C_-_Plans_&_Drawings.pdf
PDF 14 MB Posted
- Attached to
- Permanent Disinfection Boosting Systems at La Granada (CI 5771) and Lang Ranch (CI 5791) Reservoirs
- Solicitation number
- 2025/2026-24
- Issued by
- Ventura County, California
About this file
This is a comprehensive plans and drawings document for the City of Thousand Oaks, prepared by AECOM, depicting the permanent disinfection boosting systems project at La Granada Reservoir (CI 5771) and Lang Ranch Reservoir (CI 5791) in California. The project encompasses the complete design and installation of two permanent chemical disinfection boosting systems, including civil, structural, mechanical, electrical, and instrumentation components at both reservoir locations. The work scope includes procurement and installation of duplex peristaltic metering pump skids for sodium hypochlorite and liquid ammonium sulfate feed systems, chemical storage tanks with concrete containment pads, piping and valve assemblies, shade canopy structures, water quality stations, smart control centers, and all associated electrical and control systems. The drawings are organized into 29 sheets covering general notes and legends, structural details and plans, mechanical systems, electrical site plans and single-line diagrams, and process and instrumentation diagrams. The project requires coordination with existing operations to maintain compliance with state and federal regulatory requirements, with construction activities subject to restrictions and limitations detailed in the project specifications.
The design reflects a total specification number 2025/2026-24 prepared at 100% design completion dated April 3, 2026, with final approval dated April 14, 2026. The contractor must possess a valid Class A general engineering license and shall call USA Underground Alert at least two days prior to construction to locate existing underground utilities, assuming sole responsibility for any damage. Special inspections are required in accordance with CBC Chapter 17 for concrete reinforcement, structural steel welding, bolting operations, soil verification, and electrical equipment anchorage. The project involves expansion and modification of facilities at existing operational reservoirs, requiring the contractor to schedule and coordinate work so that state and federal regulatory agency requirements are continuously met. Construction sites must be maintained in a neat, clean, hazard-free condition with all excess excavated material and debris immediately removed at the contractor's expense. Fire inspection must be conducted by Ventura County Fire Department Inspector Lori Ross, and the contractor must enroll in the City's TO24 system to obtain necessary permits and arrange for building, electrical, and fire site inspections.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUNSET HILLS BLVD.
SITE ENTRANCEPEAK PL.
M O
NTE CARLO
DR.
RIKKARD DR.
R
IC
KEY C
T.
BO
R
D
ER
LN
LANG RANCH
RESERVOIR
ER
BES R
D
SITE ENTRANCE
MOUNTAIN
SITE
ENTRANCE
RANCH VIEW
PL
N C
O N
EJ
O
S C
H O
O L
R D
CR
ES
T C
IR
C
LE
TW
IN
O
AK
S
CT
RYE CT
LA GRANADA
RESERVOIR
E HILLCREST DR.
C T
SHEET INDEX
SHT. NO. DWG. NO. SHEET TITLE
GENERAL
01 G-001 COVER SHEET
02 G-002 GENERAL NOTES AND LEGENDS
03 G-003 GENERAL STRUCTURAL NOTES
04 G-004 STRUCTURAL DESIGN CRITERIA AND ABBREVIATIONS
05 G-005 SPECIAL INSPECTIONS AND STRUCTURAL OBSERVATIONS
06 G-006 TYPICAL STRUCTURAL DETAILS
07 G-007 MECHANICAL GENERAL NOTES, LEGENDS, AND SYMBOLS
08 G-008 MECHANICAL DETAILS
09 G-009 ELECTRICAL LEGEND AND SYMBOLS
10 G-010 INSTRUMENTATION LEGEND AND SYMBOLS
ARCHITECTURAL
11 A-001 CANOPY ROOF PLAN AND DETAILS
LA GRANADA PUMP STATION
12 C-001 CIVIL DEMO PLAN AND SITE PLAN
13 S-001 STRUCTURAL PLAN
14 S-002 STRUCTURAL SECTIONS
15 E-001 ELECTRICAL SITE PLAN
16 E-002 SINGLE LINE DIAGRAM & PANEL SCHEDULE
17 D-001 MECHANICAL DEMO PLAN
18 M-001 MECHANICAL PLAN
19 M-002 MECHANICAL SECTION
20 P-001 PROCESS AND INSTRUMENTATION DIAGRAM
LANG RANCH PUMP STATION
21 C-002 CIVIL DEMO PLAN AND SITE PLAN
22 S-003 STRUCTURAL PLAN
23 S-004 STRUCTURAL SECTIONS
24 E-003 ELECTRICAL SITE PLAN
25 E-004 SINGLE LINE DIAGRAM & PANEL SCHEDULE
26 D-002 MECHANICAL DEMO PLAN
27 M-003 MECHANICAL PLAN
28 M-004 MECHANICAL SECTION
29 P-002 PROCESS AND INSTRUMENTATION DIAGRAM
PUBLIC UTILITIES WITHIN CITY OF THOUSAND OAKS
NOTICE TO CONTRACTOR:
NOTICE TO CONTRACTOR:
CONTRACTOR SHALL POSSES A VALID CLASS "A" GENERAL ENGINEERING LICENSE
IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO CALL THE USA
UNDERGROUND ALERT FOR LOCATION OF EXISTING UNDERGROUND UTILITIES NO
LESS THAN TWO DAYS NOR MORE THAN SEVEN DAYS PRIOR TO CONSTRUCTION.
THE CONTRACTOR SHALL ASSUME SOLE RESPONSIBILITY FOR ANY DAMAGE DONE
TO EXISTING UTILITIES DURING CONSTRUCTION
805-379-5060 PATRICK McCULLOCK
THOUSAND OAKS, CA 91362
2100 EAST THOUSAND OAKS BOULEVARD
CITY OF THOUSAND OAKS
WATER:
WASTEWATER:
SPECTRUM
2525 KNOLL DRIVE
VENTURA, CA 93003
805-494-7013
THOUSAND OAKS, CA 91361
3589 FOOTHILL DRIVE
SOUTHERN CALIFORNIA EDISON COMPANY
BOB MIGLIORE
GAS:
CABLE TV:
ELECTRICITY:
TELEPHONE:
ERIC PINGREE
805-626-3219
JON TRELATSKY
201 FLYNN ROAD
CAMARILLO, CA 93012
805-388-2266
SOUTHERN CALIFORNIA GAS COMPANY
9400 OAKDALE AVENUE
CHATSWORTH, CA 91311
805-358-1596
FRONTIER
SPECIFICATION NO.: 2025/2026-24
FRONTIER
201 FLYNN ROAD
CAMARILLO, CA 93010
JASON EISEL
805-233-1472
CITY COUNCIL
CITY ENGINEER
H. TED GERBER
NADER HEYDARI
PUBLIC WORKS DIRECTOR
C. TIE GUTIERREZAL ADAM
DAVID NEWMAN
CITY MANAGER
ANDREW P. POWERS
WHUEY WEN HARTMAN
MIKEY TAYLOR, MAYOR
G-001 SHEET __ OF __
CITY OF THOUSAND OAKS
H. TED GERBER, CITY ENGINEER
DATEENGINEERING DIVISION MANAGER
CITY OF THOUSAND OAKS
DATEDATEREGISTERED ENGINEER
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV. SYMBOL DESCRIPTIONUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
Know what'sbelow.Callbefore you dig.
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
CITY OF THOUSAND OAKS DWG.
3027 TOWNSGATE RD., SUITE 140
WESTLAKE VILLAGE, CA 91361
WWW.AECOM.COM
DWG NO25-024A
PERMANENT DISINFECTION BOOSTING SYSTEMS AT
LA GRANADA (CI 5771), AND LANG RANCH (CI 5791) RESERVOIRS
YEIMY G. FERNANDEZ-OJEDA 04/03/2026
YF
DG
RH
04/03/26
04/03/26
04/03/26
No. C92926
CITY OF THOUSAND OAKS
CIVIC ARTS PLAZA
2100 E. THOUSAND OAKS BOULEVARD
THOUSAND OAKS, CA. 91362
BRET SHERMAN
805-379-5033
PERMANENT DISINFECTION BOOSTING SYSTEMS AT
LA GRANADA (CI 5771), AND LANG RANCH (CI 5791)
RESERVOIRS
COVER SHEET
ROBERT ENGLER
LANG RANCH PUMP STATION AND RES.
2237 PEAK PLACE
VICINITY MAP
NO SCALE
PROJECT SITE LOCATION
LA GRANADA PUMP STATION AND RES.
2354 MOUNTAIN CREST CIR.
N
LANG RANCH LOCATION MAP
LA GRANADA LOCATION MAP
N
100% DESIGN
SENIOR ENGINEER
04/09/2026
Shamir Shahamiri 04/09/2026
04-14-2026
PIPING LEGEND CIVIL LEGEND
EXISTING
PROPOSED
CHAIN LINK FENCE
BUILDING WALL / BLOCK WALL
CONCRETE FLATWORK
ASPHALT
RIGHT-OF-WAY
FLOW LINE
SURFACE FLOW
DEMOLITION
REGRADING
EXISTING PIPE
EXISTING PIPE (BELOW GROUND)
EXISTING VALVE
EXISTING PUMP
EXISTING VAULT
EXISTING TANK
BUTTERFLY
KNIFE GATE
SWING CHECK
ECCENTRIC PLUG
BALL CHECK
3-WAY GLOBE
LUBRICATED PLUG
DIAPHRAGM
PLUG
GLOBE
BALL
GATE
SOLENOID CONTROL
3-WAY SOLENOID
NEEDLE
DIAPHRAGM ACTUATED
EDUCTOR
VALVES
PINCH
MIXER
MOTOR OPERATED BUTTERFLY
(MODULATING)
MOTOR OPERATED
BUTTERFLY (OPEN/CLOSE)
PRESSURE RELIEF
PRESSURE REDUCING REGULATOR
GENERAL NOTES
1. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE STANDARD SPECIFICATION FOR PUBLIC WORKS
CONSTRUCTION, ALL APPLICABLE AMERICAN WATER WORKS ASSOCIATION (AWWA) STANDARDS, CITY OF THOUSAND OAKS WATER AND ROAD CONSTRUCTION STANDARDS, AND IN ACCORDANCE WITH THESE PLANS AND SPECIFICATIONS, ALL TO THE SATISFACTION OF THE ENGINEER AND THE OWNER. WHERE CONFLICTS BETWEEN CODES AND SPECIFICATIONS OCCUR THE
MOST STRINGENT REQUIREMENTS SHALL GOVERN.
2. CONTRACTOR SHALL COORDINATE ALL CONSTRUCTION ACTIVITIES WITH CITY OPERATIONS.
3. CONTRACTOR SHALL NOTIFY THE ENGINEER AT LEAST FIVE (5) WORKING DAYS PRIOR TO BEGINNING OF CONSTRUCTION. NO
FACILITY SHALL BE BACKFILLED UNTIL INSPECTED BY THE ENGINEER.
4. THE CONTRACTOR SHALL HAVE COPIES OF THE PLANS, SPECIFICATIONS, AND SUBMITTALS FOR THIS PROJECT ON THE SITE AT ALL TIMES AND SHALL BE FAMILIAR WITH ALL APPLICABLE STANDARDS AND SPECIFICATIONS.
5. ALL WORKS SHALL CONFORM TO THE PLANS AND SPECIFICATIONS IN ALL RESPECTS AND SHALL BE SUBJECT TO APPROVAL BY
THE ENGINEER.
6. CONSTRUCTION ACTIVITIES MAY OCCUR IN ACCORDANCE WITH RESTRICTIONS AND LIMITATIONS AS PRESENTED IN THE
PROJECT SPECIFICATIONS.
7. CONSTRUCTION UNDER THIS CONTRACT INVOLVES EXPANSION AND/OR MODIFICATION OF FACILITIES THAT ARE A PART OF EXISTING OPERATIONS. THE EXISTING OPERATIONS MUST CONTINUE SO THAT STATE AND FEDERAL REGULATORY AGENCY REQUIREMENTS ARE MET AT ALL TIMES. THE CONTRACTOR MUST SCHEDULE AND COORDINATE ITS WORK AND OPERATIONS
WITH THE OWNER SO THAT THESE REQUIREMENTS ARE MET.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE TO ALL EXISTING FACILITIES AS A RESULT OF ITS OPERATIONS AND WILL BE REQUIRED TO REPAIR OR REPLACE IN-KIND TO THE SATISFACTION OF, AND AS DIRECTED BY, THE ENGINEER OR
OWNER, AT NO ADDITIONAL COST TO THE OWNER.
9. THE WORKS SITES AND EXTERIOR STREETS SHALL BE MAINTAINED IN A NEAT, CLEAN, HAZARD-FREE ORDERLY STATE, THROUGHOUT CONSTRUCTION. SITE SHALL BE CLEANED UPON REQUEST OF THE OWNERS OR ITS REPRESENTATIVE. THE CONTRACTOR SHALL IMMEDIATELY HAUL AWAY AND DISPOSE OF, OFF THE PROJECT SITE, ALL EXCESS EXCAVATED MATERIAL
AND CONSTRUCTION DEBRIS. ALL DISPOSALS SHALL BE AT THE CONTRACTOR'S EXPENSE.
10. CONTRACTOR SHALL VERIFY THE LOCATION OF ALL SITE UTILITIES PRIOR TO START OF CONSTRUCTION. BOTH ABOVE GROUND AND BELOW GROUND, WHICH MAY BE IMPACTED BY THE WORK SHOWN ON THESE DRAWINGS. ANY CONFLICTS SHALL BE
BROUGHT TO THE ATTENTION OF THE ENGINEER.
11. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS BEFORE STARTING WORK. SHOULD CONDITIONS EXIST THAT ARE CONTRARY TO THOSE SHOWN ON PLANS, THE ENGINEER SHALL BE NOTIFIED IN WRITING BEFORE
PROCEEDING WITH WORK.
12. THE CONTRACTOR SHALL CONDUCT CONSTRUCTION OPERATIONS IN SUCH AS MANNER THAT STORM OR OTHER WATERS MAY
PROCEED UNINTERRUPTED ALONG EXISTING DRAINAGE COURSES.
13. CONSTRUCTION SITES SHALL BE MAINTAINED IN SUCH A CONDITION THAT AN UNANTICIPATED STORM DOES NOT CARRY
WASTES OR POLLUTANTS OFF THE SITE.
14. INTERRUPTIONS TO UTILITY OPERATION SHALL BE MINIMIZED. THE CONTRACTOR SHALL MAKE ALL PROVISIONS NECESSARY TO MINIMIZE INTERRUPTIONS. PRIOR TO COMMENCING WORK ON THE EXISTING UTILITIES, THE CONTRACTOR SHALL SUBMIT PROPOSED PLANS FOR EXPANSION AND/OR MODIFICATION OF UTILITIES ALONG WITH PLANS FOR MINIMIZING INTERRUPTIONS
TO THE PROJECT REPRESENTATIVE FOR REVIEW.
15. CONSTRUCTION ACCESS SHALL BE AS DIRECTED BY THE OWNER OR ITS REPRESENTATIVE.
16. THE CONTRACTOR SHALL HAVE A CLASS “A” GENERAL CONTRACTOR'S LICENSE.
17. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THAT ALL WORK IS ADEQUATELY BRACED AND SHORED
DURING CONSTRUCTION.
18. APPROXIMATE LIMITS OF DEMOLITION ARE SHOWN. THE CONTRACTOR SHALL VERIFY THE EXISTING FACILITIES AND DETERMINE THE EXACT LIMITS AND SEQUENCE OF DEMOLITION TO FACILITATE NEW CONSTRUCTION WITHOUT INTERRUPTING OPERATIONS.
19. ALL EXCESS SOIL MATERIAL AND DEBRIS SHALL BE REMOVED FROM SITE AND DISPOSED OF IN ACCORDANCE WITH THE SPECIFICATIONS. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL PERMITS INVOLVED WITH HAULING AND DUMPING.
20. UNLESS DETAILED, SPECIFIED, OR INDICATED OTHERWISE, CONSTRUCTION SHALL BE AS INDICATED IN THE APPLICABLE TYPICAL DETAILS AND THESE GENERAL NOTES. TYPICAL DETAILS ARE MEANT TO APPLY EVEN THOUGH NOT REFERENCED AT
SPECIFIC LOCATIONS ON DRAWINGS WHERE THEY OCCUR.
21. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE MEANS AND METHODS TO ACCOMPLISH THE CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE, WORKERS, AND PEDESTRIANS DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO BRACING, SHORING, TEMPORARY STRUCTURES, PARTIALLY COMPLETED WORK, ETC. OBSERVATION VISITS
TO THE SITE BY THE ENGINEER SHALL NOT BE CONSIDERED AS INSPECTION OF SUCH ITEMS.
22. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON DRAWINGS.
23. THE STRUCTURAL DRAWINGS ONLY SHOW THE STRUCTURAL REQUIREMENTS, REFER TO CIVIL, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR NON-STRUCTURAL ITEMS.
24. THE CIVIL DRAWINGS ARE TO BE USED IN CONJUNCTION WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS.
25. NO SMOKING IS ALLOWED WITHIN THE JOBSITE OR SITE ACCESS AREAS. A FIRE SPOTTER, FIRE EXTINGUISHER, ADEQUATE WATER SUPPLY, AND SHOVELS SHALL BE AVAILABLE AND WITHIN REACH AT ALL TIMES DURING ANY WELDING OR TORCH WORK.
THIS JOBSITE IS IN AN EXTREMELY HAZARDOUS FIRE AREA.
26. EXISTING TOPOGRAPHY, STRUCTURES, AND SITE FEATURES ARE SHOWN SCREENED OR LIGHT-LINED. NEW FINISH GRADE, STRUCTURES, AND SITE FEATURES ARE SHOWN HEAVY-LINED.
27. KEEP A STRICT RECORD OF ALL CHANGES AND SUBMIT THIS RECORD TO THE OWNER ALSO COORDINATE TRANSFERRING "AS-BUILT" INFORMATION ON THE CONTRACT DRAWINGS AND DELIVER THE CERTIFIED " AS-BUILT" PLANS TO THE OWNER
BEFORE THE RELEASE FOR FINAL ACCEPTANCE OF THE PROJECT SHALL BE FILES.
28. CITY STAFF SHALL HAVE 24-HOUR / 7-DAYS A WEEK ACCESS TO THE SITE.
29. FIRE INSPECTION MUST BE BY VENTURA COUNTY FIRE DEPARTMENT INSPECTOR, LORI ROSS (805) 947-8535, lori.ross@ventura.org
30. CONTRACTOR SHALL ENROLL IN CITY'S TO24 TO OBTAIN THE NECESSARY PERMITS AND ARRANGE FOR SITE INSPECTIONS
(BUILDING, ELECTRICAL, AND FIRE)
NOTICE TO CONTRACTOR
LOCATIONS, SIZES, AND INVERTS OF EXISTING UTILITIES AND YARD PIPING ARE SHOWN BASED ON THE BEST AVAILABLE INFORMATION. HOWEVER, THE ENGINEER DOES NOT GUARANTEE THAT SUCH INFORMATION IS TRUE OR EVEN APPROXIMATE. THE CONTRACTOR SHALL VERIFY, AT A MINIMUM, THE LOCATIONS, MATERIAL, SIZES, AND INVERTS OF EXISTING UTILITIES AND DETERMINE WHICH UTILITIES MAY CONFLICT WITH CONSTRUCTION WORK. THE CONTRACTOR SHALL ADJUST HIS WORK ACCORDINGLY AND NOTIFY THE PROJECT REPRESENTATIVE OF ANY SUCH CONFLICTS AND PROPOSED RESOLUTION. THE CONTRACTOR SHALL REFER TO APPLICABLE SECTIONS OF THE SPECIFICATIONS RELATIVE TO THE ABOVE.
CONTRACTOR AGREES THAT HE SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION OF THIS PROJECT, INCLUDING SAFETY OF ALL PERSONS AND PROPERTY, THAT THESE REQUIREMENTS SHALL APPLY CONTINUOUSLY AND SHALL NOT BE LIMITED TO NORMAL WORKING HOURS, AND THAT THE CONTRACTOR SHALL DEFEND, INDEMNIFY AND HOLD THE PROPERTY OWNER AND THE ENGINEER HARMLESS FROM ANY AND ALL LIABILITY, REAL OR ALLEGED IN CONNECTION WITH THE PERFORMANCE OF WORK ON THIS PROJECT, EXCEPTING FOR LIABILITY ARISING FROM SOLE
NEGLIGENCE OF PROPERTY OWNER OR ENGINEER.
UNDERGROUND UTILITIES HAVE NOT BEEN FIELD VERIFIED. IF PRECISE INFORMATION IS REQUIRED AS TO THE EXISTENCE AND LOCATIONS OF THE FEATURES IN ORDER TO EXECUTE THE WORK AS SHOWN ON THE PLANS, THE CONTRACTOR SHALL OBTAIN THE INFORMATION AT NO ADDITIONAL COST BY DETAILED FIELD INVESTIGATIONS, INSTRUMENTAL SURVEYING, AND POTHOLING TECHNIQUES. ADDITIONALLY, THE CONTRACTOR SHALL TAKE ALL PRECAUTIONARY MEASURES TO PROJECT THE UNDERGROUND UTILITIES AND STRUCTURES, WHETHER SHOWN OR NOT ON THE PLANS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL DAMAGES CAUSED BY THE FAILURE OF LOCATION AND PROTECTING UNDERGROUND UTILITIES AND STRUCTURES.
NOTE REGARDING SCALED DRAWINGS
ALL SCALES LISTED ASSUME A FULL SIZE, 24' X 36” SHEET SIZE.
POTHOLE NOTES
EXISTING UTILITY LOCATIONS ARE APPROXIMATE AND BASED ON RECORD DRAWINGS. POTHOLE AND SURVEY EXISTING UTILITIES THAT WILL BE AFFECTED BY TRENCHING OR EXCAVATIONS PRIOR TO ORDERING ANY MATERIALS. POTHOLE AND SURVEY DATA SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW. POTHOLE DATA SHALL INCLUDE EXISTING UTILITY HORIZONTAL LOCATION, PIPE ELEVATION, SIZE, PIPE ANGULAR CONFIGURATION, AND MATERIALS OF CONSTRUCTION. IDENTIFY POTENTIAL CONFLICTS WITH THE NEW PIPE LOCATION. PIPE ALIGNMENT ADJUSTMENTS THAT DO NOT INCREASE OVERALL PIPE OR FITTING QUANTITIES SHALL
BE MADE AT NO ADDITIONAL COST TO THE CITY.
FIELD VERIFY THE HORIZONTAL AND VERTICAL LOCATION, DIAMETER, AND ORIENTATION AT ALL CONNECTION POINTS AND COORDINATE WITH THE CITY PRIOR TO CONSTRUCTION. PROVIDE ALL PIPE MATERIALS AND FITTINGS, AS REQUIRED TO MEET
EXISTING FIELD CONDITIONS FOR A COMPLETE INSTALLATION.
PAVEMENT CUTS SHALL BE PERFORMED BY SAW CUTTING AND GRINDING. CUT PAVEMENT PRIOR TO REPAVING WHERE
UNDERMINING HAS OCCURRED.
REMOVAL AND REPLACEMENT OF PAVEMENT SHALL BE IN ACCORDANCE WITH THE SPECIFICATION SECTION 32 12 16.
TRENCHES SHALL BE BACKFILLED IN ACCORDANCE WITH THE CITY STANDARD PLATES 8-14.
SHEET __ OF __
CITY OF THOUSAND OAKS
H. TED GERBER, CITY ENGINEER
DATEENGINEERING DIVISION MANAGER
CITY OF THOUSAND OAKS
DATEDATEREGISTERED ENGINEER
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV. SYMBOL DESCRIPTIONUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
Know what'sbelow.Callbefore you dig.
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
CITY OF THOUSAND OAKS DWG.
3027 TOWNSGATE RD., SUITE 140
WESTLAKE VILLAGE, CA 91361
WWW.AECOM.COM
DWG NO25-024A
PERMANENT DISINFECTION BOOSTING SYSTEMS AT
LA GRANADA (CI 5771), AND LANG RANCH (CI 5791) RESERVOIRS
YEIMY G. FERNANDEZ-OJEDA 04/03/2026
YF
DG
RH
04/03/26
04/03/26
04/03/26
No. C92926
N
X TITLE
XX Scale 1/4" = 1'-0"
X
X-XXX
X
X-XXX
INDICATES DIRECTION
OF PLAN NORTH
DETAIL NUMBER
SECTION LETTER
SHEET WHERE SECTION IS
LOCATED
SHEET WHERE DETAIL IS
LOCATED
GENERAL SYMBOLOGY LEGEND
DETAIL TITLE
SECTION CUT MARKER
DETAIL CALLOUT BUBBLE
00 10' 20'
1" = 10'
NORTH ARROW AND BAR SCALE
INDICATES
SCALE OF PLAN
DETAIL NUMBER OR
SECTION LETTER
TITLE OF DETAIL
OR SECTION
SCALE OF DETAIL
OR SECTION
SHEET WHERE
DETAIL OR SECTION
IS TAKEN FROM
02G-002
GENERAL NOTES AND LEGENDS
SENIOR ENGINEER
04/09/2026
03SHEET __ OF __
CITY OF THOUSAND OAKS
H. TED GERBER, CITY ENGINEER
DATEENGINEERING DIVISION MANAGER
CITY OF THOUSAND OAKS
DATEDATEREGISTERED ENGINEER
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV. SYMBOL DESCRIPTIONUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
Know what'sbelow.Callbefore you dig.
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
CITY OF THOUSAND OAKS DWG.
3027 TOWNSGATE RD., SUITE 140
WESTLAKE VILLAGE, CA 91361
WWW.AECOM.COM
DWG NO25-024A
PERMANENT DISINFECTION BOOSTING SYSTEMS AT
LA GRANADA (CI 5771), AND LANG RANCH (CI 5791) RESERVOIRS
No. 2582
DAL E. WAH 04/03/2026
DW
TN
DK
04/03/26
04/03/26
04/03/26 GENERAL STRUCTURAL NOTES
THESE NOTES SHALL APPLY UNLESS SHOWN/INDICATED OTHERWISE ELSEWHERE ON THE
STRUCTURAL DRAWINGS.
1. MATERIALS AND CONSTRUCTION SHALL CONFORM TO THE 2025 CALIFORNIA BUILDING CODE (CBC), BASED UPON THE 2024 EDITION OF THE INTERNATIONAL BUILDING CODE (IBC). WHERE CONFLICTS
BETWEEN CODES AND SPECIFICATIONS OCCUR, THE MOST STRINGENT REQUIREMENTS SHALL
GOVERN. ALL ASTM DESIGNATIONS REFERRED TO ON THESE DRAWINGS SHALL BE THE LATEST
ADOPTED OR REVISED SPECIFICATION, AS OF THE DATE OF THESE DRAWINGS.
2. THE STRUCTURAL DRAWINGS ARE TO BE USED IN CONJUNCTION WITH CIVIL, ELECTRICAL AND
MECHANICAL DRAWINGS. NO PORTION OF STRUCTURAL RELATED WORK, INCLUDING SHOP
DRAWING DEVELOPMENT, SHALL BE PERFORMED WITHOUT CONSIDERING REQUIREMENTS OF
CONTRACT DOCUMENTS IN THEIR ENTIRETY.
3. NEITHER THE CITY NOR THE STRUCTURAL ENGINEER WILL ENFORCE SAFETY MEASURES OR
REGULATIONS. THE CONTRACTOR SHALL, AT HIS OWN EXPENSE, DESIGN, CONSTRUCT AND
MAINTAIN ALL SAFETY DEVICES, INCLUDING SHORING AND BRACING AND SHALL BE SOLELY
RESPONSIBLE FOR CONFORMING TO ALL LOCAL, STATE AND FEDERAL SAFETY AND HEALTH
STANDARDS, LAWS AND REGULATIONS. SITE OBSERVATION VISITS BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE SAFETY ITEMS. IF A LAWSUIT IS FILED BY ONE OF
THE CONTRACTOR'S OR SUBCONTRACTOR'S EMPLOYEES, OR ANY ONE ELSE, THE CONTRACTOR
WILL INDEMNIFY, DEFEND AND HOLD THE OWNER AND AECOM, THEIR PARENT AND SUBSIDIARY
COMPANIES HARMLESS OF ANY AND ALL SUCH CLAIMS.
4. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO ENSURE THAT ALL WORK IS
ADEQUATELY BRACED AND SHORED DURING CONSTRUCTION. ALL BRACING/SHORING SHALL BE
DESIGNED BY A REGISTERED ENGINEER HIRED BY THE CONTRACTOR.
5. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS BEFORE STARTING
WORK. SHOULD CONDITIONS EXIST WHICH ARE CONTRARY TO THOSE SHOWN ON PLANS, THE
ENGINEER SHALL BE NOTIFIED IN WRITING BEFORE PROCEEDING WITH WORK.
6. UNLESS DETAILED, SPECIFIED, OR INDICATED OTHERWISE, CONSTRUCTION SHALL BE AS
INDICATED IN THE APPLICABLE TYPICAL DETAILS AND THESE GENERAL NOTES. TYPICAL DETAILS
ARE MEANT TO APPLY EVEN THOUGH NOT REFERENCED AT SPECIFIC LOCATIONS ON DRAWINGS
WHERE THEY OCCUR.
7. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. THEY DO
NOT INDICATE THE MEANS AND METHODS TO ACCOMPLISH THE CONSTRUCTION. THE
CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE,
WORKERS AND PEDESTRIANS DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT
NOT BE LIMITED TO BRACING, SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT,
TEMPORARY STRUCTURES, AND PARTIALLY COMPLETED WORK, ETC. OBSERVATION VISITS TO THE
SITE BY THE ENGINEER SHALL NOT BE CONSIDERED AS INSPECTION OF SUCH ITEMS.
8. DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON DRAWINGS. DO NOT SCALE
DRAWINGS.
9. ALL WORK SHALL CONFORM TO THE PLANS AND SPECIFICATIONS IN ALL RESPECTS AND SHALL BE
SUBJECT TO APPROVAL BY THE ENGINEER.
10. THE STRUCTURAL DRAWINGS SHOW ONLY THE STRUCTURAL REQUIREMENTS. REFER TO CIVIL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR NON-STRUCTURAL ITEMS, SUCH AS:
A. SIZE AND LOCATION OF ALL OPENINGS.
B. SIZE AND LOCATION OF ALL NON-BEARING WALLS.
C. SIZE AND LOCATION OF ALL CONCRETE CURBS, WALKS, ROOF AND FLOOR DRAINS, SLOPES, DEPRESSED SLAB AREAS, ETC.
D. DIMENSIONS WHICH ARE NOT SHOWN ON STRUCTURAL DRAWINGS.
11. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED FLOORS OR ROOF.
LOAD SHALL NOT EXCEED DESIGN LIVE LOAD FOR EACH PARTICULAR LEVEL. WHEN WEIGHT OF
MATERIALS OR EQUIPMENT MAY EXCEED DESIGN LOAD, STRUCTURAL SYSTEMS SHALL BE
SHORED.
12. CONTRACTOR SHALL VERIFY LOCATION OF ALL SITE UTILITIES PRIOR TO STARTING WORK, BOTH
ABOVE GROUND AND BELOW GROUND, WHICH MAY BE IMPACTED BY THE WORK SHOWN ON THESE
DRAWINGS. ANY CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER.
13. ALL ITEMS SHOWN ON THESE PLANS ARE NEW UNLESS NOTED (E), EXIST. OR EXISTING.
GENERAL
GENERAL STRUCTURAL NOTES
AGGREGATES FOR CONCRETE SHALL CONFORM TO ASTM C33. CONCRETE f'c AT 28 DAYS SHALL BE AS NOTED BELOW. REQUIRED AVERAGE COMPRESSIVE STRENGTH (f'cr) SHALL BE IN ACCORDANCE WITH
ACI 301-20, ARTICLE 4.2.3
1. CEMENT FOR CONCRETE SHALL BE TYPE II PORTLAND CEMENT CONFORMING TO ASTM C150.
2. READY MIXED CONCRETE SHALL CONFORM TO ASTM C94.
3. CONCRETE COVER FOR REINFORCING BARS SHALL BE:
CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH OR WATER = 3"
EXPOSED TO WEATHER: = 2."
4. DRYPACK SHALL BE 1 PART CEMENT AND 3 PARTS SAND (BY VOLUME).
5. NO PIPES OR DUCTS SHALL BE PLACED IN STRUCTURAL CONCRETE UNLESS SPECIFICALLY
DETAILED. SEE MECHANICAL AND/OR ELECTRICAL DRAWINGS FOR LOCATION OF SLEEVES
THROUGH WALLS AND FLOORS.
6. REFER TO DRAWING DETAILS FOR ALL MOLDS, GROOVES, CLIPS, GROUNDS, ORNAMENTS AND
OTHER INSERTS TO BE CAST IN CONCRETE.
7. THE LOCATION OF ALL CONSTRUCTION JOINTS NOT SPECIFICALLY NOTED OR SHOWN SHALL BE
APPROVED BY THE STRUCTURAL ENGINEER.
8. "ROUGHENED SURFACES", WHERE SPECIFIED ON THE DRAWINGS, SHALL BE MECHANICALLY
ROUGHENED SUCH THAT A 1/4"± AMPLITUDE IS ACHIEVED BETWEEN HIGH AND LOW SPOTS OF THE
ROUGHENED SURFACE. THE SURFACE SHALL BE CLEAN AND FREE OF LAITANCE.
9. ALL SLABS SHALL HAVE A TROWEL FINISH EXCEPT AS NOTED ON THE DRAWINGS.
10. PROVIDE 3/4" CHAMFER AT ALL EXPOSED (I.E., NOT BURIED OR CONCEALED FROM VIEW OR
ACCESS) CONCRETE EDGES AND CORNERS.
CONCRETE NOTES
CONCRETE SCHEDULE
ITEMS
28 DAY COMPRESSIVE CYLINDER
STRENGTH
3000 PSI 4000 PSI
ALL CONCRETE, U.N.O.
1. ALL STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE ASTM A36 UNLESS NOTED OTHERWISE AND SHALL BE FABRICATED IN ACCORDANCE WITH THE AISC SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS. SPECIAL INSPECTION SHALL
BE PROVIDED FOR ALL STRUCTURAL STEEL UNLESS FABRICATION IS PERFORMED ON THE
PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO PERFORM SUCH WORK WITHOUT
SPECIAL INSPECTION, IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND SECTION
1704.2.5.1 OF THE 2025 CBC. AT THE COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE CITY BUILDING OFFICIAL AND TO THE
ENGINEER STATING THAT THE WORK WAS PERFORMED IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
2. ALL WIDE FLANGE SECTIONS (W SHAPES) SHALL CONFORM TO ASTM A992, Fy = 50 KSI.
3. STEEL TUBES SHALL CONFORM TO ASTM A500, GRADE B OR BETTER, UNLESS NOTED OTHERWISE.
4. STEEL PIPES SHALL CONFORM TO ASTM A53, GRADE B.
5. BOLTS SHALL CONFORM TO ASTM A307 OR BETTER, UNLESS NOTED OTHERWISE.
6. HOLES FOR BOLTS IN STEEL SHALL BE OF SAME DIAMETER AS BOLT +1/16" MAXIMUM. CONNECTED
MEMBERS SHALL BEAR ONLY UPON UNTHREADED PORTIONS OF BOLTS.
7. ALL WELDING SHALL BE SHIELDED ARC TYPE IN ACCORDANCE WITH THE PROVISIONS OF THE AMERICAN WELDING SOCIETY CODE D1.1, AND SHALL BE PERFORMED BY A CERTIFIED WELDER IN A
FABRICATION SHOP REGISTERED AND APPROVED IN ACCORDANCE WITH STEEL NOTE 1 ABOVE.
CONTINUOUS INSPECTION IS REQUIRED OF ALL FIELD WELDING IN ACCORDANCE WITH AISC 360, SECTION N5.4.
8. NO STRUCTURAL STEEL MEMBER SHALL BE CUT FOR PIPES, DUCTS, ETC. UNLESS SPECIFICALLY
DETAILED AND APPROVED BY THE STRUCTURAL ENGINEER.
9. STAINLESS STEEL BARS AND SHAPES SHALL CONFORM TO ASTM A276/AISI 316. STAINLESS STEEL PLATE SHALL CONFORM TO ASTM A240, TYPE 316. STAINLESS STEEL BOLTS SHALL CONFORM TO ASTM F593, TYPE 316 (CW). STAINLESS STEEL NUTS SHALL CONFORM TO ASTM F594, TYPE 316 (CW).
10. WELDING OF STAINLESS STEEL SHALL CONFORM TO STRUCTURAL WELDING CODE - STAINLESS
STEEL, ANSI/AWS D1.6-17
11. WHERE SPECIFIED, USE OF HIGH-STRENGTH BOLTS SHALL CONFORM TO THE PROVISIONS OF THE "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS" APPROVED BY THE
RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS OF THE ENGINEERING FOUNDATION (RCSC).
SPECIAL INSPECTION OF HIGH-STRENGTH BOLT CONNECTIONS IS REQUIRED.
12. ALL CARBON STEEL EXPOSED TO WEATHER OR DAMP/WET CONDITION SHALL BE HOT DIP
GALVANIZED IN ACCORDANCE WITH ASTM A123, A153, A385 AFTER FABRICATION. REPAIR/TOUCHUP OF GALVANIZING SHALL BE IN ACCORDANCE WITH ASTM A780. ALL OTHER CARBON STEEL SHALL
RECEIVE TWO COATS OF SHOP APPLIED PRIMER AND BE COATED IN ACCORDANCE WITH THE
SPECIFICATIONS.
13. ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36 AT DRY INTERIOR LOCATIONS. ALL
OTHER ANCHOR RODS SHALL CONFORM TO ADHESIVE ANCHOR AND DOWEL NOTES
STEEL NOTES
1. REFER TO STEEL DECK SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. ALL LIGHT GAGE STEEL DECKING AND FLASHING SHALL BE FABRICATED OF SHEET METAL
CONFORMING TO ASTM A446.
3. DECKING SHALL BE GALVANIZED PER COATING DESIGNATION G60 IN ACCORDANCE WITH ASTM
A653, UNLESS NOTED OTHERWISE.
4. EDGE OF PERIMETER CLOSURE SHALL BE HELD WITHIN ±1/2” OF THE DIMENSIONS REQUIRED ON
THE DRAWINGS. CONFIRM THE LOCATION OF THE BEAM CENTERLINES FROM FIXED REFERENCE
EDGE LINES.
5. MINIMUM DECK SECTION PROPERTIES SHALL BE AS FOLLOWS:
GAUGE DEPTH I(IN4) +S(IN3) -S(IN3)
22 1 1/2" 0.178 0.186 0.192
6. PROVIDE #12 SELF DRILLING SCREWS w/ NEOPRENE WASHER @ 12" MAX AT SUPPORTS PARALLEL
TO DECK. SEE DETAIL 8 ON DWG G-006.
STEEL DECK NOTES
1. ADHESIVE FOR ANCHORS AND DOWELS SHALL BE "HILTI HIT-RE 500 V3" ADHESIVE ANCHORS FOR
CONCRETE, AS MANUFACTURED BY HILTI, INC.
2. STAINLESS STEEL THREADED ROD FOR ADHESIVE ANCHORS SHALL CONFORM TO ASTM A193,
GRADE B8M. STAINLESS STEEL NUTS FOR ADHESIVE ANCHORS SHALL CONFORM TO ASTM A194,
GRADE 8M.
3. ANCHORS AND DOWELS SHALL BE INSTALLED IN ACCORDANCE WITH ICC EVALUATION REPORT NO.
3814 FOR CONCRETE.
4. SPECIAL INSPECTION PER CHAPTER 17 OF THE CBC SHALL BE PROVIDED DURING ANCHOR AND
DOWEL INSTALLATION
5. AN ALTERNATIVE ANCHOR PRODUCT MAY BE SUBMITTED TO THE ENGINEER FOR APPROVAL,
PROVIDED THAT IT HAS A CURRENT ICC OR IAPMO EVALUATION REPORT APPROVAL. ALTERNATIVE
ANCHOR PRODUCTS MUST HAVE THE SAME STRENGTH AS THOSE SPECIFIED ON THE PLANS.
6. ALL ABANDONED HOLES SHALL BE FILLED WITH A DRYPACK GROUT WITH A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 5000 PSI. THE FILLED HOLE(S) SHALL BE PREPARED AND CLEANED
AS REQUIRED BY THE GROUT MANUFACTURER.
7. LOCATE EXISTING REINFORCING USING A NON-DESTRUCTIVE METHOD (PACHOMETER OR OTHER), PRIOR TO DRILLING HOLES FOR ANCHORS. MAINTAIN A MINIMUM CLEARANCE OF 1" BETWEEN THE
REINFORCEMENT AND THE ANCHOR.
8. CONCRETE IN WHICH ADHESIVE ANCHORS AND DOWELS ARE INSTALLED SHALL HAVE A MINIMUM
AGE OF 21 DAYS AT TIME OF ANCHOR OR DOWEL INSTALLATION.
POST-INSTALLED ANCHOR AND DOWEL NOTES
1. REINFORCEMENT FOR CONCRETE SHALL BE DEFORMED BARS CONFORMING TO ASTM
SPECIFICATION A615 (A706/A706M FOR WELDED REINFORCING). GRADE 60 STEEL SHALL BE USED
EXCEPT THAT #3 BARS AND SMALLER MAY BE GRADE 40 STEEL.
2. WIRE MESH SHALL CONFORM TO ASTM A1064. LAP 12" WHERE SPLICED.
3. ALL REINFORCEMENT, ANCHOR BOLTS, AND OTHER ANCHORAGES PLACED IN CONCRETE SHALL BE
ACCURATELY PLACED AND POSITIVELY SECURED AND SUPPORTED BY CONCRETE BLOCKS, METAL
CHAIRS, SPACERS, OR METAL HANGERS, AND SHALL BE IN POSITION BEFORE CONCRETE PLACING OR GROUTING IS BEGUN. DETAILING AND PLACING OF BARS SHALL CONFORM TO THE ACI MANUAL
OF STANDARD PRACTICES.
4. BARS SPECIFIED AS "CONTINUOUS" SHALL EXTEND THE FULL LENGTH OF THE MEMBER
CONTAINING THEM AND MAY BE SPLICED (UNLESS NOTED OR SHOWN WITHOUT SPLICES ON THE
PLANS). IN CONCRETE, PROVIDE LAPS PER DETAIL 2 ON DRAWING G-006. STAGGER ALL SPLICES.
5. DOWELS SHALL BE PROVIDED AT ALL POUR JOINTS AND SHALL BE THE SAME SIZE AND SPACING AS
REINFORCING DIRECTLY BEYOND POUR JOINTS.
6. ALL REINFORCING BAR BENDS SHALL BE MADE COLD, UNLESS OTHERWISE PERMITTED BY THE
ENGINEER. REBENDING OF BARS IS NOT PERMITTED.
7. WELDING OF METAL INSERTS AND CONNECTIONS IN REINFORCED CONCRETE CONSTRUCTION
SHALL CONFORM TO ANSI/AWS D1.4-11. USE LOW HYDROGEN E-70 SERIES ELECTRODES FOR
WELDING OF REINFORCING BARS. CONTINUOUS INSPECTION IS REQUIRED OF ALL FIELD WELDING
IN ACCORDANCE WITH CBC CHAPTER 17.
REINFORCING STEEL NOTES
G-003
SENIOR ENGINEER
04/09/2026
04SHEET __ OF __
H. TED GERBER, CITY ENGINEER
DATEENGINEERING DIVISION MANAGER
CITY OF THOUSAND OAKS
DATEDATEREGISTERED ENGINEER
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV. SYMBOL DESCRIPTIONUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
Know what'sbelow.Callbefore you dig.
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
CITY OF THOUSAND OAKS DWG.
3027 TOWNSGATE RD., SUITE 140
WESTLAKE VILLAGE, CA 91361
WWW.AECOM.COM
DWG NO25-024A
PERMANENT DISINFECTION BOOSTING SYSTEMS AT
LA GRANADA (CI 5771), AND LANG RANCH (CI 5791) RESERVOIRS
No. 2582
DAL E. WAH 04/03/2026
DW
TN
DK
04/03/26
04/03/26
04/03/26 STRUCTURAL DESIGN CRITERIA AND ABBREVIATIONS
DESIGN CRITERIA
& AND
@ AT
# NUMBER
Ø DIAMETER
AB ANCHOR BOLT
ABS ANCHOR BOLTS
ACI AMERICAN CONCRETE INSTITUTE
ADJ ADJACENT
AISC AMERICAN INSTITUTE OF STEEL
CONSTRUCTION
AISI AMERICAN IRON AND STEEL INSTITUTE
ALUM ALUMINUM
ALT ALTERNATE
APROX APPROXIMATE
ARCH ARCHITECTURAL
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND
MATERIALS
AWS AMERICAN WELDING SOCIETY
BLKG BLOCKING
BLDG BUILDING
BM BEAM
BOT BOTTOM
BRG BEARING
BS BOTH SIDES
BTWN BETWEEN
C CHANNEL
CALC'S CALCULATIONS
CBC CALIFORNIA BUILDING CODE
CC,C/C CENTER-TO-CENTER
CF CUBIC FOOT
CI CAST-IRON
CJ CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
℄ CENTERLINE
CLG CEILING
CLK(G) CAULK(ING)
CLR CLEAR
CLSM CONTROLLED LOW STRENGTH MATERIAL
CMU CONCRETE MASONRY UNIT
CNJ CONTROL JOINT
CNTR CENTER
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
DBL DOUBLE
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DIV DIVISION
DR DOOR
DWG(S) DRAWINGS
DWL DOWEL
(E) EXISTING
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
EMBED EMBEDMENT
EQ EQUAL
EQUIP EQUIPMENT
ES EACH SIDE
EW EACH WAY
EXP EXPANSION
EXT EXTERIOR
(F) FUTURE
FD FLOOR DRAIN
FDN FOUNDATION
FF FINISH FLOOR
FG FINISHED GRADE
FIN FINISH
FLR FLOOR
SCH SCHEDULE
SECT SECTION
SF SQUARE FOOT
SHT SHEET
SIM SIMILAR
SLH SHORT LEG HORIZONTAL
SLV SHORT LEG VERTICAL
SMS SHEET METAL SCREW
SOG SLAB ON GRADE
SPEC(S) SPECIFICATION(S)
SQ SQUARE
SS, SST STAINLESS STEEL
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURE
STS SELF TAPPING SCREW
SUSP SUSPENDED
SYM/SYMM SYMMETRICAL
SYS SYSTEM
T THICKNESS
T&B TOP AND BOTTOM
TEMP TEMPORARY
THK THICK
TL TOTAL LOAD
TMS THE MASONRY SOCIETY
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TS TOP OF SLAB
TYP TYPICAL
TW TOP OF WALL
UON/ UNO UNLESS OTHERWISE NOTED
UT ULTRASONIC TESTING
(V)/VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W.P. WORKING POINT
W/O WITHOUT
WP WATERPROOF/WORK POINT
WT WEIGHT, STRUCTURAL TEE,
WALL THICKNESS
YD YARD
ABBREVIATIONS
FNDN/FDN FOUNDATION
FO_ FACE OF ______
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FS FINISHED SURFACE
FT FOOT/FEET
FTG FOOTING
GA GAGE/GAUGE
GALV GALVANIZED
GI GALVANIZED IRON
GRD GRADE
GRTG GRATING
HDG HOT DIP GALVANIZED
HDR HEADER
(H)/HORIZ HORIZONTAL
HM HOLLOW METAL
HP HIGH POINT
HSB HIGH STRENGTH BOLT
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
HVAC HEATING,VENTILATION,&AIR CONDITIONING
IBC INTERNATIONAL BUILDING CODE
ICC INTERNATIONAL CODE COUNCIL
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INT INTERIOR
JST JOIST
JT JOINT
KIP 1,000 POUNDS
KSI KIPS PER SQUARE INCH
KCF KIPS PER CUBIC FOOT
∠ ANGLE
LB(S) POUNDS
LB/SF POUND(S) PER SQUARE FOOT
LF LINEAR FOOT
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LLBB LONG LEG BACK-TO-BACK
LONGIT LONGITUDINAL
LP LOW POINT
LW LIGHT WEIGHT
MAS MASONRY
MAT MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MECH MECHANICAL
MIN MINIMUM
MISC MISCELLANEOUS
MFG MANUFACTURER
MO MASONRY OPENING
MTL METAL
(N) NEW
NDT NON-DESTRUCTIVE TEST(ING)
NIC NOT IN CONTACT
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NSG NON-SHRINK GROUT
NTS NOT TO SCALE
OC ON CENTERS
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OH OPPOSITE HAND, OVERHEAD
OPNG(S) OPENING(S)
OPP OPPOSITE
PCF POUNDS PER CUBIC FOOT
PCI POUNDS PER SQUARE INCH PER INCH OF DEFORMATION
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PLF POUNDS PER LINEAL FOOT
PNL PANEL
PREFAB PREFABRICATED
PP PARTIAL PENETRATION
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT(S) POINT(S)
PVC POLYVINYL CHLORIDE
R, RAD RADIUS
RD ROOF DRAIN
RECT RECTANGLE, RECTANGULAR
REF REFERENCE
REINF REINFORCING, REINFORCEMENT
REQ'D REQUIRED
REV REVISION
G-004
SENIOR ENGINEER
04/09/2026
05SHEET __ OF __
H. TED GERBER, CITY ENGINEER
DATEENGINEERING DIVISION MANAGER
CITY OF THOUSAND OAKS
DATEDATEREGISTERED ENGINEER
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV. SYMBOL DESCRIPTIONUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
Know what'sbelow.Callbefore you dig.
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
CITY OF THOUSAND OAKS DWG.
3027 TOWNSGATE RD., SUITE 140
WESTLAKE VILLAGE, CA 91361
WWW.AECOM.COM
DWG NO25-024A
PERMANENT DISINFECTION BOOSTING SYSTEMS AT
LA GRANADA (CI 5771), AND LANG RANCH (CI 5791) RESERVOIRS
No. 2582
DAL E. WAH 04/03/2026
DW
TN
DK
04/03/26
04/03/26
04/03/26 SPECIAL INSPECTIONS AND STRUCTURAL OBSERVATIONS
SPECIAL INSPECTIONS NOTES -
APPLIES TO ALL CHECKLISTS
THE SPECIAL INSPECTIONS LISTED ARE IN ADDITION TO THE CALLED INSPECTIONS
REQUIRED BY CBC 2025 CHAPTER 1 SECTION 110. THE SPECIAL INSPECTIONS
IDENTIFIED ON PLANS ARE IN ADDITION TO, AND NOT A SUBSTITUTE FOR, THOSE
INSPECTIONS REQUIRED TO BE PERFORMED BY THE GOVERNING JURISDICTION'S
BUILDING INSPECTOR. THE GOVERNING JURISDICTION IS DEFINED AS THE CITY,
COUNTY, OR GOVERNMENTAL UNIT THAT IS RESPONSIBLE FOR THE INSPECTIONS
OF CONSTRUCTION OR WORK AS SPECIFIED IN THE CONTRACT DOCUMENTS.
SPECIAL INSPECTIONS REQUIRED FOR THIS PROJECT SHALL BE PERFORMED IN
ACCORDANCE WITH CBC CHAPTER 17. SPECIAL INSPECTIONS SHALL BE
PERFORMED BY AN APPROVED INSPECTION AGENCY U.N.O, EMPLOYED BY THE
OWNER AND VENTURA COUNTY FIRE DEPARTMENT INSPECTOR.
THE SPECIAL INSPECTOR SHALL BE CERTIFIED BY THE INTERNATIONAL CODE
COUNCIL (ICC) TO PERFORM INSPECTION FOR THE PARTICULAR TYPE OF
CONSTRUCTION OR OPERATION REQUIRING SPECIAL INSPECTION PRIOR TO THE
COMPLETION OF THAT PHASE OF THE WORK.
THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE BUILDING
OFFICIAL AND/OR THE ENGINEER. ALL DISCREPANCIES SHALL BE BROUGHT TO THE
IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION, THEN, IF
UNCORRECTED, TO THE STRUCTURAL ENGINEER AND TO THE BUILDING OFFICIAL.
THE SPECIAL INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING
WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE
INSPECTOR'S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND
SPECIFICATIONS AND THE APPLICABLE WORKMANSHIP PROVISIONS OF THIS CODE.
IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY TO PROVIDE AT LEAST 48
HOURS ADVANCE NOTICE TO THE OWNER/OWNER'S REPRESENTATIVE WHEN HIS
WORK IS READY FOR ANY REQUIRED SPECIAL INSPECTIONS.
SHOP INSPECTION OF STEEL CONSTRUCTION IS NOT REQUIRED WHEN THE WORK IS
DONE ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED TO
PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION. APPROVAL SHALL BE BASED
UPON REVIEW OF THE FABRICATOR'S WRITTEN PROCEDURAL AND QUALITY
CONTROL MANUALS AND PERIODIC AUDITING OF FABRICATION PRACTICES BY AN
APPROVED SPECIAL INSPECTION AGENCY. AT COMPLETION OF FABRICATION, THE
APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE
BUILDING OFFICIAL STATING THAT THE WORK WAS PERFORMED IN ACCORDANCE
WITH THE APPROVED CONSTRUCTION DOCUMENTS.
CONTRACTOR RESPONSIBILITY
EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND- OR
SEISMIC-FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM OR A WIND- OR
SEISMIC-RESISTING COMPONENT LISTED IN THE STATEMENT OF SPECIAL
INSPECTIONS SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE
BUILDING OFFICIAL AND THE OWNER PRIOR TO THE COMMENCEMENT OF WORK ON
THE SYSTEM OR COMPONENT. THE CONTRACTOR'S STATEMENT OF
RESPONSIBILITY SHALL CONTAIN ACKNOWLEDGMENT OF AWARENESS OF THE
SPECIAL REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTION.
OWNER OR OWNER'S REPRESENTATIVE SHALL BE SYNONYMOUS WITH 'BUILDING
OFFICIAL' IN THE FOREGOING IF THE PROJECT IS NOT UNDER THE JURISDICTION OF
A BUILDING DEPARTMENT.
SPECIAL INSPECTION SHALL BE PROVIDED FOR THE FOLLOWING TYPES OF WORK
PERFORMED IN THE FIELD, OR NOT PERFORMED IN AN APPROVED FABRICATION
SHOP AS DEFINED ABOVE, UNLESS NOTED AS "N/A".
CONTINUOUS AND PERIODIC INSPECTIONS:
1. WHERE CONTINUOUS SPECIAL INSPECTION IS REQUIRED, THE SPECIAL
INSPECTOR SHALL CONTINUOUSLY PROVIDE FULL-TIME VERIFICATION OF THE
WORK.
2. WHERE PERIODIC SPECIAL INSPECTION IS REQUIRED, THE SPECIAL INSPECTOR
SHALL PROVIDE VERIFICATION THAT THE PERIODIC INSPECTION WAS
PERFORMED.
MAIN WIND- OR SEISMIC-FORCE-RESISTING SYSTEMS, DESIGNATED SEISMIC
SYSTEMS, AND SEISMIC-RESISTING COMPONENTS SUBJECT TO SPECIAL
INSPECTIONS
- FOR ACTIVE MECHANICAL AND ELECTRICAL EQUIPMENT THAT MUST REMAIN
OPERABLE FOLLOWING THE DESIGN EARTHQUAKE GROUND MOTION,
INSPECTION/VERIFICATION THAT THE LABEL, ANCHORAGE AND MOUNTING
CONFORM TO THE CERTIFICATE OF COMPLIANCE
- PERIODIC SPECIAL INSPECTION FOR INSTALLATION OF ELECTRICAL
EQUIPMENT ANCHORAGE
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION:
CONTINUOUS
INSPECTION
PERIODIC
INSPECTION
1. INSPECTION OF REINFORCING STEEL, INCLUDING PLACEMENT.
2. INSPECTION OF REINFORCING STEEL WELDING IN ACCORDANCE WITH TABLE
1705.3
3. INSPECT ANCHORS CAST IN CONC, PRIOR TO AND DURING PLACEMENT OF
CONCRETE
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS.
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED
IN 4.A.
5. VERIFY USE OF REQUIRED DESIGN MIX.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES
10. VERIFY IN-SITU CONCRETE STRENGTH, PRIOR TO REMOVAL OF SHORES
AND FORMS FROM BEAMS AND STRUCTURAL SLABS.
11. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
REQUIRED VERIFICATION AND INSPECTION OF SOILS:
CONTINUOUS
INSPECTION
PERIODIC
INSPECTION
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE THE
DESIGN BEARING CAPACITY.
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER
MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF COMPACTED FILL.
5. PRIOR TO PLACEMENT OF COMPACTED FILL, OBSERVE SUBGRADE AND VERIFY THAT SITE
HAS BEEN PREPARED PROPERLY.
9. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS
N/A
N/A
STEEL CONSTRUCTION (STRUCTURAL STEEL):
P O
1. INSPECTION TASKS PRIOR TO WELDING
A. WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE
B. MANUFACTURERS CERTIFICATIONS FOR WELDING CONSUMABLES
AVAILABLE
C. MATERIAL IDENTIFICATION (TYPE/GRADE)
D. WELDER IDENTIFICATION SYSTEM
E. FIT-UP OF GROOVE WELDS (INCLUDING GEOMETRY)
· JOINT PREPARATION
· DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
· CLEANLINESS (CONDITION OF STEEL SURFACES)
· TACKING (TACK WELD QUALITY AND LOCATION)
· BACKING TYPE AND FIT (IF APPLICABLE)
F. CONFIGURATION AND FINISH OF ACCESS HOLES
G. FIT-UP OF FILLET WELDS
· DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
· CLEANLINESS (CONDITION OF STEEL SURFACES)
· TACKING (TACK WELD QUALITY AND LOCATION)
2. INSPECTION TASKS DURING WELDING
O - OBSERVE THESE ITEMS ON A RANDOM BASIS, OPERATIONS NEED NOT BE DELAYED
PENDING THESE INSPECTIONS
P - PERFORM THESE TASKS FOR EVERY LOCATION
A. USE OF QUALIFIED WELDERS
B. CONTROL AND HANDLING OF WELDING CONSUMABLES
· PACKAGING
· EXPOSURE CONTROL
C. NO WELDING OVER CRACKED TACK WELDS
D. ENVIRONMENTAL CONDITIONS
· WIND SPEED WITHIN LIMITS
· PRECIPITATION AND TEMPERATURE
E. WPS FOLLOWED
· SETTINGS ON WELDING EQUIPMENT
· TRAVEL SPEED
· SELECTED WELDING MATERIALS
· SHIELDING GAS TYPE/FLOW RATE
· PREHEAT APPLIED
· INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
· PROPER POSITION (F, V, H, OH)
F. WELDING TECHNIQUES
· INTERPASS AND FINAL CLEANING
· EACH PASS WITHIN PROFILE LIMITATIONS
· EACH PASS MEETS QUALITY REQUIREMENTS
1. OFF-SITE FABRICATION:
FABRICATORS SHALL BE CITY, COUNTY AND/OR CBC APPROVED FABRICATORS.
FABRICATORS FOR ALL OFF-SITE FABRICATION OF THE ITEMS LISTED BELOW:
A. TRUSSES
B. GLU-LAMINATED MEMBERS
C. PRECAST CONCRETE
D. STRUCTURAL STEEL (MILL REPORTS AND IDENTIFICATION OF STEEL, AFFIDAVIT OF
COMPLIANCE)
E. OTHER: _________________________
2. DEFERRED SUBMITTALS:
SUBMITTAL DOCUMENTS FOR THE DEFERRED SUBMITTAL ITEMS LISTED BELOW SHALL
BE DESIGNED BY A PE OR SE LICENSED IN THE STATE OF CALIFORNIA AND SUBMITTED
BY THE CONTRACTOR TO THE CITY AND STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR
DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE CITY.
A. PROCESS TANK ANCHORAGE
B. CONCRETE MIX
C. OTHER:
YES NO
REQUIRED
( ) N/A
G-005
DEFERRED SUBMITTALS / CERTIFICATIONS
* CONTRACTOR TO PROVIDE ANCHORAGE CALCULATIONS IN ACCORDANCE
WITH ACI 318, CHAPTER 17.
DATEENGINEERING DIVISION MANAGER
CITY OF THOUSAND OAKS
REVIEWED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
SENIOR ENGINEER
04/09/2026
Shamir Shahamiri 04/09/2026
CONTINUOUS
INSPECTION
PERIODIC
INSPECTION
SENIOR ENGINEER
04/09/2026
3. INSPECTION TASKS AFTER WELDING
4. INSPECTION TASKS PRIOR TO BOLTING
A. WELDS CLEANED
B. SIZE, LENGTH, AND LOCATION OF WELDS
C. WELDS MEET VISUAL ACCEPTANCE CRITERIA
· CRACK PROHIBITION
· WELD/BASE-METAL FUSION
· CRATER CROSS SECTION
· WELD PROFILES
· WELD SIZE
· UNDERCUT
· POROSITY
D. ARC STRIKES
E. K-AREA
· WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS
BEEN PERFORMED IN THE K-AREA, VISUALLY INSPECT THE WEB K-AREA FOR CRACKS
WITHIN 3 IN. (75MM) OF THE WELD
F. BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)
G. REPAIR ACTIVITIES
H. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER
A. MANUFACTURER'S CERTIFICATION AVAILABLE FOR FASTENER MATERIAL
B. FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS
C. PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE)
D. PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL
E. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE
REQUIREMENTS
F. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL
OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED
G. PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER FASTENER
COMPONENTS
5. INSPECTION TASKS DURING BOLTING
A. FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND
WASHERS (IF REQUIRED) ARE POSITIONED AS REQUIRED
B. JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING
OPERATION
C. FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING
D. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION,
PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE
EDGES
6. INSPECTION TASKS AFTER BOLTING
A. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS
7. INSPECTION OF STEEL ELEMENTS OF COMPOSITE CONSTRUCTION PRIOR
TO CONCRETE PLACEMENT
A. PLACEMENT AND INSTALLATION OF STEEL DECK
B. PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS
C. DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS
STEEL CONSTRUCTION (OTHER THAN STRUCTURAL STEEL)
1. MATERIAL VERIFICATION OF COLD-FORMED STEEL DECK
A. IDENTIFICATION MARKINGS TO CONFORM TO ASTM STANDARDS
SPECIFIED IN THE APPROVED CONSTRUCTION DOCUMENTS
B. MANUFACTURER'S CERTIFIED TEST REPORTS
2. INSPECTION OF WELDING IN ACCORDANCE WITH AWS D1.3 AND SDI QA/QC
A. COLD-FORMED STEEL DECK
· FLOOR AND ROOF DECK WELDS
CONTINUOUS
INSPECTION
PERIODIC
INSPECTION N/A
1. OFF-SITE FA
FABRICATO
FABRICATO
A. TRUSS
B. GLU-LA
C. PRECA
D. STRUC
COMPL
E. OTHER
2. DEFERRED
SUBMITTAL
BE DESIGNE
BY THE CON
APPROVAL.
DESIGN AND
A. PROCE
B. CONCR
C. OTHER
DEFERRED SUBM
* CONTRAC
WITH ACI 31
STEEL CONSTRUCTION (STRUCTURAL STEEL) CONTINUED:
P O
O - OBSERVE THESE ITEMS ON A RANDOM BASIS, OPERATIONS NEED NOT BE DELAYED
PENDING THESE INSPECTIONS
P - PERFORM THESE TASKS FOR EVERY LOCATION
CONCRETE REINFORCING LAP SPLICE SCHEDULE
BAR
f'c = 2500 f'c = 3000 f'c = 4000 f'c = 4500
L (inches) L (inches) L (inches) L (inches)
3 24 22 19 18
4 32 29 25 24 5 39 36 31 30
6 47 43 37 35
7 69 63 54 51
8 78 72 62 59
9 88 81 70 66
"L"NOTES:
1. LAPS SHOWN IN THIS TABLE ARE CLASS B, CATEGORY 3 TYPE SPLICES. LAP LENGTH IS BASED UPON
SMALLER OF TWO BARS BEING SPLICED WHEN NOT THE SAME SIZE.
2. INCREASE LAP LENGTHS BY A FACTOR OF 1.3 FOR HORIZONTAL REINFORCEMENT SO PLACED THAT
MORE THAN 12 INCHES OF CONCRETE IS CAST IN THE MEMBER BELOW THIS REINFORCEMENT
d d
O R
1' 0"
M
IN
4d OR
2.5" MIN.
D d
1- 1/
2d C
LE
AR
O R
W
IR
E
TI
E
TO
G
ET
H
ER
LAP PER DETAIL 2 HEREON
6d OR 3" MIN. d
4d (#3, #4, #5)
6d (36, #7, #8)
90° BEND 180° HOOK
LAP AND OFFSET STIRRUP OR TIE
D = 8d FOR #9 AND LARGER D = 6d FOR #8 AND SMALLER BARS
135° HOOK
D
DOUBLE LAYER OF REINFORCEMENT
SINGLE LAYER OF REINFORCEMENT
INTERSECTIONCORNER ALT. CORNER
INTERSECTIONCORNER ALT. CORNER
LA
P
PE
R
D
ET
AI
L
2/
CONT. CONST. JOINT w/
BEVELED SHEAR KEY
(CONC. WALLS ONLY) TYP.
1" TYP.
VERTICAL
REINFORCEMENT
1" T
YP
LAP PER
DETAIL 2/-
REINFORCEMENT @ ℄ OF
WALL UNLESS NOTED
OTHERWISE
1" TYP.
LA
P
PE
R
D
ET
AI
L
2/
LAP PER
DETAIL 2/- 1"
T
YP
VERT. REINF. (EXCEPT
FOR TILT-UP CONST.
LAP PER
DETAIL 2/-
1" TYP.CLEARANCE AS
NOTED IN GEN.
STRUCT. NOTES
LA
P
PE
R
D
ET
AI
L
2/
LAP PER
DETAIL 2/-1"
T
YP
LA
P
PE
R
D
ET
AI
L
2/
METAL ROOF DECK
HSS4x4 BEAM PER PLAN
1/4
HSS4x4 BEAM PER PLAN
1/4PVC CLAD
METAL
FLASHING
OVERHANG ROOF DECK
6" LOW SIDE OF ROOF
2" HIGH SIDE OF ROOF
2" ALL OTHER SIDES
18ga METAL
FASCIA
STANDING SEAM
METAL ROOF
OSB OVER METAL
ROOF DECK
TOP OF STEEL
METAL ROOF DECK
ATTACH WITH HILTI SCREW S-SLC 01 OR
S-SLC 02 SIDELAP CONNECTION @ 18"
CONCRETE CONTAINMENT
SLAB - SEE PLAN FOR TYP
REINF
1' -4
M
IN
#4 @ 12"
#5 TYP
8"
HSS4x4 CANOPY
POST PER PLAN
METAL ROOF DECK - SEE
DETAIL 8 FOR ATTACHMENT
1/4" THICK END
PLATE
HSS4x4 BEAM PER PLAN
HSS4x4 BRACE PER PLAN
2'-0"
2' -0
1/4
TYP @ INSIDE
EDGES
1/4
TYP @ OUTSIDE
EDGES
CENTERED ON
CURB WIDTH
ROOF DECK OVERHANG - SEE
DETAIL 7 (WHERE OCCURS)
4 - #12 SELF DRILLING SCREWS w/ NEOPRENE
WASHER PER 35" DECK PANEL (36/4 PATTERN)
STANDING SEAM METAL ROOF -
SEE ARCHITECTURAL DRAWINGS
OSB - ATTACH WITH #10 FLAT HEAD SELF
DRILLING SCREWS @ 12" AT PANEL EDGES
AND @ 12" EACH WAY FIELD SPACING
18ga METAL FASCIA
NOTE: FOR DECK ATTACHMENT AT SUPPORTS PARALLEL TO DECK, SEE STEEL
DECK NOTES ON DWG G-003
STANDING SEAM
METAL ROOF
OSB OVER METAL
ROOF DECK
TOP OF STEEL
CONCRETE CONTAINMENT
SLAB - SEE PLAN FOR TYP
REINF
HSS4x4 CANOPY POST PER PLAN
HSS5x5x3/16 SLEEVE w/ 1/4" THICK END
PLATE, EMBED 18"
#5 @ 12"
FILL ANNULAR SPACE w/ NONSHRINK
GROUT - PROVIDE CROWN AT TOP
TO SLOPE AWAY FROM POST
1' -4
M
IN
1'-4"
#4 EACH
SIDE OF POST
#5 CONT
(N) CURB AT LA GRANADA
(E) CURB AT LANG RANCH
7'-10"
3' -0
3'-0"
(N) CONCRETE PAD
(E) CONCRETE SLAB
SECTION APLAN
(N) EQUIPMENT SKID
3" C
LR
3" CLR
(N) CONCRETE
PAD
#5 @ 12" MAX
(E) CMU WALL
(E) CMU WALL
2' -0
8"
#5 @ 10"
#5 @ 10" TYP
1/2" THK EXP JT FILLER
#5
1/4" THK JOINT SEALANT
AT TOP AND ENDS OF PAD
PERIMETER DOWELS SET IN
EPOXY ADHESIVE (5" EMBED)
VARIES - SEE PLAN
2' -4
2'-4"
M
AT
C H
(E
C O
N C
R
ET
E
PA
D (W
H
ER
E O
C C
U R
S) O
R 2'
-0
(N) CONCRETE PAD
(E) AC PAVEMENT - SAWCUT AND
REMOVE AS REQUIRED, REPLACE
IN-KIND
SECTION APLAN
EQUIPMENT
SEE DWG C-002
2" C
LR
2" CLR
3" C
LR
(N) CONCRETE
PAD
#5 @ 12" MAX
EACH WAY
(E) CMU WALL
(E) CONCRETE PAD
(WHERE OCCURS)
ONE LAYER 15 LB BUILDING
PAPER BETWEEN CONCRETE
AND CMU
4"
(E) CMU WALL
(E) FTG
#5 @ 12" MAX
EACH WAY
3" C
LR
A
A
1/2" THK EXP
JT FILLER
DRILL AND EPOXY DOWELS INTO (E)
CONCRETE PAD WHERE OCCURS (6"
EMBED) - SEE POST-INSTALLED
DOWEL NOTES ON DWG G-003
(E) AC
06G-006
TYPICAL STRUCTURAL DETAILS
1 TYPICAL BAR BENDS
Scale: NTS
2 TYPICAL CONCRETE LAP SPLICE SCHEDULE
Scale: NTS 4 TYPICAL CANOPY POST EMBEDMENT
Scale: 1" = 1'-0"
5 TYPICAL CONCRETE CURB
Scale: 1 1/2" = 1'-0"
6 TYPICAL BEAM TO COLUMN CONNECTION
Scale: 1 1/2" = 1'-0"
7 TYPICAL BEAM TO BEAM CONNECTION
Scale: 3" = 1'-0"
8 TYPICAL METAL DECK CONNECTION
Scale: NTS
3 TYPICAL REBAR AT CORNERS AND INTERSECTIONS
Scale: NTS
SHEET __ OF __
CITY OF THOUSAND OAKS
H. TED GERBER, CITY ENGINEER
DATEENGINEERING DIVISION MANAGER
CITY OF THOUSAND OAKS
DATEDATEREGISTERED ENGINEER
DATE
CHECKED
DATE
DATE
DESIGNED
DRAFTED BY
PREPARED BY
C.T.O.DATER.C.E. DATEREV. SYMBOL DESCRIPTIONUNDERGROUND SERVICE ALERT OF SOUTHERN CALIFORNIA
Know what'sbelow.Callbefore you dig.
CALL 811
AT LEAST TWO DAYS
BEFORE YOU DIG REVIEWED BY:
APPROVED BY:
DATEPROJECT ENGINEER
REVIEWED BY:
CITY OF THOUSAND OAKS DWG.
3027 TOWNSGATE RD., SUITE 140
WESTLAKE VILLAGE, CA 91361
WWW.AECOM.COM
DWG NO25-024A
No. 2582
DAL E. WAH 04/03/2026
PERMANENT DISINFECTION BOOSTING SYSTEMS AT
LA GRANADA (CI 5771) RESERVOIRS
DW
TN
DK
04/03/26
04/03/26
04/03/26
9 CONCETE EQUIPMENT PAD AT LANG RANCH
Scale: 3/4" = 1'-0"
10 CONCETE EQUIPMENT PAD AT LA GRANADA
Scale: 3/4" = 1'-0"
SENIOR ENGINEER
04/09/2026
PIPING LEGEND
EXISTING PIPE
PROPOSED PIPE
EXISTING PIPE (BELOW GROUND)
PROPOSED PIPE (BELOW GROUND)
EXISTING VALVE
PROPOSED VALVE
EXISTING PUMP
PROPOSED PUMP
EXISTING VAULT
PROPOSED VAULT
EXISTING TANK
PROPOSED TANK
GENERAL NOTES
1. PROVIDE PIPING SUPPORTS AS REQUIRED PER SPECIFICATIONS AND DETAILS.
2. ALL MATERIALS SHALL BE RESISTANT TO THE CHEMICALS STORED AND CONVEYED.
3. PROVIDE ALL SAFETY SIGNAGE REQUIRED FOR THE CHEMICALS STORED AND CONVEYED.
4. SEE SPECIFICATIONS FOR PIPING SYSTEMS MATERIALS, LINING, COATING AND DESIGN REQUIREMENTS.
5. WHEN EQUIPMENT IS NOTED AS "TYP OF X", "X" DESIGNATES THE TOTAL QUANTITY OF THAT EQUIPMENT FOR
THAT AREA BUILDING.
6. SIZE OF FITTINGS SHOWN ON PLANS SHALL CORRESPOND TO ADJACENT STRAIGHT RUN OF PIPE, UNLESS OTHERWISE INDICATED. TYPE OF JOINT AND FITTING MATERIAL SHALL BE THE SAME AS SHOWN FOR
ADJACENT RUN OF PIPE.
7. NOT ALL THE REQUIRED FITTINGS ARE SHOWN ON THE DRAWINGS. CONTRACTOR SHALL PROVIDE FITTINGS SHOWN ON DRAWINGS AND ANY ADDITIONAL FITTINGS AS REQUIRED BY PIPING ARRANGEMENTS SHOWN ON
DRAWINGS AND PER EQUIPMENT FURNISHED.
8. LAY PIPE TO UNIFORM GRADE BETWEEN INDICATED PIPE ELEVATIONS.
9. CONTRACTOR SHALL ADD IDENTIFICATION LABELS TO ALL CHEMICAL CONTAINMENT PIPING PER SECTION 15 15 10.
10. ON CHEMICAL PIPING PROVIDE UNIONS AT PIPE CONNECTIONS AND AT INSTRUMENT/VALVES/EQUIPMENT
LOCATIONS TO FACILITATE CONVENIENT REMOVAL OF INSTRUMENTS/VALVES/EQUIPMENT.
11. ALL EQUIPMENT AND MATERIALS SHALL BE AS APPROVED BY THE CITY AND IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS, UNLESS OTHERWISE NOTED.
12. ALL FLEXIBLE CONNECTORS OR FLANGED COUPLING ADAPTERS SHALL BE PROVIDED WITH THRUST TIES, BLOCK, OR ANCHORS, UNLESS OTHERWISE NOTED. THRUST PROTECTION SHALL BE ADEQUATE FOR TEST
PRESSURES SPECIFIED.
13. ALL PIPE PENETRATIONS THROUGH FIRE RATED WALLS OR FLOORS SHALL REQUIRE FIRESTOPPING.
14. THE CONTRACTOR SHALL VERIFY SUCTION AND DISCHARGE CONTAINMENT PIPING/CARRIER TUBING ARE
INSTALLED AND SUPPORTED TO PREVENT IMPARTING ANY STRAIN ON THE PUMPS.
15. PROVIDE WARNING SIGNS PER SPECIFICATIONS ON THE FRONT AND BACK OF ALL REMOTELY CONTROLLED
EQUIPMENT.
16. MOUNT ALL VALVES AND MANUAL VALVE OPERATORS IN ACCESSIBLE LOCATIONS WITH UNOBSTRUCTED
VALVE OPERATOR POSITION FOR EASE OF OPERATION.
17. NOT ALL INSTRUMENTATION AND ELECTRIC MOTOR VALVE OPERATORS ARE SHOWN ON THE MECHANICAL DRAWINGS. REFER TO ELECTRICAL AND INSTRUMENTATION DRAWINGS FOR INSTRUMENT AND VALVE
OPERATOR LOCATIONS AND DETAILS.
18. IN CASE OF CONFLICT BETWEEN DRAWINGS AND SPECIFICATIONS,…