This document appears to be a 6-month asbestos surveillance report for Building 14 at the Waco VA Medical Center. The report provides a detailed inventory of asbestos-containing materials (ACM) found in the building, including their locations, friability, condition, and damage severity. The ACM identified includes pipe insulation, floor tiles, and boiler stack materials.
The related federal contract opportunity is a solicitation (Solicitation Number: 36C25724B0015) issued by the Department of Veterans Affairs for the abatement and clean-up of Buildings 14 and 17 at the Doris Miller VA Medical Center in Waco, Texas. The contract will involve the remediation of the asbestos-containing materials documented in the surveillance report.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WACO VA MEDICAL CENTER
6-MONTH ASBESTOS SURVEILLANCE
BUILDING 14
| HMA |
| Material Description |
| Location |
| Friable Yes/No |
| Conditions at Last Inspection1 |
| Damage Severity2 |
| Conditions at Current Inspection1 |
| Comments |
| HMA-02 |
| Pipe Insulation and Fittings |
| Lower Level |
| HMA-02 |
| Pipe Insulation and Fittings |
| Upper Level/Mezzanine |
| HMA-02 |
| Pipe Insulation and Fittings |
| Generator Rm & Corridor |
| HMA-02 |
| Pipe Insulation and Fittings |
| North Wall Detail A-A' |
| HMA-02 |
| Pipe Insulation and Fittings |
| North Wall Detail B-B' |
| HMA-02 |
| Pipe Insulation and Fittings |
| East Wall |
Detail C-C'
| HMA-02 |
| Pipe Insulation and Fittings |
| Under Condensate Tank Detail D-D' |
| HMA-02 |
| Pipe Insulation and Fittings |
| Under Deaerator Tank Detail E-E' |
| HMA-02 |
| Pipe Insulation and Fittings |
| Heater Piping Detail F-F' |
| HMA-04 |
| White Cloth Material |
| Boiler Stack Detail G |
| HMA-05 |
| Gasket Material |
| Boiler Stack Detail G |
| HMA-04 |
| White Cloth Material |
| Boiler Stack Detail H |
| HMA-05 |
| Gasket Material |
| Boiler Stack Detail H |
| HMA-01 |
| 12x12 Floor Tile and Mastic |
| 2nd Floor |
| HMA-02 |
| Pipe Insulation and Fittings |
| 2nd Floor |
| HMA-03 |
| Black Sink Undercoating |
| 2nd Floor |
1Conditions: G=Good R=Repaired D=Damaged SD= Significantly Damaged
2Damage Severity: M=Minor O=Occasional X-Extensive P=Punctures N=None
HGS Engineering Inc.
1121 Noble Street
Anniston, AL 36201
Phone: 256-835-3800
Fax: 256-236-2979 www.hgsengineeringinc.com Inspectors:
Lonnie Lyro
105763
Asbestos Individual Consultant
Accreditation Agency: Texas Department of Health Services which is a recognized EPA accreditation agency.
Timothy A. Thompson, CQM
Project Manager