C05_SOW_-_Attach_001.pdf
PDF 460 KB Posted
- Attached to
- HVAC CHILLER PIPING & TANK SUPPLY
- Solicitation number
- 140R3023Q0075
About this file
This statement of work outlines the requirements for a supply contract to provide piping, tanks, and associated materials to connect a new chiller unit and air handler at the Parker Dam Powerplant in California. The Bureau of Reclamation Parker Dam Field Office seeks an contractor to supply an expansion tank, 400-gallon storage tank, carbon steel piping in various sizes, fittings, valves, insulation, and other accessories. The contractor must provide mill test certifications confirming all materials meet ASME standards. The delivery location is specified as Parker Dam Highway 95 in Parker Dam, California. The solicitation number for this opportunity is 140R3023Q0075.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| C05_140R3023Q0075.pdf | ||
| C05_SF-18.pdf | ||
| C05_Clauses_and_Provisions.pdf | ||
| C05_Combined_Synopsis.pdf | ||
| C05_Saliant_Characteristics_-_Attach_002.pdf | ||
| Sol_140R3023Q0075.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Parker Dam Powerplant
HVAC Chiller Piping & Tank Supply
Parker Dam, California 140R3023Q0075
Air Cooled, Scroll Water Chillers
Statement of Work
HVAC Chiller Piping & Tank Supply
Parker Dam, California
U.S. Department of Interior
Bureau of Reclamation, Lower Colorado Region
Parker Dam Field Office
Parker Dam, California
Parker Dam, California 140R3023Q0075
Air Cooled, Scroll Water Chillers
HVAC Chiller Piping & Tank Supply
PART 1 GENERAL
1.01 INTRODUCTION
The Bureau of Reclamation Parker Dam is installing an Air-cooled microprocessor-controlled chiller for outdoor installation with hydronic package to serve existing Mainstream MLR-
176X122X2.0-HD SN6655 60,000 cfm air handler. This is a supply contract to supply the
Expansion Tank, Storage Tank, Carbon steel Sch 40 Pipe, Elbows, Tees, Flanges, Valves, and miscellaneous fittings need to pipe the chiller and air handler together.
1.02 BACKGROUND
Parker Dam is a concrete arch structure that spans the Colorado River between Arizona and
California, 155 miles downstream of Hoover Dam. Built between 1934 and 1938 by
Reclamation, Parker Dam is one part of a system of storage and diversion structures built by
Reclamation to control and regulate the once unruly Colorado River. Parker Dam is located 25 miles south of Lake Havasu City, with temperatures ranging from 34° in the winter to 125° in the summer.
1.03 SCOPE
A. Contractor to supply Expansion Tank, Storage Tank, Carbon steel Sch 40 Pipe, Elbows, Tees, Flanges, Valves, and miscellaneous fitting in the table below. Material must meet
American Society of Mechanical Engineers (ASME) ASME SEC 8 -Boiler and Pressure
Vessel Code and provide Mill Test Certifications for material.
1. Expansion Tank: Replaceable bladder type.
a. 6-gallon tank with minimum 4.5-gallon acceptance volume 175 PSI with Sight
Glass.
2. Storage Tank: Insulated carbon-steel tank with internal baffle, drain and vent connections;
with capacity indicated.
a. Maximum footprint of 4’-6” X 5’-0” X 11’-0” (L X W X H) 400-gallon
3. Piping:
a. 4” (Sch 40) Carbon-steel pipe in 20’ lengths.
Parker Dam, California 140R3023Q0075
Air Cooled, Scroll Water Chillers
Item Description Quantity Unit Notes
1 Expansion Tank 6-Gallon with 4.5-gallon acceptance 175
PSI w Sight Glass minimum
1 EA
2 ASME Chilled Water Buffer Tank 400 Gallons 4" Flange 1 EA
3 3” Carbon-steel Threaded 90 (Sch 40) 1 EA
4 3” Carbon-steel Treaded Tee (Sch 40) 1 EA
5 3”x12” Carbon-steel Threaded Nipple (Sch 40) 2 EA
6 3” x 4” Carbon-steel Reducer Butt weld (Sch 40) 4 EA
7 4” Carbon-steel Flanged Globe Valve (Sch40) 4 EA
8 4” Carbon-steel 90 Butt Weld (Sch 40) 30 EA
9 4” Carbon-steel Slip Weld Flange (Sch 40) 30 EA
10 4” Carbon-steel Threaded Flange (Sch 40) 4 EA
11 4” Carbon-steel Tee Butt Weld (Sch 40) 4 EA
12 4” Carbon-steel Pipe (Sch 40) 20’ lengths 260 FT
13 4” SS Flexible Metal Hose Flanged 4 EA
14 1” Carbon-steel Weld Thread O-Let 10 EA
15 3” Carbon-steel Weld Chill Ring 10 EA
16 4” Carbon-steel Weld Chill Ring 80 EA
17 Hinged with Self-Sealing Lap Melamine Foam Pipe
Insulation
260 FT
Parker Dam, California 140R3023Q0075
Air Cooled, Scroll Water Chillers
1.04 DELIVERY
The delivery of the material shall be made to Parker Dam at the following address:
Parker Dam
Highway 95
Parker Dam CA 92267
1.01 ATTACHMENTS
Salient Characteristics
END OF SECTION