Building 154 UPS replacement drawing set_2024.pdf

PDF 16 MB Posted

Attached to
Building 154 UPS Replacement Federal contract opportunity
Solicitation number
12505B24Q0055
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Midwest Area

About this file

This document is a Request for Proposal (RFP) for the replacement of the Uninterruptible Power Supply (UPS) system in Building 154 in Ames, Iowa, issued by the United States Department of Agriculture (USDA), Agricultural Research Service (ARS).

The project scope requires the contractor to provide all labor, materials, and equipment to perform the UPS replacement work. The estimated construction value is between $100,000 and $250,000, with a period of performance of 150 calendar days after the Notice to Proceed. A site visit is scheduled for May 13, 2024, and quotes are due on June 3, 2024 by 5:00 PM Eastern Time. This is a Total Small Business Set-Aside procurement under NAICS code 238210, with a small business size standard of $19.0 Million. The acquisition will result in a single award firm-fixed price contract. Offerors must be registered in the System for Award Management (SAM) database to be eligible for award.

View the file

Other files for this federal contract opportunity

Other files attached to Building 154 UPS Replacement, newest first.
File Type Posted
Questions and Answers.pdf PDF
ARS-372.pdf PDF
Statement of Work.pdf PDF
ARS-371.pdf PDF
Wage Determination.pdf PDF
Past Performance Questionnaire.pdf PDF
SF18 12505B24Q0055.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Location Coordinator:Contracting Officer Rep.:Contracting Officer:Engineering Project Manager:

Task

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

UNITED STATES DEPARTMENT OF AGRICULTURE

AGRICULTURE RESEARCH SERVICE

NATIONAL CENTERS FOR ANIMAL HEALTH

INDEX OF DRAWINGS

P02

Title Page

Building 154 layout

P03

P04

Electrical panel locations

P01

UPS Room layout

P06

One line diagrams

E-PP-3 Panel Details

P07

P08

E-PP-1 Panel Details

P05

Existing UPS details

P10

Existing UPS data plates

Maintenance Bypass Switch

P11 Existing UPS internal

P09

Construction Area

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

Title Page

11/1/2023

Brandon Keith P01

22002 1 11

Building 154 UPS replacement project

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

Building 154 layout

11/1/2023

Brandon Keith P02

22020 2 11

NORTH

UPS Room located upstairs above break room

Chiller Room

Garage Door

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

Electrical Panel Locations

11/1/2023

Brandon Keith P03

22002 3 11

UPS Panel E-PP-3

Panel E-PP-1

Control Room

Office

Break Room

NORTH

Approximate location of UPS room above.

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

UPS room layout

11/1/2023

Brandon Keith P04

22002 4 11

NORTH

Existing Toshiba UPSs

Existing Maintenance Bypass Switch

Replace per SOW

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

One line diagrams

11/1/2023

Brandon Keith P05

22002 5 11

UPS Panel

Existing UPS System

Upgrade to a 100A.

60A Disconnect switch

External Maintenance Bypass

12X12 Junction

Box

Left UPS Right UPS

SW2 SW1

N.C.

N.C.

N.O.

Maintenance Bypass

UPS Output Isolation

Fr om

P an el E

-P P-

Fe ed s P an el E

-P P-

Wires are spliced here

Wires are NOT spliced here

Boiler E-Stop one line

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

E-PP-3 Panel Details

11/1/2023

Brandon Keith P06

22002 6 11

E-PP-3 UPS Panel 1 Control Room Receptacles - South wall receptacles for the monitors Control Room Receptacles - North side receptacles under the counter top. 2

3 Control Room Receptacles - South wall receptacles for the monitors

Control Room Receptacles - North side receptacles under the counter top. 4

5 Control Room Receptacles - South wall receptacles for the monitors

Control Room Receptacles - North side receptacles under the counter top. 6

7 Fuel Oil Transmitter Basin Level Transmitter 8

9 Fuel Oil Leak Detection - PAL-AT in control room SPARE 10

11 TCP-17 (JCI Panel) lower 120V power PPW Leak Detection, LIQUIDWATCH II, control room wall 12

13 Server Room Receptacles, Double Duplex on top of racks

TCP-11 (JCI Panel) Chiller MCC room TCP- 2 (JCI Panel) Chiller Plant MCC wall 14

15 Server Room Receptacles, Double Duplex on top of racks

TCP-3 (JCI Panel) Chiller Plant MCC wall TCP-4 (JCI Panel) Chiller Plant MCC wall 16

17 Server Room Receptacles, Double Duplex on top of racks

TCP-5 (JCI Panel) Chiller Plant MCC wall TCP-6 (JCI Panel) Chiller Plant MCC wall 18

19 Server Room Receptacles, Double Duplex on top of racks

NAE 11?(JCI Panel), Mezzanine, 20

21 TCP-10, (JCI Panel) Mezzanine TCP-7 (JCI Panel), Chiller Plant wall

Lenel Security Panels, Server Room 22

23 TCP-17 (JCI Panel), Chiller Plant wall, Main 120V power TCP-9 (JCI Panel) Chiller Plant wall.

CHW-CH (JCI Panel), Fire pump room, back wall 24

25 NAE01-07, Mezzanine, Metasys Supervisory Controller

208V Receptacle, Ceiling of Server Room

27 SPARE 28

29 SPARE Unit Ventilator #2 and #3 TCP (JCI Panel), Boiler MCC Room 30

31 SPARE CP-TCP-32 (JCI Panel), hallway outside air compressor room 32

33 SPARE

208V Receptacle, Ceiling of Server Room

35 Emergency Stop for Boilers 36

Panel E-PP-3 To be upgraded to a 100A

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

E-PP-1 Panel Details

11/1/2023

Brandon Keith P07

22002 7 11

E-PP-1

E-PP-1

E-PP-1

Data

Plate

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

Existing UPS details

11/1/2023

Brandon Keith P08

22020 8 11

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

Existing UPS data plates

11/1/2023

Brandon Keith P09

22002 9 11

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

Maintenance Bypass Switch

11/1/2023

Brandon Keith P10

22002 10 11

Order #:

Drawing Title:PROJECT TITLE:

FEU Project #:

Drawing Number:

Agricultural Research Service U.S. Department of Agriculture

NCAH

1920 Dayton Avenue Ames, Iowa 50010

Revision:

Client:

Sheet: Of

Designer:

Date:

Date:

Ben A'Hearn TBD Brandon Keith

Building 154 UPS replacement project

Existing UPS internal

11/1/2023

Brandon Keith P11

22002 11 11