C05_Saliant_Characteristics_-_Attach_002.pdf
PDF 93 KB Posted
- Attached to
- HVAC CHILLER PIPING & TANK SUPPLY
- Solicitation number
- 140R3023Q0075
About this file
This document outlines salient characteristics for HVAC chiller piping and tank supply required to fulfill Solicitation Number 140R3023Q0075 issued by the Department of the Interior Bureau of Reclamation. Key requirements include an insulated 400-gallon carbon steel storage tank meeting ASME standards, expansion tank with specified capacity and material meeting ASME, various carbon steel and stainless steel piping components per schedule including pipe, fittings, flanges, valves, insulation, and flexible hose meeting regulatory and material requirements. The manufacturer must provide mill certificates and warranty against defects. Materials will be shipped to the specified Parker Dam Field Division location.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| C05_140R3023Q0075.pdf | ||
| C05_SOW_-_Attach_001.pdf | ||
| C05_SF-18.pdf | ||
| C05_Clauses_and_Provisions.pdf | ||
| C05_Combined_Synopsis.pdf | ||
| Sol_140R3023Q0075.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC Chiller Piping & Tank Supply
Required Salient Characteristics
Expansion Tank: Expansion Tank 6-Gallon with 4.5-gallon acceptance 175 PSI w Sight Glass minimum. Material must meet American Society of Mechanical Engineers (ASME)
ASME SEC 8 -Boiler and Pressure Vessel Code.
Storage Tank: Insulated carbon-steel tank with internal baffle, drain and vent connections; with capacity indicated.
Maximum footprint of 4’-6” X 5’-0” X 11’-0” (L X W X H) 400-gallon.
Material must meet American Society of Mechanical Engineers (ASME) ASME SEC 8 - Boiler and Pressure Vessel Code.
Valves: 4” Carbon-steel Flanged Globe Valve (Sch40)
Carbon-steel Pipe: 4” Carbon-steel Pipe (Sch 40) 20’ lengths
Pipe Fittings and Flanges:
1. 3” Carbon-steel Threaded 90 (Sch 40)
2. 3” Carbon-steel Treaded Tee (Sch 40)
3. 3”x12” Carbon-steel Threaded Nipple (Sch 40)
4. 3” x 4” Carbon-steel Reducer Butt weld (Sch 40)
5. 4” Carbon-steel 90 Butt Weld (Sch 40)
6. 4” Carbon-steel Slip Weld Flange (Sch 40)
7. 4” Carbon-steel Threaded Flange (Sch 40)
8. 4” Carbon-steel Tee Butt Weld (Sch 40)
9. 1” Carbon-steel Weld Thread O-Let
10. 4” SS Flexible Metal Hose Flanged
Chill Rings: 1. 3” Carbon-steel Weld Chill Ring
2. 4” Carbon-steel Weld Chill Ring
Pipe Insulation: Hinged with Self-Sealing Lap Melamine Foam Pipe Insulation
Regulatory Requirements:
Material must meet American Society of Mechanical Engineers (ASME) ASME SEC 8 - Boiler and Pressure Vessel Code.
Safety:
Warranty: Manufacture shall warranty all equipment and material against defects in material and workmanship.
Shipping, Storage, and Protection:
1) Protect all material from physical damage.
2) Shipped to:
Parker Dam Highway 95 Parker Dam Field Division Parker Dam, CA 92267.
Other requirements: Provide Mill Test Certificates (MTC) or Mill Test Reports (MTR)
NOTE:
File details come from the government source that posted it. Updated .