Bid Drawings Replace Mortar and Brick.pdf
PDF 10 MB Posted
- Solicitation number
- 36C24423B0003
About this file
This document provides details on a federal contract opportunity to repair mortar and brick on Building No. 1. The solicitation number is 36C24423B0003 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 4 for Project No. 503-19-110. The opportunity type is a solicitation to repair mortar and brick for NRM 503-19-110 on Building No. 1. A bid drawing file titled "Replace Mortar and Brick.pdf" is referenced but its content is not listed. No further information is provided on response dates, award dates, pricing terms, or set asides.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24423B0003 0001 Technical Q and A.docx | DOCX document | |
| 002 01 33 23 Shop Dwgs Data and Samples.doc | DOC document | |
| 36C24423B0003.docx | DOCX document | |
| Bid Specifications Repair Mortar and Brick.pdf | ||
| Wage Determination PA20230077 1-13-2023.pdf | ||
| 010000 General Requirements 503-19-110.pdf | ||
| Statement of Work Repair Mortar and Brick.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
03/01/2021
Location
Issue Date
B
A
C
D
E
F
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
COVER SHEET
GI001
RPSF
LOADING DOCK
RENOVATION OF DAMAGED
EXTERIOR WALL
BUILDING 1 MASONRY
AND MORTAR REPAIR
BUILDING 1 MASONRY
AND MORTAR REPAIR
BUILDING 1
ROOF REPLACEMENT
B U
IL
D
IN
G
R O
F
E
P L A
C E M
E N
T
B U
IL
D
IN
G
F
E
P L A
C E M
E N
T
BUILDING 1 MASONRY
AND MORTAR REPAIR
A101
SIM
A101
SIM
A101
SIM
BUILDING SECTIONDetail No.
Sheet No.
Reference Label
Detail No.
Sheet No.
Reference Label
Detail No.
Sheet No.
Reference Label
Room No.
Room Area
Insulation
Partition Configuration
Partition Configuration
ALIGN
SECTION
DETAIL CALLOUT
ROOM TAG
DOOR TAG
PARTITION TAG
KEYNOTE
ALIGNED SURFACES
Room Name
150 SF
Room Name
Area
AREA TAG
Area NameArea Name
150 SF
F 1 aSCOPE OF PROJECT Project Limit Line
CENTERLINE
COLUMN GRID LINE
ELEVATION
WINDOW TYPE TAG1t
SLOPE INDICATOR
DATA POINT
NORTH ARROW
Xx.x
Xx.x
Sheet No.
Detail No.
1 Revision Reference Number
Revision Cloud Depicting Area Revised
REVISION
CEILING TAG
XX-1
1'-0"A.F.F. Clg Height
Clg Type
Plan North
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AS100CM/NBEB/MR3/1/2021
SITE PLAN
LEGEND
1" = 20'-0"F1 SITE PLAN
NORTH
PROJECT CODE SUMMARY
PROJECT SUMMARY:
THE PROJECT CONSISTS OF INVESTIGATION AND REPAIR SOLUTION TO MASONRY & MORTAR ISSUES RELATED TO THE EXTERIOR
WALLS ON BUILDING 1 AND THE RECONFIGURED LOADING DOCK.
SITE PLAN NOTE:
CONTRACTOR SHALL COORDINATE SIZE AND LOCATION OF STAGING AREA FOR MATERIAL STORAGE AND TRAILER WITH COR
PRIOR TO COMMENCING ANY WORK.
APPLICABLE CODES _________________
2015 INTERNATIONAL BUILDING CODE (IBC)
2015 INTERNATIONAL FIRE CODE (IFC)
2015 INTERNATIONAL FUEL GAS CODE (IFGC)
2015 INTERNATIONAL MECHANICAL CODE (IMC)
2015 INTERNATIONAL PLUMBING CODE (IPC)
2014 NATIONAL ELECTRICAL CODE (NEC)
2015 INTERNATIONAL EXISTING BUILDING CODE (IEBC)
NFPA 99 - HEALTHCARE FACILITIES
NFPA 101 - LIFE SAFETY CODE
NFPA 220 - STANDARD ON TYPES OF BUILDING CONSTRUCTION
EXISTING CONSTRUCTION TO BE DEMOLISHED
EXISTING CONSTRUCTION TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE REMOVED (DEMO)
1. THE CONSTRUCTOR SHALL PROVIDE PROTECTION FOR ALL THE GENERAL
PUBLIC AND CONSTRUCTION WORKERS IN AND AROUND THE CONSTRUCTION
SITE. ADEQUATE BARRIERS SHALL BE PROVIDED TO EXERCISE CONTROL OF
SAFE EGRESS AND EGRESS OF PREMISE. FIRE EXITS SHALL AT NO TIME BE
BLOCKED.
2. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED BUT NECESSARY FOR
PROPER CONSTRUCTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS
IF THEY WERE INDICATED ON THE DRAWINGS.
3. THE CONSTRUCTOR SHALL BE RESPONSIBLE FOR MAINTAINING WATERTIGHT
INTEGRITY OF THE BUILDING AT ALL TIMES. ALL WATER DAMAGE SHALL BE
REPAIRED AT NO ADDITIONAL COST AND TO THE SATISFACTION OF THE
GOVERNMENT.
4. THE CONSTRUCTION AREA SHALL BE THROUGHLY CLEANED.
5. ALL WORK TO BE PERFORMED OFF SCAFFOLD SUPPLIED BY THE CONTRACTOR
WITH A CERTIFIED SCAFFOLD ERECTORS LICENSE, INSURANCE AND OSHA
APPROVED TRAINING. PROOF OF THESE REQUIREMENTS WILL BE REQUIRED
PRIOR TO ANY WORK. CONTRACTOR IS TO VERIFY THE WEIGHT LIMITS OF THE
EXISTING ROOFING WITH A STRUCTURAL ENGINEER. ENGINEER, REPORTS
WILL BE REQUIRED PRIOR TO INSTALLING ANY SCAFFOLD ON ANY ROOFS.
THE VA WILL SUPPLY STRUCTURAL DRAWINGS TO THE CONTRACTOR. THE
CONTRACTOR IS TO FOLLOW ALL FEDERAL, STATE, LOCAL AND VA GUIDELINES
AND STANDARDS.
6. ALL OSHA REGULATION ARE TO BE FOLLOWED BY ALL CONTRACTING
PERSONNEL. PRIME CONTRACTOR (ON SITE PERSONNEL) TO HAVE 30 HOUR
OSHA SAFETY TRAINING AND A 10 HOUR OSHA SAFETY CERTIFICATE.
7. REFER TO OTHER CONTRACT DOCUMENTS FOR DEMOLITION REQUIREMENTS
8. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT
THE JOB SITE AND SHALL REPORT, ANY DISCREPANCIES TO THE GOVERNMENT
PRIOR TO STARTING CONSTRUCTION. BEFORE COMMENCEMENT OF WORK,
THE CONTRACTOR SHALL IMPLY HIS ACCEPTANCE OF ALL EXISTING
CONDITIONS. DIMENSION SHOWN ON PLANS ARE TO THE FINISH TO FINISH
UNLESS NOTED OTHER WISE.
9. THE DEMOLITION PLANS ARE DERIVED FROM EXISTING BUILDING PLANS AND
ARE INTENDED TO REASONABLY REPRESENT EXISTING AND CURRENT
CONDITIONS. ALL DIMENSIONS AND INFORMATION IN THESE DRAWINGS ARE
BASED, IN PART, ON THAT FACT. ACTUAL CONDITIONS MAY VARY FROM THAT
SHOWN. NOTIFY THE ARCHITECT IMMEDIATELY FOR REVIEW SHOULD ANY
DISCREPANCIES WHICH SIGNIFICANTLY AFFECT THE DEMOLITION OR NEW
CONSTRUCTION WORK OCCUR.
10. PROTECT EXISTING CONSTRUCTION, SURFACES AND MATERIALS INDICATED
TO REMAIN FROM DAMAGE OR DETERIORATION DUE TO PERFORMANCE OF
WORK. PATCH AND REPAIR EXISTING MATERIALS AND SURFACES DAMAGED BY
PERFORMANCE OF THE WORK.
11. IF MATERIALS ARE ENCOUNTERED THAT MAYBE HAZARDOUS OR MAY CONTAIN
HAZARDOUS COMPONENTS, CEASE WORK IMMEDIATELY, PREVENT FURTHER
DISTURBANCE, SECURE THE AREA AND NOTIFY THE COR.
12. DO NOT CUT STRUCTURAL COMPONENTS UNLESS INDICATED OTHERWISE.
13. COORDINATE REMOVAL OF DEMOLISHED MATERIALS WITH COR. PREVENT
DUST AND DEBRIS FROM INFILTRATING OCCUPIED AREAS. PROVIDE
ENCLOSED CHUTES AND NEGATIVE AIR PRESSURE AS REQUIRED. DISPOSE OF
DEMOLISHED MATERIALS IN LAWFUL MANNER, OFF SITE.
14. MATERIALS AND COMPONENTS TO BE SALVAGED ARE INDICATED. REMOVE
SALVAGE ITEMS AS COMPLETE UNITS TO THE EXTENT POSSIBLE AND
PROTECT FROM FURTHER DAMAGE. CLEAN COMPONENTS OF DUST AND DIRT.
STORE ON SITE AS DIRECTED BY COR.
15. COORDINATE SCHEDULE WITH COR PRIOR TO COMMENCING DEMOLITION
WORK THAT MAY INTERRUPT SERVICES. SCHEDULE WORK AND PROVIDE
TEMPORARY CONNECTIONS OR NEW SERVICES AS NECESSARY TO ELIMINATE
DISRUPTIONS AFFECTING THE OWNER'S OPERATIONS.
AD101
F4
PROJE
CT L
IM
IT
L
IN
E
RECEIVING
W203
WAREHOUSE
W202
RECEIVING
WAREHOUSE
CORRIDOR
AE201
F7
KEYPLAN
GROUND
0' - 0"
LOADING DOCK
FLOOR
2' - 10"
7 7
11 11
10' - 2" +/-
F3
AE301
SHEET NOTES
LEGEND
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
LOADING DOCK
AD101CM/NBEB/MR3/1/2021
DEMOLITION PLAN & ELEVATION
1/4" = 1'-0"F1 DEMOLITION PLAN - LOADING DOCK
1/2" = 1'-0"F4 DEMOLITION ELEVATION - LOADING DOCK
NORTH
NOTE:
MAINTAIN CONTINUOUS ACCESS TO EXISTING LOADING DOCK DURING ALL DEMOLITION AND
CONSTRUCTION PHASES.
KEYNOTES
# NOTE
1 SAW-CUT AND DEMO PORTION OF EXISTING MASONRY WALL
2 DISASSEMBLE AND SAFELY STORE OVERHEAD DOOR
3 EXISTING OVERHEAD DOORS TO REMAIN
4 EXISTING MASONRY WALL TO REMAIN
5 EXISTING DOCK LEVELER AND PIT TO REMAIN
6 EXISTING STAIRS & HANDRAILS TO REMAIN
7 EXISTING FOUNDATION WALL TO REMAIN
8 DEMOLISH PORTION OF METAL FASCIA AND EXTENSION
9 SEAL OFF OPENING WITH TEMPORARY FIRE RATED BARRIER
10 DEMOLISH DAMAGED TRUCK SHELTER ENCLOSURE
11 DEMOLISH TRUCK BUMP GUARDS
EXISTING CONSTRUCTION TO BE DEMOLISHED
EXISTING CONSTRUCTION TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE REMOVED (DEMO)
1. THE CONSTRUCTOR SHALL PROVIDE PROTECTION FOR ALL THE GENERAL
PUBLIC AND CONSTRUCTION WORKERS IN AND AROUND THE CONSTRUCTION
SITE. ADEQUATE BARRIERS SHALL BE PROVIDED TO EXERCISE CONTROL OF
SAFE EGRESS AND EGRESS OF PREMISE. FIRE EXITS SHALL AT NO TIME BE
BLOCKED.
2. MINOR DETAILS NOT USUALLY SHOWN OR SPECIFIED BUT NECESSARY FOR
PROPER CONSTRUCTION OF ANY PART OF THE WORK SHALL BE INCLUDED AS
IF THEY WERE INDICATED ON THE DRAWINGS.
3. THE CONSTRUCTOR SHALL BE RESPONSIBLE FOR MAINTAINING WATERTIGHT
INTEGRITY OF THE BUILDING AT ALL TIMES. ALL WATER DAMAGE SHALL BE
REPAIRED AT NO ADDITIONAL COST AND TO THE SATISFACTION OF THE
GOVERNMENT.
4. THE CONSTRUCTION AREA SHALL BE THROUGHLY CLEANED.
5. ALL WORK TO BE PERFORMED OFF SCAFFOLD SUPPLIED BY THE CONTRACTOR
WITH A CERTIFIED SCAFFOLD ERECTORS LICENSE, INSURANCE AND OSHA
APPROVED TRAINING. PROOF OF THESE REQUIREMENTS WILL BE REQUIRED
PRIOR TO ANY WORK. CONTRACTOR IS TO VERIFY THE WEIGHT LIMITS OF THE
EXISTING ROOFING WITH A STRUCTURAL ENGINEER. ENGINEER, REPORTS
WILL BE REQUIRED PRIOR TO INSTALLING ANY SCAFFOLD ON ANY ROOFS.
THE VA WILL SUPPLY STRUCTURAL DRAWINGS TO THE CONTRACTOR. THE
CONTRACTOR IS TO FOLLOW ALL FEDERAL, STATE, LOCAL AND VA GUIDELINES
AND STANDARDS.
6. ALL OSHA REGULATION ARE TO BE FOLLOWED BY ALL CONTRACTING
PERSONNEL. PRIME CONTRACTOR (ON SITE PERSONNEL) TO HAVE 30 HOUR
OSHA SAFETY TRAINING AND A 10 HOUR OSHA SAFETY CERTIFICATE.
7. REFER TO OTHER CONTRACT DOCUMENTS FOR DEMOLITION REQUIREMENTS
8. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS AT
THE JOB SITE AND SHALL REPORT, ANY DISCREPANCIES TO THE GOVERNMENT
PRIOR TO STARTING CONSTRUCTION. BEFORE COMMENCEMENT OF WORK,
THE CONTRACTOR SHALL IMPLY HIS ACCEPTANCE OF ALL EXISTING
CONDITIONS. DIMENSION SHOWN ON PLANS ARE TO THE FINISH TO FINISH
UNLESS NOTED OTHER WISE.
9. THE DEMOLITION PLANS ARE DERIVED FROM EXISTING BUILDING PLANS AND
ARE INTENDED TO REASONABLY REPRESENT EXISTING AND CURRENT
CONDITIONS. ALL DIMENSIONS AND INFORMATION IN THESE DRAWINGS ARE
BASED, IN PART, ON THAT FACT. ACTUAL CONDITIONS MAY VARY FROM THAT
SHOWN. NOTIFY THE ARCHITECT IMMEDIATELY FOR REVIEW SHOULD ANY
DISCREPANCIES WHICH SIGNIFICANTLY AFFECT THE DEMOLITION OR NEW
CONSTRUCTION WORK OCCUR.
10. PROTECT EXISTING CONSTRUCTION, SURFACES AND MATERIALS INDICATED
TO REMAIN FROM DAMAGE OR DETERIORATION DUE TO PERFORMANCE OF
WORK. PATCH AND REPAIR EXISTING MATERIALS AND SURFACES DAMAGED BY
PERFORMANCE OF THE WORK.
11. IF MATERIALS ARE ENCOUNTERED THAT MAYBE HAZARDOUS OR MAY CONTAIN
HAZARDOUS COMPONENTS, CEASE WORK IMMEDIATELY, PREVENT FURTHER
DISTURBANCE, SECURE THE AREA AND NOTIFY THE COR.
12. DO NOT CUT STRUCTURAL COMPONENTS UNLESS INDICATED OTHERWISE.
13. COORDINATE REMOVAL OF DEMOLISHED MATERIALS WITH COR. PREVENT
DUST AND DEBRIS FROM INFILTRATING OCCUPIED AREAS. PROVIDE
ENCLOSED CHUTES AND NEGATIVE AIR PRESSURE AS REQUIRED. DISPOSE OF
DEMOLISHED MATERIALS IN LAWFUL MANNER, OFF SITE.
14. MATERIALS AND COMPONENTS TO BE SALVAGED ARE INDICATED. REMOVE
SALVAGE ITEMS AS COMPLETE UNITS TO THE EXTENT POSSIBLE AND
PROTECT FROM FURTHER DAMAGE. CLEAN COMPONENTS OF DUST AND DIRT.
STORE ON SITE AS DIRECTED BY COR.
15. COORDINATE SCHEDULE WITH COR PRIOR TO COMMENCING DEMOLITION
WORK THAT MAY INTERRUPT SERVICES. SCHEDULE WORK AND PROVIDE
TEMPORARY CONNECTIONS OR NEW SERVICES AS NECESSARY TO ELIMINATE
DISRUPTIONS AFFECTING THE OWNER'S OPERATIONS.
KEYPLAN
13 13
EXISTING BUILDING
151515
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AD102AuthorEB/MR3/1/2021
DEMOLITION ROOF PLAN
SHEET NOTES
LEGEND
3/32" = 1'-0"1 PARTIAL ROOF PLAN Copy 1
KEYNOTES
# NOTE
12 DEMOLISH EXISTING BALLAST MEMBRANE ROOFING AND INSULATION TO CONCRETE DECK;
PREPARE SUBSTRATE TO RECEIVE NEW FINISH
13 DEMOLISH EXISTING SHEET METAL WALL COPING; PREPARE SUBSTRATE TO RECEIVE NEW
FINISH
14 DEMOLISH EXISTING WALL FLASHING; PREPARE SUBSTRATE TO RECEIVE NEW FINISH
15 SALVAGE LIGHTNING PROTECTION SYSTEM. REINSTALL AND RECONNECT FOLLWING
INSTALLATION OF NEW ROOFING
16 DEMOLISH EXISTING FLASHING AT ROOF PENETRATIONS; PREPARE SUBSTRATE TO RECEIVE
NEW ROOFING
UP
PARTIAL HT PARTITION - SEE
ELEVATION FOR HEIGHT
NEW PARTITION
EXISTING CONSTRUCTION TO REMAIN
RATED PARTITION
EXISTING DOOR
NEW CONSTRUCTION DOOR
AE201
F1
F1
AE301
101PROJE
CT L
IM
IT
L
IN
E
RECEIVING
WAREHOUSE
CORRIDOR
RECEIVING
W203
WAREHOUSE
W202
AE504
D5
AE201
F7
F3
AE301
1' - 0"
C L
109109
KEYPLAN
1. CONTRACTOR IS NOT TO SCALE CONSTRUCTION DOCUMENTS. ARCHITECT AND OWNER ARE
TO BE NOTIFIED IN THE EVENT A DISCREPANCY IS FOUND IN EITHER SPECIFICATION OR
CONSTRUCTION DOCUMENTS AT THE EARLIEST PRACTICAL OPPORTUNITY.
2. GENERAL CONTRACTOR SHALL OBSERVE ALL REGULATIONS IMPOSED BY GOVERNING BODIES.
3. IF CONFLICT BETWEEN DRAWINGS, SPECIFICATIONS, AND REQUIREMENTS OF THE BUILDING
OWNER AND OR OPERATIONS ARISE, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT AND OWNER IMMEDIATELY.
4. THE CONTRACTOR SHALL CONTAIN ALL CONSTRUCTION ACTIVITY, INCLUDING STORAGE OR
MATERIAL AND EQUIPMENT WITHIN CONTRACT LIMITS, AT ALL TIMES BEING RESPONSIBLE FOR
AND ABIDING BY THE RULES AND REGULATIONS OF THE OWNER.
5. GENERAL CONTRACTOR IS TO BE RESPONSIBLE FOR REPAIRING ANY AND ALL SURFACES
DAMAGED BY HIMSELF OR SUBCONTRACTORS UNDER HIS CONTROL. REPAIRS ARE TO MATCH
EXISTING MATERIAL AND MUST BE ACCEPTABLE TO THE OWNER.
6. GENERAL CONTRACTOR SHALL REMOVE ALL CONSTRUCTION DEBRIS FROM JOBSITE. ALL
CONSTRUCTION DEBRIS SHALL BE CONTAINED WITHIN CONSTRUCTION LIMITS.
7. FURNISH AND INSTALL U.L. APPROVED FIRE STOPPING ASSEMBLIES AT ALL PENETRATIONS
THROUGH EXISTING AND NEW FIRE RATED CONSTRUCTION REQUIRED TO BY THE SCOPE OF
THIS PROJECT. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE TO FURNISH AND INSTALL
FIRE STOPPING ASSEMBLIES AT APPLICABLE CONSTRUCTION JOINTS TO ACHIEVE THE
IDENTIFIED RATING REQUIREMENTS.
8. REMOVE ONLY AS MUCH ROOFING THAT CAN BE REPLACED OR REPAIRED IN ONE WORKDAY.
THE ROOF SHALL BE MADE WATERTIGHT AT THE END OF EACH WORKDAY.
9. THE BUILDING WILL REMAIN IN OPERATION THROUGHOUT THE CONSTRUCTION PERIOD. THE
CONTRACTOR SHALL WALK THE ROOF AND ADJACENT AREAS TO BECOME FAMILIAR WITH THE
SITE CONDITIONS THAT AFFECT THE WORKING CONDITIONS AND CONSTRUCTION PRIOR TO
THE START OF CONSTRUCTION.
10. EXISTING ROOF CONDITIONS CONTAINED WITHIN THE CONSTRUCTION DOCUMENTS ARE BASED
ON THE INFORMATION OBTAINED FROM CONSTRUCTION DOCUMENTS AND FIELD SURVEY, AND
SHALL NOT BE CONSTRUED AS "AS BUILT". THE CONTRACTOR SHALL FIELD SURVEY EXISTING
CONDITIONS PRIOR TO ONSET OF CONSTRUCTION.
11. ALL ROOFING DETAILS SHOWN ARE DIAGRAMMATIC IN NATURE DUE TO THE NUMBER AND
VARYING CONDITIONS ON THE ROOF. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS
PRIOR TO CONSTRUCTION.
12. EXISTING LOADING DOCKS SHALL REMAIN ACCESSIBLE AND FULLY OPERATIONAL DURING
CONSTRUCTION.
13. NEW BRICKWORK AND MORTAR TO MATCH EXISTING - MOCK UP REQUIRED
F1
AE301
107107
107107
107107
AE201
F7
F3
AE301
SHEET NOTES
LEGEND
KEYNOTES
# NOTE
9 SEAL OFF OPENING WITH TEMPORARY FIRE RATED BARRIER
100 EXISTING DOCK LEVELER
101 EXISTING MASONRY WALL
102 SALVAGE EXISTING COILING DOOR PRIOR TO DEMOLTIION OF MASONRY. REINSTALL
FOLLOWING REPAIRS TO WALL
103 MASONRY WALL; MATCH EXISTING CONSTRUCTION
104 EXISTING ROOF DRAIN
106 OVERLAP AND SEAL FASCIA PER MFR. RECOMMENDATION
107 EXISTING BALASTED EPDM ROOFING SYSTEM
108 EXISTING OVERHEAD DOOR
109 EXISTING SHELTER ENCLOSURE
114 SURFACE MOUNTED CONTROL BOX FOR LED BACKUP SYSTEM; REF. EXTERIOR ELEVATION
206 NEW TRUCK SHELTER ENCLOSURE; REF. SPECS
208 NEW BOLLARD; REF. DETAIL AND SPECS
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AE101CM/NBEB/MR3/1/2021
LOADING DOCK PLAN & ROOF PLAN
1/4" = 1'-0"F1 FLOOR PLAN - LOADING DOCK
NORTH
1/4" = 1'-0"F4 ROOF PLAN - LOADING DOCK
NORTH
PARTIAL HT PARTITION - SEE
ELEVATION FOR HEIGHT
NEW PARTITION
EXISTING CONSTRUCTION TO REMAIN
RATED PARTITION
EXISTING DOOR
NEW CONSTRUCTION DOOR
1. CONTRACTOR IS NOT TO SCALE CONSTRUCTION DOCUMENTS. ARCHITECT AND OWNER ARE
TO BE NOTIFIED IN THE EVENT A DISCREPANCY IS FOUND IN EITHER SPECIFICATION OR
CONSTRUCTION DOCUMENTS AT THE EARLIEST PRACTICAL OPPORTUNITY.
2. GENERAL CONTRACTOR SHALL OBSERVE ALL REGULATIONS IMPOSED BY GOVERNING BODIES.
3. IF CONFLICT BETWEEN DRAWINGS, SPECIFICATIONS, AND REQUIREMENTS OF THE BUILDING
OWNER AND OR OPERATIONS ARISE, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT AND OWNER IMMEDIATELY.
4. THE CONTRACTOR SHALL CONTAIN ALL CONSTRUCTION ACTIVITY, INCLUDING STORAGE OR
MATERIAL AND EQUIPMENT WITHIN CONTRACT LIMITS, AT ALL TIMES BEING RESPONSIBLE FOR
AND ABIDING BY THE RULES AND REGULATIONS OF THE OWNER.
5. GENERAL CONTRACTOR IS TO BE RESPONSIBLE FOR REPAIRING ANY AND ALL SURFACES
DAMAGED BY HIMSELF OR SUBCONTRACTORS UNDER HIS CONTROL. REPAIRS ARE TO MATCH
EXISTING MATERIAL AND MUST BE ACCEPTABLE TO THE OWNER.
6. GENERAL CONTRACTOR SHALL REMOVE ALL CONSTRUCTION DEBRIS FROM JOBSITE. ALL
CONSTRUCTION DEBRIS SHALL BE CONTAINED WITHIN CONSTRUCTION LIMITS.
7. FURNISH AND INSTALL U.L. APPROVED FIRE STOPPING ASSEMBLIES AT ALL PENETRATIONS
THROUGH EXISTING AND NEW FIRE RATED CONSTRUCTION REQUIRED TO BY THE SCOPE OF
THIS PROJECT. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE TO FURNISH AND INSTALL
FIRE STOPPING ASSEMBLIES AT APPLICABLE CONSTRUCTION JOINTS TO ACHIEVE THE
IDENTIFIED RATING REQUIREMENTS.
8. REMOVE ONLY AS MUCH ROOFING THAT CAN BE REPLACED OR REPAIRED IN ONE WORKDAY.
THE ROOF SHALL BE MADE WATERTIGHT AT THE END OF EACH WORKDAY.
9. THE BUILDING WILL REMAIN IN OPERATION THROUGHOUT THE CONSTRUCTION PERIOD. THE
CONTRACTOR SHALL WALK THE ROOF AND ADJACENT AREAS TO BECOME FAMILIAR WITH THE
SITE CONDITIONS THAT AFFECT THE WORKING CONDITIONS AND CONSTRUCTION PRIOR TO
THE START OF CONSTRUCTION.
10. EXISTING ROOF CONDITIONS CONTAINED WITHIN THE CONSTRUCTION DOCUMENTS ARE BASED
ON THE INFORMATION OBTAINED FROM CONSTRUCTION DOCUMENTS AND FIELD SURVEY, AND
SHALL NOT BE CONSTRUED AS "AS BUILT". THE CONTRACTOR SHALL FIELD SURVEY EXISTING
CONDITIONS PRIOR TO ONSET OF CONSTRUCTION.
11. ALL ROOFING DETAILS SHOWN ARE DIAGRAMMATIC IN NATURE DUE TO THE NUMBER AND
VARYING CONDITIONS ON THE ROOF. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS
PRIOR TO CONSTRUCTION.
12. EXISTING LOADING DOCKS SHALL REMAIN ACCESSIBLE AND FULLY OPERATIONAL DURING
CONSTRUCTION.
13. NEW BRICKWORK AND MORTAR TO MATCH EXISTING - MOCK UP REQUIRED
AE202 F1
AE203
C1
110110
111 111
112112
AE203
F1
EXISTING BUILDING
AE203
F1
AE203
C1
110110
112112
110110
112112
113113113
111111
KEYPLAN
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AE102CM/NBEB/MR3/1/2021
BLDG 1 ROOF PLAN
SHEET NOTES
LEGEND
3/32" = 1'-0"F1 PARTIAL ROOF PLAN
NORTH
KEYNOTES
# NOTE
110 NEW EPDM MEMBRANE OVER MECHANICALLY FASTENED POLYISO TAPERED INSULATION; REF.
SPECIFICATIONS
111 NEW SHEET METAL WALL COPING; REF. DETAILS
112 PROVIDE NEW FLASHING FOR EXHAUST, ROOF DRAIN, WINDOW WASHING DAVIT; REF. DETAILS
113 LIGHTNING PROTECTION SYSTEM; INSTALL TO MATCH EXISTING
GROUND
0' - 0"
LOADING DOCK
ROOF
15' - 6"
LOADING DOCK
FLOOR
2' - 10"
F1
AE301
207 207
208 208
209 209
NEW EXISTINGNEWEXISTING
6"
3'
F3
AE301
8'
209209
209209 209209
108108
109 109
215215215215215
KEYPLAN
GROUND
0' - 0"
LOADING DOCK
ROOF
15' - 6"
LOADING DOCK
FLOOR
2' - 10"
NEWEXISTING
3'
F7
AE504
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AE201CM/NBEB/MR3/1/2021
LOADING DOCK ELEVATIONS
1/2" = 1'-0"F1 LOADING DOCK ELEVATION - NORTH
SHEET NOTES LEGEND
# NOTE
4 EXISTING MASONRY WALL TO REMAIN
7 EXISTING FOUNDATION WALL TO REMAIN
108 EXISTING OVERHEAD DOOR
109 EXISTING SHELTER ENCLOSURE
206 NEW TRUCK SHELTER ENCLOSURE; REF. SPECS
207 NEW TRUCK BUMP STOP; INSTALL PER MFR. INSTRUCTION; REF. SPECS
208 NEW BOLLARD; REF. DETAIL AND SPECS
209 NEW LED GUIDE LIGHTS, BACKUP WARNING LIGHTS, AND PROXIMITY SENSOR
215 NEW MIRROR VIEWABLE INSTRUCTION SIGN; REF. SPECS
216 REINSTALLED EXISTING COILING DOOR
217 CONTROL BOX ON THE INSIDE OF DOOR IN THIS LOCATION. SPLICE AND EXTEND LOCAL
120-VOLT BRANCH CIRCUIT TO CONTROL BOX. IF BRANCH CIRCUIT CURRENTLY FEEDS LIGHTING LOADS, ENSURE CIRCUIT IS SPLICED AHEAD OF ALL SWITCHING. PROVIDE 3/4" CONDUIT FROM
CONTROL BOX TO RED/GREEN LIGHT, GUIDE LIGHTS, AND SENSOR. SEE MANUFACTURER'S
RECOMMENDATIONS FOR FURTHER INFORMATION ON SYSTEM CONNECTIONS AND WIRING
REQUIREMENTS.
KEYNOTES
1/2" = 1'-0"F7 ELEVATION - LOADING DOCK
2ND FLOOR
13' - 6 3/4"
3RD FLOOR
27' - 1 1/2"
3RD FLOOR ROOF
38' - 9 3/4"
EXISTING BUILDING
210211 F5
AE301
756 SF +/-
KEYPLAN
1. CONTRACTOR TO PROVIDE AN INSTRUMENTAL ANALYSIS OF THE ORIGINAL MORTAR USED
PER ASTM C 1324-96 "TEST MENTHOD FOR EXAMINATION AND ANALYSIS OF HARDENED
MORATARS".
2. NEW MORTAR MUST MATCH HISTORIC MORTAR IN COLOR, TEXTURE AND TOOLING, AND
MATCH THE BINDER COMPONENTS AND THEIR PROPORTIONS WITH THE HISTORIC MORTAR.
3. THE SAND MUST MATCH THE SAND IN THE HISTORIC MORTAR.
4. NEW MORTAR MUST BE AS VAPORT PERMEABLE AND AS SOFT OR SOFTER (MEASURED IN
COMPRESSIVE STRENGTH) THAN THE HISTORIC MORTAR.
5. WATER SHOULD BE POTABLE -- CLEAN AND FREE FROM ACIDS, ALKALIS, AND OTHER
DISSOLVED ORGANIC MATERIALS.
6. BONDING AGENTS SHOULD NOT BE USED AS AN ADDITIVE.
7. IDENTIFIED REPOINTING LOCATIONS ARE SHOW BUT ADDITIONAL LOCATIONS WILL BE
IDENTIFIED WHEN SCAFFOLDING IS IN PLACE.
8. ALL WORK WILL BE EXECUTED BY PHASING AS DIRECTED BY THE VA STAFF.
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AE202CM/NBEB/MR3/1/2021
BLDG 1 ELEVATIONS
1/8" = 1'-0"F1 NORTH ELEVATION - PARAPET WALL
SHEET NOTES LEGEND
# NOTE
210 CUSTOM SHEET METAL WALL COPING; REF. DETAILS
211 REPOINT EXISTING MASONRY FACADE; REF. DETAILS
KEYNOTES
2ND FLOOR
13' - 6 3/4"
3RD FLOOR
27' - 1 1/2"
4TH FLOOR
39' - 1 7/8"
5TH FLOOR
51' - 2 1/4"
6TH FLOOR
63' - 2 5/8"
7TH FLOOR
75' - 3"
VENT PENTHOUSE
88' - 9 3/4"
PENTHOUSE
ROOF
111' - 0 1/4"
211211
EXISTING BUILDING
211 211
B3
AE504
B3
AE504
KEYPLAN
1. CONTRACTOR TO PROVIDE AN INSTRUMENTAL ANALYSIS OF THE ORIGINAL MORTAR USED
PER ASTM C 1324-96 "TEST MENTHOD FOR EXAMINATION AND ANALYSIS OF HARDENED
MORATARS".
2. NEW MORTAR MUST MATCH HISTORIC MORTAR IN COLOR, TEXTURE AND TOOLING, AND
MATCH THE BINDER COMPONENTS AND THEIR PROPORTIONS WITH THE HISTORIC MORTAR.
3. THE SAND MUST MATCH THE SAND IN THE HISTORIC MORTAR.
4. NEW MORTAR MUST BE AS VAPORT PERMEABLE AND AS SOFT OR SOFTER (MEASURED IN
COMPRESSIVE STRENGTH) THAN THE HISTORIC MORTAR.
5. WATER SHOULD BE POTABLE -- CLEAN AND FREE FROM ACIDS, ALKALIS, AND OTHER
DISSOLVED ORGANIC MATERIALS.
6. BONDING AGENTS SHOULD NOT BE USED AS AN ADDITIVE.
7. IDENTIFIED REPOINTING LOCATIONS ARE SHOW BUT ADDITIONAL LOCATIONS WILL BE
IDENTIFIED WHEN SCAFFOLDING IS IN PLACE.
8. ALL WORK WILL BE EXECUTED BY PHASING AS DIRECTED BY THE VA STAFF.
GROUND
0' - 0"
2ND FLOOR
13' - 6 3/4"
3RD FLOOR
27' - 1 1/2"
4TH FLOOR
39' - 1 7/8"
5TH FLOOR
51' - 2 1/4"
6TH FLOOR
63' - 2 5/8"
7TH FLOOR
75' - 3"
VENT PENTHOUSE
88' - 9 3/4"
PENTHOUSE
ROOF
111' - 0 1/4"
EXISTING BUILDING
211 211
212 212
D8
AE301
Typ.
B3
AE504
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AE203CM/NBEB/MR3/1/2021
BLDG 1 ELEVATIONS
3/32" = 1'-0"C1 WEST ELEVATION
3/32" = 1'-0"F1 EAST ELEVATION
SHEET NOTES
LEGEND
KEYNOTES
# NOTE
210 CUSTOM SHEET METAL WALL COPING; REF. DETAILS
211 REPOINT EXISTING MASONRY FACADE; REF. DETAILS
212 REPLACE CRACKED FACE BRICK; REF. DETAILS
214 REPAIR AND PAINT DAMAGED CONCRETE AT SUNSHADE UNDERSIDE
LOADING DOCK
ROOF
15' - 6"
LOADING DOCK
FLOOR
2' - 10"
AE504
B1
EXISTING STRUCTURAL FILL
EXISTING BACKFILL
EXISTING RIGID INSULATION
EXISTING REINFORCED
CONCRETE FOUNDATION
WALL AND FOOTING
EXISTING PAVEMENT
EXISTING FILLER
EXISTING CONCRETE SLAB
EXISTING FILLER
SS THRU WALL FLASHING
W/ HEMMED DRIP EDGE
WEEP TUBE @ 16" O.C.
CONTINUOUS CRENULATED
MORTAR NET
3" THICK RIGID INSULATION
MASONRY VENEER WALL
INTERLOCK SYSTEM W/ CONT
9 GA WIRE REINFORCING
AND WIRE TIES (EVERY
OTHER CMU COURSE)
BITUMINOUS DAMPROOFING
PAINTED EXISTING
STEEL BEAM
BOND BEAM W/ (2) #5
VERTICALS AT ALTERNATING
LIFTS (GROUT SOLID)
8" REINFORCED
CMU
MASONRY TIES
NEW TRUCK BUMP GUARDS
2'
C
M U
C O
U R
S E
S
B
R
IC
K C
O U
R S
E S
DRILL EXIST. FOUNDATION
AND EPOXY
REINFORCEMENT BARS
(2) #5 VERTICALS AT 32” O.C.
HORIZONTAL JOINT
REINFORCING AT 16” O.C.,
TYP.
GROUND
0' - 0"
3RD FLOOR ROOF
38' - 9 3/4"
AE504
B3
EXIST. MASONRY
VENEER WALL
REPOINT EXIST. MASONRY;
REF. ELEVATION &
SPECIFICATIONS
KEYPLAN
GROUND
0' - 0"
LOADING DOCK
ROOF
15' - 6"
LOADING DOCK
FLOOR
2' - 10"
.040" SS THRU WALL
FLASHING W/ HEMMED
DRIP EDGE
WEEP TUBE @ 16" O.C.
CONTINUOUS CRENULATED
MORTAR NET
3" THICK RIGID INSULATION
MASONRY VENEER WALL
INTERLOCK SYSTEM W/ CONT
9 GA WIRE REINFORCING AND
WIRE TIES (EVERY OTHER
CMU COURSE)
BITUMINOUS DAMPROOFING
PAINTED EXISTING
STEEL BEAM
8" REINFORCED
CMU
MASONRY TIES
DOCK LIFT PIT
8" CMU BEYOND
FACE OF BRICK
BEYOND
STEEL PLATE
EXIST. ROLL-UP
DOOR REINSTALLED
C
M U
C O
U R
S E
S
AE504
B1
NEW TRUCK SHELTER
ENCLOSURE; INSTALL PER
MFR. INSTRUCTION
B
R
IC
K C
O U
R S
E S
AE504
D1
E X
IS
T
IN
G
(2) #5 VERTICALS AT 32” O.C.
HORIZONTAL JOINT
REINFORCING AT 16” O.C.,
TYP.
1. F1 AND F3 WALL SECTIONS AND DETAIL CALL-OUTS TO MATCH ORIGINAL
RECONFIGURED LOAD DOCK CONSTRUCTION DRAWINGS (2012). CONTACT VA
COR FOR APPROVAL OF ALTERNATIVE.
EXIST. MASONRY
VENEER WALL
REPAIR AND PAINT
DAMAGED CONCRETE AT
SUNSHADE UNDERSIDE
EXIST. STANDING
SEAM ROOF
SUNSHADE
EXIST. WINDOW
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AE301CM/NBEB/MR3/1/2021
WALL SECTIONS
SHEET NOTES
LEGEND
1" = 1'-0"F1 WALL SECTION - LOADING DOCK
1" = 1'-0"F5 WALL SECTION - MAIN BUILDING
1" = 1'-0"F3 WALL SECTION - LOADING DOCK1
1" = 1'-0"D8 SUNSHADE DETAIL
8" REINFORCED CMU
BITUMINOUS DAMPROOFING
3" THICK RIGID INSULATION
FACE BRICK
SEALANT
EXIST. STEEL BENT PLATE
STAINLESS STEEL FASCIA
EXTENSION
NEOPRENE PAD
0.063" THICK MILL
FINISHED SS FASCIA
ADHERE MEMBRANE OVER
BLOCKING AND EXIST.
TAPERED INSULATION
ADHESIVE
2 X 6 PRESSURE TREATED
WOOD BLOCKING
EXIST. ROOF STRUCTURE
EXISTINGNEW
EXIST. STL BEAM
BOLT WD BLOCKING TO
STL ANGLE AT 8" O.C.
3"
1'
STEEL ANGLE
CONT GALV CLEAT
1 1/4" SS SCREW W/ NEOPRENE
WASHER AT 12" O.C.
CONT GALV SPRING CLIP
3" WIDE SPLICE TAPE
MASONRY TIES AT 24" O.C.
EXISTING CONCRETE
ROOF DECK
EXIST. FACE BRICK
REPOINT EXIST. MASONRY;
REF. ELEVATION &
SPECIFICATIONS
INSULATION
NEW EPDM MEMBRANE ROOF;
REF. ROOF PLAN
EXISTING WALL
EXIST. STONE COPING
STAINLESS STEEL COPING &
FLASHING W/ CONT. CLEAT
ADHERE MEMBRANE OVER
COPING
AE504
B5
3" THICK RIGID
INSULATION
8" CMU BLOCK
FACE BRICK W/ WIRE
REINFORCING
EXISTING WALL
EXISTING
STRUCTURAL
COLUMN
1'
- 4
PROVIDE 2" AIR SPACE
MIN.
NEW TRUCK SHELTER
ENCLOSURE
5"
SALVAGE AND REINSTALL
DOOR RAIL SUPPORT
ANGLE
EXP. ANCHOR
SALVAGE AND REINSTALL
OVERHEAD DOOR
RETURN BRICK AT
OPENING
CONTROL JOINT WITH
BACKER ROD
NEW 6" DIA.
BOLLARD
1'
- 0
CL
KEYPLAN
EXISTING BRICK
VENEER
MASONRY UNIT OR
UNITS TO BE
REMOVED
1. SAW CUT OUT MORTAR JOINTS SURROUNDING
MASONRY UNITS TO BE REMOVED OR REPLACED.
2. UNITS REMOVED MAY BE BROKEN OR REMOVED,
PROVIDING SURROUNDING UNITS TO REMAIN ARE
NOT DAMAGED.
3. ONCE UNITS ARE REMOVED, CAREFULLY CHISEL
OUT THE OLD MORTAR AND REMOVE DUST AND
DEBRIS.
4. IF UNITS ARE LOCATED ON EXTERIOR WYTHE OF A
CAVITY OR VENEER WALL, EXCERCISE CARE TO
PREVENT DEBRIS FROM FALLING INTO CAVITY.
REMOVE MIN. 3/4" DEPTH OF MORTAR IN
HORIZONTAL AND VERTICAL JOINTS OR
UNTIL SOUND MORTAR IS FOUND. REMOVE
DUST AND DEBRIS BY BRUSHING, AIR OR
WATER (NO WATER IF TEMPERATURE IS
BELOW FREEZING).
INSTALL OF TUCK POINT MORTAR
PER SPECIFICATIONS 04 05 13
MASONRY TUCK POINTING 3.3
1/2" 1/ 2"
1/ 2"
NEW SEALANT WITH
CONTINUOUS BACKER-ROD
EXISTING WALL
EXISTING BRICK VENEER
ALIGN CONTROL JOINT TO
NEAREST VERTICAL BRICK JOINT.
SAW CUT NEW CONTROL JOINT IN
BRICK COURSING ABOVE AND
BELOW AS REQUIRED TO MAINTAIN
A STRAIGHT VERTICAL JOINT.
EXISTING WALL
FLASHING MEMBRANE EXTEND
OVER PRE-FORMED CORNER
PRE-FORMED INSIDE
CORNER
PRE-FORMED
OUTSIDE CORNER
FLASHING MEMBRANE EXTEND
OVER PRE-FORMED CORNER
EXISTING WALL
TERMINATION BAR SET IN
MASTIC (ATTACHED AS
DIRECTED BY MANUF.)
3" ST. STEEL DRIP
EDGE SET IN MASTIC
3/4"
3" ST. STEEL DRIP EDGE
SET IN MASTIC
PROJECTION
TERMINATION BAR SET IN
MASTIC (ATTACHED AS
DIRECTED BY MANUF.)
SINGLE-PLY ROOF MEMBRANE -
EXTEND MEMBRANE UP & OVER
ROOF CURB
EXIST. ROOF
STRUCTURE
WOOD BLOCKING
MECH. UNIT & FLASHING
(BY MECH. CONTR.)
EXISTING ROOF
CURB
OPENING
EXISTING ROOF DRAIN
NEW MEMBRANE
ROOFING TO BE
CONT. TO DRAIN
EXISTING ROOF TAPER
EXISTING ROOF
STRUCTURE
WATER CUT-OFF
MASTICEXIST. CLAMPING
RING
OVERLAP
6" MIN.
DRAIN FLASHING
WATER CUT-OFF MASTIC
EXISTING VENT PIPE
UNCURED MEMBRANE
FLASHING LAP SEALANT
ADHESIVE
NEW WHITE PVC MEMBRANE
ROOF; REF. ROOF PLAN
STAINLESS STEEL RAINCOLAR
W/ STAINLESS STEEL
DRAWBAND
SEALANT
EXISTING ROOF
STRUCTURE
FACE OF BRICK BEYOND
8" CMU BEYOND
.040" SS THRU WALL FLASHING
W/ HEMMED DRIP EDGE
WEEP TUBE @ 16" O.C.
CONTINUOUS CRENULATED
MORTAR NET
3" THICK RIGID INSULATION
3/8" X 15" CONT. STEEL
PLATE
MASONRY VENEER
GROUT (2)-COURSES
ABOVE LINTEL SOLID
CMU INFILL
W8X21 STEEL LINTEL
STRAP ANCHORS 1 1/2"X1/4"
@ 32" O.C. TYP.
1/2"
EXIST. STONE COPING
90°
153°
5/
8" 2"
1/
2" 1/
2"
1/2" 2 3/8" 3 1/8" 6"
SEALANT ENTIRE LENGTH
DRIP EDGE
STAINLESS STEEL COPING &
FLASHING W/ CONT. CLEAT
(FIELD VERIFY DIMENSIONS
FOR PROPER FIT)
1 1/4" SS SCREW W/ NEOPRENE
WASHER AT 12" O.C.
SEALANT ENTIRE LENGTH
2"
EPDM ROOFING MEMBRANE
OVER AND ADHERED TO COPING
6" DIA. STANDARD PIPE
CONCRETE FILLED
(PAINTED YELLOW)
GRADE
6" 2'
3'
6"
SET PIPE IN
CONCRETE
2" WIDE, WHITE
REFLECTIVE TAPE
3" 3"
2'
SLOPE AWAY
FROM PIPE
SDVOSB
CVE Location
Issue Date o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
NO. DESCRIPTION DATE
FULLY SPRINKLERED
Project Number
Building Number
Drawing Number
Project Title
Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT
Project Director
BID DOCUMENTS
REPAIR MORTAR & BRICK
ON BLDG. 1
JAMES E. VAN ZANDT VA MEDICAL CENTER
ALTOONA, PA
503-19-110
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0514-0002
MILLER-REMICK LLC
PROFESSIONAL
ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
OCULUS INC.
PROFESSIONAL
ARCHITECT
ARCHITECTURAL
AE504CM/NBEB/MR3/1/2021
DETAILS
1 1/2" = 1'-0"B1 WALL PARAPET - LOADING DOCK
1 1/2" = 1'-0"B3 WALL PARAPET - MAIN BUILDING
1 1/2" = 1'-0"D5 MASONRY WALL DETAIL
LEGEND
1 1/2" = 1'-0"F3 BRICK REPLACEMENT
1 1/2" = 1'-0"F5 TUCK POINTING DETAIL 3" = 1'-0"F7 CONTROL JOINT
3/4" = 1'-0"F1 MASONRY BASE FLASHING DETAILS
1 1/2" = 1'-0"E8 ROOF CURB DETAIL
1 1/2" = 1'-0"B8 EXISTING ROOF DRAIN DETAIL
1 1/2" = 1'-0"D8 VENT STACK DETAIL
1 1/2" = 1'-0"D1 WALL PARAPET - DOCK DOOR HEADER
3" = 1'-0"B5 COPING DETAIL - MAIN BUILDING
1" = 1'-0"D3 BOLLARD DETAIL
| GI001 |
| GI001 |
| GI001 |
| AS100 - SITE PLAN |
| AD101 - DEMOLITION PLAN & ELEVATION |
| AD102 - DEMOLITION ROOF PLAN |
| AE101 - LOADING DOCK PLAN & ROOF PLAN |
| AE102 - BLDG 1 ROOF PLAN |
| AE201 - LOADING DOCK ELEVATIONS |
| AE202 - BLDG 1 ELEVATIONS |
| AE203 - BLDG 1 ELEVATIONS |
| AE301 - WALL SECTIONS |
| AE504 - DETAILS |
File details come from the government source that posted it. Updated .