Brand Name or Equal Template for Product Salient characteristics Chiller.docx

DOCX document 24 KB Posted

Attached to
Z1DA--NRM-CONST 526-23-133 Improve OR and SPD HVAC
Solicitation number
36C24226B0027
Issued by

About this file

This document is a Brand Name or Equal Template for a Chiller Unit for a VA Medical Center HVAC improvement project. The template specifies a York Air Cooled Scroll Chiller Unit (Model: YLAA0170SJ46XFB) with detailed salient characteristics including 170 tons cooling capacity, screw compressor technology, continuous 24/7 hospital duty, and compatibility with hospital operating room and sterilization processing department (OR/SPD) requirements.

The related federal contract opportunity (Solicitation Number 36C24226B0027) is a Service-Disabled Veteran Owned Small Business (SDVOSB) set-aside construction project at the James J. Peters VA Medical Center in Bronx, NY. The project involves HVAC improvements with a construction budget between $5-10 million, NAICS Code 238220, and a 360-calendar day completion timeline. The solicitation is expected to be released on or about January 5, 2026, with all detailed requirements to be posted on www.sam.gov, and prospective bidders must be registered with a Unique Entity Identifier and verified as an SDVOSB.

View the file

Other files

File Type Posted
SOW - Improve OR and SPD HVAC 12-18-25.docx DOCX document
Brand Name or Equal Template for Product Salient characteristics Pump.docx DOCX document
36C24226B0027.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LIST OF BRAND NAME OR EQUAL EQUIPMENT

MAKE, MODEL AND SALIENT CHARACTERISTICS

REFERENCE:

ITEM: York Air Cooled Scroll Chiller Unit

VENDOR: Johnson Controls York

MODEL: YLAA0170SJ46XFB

SALIENT CHARACTERISTICS:

• Minimum 170 tons cooling capacity

• Screw compressor technology

• Continuous 24/7 hospital duty

• Stable operation at 25–100% load

• ±0.5°F chilled water temperature control

• Supports OR/SPD humidity control (20–60% RH)

• Refrigerant R-134a or VA-approved equivalent

• Compatible with existing BMS integration

• Rooftop rated, weatherproof construction

• Proven hospital OR/SPD application history

All characteristics are for reference purposes only and the VA will consider similar substitutions provided the intent of this project is still met and no federal, state or VA standards are violated.

BIDDING ON:

MANUFACTURER

NAME:

BRAND:

NO.: