C04_Attachment 7 - Drawings 04 - Mechanical-Electrical.pdf

PDF 41 MB Posted

Attached to
Construct Sugarcane Research Laboratory Federal contract opportunity
Solicitation number
1232SA26R0027
Issued by
Department of Agriculture Agricultural Research Service

About this file

These mechanical and electrical drawings and specifications establish the HVAC system design requirements for the Sugarcane Research Laboratory construction project in Houma, Louisiana. The drawings include general mechanical notes, abbreviations and legends, demolition plans, HVAC floor plans, equipment schedules, piping diagrams, mechanical details, and controls documentation for a two-story research facility with laboratory, office, and support spaces.

The project requires installation of a new air-cooled chiller (CH-1 and CH-2), two boilers (B-1 and B-2) for heating water, replacement pumps with variable frequency drives for both chilled and heating water loops, two air handling units (AHU-1 and AHU-2) with variable air volume (VAV) terminal boxes, laboratory exhaust fans (LEF-1A/1B with N+1 redundancy), general exhaust fans, and distributed ductwork with diffusers and grilles throughout the facility. The system incorporates 17 VAV boxes for zone control, multiple heating and chilled water coils, exhaust valves for laboratory equipment including fume hoods and biological safety cabinets, and condensate management systems. All equipment must comply with the Buy American Act and be rated for coastal environment durability with salt spray test certification. The HVAC controls utilize a direct digital control (DDC) system with BACnet networking, integrating the new equipment with existing systems to maintain all current monitoring, control, and alarm functions. Existing heating and chilled water systems must remain fully operational throughout construction, and any damage resulting from contractor operations must be repaired at no additional cost to the government.

View the file

Other files for this federal contract opportunity

Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL GENERAL NOTES

M-001 116 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

1. INSTALLATION OF HVAC WORK SHALL BE COORDINATED WITH OTHER TRADES BEFORE ANY INSTALLATION IS DONE. DUCTWORK SHOWN ON PLANS IS SCHEMATIC. PROVIDE ALL TRANSITIONS, ELBOWS, ETC. REQUIRED TO AVOID CONFLICTS & MAXIMIZE CEILING HEIGHTS. EQUIPMENT, PIPING OR DUCTWORK INTERFERING WITH OTHER TRADES SHALL BE RELOCATED AS REQUIRED AT NO

ADDITIONAL COST TO THE OWNER.

2. COORDINATE MECHANICAL AND ELECTRICAL SUCH THAT MECHANICAL PIPING, DUCTWORK AND EQUIPMENT IS NOT LOCATED OVER OR

ABOVE ANY ELECTRICAL, COMMUNICATIONS, OR DATA EQUIPMENT.

3. AT START OF CONSTRUCTION, PREPARE TYPED LISTS OF EQUIPMENT THAT ARE SUPPLIED REQUIRING ELECTRICAL WORK, AND SEND

LISTS TO THE ELECTRICAL CONTRACTOR FOR REVIEW AND COORDINATION.

4. WRITTEN DIMENSIONS ON DRAWINGS SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. VERIFY DIMENSIONS ON SITE.

5. EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S APPROVED CLEARANCE, UNIFIED FACILITIES CRITERIA, AND INTERNATIONAL BUILDING CODE / INTERNATIONAL MECHANICAL CODE.

6. INSTALLATION OF EQUIPMENT SHALL PERMIT ACCESSIBILITY FOR SERVICE AND/OR REPLACEMENT WITHOUT NECESSITATING

REMOVAL OR MODIFICATION TO OTHER PIPING, WIRING, OR EQUIPMENT.

7. CEILING-MOUNTED EQUIPMENT SHALL BE INSTALLED IN SUCH A MANNER THAT LIGHTS, PIPING, DUCTWORK, ETC., DO NOT BLOCK

ACCESS TO EQUIPMENT AND RELATED ACCESSORIES.

8. DUCTWORK AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS AND THE PRESSURE

CLASSIFICATION OF EACH INDIVIDUAL DUCTWORK SYSTEM.

9. VOLUME DAMPERS SHALL BE PROVIDED AT EACH MAIN BRANCH TAKE-OFF, EACH TAKEOFF TO DIFFUSERS/GRILLS/REGISTERS, AND OTHER LOCATIONS WHERE REQUIRED TO PROPERLY BALANCE THE SYSTEM. ALL REQUIRED VOLUME DAMPERS MAY NOT BE SHOWN

ON PLANS.

10. INSTRUMENT TEST HOLES SHALL BE PROVIDED IN AIR DISTRIBUTION SYSTEMS WHEREVER VOLUME DAMPERS ARE INSTALLED. TEST

HOLES SHALL BE SEALED WITH RUBBER OR PLASTIC TEST HOLE PLUGS.

11. SQUARE ELBOWS SHALL ONLY BE USED WHERE SPACE LIMITATIONS PREVENT USE OF 1.5 RADIUS ELBOW AND ONLY UPON APPROVAL OF CONTRACTING OFFICER. PROVIDE TURNING VANES IN ALL SQUARE ELBOWS GREATER THAN OR EQUAL TO 45°. TURNING VANES SHALL BE SINGLE THICKNESS TYPE WITHOUT RAILING EDGE. TURNING VANES LONGER THAN 36 INCHES SHALL BE DOUBLE THICKNESS

TYPE.

12. DUCTWORK RUNOUTS TO AIR DISTRIBUTION DEVICES SHALL BE SAME DIAMETER AS AIR DISTRIBUTION DEVICE INLET CONNECTION

UNLESS OTHERWISE NOTED ON THE DRAWINGS.

13. FLEXIBLE DUCTWORK RUNOUTS FROM BRANCH DUCTS TO AIR DISTRIBUTION DEVICES SHALL NOT EXCEED 5 FEET IN LENGTH. BENDS IN FLEXIBLE DUCTWORK SHALL NOT EXCEED A MAXIMUM OF 45 DEGREE CHANGE OF DIRECTION AND SHALL BE SUPPORTED SUCH THAT THE BEND RADIUS IS NOT RESTRICTIVE TO AIR FLOW THROUGH THE DUCT. FLEXIBLE DUCTWORK SHALL NOT BE CRUSHED OR

DISTORTED IN ITS FINAL CONFIGURATION.

14. PROVIDE SHEETMETAL TRANSITIONS AT AIR HANDLING UNITS, HEAT PUMP UNITS, FANS, AND OTHER SIMILAR HVAC EQUIPMENT.

TRANSITION TO FULL SIZE OF CONNECTION ON UNIT. FLEXIBLE DUCT CONNECTORS SHALL BE USED ON FINAL CONNECTION TO AIR

HANDLING EQUIPMENT.

15. EXACT LOCATION OF CEILING DIFFUSERS, GRILLES AND REGISTERS SHALL BE DETERMINED BY ARCHITECTURAL REFLECTED CEILING

PLAN.

16. EXACT LOCATIONS OF THERMOSTATS, CO2 SENSORS, AND EMCS SENSORS SHALL BE COORDINATED WITH FINAL LOCATIONS OF WALL-MOUNTED ARCHITECTURAL AND ELECTRICAL EQUIPMENT. MOUNT THERMOSTATS AND CO2 SENSORS MINIMUM 48" AFF.

17. SPECIFICATIONS TAKE PRECEDENCE OVER DRAWINGS. HOWEVER, ITEMS SHOWN ON DRAWING BUT NOT IN THE SPECIFICATIONS ARE REQUIRED WITHIN THE PROJECT SCOPE. IN ADDITION, SPECIFIC ITEMS SHOWN ON THE DRAWINGS TAKE PRECEDENCE OVER

SPECIFICATIONS IN CASES WHERE THE SPECIFICATION HAS OPTIONS.

18. DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

19. EXPOSED DUCTWORK, WITH THE EXCEPTION OF DUCTWORK IN MECHANICAL ROOMS SHALL BE DOUBLE-WALL, DUCTWORK WITH

COATING.

20. NOT ALL MECHANICAL ABBREVIATIONS SHOWN WILL BE USED FOR THIS PROJECT.

21. ALL THERMOSTATS SHALL BE WALL MOUNTED AND WIRED.

22. ALL EQUIPMENT INSTALLED IN THIS PROJECT SHALL COMPLY WITH THE "BUY AMERICAN ACT". BASIS OF DESIGN SHOWN ON SCHEDULES IS TO ESTABLISH A STANDARD OF QUALITY, NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT FROM ANOTHER MANUFACTURER IS ACCEPTABLE. MANUFACTURER NAME AND MODEL NUMBERS ARE BASIS OF DESIGN AND ARE SHOWN FOR

INFORMATION ONLY. REFER TO SPECIFICATIONS FOR COMPLETE REQUIREMENTS.

23. ALL COMMUNICATIONS PREMISE WIRING AND CABLE TRAYS THROUGHOUT THE FACILITY MUST BE PROTECTED AND UNINTERRUPTED DURING CONSTRUCTION. THIS INCLUDES ELECTRICAL POWER TO COMMUNICATIONS EQUIPMENT. NO COMMUNICATIONS OUTAGES MUST TAKE PLACE WITHOUT THE CONSENT OF THE CONTRACTING OFFICER.

24. CONTRACTOR MUST DEMOLISH ALL EQUIPMENT, PIPING, DUCTWORK, INSULATION, SUPPORTS, CONTROLS THERMOSTATS, WIRING AND ALL APPURTENANCES WITH THE HVAC SYSTEM TO BE DEMOLISHED.

25. CONTROLS CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE DEVICES, CONDUCTORS, AND PATHWAYS IN ACCORDANCE WITH THE REQUIREMENTS OF 26 20 00. INSTALL CONTROL WIRING IN CONDUIT. SEE DIVISION 26 SPECIFICATIONS FOR REQUIREMENTS.

26. THE DESIGN INTENT OF THIS PROJECT IS TO REPLACE THE EXISTING CONTROLS SYSTEM IN ITS ENTIRETY, EXCLUDING EXISTING TO REMAIN ITEMS BUT INCLUDING ALL CONTROL PANELS, DEVICES, WIRING, COMPONENTS, AND ASSOCIATED APPURTENANCES TO BE DEMOLISHED NECESSARY TO PROVIDE A COMPLETE, FULLY FUNCTIONAL, AND OPERATIONAL SYSTEM. ALL EXISTING EQUIPMENT INDICATED TO REMAIN MUST BE COMPLETELY CONNECTED TO AND FULLY INTEGRATED WITH THE NEW CONTROLS SYSTEM. THE NEW CONTROLS SYSTEM MUST MAINTAIN ALL EXISTING MONITORING, CONTROL, TRENDING, INTERLOCK, AND ALARM FUNCTIONS CURRENTLY PROVIDED BY THE EXISTING SYSTEM. ALL EXISTING CONTROL POINTS, WHETHER SPECIFICALLY INDICATED ON THE DRAWINGS OR NOT, MUST BE MAINTAINED AND INCORPORATED INTO THE NEW SYSTEM. CONTRACTOR MUST FIELD-VERIFY ALL EXISTING CONTROL POINTS, SEQUENCES OF OPERATION, INTERLOCKS, AND CONNECTIONS PRIOR TO INSTALLATION. UPON COMPLETION OF THE CONTROLS SYSTEM WORK, ALL NEW AND EXISTING EQUIPMENT AFFECTED BY THIS PROJECT MUST BE TESTED, CALIBRATED, AND BALANCED AS REQUIRED TO VERIFY PROPER SYSTEM OPERATION AND

PERFORMANCE IN ACCORDANCE WITH THE FINAL SEQUENCES OF OPERATION.

27. ALL EQUIPMENT PROVIDED MUST BE SELECTED FOR USE IN A COASTAL ENVIRONMENT AND MUST HAVE 3000 HOUR DURATION TEST FOR OUTSIDE EQUIPMENT AND EQUIPMENT BRINGING IN OR IN CONTACT WITH OUTDOOR AIR. PROVIDE MECHANICAL EQUIPMENT COILS WITH A MANUFACTURE APPROVED COATING SYSTEM THAT IS DESIGNED FOR A 5000 HOUR DURATION SALT

SPRAY TEST.

GENERAL MECHANICAL NOTES:

DylanMitchell JMC Drawing Template

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL

ABBREVIATIONS AND LEGEND

M-002 117 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

ABBREVIATIONS:

@ AT

& AND

AHU AIR HANDLING UNIT

ARCH ARCHITECT, ARCHITECTURAL

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATING,

AND AIR CONDITIONING ENGINEERS

ASTM AMERICAN SOCIETY FOR TESTING AND

MATERIALS

BDD BACKDRAFT DAMPER

BLDG BUILDING

BTU, BTUH BRITISH THERMAL UNITS, BTUs PER HOUR

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE

CHW CHILLED WATER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CLG COOLING

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

CO2 CARBON DIOXIDE

CONC CONCRETE

COND STEAM CONDENSATE

CONN CONNECT, CONNECTING, CONNECTION

CONT CONTINUED

CONV STEAM CONVERTER

COP COEFFICIENT OF PERFORMANCE

COR CONTRACTING OFFICER'S (OWNER'S)

REPRESENTATIVE

CT COOLING TOWER

CU CONDENSING UNIT

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

D DEPTH

DB, Tdb DRY BULB (TEMPERATURE) dBA DECIBELS

DCW DOMESTIC COLD WATER

DDC DIRECT DIGITAL CONTROLS

DEG. F (°F) DEGREES FAHRENHEIT

DF DESTRATIFICATION FAN

DFCU DUCTLESS FAN COIL UNIT

DH DEHUMIDIFIER

DIA, Ø DIAMETER

DIV DIVISION

DN DOWN

DP, PD DIFFERENTIAL PRESSURE, PRESSURE DROP

DSCU DUCTLESS SPLIT CONDENSING UNIT

DSHP DUCTLESS SPLIT HEAT PUMP

DWG DRAWING

DX DIRECT EXPANSION

EA EXHAUST AIR

EAG EXHAUST AIR GRILLE

EAT ENTERING AIR TEMPERATURE

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRICAL

EMCS ENERGY MONITORING AND CONTROLS SYSTEM

ERU ENERGY RECOVERY UNIT

ERV ENERGY RECOVERY VENTILATOR

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EWT ENTERING WATER TEMPERATURE

EXT EXTERIOR

EXH EXHAUST

EXIST. EXISTING

FCU FAN COIL UNIT

FD FIRE DAMPER

FFE FINISHED FLOOR ELEVATION

FLA FULL LOAD AMPS

FOB FLAT ON BOTTOM

FOT FLAT ON TOP

FPM FEET PER MINUTE

FSD FIRE SMOKE DAMPER

FT FOOT, FEET

FT WG FEET WATER GAUGE

FV FLUE VENT

GA GAGE

GC GENERAL CONTRACTOR

GPM GALLONS PER MINUTE

GWH GAS WATER HEATER

H HEIGHT

HPS HIGH PRESSURE STEAM

HR HOUR

HTG HEATING

HTR HEATER

HTW HEATING WATER

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HVAC HEATING, VENTILATING, AND AIR CONDITIONING

HX HEAT EXCHANGER

HZ HERTZ

IMC INTERNATIONAL MECHANICAL CODE

IN INCH, INCHES

IN WC INCHES WATER COLUMN

IN WG INCHES WATER GAUGE

IPLV INTEGRATED PART LOAD VALUE

KW KILOWATTS

L LENGTH, LOUVER (WALL)

LAT LEAVING AIR TEMPERATURE

LBD LINEAR BAR DIFFUSER

LBS POUNDS

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH 1000 BRITISH THERMAL UNITS

MCA MINIMUM CIRCUIT AMPACITY

MECH MECHANICAL

MERV MINIMUM EFFICIENCY REPORTING VALUE

MFCR, MFCG MANUFACTURER, MANUFACTURING

MIN MINIMUM

MOCP, MOP MAXIMUM OVER CURRENT PROTECTION

MTWR MEDIUM TEMPERATURE WATER RETURN

MTWS MEDIUM TEMPERATURE WATER SUPPLY

MXB MIXING BOX

N.C. NORMALLY CLOSED

NC NOISE CRITERIA

NG NATURAL GAS

NO. NUMBER

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OA OUTSIDE AIR

OD OUTSIDE DAMPER

PCHWR PLANT CHILLED WATER RETURN

PCHWS PLANT CHILLED WATER SUPPLY

PD PRESSURE DROP

PH PHASE

PLBG PLUMBING

PMTWR PLANT MEDIUM TEMPERATURE WATER RETURN

PMTWS PLANT MEDIUM TEMPERATURE WATER SUPPLY

PPM PARTS PER MILLION

PRV PRESSURE RELIEF VALVE

PSI POUNDS PER SQUARE INCH

QTY QUANTITY

RA RETURN AIR

RAG RETURN AIR GRILLE

RH RELATIVE HUMIDITY, ROOF HOOD

RM ROOM

RPM REVOLUTIONS PER MINUTE

SA SUPPLY AIR

SAD SUPPLY AIR DIFFUSER

SAG SUPPLY AIR GRILLE

SD SMOKE DAMPER, SMOKE DETECTOR

SEER SEASONAL ENERGY EFFICIENCY RATIO

SF SUPPLY FAN

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTOR'S NATIONAL ASSOCIATION

SP STATIC PRESSURE

SS STAINLESS STEEL

TEMP TEMPERATURE

TSTAT THERMOSTAT

TYP TYPICAL

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UMCS UTILITY MONITORING AND CONTROL SYSTEM

V VOLTAGE, VOLTS

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER

VFD VARIABLE FREQUENCY DRIVE

VRF VARIABLE REFRIGERANT FLOW

WB, Twb WET BULB (TEMPERATURE)

BALANCING VALVE - PLUMBING

BALANCING VALVE - MECHANICAL

INDICATE DIRECTION OF FLOW

LEGEND

GATE VALVE

RS REFRIGERANT SUCTION

RL REFRIGERANT LIQUID

FIGURE IS SIDE SHOWN)

INSIDE DUCT SIZE (FIRST500x300

FLEXIBLE DUCT CONNECTION

AIR DIFFUSER, ARROWS

CEILING MOUNTED SUPPLY

EXHAUST AIR GRILLE

MANUAL VOLUME DAMPER

M MOTORIZED DAMPER

SOLENOID VALVE

GAS VALVE

FIRE DAMPER

DUCTWORK

CHILLED WATER RETURN

CHILLED WATER SUPPLY

HEATING WATER SUPPLY

HEATING WATER RETURN

HVAC PIPING

HWS

HWR

CHR

CHS

BUTTERFLY VALVE

SWING GATE CHECK VALVE

VALVES

GLOBE VALVE

ELECTRIC OPERATED GATE VALVE

3WAY ELECTRIC MOTOR CONTROLLER

M

M

S

BALL VALVE

SPRING CHECK VALVE

CONTROL DIAGRAMS

SUPPLY AIR DIFFUSER

LABORATORY SUPPLY AIR DIFFUSER

EXHAUST AIR GRILLE

WITH HEPA FILTER

CONSTANT VOLUME VENTURI AIR VALVE

VARIABLE VOLUME VENTURI AIR VALVE

SOLENOID OPERATED GATE VALVE

S

PNEUMATIC OPERATED GATE VALVE

M

M

MCC MOTOR CONTROL CENTER

HC HUMIDITY CONTROLLER

PC PRESSURE CONTROLLER

TC TEMPERATURE CONTROLLER

VSC VARIABLE SPEED MOTOR CONTROLLER

CS CURRENT SENSOR

PS

DIFFERENTIAL PRESSURE SWITCH (BINARY)

DIFFERENTIAL PRESSURE SENSOR (ANALOG)

ES DAMPER END SWITCH (BINARY)

H HUMIDITY SENSOR

P PRESSURE SENSOR

P

AIR FLOW SWITCH

HAND OFF AUTO SWITCH

S MANUAL SWITCH

S/S START / STOP SWITCH

TTT AIR FLOW MEASURING STATION

AFS

HOA

T TEMPERATURE SENSOR

H HUMIDISTAT (SPACE)

T THERMOSTAT (SPACE)

VARIABLE VOLUME VENTURI AIR VALVE

M

WITH ROOM LEVEL CONTROLLER

CONSTANT VOLUME VENTURI AIR VALVE

WITH ROOM LEVEL CONTROLLER

APM ACTIVE ROOM PRESSURE MONITOR

LDU LOCAL DISPLAY UNIT FOR MONITORING AND CONTROLFLEXIBLE DUCT

ROUND OR RECTANGULAR DUCT

SQUARE OR RECTANGULAR DUCT

ELBOW WITH TURNING VANES

RADIUS ELBOW

LABORATORY SUPPLY AIR DIFFUSER

S SMOKE DETECTOR

FS FLOW SENSOR

HUMIDITY CONTROLLER

ENTHALPY CONTROLLER

BACKDRAFT DAMPER

PARALLEL BLADE DAMPER

OPPOSED BLADE DAMPER

UCM UNIT CONTROL MODULE

RETURN AIR GRILLE

SUPPLY AIR DUCT UP

SUPPLY AIR DUCT DOWN

RETURN AIR DUCT UP

RETURN AIR DUCT DOWN

EXHAUST AIR DUCT UP

EXHAUST AIR DUCT DOWN

A ROOM SETPOINT ADJUSTMENT

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

FIRST FLOOR MECHANICAL

DEMOLITION PLAN

MD101

118 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

4" HTWS AND HTWR

UP TO PENTHOUSE

6" CHWS AND CHWR UP

TO PENTHOUSE

3"

6" 6"

DEMOLISH EXISTING CHILLER AND

PIPING BACK TO ISOLATION VALVES.

EXISTING UNIT HEATER (TYP.)

EXISTING HYDRONIC PIPING TO

EXISTING GREENHOUSE

EXISTING HEATING COIL TO

REMAIN (TYP.)

EXISTING HEATING COIL TO

REMAIN (TYP.)

EXISTING HEATING COIL TO

REMAIN (TYP.)

EXISTING HEATING COIL TO

REMAIN (TYP.)

EXISTING HEATING COIL TO

REMAIN (TYP.)

EXISTING PIPING UP TO

SECOND FLOOR TO REMAIN EXISTING PIPING ROUTED

BELOW GRADE TO

PHOTOPERIOD BUILDING

EXISTING UNIT HEATER TO

REMAIN (TYP.)

1. DEMOLISH EXISTING CHILLER AND ALL

APPURTENANCES. DEMOLISH EXISTING PIPING

UP TO EXISTING ELBOW SHOWN AS AN EXTENT

OF DEMOLITION AND TEMPORARILY CAP FOR

RECONNECTION.

1. THE DEMOLITION PLAN AND EXISTING

CONDITIONS ARE APPROXIMATE. ITEMS TO BE

REMOVED ARE DESIGNATED BY HATCHING AND

DASHED LINES. OTHER ITEMS ARE INTENDED TO

REMAIN IN PLACE UNLESS NOTED OTHERWISE.

2. ANY DAMAGE TO EXISTING TO REMAIN SYSTEMS

MUST BE REPAIRED AT NO COST TO THE

GOVERNMENT.

KEYED NOTES

GENERAL NOTES

EXTENT OF DEMOLITION

LEGEND

EXISTING HYDRONIC PIPING TO

EXISTING GREENHOUSE

EXISTING HYDRONIC PIPING TO

EXISTING GREENHOUSE

EXISTING UNIT HEATER TO

REMAIN (TYP.)

EXISTING PIPING UP TO

SECOND FLOOR TO REMAIN

EXISTING PIPING UP TO

SECOND FLOOR TO REMAIN

SCALE:

FIRST FLOOR MECHANICAL DEMOLITION PLAN

1/8"=1'-0"

MD101

PLAN

NORTH

TRUE

NORTH

DN

DN

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

SECOND FLOOR MECHANICAL

DEMOLITION PLAN

MD102

119 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

6"

6"

4"

6"

3"

1-1/2"

1-1/2"

1-1/2"2"

4"

3"

4"

EXISTING UNIT HEATER (TYP.)

DEMOLISH EXISTING BOILER AND ALL

APPURTENANCES. EXISTING BOILER

FLUES THROUGH ROOF MUST REMAIN

IN PLACE FOR RECONNECTION. CAP

EXISTING PIPING FOR RECONNECTION.

EXISTING HEATING COIL (TYP.)

EXISTING HEATING COIL (TYP.)

EXISTING HYDRONIC PIPING

DOWN TO FIRST FLOOR

EXISTING UNIT HEATER (TYP.)

EXISTING UNIT HEATER (TYP.)

DEMOLISH EXISTING

EXPANSION TANK

DEMOLISH EXISTING PUMPS

AND ALL APPURTENANCES.

CAP EXISTING PIPING FOR

RECONNECTION.

1. DEMOLISH EXISTING PIPING, HANGERS AND

ALL APPURTENANCES UP TO EXISTING TEE

AND TEMPORARILY CAP FOR RECONNECTION.

TEMPORARILY CAP PIPING SERVING EXISTING

EQUIPMENT TO REMAIN.

2. DEMOLISH EXISTING AIR SEPARATOR AND

TEMPORARILY CAP PIPING FOR

RECONNECTION. EXISTING MAKEUP WATER

CONNECTION MUST BE CAPPED AND REMAIN

IN PLACE FOR REUSE.

1. THE DEMOLITION PLAN AND EXISTING

CONDITIONS ARE APPROXIMATE. ITEMS TO BE

REMOVED ARE DESIGNATED BY HATCHING AND

DASHED LINES. OTHER ITEMS ARE INTENDED TO

REMAIN IN PLACE UNLESS NOTED OTHERWISE.

2. THE EXISTING HEATING WATER AND CHILLED

WATER SYSTEMS MUST REMAIN FULLY

OPERATIONAL THROUGHOUT CONSTRUCTION. IF

THE EXISTING SYSTEM IS REQUIRED TO BE

TAKEN OUT OF SERVICE AT ANY TIME, THE

CONTRACTOR MUST PROVIDE A TEMPORARY

SYSTEM TO MAINTAIN CONTINUOUS SERVICE,

OR OBTAIN PRIOR APPROVAL FOR A SCHEDULED

DOWNTIME WINDOW. ALL PROPOSED OR

ESTIMATED DOWNTIME MUST BE COORDINATED

IN ADVANCE AND RECEIVE WRITTEN APPROVAL

FROM THE GOVERNMENT PRIOR TO

IMPLEMENTATION. THE CONTRACTOR IS

RESPONSIBLE FOR PROTECTING ALL

COMPONENTS AND FUNCTIONS OF ALL EXISTING

SYSTEM THROUGHOUT ALL PHASES OF

CONSTRUCTION. ANY DAMAGE OR

INTERRUPTION TO THE SYSTEM RESULTING

FROM THE CONTRACTOR’S OPERATIONS MUST

BE REPAIRED OR REPLACED AT NO ADDED COST

TO THE GOVERNMENT.

KEYED NOTES

GENERAL NOTES

EXTENT OF DEMOLITION

LEGEND

EXISTING AHU-3 TO

REMAIN

DEMOLISH EXISTING PUMPS AND ALL

APPURTENANCES. CAP EXISTING

PIPING FOR RECONNECTION.

6" CHWS AND CHWR

DOWN TO FIRST FLOOR

4" HTWS AND HTWR

DOWN TO FIRST FLOOR

EXISTING HYDRONIC PIPING

DOWN TO FIRST FLOOR

SCALE:

SECOND FLOOR MECHANICAL DEMOLITION PLAN

1/8"=1'-0"

MD102

PLAN

NORTH

TRUE

NORTH

DEMOLISH EXISTING

EXPANSION TANK

1EXISTING MAKEUP WATER

PIPING TO REMAIN IN PLACE

EXISTING MAKEUP WATER

PIPING TO REMAIN IN PLACE

18"Ø34x20

20"Ø16"Ø

"Ø

"Ø

24x20

"Ø

18"Ø

26x18

20"Ø 18"Ø 16"Ø 14"Ø 12"Ø

"Ø

"Ø

10"Ø 10"Ø

10"Ø

"Ø

"Ø 12"Ø

10"Ø

"Ø

10"Ø

"Ø

14"Ø 14"Ø 10"Ø

16"Ø20"Ø20"Ø

"Ø

10"Ø

10"Ø 10"Ø

8" Ø

14"Ø

"Ø

"Ø

12"Ø

22"Ø22"Ø

10"Ø 14"Ø 14"Ø

14"Ø

"Ø

"Ø

12"Ø12"Ø 14"Ø

8"Ø

8" Ø8"Ø

8" Ø

"Ø

10"Ø

8" Ø

8" Ø

8" Ø

12"Ø16"Ø

"Ø

14"Ø

"Ø

"Ø

"Ø

"Ø

"Ø

"Ø

10"Ø

10"Ø

"Ø

18"Ø

16"Ø

"Ø

"Ø

"Ø

"Ø

"Ø

12"Ø

"Ø

18"Ø16"Ø12"Ø

"Ø

"Ø

"Ø10

"Ø

10"Ø

"Ø

14"Ø

12"Ø

10"Ø

"Ø

12"Ø

10"Ø

14"Ø

12"Ø 14"Ø 14"Ø

10"Ø 10"Ø

12"Ø14"Ø16"Ø

12"Ø14"Ø

22"Ø 12"Ø14"Ø20"Ø20"Ø x2

14"Ø

14"Ø

12"Ø

14"Ø

8"Ø

"Ø

6" Ø

"Ø

"Ø

"Ø

10" Ø

48x32 x3 x1 x3 x1

"Ø

"Ø

14"Ø

22"Ø x1 x1 x1 x1

24x18 x1

12x12 x1

12x10

16x1418x1420x1420x16 x1

814x1010x10

36x22

12x12 x1

20x18 x2

48x22 48x22

34x22

10x10 x1 x1 x1

8 8x8

22x18

12x12 x1

10x10 x1

34x22

8" Ø

12"Ø

16"Ø 16"Ø

20"Ø

"Ø

"Ø

8"Ø 8"Ø

6"Ø 14"Ø

12"Ø

14"Ø

12"Ø

"Ø

"Ø

"Ø

14"Ø

"Ø

"Ø

8" Ø

12"Ø

6" Ø

12"Ø

"Ø

10"Ø

"Ø

10"Ø

16"Ø

"Ø

8" Ø

10"Ø

14"Ø

8"Ø

10"Ø

10"Ø

10"Ø

8x8

1058 1059 1060

1045 1046

1042 1038

1034 1033

101710161015101410131012

1035 1036

12"Ø 14x18

10x10 x1

12"Ø x1

14"Ø x2

"Ø

34x20 x2

32x20

"Ø

"Ø

8" Ø

10" Ø

"Ø

"Ø48x22

14"Ø

14"Ø 16"Ø

16"Ø

"Ø

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC OVERALL

FIRST FLOOR PLAN

MH101

120 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

MH404

SCALE:

OVERALL FIRST FLOOR HVAC PLAN

1/8"=1'-0"

MH101

PLAN

NORTH

TRUE

NORTH

MH402

MH403

MH401

34x32

62x24 48x42 x2

22x22

16"Ø

"Ø x1

16"Ø

14"Ø

"Ø

14"Ø 14"Ø

16"Ø

"Ø

14"Ø14"Ø

"Ø

6"Ø

6"Ø

6" Ø x2

24x24

36x36

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC

SECOND FLOOR PLAN

MH102

121 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

SCALE:

SECOND FLOOR HVAC PLAN

1/8"=1'-0"

MH102

PLAN

NORTH

TRUE

NORTH

H S

P

UC

CF

L

KEY PLAN

BP

C

VAV-1-17

38"x36" EXHAUST DUCT

UP TO LEF-1A/1B ON

ROOF AND DOWN TO

FIRST FLOOR

34"x32" SUPPLY DUCTWORK

DOWN TO FIRST FLOOR

SUPPLY DUCTWORK

DOWN TO FIRST FLOOR

L-1

48" X 32" RETURN

DUCTWORK DOWN TO

FIRST FLOOR

AHU-1

AHU-2

20" EXHAUST DUCT UP TO EF-1

AND DOWN TO FIRST FLOOR

EAG-1

75 CFM

SAG-1

285 CFM

SAG-1

290 CFM

RAG-5

240 CFM

RAG-5

240 CFM

SAG-1

450 CFM

SAG-1

455 CFM

RAG-5

375 CFM

RAG-5

380 CFM

SAG-1

485 CFM

SAG-1

485 CFM

SAG-1

480 CFM

RAG-5

405 CFM

RAG-5

405 CFM

RAG-5

400 CFM

IDU-1

1. DUCT PENETRATION LOCATIONS MUST BE

COORDINATED IN A WAY TO AVOID STRUCTURAL

COMPONENTS. CONCRETE FLOORING

PENETRATION MUST BE PRECAST AND CONTAIN

A BUILT UP CURB AROUND THE DUCTWORK TO

PROTECT THE FIRST FLOOR FROM ANY SPILLS

THAT MAY OCCUR IN THE MECHANICAL ROOM.

PROVIDE FIRE DAMPER IN DUCTWORK IN FLOOR

PENETRATION.

2. PROVIDE INSULATED MANUFACTURE APPROVED

TRANSITION FROM DUCTWORK TO SHARED

INTAKE LOUVER. ALL DUCTWORK MUST BE

SLOPPED TO PREVENT THE INTAKE OF WATER.

KEYED NOTES

PROVIDE AIR HANDLER WITH

CONCRETE EQUIPMENT PAD

PROVIDE AIR HANDLER WITH

CONCRETE EQUIPMENT PAD

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC ROOF PLAN

MH103

122 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

SCALE: 1/16" = 1'-0"

48'8' 16' 32'0

SCALE:

HAVC ROOF PLAN

1/8"=1'-0"

MH103

PLAN

NORTH

TRUE

NORTH

H S

P

UC

CF

L

KEY PLAN

BP

C

EF-1

LEF-1A/1B

ODU-1

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC ELEVATION

MH201

123 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

SCALE: 1/16" = 1'-0"

48'8' 16' 32'0

SCALE:

HAVC ELEVATION

1/8"=1'-0"

MH201

PLAN

NORTH

TRUE

NORTH

H S

P

UC

CF

L

KEY PLAN

BP

C

AHU-2

L-1

OUTDOOR AIR DUCT ROUTED

TO INTAKE LOUVER

LEF-1BLEF-1A

38"x36" LABORATORY

EXHAUST DUCTWORK

DOWN TO FIRST FLOOR

HOUSEKEEPING PAD

PROVIDE FIRE DAMPER IN

DUCTWORK DROPPING

THROUGH FLOOR

1. DUCT PENETRATION LOCATIONS MUST BE

COORDINATED IN A WAY TO AVOID STRUCTURAL

COMPONENTS. CONCRETE FLOORING

PENETRATION MUST BE PRECAST AND CONTAIN

A BUILT UP CURB AROUND THE DUCTWORK TO

PROTECT THE FIRST FLOOR FROM ANY SPILLS

THAT MAY OCCUR IN THE MECHANICAL ROOM.

KEYED NOTES

34x20

20"Ø16"Ø

"Ø

"Ø

"Ø

"Ø

"Ø

"Ø

"Ø

12"Ø

"Ø

18"Ø16"Ø12"Ø

"Ø

"Ø

"Ø10

"Ø

10"Ø

"Ø 14"Ø

12"Ø

12"Ø14"Ø 8"Ø

"Ø

"Ø

"Ø

"Ø

14"Ø

20x18 x2

48x22

34x22 x1 x1 8 8x8

22x18

12x12 x1

10x10 x1

34x22

8" Ø

12"Ø

"Ø

10"Ø

8x8

12"Ø 14x18

10x10 x1

12"Ø x1

"Ø

34x20 x2

10" Ø

"Ø

ROOM LEGEND

ROOM NO ROOM NAME

STORAGE

STORAGE

MEETING ROOM

CORRIDOR

CORRIDPOR

WOMEN

MAIL / WORK ROOM

ENTRY LOBBY

CORRIDOR

TECH OFFICE

TECH OFFICE

TECH OFFICE

PROGRAM ASSISTANT

RESEARCH LEADER

OFFICE

OFFICE

OFFICE

CORRIDOR

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC ENLARGED

FIRST FLOOR PLAN

MH401

124 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

SAD-2

265 CFM

SAD-2

285 CFM

SAD-2

285 CFM

SAD-2

240 CFM

SAD-2

235 CFM SAD-2

240 CFM

SAD-3

380 CFM

SAD-1

180 CFM

SAD-1

180 CFM

SAD-1

180 CFM

SAD-2

225 CFM

SAD-2

225 CFM

SAD-1

150 CFM

SAD-1

150 CFM

SAD-1

175 CFM

SAD-1

200 CFM

SAD-1

200 CFM

SAD-1

200 CFM

SAD-1

200 CFM

SAD-2

290 CFM

SAD-3

325 CFM

SAD-3

325 CFM

SAD-3

325 CFMSAD-1

325 CFM

SAD-4

450 CFM

VAV-1-1

VAV-1-2

VAV-1-3

VAV-1-6

VAV-1-8

VAV-1-10 VAV-1-9

RAG-3

450 CFM

RAG-2

280 CFM

RAG-2

265 CFM

RAG-1

225 CFM

RAG-2

265 CFM

RAG-1

200 CFM

RAG-2

325 CFM

RAG-2

325 CFM

RAG-2

330 CFM RAG-1

160 CFM

RAG-1

160 CFM

RAG-1

160 CFM

RAG-1

200 CFM

RAG-1

135 CFM

RAG-2

295 CFM

RAG-1

155 CFM

RAG-2

280 CFM

EAG-4

310 CFM

EAG-4

310 CFM

EAG-4

350 CFM

EAG-2

200 CFM

EAG-2

150 CFM

EAG-2

150 CFM

EAG-1

85 CFM

VAV-1-7

SCALE:

ENLARGED FIRST FLOOR HVAC PLAN

1/8"=1'-0"

MH401

PLAN

NORTH

TRUE

NORTH

1. ROUTE DUCTWORK UP ABOVE STRUCTURE TO

SERVE ROOM 1056 AND 1051 WITH RAISED

CEILING HEIGHTS. COORDINATE DUCT HEIGHT

AND LOCATION WITH STRUCTURAL COMPONENT.

KEYED NOTES

18"Ø

14"Ø

12"Ø16"Ø

"Ø

14"Ø

"Ø

"Ø

"Ø

"Ø

18"Ø

16"Ø

10"Ø 6" Ø

"Ø

"Ø x3 x3

22"Ø x1 x1

24x18 x1

12x1216x1418x1420x1420x16 x1

814x1010x10

36x22

12x12 x1

20x18

48x22 48x22

12"Ø

"Ø

10"Ø

16"Ø

8"Ø

10"Ø

10"Ø x2

"Ø

"Ø

"Ø

48x22

16"Ø

ROOM LEGEND

ROOM NO ROOM NAME

MEETING ROOM

PREP

JANITORIAL

CORRIDOR

MEN

CORRIDOR

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

SMALL CONFERENCE

CORRIDOR

TECH OFFICE

TECH OFFICE

TECH OFFICE

CAT 3 OFFICE

CORRIDOR

101610151014

1021 1022

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC ENLARGED

FIRST FLOOR PLAN

MH402

125 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

SAD-1

200 CFM

SAD-1

200 CFM

SAD-1

200 CFM

SAD-1

200 CFM

SAD-3

365 CFM

SAD-3

365 CFM

SAD-1

180 CFM

SAD-1

180 CFM

SAD-1

180 CFM

SAD-1

180 CFM

SAD-1

180 CFM

SAD-1

180 CFM

SAD-3

315 CFM

SAD-3

315 CFM

SAD-1

150 CFM

SAD-2

225 CFM

SAD-2

225 CFM

SAD-3

360 CFM

SAD-2

290 CFM

SAD-3

400 CFM

SAD-3

400 CFM

SAD-3

400 CFM

SAD-3

400 CFM

VAV-1-15

VAV-1-13

VAV-1-14

VAV-1-16

VAV-1-11

VAV-1-12

RAG-3

425 CFM

RAG-3

425 CFM

RAG-2

315 CFM

RAG-3

545 CFM

RAG-1

160 CFM

RAG-1

160 CFM

RAG-1

160 CFM

RAG-1

160 CFM

RAG-1

160 CFM

RAG-1

160 CFM

RAG-2

315 CFM

RAG-2

310 CFM

RAG-3

450 CFM

RAG-3

460 CFM

RAG-2

295 CFM

RAG-1

135 CFM

RAG-1

200 CFM

RAG-1

200 CFM

EAG-4

340 CFM

EAG-4

340 CFM

EAG-4

335 CFM

EAG-2

150 CFM

EAG-2

150 CFM

EAG-1

60 CFM

SCALE:

ENLARGED FIRST FLOOR HVAC PLAN

1/8"=1'-0"

MH402

PLAN

NORTH

TRUE

NORTH

PROVIDE BROAN 88000

OR EQUAL HOOD

PROVIDE STAINLESS STEEL DUCT TO

EXTERIOR. PROVIDE WITH BACKDRAFT

LOUVER TYPE WEATHERHOOD CAP.

TD

"Ø

24x20

"Ø

18"Ø 20"Ø 18"Ø

10"Ø 14"Ø 14"Ø

14"Ø

"Ø

12"Ø 14"Ø

8"Ø

8" Ø8"Ø

8" Ø

"Ø

10"Ø

8" Ø

8" Ø

8" Ø

10"Ø

"Ø

12"Ø

14"Ø

12"Ø 14"Ø 14"Ø

10"Ø 10"Ø

22"Ø 20"Ø x2

14"Ø

12"Ø

14"Ø

8"Ø x1

"Ø

10x10 x1

8" Ø

12"Ø

16"Ø 16"Ø

20"Ø

"Ø

8"Ø 8"Ø

12"Ø

14"Ø

12"Ø

"Ø

"Ø

"Ø

14"Ø

"Ø

"Ø

6" Ø

"Ø

8" Ø

10"Ø

14"Ø

14"Ø

ROOM LEGEND

ROOM NO ROOM NAME

WOMEN

SCOPE

SUPPORT

STORAGE

SERVICE / UTILITY CORRIDOR

HALL

BSL-2 LABORATORY

SUPPORT

PATHOLOGY / MOLECULAR GENETICS (CLEAN)

PATHOLOGY / MOLECULAR GENETICS (DIRTY)

FILES

BREAK ROOM

POST-DOC / TECHICAL OFFICE

MAIL / WORK ROOM

CORRIDOR

1045 1046

1038 1039

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

04/03/2026

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC ENLARGED

FIRST FLOOR PLAN

MH403

126 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

SAD-2

290 CFM

SAD-2

290 CFM

SAD-2

295 CFM

SAD-1

190 CFM

SAD-4

450 CFM

VAV-1-5

VAV-1-4

RAG-2

260 CFM

RAG-2

255 CFM

RAG-3

400 CFM

RAG-3

400 CFM

RAG-2

260 CFM

RAG-1

160 CFM

SAD-2

205 CFM

SAD-2

205 CFM

SAD-2

205 CFM

SAD-2

205 CFM

SAD-2

205 CFM

SAD-2

205 CFM

SAD-2

285 CFM

SAD-2

285 CFM

SAD-3

330 CFM

SAD-3

335 CFM

SAD-3

345 CFM

SAD-1

140 CFM

SAD-1

190 CFM

SAD-1

200 CFM

SAD-3

360 CFM

SAG-2

335 CFM

SAG-2

335 CFM SAG-2

335 CFM

SAD-1

170 CFM

EAG-3

300 CFM

EAG-3

295 CFM

EAG-3

235 CFM

EAG-2

195 CFM

EAG-2

140 CFM

EAG-4

305 CFM

EAG-4

305 CFM

EAG-4

345 CFM

SAV-10

SAV-11 SAV-7

SAV-8

SAV-12

SAV-13

SAV-14

SAV-4

GEV-13

GEV-14

HEV-5

GEV-12

GEV-7

GEV-4

GEV-5

HEV-4

HWC-10

HWC-11

HWC-7

HWC-12

HWC-13 HWC-4

HWC-8

EAG-1

75 CFM

1. PROVIDE HOOD EXHAUST VALVE IN VERTICAL

DUCTWORK DOWN TO FUME HOOD. PROVIDE

VALVE WITH MANUFACTURER RECOMMENDED

DISTANCES BEFORE AND AFTER IN STRAIGHT

DUCTWORK TO ALLOW FOR PROPER AIRFLOW

MONITORING.

2. PROVIDE EXHAUST VALVE IN VERTICAL

DUCTWORK DOWN TO BIOLOGICAL SAFETY

CABINET. PROVIDE WITH MANUFACTURER

PROVIDED EXHAUST THIMBLE CONNECTION.

PROVIDE VALVE WITH MANUFACTURER

RECOMMENDED DISTANCES BEFORE AND AFTER

IN STRAIGHT DUCTWORK TO ALLOW FOR

PROPER AIRFLOW MONITORING.

KEYED NOTES

SCALE:

ENLARGED FIRST FLOOR HVAC PLAN

1/8"=1'-0"

MH403

PLAN

NORTH

TRUE

NORTH

EAG-5

230 CFM

EAG-5

230 CFM

EAG-5

230 CFM

BSC-1

BSC-2

H-4

HEV-6

SAD-3

340 CFM

SAD-3

365 CFM

GEV-11

HEV-7

PROVIDE PRIORCLAVE

SH150D OR EQUAL

AUTOCLAVE, PROVIDE

EXHAUST HOOD ABOVE

AND ALL REQUIRED

UTILITY CONNECTIONS.

26x18

16"Ø 14"Ø 12"Ø

"Ø

"Ø

10"Ø 10"Ø

10"Ø

"Ø

"Ø 12"Ø

10"Ø

"Ø

10"Ø

"Ø

14"Ø 14"Ø 10"Ø

16"Ø20"Ø20"Ø

"Ø

10"Ø

10"Ø 10"Ø

8" Ø

14"Ø

"Ø

"Ø

12"Ø

22"Ø22"Ø

"Ø

12"Ø

"Ø

"Ø

10"Ø

10"Ø

"Ø

12"Ø14"Ø16"Ø 12"Ø14"Ø20"Ø20"Ø

14"Ø

48x32 x1 x1 x1 x1 x1

12x10

"Ø

8"Ø

6"Ø 14"Ø

14"Ø

10"Ø

32x20

8" Ø

14"Ø 16"Ø

16"Ø

"Ø

ROOM LEGEND

ROOM NO ROOM NAME

CAT 3 OFFICE

TECHNICIAN OFFICE

TECHNICIAN OFFICE

CORRIDOR

STORAGE

PLANT PHYSIOLOGY / SOILS

SUPPORT

SUPPORT

HALL

SCOPE

SHARED EQUIPMENT ROOM

STORAGE

SUPPORT

SERVICE / UTILITY CORRIDOR

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL HVAC ENLARGED

FIRST FLOOR PLAN

MH404

127 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

SAD-3

360 CFM

SAD-3

360 CFM

SAD-3

360 CFM

SAG-2

280 CFM

SAD-3

400 CFM

RAG-3

425 CFM

RAG-2

315 CFM

RAG-2

240 CFM

RAG-3

425 CFM

RAG-2

315 CFM

RAG-2

315 CFM

SAD-1

140 CFM

SAD-1

190 CFM

SAD-3

305 CFM

SAD-3

305 CFM SAD-3

310 CFM

SAD-3

315 CFM

SAD-3

350 CFM

SAD-3

350 CFM

SAD-2

245 CFM

SAD-2

245 CFM

SAD-2

240 CFM

SAD-2

240 CFM

SAD-2

240 CFM

SAD-2

240 CFM

SAD-2

240 CFM

SAD-2

240 CFM

SAG-2

335 CFM

SAG-2

340 CFM

SAG-2

340 CFM

EAG-2

180 CFM

EAG-2

140 CFM

EAG-2

140 CFM

EAG-4

305 CFM

EAG-4

305 CFM

EAG-4

340 CFM

EAG-4

340 CFM

EAG-4

335 CFM

EAG-5

290 CFM

EAG-5

290 CFM

EAG-2

140 CFM

EAG-5

225 CFM

EAG-5

230 CFM

SAV-3

SAV-9

SAV-2

SAV-1

SAV-6

SAV-5

GEV-6

GEV-8

GEV-9

GEV-10 GEV-1

GEV-3

GEV-2

H-3 H-2 H-1

HEV-1HEV-2

HEV-3

HWC-3

HWC-2

HWC-5

HWC-6 HWC-1

HWC-9

SCALE:

ENLARGED FIRST FLOOR HVAC PLAN

1/8"=1'-0"

MH404

PLAN

NORTH

TRUE

NORTH

EAG-5

230 CFM

1. PROVIDE HOOD EXHAUST VALVE IN VERTICAL

DUCTWORK DOWN TO LABORATORY EQUIPMENT

SHOWN. PROVIDE VALVE WITH MANUFACTURER

RECOMMENDED DISTANCES BEFORE AND AFTER

IN STRAIGHT DUCTWORK TO ALLOW FOR

PROPER AIRFLOW MONITORING.

KEYED NOTES

102210211020

10551054

43 1042

1058 1059 1060

1006 1012 1013 1014 1015 1016 1017

1026103210 331034

103910

T

T

T

T

T

T

T

T

TT

T

T T T T T T

T

TT

T

T

T

T

A A A A A A

A

A

A

A

A A

T

A A

T

T T

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

FIRST FLOOR

MECHANICAL PIPING PLAN

MP101

128 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

EXISTING 4" HTWS AND

HTWR UP TO PENTHOUSE

EXISTING 6" CHWS AND

CHWR UP TO PENTHOUSE

3"

6"

4"

EXISTING UNIT HEATER (TYP.)

EXISTING HYDRONIC PIPING TO

EXISTING GREENHOUSE BP

EXISTING HEATING COIL (TYP.)

EXISTING HEATING COIL (TYP.)

EXISTING HEATING COIL (TYP.)

EXISTING HEATING COIL (TYP.)

EXISTING HEATING COIL (TYP.)

EXISTING PIPING DOWN

FROM SECOND FLOOR EXISTING PIPING ROUTED TO

PHOTOPERIOD BUILDING

EXISTING UNIT HEATER (TYP.)

EXISTING HYDRONIC PIPING TO

EXISTING GREENHOUSE UC

EXISTING HYDRONIC PIPING TO

EXISTING GREENHOUSE CF

1. PROVIDE AIR COOLED CHILLER ON EXISTING

EQUIPMENT PAD. ENLARGE EXISTING

EQUIPMENT PAD IF NEW CHILLER IS LARGER

THAN EXISTING. MATCH EXISTING CONCRETE

CONSTRUCTION AND THICKNESS. MODIFY/

EXTEND EXISTING PIPING AS NEEDED FOR

CONNECTION TO NEW CHILLER.

1. PROVIDE ALUMINUM JACKETING ON ALL

EXTERIOR CHILLED WATER PIPING.

KEYED NOTES

GENERAL NOTES

POINT OF DEMOLITION

LEGEND

CH-1

CH-2

EXISTING UNIT HEATER (TYP.)

HWC-1

HWC-2

HWC-5

HWC-3

HWC-9

HWC-6

HWC-8

HWC-11 HWC-7

HWC-13

HWC-14

HWC-12

HWC-10

HWC-4

VAV-1-5

VAV-1-4

VAV-1-2

VAV-1-1

VAV-1-3

VAV-1-6

VAV-1-7

VAV-1-10

VAV-1-9

VAV-1-11

VAV-1-12

VAV-1-13

VAV-1-14

VAV-1-16

VAV-1-15

PIPING DOWN

FROM SECOND

FLOOR

VAV-1-8

EXISTING PIPING DOWN

FROM SECOND FLOOR

EXISTING PIPING DOWN

FROM SECOND FLOOR

SCALE:

FIRST FLOOR

MECHANICAL PIPING PLAN

1/8"=1'-0"

MP101

PLAN

NORTH

TRUE

NORTH

1/2" 3/4" 1"

1-1/4" 1-1/4"

1-1/4"

1-1/2"

2" 2"2"2-1/2"2-1/2"

2-1/2"2-1/2"3"

3"

3"

3" 3" 3"

3"

3" 3"

3" 3" 3"

3"

3" 2-1/2"

2-1/2"2-1/2"2-1/2"2"

2"2"2"

1-1/2"

1-1/2"

1-1/2"

1-1/4" 1"

1"

4"

THERMOSTATT

ROOM SETPOINT

ADJUSTMENT

A

MECHANICAL

PENTHOUSE

SERVICE/UTILITY

CORRIDOR

STAIR

COMM

ELEC

ROOM

2005 2006

DN

DN

STORAGE

ROOF BELOW

DN

T

T

T

H S

P

UC

CF

L (W) L (E)

KEY PLAN

BP

(E)C(W)C

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

SECOND FLOOR

MECHANICAL PIPING PLAN

MP102

129 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

0 16'8'4' 24'

SCALE: 1/8"= 1'-0"

6"

6"

4"

6"

3"

1-1/2"

1-1/2"

1-1/2" 2"

4"

4"

4"

6"

6"

4"

6"

4"

2" HWS/R

DOWN

3" 2" 4"

4"

VAV-1-17

BBH-1

AHU-1

AHU-2

1. PROVIDE PIPING, HANGERS, INSULATION, AND

ALL APPURTENANCES. RECONNECT EXISTING

CAPPED PIPING.

2. PROVIDE BOILER, EQUIPMENT PAD, FLUE AND

VENT, AND ALL APPURTENANCES. ROUTE FLUE

AND VENT TO EXISTING CAPPED CONNECTIONS.

CONTRACTOR MUST ENSURE THAT EXISTING

FLUE MATERIAL AND DESIGN IS COMPATIBLE

WITH SCHEDULED BOILERS.

3. ROUTE PIPING TO EXISTING AIR SEPARATOR.

4. PROVIDE CONNECTION TO EXISTING

TEMPORARILY CAPPED PIPING.

5. ROUTE 6" CHILLED WATER SUPPLY AND RETURN

TO SERVE AHU-1 AND AHU-2.

6. ROUTE PIPING DOWN TO PIPING CHASE BELOW

BRIDGE. SEE PLUMBING DETAIL SECTION 4/P-503.

KEYED NOTES

GENERAL NOTES

POINT OF CONNECTION

LEGEND

EXISTING UNIT HEATER (TYP.)

EXISTING HEATING COIL (TYP.)

EXISTING HEATING COIL (TYP.)

EXISTING HYDRONIC PIPING DOWN

TO FIRST FLOOR TO REMAIN

EXISTING UNIT HEATER (TYP.)

EXISTING UNIT HEATER (TYP.)

ET-2

ET-1

AS-2

CHWP-1

6" CHWS AND CHWR

DOWN TO FIRST FLOOR

4" HTWS AND HTWR

DOWN TO FIRST FLOOR

EXISTING HYDRONIC PIPING

DOWN TO FIRST FLOOR

BT-1

CHWP-2

B-1 B-2

HTWP-1

HTWP-2

AHU-3

AS-1

CFF-1

GFU-1

SCALE:

SECOND FLOOR

MECHANICAL PIPING PLAN

1/8"=1'-0"

MP102

IDU-1

INSULATED 1" CONDENSATE

PIPING ROUTED TO FLOOR

DRAIN

EXISTING HYDRONIC PIPING

TO HEATING COIL TO REMAIN

2"

EXISTING MAKEUP WATER PIPING

EXISTING MAKEUP WATER PIPING

1. ALL CONDENSATE PIPING LOCATED INSIDE THE

BUILDING ENVELOPE MUST BE INSULATED AND

SLOPPED TO ALLOW FOR GRAVITY DRAINAGE.

2. THE EXISTING HEATING WATER AND CHILLED

WATER SYSTEMS MUST REMAIN FULLY

OPERATIONAL THROUGHOUT CONSTRUCTION. IF

THE EXISTING SYSTEM IS REQUIRED TO BE

TAKEN OUT OF SERVICE AT ANY TIME, THE

CONTRACTOR MUST PROVIDE A TEMPORARY

SYSTEM TO MAINTAIN CONTINUOUS SERVICE,

OR OBTAIN PRIOR APPROVAL FOR A SCHEDULED

DOWNTIME WINDOW. ALL PROPOSED OR

ESTIMATED DOWNTIME MUST BE COORDINATED

IN ADVANCE AND RECEIVE WRITTEN APPROVAL

FROM THE GOVERNMENT PRIOR TO

IMPLEMENTATION. THE CONTRACTOR IS

RESPONSIBLE FOR PROTECTING ALL

COMPONENTS AND FUNCTIONS OF ALL EXISTING

SYSTEM THROUGHOUT ALL PHASES OF

CONSTRUCTION. ANY DAMAGE OR

INTERRUPTION TO THE SYSTEM RESULTING

FROM THE CONTRACTOR’S OPERATIONS MUST

BE REPAIRED OR REPLACED AT NO ADDED COST

TO THE GOVERNMENT.

THERMOSTATT

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL DETAILS

M-501 130 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

DUCT HANGERS, ATTACH TO THE

STRUCTURE ABV.

DUCT MAIN WITH

EXTERNAL INSULATION

CEILING DIFFUSER

DUCT HANGERS, ATTACH TO THE STRUCTURE ABV.

DUCT MAIN WITH EXTERNAL INSULATION

CEILING DIFFUSER

AREAS WITH

HARD OR LAY IN

CEILINGS

AREAS ABOVE

CEILING (TYP.)

ROUND DUCT WITH EXTERNAL INSULATION

ATTACH THE FLEXIBLE DUCT TO THE RIGID

DUCT AND THE DIFFUSER USING TWO (2)

BANDS; ONE FOR THE DUCT AND ONE FOR

THE INSULATION.

U.L. LISTED FLEXIBLE DUCT. SUPPORT TO

PREVENT SAG. FLEXIBLE DUCT MUST BE

LESS THAN 5 FT. IN LENGTH AND MUST

NOT BE USED FOR BENDS GREATER THAN

45°.

MANUAL DAMPER WITH LOCKING

QUADRANT REGULATOR.

RIGID 90° DUCT ELBOW WITH

EXTERNAL INSULATION

ATTACH THE FLEXIBLE DUCT TO THE RIGID

DUCT AND THE DIFFUSER USING TWO (2)

BANDS; ONE FOR THE DUCT AND ONE FOR

THE INSULATION.

U.L. LISTED FLEXIBLE DUCT. SUPPORT TO

PREVENT SAG. FLEXIBLE DUCT MUST BE

LESS THAN 5 FT. IN LENGTH AND MUST

NOT BE USED FOR BENDS GREATER THAN

45°.

MANUAL DAMPER WITH LOCKING

QUADRANT REGULATOR.

RIGID 90° DUCT ELBOW WITH

EXTERNAL INSULATION

ROUND DUCT WITH EXTERNAL INSULATION

3"

CABLE WRAP

AROUND BEAM AND

BAR JOIST

CL20 DUCTMATE

CLUTCHERS

WR20 CABLE

DUCT

DUCT INSULATION

THREADED ROD

DOUBLE NUT

UNISTRUT OR ANGLE

UNISTRUT BAR

BAR JOIST

CL20 DUCTMATE

CLUTCHER OR

EQUAL

DUCTMATE WR20

CABLE OR EQUAL

MINIMUM 3/8" DIA.

THREADED ROD

12 GAUGE GALVANIZED

STEEL

DUCT

DUCT INSULATION

DOUBLE NUT

DUCT

EXTERNAL INSULATION WHERE SPECIFIED

NOTE: FOR SIZES UP TO 60"

WITH 10' MAXIMUM SPACING.

NOTE: SEMI-CIRCLE HANGER.

61"-72" DIAMETER WITH 10'

MAXIMUM SPACING.

END VIEW ELEVATION VIEW

2"3 1/2" 1"

NOTE: FOR SIZES UP TO 60"

WITH 10' MAXIMUM SPACING.

SINGLE

DOUBLE

NOTE: 10' MAXIMUM SPACING.

97-120

85-96

72-84

61-72

DUCT SIZE (IN.) STRUT SIZE

1 5/8 X 1 5/8 X 12 GA

N/A

N/A

N/A

2 1/2 X 2 1/2 X 1/4

2 X 2 X 1/4

N/A

ANGLE SIZE

3 X 3 X 1/4

3/8

ROD SIZE

3/8

3/8

3/8

SCALE:

TYPICAL DIFFUSER CONNECTION DETAIL

N.T.S

M-501 SCALE:

DUCT HANGER DETAILS

N.T.S

M-501

PROVIDE MANUAL OPPOSED DAMPER IN EACH BRANCH LINE

UNLESS OTHERWISE NOTED ON DRAWINGS. DAMPERS SHALL

BE INSTALLED IN ACCESSIBLE LOCATION NEAR TRUNK DUCT

AND MINIMUM OF 5'-0" FROM ANY AIR INLET OR OUTLET

DEVICE. COORDINATE W/ ACCESS DOORS IN NON-ACCESSIBLE

CEILINGS.

TRUNK

DUCT

OVAL BRANCH

DUCT

45° CLINCH COLLAR PER SAMNA

USE AT ALL BRANCH TAPS UNLESS

SPLITTER DAMPERS ARE INDICATED.

BELL-MOUTH

FITTING

NOTE:

DAMPERS SHALL BE PROVIDED IN ALL BRANCH RUN-OUTS TO DIFFUSERS, R.A AND EXHAUST GRILLES, UNLESS SPECIFICALLY NOTED OTHERWISE ON DRAWINGS.

LOCATE DAMPERS SO THEY ARE ACCESSIBLE FROM LAY-IN CEILING OR ACCESS DOORS.

ROUND DUCT

SCALE:

ROOF MOUNTED EXHAUST FAN DETAIL

N.T.S

M501

EXHAUST FAN

(SEE SCHEDULE)

BACKDRAFT DAMPER

FLASHING CAULK

WATER TIGHT

MANUFACTURER PROVIDED ROOF

CURB

EXISTING ROOF

MIN

MIN

3.5"

2" MIN

6.5"

DRAIN PAN

DRAIN LINE SHALL BE AT LEAST THE

SAME SIZE AS THE NIPPLE ON THE

DRAIN PAN. SEE PLANS FOR SIZES.

UNION

UNION FOR DRAINING

CLEAN OUT

SCALE:

CONDENSATE DRAIN P-TRAP DETAIL

N.T.S

M-501

NOTE:

INSULATE ALL CONDENSATE PIPING IN BUILDING.

20% MAXIMUM AREA

REDUCTION

R=H (MIN.)

L

W 15°H

W

L

DIM. "D"

ELEVATION

VIEW

PLAN

VIEW

DUCT DIM. (SEE

PLAN)

DUCT "VENTURI" DEPRESSION

DETAIL

NOTE: USE DETAIL WHERE

REQUIRED BY FIELD

CONDITIONS.

H R

TRANS.

DN.

TRANS.

UP

MIN. 2/3 "D"

TYPICAL OBSTRUCTION

TO DUCT PATH

SCALE:

DUCT DEPRESSION FOR STRUCURAL CONFLICTS DETAIL

N.T.S

M-501

SCALE:

EQUIPMENT PAD PIPING SUPPORT DETAIL

N.T.S

M-501

U-CLAMP OR CONDUIT CLAMP

INSULATED PIPE WITH

METAL SHIELD

MIN. 18GA. INSULATION SHIELD

GALVANIZED IRON TRAPEZE

OR UNISTRUT

EQUIPMENT PAD

RUBBERIZED BLOCK SUPPORT. BASIS OF

DESIGN DURABLOK

PIPE PENETRATION NOTES:

1. PROVIDE PITCH POCKET CONSTRUCTION, ADDITIONAL FLASHING, OR WEATHER CAP AS

REQUIRED FOR WATERPROOF CONSTRUCTION. DO NOT MECHANICALLY ATTACH PIPE TO

STRUCTURE IN ANY WAY.

2. SPACE BETWEEN PIPE AND SLEEVE SHALL BE FREE OF ANY FOREIGN MATERIALS.

3. PIPE SHALL NOT CONTACT STRUCTURE AT ANY TIME. WEDGES ARE NOT BE USED TO MAINTAIN

PIPE POSITION.

4. PIPE MUST BE APPROXIMATELY CENTERED IN OPENING.

CAULK ALL JOINTS AND

SLEEVE ENDS

WATERTIGHT

PIPING

SCH. 40 PIPE STEEL SLEEVE

FOAM INSULATION OR FIRE

STOP MATERIAL (FOR FIRE

RATED PARTITIONS)

PIPE INSULATION AS APPLICABLE

PARTITION

SCALE:

PIPE PENETRATION DETAIL

N.T.S

M-501

SCALE:

SINGLE DUCT VAV BOX DETAIL

N.T.S

M-501

EXTERNALLY

INSULATED RIGID GALV

SHT MTL ROUND DUCT

EXTERNALLY

INSULATED

PRIMARY SA DUCTS

AIR FLOW

EXTERNALLY INSULATED

SUPPLY DUCT

VAV BOX

TRANSITION

AS REQUIRED

SA

HEATING WATER REHEAT

COIL

H.P. FLEX

(12" MAX

LENGTH)

TRANSITION

AS REQUIRED

CONTROL PANEL. LOCATE FOR OPTIMUM

ACCESS ABOVE CEILING. MAINTAIN MFR'S

RECOMMENDED ACCESS CLEARANCESHIGH EFF TAKE-OFF FITTING

(W/O DAMPER).

AIR FLOW

REDUCING OR ENLARGING

TRANSITION AS REQUIRED

(W/O DAMPER).

EXTERNALLY

INSULATED RIGID GALV

SHT MTL ROUND DUCT

EXTERNALLY

INSULATED GALV

SHT MTL DUCT

SEE BELOW FOR DUCT

CONTINUATION TO BOX

EXTERNALLY

INSULATED GALV

SHT MTL DUCT

ALTERNATE TAKEOFF FOR

BOXES WITH TAKEOFF

FROM END OF RECT DUCT

SCALE:

EXPANSION TANK DETAIL

N.T.S

M-501

TO PUMP SUCTION

DIAPHRAGM TYPE

EXPANSION TANK

GATE VALVE

(TYPICAL)

SEE PLANS FOR

PIPE SIZE

TANGENTIAL

AIR

SEPARATOR

SCALE:

BRANCH DUCT TAP DETAIL

N.T.S

M-501

SCALE:

BASE MOUNTED PUMP DETAIL

N.T.S

M-501

P

P

PUMP DISCHARGE

PIPING (SEE PLANS) PUMP SUCTION

PIPING (SEE PLANS)

PRESSURE GAUGE

PRESSURE GAUGE

THERMOMETER

BUTTERFLY VALVE

BUTTERFLY VALVE

BALANCING VALVE

CHECK VALVE

STAINLESS STEEL BRAIDED

FLEX CONNECTION

CONCENTRIC

REDUCER

BASE MOUNTED

PUMP

SUCTION DIFFUSER W/ PULLOUT STRAINER

DRAIN WITH BALL

VALVE

FINISHED FLOOR

HOUSEKEEPING PAD

PUMP BASE

STAINLESS STEEL BRAIDED

FLEX CONNECTION

PETES PLUG (TYP.)

SUCTION DIFFUSER SUPPORT

HEAVY DUTY

CLEVIS HANGER:

MSS SP-69 AND

MSS SP-58

PIPE

RIGID INSULATION INSERT

(12" LONG, 180^ ARC)

CLEVIS HANGER

WITH INSULATION

SHIELD

INSULATION

BOLT & NUT

SUPPORT NUT

LOCKING NUT

TURNBUCKLE W/LOCKNUT

HANGER ROD

SCALE:

CLEVIS HANGER DETAIL

N.T.S

M-501

SCALE:

PIPE HANGER DETAILS

N.T.S

M-501

12" MIN

12" MIN

U-CLAMP OR

CONDUIT CLAMP

GALVANIZED IRON

TRAPEZE OR

UNISTRUT

16 GAUGE GALVANIZED

SHEET SHIELD

WRAPPED FULLY

AROUND INSULATION

INSULATION

PIPE

PROVIDE A SECTION OF HIGH

COMPRESSION STRENGTH

INSULATION AT EACH HANGER

POINT. INSULATION SHALL BE HALF

ROUND AND EXTEND 2" BEYOND

GALVANIZED SHIELD EACH WAY.

16 GAUGE GALVANIZED

SHEET SHIELD

WRAPPED FULLY

AROUND INSULATION

INSULATION

PIPE

SCALE:

CHEMICAL FILTER FEEDER DETAIL (CFF-1)

N.T.S

M-501

PUMP DISCHARGE LINE

5 GALLON SHOT

FEEDER

3/4"

TO FLOOR DRAIN

PUMP LINE SUCTION

NOT GREATER

THAN 30" A.F.F.

3/4"

CAP

1/2" VENT

NOTE:

PROVIDE MANUFACTURER

RECOMMENDED DUCT LENGTH

ON EACH SIDE OF THE VAV BOX

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM

P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943

Johnson M Adams

ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT

USDA AGRICULTURAL RESEARCH SERVICE

SUGARCANE RESEARCH LABORATORY

HOUMA, LOUISIANA

MECHANICAL DETAILS

M-502 131 17605/20/2026

REH

SME

DRL FACILITIES ENGINEERING BRANCH

5106 SUNNYSIDE AVENUE

BELTSVILLE, MD 20705-5100

XXX

WN

XXX

CM

JS

BYPASS AIR

SHIPPING SPLIT

AI

RF

LO

W

CU

RB

O

VE

RL

AP

2.

5"

INLET CONNECTION DETAIL

1.2"

WINDBAND

NOZZLE

FAN WITH MOTOR

DISCONNECT SWITCH

BYPASS PLENUM

BYPASS WEATHERHOOD

BYPASS DAMPER

DRAIN HOLE 1 INCH

MPT

PLENUM

SKIRT

ROOF

CURBDUCT

DROP BY

OTHERS

FRONT SIDE

RIGHT SIDE

TOP VIEW

AI

RF

LO

W

PROVIDE GUY WIRES AS

RECOMMENDED BY

MANUFACTURER

SCALE:

LAB EXHAUST FAN DETAIL (LEF-X)

N.T.S

M-502

SCALE:

2-WAY HEATING WATER COIL DETAIL

N.T.S

M-502

SCALE:

3-WAY HEATING WATER COIL DETAIL

N.T.S

M-502

SCALE:

TYPICAL RETURN / EXHAUST GRILL CONNECTION

N.T.S

M-502

HARD METAL ROUND DUCT RUN OUT TO

DIFFUSER. SEE PLAN FOR SIZE

SAME SIZE AS GRILLE

NECK

REDUCER IF REQ'D.

BUTTERFLY DAMPER SHALL BE USED

AT THIS LOCATION OR AT

CONNECTION OF RUN-OUT TO MAIN

DUCT.

WORM GEAR DRIVE,

STAINLESS STEEL STRAP

LAY-IN GRILLE SHOWN.

SURFACE MOUNTED SIMILAR

AREAS WITH

HARD OR LAY IN

CEILINGS

AREAS OPEN

CEILINGS (TYP.)

TURNING VANES, TYPICAL

TURNS 45° OR LARGER

RUNNER

INSTALL VANES TANGENT

TO AIRSTREAM

DOUBLE SIDED TURNING VANES

REQUIRED WHERE DUCT

HEIGHT IS 24" OR GREATER.

TOP RUNNER NOT SHOWN FOR CLARITY.

NUMBER AND CONFIGURATION OF VANES

PER SMACNA STANDARDS.

SCALE:

TURNING VANE DETAIL

N.T.S

M-502 SCALE:

HOUSE KEEPING PAD DETAIL

N.T.S

M-502

HOUSEKEEPING PADS MUST EXTEND A

MINIMUM OF 6" BEYOND ALL SIDES OF

SUPPORTED EQUIPMENT UNLESS

OTHERWISE INDICATED. PADS MUST BE

A MINIMUM OF 4" THICK

PROVIDE 4000 PSI CONCRETE

HOUSEKEEPING PADS FOR ALL

GROUND AND/OR FLOOR

MOUNTED EQUIPMENT

EDGE OF SUPPORTED

EQUIPMENT

CHAMFERED

EDGED ALL SIDES

FLOOR

ALL PADS INSTALLED ON CONCRETE FLOORS

ARE TO BE PROVIDED WITH #4 REBAR DOWEL

RODS PENETRATING A MINIMUM OF 2" INTO

BOTH THE PAD AND THE SUPPORTING FLOOR.

PROVIDE A MINIMUM OF FOUR (4) DOWEL RODS

PER PAD, WITH SPACING OF DOWEL RODS AT 18"

ON CENTER MAXIMUM BOTH WAYS.

#4 REINFORCEMENT MAX 4"

ON CENTER EACH WAY

TO UNISTRUT P2500

SERIES PIPE STRAP

(TYP.)

TO UNISTRUT P3400

SERIES PIPE CLAMPS

(TYP.)

TO UNISTRUT P 1000 12 GA CHANNEL

(TYP.)

SECURE W/APPROVED ANCHOR TO MATCH BASE

MATERIAL AND LOAD REQUIREMENTS

INSULATE AS REQD

CONC. OR MASONRY WALL

TO UNISTRUT P 1000 12 GA CHANNEL

(TYP.)

SECURE W/APPROVED ANCHOR TO MATCH BASE

MATERIAL AND LOAD REQUIREMENTS

INSULATE AS REQD

CONC OR MASONRY WALL

NOTE:

PROVIDE MIN ANCHOR

SUPPORT SPACING EVERY 3'

VERTICALLY

FOR PIPES < 4"Ø

FOR CONDUIT < 2"Ø

SCALE:

PIPING WALL SUPPORT DETAIL

N.T.S

M-502

Ø 40"

DRAIN HOLE 1/2 INCH FPT

ISOLATION DAMPER

FACTORY SUPPLIED

ROOF CURB

FRONT SIDE

AI

RF

LO

W

TOP VIEW

CHWS

SHUT-OFF VALVE (TYP.)

CHWR

BALANCING VALVE

3-WAY CONTROL VALVE

DIRECT ACTING SIGNAL

TEST PLUG (TYP.)

1/2" PLUGGED DRAIN VALVE COIL

MANUAL AIR VENT,

3/8"

BALL VALE (TYP.)

NO

NC

C

AIR FLOW

KEYED NOTES

CHWS

SHUT-OFF VALVE (TYP.)

CHWR

BALANCING VALVE

2-WAY CONTROL VALVE

REVERSE ACTING SIGNAL

TEST PLUG (TYP.)

1/2" PLUGGED DRAIN VALVE COIL

BALL VALE (TYP.)

AIR FLOW

NO

KEYED NOTES

HTWS

SHUT-OFF

VALVE (TYP.)

HTWR

BALANCING VALVE

2-WAY CONTROL VALVE

REVERSE ACTING SIGNAL

TEST PLUG (TYP.)

1/2" PLUGGED DRAIN

VALVE

COIL

MANUAL AIR VENT, 3/8"

BALL VALE (TYP.)

AIR FLOW

NO

KEYED NOTES

STRAINER

W/BLOWDOWN

HTWS

SHUT-OFF VALVE (TYP.)

HTWR

BALANCING VALVE

3-WAY CONTROL VALVE

DIRECT ACTING SIGNAL

TEST PLUG (TYP.)

1/2" PLUGGED DRAIN VALVE COIL

MANUAL AIR VENT,

3/8"

BALL VALE (TYP.)

AIR FLOW

KEYED NOTES

NC

NO

C

NOTE: (VARIABLE FLOW FULL HEAT)

THROUGH COIL, FAIL TO

INSTALL CIRCUIT SETTER BALANCING VALVE

WITH MINIMUM OF 3 STRAIGHT PIPE

DIAMETERS UPSTREAM AND 1 STRAIGHT

PIPE DIAMETER DOWNSTREAM.

MAINTAIN 6" MINIMUM CLEARANCE ABOVE

TEST PLUG TO ALLOW GAUGE TO BE

INSERTED. DO NOT COVER PLUG WITH

INSULATION.

INSTALL SWING JOINTS AT COIL

CONNECTIONS.

CONNECT BRANCH LINES FROM COIL INTO

TOP OR SIDE OF SUPPLY AND RETURN

MAINS. CONNECTING INTO BOTTOM OF MAIN

IS NOT ACCEPTABLE.

PROVIDE COILS WITH INLET STRAINERS AND

CAPPED HOSE CONNECTION BLOW DOWN

VALVES.

INSTALL MANUAL AIR VENTS IN SUPPLY AND

RETURN COIL BRANCH PIPING AS FOLLOWS:

A) IN PIPING HIGH POINT WHEN PIPING IS

ABOVE MAIN.

B) CLOSE TO COIL WHEN PIPING IS NOT

ABOVE MAIN (SIDE CONNECTION).

INSTALL CIRCUIT SETTER BALANCING VALVE

WITH MINIMUM OF 3 STRAIGHT PIPE

DIAMETERS UPSTREAM AND 1 STRAIGHT

PIPE DIAMETER DOWNSTREAM.

MAINTAIN 6" MINIMUM CLEARANCE ABOVE

TEST PLUG TO ALLOW GAUGE TO BE

INSERTED. DO NOT COVER PLUG WITH

INSULATION.

INSTALL SWING JOINTS AT COIL

CONNECTIONS.

CONNECT BRANCH LINES FROM COIL INTO

TOP OR SIDE OF SUPPLY AND RETURN

MAINS. CONNECTING INTO BOTTOM OF MAIN

IS NOT ACCEPTABLE.

PROVIDE COILS WITH INLET STRAINERS AND

CAPPED HOSE CONNECTION BLOW DOWN

VALVES.

INSTALL MANUAL AIR VENTS IN SUPPLY AND

RETURN COIL BRANCH PIPING AS FOLLOWS:

A) IN PIPING HIGH POINT WHEN PIPING IS

ABOVE MAIN.

B) CLOSE TO COIL WHEN PIPING IS NOT

ABOVE MAIN (SIDE CONNECTION).

STRAINER

W/BLOWDOWN

MANUAL AIR VENT, 3/8"

PLUG VALVE, ADJUST TO GPM

THRU COIL AT DESIGN EQUAL

FLOW

INSTALL CIRCUIT SETTER BALANCING VALVE

WITH MINIMUM OF 3 STRAIGHT PIPE

DIAMETERS UPSTREAM AND 1 STRAIGHT

PIPE DIAMETER DOWNSTREAM.

MAINTAIN 6" MINIMUM CLEARANCE ABOVE

TEST PLUG TO ALLOW GAUGE TO BE

INSERTED. DO NOT COVER PLUG WITH

INSULATION.

INSTALL SWING JOINTS AT COIL

CONNECTIONS.

CONNECT BRANCH LINES FROM COIL INTO

TOP OR SIDE OF SUPPLY AND RETURN

MAINS. CONNECTING INTO BOTTOM OF MAIN

IS NOT ACCEPTABLE.

PROVIDE COILS WITH INLET STRAINERS AND

CAPPED HOSE CONNECTION BLOW DOWN

VALVES.

INSTALL MANUAL AIR VENTS IN SUPPLY AND

RETURN COIL BRANCH PIPING AS FOLLOWS:

A) IN PIPING HIGH POINT WHEN PIPING IS

ABOVE MAIN.

B) CLOSE TO COIL WHEN PIPING IS NOT

ABOVE MAIN (SIDE CONNECTION).

NOTE: PROVIDE 3-WAY VALVES WHERE INDICATED ON

PIPING DIAGRAMS. 2-WAY CONTROL VALVES MUST BE

PROVED IN ALL LOCATIONS WHERE 3-WAY VALVES ARE

NOT INDICATED

INSTALL CIRCUIT SETTER BALANCING VALVE

WITH MINIMUM OF 3 STRAIGHT PIPE

DIAMETERS UPSTREAM AND 1 STRAIGHT

PIPE DIAMETER DOWNSTREAM.

MAINTAIN 6" MINIMUM CLEARANCE ABOVE

TEST PLUG TO ALLOW GAUGE TO BE

INSERTED. DO NOT COVER PLUG WITH

INSULATION.

INSTALL SWING JOINTS AT COIL

CONNECTIONS.

CONNECT BRANCH LINES FROM COIL INTO

TOP OR SIDE OF SUPPLY AND RETURN

MAINS. CONNECTING INTO BOTTOM OF MAIN

IS NOT ACCEPTABLE.

PROVIDE COILS WITH INLET STRAINERS AND

CAPPED HOSE CONNECTION BLOW DOWN

VALVES.

INSTALL MANUAL AIR VENTS IN SUPPLY AND

RETURN COIL BRANCH PIPING AS FOLLOWS:

A) IN PIPING HIGH POINT WHEN PIPING IS

ABOVE MAIN.

B) CLOSE TO COIL WHEN PIPING IS NOT

ABOVE MAIN (SIDE CONNECTION).

STRAINER

W/BLOWDOWN

STRAINER

W/BLOWDOWN

PLUG VALVE, ADJUST TO GPM

THRU COIL AT DESIGN EQUAL

FLOW

NOTE: PROVIDE 3-WAY VALVES WHERE INDICATED ON

PIPING DIAGRAMS. 2-WAY CONTROL VALVES MUST BE

PROVIDED IN ALL LOCATIONS WHERE 3-WAY VALVES ARE

NOT INDICATED.

SCALE:

2-WAY CHILLED WATER COIL DETAIL

N.T.S

M-502

SCALE:

3-WAY CHILLED WATER COIL DETAIL

N.T.S

M-502

Agricultural

Service Research

DESCRIPTION

SHEET

DATEc P.A.

FIRM

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

THE

DESIGNER

PROJECT…