Building 154 UPS replacement drawing set_2024.pdf
PDF 16 MB Posted
- Attached to
- Building 154 UPS Replacement Federal contract opportunity
- Solicitation number
- 12505B24Q0055
About this file
This document is a Request for Proposal (RFP) for the replacement of the Uninterruptible Power Supply (UPS) system in Building 154 in Ames, Iowa, issued by the United States Department of Agriculture (USDA), Agricultural Research Service (ARS).
The project scope requires the contractor to provide all labor, materials, and equipment to perform the UPS replacement work. The estimated construction value is between $100,000 and $250,000, with a period of performance of 150 calendar days after the Notice to Proceed. A site visit is scheduled for May 13, 2024, and quotes are due on June 3, 2024 by 5:00 PM Eastern Time. This is a Total Small Business Set-Aside procurement under NAICS code 238210, with a small business size standard of $19.0 Million. The acquisition will result in a single award firm-fixed price contract. Offerors must be registered in the System for Award Management (SAM) database to be eligible for award.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and Answers.pdf | ||
| ARS-372.pdf | ||
| Statement of Work.pdf | ||
| ARS-371.pdf | ||
| Wage Determination.pdf | ||
| Past Performance Questionnaire.pdf | ||
| SF18 12505B24Q0055.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Location Coordinator:Contracting Officer Rep.:Contracting Officer:Engineering Project Manager:
Task
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
UNITED STATES DEPARTMENT OF AGRICULTURE
AGRICULTURE RESEARCH SERVICE
NATIONAL CENTERS FOR ANIMAL HEALTH
INDEX OF DRAWINGS
P02
Title Page
Building 154 layout
P03
P04
Electrical panel locations
P01
UPS Room layout
P06
One line diagrams
E-PP-3 Panel Details
P07
P08
E-PP-1 Panel Details
P05
Existing UPS details
P10
Existing UPS data plates
Maintenance Bypass Switch
P11 Existing UPS internal
P09
Construction Area
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
Title Page
11/1/2023
Brandon Keith P01
22002 1 11
Building 154 UPS replacement project
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
Building 154 layout
11/1/2023
Brandon Keith P02
22020 2 11
NORTH
UPS Room located upstairs above break room
Chiller Room
Garage Door
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
Electrical Panel Locations
11/1/2023
Brandon Keith P03
22002 3 11
UPS Panel E-PP-3
Panel E-PP-1
Control Room
Office
Break Room
NORTH
Approximate location of UPS room above.
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
UPS room layout
11/1/2023
Brandon Keith P04
22002 4 11
NORTH
Existing Toshiba UPSs
Existing Maintenance Bypass Switch
Replace per SOW
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
One line diagrams
11/1/2023
Brandon Keith P05
22002 5 11
UPS Panel
Existing UPS System
Upgrade to a 100A.
60A Disconnect switch
External Maintenance Bypass
12X12 Junction
Box
Left UPS Right UPS
SW2 SW1
N.C.
N.C.
N.O.
Maintenance Bypass
UPS Output Isolation
Fr om
P an el E
-P P-
Fe ed s P an el E
-P P-
Wires are spliced here
Wires are NOT spliced here
Boiler E-Stop one line
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
E-PP-3 Panel Details
11/1/2023
Brandon Keith P06
22002 6 11
E-PP-3 UPS Panel 1 Control Room Receptacles - South wall receptacles for the monitors Control Room Receptacles - North side receptacles under the counter top. 2
3 Control Room Receptacles - South wall receptacles for the monitors
Control Room Receptacles - North side receptacles under the counter top. 4
5 Control Room Receptacles - South wall receptacles for the monitors
Control Room Receptacles - North side receptacles under the counter top. 6
7 Fuel Oil Transmitter Basin Level Transmitter 8
9 Fuel Oil Leak Detection - PAL-AT in control room SPARE 10
11 TCP-17 (JCI Panel) lower 120V power PPW Leak Detection, LIQUIDWATCH II, control room wall 12
13 Server Room Receptacles, Double Duplex on top of racks
TCP-11 (JCI Panel) Chiller MCC room TCP- 2 (JCI Panel) Chiller Plant MCC wall 14
15 Server Room Receptacles, Double Duplex on top of racks
TCP-3 (JCI Panel) Chiller Plant MCC wall TCP-4 (JCI Panel) Chiller Plant MCC wall 16
17 Server Room Receptacles, Double Duplex on top of racks
TCP-5 (JCI Panel) Chiller Plant MCC wall TCP-6 (JCI Panel) Chiller Plant MCC wall 18
19 Server Room Receptacles, Double Duplex on top of racks
NAE 11?(JCI Panel), Mezzanine, 20
21 TCP-10, (JCI Panel) Mezzanine TCP-7 (JCI Panel), Chiller Plant wall
Lenel Security Panels, Server Room 22
23 TCP-17 (JCI Panel), Chiller Plant wall, Main 120V power TCP-9 (JCI Panel) Chiller Plant wall.
CHW-CH (JCI Panel), Fire pump room, back wall 24
25 NAE01-07, Mezzanine, Metasys Supervisory Controller
208V Receptacle, Ceiling of Server Room
27 SPARE 28
29 SPARE Unit Ventilator #2 and #3 TCP (JCI Panel), Boiler MCC Room 30
31 SPARE CP-TCP-32 (JCI Panel), hallway outside air compressor room 32
33 SPARE
208V Receptacle, Ceiling of Server Room
35 Emergency Stop for Boilers 36
Panel E-PP-3 To be upgraded to a 100A
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
E-PP-1 Panel Details
11/1/2023
Brandon Keith P07
22002 7 11
E-PP-1
E-PP-1
E-PP-1
Data
Plate
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
Existing UPS details
11/1/2023
Brandon Keith P08
22020 8 11
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
Existing UPS data plates
11/1/2023
Brandon Keith P09
22002 9 11
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
Maintenance Bypass Switch
11/1/2023
Brandon Keith P10
22002 10 11
Order #:
Drawing Title:PROJECT TITLE:
FEU Project #:
Drawing Number:
Agricultural Research Service U.S. Department of Agriculture
NCAH
1920 Dayton Avenue Ames, Iowa 50010
Revision:
Client:
Sheet: Of
Designer:
Date:
Date:
Ben A'Hearn TBD Brandon Keith
Building 154 UPS replacement project
Existing UPS internal
11/1/2023
Brandon Keith P11
22002 11 11
File details come from the government source that posted it. Updated .