4.0 in

Insulation: Single Layer Insulation to Suction at each Compressor

Entering Fluid Temperature

Leaving Fluid Temperature

Fluid Type Glycol Concentration

Fluid Flow

Fluid Flow (with glycol) Min / Max

Pressure Drop

Pressure Drop (with glycol) Min / Max

Fouling Factor

54.00 °F 44.00 °F Ethylene

Glycol 40.0 % 388.5 gpm

215.9 / 593.6 gpm

16.4 ft H₂O

6.20 / 34.7 ft H₂O

0.000100 °F.ft².h/Btu

Note: Evaporator Pressure Drop does not include a strainer. Minimum flow is based on a Constant Flow Pumping System Type.

Condenser

Coil Fins: MicroChannel Guards: Condenser Coil Louvers & Base Frame Wire Grilles

Design Ambient Air Temperature Altitude Fan Diameter Minimum Design Ambient Temperature

95.0 °F 0.000 ft 31.5 in 0.0 °F

Image may not represent ordered unit http://www.daikinapplied.com/

DST Pathfinder v16.80 Generated 4/29/2025 Page 2 of 4 www.DaikinApplied.com

Unit Performance Design

Capacity Input Power Efficiency (EER) IPLV.IP (EER)*

141.5 ton 161.6 kW 10.51 Btu/W.h 17.48 Btu/W.h Performance Points rated at AHRI Ambient Relief - with Glycol

Unit Evaporator Condenser Point # % Load Capacity ton Input Power kW

Efficiency

(EER)

Btu/W.h

Fluid Flow gpm

Pressure Drop ft H₂O

Entering Fluid

°F

Leaving Fluid

°F

Ambient Air °F

Altitude ft

1 100.0 141.5 161.6 10.51 388.5 16.4 54.00 44.00 95.0 0.000 2 75.0 106.1 87.47 14.56 388.5 16.4 51.50 44.00 80.0 0.000 3 50.0 70.76 44.39 19.13 388.5 16.4 49.00 44.00 65.0 0.000 4 25.0 35.38 20.87 20.35 388.5 16.3 46.50 44.00 55.0 0.000

Performance Points rated at AHRI Standard Conditions - with Water

Point # % Load Capacity ton

Input Power kW

Efficiency (EER) Btu/W.h

1 100 144.4 162.9 10.64 2 75 108.3 88.18 14.74 3 50 72.20 44.75 19.36 4 25 36.10 21.04 20.59

* IPLV reflects AHRI standard rating conditions with water and does not change with user defined conditions

Sound (with insulation) Sound Pressure (at 30 feet)

63 Hz dB

125 Hz dB

250 Hz dB

500 Hz dB

1 kHz dB

2 kHz dB

4 kHz dB

8 kHz dB

Overall dBA

43 53 56 61 60 64 53 50 67 Sound Power

63 Hz dB

125 Hz dB

250 Hz dB

500 Hz dB

1 kHz dB

2 kHz dB

4 kHz dB

8 kHz dB

Overall dBA

70 80 83 89 87 91 80 77 94 Octave band is non 'A' weighted and overall readings are 'A' weighted. Sound data rated in accordance with AHRI Standard-370.

Physical Unit

Length* Height Width* Shipping Weight* Operating Weight*

170 in 99 in 88 in 6618 lb 6741 lb

* Shipping and operating weights are based on ‘worst case’ unit configuration variations but do not include the weights of any Options or Accessories. Contact Chiller Applications for additional information.

DST Pathfinder v16.80 Generated 4/29/2025 Page 3 of 4 www.DaikinApplied.com

Electrical Unit Electrical Data

Voltage Starter Type Fan Motor Quantity FLA Fan Motors (each)

460 V / 60 Hz / 3 Ph Across the Line 8 3.2 A Power Connection Type: Single Point Disconnect Switch with Circuit Protection

Short Circuit Current Rating: 65KA Phase Voltage: Phase & Under/Over Voltage Protection with LED

Single Point Power Connection

Minimum Circuit Ampacity

(MCA): 305 A

Recommended Overcurrent Protection Size: 350 A

Maximum Overcurrent Protection Size(MOCP): 350 A

Lug Connection Size: (1) 3/0 to 500 MCM Compressor Electrical Data

Compressor Type Compressor Quantity Starter Type

Scroll 4 Across the Line Circuit #: 1 2

Compressor #: 1 3 2 4 Rated Load Amps (RLA): 65 A 65 A 65 A 65 A

Inrush Current: 389 A 389 A 389 A 389 A

Options Basic Unit

Suction Shut-off Valve: Included High Stage Relief Valve: Included

Hot Gas Bypass: Included Control

Communication: Combination of Modbus, BACnet MS/TP, BACNet IP RapidRestore®: Included

Electrical

Ground Fault: Unit Ground Fault Protection Water Flow Indicator: Included

Warranty Unit Startup By Others

Standard Warranty: 1st Year Entire Unit Parts only Extended Compressor Warranty: Compressor Only; extended 4 years parts only (5 Years Total)

AHRI Certification

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found In the AHRI Directory at www.ahridirectory.org. Unit contains freeze protection liquids in the evaporator and is certified when rated per the Standard with water.

Performance at AHRI Standard Condition – with Water

Unit Evaporator Condenser % Load Capacity ton Input Power kW

Efficiency

(EER)

Btu/W.h

IPLV.IP*

(EER)

Btu/W.h

Fluid Flow gpm

Pressure Drop ft H₂O

Entering Fluid

°F

Leaving Fluid

°F

Ambient Air °F

Altitude ft

100 144.4 162.9 10.64 17.48 345.6 10.5 54.00 44.00 95.0 0.000 Note: Performance with water given as reference only to show compliance with AHRI Standard 550/590. Unit will be configured from the factory to support glycol performance as rated. The unit must not operate with water only without consulting the factory.

DST Pathfinder v16.80 Generated 4/29/2025 Page 4 of 4 www.DaikinApplied.com

Accessories Mandatory

Part Number Description

334767504 RIS Isolator Kit; BlackRP3 334767505 RIS Isolator Kit; BrownRP4

Optional

Part Number Description

334767703 Strainer Kit, Grooved, 4.0", AGZF PPA502

Technical Data Sheet
Job Information
Performance Points rated at AHRI Ambient Relief - with Glycol
Performance at AHRI Standard Condition – with Water

File details come from the government source that posted it. Updated .