This is an asbestos bulk sampling inspection report for a USDA storage building. The inspection was conducted by Midwest Environmental Consulting Services, Inc. (MEC) on April 23, 2026, at USDA Storage Building 004, located at 1815 N University Street, Peoria, Illinois 61604. The comprehensive survey was performed prior to planned demolition of the facility.
The inspection identified four homogeneous areas within the building, three of which tested positive for asbestos-containing materials (ACM). Materials confirmed to contain asbestos include: plaster (SPA) in the North Side Room containing 2% chrysotile; cementitious fittings (TJA) in the North Side Room containing 60% chrysotile; and pipe insulation (TPA) in the North Side Room containing 20% chrysotile. Asphalt shingles on the roof tested negative for asbestos. The sampling strategy followed United States Environmental Protection Agency (USEPA) homogeneous area protocols, and bulk samples were analyzed using Polarized Light Microscopy (PLM) via the EPA 600/M4-82-020 method with AHERA "positive stop" protocol. Laboratory analysis was conducted by EMSL Analytical, Inc., an NVLAP-accredited facility. The report recommends that prior to any renovation or demolition, an Illinois Department of Public Health licensed asbestos abatement contractor be retained, and that project design, oversight, and air monitoring be implemented to address the identified ACM.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MEC Project #: 26-04-0339-INSP
USDA STORAGE BUILDING 004
1815 N University Street
Peoria, IL 61604
Inspection Date: April 23, 2026
Project Location:
ASBESTOS BULK SAMPLING
Performed For:
USDA PEORIA
1815 N University Street
Peoria, IL 61604
Laboratory Analytical Report Section 5
Licensing / Certifications Section 6
Narrative Section 1
Section 2
Photographs of Homogeneous Areas Section 4
Drawings of Homogeneous Areas Section 3
Asbestos Bulk Sample Summary Table
MEC Project #: 26-04-0339-INSP
USDA PEORIA
USDA STORAGE BUILDING 004
1815 N University Street
Peoria, IL 61604
Table of Contents
Midwest Environmental Consulting Services, Inc.
2551 N. Bridge Street
Yorkville, IL 60560
Phone: (630) 553-3989 Fax: (630) 553-3990
Section 1:
Introduction:
MEC Project #:
Observe, assess, and collect bulk samples of friable and non-friable asbestos containing building materials within the specific scope of work.
The inspection was intended to identify all homogeneous areas, and did not attempt to identify or address any other environmental health hazards.
The scope of work did not include identifying all potential concerns or eliminate possible risks.
A total of four (4) homogeneous areas were identified within the scope of work and of the four (4) homogeneous areas, three (3) homogeneous areas tested positive for asbestos content. Zero (0) homogeneous areas were assumed to contain asbestos.
The inspection was to address the following objectives:
Section 3:
Building Description:
The bulk sampling strategy is based upon the protocol of homogeneous areas established by the
United States Environmental Protection Agency (USEPA). A homogeneous sampling area (HSA) is defined as an area of material that is uniform in color, texture, construction, general appearance, and date of installation.
Bulk samples of suspect ACM were analyzed by Polarized Light Microscopy (PLM) utilizing the EPA-
600/M4-82-020 Method. Bulk samples were analyzed using Asbestos Hazard Emergency Response
Act (AHERA) “positive stop” protocol, meaning each sample of each HSA group is analyzed until asbestos is found in the HSA or all samples in the group are analyzed and are negative for asbestos content.
Midwest Environmental Consulting Services, Inc. (MEC) was retained by USDA Peoria to conduct a comprehensive asbestos bulk sampling survey for suspect asbestos-containing materials (ACM) in a storage building located at 1815 N University Street, Peoria, IL 61604. The asbestos inspection was performed on April 23, 2026. This comprehensive asbestos bulk sampling inspection was intended to address the potential existence of ACM on the interior and exterior prior to future planned demolition of the storage building.
Section 4:
Scope of Work:
Section 2:
Protocol:
Midwest Environmental Consulting Services, Inc. (MEC) was retained by USDA Peoria to conduct a comprehensive asbestos bulk sampling survey for suspect asbestos-containing materials (ACM) in a storage building located at 1815 N University Street, Peoria, IL 61604. The asbestos inspection was performed on April 23, 2026. This comprehensive asbestos bulk sampling inspection was intended to address the potential existence of ACM on the interior and exterior prior to future planned demolition of storage building 004.
26-04-0339-INSP
Peoria, IL 61604
1815 N University Street
USDA PEORIA
Inspection Performed For:
Asbestos-Containing Materials:
SPA - Plaster
TJA - Cementitious Fittings
TPA - Pipe Insulation
Assumed Asbestos-Containing Materials:
N/A
Section 5:
Prior to any planned renovation or demolition taking place, Midwest Environmental Consulting Services, Inc., strongly recommends that either the client contact Midwest Environmental Consulting Services, Inc., or the Illinois Department of Public Health or the Illinois Environmental Protection Agency in regards to applicable rules and regulations.
This survey report is for the exclusive use of USDA and its respective affiliates, designees, successors, and assignees, and no other party shall have any right to rely on service provided by Midwest
Environmental Consulting Services, Inc., without prior written consent. This asbestos survey is not intended to be a scope of work or project design. Estimated quantities of materials are for information only and should not be utilized for abatement bidding purposes.
Although Midwest Environmental Consulting Services, Inc., has attempted to identify all suspect asbestos materials located on the inside of the building; some materials may have been inaccessible.
Midwest Environmental Consulting Services, Inc. makes no warranty, expressed or implied.
Sincerely, Executive Summary:
Standard practice requires that the owner provide Certified-As-Built drawings for review by the inspector. At the time of the inspection, these drawings were not available. Therefore, the accuracy of the inspection can only be based on the materials that were accessible or known about prior to the inspection. If a suspect material is identified during demolition, all work shall stop immediately until the materials can be sampled for asbestos content.
During renovation or demolition, it is recommended that a project design, project oversight, and air monitoring be in place prior to any asbestos abatement work being conducted. An Illinois Department of Public Health licensed asbestos abatement contractor must be in place prior to any asbestos abatement activities.
USDA PEORIA
1815 N University Street
Peoria, IL 61604
MEC Project #: 26-04-0339-INSP
Eden Dennis
IDPH-Licensed Asbestos Building Inspector 100-20748
Inspection Performed For:
Client: Project Location:
Address: Address:
H S A
MATERIAL
CONDITION
MATERIAL
TYPE
APPROX.
QUANTITY
ACM
YES/NO
MRA G M 1080 S.F. No
SPA G S 638 S.F. Yes
TJA D T 5 fittings Yes
TPA G T 30 L.F. Yes
26-04-0339-INSP
April 23, 2026
Eden Dennis
100-20748
Cementitious Fittings North Side Room Friable PLM N/A
N/A
Plaster North Side Room Cat. II Non-Friable PLM N/A
MATERIAL DESCRIPTION MATERIAL LOCATION ACM CATEGORY
MEC Project #:
Insp. Date:
Inspector:
IDPH #:
USDA PEORIA USDA STORAGE BUILDING 004
1815 N University Street
Peoria, IL 61604
N/A
1815 N University Street
Peoria, IL 61604
TYPE OF
ANALYSIS OR
ASSUMED
Asphalt Shingles Roof N/A PLM
Friable PLMNorth Side RoomPipe Insulation
COMMENTS
MRA
ASPHALT SHINGLES
1080 S.F
NO
N/A
1ST FLOOR
HOMOGENEOUS AREA:
DESCRIPTION:
QUANTITY ESTIMATE:
ACM Y/N:
COMMENTS:
Consultant: INSPECTION SURVEY Project No.REV. BY:REV. NO. DATE
REVISIONS
Drawing Date:
Inspector:
Scale: Drawn By:
Client: Project Location:
26-04-0339-INSP
05/05/2026 Eden Dennis
NTS SKM
USDA Peoria 1815 N University Street Peoria, IL 61604
USDA Storage Building 004
SPA
PLASTER
638 S.F
YES
N/A
1ST FLOOR
HOMOGENEOUS AREA:
DESCRIPTION:
QUANTITY ESTIMATE:
ACM Y/N:
COMMENTS:
Consultant: INSPECTION SURVEY Project No.REV. BY:REV. NO. DATE
REVISIONS
Drawing Date:
Inspector:
Scale: Drawn By:
Client: Project Location:
26-04-0339-INSP
05/05/2026 Eden Dennis
NTS SKM
USDA Peoria 1815 N University Street Peoria, IL 61604
USDA Storage Building 004
TJA
CEMENTITIOUS FITTINGS
5 FITTINGS
YES
N/A
1ST FLOOR
HOMOGENEOUS AREA:
DESCRIPTION:
QUANTITY ESTIMATE:
ACM Y/N:
COMMENTS:
Consultant: INSPECTION SURVEY Project No.REV. BY:REV. NO. DATE
REVISIONS
Drawing Date:
Inspector:
Scale: Drawn By:
Client: Project Location:
26-04-0339-INSP
05/05/2026 Eden Dennis
NTS SKM
USDA Peoria 1815 N University Street Peoria, IL 61604
USDA Storage Building 004
TPA
PIPE INSULATION
30 L.F.
YES
N/A
1ST FLOOR
HOMOGENEOUS AREA:
DESCRIPTION:
QUANTITY ESTIMATE:
ACM Y/N:
COMMENTS:
Consultant: INSPECTION SURVEY Project No.REV. BY:REV. NO. DATE
REVISIONS
Drawing Date:
Inspector:
Scale: Drawn By:
Client: Project Location:
26-04-0339-INSP
05/05/2026 Eden Dennis
NTS SKM
USDA Peoria 1815 N University Street Peoria, IL 61604
USDA Storage Building 004
Comments:
Material Location:
ACM Y/N:
N/A
MRA
Asphalt Shingles
Roof
No
Homogeneous Area:
Material Description:
Midwest Environmental Consulting Services, Inc.
MEC Project #: 26-04-0339-INSP
N/A
Homogeneous Area:
Material Description:
Material Location:
ACM Y/N:
SPA
Plaster
North Side Room
Yes
USDA PEORIA
USDA STORAGE BUILDING 004
MEC Project #: 26-04-0339-INSP
Midwest Environmental Consulting Services, Inc.
N/A
Material Location:
ACM Y/N:
North Side Room
Yes
N/A
Homogeneous Area:
Material Description:
TPA
Pipe Insulation
Material Description:
Material Location:
ACM Y/N:
Cementitious Fittings
North Side Room
Yes
Homogeneous Area: TJA
USDA PEORIA
USDA STORAGE BUILDING 004
EMSL Analytical, Inc.
4140 Litt Drive Hillside, IL 60162
Tel/Fax: (773) 313-0099 / (773) 313-0139 http://www.EMSL.com / chicagolab@emsl.com
262604259EMSL Order:
Customer ID: MECO77
Customer PO:
Project ID:
Attention: Phone:EDEN DENNIS (630) 553-3989
Fax:Midwest Environmental Consulting Svs. (630) 553-3990
Received Date:2551 North Bridge Street 04/24/2026 12:21 PM
Analysis Date:Yorkville, IL 60560 05/01/2026
Collected Date:
Project: USDA STORAGE BUILDING 004 26-04-0339-INSP
Test Report: Asbestos Analysis of Bulk Materials via AHERA Method 40CFR 763 Subpart E
Appendix E supplemented with EPA 600/R-93/116 using Polarized Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
MRA 1
262604259-0001
None DetectedNon-fibrous (Other)10%Cellulose90%Black
Fibrous
Homogeneous
ASPHALT
SHINGLES
MRA 2
262604259-0002
None DetectedNon-fibrous (Other)10%Cellulose90%Black
Fibrous
Homogeneous
ASPHALT
SHINGLES
MRA 3
262604259-0003
None DetectedNon-fibrous (Other)10%Cellulose90%Black
Fibrous
Homogeneous
ASPHALT
SHINGLES
SPA 1
262604259-0004
2% ChrysotileNon-fibrous (Other)98%Gray
Non-Fibrous
Homogeneous
PLASTER
SPA 2
262604259-0005
Positive Stop (Not Analyzed)PLASTER
SPA 3
262604259-0006
Positive Stop (Not Analyzed)PLASTER
TJA 1
262604259-0007
60% ChrysotileNon-fibrous (Other)20%Cellulose20%Gray
Fibrous
Homogeneous
CEMENTITIOUS
FITTING
TJA 2
262604259-0008
Positive Stop (Not Analyzed)CEMENTITIOUS
FITTING
TJA 3
262604259-0009
Positive Stop (Not Analyzed)CEMENTITIOUS
FITTING
TPA 1
262604259-0010
20% ChrysotileMica
Non-fibrous (Other)
10%
50%
Cellulose20%Gray/Tan
Non-Fibrous
Homogeneous
PIPE INSULATION
TPA 2
262604259-0011
Positive Stop (Not Analyzed)PIPE INSULATION
TPA 3
262604259-0012
Positive Stop (Not Analyzed)PIPE INSULATION
Initial report from: 05/01/2026 14:44:55
Page 1 of 2ASB_PLM_0008_0002 - 2.31 Printed: 5/1/2026 1:44 PM
EMSL Analytical, Inc.
4140 Litt Drive Hillside, IL 60162
Tel/Fax: (773) 313-0099 / (773) 313-0139 http://www.EMSL.com / chicagolab@emsl.com
262604259EMSL Order:
Customer ID: MECO77
Customer PO:
Project ID:
Analyst(s)
Mazen Elkhatib (6) James Hahn, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Hillside, IL NVLAP Lab Code 200399-0
Initial report from: 05/01/2026 14:44:55
Page 2 of 2ASB_PLM_0008_0002 - 2.31 Printed: 5/1/2026 1:44 PM
OrderID: 262604259
United States Department of Commerce National Institute of Standards and Technology
Certificate of Accreditation to ISO/IEC 17025:2017
NVLAP LAB CODE: 200399-0
EMSL Analytical Inc.
Hillside, IL is accredited by the National Voluntary Laboratory Accreditation Program for specific services, listed on the Scope of Accreditation, for:
Asbestos Fiber Analysis
2025-04-01 through 2026-03-31
Effective Dates For the National Voluntary Laboratory Accreditation Program
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017.
This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality management system (refer to joint ISO-ILAC-IAF Communique on ISO/IEC 17025).
Effective 2025-04-01 through 2026-03-31
.1
IDPH
ILLINOIS DEPARTMENT OF PUBLIC HEALTH
525·535 West Jefferson Street • Springfield. Illinois 62761·0001 • www.dph.illinols.gov
EDEN P DENNIS
1306 N Main St, Apt 1
BLOOMINGTON, IL 61701
3/23/2026
Enclosed is your Asbestos Professional License. Please note the expiration date on the card and in the image depicted below.
COPY OF THE ASBESTOS PROFESSIONAL LICENSE
ID NUMBER
100 - 20748
EDEN P DENNIS
Front of License
ASBESTOS
PROFESSIONAL
LICENSE
ISSUED
3/23/2026
EXPIRES
05/15/2027
1306 N Main s,( Apt 1 BLOOMINGTOt:J, IL 61701
Environm}ntal Health i
Back of License
ENDORSEMENTS TC EXPIRES
! INSPECTOR 10/10/2026
PROJECT MANAGER 10/11/2026
AIR SAMPLING PROFESSIONAL
Alteration of this license shall result in legal action This license Issued under authority of the State of Illinois
Department of Public Health This license is valid only when accompanied by a valid training course certificate.
If you have any questions or need further assistance, contact the Asbestos Program at (217)782-3517 or fax (217)785-5897.
Our WEB address is: dph.illinois.gov/topics-services/environmental-health-protection/asbestos EMAIL Address: doh.asbestos(@,illinois. eov
PROTECTING HEALTH, IMPROVING LIVES
Nationally Accredited by PHAB
| NVLAP Hillside Exp. 03.31.26 (11).pdf |
| AccreditationCertificate2017 - 2025-03-17T154750.734 printed |
| AccreditationScope2017 - 2025-03-17T154756.749 printed |
| 0339-insp.pdf |
| Sheets and Views |
| 0339-insp-MRA |
| 0339-insp-SPA |
| 0339-insp-TJA |
| 0339-insp-TPA |
{"type":"Document","isBackSide":false,"languages":["en-us"],"usedOnDeviceOCR":false}
File details come from the government source that posted it. Updated .