Amd_1_Attachment_1_Revised_Brand_Name_or_Equal_Specs_150KVA__3-Phase_Transformer_0001.pdf

PDF 96 KB Posted

Attached to
Pole Mounted Transformer: 150 kVA, 3-phase
Solicitation number
140R2025Q0088
Issued by

About this file

This document is an Amendment 1 Revised Brand Name or Equal Specifications for a 150 KVA 3-Phase Transformer with a detailed technical specification. The transformer is a liquid-filled, pole-mounted unit with a three-phase configuration, designed for 13800V primary voltage and 208Y/120V secondary voltage. Key technical specifications include a 5-position tap changer, copper windings, mineral oil non-PCB fluid, and compliance with DOE 2016 efficiency standards and multiple ANSI/IEEE standards.

The transformer features comprehensive technical requirements such as a 65°C temperature rise, ONAN cooling class, porcelain high voltage bushings, and NEMA 4-hole drilled spade terminals. It undergoes extensive factory testing including winding resistance, insulation resistance, voltage ratio error, short-circuit impedance, and multiple other quality assurance tests. The unit is UL approved, has 99% efficiency at 50% of nameplate base kVA, and includes external labeling with a stainless steel riveted nameplate. The specifications are part of solicitation 140R2025Q0088 and provide detailed performance and technical requirements for potential suppliers.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140R2025Q0088 Attachment 1 Amendment 1 Revised Brand Name or Equal Specifications

Item: 150 KVA 3-PH Transformer

Equivalent to Part number: MT-UPM-R7-3P-DMP-150KVA-YT-CP-A6-BM-CZ-2ZZ-M1

SALIENT CHARACTERISTICS/SPECIFICATIONS REQUIREMENTS:

• Transformer Type: Liquid Filled Pole Mounted

• Transformer Polarity Type: Subtractive

• Voltage Phase: Three Phase

• Power Capacity: 150 KVA

• Primary Voltage: 13800V

• Primary Winding: Delta

• Primary BIL: 95 kV Minimum

• Secondary Voltage: 208Y/120

• Secondary Winding: Wye-N

• Secondary BIL: 30 KV

• Frequency: 60 Hz

• Temperature Rise: 65°C

• Insulation Rating: Class E Insulation

• Cooling Class: ONAN

• Tap Changer: 5-Position Tap Changer w/ External Operating Handle

• Tap Qty: (2) FCAN Above, (2) FCBN Below

• Tap %: 2.5%

• Impedance: 1.2-6.0% Typical

• Primary Termination: Porcelain High Voltage Bushings

• Mounting Provisions for Installing Lightning Arrestors on H1, H2 & H3 Primary Terminals

• Secondary Connections: NEMA 4-Hole Drilled Spade Terminals

• Secondary Neutral Connection: Secondary X0 Neutral Grounded to Tank via Copper Ground

Strap

• Terminals: Tin Plated Primary and Secondary - Accepts Copper or Aluminum Connections

• Grounding Provisions: (1) Lug w/ Grounding Strap, Tank Grounding Lug

• Efficiency Standard(s): Meets DOE 2016 Standards, Meets ANSI/IEEE Standards K-Factor

Rating (Harmonic Mitigation): K-1 (Standard)

• Insulation Fluid: Mineral Oil - Non PCB Fluid

• Pressure Relief Device: Included, Automatic Action

• Winding Material: Copper

• Ambient Temperature Rating: 40°C Minimum

• Sound Level: 55 dBA

• Tank Material: Coated Steel

• Hardware Material: Stainless Steel Hardware

• Paint Type: Weatherproof and UV Resistant Epoxy Coating and Undercoating Finish

• Mounting: Pole Mount via Double Hangar Brackets

• Lifting Lugs: Included

140R2025Q0088 Attachment 1 Amendment 1 Revised Brand Name or Equal Specifications

• Ratings:

o Underwriters Laboratories (UL) Approved o Meets/Exceeds DOE 2016 Efficiency Ratings o Complies with ANSI / IEEE #C57.12.00 o Complies with ANSI / IEEE #C57.12.20 o Complies with ANSI / IEEE #C57.12.28 o Complies with ANSI / IEEE #C57.12.31 o Complies with ANSI / IEEE C57.12.70 o Complies with ANSI / IEEE C57.12.80 o Complies with ASTM D3487

• Efficiency: 99.00% - Based on transformer operating at 50% of nameplate base kVA.

• Labeling:

o Externally Stencilled (Painted) KVA Rating o External Non-PCB Label o Stainless Steel Riveted Nameplate

• Factory Tests:

o Winding Resistance Test o Insulation Resistance Test o Voltage Ratio Error Test o Short-circuit Impedance Test o No-load Loss (Wattage) Test o Load Loss (Wattage) Test o Induced Voltage Withstand Test o Separate Source Voltage Withstand Test o Pressure Integrity Test o Polarity Test o Excitation Current Test

File details come from the government source that posted it. Updated .