C05_02__Attachment_No__3_SOW_Drawings_-_Structural_Steel.pdf

PDF 2 MB Posted

Attached to
NCAO SHASTA DAM TCD HANGER ROD INSTALLATION
Solicitation number
140R2024Q0125
Issued by

About this file

This document appears to be a set of engineering drawings and technical specifications for the replacement of hanger rod assemblies for the shutter structure at Shasta Dam. The drawings provide detailed dimensions and materials requirements for the replacement hanger rod assemblies, including box girders, shutter beams, and connection plates. The key details include:

The replacement hanger rods are to be 59'6" in total length, fabricated from ASTM A572 Grade 50 steel. The drawings provide specific dimensions and detail for the coupler, heavy hex nuts, and plate washers required. The replacement concrete for the connection areas is specified to be an ASTM C387/C387M packaged crack-resistant mix with a minimum 4,000 psi compressive strength. The drawings also note the required clearances, elevations, and layout of the hanger rod assembly in relation to the dam structure.

This document appears to be supporting a federal contract opportunity with Solicitation Number 140R2024Q0125, issued by the Department of the Interior's Bureau of Reclamation, for the NCAO Shasta Dam TCD Hanger Rod Installation project.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

El. 1 067.50

CL. B

OX GIRDER

El. 1

044.96CL. D

C3 PIN

TO SHUTTER BEAM

El. 1 076.67

El. 1 018.00

CL. H

ANGER PIN

5 1/4"ø

5 1/4"ø

5 1/4"ø

BOTTOM

TOP

T h re a d

T h re a d

T h re a d

T h re a d

T h re a d

(2

(2

"c lr

"c lr

Jam Nut (Typ.):

(A194 Gr.2H)

Coupler (Typ.)

(A194 Gr.2H)

Heavy Hex Nut:

(A194 Gr.2H)

Plate Washer:

(A572 Gr.50) PL 2¼"x10½"ø with 5 5/16"ø Hole

Coupler (Typ.)

(A194 Gr.2H)

Heavy Hex Nut:

(A194 Gr.2H)

Plate Washer:

(A572 Gr.50) PL 2¼"x10½"ø with 5 5/16"ø Hole

(2

T o ta l A s s e m b le d H a n g e r

R o d L e n g th

(A G r

M in

Jam Nut (Typ.):

(A194 Gr.2H)

T h re a d

SHASTA DAM

C L

S h u tt e r

S tr u c tu re N o

R

C L

S h u tt e r

S tr u c tu re N o

C L

S h u tt e r

S tr u c tu re N o

C L

S h u tt e r

S tr u c tu re N o

C L

S h u tt e r

S tr u c tu re N o

Axis of dam

F L O

W

Trashrack Structure (Typ.)

/2

49' - 9" 49' - 9" 49' - 9" 49' - 9"

Shutter structure not shown

Connection SC31 (22417)

Coupler (Typ.)

Box Girder

Remove and Replace LS-US Temporary Hanger Rod Assembly

Shutter Beam (22142)

RS-US Rod

RS-DS Rod

LS-US Rod

LS-DS Rod

Connection DC3 (22436) Connection SC36 (22419)

Connection Pl. CP2B (22435)

Replacement Concrete

±4'-1 1/2"

3'-7 1/2"

Edge of Walkway

C o n n e c ti o n

P la te C

P B

R e p la c e m e n t

C o n c re te

Connection Plate

CP2B

Remove and Replace LS-US Temporary Hanger Rod Assembly

Replacement Concrete, see Materials Table

RS-US Rod

RS-DS RodLS-DS Rod

LS-US Rod

Connection Plate CP2B (22435)

F L O

W

See Note 2

A

B

Connection Pl. CP2B (22435)

Connection SC31 (22417)

Shutter Beam (22142)

HP, Approx. El. 1078.3

Shutter structure not shown

Edge of Walkway

Upstream (US) Hanger Rods

Downstream (DS) Hanger RodsFLOW

Box Girder

Replacement Concrete, see Materials Table

/2

/2

Box Girder

See Note 2

Axis of Dam

El. 1019.75

Connection DC3 (22436) Connection SC36 (22419)

Connection DC5 (22436)

B R e p la c e m e n t

H a n g e r

R o d A s s e m b li e s L

(T y p

El. 1067.50

CL. BOX GIRDER

El. 1044.96

CL. DC3 PIN

TO SHUTTER BEAM

El. 1076.67

El. 1018.00

CL. HANGER PIN

A

Box Girder

Left Side (LS) Hanger Rods

Right Side (RS) Hanger Rods

Connection SC31 (22417)

Shutter structure not shown

Connection Pl. CP2B (22435)

Shutter Beam (22142)

Box Girder

See Note 2

Replacement Concrete, see Materials Table

El. 1019.75

Connection DC3 (22436) Connection SC36 (22419)

D

C

B

D

C

B

A

A

S A

F E T Y

A L W

A Y S T

H

IN

K

B U

R E A U

O F R

E C L A M

A T

IO

N

U .S

D

E P A R T M

E N

T O

F T

H E I

N T E R

IO

R

DESIGNED

REVIEWED

C E N

T R A L V

A L L E Y P

R O

JE

C T

S H

A S T A D

IV

IS

IO

N

S H

A S T A D

A M

H A N

G E R R

O D

R E P L A C E M

E N

T

Brandon Jackson, PE

Richard Moore, PE

DENVER, CO 2024-07-24

STRUCTURAL STEEL

PLAN, DETAILS, AND

SECTIONS

FIGURE 1

REPLACEMENT HANGER ROD ASSEMBLY

GOVERNMENT FURNISHED (ESTIMATED ASSEMBLED WEIGHT 5,000 LBS)

Scale: 3/64" = 1'-0"

KEY PLAN

HANGER ROD GROUP

Scale: 1/2" = 1'-0"

DETAIL

Scale: 1/4" = 1'-0" A

SECTION

Scale: 1/4" = 1'-0"

B

SECTION

1. All elevations are based on NAVD88 vertical datum

2. Cut off excess rod length after pre-tensioning, provide 2-inch minimum concrete cover over rods. Field cutting should be done with an abrasive wheel or band saw.

3. Existing components/elements denoted by halftone.

NOTES

ABBREVIATIONS

0 20' 40'

Scale: 3/64" = 1'-0"

0 1' 2' 4'

Scale: 1/2" = 1'-0"

2'0 4' 8'

Scale: 1/4" = 1'-0"

CL. Center Line clr. Clear CP Connection Plate DC Dam Connection DWG Drawing DS Downstream El. Elevation HP High Point LS Left Side

NTS Not to Scale RS Right Side SC Steel Connection TO Top of (Object Listed) Typ. Typical US Upstream PL/Pl. Plate psi Pounds-per-square-inch

Replacement Concrete

ASTM C387/C387M Packaged Crack-Resistant

Concrete mix containing fiber reinforcement.

Minimum Compressive Strength (f'c) = 4,000psi at

28 days

CONCRETE

MATERIAL STANDARD

MATERIAL TABLE

Scale: NTS

Sheets
FIGURE 1 - Unnamed
2024-07-24T10:27:29-0600
BRANDON JACKSON
I am approving this document
2024-07-24T10:39:20-0600
RICHARD MOORE