Bid_#2027-04_Project_Manual_0501052.001.pdf

PDF 971 KB Posted

Attached to
Police Department Garage Door and Ventilation Upgrades
Solicitation number
Bid #2027-04
Issued by
Mclean County, Illinois

About this file

Project Manual Summary: Bloomington Police Garage Door and Ventilation Upgrades

This is a project manual for Bid #2027-04 issued by the City of Bloomington, Illinois for the Police Department Garage Door and Ventilation Upgrades at 305 South East Street. The project encompasses the installation of one high-speed roll-up metal door and comprehensive HVAC modifications at the Lower Level 1 of the Bloomington Police Department facility. The scope of work includes selective demolition of existing electrical components, installation of a dedicated outdoor air unit (DOAS) with makeup air capabilities, ductwork installation and insulation, direct-digital control system integration with the building automation system, and associated electrical work including conduit installation, low-voltage conductors and cables, and system identification. The project manual includes detailed specifications across 26 divisions covering structural, mechanical, electrical, and control system requirements. Sealed bids are due Thursday, August 27, 2026, at 11:00 AM CST through the City's e-Procurement Portal (OpenGov). The professional team preparing the specifications includes a licensed architect (John Bishop), mechanical engineer (Dustin Rhoades), electrical engineer (Warren Kohm), and structural engineer (John Paul Goedken), all from Illinois.

The project requires compliance with the City of Bloomington's prevailing wage standards and project labor agreement provisions for public works contracts exceeding $50,000, though union membership is not mandated. The high-speed roll-up door must be rated for a 100 psf wind load with variable opening speeds up to 80 inches per second and closing speeds up to 20 inches per second, featuring wireless failsafe safety edges and a springless operator system. HVAC components must comply with ASHRAE and NFPA standards, with testing, adjusting, and balancing performed by a certified TAB agency (AABC, NEBB, or TABB certified). All electrical work must conform to the National Electrical Code with copper conductors only, proper identification systems, and specified conduit types based on installation location. The project manual establishes rigorous quality assurance requirements, including manufacturer qualifications, installer certifications, mock-up inspections for the metal canopy, and comprehensive startup and demonstration services. Manufacturers are specified for major components with substitution options available through the product requirements section, and extended warranties are required for key equipment including five-year coverage on the door system and outdoor air unit compressor.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT MANUAL

FOR

City of Bloomington

BLOOMINGTON POLICE

GARAGE DOOR and

VENTILATION UPGRADES

305 South East Street Bloomington, Illinois

Project No: 02501052.001

March 17, 2026

200 W. College Avenue, Suite 301 – Normal, IL 61761 (309) 663-8436 www.f-w.com

BLOOMINGTON POLICE GARAGE DOOR AND

PROJECT: 02501052.001

SEALS PAGE 00 01 07 - 1

SECTION 00 01 07 - SEALS PAGE

THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED

BELOW WAS PREPARED BY ME OR UNDER MY DIRECT

SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY

LICENSED ARCHITECT UNDER THE LAWS OF THE STATE OF

ILLINOIS.

SIGNATURE:

NAME: JOHN BISHOP

DATE: 03/17/2026

LICENSE EXPIRES: 11/30/2026 SEAL

SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY

LICENSED MECHANICAL ENGINEER UNDER THE LAWS OF

THE STATE OF ILLINOIS.

NAME: DUSTIN RHOADES

LICENSE EXPIRES: 11/30/2027 SEAL

SEALS PAGE 00 01 07 - 2

SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY

LICENSED ELECTRICAL ENGINEER UNDER THE LAWS OF

NAME: WARREN KOHM

SUPERVISION AND RESPONSIBLE CHARGE. I AM A DULY

LICENSED STRUCTURAL ENGINEER UNDER THE LAWS OF

NAME: JOHN PAUL GOEDKEN

END OF SECTION

VENTILATION UPGRADES PROJECT: 02501052.001

TABLE OF CONTENTS 000110 - 1

SECTION 000110 - TABLE OF CONTENTS

PROCUREMENT AND CONTRACTING REQUIREMENTS

1.1. Division 00 -- Procurement and Contracting Requirements

A. 000107 - Seals Page

B. 000110 - Table of Contents

C. 000115 - List of Drawing Sheets

SPECIFICATIONS

2.1. Division 01 -- General Requirements

2.2. Division 02 -- Existing Conditions

2.3. Division 03 -- Concrete

2.4. Division 04 -- Masonry

2.5. Division 05 -- Metals

2.6. Division 06 -- Wood, Plastics, and Composites

2.7. Division 07 -- Thermal and Moisture Protection

2.8. Division 08 -- Openings

A. 083323.13 - Overhead Rapid Coiling Doors - Overhead Door

2.9. Division 09 -- Finishes

2.10. Division 10 -- Specialties

A. 107316.13 - Metal Canopies

2.11. Division 11 -- Equipment

2.12. Division 12 -- Furnishings

2.13. Division 13 -- Special Construction

2.14. Division 14 -- Conveying Equipment

2.15. Division 21 -- Fire Suppression

2.16. Division 22 -- Plumbing

2.17. Division 23 -- Heating, Ventilating, and Air-Conditioning (HVAC)

A. 230593 - Testing, Adjusting, and Balancing for HVAC

B. 230713 - Duct Insulation

TABLE OF CONTENTS 000110 - 2

C. 230923 - Direct-Digital Control System for HVAC

D. 233100 - HVAC Ducts and Casings

E. 233300 - Air Duct Accessories

F. 233423 - HVAC Power Ventilators

G. 237433 - Dedicated Outdoor Air Units

2.18. Division 25 -- Integrated Automation

2.19. Division 26 -- Electrical

A. 260505 - Selective Demolition for Electrical

B. 260519 - Low-Voltage Electrical Power Conductors and Cables

C. 260533.13 - Conduit for Electrical Systems

D. 260553 - Identification for Electrical Systems

E. 262816.16 - Enclosed Switches

2.20. Division 27 -- Communications

2.21. Division 28 -- Electronic Safety and Security

2.22. Division 31 -- Earthwork

2.23. Division 32 -- Exterior Improvements

2.24. Division 33 -- Utilities

2.25. Division 34 -- Transportation

2.26. Division 40 -- Process Integration

LIST OF DRAWING SHEETS 00 01 15 - 1

SECTION 00 01 15 - LIST OF DRAWING SHEETS

ARCHITECTURE

A0.1 General Information

A1.L1n Lower Level 1 Floor Plan – North

A3.1 Exterior Elevations

STRUCTURAL

S1.1 General Notes, Details, and Plan

MECHANICAL

M0.1 General Information

M1.1 Lower Level 1 Plan

M1.2 First Floor Plan

M1.3 Enlarged Lower Level 1 Plan and Section

M2.1 Mechanical Details and Schedules

ELECTRICAL

E0.1 General Information

E0.2 General Information and Schedules

E1.1 Lower level 1 Plan

E1.2 First Floor Plan

E5.1 Electrical Schedules

OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR 083323.13 - 1

SECTION 083323.13 - OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR

PART 1 GENERAL

1.1. Section Includes

A. High Performance Exterior High Speed Roll-Up Metal Doors

1.2. Related Requirements

A. Section 260583 - Wiring Connections: Power to disconnect.

1.3. Reference Standards

A. ASTM A 36 - Standard Specification for Carbon Structural Steel.

B. ASTM A 500 - Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes.

C. ASTM E 283 - Standard Test Method for Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen.

D. ASTM E 330 - Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference.

E. ASTM A 653 - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy- Coated (Galvannealed) by the Hot-Dip Process.

F. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum).

G. UL Listed - Underwriters Laboratories Inc. Product Listed.

1.4. Design Perfomance Requirements

A. High Performance Exterior High Speed Roll-Up Metal Door

1) Wind Load: Design door assembly to withstand ultimate static pressure load of 100 psf (478 Pa) at 15 feet wide, in conformance to ASTM E 330.

B. Single-Source Responsibility: Provide doors, guides, motors, and accessories from one manufacturer for each type of door. Provide secondary components from sourc eacceptable to manufacturer of primary components

C. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories, Inc.

acceptable to authority having jurisdiction as suitable for purpose specified.

1.5. Submittals

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Manufacturer's data sheets on each product to be used, including:

1) Preparation instructions and recommendations.

OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR 083323.13 - 2

2) Storage and handling requirements and recommendations.

3) Details of door materials, construction and fabrication.

4) Operating characteristics, electrical characteristics, and furnished accessories. Include automatic closing devices and testing and resetting instructions

5) Installation instructions.

C. Shop Drawings: Include detailed plans, elevations, details of framing members, anchoring methods, required clearances, hardware, and accessories. Include relationship with adjacent construction.

D. Selection Samples: For each finish specified, two complete sets of color chips representing manufacturer's full range of available colors and finishes.

E. Verification Samples: For each finish specified, two samples, minimum size 6

F. Manufacturer's Certificates: Certify products meet or exceed specified requirements.

G. Closeout Submittals: Provide manufacturer’s maintenance instructions Including a detailed parts lists and maintenance recommendations.

1.6. Quality Assurance

A. Manufacturer Qualifications: Company specializing in performing Work of this section with a minimum of 3 years experience in the fabrication and installation of security closures.

B. Installer Qualifications: Installer Qualifications: Company specializing in performing Work of this section with minimum 2 years and approved by manufacturer.

1.7. Delivery, Storage, and Handling

A. Store products in manufacturer's unopened packaging until ready for installation.

B. Protect materials from exposure to moisture. Do not deliver until after wet work complete and dry.

C. Store materials in dry, warm, ventilated weathertight location.

1.8. Project Conditions

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

1.9. Coordination

A. Coordinate Work with other operations and installation of adjacent materials to avoid damage to installed materials.

1.10. Warranty

A. See Section 017800 - Closeout Submittals for additional warranty requirements.

OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR 083323.13 - 3

B. Warranty: Manufacturer’s limited door warranty and operator system, except the finish, to be free of defects in material and workmanship for 5 years.

PART 2 PRODUCTS

2.1. Manufacturers

A. Overhead Door Corporation; _______: www.overheaddoor.com/#sle.

B. Overhead Door Corporation; RapidShield Model 998: www.overheaddoor.com/#sle.

C. Rite-Hite Corp; Raptor Rigid High Speed and XL: www.ritehite.com/#sle.

D. Wayne-Dalton, a Division of Overhead Door Corporation; High Speed Metal Door, Model ADV-X 888:

www.wayne-dalton.com/#sle.

E. Substitutions: See Section 016000 - Product Requirements.

2.2. High Performance Exterior High Speed Roll-Up Metal Doors

A. Performance

1) Opening Speed: Door to operate at a variable speed up to 80 inches (2032 mm) per second (control system dependent).

2) Closing Speed: Door to operate at a variable speed up to 20 inches (508 mm) per second.

3) Operation Cycles: Drive motor and gearbox capable of operating for not less than 1,000,000 cycles. One operation cycle is complete when a door is opened from the closed position to the fully open position and returned to the closed position.

B. Materials and Components:

1) Door Curtain Design

a. Door Curtain: Double-Walled 6063-T6 Aluminum, 5.8 inch by 1.2 inch thick, with interior face also using 6063-T6 aluminum for the hinge system. Doors that use hinges not made of metal will not be accepted. Door will have UV-Resistant weatherseal between aluminum panel sections.

b. 6063-T6 Aluminum

c. Finish: Premium Powder Coat, color as selected by Architect.

2) Bottom Bar: 6063-T6 Aluminum with integrated wireless sensing edge.

a. Finish: Premium powder coat, color as selected by Architect.

b. Provide door with a wireless failsafe electric safety edge.

3) Guides: Construct of structural steel, high strength steel cover with structural aluminum track.

a. Extend assembly a maximum of 10 inches (254 mm) from the wall.

OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR 083323.13 - 4

b. Extend assembly width a maximum of 17 inches (432 mm) outward to the side from clear daylight opening.

c. Guides have a minimum wall thickness of 3/8 inch for the wall angle and 0.18 inches (4.5 mm) for the cover, to minimize damage if impacted.

d. Integrated blanking light curtain channel within the guide. Doors with light curtains mounted outside of the guide will not be accepted. Doors without blanking light curtain will not be accepted

e. Door shall have no visible air gaps along the side or top of the door when door panel is in the closed or down position.

f. Guides will have weather seal on entire height of door panel.

g. Springless System: No springs permitted to assist operation of the door. Guides with enclosed spring must not be accepted due to

4) Door Header: Head plates with structural steel truss system spanning the width of the opening. Brackets made of structural Steel and powder coated finish with self-aligning bearings.

a. Truss System: Pre-fabricated structure made of structural steel and powder coated finish.

b. Header Door Track: Design that is of concentric circular shape and appropriate spacing to prevent metal to metal contact of slats on each concentric loop for smooth door movement and minimal noise. Doors with header track made of aluminum will not be accepted due to potential strength and fatigue issues for load bearing.

c. Brackets: Minimum 1/4 inch (6 mm) thick ASTM A 36 hot rolled steel with heavy-duty, self-aligning bearings with cast iron housings.

d. Head frame with a single brush seal along the top of the door.

e. Finish: Premium powder coat, color as selected by Architect.

5) Optional Fascia:

a. Finish: Premium powder coat, color as selected by Architect.

6) Electric Door Operator: UL listed.

a. Usage Classification: Heavy duty, rated up to 60 cycles per hour under constant load.

b. Motor Exposure: Exterior use.

c. Direct Side Mounted: Operator mounted directly to door drive shaft to the left or right side of the door. No chain and sprocket allowed.

d. Electrical Characteristics: Phase and Voltage: 3-Phase 220-240V AC; Hertz: 50/60.

OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR 083323.13 - 5

e. Operator: Minimum 1.0 horsepower. Motor and gearbox designed for high cycle operation with built-in gearbox failure door stop safety device

f. Hand Chain: Manual brake disengagement pull switch and hand chain which allows door to be manually opened and closed during a power outage and installation.

Provide locked enclosure for secure storage of chain and pull switch when manual lifting is not required.

g. Limit System: Magnetic type providing absolute positioning with push to set and remote setting capabilities. Limit system shall remain synchronized with the door during manual operation and supply power interruptions.

h. Timer to Close: Each door to have automatic closing controlled by an adjustable hold open time delay.

7) Control System

a. Microprocessor based with variable frequency drive controller, capable of variable speed control in both up and down directions. System incorporates a Liquid Crystal Display (LCD) to display the system status.

b. Capable of monitoring and reporting on a variety of operating conditions, including:

Current operating status, Current command status, Current error status (if applicable), Hoist interlock status (if applicable), Service reminder status, and 24VDC status.

c. Control system is housed in a NEMA 4X panel with built-in push buttons and main power padlock-able rotary disconnect switch.

8) Activation Devices:

a. Vehicular Type Activation Devices: Radio Control Activation: Near proximity portable push button remote control programmable to individual doors or multiple doors in common.

b. One Button Remote Control

9) Safety Devices: Provide for condition of exposure and for long-term, maintenance-free operation under normal traffic load for type of occupancy indicated. Coordinate safety devices with door operation and door operator mechanisms.

a. Door provided with blanking light curtain located in plane to the travelling path of the door curtain. Doors with light curtain mounted to the exterior of the guide will not be accepted.

10) Finish Requirements:

a. Galvanized Steel: Hood galvanized in accordance with ASTM A 653 and receive rust-inhibitive, roll coating process, including 0.2 mils thick baked-on prime paint, and 0.6 mils thick baked-on black polyester top coat.

OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR 083323.13 - 6

b. PowderGuard powder coat: Guides, Truss and brackets shall be powder coated with weather and corrosion resistant polyester powder coat.

PART 3 EXECUTION

3.1. Examination

A. Verify opening sizes, tolerances and conditions are acceptable.

B. Verify site electrical characteristics and supplies.

C. Examine conditions of substrates, supports, and other conditions under which this work is to be performed.

D. If substrate preparation is the responsibility of another installer, notify Architect of unsatisfactory preparation before proceeding.

3.2. Preparation

A. Clean surfaces thoroughly prior to installation.

B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3. Installation

A. Install in accordance with manufacturer's written instructions.

B. Use anchorage devices to securely fasten assembly to wall construction and building structure without distortion or stress.

C. Securely and rigidly brace components suspended from structure. Secure guides to structural members only.

D. Fit and align assembly including hardware; level and plumb, to provide smooth operation.

E. Coordinate installation of electrical service; see Section 260583.

F. Install enclosure and perimeter trim.

G. Instruct Owner’s personnel in proper operating procedures and maintenance schedule.

3.4. Startup Service

A. Engage a factory-authorized service representative to perform startup service.

1) Perform installation and startup checks according to manufacturer's written instructions.

2) Test and adjust controls and safety devices. Replace damaged and malfunctioning controls and equipment.

3.5. Tolerances

A. Maintain dimensional tolerances and alignment with adjacent work.

OVERHEAD RAPID COILING DOORS - OVERHEAD DOOR 083323.13 - 7

B. Maximum Variation from Plumb: 1/16 inch (1.6 mm).

C. Maximum Variation from Level: 1/16 inch (1.6 mm).

D. Longitudinal or Diagonal Warp: Plus or minus 1/8 inch per 10 feet (3.2 mm per 3 m).

3.6. Adjusting

A. Test for proper operation and adjust as necessary to provide proper operation without binding or distortion.

B. Adjust hardware and operating assemblies for smooth and noiseless operation.

C. Adjust seals to provide tight fit around entire perimeter.

3.7. Cleaning

A. Clean curtain and components using non-abrasive materials and methods recommended by manufacturer.

B. Remove labels and visible markings.

C. Touch-up, repair or replace damaged products before Substantial Completion

3.8. Demonstration

A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain high speed roll-up doors.

3.9. Protection

A. Protect installed products until completion of project.

METAL CANOPIES 107316.13 - 1

SECTION 107316.13 - METAL CANOPIES

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Attached metal canopies.

1.2. SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Submit product data sheets, including material descriptions and finishes, and preparation instructions and recommendations.

C. Shop Drawings: Prior to commencement of fabrication, submit detailed shop drawings, showing profiles, sections of components, finishes, and fastening details.

D. Design Data: Submit comprehensive structural analysis of design for the specified loads. Stamp and sign calculations by professional engineer.

1.3. QUALITY ASSURANCE

A. . Manufacturer Qualifications: Company specializing in manufacturing products specified in this

B. Installer Qualifications: Company specializing in performing Work of this section with minimum five years documented experience with projects of similar scope and complexity, and approved by Manufacturer.

C. Source Limitations: Provide each type of product from a single manufacturing source to ensure uniformity.

D. Mock-Up: Construct a mock-up with actual materials in sufficient time for Architect’s review and to not delay construction progress. Locate mock-up as acceptable to Architect and provide temporary foundations and support.

1) Intent of mock-up is to demonstrate quality of workmanship and visual appearance.

2) If mock-up is not acceptable, rebuild mock-up until satisfactory results are achieved.

3) Retain mock-up during construction as a standard for comparison with completed work.

4) Do not alter or remove mock-up until work is completed or removal is authorized.

1.4. PRE-INSTALLATION CONFERENCE

A. Convene a conference approximately two weeks before scheduled commencement of the Work.

Attendees shall include Architect, Contractor and trades involved. Agenda shall include schedule,responsibilities, critical path items and approvals.

1.5. DELIVERY, STORAGE, AND HANDLING

A. Store and handle in strict compliance with manufacturer's written instructions and recommendations.

METAL CANOPIES 107316.13 - 2

B. Protect from damage due to weather, excessive temperature, and construction operations.

1.6. PROJECT CONDITIONS

A. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's recommended limits.

1.7. WARRANTY

A. Manufacturer's Warranty: Aluminum frames are warranted against defects in workmanship for five

PART 2 PRODUCTS

2.1. MANUFACTURERS

A. Metal Canopies:

1) Columbus Awning Company: www.columbusawningcompany.com/#sle.

2) Lawrence Fabric & Metal Structures, Inc; LFS-FLA Canopy :

www.lawrencefabric.com/#sle.

3) Mapes Industries; Super Lumideck: https://mapes.com/#sle.

4) Substitutions: See Section 016000 - Product Requirements.

2.2. Metal Canopies

A. Performance and Design Requirements:

1) . Standards Compliance: Comply with local building codes.

B. Standard Canopy, Basis of Design: LFS-FLA Canopy; as manufactured by Lawrence Fabric and Metal Structures Inc.

1) Material: Extruded aluminum, alloy 6063-T6.

2) Fabrication Method: Welded and mechanically fastened

3) Fascia: G-style gutter fascia

C. Welded as one piece or in sections as required for width of canopy.

a. Profile: 8 inches

2) Decking: Aluminum Interlocking Pan.

a. Profile: Profile: 3x6 Inch

3) Water Dispersal:

a. Include scupper(s)

4) Support:

METAL CANOPIES 107316.13 - 3

5) Internal Steel Outriggers: 3 inch x 3 inch x .188 square steel tube with plate

6) Finishes

a. AAMA 2603 Compliant Two-Part Polyurethane Enamel or Powder Coat Finish: 1- Year Warranty

PART 3 EXECUTION

3.1. EXAMINATION

A. Do not begin installation until substrates have been properly constructed and prepared.

B. Confirm dimensions and elevations.

C. Verify that wall structure can support canopy loads.

D. If substrate preparation is the responsibility of another installer, notify Architect in writing of unsatisfactory preparation before proceeding.

3.2. PREPARATION

A. Clean surfaces thoroughly prior to installation.

B. Prepare surfaces using the methods recommended by the manufacturer for achieving the best result for the substrate under the project conditions.

3.3. INSTALLATION

A. Install in accordance with manufacturer's instructions, approved submittals, and in proper relationship with adjacent construction.

3.4. CLEANING AND PROTECTION

A. Clean products in accordance with the manufacturer's recommendations.

B. Touch-up, repair or replace damaged products before Substantial Completion.

TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 1

SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Testing, adjustment, and balancing of air systems.

1.2. REFERENCE STANDARDS

A. AABC (NSTSB) - AABC National Standards for Total System Balance, 7th Edition; 2016.

B. ASHRAE Std 111 - Measurement, Testing, Adjusting, and Balancing of Building HVAC Systems; 2024, with Errata (2025).

C. NEBB (TAB) - Procedural Standard for Testing, Adjusting and Balancing of Environmental Systems;

2019, with Errata (2022).

D. SMACNA (TAB) - HVAC Systems Testing, Adjusting and Balancing; 2023.

1.3. SUBMITTALS

A. See Section 013000 - Administrative Requirements, for submittal procedures.

B. Final Report: Indicate deficiencies in systems that would prevent proper testing, adjusting, and balancing of systems and equipment to achieve specified performance.

1) Provide final copies for Engineer and for inclusion in operating and maintenance manuals.

2) Provide reports in PDFformat .

3) Include actual instrument list, with manufacturer name, serial number, and date of calibration.

4) Form of Test Reports: Where the TAB standard being followed recommends a report format use that; otherwise, follow ASHRAE Std 111.

5) Units of Measure: Report data in I-P (inch-pound) units only.

6) Include the following on the title page of each report:

a. Name of Testing, Adjusting, and Balancing Agency.

b. Address of Testing, Adjusting, and Balancing Agency.

c. Telephone number of Testing, Adjusting, and Balancing Agency.

d. Project name.

e. Project location.

f. Project Engineer.

TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 2

g. Project Contractor.

h. Report date.

PART 2 PRODUCTS - NOT USED

PART 3 EXECUTION

3.1. GENERAL REQUIREMENTS

A. Perform total system balance in accordance with one of the following:

1) SMACNA (TAB).

B. Begin work after completion of systems to be tested, adjusted, or balanced and complete work prior to Substantial Completion of the project.

C. TAB Agency Qualifications:

1) Company specializing in the testing, adjusting, and balancing of systems specified in this section.

2) Certified by one of the following:

a. AABC, Associated Air Balance Council: www.aabc.com/#sle; upon completion submit AABC National Performance Guaranty.

b. NEBB, National Environmental Balancing Bureau: www.nebb.org/#sle.

c. TABB, The Testing, Adjusting, and Balancing Bureau of National Energy Management Institute: www.tabbcertified.org/#sle.

D. TAB Supervisor and Technician Qualifications: Certified by same organization as TAB agency.

3.2. EXAMINATION

A. Verify that systems are complete and operable before commencing work. Ensure the following conditions:

1) Systems are started and operating in a safe and normal condition.

2) Temperature control systems are installed complete and operable.

3) Final filters are clean and in place. If required, install temporary media in addition to final filters.

4) Duct systems are clean of debris.

5) Fans are rotating correctly.

6) Access doors are closed and duct end caps are in place.

B. Beginning of work means acceptance of existing conditions.

TESTING, ADJUSTING, AND BALANCING FOR HVAC 230593 - 3

3.3. ADJUSTMENT TOLERANCES

A. Air Handling Systems: Adjust to within plus or minus 5 percent of design for supply systems and plus or minus 10 percent of design for return and exhaust systems.

3.4. AIR SYSTEM PROCEDURE

A. Adjust air distribution systems to provide required or design supply,and exhaust air quantities at site altitude.

B. Adjust outside air automatic dampers for design conditions.

3.5. SCOPE

A. Test, adjust, and balance the following:

1) Fans.

3.6. MINIMUM DATA TO BE REPORTED

A. Supply and Exhaust Fans:

1) Location.

2) Manufacturer.

3) Model number.

4) Serial number.

5) Air flow, specified and actual.

6) Total static pressure (total external), specified and actual.

7) Inlet pressure.

8) Discharge pressure.

DUCT INSULATION 230713 - 1

SECTION 230713 - DUCT INSULATION

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Duct insulation.

B. Jacketing and accessories.

1.2. REFERENCE STANDARDS

A. ASTM B209/B209M - Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate;

2021a.

B. ASTM C553 - Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications; 2024.

C. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials; 2025.

D. UL 723 - Standard for Test for Surface Burning Characteristics of Building Materials; Current Edition, Including All Revisions.

1.3. SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide product description, thermal characteristics, list of materials and thickness for each service, and locations.

1.4. DELIVERY, STORAGE, AND HANDLING

A. Accept materials on site in original factory packaging, labelled with manufacturer's identification, including product density and thickness.

B. Protect insulation from weather and construction traffic, dirt, water, chemical, and mechanical damage, by storing in original wrapping.

PART 2 PRODUCTS

2.1. REGULATORY REQUIREMENTS

A. Surface Burning Characteristics: Flame spread index/Smoke developed index of 25/50, maximum, when tested in accordance with ASTM E84 or UL 723.

2.2. RIGID FOAM SHEATHING

A. Manufacturer:

1) CertainTeed Corporation; ______: www.c

2) Dow

3) OX Engineered Products

DUCT INSULATION 230713 - 2

4) Owens Corning Corporation

B. Insulation: Rigid foam sheet.

1) Maximum Service Temperature: 165 degrees F.

2) Maximum Water Vapor Absorption: 0.3 percent by volume.

3) Compressive Strength Minimum PSI: 15

2.3. JACKETING AND ACCESSORIES

A. Flexible Weather-Proofing Outdoor Jacket:

1) Manufacturers:

2) Material: Aluminum foil/polymer laminate with rubberized asphalt layer and acrylicadhesive..

3) Color: Gray

4) Finish: Embossed.

B. Reinforced Tape:

1) Manufacturers:

a. Same manufacturer as jacketing.

2) Factory-applied, pressure sensitive adhesive jacketing on paper release liner.

PART 3 EXECUTION

3.1. EXAMINATION

A. Test ductwork for design pressure prior to applying insulation materials.

B. Verify that surfaces are clean, foreign material removed, and dry.

3.2. INSTALLATION

A. Install jacketing in strict compliance with manufacturer's instructions.

B. Neatly cut and trim foam sheets to form tight seams and corners.

C. Secure foam sheets to duct with proper construction adhesive and tape joints prior to application of jacketing.

D. Slope exterior ductwork to shed water.

3.3. SCHEDULES

A. Ducts Exposed to Outdoors:

DUCT INSULATION 230713 - 3

1) Rigid Foam Sheet Insulation: 1 inch thick.

DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC 230923 - 1

SECTION 230923 - DIRECT-DIGITAL CONTROL SYSTEM FOR HVAC

PART 1 GENERAL

1.1. SECTION INCLUDES

A. System description.

PART 2 PRODUCTS

2.1. TEMPERATURE CONTROL CONTRACTOR (TCC) FURNISHED PRODUCTS

A. New Products: TCC's standard controllers and devices compatible with existing Building Automation System.

B. Existing Products: Building Automation System front end, carbon monoxide sensors.

2.2. SYSTEM DESCRIPTION

A. Automatic temperature control field monitoring and control system using field programmable micro-processor based units.

B. Provide control systems consisting of control dampers and operators, indicating devices, interface equipment and other apparatus and accessories required to operate ventilation system and to perform functions specified.

C. Include installation and calibration, supervision, adjustments, and fine tuning necessary for complete and fully operational system.

PART 3 EXECUTION

3.1. INSTALLERS

A. Installer List:

3.2. EXAMINATION

A. Verify existing conditions before starting work.

3.3. INSTALLATION

A. Install control units and other hardware in position on permanent walls where not subject to excessive vibration.

B. Install software in control units and in operator work station as required to implement specified requirements and appropriate to sequence of operation.

C. Provide conduit and electrical wiring as required to provide sequence of operation.

3.4. DEMONSTRATION AND INSTRUCTIONS

A. Demonstrate complete and operating system to Owner.

HVAC DUCTS AND CASINGS 233100 - 1

SECTION 233100 - HVAC DUCTS AND CASINGS

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Metal ducts.

1.2. RELATED REQUIREMENTS

A. Section 230713 - Duct Insulation: External insulation and duct liner.

B. Section 233300 - Air Duct Accessories.

C. Section 233700 - Air Outlets and Inlets: Fabric air distribution devices.

1.3. REFERENCE STANDARDS

A. ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process; 2025a.

B. NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilating Systems; 2024.

C. NFPA 90B - Standard for the Installation of Warm Air Heating and Air-Conditioning Systems; 2024.

D. SMACNA (DCS) - HVAC Duct Construction Standards Metal and Flexible; 2020.

PART 2 PRODUCTS

2.1. GENERAL REQUIREMENTS

A. Provide UL Class 1 ductwork, fittings, hangers, supports, and appurtenances in accordance with NFPA 90A and SMACNA (DCS) guidelines unless stated otherwise.

B. Provide metal duct unless otherwise indicated.

C. Duct Shape and Material in accordance with Allowed Static Pressure Range:

1) Rectangular: Plus or minus 2 in-wc (500 Pa) of galvanized steel.

2) Flexible Duct (Fabric and wire): Plus or minus 1/2 in-wc (125 Pa); see Section 233700.

D. Duct Sealing and Leakage in accordance with Static Pressure Class:

1) Duct Pressure Class and Material for Common Mechanical Ventilation Applications:

a. Supply Air: 2 in-wc (500 Pa) pressure class, galvanized steel.

2) Low Pressure Service: Up to 2 in-wc (500 Pa):

a. Seal: Class C, apply to seal off transverse joints.

b. Leakage: Rectangular: Class 12 or 12 cfm/100 sq ft (680 Lpm/9.3 sq m).

E. Duct Fabrication Requirements:

HVAC DUCTS AND CASINGS 233100 - 2

1) Duct and Fitting Fabrication and Support: SMACNA (DCS) including specifics for continuously welded round and oval duct fittings.

2) Use reinforced and sealed sheet-metal materials at recommended gauges for indicated operating pressures or pressure class.

3) Construct tees, bends, and elbows with radius of not less than 1-1/2 times width of duct on centerline. Where not possible and where rectangular elbows must be used, provide airfoil turning vanes of perforated metal with glass fiber insulation.

4) Increase duct sizes gradually, not exceeding 15 degrees divergence wherever possible;

maximum 30 degrees divergence upstream of equipment and 45 degrees convergence downstream.

2.2. METAL DUCTS

A. Material Requirements:

1) Galvanized Steel: Hot-dipped galvanized steel sheet, ASTM A653/A653M FS Type B, with G60/Z180 coating.

PART 3 EXECUTION

3.1. INSTALLATION

A. Install, support, and seal ducts in accordance with SMACNA (DCS).

B. Comply with safety standards NFPA 90A and NFPA 90B.

C. During construction, provide temporary closures of metal or taped polyethylene on open ductwork to prevent construction dust from entering the ductwork system.

D. Increase duct sizes gradually, not exceeding 15 degrees divergence wherever possible; maximum 30 degrees divergence upstream of equipment and 45 degrees convergence downstream.

E. Flexible Ducts: Connect to metal ducts with draw bands.

F. Duct sizes indicated are precise inside dimensions. For lined ducts, maintain sizes inside lining.

G. Locate ducts with sufficient space around equipment to allow normal operating and maintenance activities.

H. Connect diffusers to low-pressure ducts directly or with 3 feet (1.5 m) maximum length of flexible duct held in place with strap or clamp.

AIR DUCT ACCESSORIES 233300 - 1

SECTION 233300 - AIR DUCT ACCESSORIES

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Air turning devices/extractors.

B. Backdraft dampers - metal.

C. Backdraft dampers - fabric.

D. Duct access doors.

E. Duct test holes.

F. Flexible duct connectors.

G. Low leakage (Class 1A) control dampers.

1.2. RELATED REQUIREMENTS

A. Section 233100 - HVAC Ducts and Casings.

1.3. REFERENCE STANDARDS

A. NFPA 90A - Standard for the Installation of Air-Conditioning and Ventilating Systems; 2024.

B. SMACNA (DCS) - HVAC Duct Construction Standards Metal and Flexible; 2020.

1.4. SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide for shop-fabricated assemblies including duct access doors and low leakage motorized dampers.

1.5. DELIVERY, STORAGE, AND HANDLING

A. Protect dampers from damage to operating linkages and blades.

PART 2 PRODUCTS

2.1. AIR TURNING DEVICES/EXTRACTORS

A. Manufacturers:

1) Carlisle HVAC Products

2) Elgen Manufacturing Company, Inc

3) Ductmate

4) Ruskin Company

AIR DUCT ACCESSORIES 233300 - 2

B. Multi-blade device with double wall blades aligned in short dimension; aluminum construction; with individually adjustable blades, mounting straps.

2.2. BACKDRAFT DAMPERS - METAL

2.3. BACKDRAFT DAMPERS - FABRIC

A. Fabric Backdraft Dampers: Factory-fabricated.

1) Blades: Neoprene coated fabric material.

2) Birdscreen: 1/2 inch (12 mm) nominal mesh of galvanized steel or aluminum.

3) Maximum Velocity: 1000 fpm (5 mps) face velocity.

2.4. DUCT ACCESS DOORS

A. Manufacturers:

1) Ductmate Industries, Inc.

2) Elgen Manufacturing Company, Inc.

3) Ruskin Company

B. Fabrication: Rigid and close fitting of galvanized steel with sealing gaskets and quick-fastening locking devices.

1) Up to 18 inches (450 mm) Square: Provide two hinges and two sash locks.

2.5. DUCT TEST HOLES

2.6. FLEXIBLE DUCT CONNECTORS

A. Manufacturers:

1) Carlisle HVAC Products

2) Ductmate Industries, Inc

3) Elgen Manufacturing Company, Inc

B. Fabricate in accordance with SMACNA (DCS) and as indicated.

C. Flexible Duct Connections: Fabric crimped into metal edging strip.

2.7. LOW LEAKAGE (CLASS 1A) CONTROL DAMPERS

A. Manufacturers:

1) Ruskin Company

2) United Enertech

3) Greenheck.

AIR DUCT ACCESSORIES 233300 - 3

B. Maximum Leakage Allowed: 3 cfm/sq ft at 1 in-wc (15.2 L/sec/sq m at 0.25 kPa).

C. Frame:

1) Material: 16-gauge galvanized steel.

D. Blade:

1) Type: Multi-blade airfoil for high pressure.

2) Operation: Opposed type.

3) Material: 20-gauge galvanized steel.

PART 3 EXECUTION

3.1. INSTALLATION

A. Install accessories in accordance with manufacturer's instructions, NFPA 90A, and follow SMACNA (DCS). See Section 233100 for duct construction and pressure class.

B. Provide access door(s) where indicated on drawings.

C. Provide turning vanes where indicated on drawings.

HVAC POWER VENTILATORS 233423 - 1

SECTION 233423 - HVAC POWER VENTILATORS

PART 2 PRODUCTS

1.1. POWER VENTILATORS - GENERAL

A. Static and Dynamically Balanced: Comply with AMCA 204.

B. Performance Ratings: Comply with AMCA 210, bearing certified rating seal.

C. Sound Ratings: Comply with AMCA 301, tested to AMCA 300, bearing certified sound ratings seal.

D. Fabrication: Comply with AMCA 99.

E. Electrical Components: Listed and classified by Underwriters Laboratories Inc. as suitable for the purpose specified and indicated.

DEDICATED OUTDOOR AIR UNITS 237433 - 1

SECTION 237433 - DEDICATED OUTDOOR AIR UNITS

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Outdoor-mounted Make-up air unit.

1.2. REFERENCE STANDARDS

A. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

B. UL (DIR) - Online Certifications Directory; Current Edition.

1.3. SUBMITTALS

A. See Section 013000 - Administrative Requirements for submittal procedures.

B. Product Data: Provide data with dimensions, duct and service connections, accessories, controls, electrical nameplate data, and wiring diagrams.

C. Manufacturer's Instructions: Indicate rigging, assembly, and installation instructions.

D. Warranty: Submit manufacturers warranty and ensure forms have been filled out in Owner's name and registered with manufacturer.

1.4. WARRANTY

A. See Section 017800 - Closeout Submittals for additional warranty requirements.

B. Provide five year manufacturers warranty for compressor/condenser unit.

PART 2 PRODUCTS

2.1. MANUFACTURERS

A. CaptiveAire Systems

B. Greenheck

C. Loren Cook

2.2. OUTDOOR-MOUNTED DOAS

A. Packaged Unit:

1) Casing and Components:

a. 18 gauge, 0.0478 inch (1.21 mm) steel panels reinforced with structural angles and channels to ensure rigidity.

b. Provide bolted access panels to access each sections from either side of unit.

c. Provide hinged door with lockable handle for serviceable sections.

DEDICATED OUTDOOR AIR UNITS 237433 - 2

d. Drain Pan: Galvanized steel with corrosion-resistant coating.

2) Performance Ratings: ASHRAE Std 90.1, EER and COP as applicable.

3) Regulatory Requirements: AHRI 270 (SI/I-P) rated, NFPA 70, and UL (DIR) listed.

4) Insulation: Minimum 3/4 inch (13 mm) thick acoustic duct liner for lining cabinet interior.

5) External Surface Finish: Heat resistant baked enamel.

6) Outdoor Installation: Weatherproofed casing, with intake louver.

7) Outside Air Damper:

a. Set outdoor air dampers to fully open when fan starts and close 30 seconds after fan stops, adjustable.

B. Filter Section:

1) Filter: Removable, 2 inches (50 mm) thick MERV-8.

C. Fan Section:

1) Provide direct or plenum mounted constant volume fan motors; see Section 230513.

2) Draw-through, backward-curved fan, constructed of corrosion-resistant, galvanized material and designed for efficient, quiet operation.

3) Factory program for both soft start and constant flow output over static pressure range.

4) Provide preinstalled neutral wire protection when required to support specified fan type.

5) Motor to include thermal overload protection, quick disconnect plug, and permanently lubricated bearings.

D. Unit Controls:

1) DDC:

a. BACNET compatible

2) Local Control Panel: Interface to include on-off-auto switch, indicating lights for supply fan, and clogged filter indication.

E. Furnish make-up air unit and associated components and accessories produced by a single manufacturer.

PART 3 EXECUTION

3.1. INSTALLATION

A. Install in accordance with manufacturer's instructions.

B. Provide flexible duct connections on outlet from unit; see Section 233300.

DEDICATED OUTDOOR AIR UNITS 237433 - 3

C. Coordinate BAS, BMS, or Integrated Automation linking between unit controller(s) and remote front end interface.

SELECTIVE DEMOLITION FOR ELECTRICAL 260505 - 1

SECTION 260505 - SELECTIVE DEMOLITION FOR ELECTRICAL

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Electrical demolition.

1.2. RELATED REQUIREMENTS

A. Section 017000 - Execution and Closeout Requirements: Additional requirements for alterations work.

B. Section 028400 - Polychlorinate Biphenyl (PCB) Remediation: Removal of equipment and materials containing substances regulated under the Federal Toxic Substances Control Act (TSCA), including but not limited to those containing PCBs and mercury.

1.3. SUBMITTALS

A. See Section 013000 - Administrative Requirements, for submittal procedures.

B. Sustainable Design Documentation: Submit certification of removal and appropriate disposal of abandoned cables containing lead stabilizers.

PART 2 PRODUCTS

2.1. MATERIALS AND EQUIPMENT

A. Materials and equipment for patching and extending work: As specified in individual sections.

PART 3 EXECUTION

3.1. EXAMINATION

A. Verify field measurements and circuiting arrangements are as indicated.

B. Verify that abandoned wiring and equipment serve only abandoned facilities.

C. Demolition drawings are based on casual field observation and existing record documents.

D. Report discrepancies to Architect before disturbing existing installation.

E. Beginning of demolition means installer accepts existing conditions.

3.2. PREPARATION

A. Disconnect electrical systems in walls, floors, and ceilings to be removed.

B. Provide temporary wiring and connections to maintain existing systems in service during construction.

When work must be performed on energized equipment or circuits, use personnel experienced in such operations.

C. Existing Fire Alarm System: Maintain existing system in service until new system is accepted. Disable system only to make switchovers and connections. Minimize outage duration.

SELECTIVE DEMOLITION FOR ELECTRICAL 260505 - 2

1) Notify Owner before partially or completely disabling system.

2) Notify local fire service.

3) Make notifications at least 24 hours in advance.

4) Make temporary connections to maintain service in areas adjacent to work area.

3.3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL WORK

A. Perform work for removal and disposal of equipment and materials containing toxic substances regulated under the Federal Toxic Substances Control Act (TSCA) in accordance with applicable federal, state, and local regulations. Applicable equipment and materials include, but are not limited to:

1) PCB-containing electrical equipment, including transformers, capacitors, and switches.

2) PCB- and DEHP-containing lighting ballasts.

3) Mercury-containing lamps and tubes, including fluorescent lamps, high intensity discharge (HID), arc lamps, ultra-violet, high pressure sodium, mercury vapor, ignitron tubes, neon, and incandescent.

B. Remove, relocate, and extend existing installations to accommodate new construction.

C. Remove abandoned wiring to source of supply.

D. Remove exposed abandoned conduit, including abandoned conduit above accessible ceiling finishes. Cut conduit flush with walls and floors, and patch surfaces.

E. Disconnect and remove abandoned luminaires. Remove brackets, stems, hangers, and other accessories.

F. Repair adjacent construction and finishes damaged during demolition and extension work.

G. Maintain access to existing electrical installations that remain active. Modify installation or provide access panel as appropriate.

H. Extend existing installations using materials and methods compatible with existing electrical installations, or as specified.

3.4. CLEANING AND REPAIR

A. See Section 017419 - Construction Waste Management and Disposal for additional requirements.

B. Clean and repair existing materials and equipment that remain or that are to be reused.

C. Panelboards: Clean exposed surfaces and check tightness of electrical connections. Replace damaged circuit breakers and provide closure plates for vacant positions. Provide typed circuit directory showing revised circuiting arrangement.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 1

SECTION 260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 GENERAL

1.1. SECTION INCLUDES

A. Single conductor building wire.

B. Metal-clad cable.

C. Wiring connectors.

D. Electrical tape.

E. Heat shrink tubing.

F. Oxide inhibiting compound.

G. Wire pulling lubricant.

H. Cable ties.

1.2. RELATED REQUIREMENTS

A. Section 260505 - Selective Demolition for Electrical: Disconnection, removal, and/or extension of existing electrical conductors and cables.

B. Section 260553 - Identification for Electrical Systems: Identification products and requirements.

1.3. REFERENCE STANDARDS

A. ASTM B3 - Standard Specification for Soft or Annealed Copper Wire; 2013 (Reapproved 2024).

B. ASTM B8 - Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium- Hard, or Soft; 2023.

C. ASTM B33 - Standard Specification for Tin-Coated Soft or Annealed Copper Wire for Electrical Purposes; 2010, with Editorial Revision (2020).

D. ASTM B787/B787M - Standard Specification for 19 Wire Combination Unilay-Stranded Copper Conductors for Subsequent Insulation; 2004 (Reapproved 2020).

E. ASTM D3005 - Standard Specification for Low-Temperature Resistant Vinyl Chloride Plastic Pressure- Sensitive Electrical Insulating Tape; 2024.

F. ASTM D4388 - Standard Specification for Nonmetallic Semi-Conducting and Electrically Insulating Rubber Tapes; 2020.

G. NECA 1 - Standard for Good Workmanship in Electrical Construction; 2023.

H. NECA 120 - Standard for Installing Armored Cable (AC) and Type Metal-Clad (MC) Cable; 2018.

I. NEMA WC 70 - Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy; 2021.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 2

J. NETA ATS - Standard for Acceptance Testing Specifications for Electrical Power Equipment And Systems; 2025.

K. NFPA 70 - National Electrical Code; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.

L. UL 4 - Armored Cable; Current Edition, Including All Revisions.

M. UL 44 - Thermoset-Insulated Wires and Cables; Current Edition, Including All Revisions.

N. UL 83 - Thermoplastic-Insulated Wires and Cables; Current Edition, Including All Revisions.

O. UL 267 - Outline of Investigation for Wire-Pulling Compounds; Current Edition, Including All Revisions.

P. UL 486A-486B - Wire Connectors; Current Edition, Including All Revisions.

Q. UL 486C - Splicing Wire Connectors; Current Edition, Including All Revisions.

R. UL 486D - Sealed Wire Connector Systems; Current Edition, Including All Revisions.

S. UL 510 - Polyvinyl Chloride, Polyethylene, and Rubber Insulating Tape; Current Edition, Including All Revisions.

T. UL 1569 - Metal-Clad Cables; Current Edition, Including All Revisions.

1.4. ADMINISTRATIVE REQUIREMENTS

A. Coordination:

1) Coordinate sizes of raceways, boxes, and equipment enclosures installed under other sections with the actual conductors to be installed, including adjustments for conductor sizes increased for voltage drop.

2) Coordinate with electrical equipment installed under other sections to provide terminations suitable for use with the conductors to be installed.

3) Notify Architect of any conflicts with or deviations from Contract Documents. Obtain direction before proceeding with work.

1.5. SUBMITTALS

A. See Section 013000 - Administrative Requirements, for submittal procedures.

B. Product Data: Provide manufacturer's standard catalog pages and data sheets for conductors and cables, including detailed information on materials, construction, ratings, listings, and available sizes, configurations, and stranding.

1.6. QUALITY ASSURANCE

A. Comply with requirements of NFPA 70.

B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 3

C. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.

D. Product Listing Organization Qualifications: An organization recognized by OSHA as a Nationally Recognized Testing Laboratory (NRTL) and acceptable to authorities having jurisdiction.

1.7. DELIVERY, STORAGE, AND HANDLING

A. Receive, inspect, handle, and store conductors and cables in accordance with manufacturer's instructions.

1.8. FIELD CONDITIONS

A. Do not install or otherwise handle thermoplastic-insulated conductors at temperatures lower than 14 degrees F (-10 degrees C), unless otherwise permitted by manufacturer's instructions. When installation below this temperature is unavoidable, notify Architect and obtain direction before proceeding with work.

PART 2 PRODUCTS

2.1. CONDUCTOR AND CABLE APPLICATIONS

A. Do not use conductors and cables for applications other than as permitted by NFPA 70 and product listing.

B. Provide single conductor building wire installed in suitable raceway unless otherwise indicated, permitted, or required.

C. Nonmetallic-sheathed cable is not permitted.

D. Armored cable is not permitted.

E. Metal-clad cable is permitted only as follows:

1) Where not otherwise restricted, may be used:

a. Where concealed above accessible ceilings for final connections from junction boxes to luminaires.

1) Maximum Length: 6 feet (1.8 m).

2) In addition to other applicable restrictions, may not be used:

a. Where exposed to view.

b. Where exposed to damage.

c. For damp, wet, or corrosive locations, unless provided with a PVC jacket listed as suitable for those locations.

2.2. CONDUCTOR AND CABLE GENERAL REQUIREMENTS

A. Provide products that comply with requirements of NFPA 70.

B. Provide products listed, classified, and labeled as suitable for the purpose intended.

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260519 - 4

C. Unless specifically indicated to be excluded, provide all required conduit, boxes, wiring, connectors, etc.

as required for a complete operating system.

D. Comply with NEMA WC 70.

E. Thermoplastic-Insulated Conductors and Cables: Listed and labeled as complying with UL 83.

F. Thermoset-Insulated Conductors and Cables: Listed and labeled as complying with UL 44.

G. Conductors for Grounding and Bonding: Also comply with Section 260526.

H. Conductors and Cables Installed Exposed in Spaces Used for Environmental Air (only where specifically permitted): Plenum rated, listed and labeled as suitable for use in return air plenums.

I. Conductor Material:

1) Provide copper conductors only. Aluminum conductors are not acceptable for this project. Conductor sizes indicated are based on copper.

2) Copper Conductors: Soft drawn annealed, 98 percent conductivity, uncoated copper…

This is the start of the file's text. The full file is on GovTribe.