This is a technical drawing document for the City of Philadelphia Water Department detailing concrete repair sections and specifications for the Baxter Water Treatment Plant's filter rehabilitation project (Work No. 61125). The document provides comprehensive guidance for contractors on five types of spall repairs and three types of deck repairs, specifying repair methodologies, material requirements, reinforcement specifications, and quality standards. The contract opportunity is a pre-qualification solicitation with an estimated value exceeding $5,000,000 for the rehabilitation of 10 filters at the Baxter Water Treatment Plant in Pennsylvania.
The technical specifications require contractors to utilize specific repair details based on deterioration depth and reinforcement exposure, with minimum repair thicknesses of 3/4 inch and maximum sawcut depths of 1 inch. All materials must comply with NSF 61 approval standards for drinking water exposure, and reinforcing materials must conform to ASTM A615 for deformed bars and ASTM A185 for welded wire fabric. Contractors are required to submit product specifications, samples, and installation instructions for approval prior to work commencement, maintain logs of actual quantities for each repair type, and use Hilti HIT-HY 200-A hybrid mortar or equivalent for dowel installation. The document emphasizes engineer confirmation of repair type selection following deterioration demolition and establishes responsibility on contractors to verify all field dimensions and provide necessary equipment, labor, formwork, lighting, ventilation, and scaffolding.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DETERIORATED CONCRETE
SOUND CONCRETE
SAWCUT TO NEAT LINES AT
LIMITS OF REPAIR
ELEVATION VIEW SECTION B-B
±12" 1
2" Ø DOWEL WITH
90° HOOK AND 2"
LENGTH OF HOOK (TYP.)
±6"
3x3-W10xW10 WWF
(EDGES OF WIRES BENT
BACK MIN 1" INTO PATCH)
B
B
DETERIORATED
CONCRETE
DEMOLISH 34" CLEAR
BEHIND EXPOSED
REINFORCING
SOUND CONCRETE
EXISTING REINFORCEMENT
(IF PRESENT)
2" MIN. COVER
BEVELED SAWCUT
4" TO 1" DEEP
2 SPALL REPAIR TYPE 2
N.T.S.
DETERIORATED
CONCRETE
SOUND CONCRETE
SAWCUT TO
NEAT LINES AT
LIMITS OF
REPAIR
1 SPALL REPAIR TYPE 1
N.T.S.
A
A
ELEVATION VIEW SECTION A-A
DETERIORATED
CONCRETE
LIMIT OF REMOVAL
SOUND CONCRETE
EXISTING REINFORCEMENT
(IF PRESENT)
BEVELED SAWCUT
4" TO 1" DEEP
DEMOLISH 34" CLEAR
BEHIND EXPOSED
REINFORCING
3 SPALL REPAIR CORNER DETAIL
N.T.S.
6" MAX.
4" MIN.
FROM EDGE
BEVELED SAWCUT
4" TO 1" DEEP
WWF TIED TO DOWELS
SURFACE OF REPAIR
OFFSET DOWELS 6"
ON EITHER SIDE OF CORNER
SOUND CONCRETE
4 SPALL REPAIR DOWEL DETAIL
N.T.S.
WWF
EXISTING REINFORCING
(IF PRESENT)
ATTACH WWF TO DOWELS
WITH ANNEALED WIRE
2" COVER TYP. OVER REINFORCINGAPPLY EPOXY
BONDING COMPOUND
2"Ø DOWEL
EMBEDDED 4"
W/ HILTI HY-200
1 12" MIN. COVER OVER DOWELS
SURFACE OF REPAIR
SOUND CONCRETE
DETERIORATED
CONCRETE
LIMIT OF REMOVAL
SOUND CONCRETE
REINFORCEMENT
5 DECK REPAIR TYPE 1
N.T.S.
BEVELED SAWCUT
4" TO 1" DEEP
T
IF DEPTH OF REPAIR IS >T/2
USE DECK REPAIR TYPE 3
DETERIORATED
CONCRETE
LIMIT OF REMOVAL
SOUND CONCRETE
REINFORCEMENT
6 DECK REPAIR TYPE 2
N.T.S.
BEVELED SAWCUT
4" TO 1" DEEP
T
IF DEPTH OF REPAIR IS >T/2
USE DECK REPAIR TYPE 3
DEMOLISH 34" MIN.CLEAR BEHIND
EXPOSED REINFORCING
DETERIORATED
CONCRETE
LIMIT OF REMOVAL
SOUND CONCRETE
REINFORCEMENT
7 DECK REPAIR TYPE 3
N.T.S.
BEVELED SAWCUT
4" TO 1" DEEP
T
SPALL REPAIR NOTES:
1. SELECT THE APPROPRIATE SPALL REPAIR DETAIL AFTER COMPLETING DEMOLITION
OF DETERIORATED CONCRETE. CONFIRM WITH THE ENGINEER
1.1. USE SPALL REPAIR TYPE1 FOR SURFACE REPAIRS NOT GREATER THAN 1"
DEEP AND REBAR IS NOT EXPOSED
1.2. USE SPALL REPAIR TYPE 2 FOR REPAIRS GREATER THAN 1" DEEP OR WHERE
EXISTING REINFORCING IS EXPOSED.
1.3. A GREATER SPALL REPAIR MAY BE REQUIRED WITHIN THE AREA OF A
LESSER REPAIR.
2. UTILIZE SPALL REPAIR DETAILS WHERE THE CONCRETE IS GENERALLY GREATER
THAN 12" THICK. WHERE MEMBERS EXHIBIT GREATER THAN 25% SECTION LOSS,
NOTIFY THE ENGINEER
3. SQUARE OFF DETERIORATED CONCRETE TO SOUND CONCRETE WITH A SAWCUT OF
4" MINIMUM TO 1" MAXIMUM BUT NOT TO THE DEPTH OF THE REINFORCING STEEL.
BACK BEVEL EDGE OF REPAIR AREA BEYOND SAWCUT.
4. USE HAND TOOLS TO REMOVE LOOSE AND DELAMINATED CONCRETE TO PROVIDE A
SOUND BOND BETWEEN EXISTING CONCRETE AND NEW REPAIR MATERIALS.
DEMOLITION HAMMERS WITH IMPACT RATINGS OF 16 FT/LB OR LESS MAY BE USED IF
REQUIRED. PROVIDE A MINIMUM 34" THICK REPAIR.
5. IF DEPTH OF DETERIORATED CONCRETE EXTENDS BEYOND THE PRIMARY
REINFORCEMENT, REMOVE THE CONCRETE TO A LEAST 34" BEHIND THE
REINFORCEMENT.
7. CLEAN EXISTING REINFORCEMENT BY MECHANICAL MEANS. NOTIFY ENGINEER OF
DETERIORATION OF THE REINFORCING, ADDITIONAL DIRECTION MAY BE REQUIRED.
8. APPLY AN EPOXY BONDING COMPOUND BETWEEN THE EXISTING CONCRETE AND
NEW REPAIR MATERIAL.
9. USE DOWELS ONLY WHEN THE LEAST DIMENSION OF THE PREPARED REPAIR AREA
IS LESS THAN 2'-0", OR WHEN NEW REINFORCEMENT CANNOT BE ADEQUATELY
DEVELOPED BY LAPPING WITH THE EXISTING REINFORCEMENT.
10. INSTALL DOWELS WITH AN ADHESIVE ANCHORING SYSTEM PER THE
MANUFACTURERS RECOMMENDATIONS. USE HILTI HIT-HY 200-A HYBRID MORTAR,
OR EQUAL.
GENERAL NOTES:
1. CONTRACTOR IS RESPONSIBLE TO VERIFY ALL DIMENSIONS IN FIELD
2. SUBMIT PRODUCT SPECIFICATIONS, SAMPLES, INSTALLATION
INSTRUCTIONS/METHODS, ETC. FOR REVIEW AND APPROVAL PRIOR TO THE START
OF WORK.
3. ALL MATERIALS INSTALLED INSIDE THE CLEAR WELL BASINS, OR OTHERWISE
EXPOSED TO DRINKING WATER SHALL BE NSF 61 APPROVED.
4. PROVIDE ALL NECESSARY EQUIPMENT, LABOR, AND MATERIALS, INCLUDING
FORMWORK, LIGHTING, VENTILATION, AND SCAFFOLDING OR OTHER ACCESS
SYSTEM NECESSARY TO COMPLETE THE WORK.
5. SEE 03930 CONCRETE REPAIR & REHABILITATION SPECIFICATION FOR REPAIR
MATERIAL REQUIREMENTS
6. REINFORCING SHALL CONFORM TO THE FOLLOWING STANDARDS
6.1. DEFORMED BARS: ASTM A615
6.2. WELDED WIRE FABRIC: ASTM A185
7. CONTRACTOR SHALL MAINTAIN HIS OWN LOG OF ACTUAL QUANTITIES OF EACH
REPAIR TYPE FOR REVIEW BY THE PROJECT MANAGER.
8. CONTRACTOR SHALL COMPLETELY REMOVE EXISTING SURFACE COATINGS,
SEALANTS/SEALANT SYSTEMS, EPOXY, ETC., IF PRESENT, FROM THE AREA TO BE
REPAIRED OR INJECTED.
DECK REPAIR NOTES:
1. SELECT THE APPROPRIATE DECK REPAIR DETAIL AFTER COMPLETING DEMOLITION
OF DETERIORATED CONCRETE. CONFIRM WITH THE ENGINEER.
1.1. USE DECK REPAIR TYPE 1 FOR SURFACE REPAIRS NOT GREATER THAN T/2
DEEP WHERE REBAR IS NOT EXPOSED.
1.2. USE DECK REPAIR TYPE 2 FOR REPAIRS NOT GREATER THAN T/2 DEEP
WHERE EXISTING REINFORCING IS EXPOSED.
1.3. USE DECK REPAIR TYPE 3 WHERE REPAIRS EXCEED T/2 DEEP.
2. DECK REPAIRS DETAILS ARE TYPICAL FOR REPAIRS MADE FROM TOP-SIDE OR
UNDERSIDE OF ROOF DECK AND INTERMEDIATE FLOOR, OR OTHER LOCATIONS
WHERE MEMBERS ARE 12" THICK OR LESS.
3. SQUARE OFF DETERIORATED CONCRETE TO SOUND CONCRETE WITH A SAWCUT OF
4" MINIMUM TO 1" MAXIMUM,BUT NOT TO THE DEPTH OF THE REINFORCING STEEL.
BACK BEVEL EDGE OF REPAIR AREA BEYOND SAWCUT.
4. USE HAND TOOLS TO REMOVE LOOSE AND DELAMINATED CONCRETE TO PROVIDE A
SOUND BOND BETWEEN EXISTING CONCRETE AND NEW REPAIR MATERIALS.
DEMOLITION HAMMERS WITH IMPACT RATINGS OF 16 FT/LB OR LESS MAY BE USED IF
REQUIRED. PROVIDE A MINIMUM 34" THICK REPAIR.
5. IF DEPTH OF DETERIORATED CONCRETE EXTENDS BEYOND THE PRIMARY
REINFORCEMENT, REMOVE THE CONCRETE TO A LEAST 34" BEHIND THE
REINFORCEMENT.
7. CLEAN EXISTING REINFORCEMENT BY MECHANICAL MEANS. NOTIFY ENGINEER OF
DETERIORATION OF THE REINFORCING, ADDITIONAL DIRECTION MAY BE REQUIRED.
8. APPLY AN EPOXY BONDING COMPOUND BETWEEN THE EXISTING CONCRETE AND
NEW REPAIR MATERIAL.
9. USE DOWELS ONLY WHEN THE LEAST DIMENSION OF THE PREPARED REPAIR AREA
IS LESS THAN 2'-0", OR WHEN NEW REINFORCEMENT CANNOT BE ADEQUATELY
DEVELOPED BY LAPPING WITH THE EXISTING REINFORCEMENT.
10. INSTALL DOWELS WITH AN ADHESIVE ANCHORING SYSTEM PER THE
MANUFACTURERS RECOMMENDATIONS. USE HILTI HIT-HY 200-A HYBRID MORTAR,
OR EQUAL.
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SUPERVISOR
AutoCAD SHX Text
BAXTER WATER TREATMENT PLANT
AutoCAD SHX Text
CONCRETE REPAIRS SECTIONS AND DETAILS
AutoCAD SHX Text
CITY OF PHILADELPHIA WATER DEPARTMENT
AutoCAD SHX Text
DESIGNED BY
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text 61125
AutoCAD SHX Text
WORK NO.
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text
OF
AutoCAD SHX Text S-1
AutoCAD SHX Text
SHEETS
AutoCAD SHX Text S-1
AutoCAD SHX Text
REHABILITATION OF 10 FILTERS
AutoCAD SHX Text
MW
AutoCAD SHX Text
MW
AutoCAD SHX Text
KEH
AutoCAD SHX Text 07/20/2026
AutoCAD SHX Text 07/20/2026
AutoCAD SHX Text 07/20/2026
AutoCAD SHX Text 07/20/2026
AutoCAD SHX Text
KELLY HOGAN
AutoCAD SHX Text
CHIEF, DESIGN BRANCH, ENGINEERING DIVISION
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DEPUTY COMISSIONER, ENGINEERING DIVISION
AutoCAD SHX Text
WATER COMMISSIONER
David.Weld Dtw w date Stamp
William.Dobbins Stamp
| Sheets and Views |
| D-1 - 63107 |
File details come from the government source that posted it. Updated .