This document is an Attachment Brand Name or Equal Specifications for a 150 KVA 3-Phase Transformer, solicitation number 140R2025Q0088. The specifications detail a liquid-filled, pole-mounted transformer with a Larson/MT-UPM-R7-3P-DMP-150KVA-YT-CP-A6-BM-CZ-2ZZ-M1 equivalent part number. Key technical requirements include three-phase configuration, 13800V primary voltage, 208Y/120V secondary voltage, delta and wye-n windings, 150 KVA power capacity, and 60 Hz frequency. The transformer features a 5-position tap changer, copper windings, mineral oil insulation, stainless steel hardware, and a weatherproof epoxy coating.
The transformer meets multiple compliance standards, including DOE 2016 Efficiency Ratings and various ANSI/IEEE specifications (C57.12.00 through C57.12.80). It achieves 99.00% efficiency when operating at 50% of nameplate base kVA. Factory testing includes comprehensive evaluations such as winding resistance, insulation resistance, voltage ratio error, short-circuit impedance, no-load and load loss tests, induced voltage withstand, pressure integrity, polarity, and excitation current tests. The unit includes external labeling with KVA rating, a non-PCB label, and a stainless steel riveted nameplate.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140R2025Q0088_Amd_0001.pdf | ||
| Amd_1_Attachment_1_Revised_Brand_Name_or_Equal_Specs_150KVA__3-Phase_Transformer_0001.pdf | ||
| Sol_140R2025Q0088.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140R2025Q0088
Attachment Brand Name or Equal Specifications
Item: 150 KVA 3-PH Transformer
Equivalent to Make/Part number: Larson/MT-UPM-R7-3P-DMP-150KVA-YT-CP-A6-BM-CZ-2ZZ-M1
SALIENT CHARACTERISTICS/SPECIFICATIONS REQUIREMENTS:
• Transformer Type: Liquid Filled Pole Mounted
• Transformer Polarity Type: Subtractive
• Voltage Phase: Three Phase
• Power Capacity: 150 KVA
• Primary Voltage: 13800V
• Primary Winding: Delta
• Primary BIL: 95 kV Minimum
• Secondary Voltage: 208Y/120
• Secondary Winding: Wye-N
• Secondary BIL: 30 KV
• Frequency: 60 Hz
• Temperature Rise: 65°C
• Insulation Rating: Class E Insulation
• Cooling Class: ONAN
• Tap Changer: 5-Position Tap Changer w/ External Operating Handle
• Tap Qty: (2) FCAN Above, (2) FCBN Below
• Tap %: 2.5%
• Impedance: 1.2-6.0% Typical
• Primary Termination: Porcelain High Voltage Bushings
• Mounting Provisions for Installing Lightning Arrestors on H1, H2 & H3 Primary Terminals
• Secondary Connections: NEMA 4-Hole Drilled Spade Terminals
• Secondary Neutral Connection: Secondary X0 Neutral Grounded to Tank via Copper Ground
Strap
• Terminals: Tin Plated Primary and Secondary - Accepts Copper or Aluminum Connections
• Grounding Provisions: (1) Lug w/ Grounding Strap, Tank Grounding Lug
• Efficiency Standard(s): Meets DOE 2016 Standards, Meets ANSI/IEEE Standards K-Factor
Rating (Harmonic Mitigation): K-1 (Standard)
• Insulation Fluid: Mineral Oil - Non PCB Fluid
• Pressure Relief Device: Included, Automatic Action
• Winding Material: Copper
• Ambient Temperature Rating: 40°C Minimum
• Sound Level: 55 dBA
• Tank Material: Coated Steel
• Hardware Material: Stainless Steel Hardware
• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating Finish
• Mounting: Pole Mount via Double Hangar Brackets
• Lifting Lugs: Included
140R2025Q0088
Attachment Brand Name or Equal Specifications
• Ratings:
o Meets/Exceeds DOE 2016 Efficiency Ratings o Complies with ANSI / IEEE #C57.12.00 o Complies with ANSI / IEEE #C57.12.20 o Complies with ANSI / IEEE #C57.12.28 o Complies with ANSI / IEEE #C57.12.31 o Complies with ANSI / IEEE C57.12.70 o Complies with ANSI / IEEE C57.12.80 o Complies with ASTM D3487
• Efficiency: 99.00% - Based on transformer operating at 50% of nameplate base kVA.
• Labeling:
o Externally Stencilled (Painted) KVA Rating o External Non-PCB Label o Stainless Steel Riveted Nameplate
• Factory Tests:
o Winding Resistance Test o Insulation Resistance Test o Voltage Ratio Error Test o Short-circuit Impedance Test o No-load Loss (Wattage) Test o Load Loss (Wattage) Test o Induced Voltage Withstand Test o Separate Source Voltage Withstand Test o Pressure Integrity Test o Polarity Test o Excitation Current Test