This is a bidding package for design and construction drawings issued by the Department of Technology, Management and Budget (DTMB), State of Michigan, for Day Use Improvements at William Mitchell State Park located in Cadillac, Michigan (Wexford County). The project, filed under number 751/23309.HJD, was issued for bidding on August 19, 2026, following owner review on May 29, 2026, and permitting approval on August 7, 2026. The scope of work encompasses comprehensive site and civil improvements including a new restroom structure (986 square feet), a picnic shelter with alternates, a contact station with alternates, parking lot expansions accommodating 96 parking spaces, concrete and bituminous pavement, utility infrastructure (water, sanitary sewer, electrical, and storm drainage systems), landscaping restoration, and soil erosion and sedimentation control measures. The project site encompasses approximately 6093 East M-115 in Cadillac, Michigan, adjacent to Lake Mitchell and situated within Mitchell State Park. Construction is anticipated to occur from September 2026 through July 2027, with specific components including sanitary and storm sewer systems, catch basins, bioswales, manufactured treatment units, and riprap installations. The design team includes Beckett & Raeder, Inc. (landscape architecture, planning, and engineering), Structural Design Inc. (structural), V.F. & Associated, Inc. (mechanical/plumbing), and Montero Enterprises Inc. (electrical).
Pricing information, contract award amounts, and specific payment terms are not detailed within this drawing and specification document. The project must comply with the 2021 Michigan Building Code, 2021 Michigan Plumbing Code, 2021 Michigan Mechanical Code, 2023 National Electric Code, and 2017 ANSI A117.1 accessibility standards. The restroom facility is classified as Assembly (Use Group A-3) under construction classification V-B with a maximum allowable area of 6,000 square feet. Permits required include SESC (Soil Erosion and Sediment Control), LARA Plan Review, MDOT Right-of-Way, and BRI (Building and Related Infrastructure) contractor certifications. The project involves coordination with multiple utility providers including Consumers Energy and existing utility infrastructure protection requirements. Maintenance schedules are delineated for both during-construction and post-construction phases, with specific inspection and maintenance intervals for storm systems, swales, sedimentation basins, and riprap installations. Environmental considerations address wetlands protection, waterway management, and sediment control throughout the construction period, with daily contractor inspections required and penalties of $500 per day assessed for non-compliance with erosion control measures.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
William Mitchell State Park Day Use Improvements Date Issued: August 19, 2026
Issued For: Bidding
Vicinity Maps
NTS
Vicinity Map
File Number: 751/23309.HJD Wexford County, MI 49601
Permits Required
Landscape Architect / Engineer
Agency and Project Director
Contacts Christy Summers
Project Location 6093 East M-115 Cadillac, MI 49601
Surveyor
M 55
US
M
S
M ile
R d
S
M ile
R d
U S
Sunnyside Dr.
Paluster St.
E Division St. M 55
M
Boon Rd
W 13th St.
Le es on A ve
O ld
U S
Cadillac
PROJECT
SITE
Lake Mitchell Lake
Cadillac
Sheet Index
W Division St.
Pl et t Rd
G1.0 RS General Information
A 1.0 RS Floor Plan
A 2.0 RS Reflected Ceiling Plan
A 3.0 RS Exterior Elevations
A 4.0 RS Building Section
Project Location
Lake Cadillac
Lake Mitchell
M 55
M
Sunnyside Dr.
Sunset Ave.
Leisure St
North Blvd.
PROJECT
SITE
Mitchell Day Use Park
Mitchell State ParkCampground
Canal
Consultants
Structural:
Structural Design Inc.
275 East Liberty Ann Arbor, MI 48104 734.213.6091
Mechanical/Plumbing:
V.F. & Associated, Inc.
4444 Wyman Rd.
Tipton, MI 49287 517.431.3732
Electrical:
Montero Enterprises Inc.
3475 Jeanette Dr.
Chelsea, MI 48118 734.475.3592
M 1.0 RS Mechanical Plan
A 3.0 PS Elevations
A 5.0 RS Exterior Details
A 6.0 RS Enlarged Plan & Interior Elevations
A 6.1 RS Enlarged Plan, Interior Elevations & Details
A 6.2 RS Interior Details
A 7.0 RS Door and Window Schedules
S 0.1 RS Structural General Notes
S 0.2 RS Structural Details
S 0.3 RS Structural Details
S 1.0 RS Footing and Foundation Plan
S 1.1 RS Structural Floor Plan
S 1.2 RS Roof Structural Plan
E 1.0 RS Electrical Notes, Details, Riser, Schedule
E 1.1 RS Electrical Plan
P 1.0 RS Plumbing Plan
P 2.0 RS Plumbing Details
M 0.1 RS Mechanical Schedules
A 4.1 RS Building Section
A 4.0 PS Building Section
A 5.0 PS Exterior Details
A 6.0 PS Interior Details
S 0.1 PS Structural General Notes
S 0.2 PS Structural Details
S 0.3 PS Structural Details
S 1.0 PS Footing and Foundation Plan
S 1.1 PS Roof and Floor Structural Plan
Legal Description Situated in the city of Cadillac, County of Wexford, State of Michigan and described as follows, to-wit: all that part of government lot four (4) in section six (6), township twenty one (21) north, range nine (9) west, lying south of a line fifty (50) feet north of the centerline of the canal running east and west through said government lot four, as said canal is now located and existing, subject to the easement to erect and maintain a line of electric wires supported on poles or towers, on over and across said lands, granted and conveyed by the Cadillac Resort Club to the Western Michigan Power Company, its successors and assigns, by instrument in writing, executed January 29, 1914, and recorded in the office of the register of deeds of said county on January 29, 1914, in liber 4 of miscellaneous records, on page 19
P 0.1 RS Plumbing Schedules
A 2.0 PS Reflected Ceiling Plan
E 1.0 PS Electrical Notes, Details, Riser, Schedule
E 1.1 PS Electrical Plans & Notes
A 4.2 RS Building Section
A 1.0 PS Floor Plan
Permit Type
SESC
LARA Plan Review
Submittal by Secure Permit
MDOT ROW
BRI Contractor
BRI / ADG
BRI
Contractor
Contractor
C6.0 Site Utilities Plan
C6.1 Site Utilities Details
C7.0
C7.1 Site Details
C7.2 Site Details
C8.0 Seeding & Restoration Plan
Cover Sheet
Existing Conditions PlanC1.0
Soil Erosion & Sedimentation Control PlanC2.0
Demolition Plan C3.0
C4.0 Layout & Materials Plan
Grading PlanC5.0
Soil Erosion & Sedimentation Control Details
Landscape Architecture Planning, Engineering &
Beckett & Raeder, Inc.
535 West William, Suite 101 Ann Arbor, MI 48103
Beckett&Raeder
734 663.6759 fx
B
734 663.2622 ph
R i
Environmental Services
C7.3 Site Details
Site and Civil Drawings
Restroom Structure Drawings
Picnic Shelter Drawings (Alternate No.2)
Beckett & Raeder, Inc. 734.663.2622 csummers@bria2.com
Steve Tinskey DNR 231.878.9113 tinskeys1@michigan.gov
Heather DeKorte DTMB 517.243.7248 dekorteh@michigan.gov
DEPARTMENT OF TECHNOLOGY, MANAGEMENT AND BUDGET
STATE OF MICHIGAN
ADAM P. LACH, RA, DIRECTOR
STATE FACILITIES ADMINISTRATION
DESIGN AND CONSTRUCTION DIVISION A 4.3 RS Building Section
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
BM
BM
BM #3
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C1.0
Existing Conditions Plan
EXISTING CONDITIONS LEGEND
EXISTING CHAIN LINK FENCE
EXISTING WATER MAIN
EXISTING ELECTRIC LINE
EXISTING GAS MAIN
EXISTING COMM LINE
EXISTING SANITARY LINE
EXISTING PARCEL LINE
EXISTING RIGHT-OF-WAY LINE
SANITARY MANHOLE
SQUARE CATCH BASIN
UTILITY POLECONTROL POINT
WATER SHUT OFF VALVE
SPIGOT
GUY ANCHOR
TELEPHONE RISER
ELECTRIC RISER
SANITARY CLEANOUT
BENCH MARK
SIGN
POST/BOLLARD
EXISTING TREE
EXISTING CURB AND GUTTER
1. CONTRACTOR SHALL CALL MISS DIG (811) A MINIMUM OF THREE WORKING DAYS
PRIOR TO START OF CONSTRUCTION.
2. CONTRACTOR SHALL INVESTIGATE EXTENT AND LOCATION OF ALL EXISTING
UTILITIES AND SHALL BE RESPONSIBLE FOR PROTECTION AND RESTORATION OF
SAME IF DAMAGED AS A RESULT OF CONTRACTOR'S OPERATIONS.
3. CONTOUR INTERVAL SHOWN IS 1-FOOT.
EXISTING CONDITIONS NOTES
SURVEY COMPLETED BY DRIESENGA ON 02.20.2024
HOLLAND, MI 616.396.0255
www.driesenga.com
SURVEY PREPARED BY:
BM #1 EL1300.01' (NVAD 88)
SET NAIL ON THE SOUTHEAST SIDE OF UTILITY POLE, LOCATED 95, WEST
OF THE CENTERLINE OF M-115 AND 30, SOUTH OF THE CANAL SEA WALL
BM # 2 EL 1296.01' (NAVD 88)
SET NAIL ON THE EAST SIDE OF UTILITY POLE, LOCATED 35'WEST OF THE
CENTERLINE OF M-115 AND 218' NORTH OF THE CENTERLINE OF MITCHELL
STATE PARK PARKING LOT ENTRANCE.
BM # 3 EL 1295.93' (NAVD 88)
CUT "X" ON THE NORTH CORNER OF CONCRETE OUTHOUSE PAD NEAR
THE BOAT LAUNCH, LOCATED 18' SOUTH OF THE CENTERLINE OF
EAST-WEST ACCESS DRIVE TO BOAT LAUNCH AND 55' NORTHEAST OF THE
CENTER OF BOAT LAUNCH.
BENCHMARK NOTES
THE NATURAL RESOURCE CONSERVATION SERVICE SOIL SURVEY INDICATES THE SITE IS
COMPRISED OF
10A: AU GRES-FINCH SANDS, 0 TO 4 PERCENT SLOPES
20B: MONTCALM-GRAYCALM COMPLEX, 0 TO 6 PERCENT SLOPES
CSWAAA: CROSWELL SAND, 0 TO 6 PERCENT SLOPES
SOIL TYPES
BM #1
GAS LINE MARKER
EXISTING BENCH
EXISTING BOAT LAUNCH
PARKING
EXISTING BOAT LAUNCH
RAMP
EXISTING TELESCOPE
EXISTING TRASHCAN
EXISTING RESTROOM
AND PICNIC SHELTER
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
EXISTING PORTABLE
RESTROOM
M - 115
C
LA
M L
A K
E C
A N
A L
LAKE MITCHELL
SITUATED IN THE CITY OF CADILLAC, COUNTY OF WEXFORD, STATE OF MICHIGAN AND DESCRIBED AS FOLLOWS, TO-WIT: ALL THAT PART OF GOVERNMENT LOT FOUR (4) IN SECTION SIX (6), TOWNSHIP TWENTY ONE (21) NORTH, RANGE NINE (9) WEST, LYING SOUTH OF A LINE FIFTY (50) FEET NORTH OF THE CENTERLINE OF THE CANAL RUNNING EAST AND WEST THROUGH SAID GOVERNMENT LOT FOUR, AS SAID CANAL IS NOW LOCATED AND EXISTING, SUBJECT TO THE EASEMENT TO ERECT AND MAINTAIN A LINE OF ELECTRIC WIRES SUPPORTED ON POLES OR TOWERS, ON OVER AND ACROSS SAID LANDS, GRANTED AND CONVEYED BY THE CADILLAC RESORT CLUB TO THE WESTERN MICHIGAN POWER COMPANY, ITS SUCCESSORS AND ASSIGNS, BY INSTRUMENT IN WRITING, EXECUTED JANUARY 29, 1914, AND RECORDED IN THE OFFICE OF THE REGISTER OF DEEDS OF SAID
COUNTY ON JANUARY 29, 1914, IN LIBER 4 OF MISCELLANEOUS RECORDS, ON PAGE 19
LEGAL DESCRIPTION
MH-A - 4'Ø CONCRETE
RIM 1296.31
INV (NW) 18" RCP=1275.39
INV (S) 18" RCP=1275.37
MH-B - 4'Ø CONCRETE
RIM 1296.66
INV (N) 18" RCP=1275.88
INV (SW) 18" RCP=1275.86
MH-C - 4'Ø CONCRETE
RIM 1296.38
INV (N) 18" RCP=1276.36
INV (S) 18" RCP=1276.39
MH-D - 4'Ø CONCRETE
RIM 1296.22
INV (N) 18" RCP=1276.58
INV (S) 18" RCP=1276.54
MH-E - 4'Ø CONCRETE
RIM 1293.72
INV (N) 18" RCP=1277.87
INV (S) 18" RCP=1277.68
INV (N) 18" RCP=1281.44
SANITARY STRUCTURE DATA
CB#1 - 4'Ø CONCRETE
LEACHING BASIN
RIM 1300.38
TOP OF DEBRIS=1294.0±
STORM STRUCTURE DATA
EXISTING SPOT
ELEVATION
EXISTING CHARCOAL
GRILLS
PARK RULES SIGNS
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
BM
BM
BM #3
FF
FF FF
FF
FF
FF
FF
FF
FF FF
FF
FF
FF
FF
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
SESC LEGEND
PROPOSED TREE PROTECTION FENCE
PROPOSED FILTER FABRIC FENCE
PROPOSED LIMIT OF WORK LINE
EXISTING PARCEL LINE
EXISTING RIGHT-OF-WAY LINE
PROPOSED STABILIZED CONSTRUCTION ACCESSMTDMB SILT FENCE KEY SYSTEM: USE
ADJACENT TO CRITICAL AREAS, TO PREVENT
SEDIMENT LADEN SHEET FLOW FROM ENTERING
THESE AREAS.
MTDMB STABILIZED CONSTRUCTION ACCESS
KEY SYSTEM: USED AT EVERY POINT WHERE
CONSTRUCTION TRAFFIC ENTERS OR LEAVES A
CONSTRUCTION SITE. ALL CONSTRUCTION
ACCESS POINTS ARE NEW, IF NEEDED.
MTDMB PERMANENT SEEDING / SODDED KEY SYSTEM:
STABILIZATION METHOD UTILIZED ON SITES WHERE EARTH CHANGE
HAS BEEN COMPLETED (FINAL GRADING ATTAINED) (REFERENCE
SHEET C8 SEEDING AND RESTORATION PLAN FOR PERMANENT
SEEDING LOCATIONS.)
NOTE: SEE SPECIFICATIONS FOR WRITTEN DESCRIPTION INSTALLATION AND MAINTENANCE.
S51
S53
E8
MDTMB SESC LEGEND
1. THIS PROJECT MUST BE CONSTRUCTED IN COMPLIANCE WITH PART 91 OF MICHIGAN
NATURAL RESOURCES AND ENVIRONMENTAL PROTECTION ACT 451 OF 1994, AS
AMENDED, THE SOIL EROSION AND SEDIMENT CONTROL ACT.
2. PRIOR TO ANY SITE DISTURBANCE, INCLUDING DEMOLITION, CONTRACTOR SHALL
PLACE EROSION CONTROL MEASURES ON ALL EXISTING STORM SEWER STRUCTURES
AFFECTED BY WORK IN THIS CONTRACT. SUCH EROSION CONTROL MEASURES SHALL
BE MAINTAINED UNTIL PERMANENT MEASURES ARE IN PLACE.
3. CONTRACTOR SHALL PLACE TEMPORARY EROSION AND SEDIMENTATION CONTROL
MEASURES AS REQUIRED AND SHOWN ON PLANS.
4. CONTRACTOR SHALL PROVIDE AND MAINTAIN ALL EROSION CONTROL MEASURES AS
REQUIRED BY STATE AND LOCAL GOVERNING AUTHORITIES.
5. DAILY INSPECTIONS SHALL BE MADE BY THE CONTRACTOR TO DETERMINE THE
EFFECTIVENESS OF EROSION AND SEDIMENT CONTROL MEASURES. ANY NECESSARY
REPAIRS SHALL BE MADE WITHOUT DELAY.
6. ALL EROSION AND SEDIMENT RESULTING FROM WORK ON SITE SHALL BE CONTAINED
ON SITE AND NOT ALLOWED TO COLLECT IN ANY OFF-SITE AREAS OR WATERWAYS.
WATERWAYS INCLUDE BOTH NATURAL AND MAN-MADE OPEN DITCHES, STREAMS,
STORM DRAINS, RIVERS, OR PONDS.
7. CONTRACTOR SHALL PLACE TEMPORARY EROSION AND SEDIMENTATION CONTROL
MEASURES AS REQUIRED AND SHOWN ON PLANS.
8. CONTRACTOR SHALL PLACE INLET FILTER PROTECTION ON ALL STORM STRUCTURES
AFFECTED BY THIS PROJECT.
9. ALL TEMPORARY SEDIMENT BASINS USED DURING CONSTRUCTION SHALL BE CLEANED
AND ALL SEDIMENT LEGALLY DISPOSED OF PRIOR TO STABILIZATION. REMOVAL OF ALL
FINES AND SEDIMENT IS CRITICAL IN AREAS WHERE INFILTRATION PRACTICES SHALL
BECOME PERMANENT BEST MANAGEMENT PRACTICE.
10. CONTRACTOR SHALL CLEAN DEBRIS FROM STREETS ON A DAILY BASIS AS NEEDED.
STREETS SHALL BE SWEPT WEEKLY.
11. CONTRACTOR SHALL BE ASSESSED A $500 PER DAY THAT THE SITE DOES NOT MEET
THE APPROPRIATE SESC MEASURES. ALL DAMAGES CAUSED DUE TO LACK OF THE SESC
MEASURES WILL BE ASSESSED DIRECTLY TO THE CONTRACTOR.
SESC NOTES
EXISTING BOAT LAUNCH
PARKING
EXISTING BOAT LAUNCH
RAMP
S51 S51
S51
S53
MTDMB DUST CONTROL KEY SYSTEM: FOR USE ON
CONSTRUCTION SITES, UNPAVED ROADS, ETC. TO
REDUCE DUST AND SEDIMENTATION FROM WIND AND
CONSTRUCTION ACTIVITIES, IF NEEDED.
E5
E5
E5M - 115
C
LA
M L
A K
E C
A N
A L
LAKE MITCHELL
PROPOSED INLET PROTECTION FILTER
INLET PROTECTION FILTER
ON PROPOSED STORM INLET
INLET PROTECTION FILTER
ON PROPOSED STORM
INLET
C7.0
2TREE PROTECTION FENCE
C7.0
3 STABILIZED CONSTRUCTION
ACCESS
C7.0
1FILTER FABRIC FENCE
E8
E8
E8
E8
PROPOSED TOPSOIL STOCKPILE AREA
Soil Erosion & Sedimentation Control Plan
C2.0
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
XXXX
X
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
1. CONTRACTOR SHALL CALL MISS DIG (811) A MINIMUM OF THREE WORKING DAYS
PRIOR TO START OF CONSTRUCTION.
2. CONTRACTOR SHALL INVESTIGATE EXTENT AND LOCATION OF EXISTING UTILITIES
AND SHALL BE RESPONSIBLE FOR PROTECTION AND RESTORATION OF SAME IF
DAMAGED AS A RESULT OF CONTRACTOR'S OPERATIONS.
3. ALL ITEMS NOT INDICATED FOR REMOVAL SHALL REMAIN UNDISTURBED AND
PROTECTED. CONTRACTOR SHALL FULLY RESTORE ANY ITEMS/MATERIALS
DAMAGED DURING CONSTRUCTION AT NO ADDITIONAL COST TO THE OWNER.
4. ALL CONCRETE PAVEMENT AND CURB REMOVALS SHALL BE TO THE NEAREST
JOINT BEYOND INDICATED EXTENT.
5. CONTRACTOR SHALL MAINTAIN CLEAN SAW CUT EDGES FOR PROPOSED WORK
TO ABUT. BROKEN EDGES RESULTING FROM CONTRACTOR'S FAILURE TO PROTECT
THE EDGE WILL BE SAW CUT BEYOND THE BREAKS AT THE NEAREST JOINT, AT THE
CONTRACTOR'S EXPENSE.
6. ALL REMOVALS SHALL BE SAW CUT FULL DEPTH AND COORDINATED WITH
LAYOUT / GRADING PLANS.
7. REMOVALS SHALL INCLUDE SUBSOIL/EXISTING BASE MATERIALS TO FULL DEPTH
REQUIRED FOR INSTALLATION OF NEW WORK INCLUDING BASE COURSE. ALL
EXCAVATIONS SHALL PROVIDE ADEQUATE SOIL SUPPORT THROUGH THE USE OF
ADEQUATE CUT SLOPES OR STRUCTURAL SHORING.
8. OWNER TO COORDINATE WITH RESPECTIVE UTILITY COMPANY FOR REMOVAL OF
EXISTING TRANSFORMER, ELECTRICAL, CABLE, TELEPHONE AND FIBER OPTIC LINES.
9. CONTRACTOR SHALL REPAIR ALL DISTURBED TURF AREAS OUTSIDE OF PROJECT
LIMITS DAMAGED DURING CONSTRUCTION.
10. ALL TOPSOIL AND ORGANIC MATERIAL SHALL BE REMOVED FROM UNDER
PROPOSED BUILDING, FOOTINGS, SLABS, AND PAVED AREAS.
11. ALL SPOIL MATERIAL, INCLUDING TOPSOIL, TO BE REMOVED OFF SITE AND
DISPOSED IN A LEGAL MANNER.
12. CONTRACTOR TO RELOCATE TREE PROTECTION FENCE WITH LANDSCAPE
ARCHITECT/ENGINEER'S APPROVAL IN ORDER TO ACCOMPLISH WORK.
13. LAWN AND TOPSOIL REMOVALS AROUND EXISTING TREES TO BE PERFORMED
WITH EXTREME CARE. REMOVALS TO BE COMPLETED BY HAND. NO HEAVY
EQUIPMENT ALLOWED BENEATH TREE CANOPY. CONTRACTOR TO COORDINATE
REMOVALS WITH OWNER.
14. DISCHARGE OF WATER, DUST, OR DEBRIS FROM CONCRETE AND ASPHALT WORK
TO STORM OR SANITARY SYSTEMS IS PROHIBITED.
15. STORM DRAINS MUST BE PROTECTED FROM DUST AND DEBRIS.
16. ANY WATER USED DURING CONCRETE AND ASPHALT WORK (INCLUDING
SWEEPING AND SAWCUTTING) MUST BE CONTAINED AND COLLECTED FOR
PROPER DISPOSAL. SUGGESTED CONTROLS INCLUDE WET VACUUM OR
ABSORBENTS.
DEMOLITION NOTES DEMOLITION LEGEND
TREE PROTECTION FENCE
LIMIT OF WORK LINE
ABANDON ITEM IN PLACE
PROTECT ITEM
REMOVE ITEM
P
A
SAWCUT
PARCEL LINE
RIGHT-OF-WAY LINE
R GRAVEL
R CONCRETE RETAINING
WALL
R BENCH
R BENCH
R BENCH
R BENCH, TYP.
S GRILLS
SGRILL
S PARK REGULATORY SIGN
R BUILDING AND
CONCRETE PAD
R CONCRETE
PAD
R CONCRETE APRON
R CONCRETE PAD
R ENTRY GATE
R PARKING SIGNS,
TYP.
UTILITY RISERS,
TYP.
R
RPARK
REGULATORY
SIGN
R PARK REGULATORY
SIGN
P GRILL
P PARK REGULATORY
SIGN
R BENCH, TYP.
S PARK REGULATORY
SIGN
S PARK REGULATORY
SIGN
S GRILL
R GRILL
P WOOD EDGING
M - 115
C
LA
M L
A K
E C
A N
A L
LAKE MITCHELL
SPARK SIGN
WATER LINE A
P COMM LINE
SALVAGE ITEM TO OWNERS
R
TREE REMOVAL
WATER
FAUCET
R
R WATER FAUCET
UNDERGROUND ELECTRICAL SERVICE
(CONTRACTOR TO COORDINATE WITH
ELECTRICAL UTILITY COMPANY
R
R SANITARY SERVICE AS REQUIRED
TO MEET SLOPE SPECIFIED
DEMOLITION OF UTILITY LINE
ABANDON UTILITY LINE IN PLACEXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
WATER SERVICE,
TYP.
A
WATERLINE TO FAUCETS A
S KAYAK RACKS
R
P
A
S
ASPHALT DEMOLITION
CONCRETE DEMOLITION
BUILDING DEMOLITION
Demolition Plan
C3.0
SPARK SIGNS
DEMOLITION OF WALL
S LIFE
PRESERVER R BENCH
S"PAY HERE"
POST
P STOP SIGN
PPARK REGULATORY
SIGN
PARK SIGN R
GRILL R
P GRILL
PGRILL
P GRILL P PLAYGROUND
EQUIPMENT
P GRILL
P GRILL
P GRILL
P GRILL
P GRILL
P GRILL
PEXISTING CONTACT STATION
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
R46' R36'
R11'
R40'
30'R
R5'
R27'
R26'
R3'
R15' R300'
R40'
R25'
10'R5'R, TYP.
R27' R27'
R3', TYP.
R3'
R100'
SN
UGE
UGE
UGE
UGE UGE
UGE
UGE
18.0' 24.0'
18.0' 8.0'
6.0'
8.0'
20.0'
8.0'
6.0'
10.3'
20.0'
60.0' 14.0'
TYP.
20'R
R54'
5'R
3'R 3'R
3'R
5'R 3'R
75'R
5.0'
TYP8.0'
TYP8.0'
TYP
20 SPACES @ 9.5' = 190.0'
24 SPACES @ 9.5' = 228.0'
52 SPACES @ 9.0' = 468.0'
N 7758.32 E 9844.17
N 8217.78 E 9716.01 co
UD UD UD UD
U D
UD
UD
UD
UD
UD
U D
UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD
UD
UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD
UD
UD
UD
UD
UD
U D
UD
UD
UD
BITUMINOUS
PAVEMENT
STANDARD PARKING
STRIPING
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C4.0
Layout & Materials Plan
CONTROL JOINT
EXPANSION JOINT
LAYOUT & MATERIALS LEGEND
CONTROL JOINT
EXPANSION JOINT
LIMIT OF WORK LINE
RIGHT-OF-WAY LINE
LAYOUT & MATERIALS NOTES
1. ALL WORK SHALL BE COMPLETED IN CONFORMANCE WITH CURRENT ADA
STANDARDS.
2. ALL DIMENSIONS ARE TO BACK OF CURB, FACE OF BUILDING OR EDGE OF
MATERIAL UNLESS OTHERWISE NOTED.
3. ALL LINES ARE PARALLEL OR PERPENDICULAR TO THE CURB/ PAVEMENT/ BUILDING
LINE FROM WHICH THEY ARE DIMENSIONED UNLESS OTHERWISE NOTED.
4. FOLLOWING LAYOUT OF ALL MATERIALS, CONTRACTOR SHALL REVIEW WITH
OWNER'S REPRESENTATIVE.
5. ANY DISCREPANCIES IN THE LAYOUT PLAN SHOULD BE IMMEDIATELY REPORTED
TO OWNER'S REPRESENTATIVE.
6. NORTHINGS AND EASTINGS ON THE PLAN HAVE BEEN TRUNCATED BY THE
FOLLOWING: NORTHINGS: -330000; EASTINGS: -1939000
PROPOSED TURN AROUND
C7.1
2 CONCRETE PAVEMENT
C7.1
C7.2
C7.1
8 UNIT RETAINING WALL
WALL TYPE 2
EXISTING PLAY
GROUND PIT
EXISTING PLAY
AREA
PROPOSED
PICNIC SHELTER
PROPOSED
RESTROOM
PROPOSED STANDARD DUTY
CONCRETE PAVEMENT
PROPOSED HEAVY DUTY
CONCRETE PAVEMENT
PROPOSED STANDARD DUTY
HMA PAVEMENT
PROPOSED HEAVY DUTY
HMA PAVEMENT
PROPOSED REGULATORY SIGNS
CONCRETE CURB &
GUTTER
C7.2
7 REGULATORY SIGN
C7.2
3DOUBLE SWING PARK
GATE
K-4298
K-4298
(5)K2-1220
(1) K-1479
R1-1
R1-1
THICKENED EDGE WALK
AT BEACH
PROPOSED BENCH WITH ADA COMPANION SEATING
(BENCH BY OTHERS)
C7.2
2PRECAST BOLLARD
M - 115
C
LA
M L
A K
E C
A N
A L
LAKE MITCHELL C7.1
6 SAND TRACKING PAD
CL
CL
CL
C7.1
8 UNIT RETAINING WALL
WALL TYPE 1
C7.1
C7.1
PROPOSED CONCRETE CURB AND GUTTER
CURB TAPPER
PROPOSED SAND TRACKING PAD
(ALTERNATE NO. 3)
PROPOSED PRECAST BOLLARD
PROPOSED UNIT RETAINING WALL -
TYPE 1
PROPOSED RESTROOM BUILDING
C7.1
1 TYPICAL CURB RAMPS AT
PARKING LOT - RAMP 1
C7.1
1 TYPICAL CURB RAMPS AT
PARKING LOT - RAMP 2
C7.3
1CONTACT STATION
C7.1
8UNIT RETAINING WALL
WALL TYPE 1
PROPOSED UNIT RETAINING WALL -
TYPE 2
CONTROL JOINT
EXPANSION JOINT
PROPOSED THICKENED
EDGE WALK AT BEACH
PROPOSED PICNIC SHELTER
(ALTERNATE NO. 2)
PROPOSED CONTACT STATION
(ALTERNATE NO. 1)
(ALTERNATE NO. 3)
(ALT NO. 3)
(ALT NO. 2)
(ALTERNATE NO. 1)
(ALT NO. 1)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
BM
BM
BM #3
FF
2%
FFE
96.40
FFE
96.50
HP
97.11TC
97.11BC
97.22TC
96.79BC
+96.97
HP
97.36
97.21
97.40TC
96.97BC
1.8%
+97.32
96.17TC
95.74RE
+96.27+
96.43TC
96.00BC
+96.53
96.43TC
96.00BC
96.53
1.6%
97.43TC
97.00BC
+97.53
1.6%
1.6%
1.6%
+97.63TC
97.20BC
+97.75TC
97.32BC
+97.73
+ 97.28TC
96.71BC
+97.65TC
97.22BC +
97.65TC
97.08BC
+97.55TC
96.98BC
+ 96.58ME
+ 96.77ME
96.68ME
+96.72ME
+ME
+96.93ME
+ 96.77
96.97
(96.60)ME
(96.32)ME
1.3%
97.10
96.43TC
96.00BC
+96.53
95.43TC
95.00BC
+95.53
94.68TC
94.25RE
+94.78
95.43TC
95.00BC
95.53
96.00TC
96.00BC
96.10 96
ME(92.03)
ME(92.03)
4.9%
1.5%
2%
2%
+97.50
97.11+
96.31
96.36
+96.25
+ 96.40
3.8%
96.25
++96.40
96.42
96.50
96.42
+96.40
+96.40
+96.25
96.05
+96.00
95.90
96.25
+96.19 + 96.50
+ +96.02 96.07
95.72
95.62
95.82
95.72
95.34
95.24
95.15 95.25
96.00ME
96.00ME2%
4.0%
+92.86+
94.00
94.12
4.8% 4.8% + +92.98
+94.12
94.00
+94.00TW
92.50BW
94.00TW
92.86BW
+94.00TW
92.50BW
94.12BW
91.25+
+94.00 4.9%
+94.23+
94.00TW
92.50BW
+94.12
+94.23+
94.00TW
92.50BW
94.12
+94.12
+94.23+
+94.00TW
92.50BW
+94.00
94.12+
++92.14 +92.26
92.26
+92.14 +92.14
92.26
92.02ME
92.00ME
3.9%
94.00TW
92.50BW
92.50TW
92.00BW
93 +
93.50TW
92.50BW
93.00TW
92.00BW
+96.16
FF FF
FF
FF
FF
FF
FF
FF FF
FF
ME90.00 ME90.11
91.38
92.50TW
91.41BW
+ +ME89.60 ME89.71
93.50TW
92.50BW
93.00TW
92.50BW
92.50TW
92.00BW
4.9%
94.50TW
92 94
94.50TW
94.00BW
94.00TW
93.00BW
93.50TW
92.50BW
93.00TW
92.25BW
91.46 93
+97.15
97.35
97.22
96.86TC
96.86BC
98.67TC
98.10BC
96.50TC
96.50BC
+95.62TC
95.05BC
97.07TC
96.50BC
98.09TC
97.52BC
98.05TC
97.48BC
97.91 97.73
+98.18
FF
FF
FF
co
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C5.0
Grading Plan
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING MINOR CONTOUR
LIMIT OF WORK LINE
PARCEL LINE
RIGHT-OF-WAY LINE
EXISTING SPOT GRADE
80.84
PROPOSED RIM ELEVATION
PROPOSED SPOT ELEVATION
PROPOSED TOP OF CURB ELEVATIONTC 77.52
RE 89.00
ME MATCH EXISTING ELEVATION
PROPOSED INVERT ELEVATIONINV 73.25
PROPOSED BOTTOM OF CURB (EDGE OF METAL) ELEVATIONBC 77.02
TREE PROTECTION FENCE
FILTER FABRIC FENCE
1. CONTRACTOR IS RESPONSIBLE FOR CONSTRUCTION ALL WORK COMPLETED IN
CONFORMANCE WITH CURRENT ADA STANDARDS.
2. PROPOSED CONTOUR LINES AND SPOT ELEVATIONS REFLECT FINISH GRADES.
HOLD DOWN SUBGRADE ELEVATIONS ACCORDINGLY. ADJUST RIM ELEVATIONS OF
ALL UTILITIES AFFECTED BY WORK IN THIS CONTRACT. CONTRACTOR SHALL
ENSURE POSITIVE DRAINAGE ON THE SITE. ANY AREA THAT APPEARS TO NOT
PROPERLY DRAIN SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
LANDSCAPE ARCHITECT/ ENGINEER FOR RESOLUTION.
3. CONTRACTOR TO REMOVE EXISTING PAVEMENT AND DISPOSE OFF SITE.
4. CONTRACTOR TO RETAIN NO MORE THAN 4 INCHES OF EXISTING AGGREGATE
BASE UNDER PAVEMENT.
5. PROPOSED CONTOUR AND SPOT ELEVATIONS HAVE BEEN TRUNCATED. ADD 1200
TO ALL PROPOSED SPOT ELEVATIONS TO MATCH THE DATUM OF EXISTING
CONTOUR LINES AND SPOT ELEVATIONS.
GRADING NOTES
PROPOSED
RESTROOM
FFE 96.40
SEE SHEET C6.0 FOR
STORM DRAINAGE
M - 115
C
LA
M L
A K
E C
A N
A L
LAKE MITCHELL
2% PROPOSED SLOPE AND DIRECTION
QUALITY UNIT
PROPOSED
RESTROOM
(SEE ARCHITECTURAL
PLANS)
PROPOSED PICNIC
SHELTER AND SLAB
(SEE ARCHITECTURAL PLANS)
GRADING LEGEND
PROPOSED BOTTOM OF WALL (FINISH GRADE)92.50 BW
PROPOSED TOP OF WALL92.50 TW
Enlargement - See Sheet C5.0
97.35
97 97
+97.11 +97.15 +97.21 +97.50
97.40 TC
96.97 BC
HP
97.11 TC
96.11 BC
96.86 TC
96.86 BC
97.22 TC
96.79 BC
97.32
96.97
HP
97.36
+97.22
ENLARGEMENT
(ALT NO. 3)
(ALT NO. 2)
(ALT NO. 1)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
BM
BM
BM #3
ST
R
ST
R
STR
STR
STR
STR
STR
STR
SN
UGE
UGE
UGE
UGE UGE
UGE
UGE
co
UD UD UD UD
U D
UD
UD
UD
UD
UD
U D
UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD
UD
UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD
UD
UD
UD
UD
UD
U D
UD
UD
UD
co
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
PROPOSED STORM LINE
PROPOSED STORM WATER STRUCTURE
PROPOSED SANITARY LINE
PROPOSED ELECTRIC LINE
PROPOSED WATER LINE
PROPOSED STORM WATER QUALITY UNIT
LIMIT OF WORK LINE
PARCEL LINE
RIGHT-OF-WAY LINE
1. ALL UTILITIES SHOWN FOR CONCEPTUAL DESIGN DEVELOPMENT ONLY. FINAL
ROUTING, SIZING AND CONNECTIONS WILL VARY.
2. PROPOSED CONTOUR LINES AND SPOT ELEVATIONS REFLECT FINISH GRADES.
HOLD DOWN SUBGRADE ELEVATIONS ACCORDINGLY. ADJUST RIM ELEVATIONS OF
ALL UTILITIES AFFECTED BY WORK IN THIS CONTRACT. CONTRACTOR SHALL
ENSURE POSITIVE DRAINAGE ON THE SITE. ANY AREA THAT APPEARS TO NOT
PROPERLY DRAIN SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
LANDSCAPE ARCHITECT/ ENGINEER FOR RESOLUTION.
3. CONTRACTOR SHALL VERIFY ALL EXISTING UTILITY LOCATIONS, DEPTHS AND
ELEVATIONS PRIOR TO CONSTRUCTION. NO CHANGES IN CONTRACT PRICE WILL
BE AWARDED FOR ACTUAL DISCREPANCIES IN UTILITY LOCATIONS DUE TO THE
FAILURE TO VERIFY ACTUAL FIELD LOCATIONS.
4. THE CONTRACTOR SHALL RESTORE ALL AREAS DISTURBED BY HIS CONSTRUCTION
OPERATIONS TO A CONDITION EQUAL TO OR BETTER THAN THAT EXISTING PRIOR
TO CONSTRUCTION. THE CONTRACTOR SHALL CLEAN UP AND HAUL AWAY ALL
CONSTRUCTION DEBRIS AND LITTER CAUSED BY HIS OPERATIONS.
5. CONTRACTOR SHALL PROTECT ALL EXISTING UTILITIES FROM DAMAGE DURING
CONSTRUCTION. ANY DAMAGE INCURRED SHALL BE REPAIRED AT THE
CONTRACTOR'S EXPENSE.
6. ALL UTILITY CROSSINGS SHALL HAVE A MINIMUM OF 18" VERTICAL CLEARANCE.
7. SEE ARCHITECTURAL AND MECHANICAL SHEETS FOR CONTINUATION OF UTILITIES
WITHIN STRUCTURES.
UTILITIES PLAN NOTES
PROPOSED
PICNIC SHELTER
PROPOSED
RESTROOM
M - 115
C
LA
M L
A K
E C
A N
A L
LAKE MITCHELL
189 LF 2" K-COOPER WATER
SERVICE WITH MINIMUM 6'
DEPTH OF BURY
SAN CO#1
SEE SHEET C6.1 DETAIL 5
INV 4" E/W 90.90
CONNECT TO THE EXISTING
SERVICE LINE WITH BRASS
COMPRESSION COUPLING
80 LF 6" SCH 40 PVC @ 2.0%
MINIMUM
CONNECT TO EXISTING SEWER
SERVICE INVERT AS REQUIRED FOR
MINIMUM PIPE SLOPE
CONTRACTOR TO COORDINATE
NEW ELECTRICAL SERVICE WITH
ELECTRICAL COMPANY
PROPOSED SANITARY CLEANOUT
R 110 94.25
INV 12" E 91.10
Structure Table
STRUCTURE ID
QU 115
TYPE CASTING RIM ELEV
95.90
INVERT ELEVATIONS
INV 15" SE 90.88
Storm
48" DIA
CATCH BASIN
60" DIA
QUALITY
UNITY
PER
MANUFACTURER
R 105 95.74 INV 12" N 92.8424" DIA
INLET
INV 15" NW 91.00
EJIW 7210 Z2,
T2, M1 GRATE
SEE ELECTRICAL PLANS
FOR METER AND SWITCH
SEE MECHANICAL/ PLUMBING WATER
SERVICE ENTRANCE DETAIL FOR THE
CAPPED AIR BLOW OFF LINE
PROVIDE MINIMUM 18" VERTICAL SEPARATION
BETWEEN SANITARY SEWER AND WATER MAIN
FES 120 N/A INV 15"SE 90.10
15" DIA
FES WITH
GRATE
N/A
INV 15"NW 90.78
136 LF 15" CL VI RCP @ 0.5%
347 LF 12" CL VI RCP @ 0.5%24 LF 15" CL VI RCP @ 0.5%
UGE
SN
STR
WATER QUALITY UNIT
Site Utilities Plan
C6.0
SITE UTILITIES LEGEND
co
INLET R105 (24" DIA)
SEE SHEET C6.1 DETAIL 3
RIM 95.74
12" INV N 92.84
CB R110 (48" DIA)
SEE SHEET C6.1 DETAIL 2
RIM 94.25
15" INV SE 91.10
15" INV NW 90.00
PROPOSED UNDERDRAINUD
QU R115 (60" DIA)
SEE SHEET C6.1 DETAIL 6
RIM 95.90
15" INV SE 90.88
15" INV NW 90.78
FES R120
SEE SHEET C6.1 DETAIL 1
RIM 95.74
15" INV N 90.10
EJIW 7210 Z2,
T2, M1 GRATE
4" SCH 40 PVC SLEEVE FOR
ELECTRICAL SERVICE TO
CONTACT STATION
(ALT NO. 3)
(ALT NO. 2)
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
NO SCALE
4' Diameter Catch Basin
2' -8
M
IN
IM
U M
FRAME AND COVER
AS SPECIFIED; SET IN
1" MORTAR
PRECAST CONCRETE
ADJ. RINGS OR BRICK
PRECAST CONCRETE
MANHOLE CONE AS
SPECIFIED
PRECAST CONCRETE
MANHOLE SECTIONS
OR 6" CONCRETE
BLOCK AS SPECIFIED
MORTAR FILLET (TYP.)
10' MIN. LENGTHS OF 6"
WRAPPED SUBDRAIN AT
QUAARTER POINTS
ALUMINUM OR REINFORCED
POLYPROPYLENE STEPS, 16"
SPACING MAX.
PRECAST CONCRETE BASE
OR POURED-IN0-PLACE AS
SPECIFIED
6" COMPACTED GRANULAR
MATERIAL AS SPECIFIED
UNDISTURBED EARTH
4'-0" DIA.
4" MIN
2' -0
M
IN
SU
M P
8"
3' -4
ST
A N
D A
R D
1' -9
M
A
NO SCALE
2' Diameter Storm Inlet
2'
2'
12"
LONGITUDINAL SECTION
SECTION A-A
NOT TO SCALE
Flared End Section w/ Grate
A A
SALVAGE EXISTING
HEAVY RIP RAP AND
RESET AFTER FLARED END
SECTION IS INSTALLED
FILTER FABRIC
SALVAGE EXISTING HEAVY RIP
RAP AND RESET AS NEEDED
AFTER FLARED END SECTION
IS INSTALLED
FILTER FABRIC UNDER
RIP-RAP
12" STONE RIP-RAP
BURIED 6" MIN.
2'-6"
3'-0"MIN
SALVAGE EXISTING HEAVY RIP
RAP AND RESET AFTER
FLARED END SECTION IS
INSTALLED
100 YR, OHWM, ELEVATION 91.10
PROPOSED SIDEWALK
100 YR, OHWM,
ELEVATION +90.10
6"
EQ EQ EQ EQ
2 GRATE
HOLDERS
EQ
6" TYP.
45° 6"
END OF BAR, TYP.
MIN (1) MAX (3)
BRICKS OR PRECAST
CONC. ADJUSTMENT
RING COURSES FOR
ADJUSTING CASTING
TO FINISH GRADE
MORTAR BED
BLOCK OR PRECAST
MASONRY
PLASTER COAT ENTIRE
STRUCTURE WITH 1#2"
CEMENT MORTAR IF BLOCK
4" TYP. MIN.
3" MIN.
FOUNDATION SLAB
8" CAST IN PLACE
W/ #4 @ 12" E.W.
OR PRECAST
BOTTOM SECTION
6" TO 8"
6" MIN. GRANULAR BACKFILLNOTES:
ALL STRUCTURES TO BACKFILLED WITH
CLASS II FILL OR 21AA LIMESTONE
COMPACTED TO 95% MAXIMUM DENSITY.
CASTING TO BE COATED (TYPICAL TO ALL)
GROUT OPENING
WATER TIGHT
INV. ELEVATION
GROUT OPENING
WATER TIGHT
1/2"CEMENT PLASTER
FRAME AND COVER AS
SPECIFIED: SET IN 1"
MORTAR
NO SCALE
Sewer Cleanout
V A
RI
ES
FLOW
LC
NEENAH CASTING R-7506-D
1.5'X 1.5' SQUARE CONCRETE
PAD IN PAVED AREAS W/ NO.4
REBAR EACH SIDE
BEND AS REQUIRED
WYE FITTING TO MATCH LEAD
PIPE, AS REQUIRED
GRADE
RISER
12" TYP.
4"
Xref .\DETAILS\CDS2025-5-C Standard Detail .dwg
SCALE: 1/2" = 1'-0"
Water Quality Unit
EXISTING SUBGRADE
UNDER GREENBELTUNDER WALKS AND
PAVEMENT
ZONE OF 1:1 INFLUENCE
M
IN
6" MIN.
4" M
IN
D
EP
TH
A
S
SP
EC
IF
IE
D MDOT CLASS II
GRANULAR MATERIAL
COMPACTED TO 98%
GRANULAR MATERIAL
COMPACTED TO 98%
PIPE AS SPECIFIED
4 Trench Detail
NO SCALE
Site Utilities Details
C6.1
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C7.0
Soil Erosion & Sedimentation
NO SCALE
Stabilized Construction Access
FLOW
PLAN VIEW
2"-3" CRUSHED ROCK (8" DEPTH)
NON-WOVEN GEOTEXTILE FABRIC EXISTING GROUND
PROFILE
SEDIMENT SUMP
SEDIMENT SUMP
3. CARE SHOULD BE TAKEN TO MAINTAIN EXISTING ROADSIDE DRAINAGE
VIA CULVERT INSTALLATION, WITH SEDIMENT SUMP PLACED DOWNFLOW
OF CULVERT.
2. CARE SHOULD BE TAKEN TO PREVENT MATERIAL MOVEMENT INTO
ADJACENT WETLANDS/WATERBODIES.
1. ESTABLISH STABILIZED CONSTRUCTION ENTRANCE PRIOR TO THE
INITIATION OF SITE CONSTRUCTION ACTIVITIES.
NOTES:
STANDARD SYMBOL
10' MIN.
10' MIN.
50' MINIMUM LENGTH
LENGTH OF STABILIZED ROAD
12' MINIMUM
WIDTH
SEDIMENT
SUMP
* 50' MINIMUM LENGTH LENGTH
OF STABILIZED ROAD
EXISTING
PAVEMENT
NO SCALE
Filter Fabric Fence
BOTTOM OF BURIED FABRIC
FILTER FABRIC6' MAX.
SECTION
ELEVATION
DISTURBED AREAUNDISTURBED AREA
FABRIC STAPLED TO POST
2" X 2" WOOD POST
TOE IN 6" OF FABRIC BELOW GRADE
EXISTING GRADE
NOTE:
FABRIC IS TO BE ON DISTURBED
SIDE OF STAKE.
ELEVATION
NO SCALE
Tree Protection Fence
PLAN
3.
2.
NOTES:
1.
6' TYP.
ALL DEBRIS, FILL, EQUIPMENT AND MATERIAL SHALL BE KEPT
CLEAR OF AREA WITHIN PROTECTIVE FENCE. NO CLEANING,
STORAGE, OR DISPOSAL OF ANY MATERIAL ALLOWED WITHIN
THE DRIP LINE OF TREES TO BE SAVED.
FENCE SHALL BE LOCATED AT THE OUTER PERIMETER OF
THE SPREAD OF THE BRANCHES OR CLOSER ONLY AT
THE DIRECTION OF THE PROJECT LANDSCAPE
ARCHITECT.
TREE PROTECTION FENCING SHALL BE ERECTED PRIOR TO
ANY EARTHWORK OR CONSTRUCTION AND IS TO REMAIN
IN PLACE UNTIL CONSTRUCTION IS COMPLETE.
PLASTIC CONSTRUCTION FENCE
STEEL FENCE POST
4' T
Y P.
CONSTRUCTION SEQUENCE
SEEDING AND EROSION BLANKETS
FOUNDATION / BUILDING CONSTRUCTION
PERMANENT CONTROL MEASURES
TOPSOIL / SEDIMENT CONTROL
TREE REMOVAL & STUMP GRINDING
TEMPORARY CONTROL MEASURES
FINISH GRADING
SITE CONSTRUCTION
TEMPORARY ACCESS
SITE UTILITIES
OPERATION TIME SCHEDULE (2026-2027)
CONSTRUCTION SEQUENCE
SEPT OCT NOV DEC JAN FEB MAR APR MAY JUN
TASK
X
C O
M
PO
N
EN
T
ST
O
RM
S
EW
ER
S Y
ST
EM
C A
TC
H
B A
SI
N
S U
M
PS
C A
TC
H
B A
SI
N
IN
LE
T C
A
SI
N G
S
BI
O
SW
A
LE
S
D
ET
EN
TI
O N
B A
SI
N
U N
D
ER
G
RO
U N
D D
ET
EN
TI
O
N
M A
N U
FA
C
TU
RE
D T
RE
A
TM
EN
T U
N
IT
S
O U
TL
ET
C O
N
TR
O L
ST
RU
C
TU
RE
S
EM
ER
G
EN
C Y
O V
ER
FL
O W
SCHEDULE
INSPECT FOR SEDIMENT ACCUMULATION WEEKLY
REMOVAL OF SEDIMENT ACCUMULATION AS NEEDED AND PRIOR TO TURNOVER
INSPECT FOR FLOATABLES AND DEBRIS QUARTERLY
REMOVAL OF FLOATABLES AND DEBRIS QUARTERLY AND AT TURNOVER
INSPECT FOR EROSION WEEKLY
RE-ESTABLISH VEGETATION ON ERODED SLOPES AS NEEDED AND PRIOR TO TURNOVER
REPLACEMENT OF STONE AS NEEDED*
RI
P
RA
P
MOWING 0 TO 2 TIMES PER YEAR
INSPECT STRUCTURAL ELEMENTS DURING WET
WEATHER AND COMPARE TO AS-BUILT PLANS
(BY PROFESSIONAL ENGINEER)
ANNUALLY AND PRIOR TO TURNOVER
MAKE ADJUSTMENTS OR REPLACEMENTS AS
DETERMINED BY PRE-TURNOVER INSPECTION
AS NEEDED
X X X X X
X X X X X X
X X X X X X
X X X X X X
X X X
X X
X
X X
X X X X X X X
X X X X X X X X X
XXX
MAINTENANCE SCHEDULE (DURING CONSTRUCTION BY GC)
Control Details
Inlet Protection-Fabric Drop
INSTALLATION DETAIL
STANDARD SYMBOL
2'-0"
ISOMETRIC VIEW
4'-0"
3' -0
INLET
GRATE
1" REBAR FOR
BAG REMOVAL
FROM INLET
TASK
X
C O
M
PO
N
EN
T
SCHEDULE
INSPECT FOR SEDIMENT ACCUMULATION ANNUALLY
REMOVAL OF SEDIMENT ACCUMULATION ANNUALLY AS NEEDED
INSPECT FOR FLOATABLES AND DEBRIS
REMOVAL OF FLOATABLES AND DEBRIS
INSPECT FOR EROSION
RE-ESTABLISH VEGITATION ON ERODED SLOPES AS NEEDED
REPLACEMENT OF STONE EVERY 3-5 YEARS AS NEEDED
MOWING 0 TO 2 TIMES PER YEAR
INSPECT STRUCTURAL ELEMENTS DURING WET
WEATHER AND COMPARE TO AS-BUILT PLANS
(BY PROFESSIONAL ENGINEER)
ANNUALLY
MAKE ADJUSTMENTS OR REPLACEMENTS AS
DETERMINED BY INSPECTION
AS NEEDED
X
X X
X X
X X
X
X
X X X X
X X X
CLEAN STREETS, DRIVES AND PARKING AREAS 0 TO 2 TIMES PER YEAR
ANNUALLY
ANNUALLY AS NEEDED
ANNUALLY
ST
O
RM
S
EW
ER
C
U
LV
ER
TS
SW
A
LE
S
SE
D
IM
EN
TA
TI
O N
B A
SI
N
S
RI
P
RA
P
X
X
X
X
X X
X X
X X
X
MAINTENANCE SCHEDULE (POST CONST. BY
OWNER)
JUL
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C7.1
Site Details
NO SCALE
Concrete Curb & Gutter \ MDOT F2
5 1
4" 4"
4"
9"
2"R
2"R "
7 8
"1 2 "
6"
DROP CURB
CONCRETE CURB &
GUTTER WITH LIGHT
BROOM FINISH PARALLEL
TO ROADWAY
6" COMPACTED MDOT 21AA
LIMESTONE BASE
COMPACTED SUBGRADE
#4 REBAR
1'-6"
4 Bituminous Pavement - Standard & Heavy Duty
SCALE: 1" = 1'-0"
1.
5"
1.
5"
6"
5'-0"
NO SCALE
Typical Curb Ramps at Parking Lot
Concrete Sidewalk / Pavement
NO SCALE
FILLER, HELD DOWN 1/2"
TO DIRECTION OF TRAVEL
FINISH PERPENDICULAR
HAND-TOOLED CONTROL JOINT
APPROVED COMPACTED SUBBASE
WITH 1/2" PREMOLDED
TYPICAL EXPANSION JOINT
MEDIUM BROOM
CONCRETE WALK WITH
1/4 DEPTH OF SLAB
1/4"
1/4" R 1/4" R
ST
A
N D
A
RD
D U
TY
H
EA
V Y
D U
TY
4" 4"
6" 8"
NO SCALE
Thickened Edge Walk at Beach
12"MIN.
6" 8"
C7.1
CONCRETE SIDEWALK/PAVEMENT
ADJACENT STANDARD DUTY
SIDEWALK
BITUMINOUS WEARING COURSE
TACK COAT AS SPECIFIED
BITUMINOUS LEVELING COURSE
PLACE AND COMPACT NEW
AGGREGATE BASE AS SPECIFIED
PROOF ROLL SUBGRADE
STANDARD
DUTY
SEAL JOINTS AT BUILDING
WALLS AND
FOUNDATIONS PER
4 x 4 x W4 WWF AT CENTER OF
CONCRETE ( HEAVY DUTY ONLY)
60°
COMPACTED BASE,
AS SPECIFIED.
1-1/2"ROUNDED
EDGE
EXISTING ADJACENT
BEACH
(2) #4 BARS, EPOXY
COATED, 3" COVER
MIN.
Sand Tracking Mat (Alternate No. 3)
ANCHOR SPIKES
RIGID CONNECTOR
EYELET
WOVEN FIBER MAT
ANCHOR SPIKES
RIGID CONNECTOR
NOTES:
SEE SPECIFICATIONS FOR PRODUCT
DESCRIPTION. FOLLOW
MANUFACTURES INSTALLATION
MANUAL.
ANCHOR SPIKES PROVIDED BY
MANUFACTURER TO BE
INSTALLED PER SPECIFICATION
CONNECTING MAT-PLAN VIEW
CONNECTION TO ADJOINING MAT
2" 2"
8"
HEAVY
DUTY
EXISTING AGGREGATE BASE
MAINTAIN UNIFORM THICKNESS
*= CONTRACTOR IS GIVEN THE OPTION OF RE-USING UP TO 4 INCHES
OF EXISTING AGGREGATE BASE WITH REMAINING DIMENSION OF
AGGREGATE BASE BEING NEW/IMPORTED AS SPECIFIED.
WOVEN FIBER MAT
6' - 6"
C7.1
CONCRETE
SIDEWALK/PAVEMENT
C7.1
UNIT RETAINING
WALL
SMOOTH SAND BENEATH
MAT BEFORE
INSTALLATION, CLEAR
ALL DEBRIS AND ROCK.
2% LATERAL SLOPE MAX
SAND
LEVEL
LANDING
0.0' 0.0'
0.0' 0.0'
0.0' 0.0'
0.5' 0.5'
0.62'0.62'
0.62' 0.62'
0.62' 0.62' 0.12' 0.12'
LAWN
BITUMINOUS
PAVEMENT
2% 2%2%
EJ EJ
CJ
CJ CJ
INTEGRAL RAMP CURB - TOP OF
CURB ELEVATION CONSTANT
WITH BACK OF WALK
8' SIDEWALK
CURB TAPERS
6" IN 12'
FLUSH CURB
6'-0" VARIES 6'-0" RAMP TYPE 2
6' -0
RAMP TYPE 1
BATTER AS
SPECIFIED
BURY MIN. 2 UNITS
BASE COURSE
MAINTAIN LEVEL
EXISTING BEACH SAND
BW
WALL UNIT. INSTALL MIX OF
SMALL, MEDIUM AND
LARGE UNITS. SEE NOTES
FOR UNIT SIZES
ADHESIVE
LOCATION PIN
COPING UNIT
NOTES:
USE CORNER UNITS FOR ALL 90 DEGREE CORNERS
UNIT SIZES, LARGE: 15" - 5.625" - 9", MEDIUM: 12.625" -
5.875" - 9", SMALL: 9.875" - 5.875" - 9", COPING: 12.625"
- 3" - 11.875"
TW
C7.1
SEE CONCRETE/SIDEWALK
PAVEMENT DETAIL
COMPACTED BASE MDOT 21 AA
COMPACTED SUBGRADE
FILTER FABRIC AS SPECIFIED
EXPANSION JOINT
1.5% SLOPE
TOP OF WALK
ELEVATION VARIES, SEE
GRADING SHEET, C5.0
12"
MIN
SCALE: 1" = 1' - 0"
Unit Retaining Wall
WALL TYPE 1
BATTER AS
SPECIFIED
BURY MIN. 2 UNITS
BASE COURSE
MAINTAIN LEVEL
EXISTING BEACH SAND
BW
WALL UNIT. INSTALL MIX OF
SMALL, MEDIUM AND
LARGE UNITS. SEE NOTES
FOR UNIT SIZES
ADHESIVE
LOCATION PIN
COPING UNIT
TW
C7.1
SEE CONCRETE/SIDEWALK
PAVEMENT DETAIL
COMPACTED BASE MDOT
21 AA, 12" DEPTH
COMPACTED
SUBGRADE
FILTER FABRIC AS
SPECIFIED
EXPANSION JOINT
1.5% SLOPE
TOP OF WALK FLUSH
WITH COPING STONE
12"
MIN
WALL TYPE 2
DRAINAGE STONE AS SPECIFIED
BEHIND WALL
DRAINAGE STONE AS SPECIFIED
BEHIND WALL
RAMP
MIN.ROLLED CURB
"NON-WALKING"
AREA
"NON-WALKING"
AREA
5' -0
M
IN
18", TYP.
C7.1
6" DIAMETER PERFORATED
DRAIN TILE AT 0.5%,
DAYLIGHT AT WALL ENDS
6" DIAMETER PERFORATED DRAIN TILE
AT 0.5%, DAYLIGHT AT WALL ENDS
ALL LOCATIONS WHERE ALL PROPOSED
CONCRETE PAVEMENT OR BASE SLAB
NOTE: SEALANT JOINT TO OCCUR AT
1/2"
1/ 2"
COMPACTED BASE
1/2" PREMOLDED EXPANSION
POLYSEALANT
MATERIAL
BACKER ROD
WALL
OR FOUNDATION
ABUTS BUILDING WALLS
CONCRETE WALK
(WHERE APPLICABLE)
ADJACENT WALK OR PAVEMENT
(WHERE APPLICABLE)
Expansion Joint W/ Backer Rod and Sealant
NO SCALE
NOTES:
UTILIZE THIS DETAIL AT LEADING EDGE OF
ALL WALKWAY ADJACENT TO BEACH, AS
INDICATED
SEE GRADING
PLAN
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C7.2
Site Details
6 Bench, Surface Mount By Owner - Reference Detail Only
NO SCALE
LANDSCAPE FORMS
SCARBOROUGH BENCH, 96"
BACKED, OR APPROVED
ALTERNATE (BY OWNER)
(4) ANCHOR BOLTS AS
RECOMMENDED BY MFR.
CORE DRILL BRICK,
BITUMINOUS SETTING BED
AND CONCRETE SLAB TO
ACCEPT ANCHOR BOLT
(MIN. 4-1/2" EMBEDMENT
IN CONCRETE). EPOXY
GROUT BOLT TO CONCRETE
SLAB (BY OWNER)
COMPACTED SUBGRADE
8-0"
2' -9
.7 5"
4", TYP.
ALL SIDES
6"
SCALE 1/4" = 1' - 0"
Standard Parking Striping
NOTE:
DIMENSIONS ARE TYPICAL FOR
EACH PARKING STALL UNLESS
NOTED OTHERWISE ON PLANS
4" PAINTED STRIPE
A S
D
IM
EN
SI
O N
ED
O
N P
LA
N
AS DIMENSIONED
ON PLAN
SCALE: 1" = 1'-0"
Precast Bollard
12"12"7"
4"
PRECAST CONCRETE BOLLARD
SET BOLLARD WITH (1) 1/2" SS
DOWELS (BOLLARD PREDRILLED),
DRILL PVMT. & SET WITH EPOXY
TURN DOWN SLAB 12",
3'x3' AREA
COMPACTED GRANULAR MATERIAL
COMPACTED SUBGRADE
1 Precast Concrete Bumper Block
SCALE: 3/4" = 1'-0"
IN BITUMINOUS PAVEMENTIN GRAVEL
A
A'
SECTION A-A'
CL
CL
3/4" DIA. HOLE TO
ACCOMMODATE REBAR
3 PER BUMPER BLOCK
#4 VERT. REBAR 3 PER
BUMPER BLOCK
#4 HORIZ. REBAR 2" MIN.
COVER 2 PER BUMPER
BLOCK
3' -6
8"
2"
4 1/2"
TYP.
8'-0"
9" 9"
4" 4"
6"
1"
SCALE 1/4" = 1' - 0"
Barrier Free Parking Stall Striping o
AS DIMENSIONED
ON PLAN
AS DIMENSIONED
ON PLAN
36"
NO SCALE
Regulatory Signage
10" DIAMETER
3' -6
M
IN
2' -6
6'
-8
FORM TOP 6" OF FOOTING
V A
RI
ES
VARIES
CONCRETE FOOTING - SLOPE TOP TO
DRAIN
4" X 13
4" TELESPAR
REGULATORY SIGN AS SHOWN ON LAYOUT
AND PER MI MANUAL OF UNIFORM TRAFFIC
CONTROL DEVICES (MMUTCD)
SQUARE 12 GUAGE
PERFORATED TUBING AS MF'D
BY UNISTRUT, BLACK FINISH
SUPPLEMENTAL PLAQUE
AT VAN-ACCESSIBLE PARKING SPACES
MESSAGE QTY MMUTCD SIZE
STOP 01 R1-1 36 X 36"
RESERVED PARKING ADA ONLY 05 K2-1220 12 X 18"
VAN ACCESSIBLE (PLAQUE) 01 K-1479 12 X 6"
AUTHORIZED VEHICLES ONLY 01 K-4298 12 X 18"
C7.1
CONCRETE SIDEWALK/PAVEMENT
NOT TO SCALE
Vehicular Bar Gate
2"DIA. x .375"
6-5/8" BOX HINGES
6-58" DIA. SCH40
4' -0
3'
-6
GALV STEEL
2" DIA. x .375" WALL
2" DIA. x .375" WALL
15'
1/4"x2"x1-1/2" LATCH
TABS WITH PADLOCK HOLE
2" DIA. x .375" WALL ALUMINUM
UPRIGHT WITH PRESSED CAP
15'
30'
1-5/8" DIA. x .375" WALL
ALUMINUM SUPPORTS
ALUMINUM BOTTOM RAIL
ALUMINUM TOP RAIL
POSTS CONCRETE
FILLED
ALUMINUM UPRIGHT
NOTE:
VEHICULAR BAR GATE DEPICTED IS
SCHEMATIC; CONTRACTOR SHALL
SUBMIT SHOP DRAWINGS FOR
REVIEW AND APPROVAL.
BITUMINOUS PAVEMENT 4
C7.1
Section
SCALE: 1/4"=1'-0"
FACE OF CURB
UNIVERSAL BARRIER
FREE PARKING
SYMBOL
4" BLUE PARKING
SPACE STRIPE
FACE OF CURB
4" BLUE
AISLE STRIPE
NIC
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C7.3
Site Details
8'-6"
6' -6
9'-0"
46"
7' -0
67"
44"
46" 44"
3' -3
3'
-3
8' -6
2' -7
4'-3" 4'-3"
10'-6"
2'-11 7/8"
7'-0"W X 9'-0"L X 9'-3"H 6'-6" X 8'-6"
Contact Station (Alternate No. 1)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
XX
X
X
X X
X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X
X
X
X
SN
UGE
UGE
UGE
UGE UGE
UGE
UGE
co
UD UD UD UD
U D
UD
UD
UD
UD
UD
U D
UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD
UD
UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD UD
UD
UD
UD
UD
UD
U D
UD
UD
UD
Checked: NA / CS
2023087
Approved: CS
Drawn: MK / NA / NJ
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder RB i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
6030150 90 FEET
Know what's below.
before you dig.Call
R
1" = 30'
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
Bidding08.19.2026
C8.0
Seeding & Restoration Plan
LANDSCAPE LEGEND
LANDSCAPE RESTORATION
4" TOPSOIL AND HYDRO SEED
LANDSCAPE NOTES
1. TOPSOIL (4") AND HYDRO SEED ALL DISTURBED TURF AREAS.
2. ALL IMPORTED TOPSOIL SHALL BE SCREENED AND BE APPROVED BY LANDSCAPE
ARCHITECT/ENGINEER PRIOR TO INSTALLATION. PROVIDE CERTIFICATION FOR ALL
IMPORTED TOPSOIL.
PROPOSED
PICNIC SHELTER
PROPOSED
RESTROOM
M - 115
C
LA
M L
A K
E C
A N
A L
LAKE MITCHELL
(ALT NO. 3)
(ALT NO. 2)
CODE REVIEW
CURRENT APPLICABLE CODES
BUILDING: 2021 MICHIGAN BUILDING CODE
PLUMBING: 2021 MICHIGAN PLUMBING CODE
MECHANICAL: 2021 MICHIGAN MECHANICAL CODE
ELECTRICAL: 2023 NATIONAL ELECTRIC CODE
ACCESSIBILITY 2017 ANSI A117.1 STANDARDS FOR ACCESSIBILITY
CODE ANALYSIS
CONSTRUCTION: MASONRY CONSTRUCTION
FLOOR AREA: FIRST FLOOR - 986 SQ FT
CONSTRUCTION CLASSIFICATION: V B - TABLE 601
USE GROUP A-3 ASSEMBLY
MAXIMUM ALLOWABLE AREA 6,000 SQ FT - TABLE 506.2
FIRE RESISTANCE REQUIREMENTS - TABLE 601
PRIMARY STRUCTURE - 0 HOUR
- EXTERIOR BEARING WALLS - 0 HOUR
- INTERIOR BEARING WALLS - 0 HOUR
- EXTERIOR NON BEARING WALLS - 0 HOUR
- INTERIOR NON BEARING WALLS - 0 HOUR
- FLOOR CONSTRUCTION - 0 HOUR
- ROOF CONSTRUCTION - 0 HOUR
OCCUPANT LOAD: 986 / 50 - 20 - TABLE 1004.1.2
MALE - 10
FEMALE - 10
REQUIRED PLUMBING WATER CLOSETS ( MEN ) - 1 PER 125
WATER CLOSETS ( WOMEN ) - 1 PER 65
LAVATORIES ( MEN ) - 1 PER 200
LAVATORIES ( WOMEN ) - 1 PER 200
PLUMBING PROVIDED WATER CLOSETS ( MEN) - 2
URINALS (MEN) - 2
WATER CLOSETS ( WOMEN ) - 4
LAVATORIES ( MEN ) - 2
LAVATORIES ( WOMEN ) - 2 Checked: PF
2023087
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
G1.0 RS
General information
Checked: PF
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A1.0 RS
Floor Plan
RCP GENERAL NOTES:
• SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURE
SCHEDULES, ELECTRICAL NOTES, RISERS & DETAILS
Checked: PF
2023087
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A2.0 RS
Reflected Ceiling Plan
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A3.0 RS
Exterior Elevations
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A4.0 RS
Building Section
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A4.1 RS
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A4.2 RS
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A4.3 RS
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A5.0 RS
Exterior Details
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A6.0 RS
Enlarged Plan & Interior Elevations
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A6.1 RS
Enlarged Plan, Interior Elevations & Details
• Checked: PF
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A6.2 RS
Interior Details
Checked: PF
2023087
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
A7.0 RS
Door and Window Schedules
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
Restroom Structure
S0.1 RS
Structural General Notes
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering & Landscape Architecture
Beckett & Raeder, Inc.
Ann Arbor, MI 48103
663.2622 663.6759 ph fx
Beckett&Raeder i
Day Use Improvements William Mitchell State Park
Cadillac, Michigan
Environmental Services
Owner Review05.29.2026
Permitting08.07.2026
751/23309.HJD
As shown
Bidding08.19.2026
S0.2 RS
Structural Details
Restroom Structure
2023087
Approved: RMO
Drawn: RMO
Issued forDates
535 West William, Suite 101
Planning, Engineering &…