C05__Attachment_Brand_Name_or_Equal_Specs_150KVA__3-Phase_Transformer.pdf

PDF 137 KB Posted

Attached to
Pole Mounted Transformer: 150 kVA, 3-phase Federal contract opportunity
Solicitation number
140R2025Q0088
Issued by
Department of the Interior Bureau of Reclamation

About this file

This document is an Attachment Brand Name or Equal Specifications for a 150 KVA 3-Phase Transformer, solicitation number 140R2025Q0088. The specifications detail a liquid-filled, pole-mounted transformer with a Larson/MT-UPM-R7-3P-DMP-150KVA-YT-CP-A6-BM-CZ-2ZZ-M1 equivalent part number. Key technical requirements include three-phase configuration, 13800V primary voltage, 208Y/120V secondary voltage, delta and wye-n windings, 150 KVA power capacity, and 60 Hz frequency. The transformer features a 5-position tap changer, copper windings, mineral oil insulation, stainless steel hardware, and a weatherproof epoxy coating.

The transformer meets multiple compliance standards, including DOE 2016 Efficiency Ratings and various ANSI/IEEE specifications (C57.12.00 through C57.12.80). It achieves 99.00% efficiency when operating at 50% of nameplate base kVA. Factory testing includes comprehensive evaluations such as winding resistance, insulation resistance, voltage ratio error, short-circuit impedance, no-load and load loss tests, induced voltage withstand, pressure integrity, polarity, and excitation current tests. The unit includes external labeling with KVA rating, a non-PCB label, and a stainless steel riveted nameplate.

View the file

Other files for this federal contract opportunity

Other files attached to Pole Mounted Transformer: 150 kVA, 3-phase, newest first.
File Type Posted
Sol_140R2025Q0088_Amd_0001.pdf PDF
Amd_1_Attachment_1_Revised_Brand_Name_or_Equal_Specs_150KVA__3-Phase_Transformer_0001.pdf PDF
Sol_140R2025Q0088.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140R2025Q0088

Attachment Brand Name or Equal Specifications

Item: 150 KVA 3-PH Transformer

Equivalent to Make/Part number: Larson/MT-UPM-R7-3P-DMP-150KVA-YT-CP-A6-BM-CZ-2ZZ-M1

SALIENT CHARACTERISTICS/SPECIFICATIONS REQUIREMENTS:

• Transformer Type: Liquid Filled Pole Mounted

• Transformer Polarity Type: Subtractive

• Voltage Phase: Three Phase

• Power Capacity: 150 KVA

• Primary Voltage: 13800V

• Primary Winding: Delta

• Primary BIL: 95 kV Minimum

• Secondary Voltage: 208Y/120

• Secondary Winding: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• Temperature Rise: 65°C

• Insulation Rating: Class E Insulation

• Cooling Class: ONAN

• Tap Changer: 5-Position Tap Changer w/ External Operating Handle

• Tap Qty: (2) FCAN Above, (2) FCBN Below

• Tap %: 2.5%

• Impedance: 1.2-6.0% Typical

• Primary Termination: Porcelain High Voltage Bushings

• Mounting Provisions for Installing Lightning Arrestors on H1, H2 & H3 Primary Terminals

• Secondary Connections: NEMA 4-Hole Drilled Spade Terminals

• Secondary Neutral Connection: Secondary X0 Neutral Grounded to Tank via Copper Ground

Strap

• Terminals: Tin Plated Primary and Secondary - Accepts Copper or Aluminum Connections

• Grounding Provisions: (1) Lug w/ Grounding Strap, Tank Grounding Lug

• Efficiency Standard(s): Meets DOE 2016 Standards, Meets ANSI/IEEE Standards K-Factor

Rating (Harmonic Mitigation): K-1 (Standard)

• Insulation Fluid: Mineral Oil - Non PCB Fluid

• Pressure Relief Device: Included, Automatic Action

• Winding Material: Copper

• Ambient Temperature Rating: 40°C Minimum

• Sound Level: 55 dBA

• Tank Material: Coated Steel

• Hardware Material: Stainless Steel Hardware

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating Finish

• Mounting: Pole Mount via Double Hangar Brackets

• Lifting Lugs: Included

140R2025Q0088

Attachment Brand Name or Equal Specifications

• Ratings:

o Meets/Exceeds DOE 2016 Efficiency Ratings o Complies with ANSI / IEEE #C57.12.00 o Complies with ANSI / IEEE #C57.12.20 o Complies with ANSI / IEEE #C57.12.28 o Complies with ANSI / IEEE #C57.12.31 o Complies with ANSI / IEEE C57.12.70 o Complies with ANSI / IEEE C57.12.80 o Complies with ASTM D3487

• Efficiency: 99.00% - Based on transformer operating at 50% of nameplate base kVA.

• Labeling:

o Externally Stencilled (Painted) KVA Rating o External Non-PCB Label o Stainless Steel Riveted Nameplate

• Factory Tests:

o Winding Resistance Test o Insulation Resistance Test o Voltage Ratio Error Test o Short-circuit Impedance Test o No-load Loss (Wattage) Test o Load Loss (Wattage) Test o Induced Voltage Withstand Test o Separate Source Voltage Withstand Test o Pressure Integrity Test o Polarity Test o Excitation Current Test