This document is a Brand Name or Equal Specifications sheet for a Lithium Battery Storage/Charging Container manufactured by U.S. Chemical Storage, Inc. (Part No. 9033-SL2111-35525, Model No. 4HRBFR 21X11X9). The container must support a minimum full storage capacity of 75,000 lbs with a maximum building weight of 26,000 lbs, and comply with structural requirements including 150 MPH wind load capacity, 250 psf floor load minimum, 40 psf snow load minimum, and Category C seismic classification. The container features a 740-gallon minimum sump capacity and accommodates a minimum of 50 drums.
The structural specifications require four-hour bi-directional fire-rated construction using 14-gauge galvanized steel with 6"x4"x1/8" perimeter steel tubing. The roof system must be one-hour fire-rated with Class A flame spread rating, constructed from 4"X2"X1/8" structural tubing with continuously welded exterior sheets. The floor system includes one-inch deep welded galvanized steel grating over a six-inch leak-proof secondary containment sump with continuously welded 10-gauge steel sheets. Additional standard features include static grounding systems with three interior lugs and one exterior connection, UL-listed gravity air flow vents with three-hour fire dampers, high-solids alkyd primer and acrylic enamel finish, and permanent DOT metal flip placards with NFPA 704 hazard rating signs. Included accessories comprise four lifting lugs, R8.4 minimum floor insulation, R12 minimum wall insulation, R13 minimum ceiling insulation, 240V load center, LED lighting fixtures, explosion-proof exhaust fan, dry chemical fire suppression system, fire alarm system, explosion-proof receptacles, Factory Mutual approval, wind-rated louvered vents, water sprinkler system with two heads and fire department hose connection, sump drain valve, adjustable sump shelving across 36 linear feet, three-hour fire-rated double-leaf doors, mini-split heating/cooling unit, lithium battery signage, and DOT placards for installation on all four building sides.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| C27 Questions and Answers N61331-26-Q-KS17.pdf | ||
| C27 Questions and Answers N61331-26-Q-KS17.pdf | ||
| A8 Redacted CDRL.pdf | ||
| A5 Statement of Work.pdf | ||
| C12. Clauses-Supply.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BRAND NAME OR EQUAL SPECIFICATIONS
FOR
LITHIUM BATTERY STORAGE/CHARGING CONTAINER
Brand Name: U.S. Chemical Storage, Inc.
Part No.: 9033-SL2111-35525 Model No: 4HRBFR 21X11X9 -Lithium Battery Charging
Full Storage: minimum 75,000 Lbs Wind Load: 150 MPH Exp. C
Building Weight: maximum 26,000 Lbs Floor Load: minimum 250 psf
Snow Load: minimum 40 psf Seismic: Category C
Sump Capacity: minimum 740 Gallons Drum Capacity: minimum 50
Standard Features
Minimum Exterior: 22'-0'' x 11'-6'' x 9'-9'' Minimum Interior: 20'-0'' x 10'-0'' x 7'-6''
WALL STRUCTURAL FRAMEWORK:
Four hour bi-directional fire rated, weatherproof construction that meets or exceeds UL 263 and ASTM E-119.
Fabricated from 14ga galvanized steel .
Building perimeter shall have 6”x4”x1/8” steel tubing minimum below and above wall studs.
The corner studs and door frame opening studs shall be minimum 4”x3”x1/8”.
ROOF SYSTEM:
One (1) hour Per IBC Section 722, fire rated Class A flame spread rating.
Wind uplift exceeds UL I-60 and is constructed of 1 hour fire rated, weatherproof construction.
Exterior roof sheets are continuously welded.
Roof Structural System is fabricated from 4"X2"X1/8" structural tubing on 24" centers, welded to roof supports at each seam. 12 ga. HRS steel roof with multiple layers of UL Listed fire resistant gypsum wall board lined on the interior with galvanized steel sheets on interior.
Assembly meets or exceeds UL 263 and ASTM-E119.
Roof is sloped to facilitate runoff and door(s) are equipped with rain shields on exterior.
FLOOR SYSTEM:
Grating and Leak Proof Spill-Containment Sump Assembly consisting of 1” deep welded galvanized steel floor grating over 6” deep leak proof secondary containment sump.
Galvanized steel floor grating fabricated from welded steel grating with 1" tall x 3/16” thick bearing bars at 1" on center and crossbars at 4" on center.
Sump floor is fabricated utilizing continuously welded 10 gauge steel sheets for maximum spill containment.
Acrylic alkyd enamel coating is applied to secondary containment sump.
Floor System is fabricated to comply with NAAMM MBG 531, “Metal Bar Grating Manual for Steel, Stainless Steel, and Aluminum Gratings and Stair Treads.”
BUILDING BASE:
Open channel construction, underside coated with corothan I-Coal Tar for maximum corrosion resistance.
Forklift pockets and hold-down brackets for ease of off-loading and relocation.
The building base assembly shall consist of the following materials: 6 x 4 x 3/16” rectangular tubing, Hold
Down Brackets welded to building are ½” thick plate steel angles, Floor Channel C 4x5.4, Floor Channel
C6x8.2, and 4 x 2 x 1/8” rectangular tubing
STATIC GROUNDING SYSTEM:
Three (3) Interior grounding lugs, one (1) exterior static grounding connection and one (1) 10-foot long 5/8” diameter copper-clad steel grounding rod, and grounding lugs.
GRAVITY AIR FLOW VENTS:
UL listed with 3 hour rated fire dampers with UL listed 165 degree fusible links.
Dampers include louvers and screens to provide airflow and have a galvanized steel frame and curtain type galvanized steel blades.
BUILDING FINISH:
Interior and exterior surfaces are protected with a high solids alkyd universal metal primer (primer) and a high solid acrylic alkyd enamel top coat.
SIGNAGE:
Permanent D.O.T. metal flip placard with rust proof aluminum holder and stainless steel clips on each building. One (1) pressure sensitive NFPA 704 Hazard Rating sign.
ACCESSORIES – based on (1) unit
4 LIFTING LUGS, UP TO 32'L
(4) 1" Flat Bar X 4" Wide Hot Rolled Steel with 1 1/4" Hole For Chain.
FLOOR INSULATION: MINUMUM R8.4 MFB, with steel lining protection
WALL INSULATION: MINIMUM R12 MINERAL FIBER
CEILING INSULATION: MINIMUM R13 BATT CEILING CAVITY
LOAD CENTER, 240V1 12 SPACE 1
UL Listed, Single Phase, 3 Wire, 120/240V Load Center (NEMA 3R). Rainproof And Sleet -(ICE) Resistant-
LIGHT C1D2 LED RND 2
Led Light Fixture, Ceiling or Wall Mount, Round Light. UL 1598A, 844, 1598, & 8750; CUL Listed. Class 1, DIV 2, Groups A, B, C, & D. CLASS 2, DIV 2, Groups F & G. NEMA 4X. Aluminum Body; One Piece, Neoprene Gasket and Diffused Polycarbonate Lens. 120- 277V, 1-Phase, 50 OR 60HZ. 3870 Lumens, 27 Watts
EXPLOSION PROOF EXHAUST FAN 1
Explosion proof exhaust fan consisting of one (1) UL Listed, Class I, Division 1, Group C And D Totally Enclosed Explosion Proof 1/3 HP 1800 RPM Motor (115VAC, 6.6A, 60HZ, 1-PHASE) With Non-Static Twelve-Inch (12) Diameter Cast Aluminum Fan Blade, 1,160 CFM @ 0.0" SP. External Housing Constructed Of 18 Ga Steel. Exhaust Intake Vents Located Within Twelve Inches (12) of the Floor (Gases Heavier Than Air). Activated By An Exterior UL Listed Fan Switch, Other Configurations Available (May Affect Cost And Shipping Dimensions). Exterior Exhaust Fan Port Opening Equipped With Shutter Assembly And Screen.
DRY CHEM 21LB 1
UL, ULC Listed and FM Approved Pre-Engineered Dry Chemical Fire Suppression System for Class A, B AND C Fires. Equipped With Means for Remote Annunciation. System Includes Fusible Link Detection for Automatic
Actuation, Manual Pull Station, and Nozzle(s) For Total Flooding Application. Audible alarm included with system.
Dry chemical systems ship with a full tank of suppressant.
ALARM H/S RED 120V NEP - FIRE ALARM 1
Outdoor Fire Alarm Horn/ Strobe Non Ep Red Strobe Warning Light, Red In Color, 120 VAC. Sounder/ Flasher 85 Decibel 25 Watts, Incandescent. Flash Rate 75 Per Minute.
RECEPTACLE 2-GANG EP CH 20A W/PLG – Dedicated Circuits 3
Explosion Proof Receptacle, 2 Gang 20 AMP 125 VOLT. Designed For Use In Hazardous Environments. Class 1 Division 1 And 2 Groups B*, C, D. * Refer to Material Cut sheet For Restrictions Concerning Use In Group B Environments.
FACTORY MUTUAL APPROVAL 1
This unit will have factory mutual (FM) approval.
FLORIDA APPROVED LOUVER - WIND RATED 1
Florida approved drainable blade louver Florida product approved drainable blade louver designed to protect air intake and exhaust openings in building exterior walls. Qualified for wind-loads up TO 200 PSF. Florida Product Approval No. FL6876.3
WATER SPRINKLER (2) HEADS - FIREFIGHTING RESPONSE 1
Water Sprinkler (2) Nozzle System Water Sprinkler Piping Assembly With UL Listed And FM Approved Sprinkler Heads and a One and One-Half Inch (1-1/2") NPT Exterior Coupling With Cap
Fire Dept Hose CONNECTION 2.5” – Firefighting Response 1
Solid Brass 2-1/2" Fire Department Hose Connection and Adapter for use with Water Sprinkler System.
Sump Drain W/ Ball Valve – Firefighting Response 1
2" SCH 40 Sump Drain Threaded on One End With 2" Lockable Ball Valve.
SUMP SHELVING 24IN DEPTH - 3 TIERS/FRONT WALL 36 linear ft
Adjustable Steel Sump Shelving 24": Leak-proof with a 2" Lip Around The Entire Shelf.
DOOR 72 X 80 3HR PH DOUBLE 1
Third Party Classified and Labeled, (3) Hour Fire-Rated 72" X 80" Double Leaf Steel Door. Located on Front Building. Equipped with a UL Listed Self-Door Closer, Steel Latch Guard, Surface Slide Bolt, Positive Pressure Threshold, and an Exterior UL Listed Grade 2-Keyed Lever Set. Complete with UL Listed Panic Hardware Set.
HEAT PUMP MINI SPLIT 24K C1D2 1
Mini Split Heating/Cooling Unit 2 Tons 24,000 BTU Cooling Capacity, Heat 24,000 BTU 240v/1p/60Hz, 441-850 Cfm R-32 Refrigerant. Class 1 Division 2 Interior, Exterior General Purpose. 11.6 Eer2 18 Seer2 Minimum Circuit Ampacity 14.7 Max Circuit Breaker 20. Includes Refrigerant Lineset/Com Cables, Wall Mounted, Non Fused Disconnect, 12/3 Flexible Whip.
35525 - 150 MPH WIND LOAD 1
Upgrade Building to 150 Mph Wind Load Requirement.
35525 - SS WORK TABLE 72X48 (minimum) 3
Stainless Steel Work Table, 72"L X 48"D With 1.5" Rounded Front and Back Edge, Bottom Shelf, 16 Gauge, Type 430 Stainless Steel Top. (4) Heavy Gauge Galvanized 1 5/8"DIA. Legs With Plastic Leveling Feet, 600 LB Capacity. NSF Certified.
35525 - LITHIUM BATTERY SIGNAGE 4
Lithium Battery Charging Station Signage to be installed on 4 Sides of Building.
35525 - DOT PLACARDS - LITHIUM CLASS 9 4
Additional DOT Placards to be installed on 4 Sides of Building.
35525 – DATA LABEL 9033-SL2111-26778 1
Additional DOT Placards to be installed on 4 Sides of Building.