CH-1 Scroll - Technical Data Sheet.pdf
PDF 272 KB Posted
- Attached to
- Courthouse Mechanical Equipment
- Solicitation number
- CME0911
- Issued by
- Wayne County, Michigan
About this file
This document is a Daikin Applied Technical Data Sheet for a Trailblazer® Packaged Air-Cooled Scroll Chiller, specifically for the Plymouth 35th District Courthouse project dated 4/29/2025. The chiller (Model AGZ008F) has a capacity of 141.5 tons, operates on 460 V / 60 Hz / 3 Ph power, and uses R32 refrigerant with a total refrigerant weight of 100 lbs. The unit is a standard efficiency, platform-style air-cooled scroll compressor chiller with a door-mounted display and DC fan motors.
The chiller features a fluid volume of 13.9 gallons, uses 40% ethylene glycol, and has a fluid flow range of 215.9 to 593.6 gpm. Its electrical specifications include a minimum circuit ampacity of 305 A, with recommended and maximum overcurrent protection of 350 A. The unit comes with standard warranty coverage of 1 year for entire unit parts, with an extended 4-year compressor warranty. Additional features include communication capabilities via Modbus, BACnet MS/TP, and BACnet IP, ground fault protection, and AHRI certification. The physical dimensions are 170 in length, 99 in height, and 88 in width, with a shipping weight of 6,618 lbs and an operating weight of 6,741 lbs.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AtmosAir BPI Schedule_Canton Courthouse.pdf | ||
| CH-1 Scroll - Air-Cooled Chiller Drawings.pdf | ||
| D35 - ITB - Mechanical.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TRAILBLAZER ® Packaged Air-Cooled Scroll Chiller
DST Pathfinder v16.80 Generated 4/29/2025 Page 1 of 4 www.DaikinApplied.com
Job Information Technical Data Sheet
Job Name Plymouth 35th District Courthouse Date 4/29/2025 Submitted By Derik Melo Software Version 16.80 Unit Tag CH-1 Scroll
Unit Overview
Model Number
Capacity ton
Voltage Unit Starter Type
ASHRAE 90.1 LEED Enhanced Refrigerant Management Credit
AGZ008F 141.5 460 V / 60 Hz / 3 Ph Across the Line '07, '10, '13, '16 & '19 Pass
Unit Type Platform Unit Revision Air-Cooled Scroll Compressor Chiller Standard Efficiency Packaged 00
Display Tubing
Door Mounted Display EEXV, Repl FD, Liq/Disch Shutoff, HS Relief, Suction Shutoff, HGBP
Fan Type Refrigerant Type Refrigerant Weight
DC Fan Motors / All Fans VFD - 850 RPM - DC R32 100 lb (per unit)
Compressor Approval UUNNUUNN ETL/cETL, AHRI & ASHRAE 90.1
Actual refrigerant charge depends on the final unit construction, refer to unit nameplate.
Evaporator
Evaporator Model: PPA502H206 Fluid Volume: 13.9 gal
Connection Hand: Universal, 1-Pass, Grooved, Standard Head Connection Size: 4.0 in
Insulation: Single Layer Insulation to Suction at each Compressor
Entering Fluid Temperature
Leaving Fluid Temperature
Fluid Type Glycol Concentration
Fluid Flow
Fluid Flow (with glycol) Min / Max
Pressure Drop
Pressure Drop (with glycol) Min / Max
Fouling Factor
54.00 °F 44.00 °F Ethylene
Glycol 40.0 % 388.5 gpm
215.9 / 593.6 gpm
16.4 ft H₂O
6.20 / 34.7 ft H₂O
0.000100 °F.ft².h/Btu
Note: Evaporator Pressure Drop does not include a strainer. Minimum flow is based on a Constant Flow Pumping System Type.
Condenser
Coil Fins: MicroChannel Guards: Condenser Coil Louvers & Base Frame Wire Grilles
Design Ambient Air Temperature Altitude Fan Diameter Minimum Design Ambient Temperature
95.0 °F 0.000 ft 31.5 in 0.0 °F
Image may not represent ordered unit http://www.daikinapplied.com/
DST Pathfinder v16.80 Generated 4/29/2025 Page 2 of 4 www.DaikinApplied.com
Unit Performance Design
Capacity Input Power Efficiency (EER) IPLV.IP (EER)*
141.5 ton 161.6 kW 10.51 Btu/W.h 17.48 Btu/W.h Performance Points rated at AHRI Ambient Relief - with Glycol
Unit Evaporator Condenser Point # % Load Capacity ton Input Power kW
Efficiency
(EER)
Btu/W.h
Fluid Flow gpm
Pressure Drop ft H₂O
Entering Fluid
°F
Leaving Fluid
°F
Ambient Air °F
Altitude ft
1 100.0 141.5 161.6 10.51 388.5 16.4 54.00 44.00 95.0 0.000 2 75.0 106.1 87.47 14.56 388.5 16.4 51.50 44.00 80.0 0.000 3 50.0 70.76 44.39 19.13 388.5 16.4 49.00 44.00 65.0 0.000 4 25.0 35.38 20.87 20.35 388.5 16.3 46.50 44.00 55.0 0.000
Performance Points rated at AHRI Standard Conditions - with Water
Point # % Load Capacity ton
Input Power kW
Efficiency (EER) Btu/W.h
1 100 144.4 162.9 10.64 2 75 108.3 88.18 14.74 3 50 72.20 44.75 19.36 4 25 36.10 21.04 20.59
* IPLV reflects AHRI standard rating conditions with water and does not change with user defined conditions
Sound (with insulation) Sound Pressure (at 30 feet)
63 Hz dB
125 Hz dB
250 Hz dB
500 Hz dB
1 kHz dB
2 kHz dB
4 kHz dB
8 kHz dB
Overall dBA
43 53 56 61 60 64 53 50 67 Sound Power
63 Hz dB
125 Hz dB
250 Hz dB
500 Hz dB
1 kHz dB
2 kHz dB
4 kHz dB
8 kHz dB
Overall dBA
70 80 83 89 87 91 80 77 94 Octave band is non 'A' weighted and overall readings are 'A' weighted. Sound data rated in accordance with AHRI Standard-370.
Physical Unit
Length* Height Width* Shipping Weight* Operating Weight*
170 in 99 in 88 in 6618 lb 6741 lb
* Shipping and operating weights are based on ‘worst case’ unit configuration variations but do not include the weights of any Options or Accessories. Contact Chiller Applications for additional information.
DST Pathfinder v16.80 Generated 4/29/2025 Page 3 of 4 www.DaikinApplied.com
Electrical Unit Electrical Data
Voltage Starter Type Fan Motor Quantity FLA Fan Motors (each)
460 V / 60 Hz / 3 Ph Across the Line 8 3.2 A Power Connection Type: Single Point Disconnect Switch with Circuit Protection
Short Circuit Current Rating: 65KA Phase Voltage: Phase & Under/Over Voltage Protection with LED
Single Point Power Connection
Minimum Circuit Ampacity
(MCA): 305 A
Recommended Overcurrent Protection Size: 350 A
Maximum Overcurrent Protection Size(MOCP): 350 A
Lug Connection Size: (1) 3/0 to 500 MCM Compressor Electrical Data
Compressor Type Compressor Quantity Starter Type
Scroll 4 Across the Line Circuit #: 1 2
Compressor #: 1 3 2 4 Rated Load Amps (RLA): 65 A 65 A 65 A 65 A
Inrush Current: 389 A 389 A 389 A 389 A
Options Basic Unit
Suction Shut-off Valve: Included High Stage Relief Valve: Included
Hot Gas Bypass: Included Control
Communication: Combination of Modbus, BACnet MS/TP, BACNet IP RapidRestore®: Included
Electrical
Ground Fault: Unit Ground Fault Protection Water Flow Indicator: Included
Warranty Unit Startup By Others
Standard Warranty: 1st Year Entire Unit Parts only Extended Compressor Warranty: Compressor Only; extended 4 years parts only (5 Years Total)
AHRI Certification
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found In the AHRI Directory at www.ahridirectory.org. Unit contains freeze protection liquids in the evaporator and is certified when rated per the Standard with water.
Performance at AHRI Standard Condition – with Water
Unit Evaporator Condenser % Load Capacity ton Input Power kW
Efficiency
(EER)
Btu/W.h
IPLV.IP*
(EER)
Btu/W.h
Fluid Flow gpm
Pressure Drop ft H₂O
Entering Fluid
°F
Leaving Fluid
°F
Ambient Air °F
Altitude ft
100 144.4 162.9 10.64 17.48 345.6 10.5 54.00 44.00 95.0 0.000 Note: Performance with water given as reference only to show compliance with AHRI Standard 550/590. Unit will be configured from the factory to support glycol performance as rated. The unit must not operate with water only without consulting the factory.
DST Pathfinder v16.80 Generated 4/29/2025 Page 4 of 4 www.DaikinApplied.com
Accessories Mandatory
Part Number Description
334767504 RIS Isolator Kit; BlackRP3 334767505 RIS Isolator Kit; BrownRP4
Optional
Part Number Description
334767703 Strainer Kit, Grooved, 4.0", AGZF PPA502
| Technical Data Sheet |
| Job Information |
| Performance Points rated at AHRI Ambient Relief - with Glycol |
| Performance at AHRI Standard Condition – with Water |
File details come from the government source that posted it. Updated .