This is a bid set of construction plan drawings and specifications for the City of Bloomington, Illinois Police Department Garage Door and Ventilation Upgrades project (Bid #2027-04). The project involves the installation of one high-speed rollup garage door, removal and demolition of existing security gates and equipment, installation of a makeup air unit (MAU-1) with 11,020 CFM capacity, modifications to exhaust ventilation systems, and associated HVAC ductwork and piping. The scope includes work at the Lower Level 1 of the Bloomington Police Department located at 305 South East Street, Bloomington, Illinois. The construction documents include architectural drawings showing floor plans and exterior elevations, structural details for equipment pad and bollard installations, mechanical plans detailing the MAU-1 intake louver opening, ductwork routing, and control systems, and electrical plans for power connections and controls. Sealed bids are due via the City's e-Procurement Portal by Thursday, August 27, 2026, at 11:00 am CST. The design was prepared by licensed professionals registered with the State of Illinois, including architects Dustin Rhoades, Warren Kohm, and John Bishop, and structural engineer John Paul Goedken, with a bid set date of March 17, 2026.
The project includes demolition of an existing rolling security gate and transponder receiver, removal of precast concrete bollards, and salvage and reinstallation of existing signage. New construction includes an 8-inch diameter galvanized steel pipe bollard painted safety yellow, a new metal canopy structure, a high-speed overhead door measuring 24 feet wide by 8 feet 5¼ inches high with steel prefinished aluminum-clad wood construction, and an enclosed overhead door guide enclosure. The MAU-1 unit includes a motorized intake damper and louvered intake coordinated with existing carbon monoxide sensors to activate the supply fan when CO levels exceed 25 PPM. Electrical work includes a 60-ampere, 3-phase connection to Panel H for the MAU-1 and a 20-ampere, single-phase connection for the exhaust fan (EF-7). The City of Bloomington has indicated that for public works projects estimated in excess of $50,000, a project labor agreement may be required unless determined not to advance the City's interests in cost, efficiency, quality, safety, timeliness, and skilled labor force development.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
City of Bloomington
305 S. East Street, Bloomington, IL
DATE: 03/17/2026
LOCATION MAP INDEX OF DRAWINGS
PROFESSIONAL REGISTRATIONS
Bl oo m in gt on
P ol ic e
G ar ag e
D oo r a nd
V en til at io n
U pg ra de s
BI
D S
ET
C ity o f B lo om in gt on
PROJECT NO.: 02501052.001
BID SET
03/17/2026
BLOOMINGTON POLICE GARAGE DOOR
Design Firm Registration #184001856
200 West College Avenue, Suite 301 - Normal, Illinois, 61761 - Phone: (309) 663-8436 / info@f-w.com
AND VENTILATION UPGRADES
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL SUPERVISION. I AM
A DULY LICENSED ARCHITECT/ENGINEER UNDER THE LAWS OF THE
STATE OF ILLINOIS.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
DUSTIN RHOADES
03/17/2026
11/30/2027
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL SUPERVISION. I AM
A DULY LICENSED ARCHITECT/ENGINEER UNDER THE LAWS OF THE
STATE OF ILLINOIS.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
WARREN KOHM
03/17/2026
11/30/2027
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL SUPERVISION. I AM
A DULY LICENSED ARCHITECT/ENGINEER UNDER THE LAWS OF THE
STATE OF ILLINOIS.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
JOHN BISHOP
03/17/2026
11/30/2026
ARCHITECTURE MECHANICAL ELECTRICAL
Grossinger Arena
Bloomington Police
City Hall Bloomington Libray
McLean County Law and Justice Center
M ai n St re et
Ce nt er S tre et
Olive Street
Ea st
S tre et
ARCHITECTURE
A0.1 GENERAL INFORMATION
A1.Ln LOWER LEVEL 1 FLOOR PLAN - NORTH
A3.1 EXTERIOR ELEVATIONS
STRUCTURAL
S1.1 GENERAL NOTES, DETAILS, AND PLAN
MECHANICAL
M0.1 GENERAL INFORMATION
M1.1 LOWER LEVEL 1 PLAN
M1.2 FIRST FLOOR PLAN
M1.3 ENLARGED LOWER LEVEL 1 PLAN AND SECTION
M2.1 MECHANICAL DETAILS AND SCHEDULES
ELECTRICAL
E0.1 GENERAL INFORMATION
E0.2 GENERAL INFORMATION AND SCHEDULES
E1.1 LOWER LEVEL 1 PLAN
E1.2 FIRST FLOOR PLAN
E5.1 ELECTRICAL SCHEDULES
THE PORTION OF THIS TECHNICAL SUBMISSION DESCRIBED BELOW WAS
PREPARED BY ME OR UNDER MY DIRECT PERSONAL SUPERVISION. I AM
A DULY LICENSED ARCHITECT/ENGINEER UNDER THE LAWS OF THE
STATE OF ILLINOIS.
PAGES OR DIVISIONS COVERED:
LICENSE RENEWAL DATE:
DATE:
NAME:
SIGNATURE:
JOHN PAUL GOEDKEN
03/17/2026
11/30/2027
STRUCTURAL
ALIGN
ABBREVIATIONS
CL
IN INCH
INCL INCLUDING
INSUL INSULATION
INT INTERIOR
JAN JANITOR
JT JOINT
L/S LANDSCAPE
LAM PLASTIC LAMINATE
LAV LAVATORY
LB(S) POUND(S)
LF LINEAR FEET (FOOT)
LT LIGHT
LTTR LONG-TERM THERMAL
RESISTANCE
MAS MASONRY
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
N NORTH
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED,
CONTRACTOR INSTALLED
OFCR OWNER FURNISHED,
CONTRACTOR ROUGH-IN
OFOI OWNER FURNISHED,
INSTALLED BY OTHERS
O TO O OUT TO OUT
OPNG OPENING
OPP OPPOSITE
OVHD OVERHEAD
PEB PRE-ENGINEERED BUILDING
PERIM PERIMETER
PFIN PREFINISHED
PJF PREFORMED JOINT FILLER
PL PLATE
PLBG PLUMBING
PLYWD PLYWOOD
PNT PAINT
PR PAIR
PT PRESSURE TREATED
PTD PAINTED
PWR POWER
RAD RADIUS
RB RUBBER BASE
REC RECESSED
REINF REINFORCED
REQ'D REQUIRED
REV REVISED (REVISION)
RD ROOF DRAIN
RM ROOM
RO ROUGH OPENING
RV DRYWALL/MILLWORK REVEAL
S SOUTH
SB SPLASH BLOCK
SF SQUARE FEET (FOOT)
SIM SIMILAR
SPEC SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUSP SUSPENDED
SY SQUARE YARD(S)
T/O TOP OF
T&G TONGUE AND GROOVE
TELE TELEPHONE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W/ WITH
W/O WITHOUT
W WEST
WC WATER CLOSET
WD WOOD
WH WATER HEATER
WT WEIGHT
WWF WELDED WIRE FABRIC
GENERAL
ACP/APC ACOUSTIC CEILING PANEL/
ACOUSTIC PANEL CEILING
ACT ACOUSTIC(AL) TILE
ADJ ADJUSTABLE
ADT'L ADDITIONAL
AFF ABOVE FINISHED FLOOR
AGG AGGREGATE
ALT ALTERNATE
AL ALUMINUM
APPROX APPROXIMATE(LY)
ASPH ASPHALT
AUTO AUTOMATIC
B/O BOTTOM OF
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
CENTERLINE
C/C CENTER TO CENTER
CEM CEMENT(ITIOUS)
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CFOI CONTRACTOR FURNISHED,
INSTALLED BY OTHERS
CJ CONTROL JOINT
CLL CONTRACT LIMIT LINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CTR CENTER(ED)
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DET/DTL DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
DWG(S) DRAWING(S)
E EAST
EA EACH
EC ELECTRICAL CONTRACTOR
EHO ELECTRICAL HOLD OPEN
EIFS EXTERIOR INSULATION
FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EX/EXIST EXISTING
EXJ EXPANSION JOINT
EXP EXPOSED
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISH FLOOR ELEVATION
FIN FINISH
FLSHG FLASHING
FLR FLOOR
FRMG FRAMING
FT FOOT/FEET
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GYP GYPSUM
HDWR HARDWARE
HM HOLLOW METAL
HOL HOLLOW
HOR HORIZONTAL
HT HEIGHT
HVAC HEATING/VENTILATION/AIR
CONDITIONING
ID INSIDE DIAMETER
IDPH ILLINOIS DEPARTMENT OF
PUBLIC HEALTH
A. REFER TO LIFE SAFETY SHEETS FOR LIFE SAFETY INFORMATION.
B. CONTRACTOR TO PROVIDE ALL ADDITIONAL FRAMING NECESSARY FOR ALL
OPENINGS AND SUPPLEMENTAL FRAMING ABOVE PARTITIONS.
C. CONTRACTOR SHALL COORDINATE WITH OTHER TRADES FOR SYSTEM RELATED
PENETRATIONS NOT SHOWN.
D. CONTRACTOR SHALL MAINTAIN THE BUILDING IN A WEATHERPROOF CONDITION
AT ALL TIMES.
E. TEMPORARY BARRICADES SHALL BE INSTALLED BY CONTRACTOR AT AREAS OF
WORK TO CONTAIN CONSTRUCTION ACTIVITY AND TO PREVENT UNAUTHORIZED
PERSONS FROM ENTERING THE WORK AREA. COORDINATE LOCATIONS WITH
OWNER.
F. ALL AREAS TO BE DEMOLISHED OR DISTURBED BY ANY DEMOLITION ARE TO BE
PATCHED AND PAINTED (OR PREPARED FOR OTHER SCHEDULED FINISH). IF
PAINTING IS REQUIRED, ENTIRE WALL SHALL RECEIVE PAINT TO AVOID
MISMATCH OF COLOR.
G. UPON REMOVAL OF TEMPORARY PARTITIONS, CONTRACTOR IS RESPONSIBLE
FOR PATCHING TO MATCH EXISTING ADJACENT CONSTRUCTION.
H. IT IS THE RESPONSIBILITY OF EACH CONTRACTOR TO PROVIDE COMPLETE
WORKING SYSTEMS FOR ALL NEW ELEMENTS AND TO COORDINATE THEIR
WORK WITH ALL OTHER TRADES.
I. ALL CONTRACTORS SHALL PROVIDE NEW, UNDAMAGED MATERIALS UNLESS
OTHERWISE SPECIFIED.
J. STORE MATERIALS IN SUCH A MANNER AS NOT TO OVERSTRESS, OVERLOAD, OR
OTHERWISE PUT AN UNSAFE LOAD ON ANY STRUCTURE DURING
CONSTRUCTION.
K. INSTALL ALL WORK IN ACCORDANCE WITH CURRENT APPLICABLE CODES,
PUBLISHED STANDARDS, AND ACCEPTABLE CONSTRUCTION STANDARDS.
L. DETAILS ARE GENERALLY TYPICAL AND ARE NOT TO BE CONSTRUED AS LIMITED
TO THOSE AREAS SPECIFICALLY INDICATED. REVIEW ANY QUESTIONS OR
CONFLICTING INFORMATION WITH THE DESIGN PROFESSIONAL PRIOR TO
FABRICATION OR INSTALLATION.
M. CONTRACTOR SHALL VERIFY DIMENSIONS IN FIELD PRIOR TO BEGINNING
CONSTRUCTION.
N. HINGE SIDE OF DOOR JAMBS TO BE LOCATED 4” FROM NEAREST WALL
INTERSECTION UNLESS OTHERWISE NOTED.
GENERAL NOTES
GLAZING TYPE
ROOF PITCH
DOOR NUMBER
CEILING/ SOFFIT
HEIGHT
MATL
1'-0"
-1
SLOPE: 1/4"
SLOPE/ROOF SLOPE
WALL SECTION
INTERIOR ELEVATION
COLUMN GRID
ELEVATION
REVISION NOTE
ENLARGED CALLOUT
ROOM DESIGNATION
BREAK LINE
DETAIL #
SHEET #
DETAIL #
SHEET #
A8.1
EXTERIOR ELEVATION
DETAIL #
SHEET #
A8.1
A8.1
A8.1
BUILDING SECTION
DETAIL #
PAGE #
A8.1
A8.1
DETAIL SECTION
DETAIL #
SHEET #
A8.1
WALL GRID
(REPRESENTS
FACE OF EXISTING
WALL)
XX.X
XX.X
ELEVATION
0'-0"
0"
-6" CHANGE IN LEVEL
ALIGN
ARCHITECTURE
ROOM
NAME
CASEWORK TYPE AL1
DEMOLITION KEYNOTE
TOILET ACCESSORY
WALL TYPE
KEYNOTE#.#
D#.#
T#
B#
FINISH MATERIAL
TRANSITION
FLOOR FINISH
WALL FINISH
ACCENT WALL
WALL BASE
PATTERN/LINEAR
DIRECTION
CASEWORK
HORIZONTAL FACE
FINISH
CASEWORK
VERTICAL FACE
FINISH
MISCELLANEOUS
FINISH
SIGNAGE / ARTWORK
FINISH
CORNER GUARD
WINDOW
TREATMENT FINISH
ROLLER SHADE
DRAPERY / CUBICLE
CURTAIN
VALANCE / CORNICE
FINISH KEYNOTE
CEILING FINISH
XXX-#
XXX-#
X-#
X-#
X-#
X-#
X-#
X-#
X-#
X-#
X-#
X-#
DOOR, WINDOW &
FRAME FINISH
X-#
INTERIOR
SYMBOLS LEGEND
NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
200 W. COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:3 :5
P
M A0.1
GENERAL
INFORMATION
GDK
JEB
02501052.001
Bloomington Police Garage Door and Ventilation Upgrades
City of Bloomington
305 S. East Street Bloomington, Illinois
03/17/2026
03/17/2026
BID SET
GDK
BID SET
A
A
B
B
C
C
D
D
E
E
F
F
G
G
01-1
PARKING
STAIR
D
A3.1
A3.1
A3.1
2'-8"
2'-0"
7"
32.02
32.02 D32.01
A. ALL DIMENSIONS ARE TO FACE OF STUD, CMU AND/OR CONCRETE UNLESS
NOTED OTHERWISE.
B. OPENING DIMENSIONS ARE TO FINISH FRAME. CONTRACTOR TO VERIFY ROUGH
OPENING REQUIREMENTS
C. ALL WOOD IN CONTACT WITH CONCRETE SHALL BE PRESSURE TREATED.
D. ALL NEW WORK SHALL BE PLUMB TRUE, AND LEVEL UNLESS OTHERWISE NOTED.
PLAN GENERAL NOTES
1. DOORS WITH ELECTRICAL REQUIREMENTS TO COORDINATE WITH ELECTRICAL
CONTRACTOR
DOOR SCHEDULE GENERAL NOTES
PF=
STL=
PREFINISHED
ALUMINUM CLAD WOOD
ABBREVIATIONS:
OHCD
SEE SCHEDULE
S E
E S
C H
E D
U L E
DOOR SCHEDULE
DOOR
WIDTH HEIGHT MAT'L
DOOR HEAD DETAIL
NO
JAMB
DETAIL NO
THRESH
DETAIL NO
REQ'S
ELECT REMARKSNO FINISH ELEV
LOWER LEVEL I
01-1 24' - 0" 8' - 5 1/4" STL PF OHCD 4/A3.1 1&2/A3.1 - Yes www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
200 W. COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:3 :5
P
M A1.L1n
LOWER LEVEL 1
PLAN - NORTH
GDK
JEB
02501052.001
Bloomington Police Garage Door and Ventilation Upgrades
City of Bloomington
305 S. East Street Bloomington, Illinois
03/17/2026
03/17/2026
BID SET
GDK
BID SET
SCALE: 1/8" = 1'-0"
LOWER LEVEL 1 FLOOR PLAN - NORTH
NORTH
KEY PLAN
N.T.S.
NORTH
SOUTH
SCALE: 1/4" = 1'-0"
DOOR ELEVATIONS
0 4 8 16
NORTH
PLAN
KEYNOTES (BY DIVISION)
DIVISION 00
DIVISION 03
03.01 6" PC CONCRETE SIDEWALK ON COMPACTED SLAB. CONCRETE SHALL BE
CLASS SI, 3500 PSI IN ACCORDANCE WITH SECTION 1020 OF THE STANDARD
SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION INDICATED IN TABLE
03.02 3/4" BITUMINOUS EXPANSION JOINT FILLER
03.03 INTREGAL CURB, MONOLITHIC WITH THE SIDE WALK AT 6" HIGH (OR AS
NECESSARY TO ACCOMODATE ADJACENT GRADE AND 6" WIDE. THE CURB
HEIGHT SHALL TAPER TO FOLLOW SLOPE OF ADJACENT GRADE.
DIVISION 08
08.01 HIGH-SPEED OVERHEAD DOOR
08.02 OVERHEAD DOOR CONTROLLER; COORDINATE LOCATION IN FIELD
08.03 HINGED GUIDE OPENING AREA
08.04 ENCLOSED OHD GUIDE ENCLOSURE
DIVISION 10
10.01 REINSTALL SALVAGED "NO TRESPASSING" SIGN. COORDINATE LOCATION IN
THE FIELD
10.02 REINSTALL SALVAGED "PARKING LOT #4" SIGN. COORDINATE LOCATION IN
THE FIELD
10.03 NEW METAL CANOPY
DIVISION 32
32.01 8" DIAMETER STANDARD WEIGHT GALVANIZED STEEL PIPE (CONCRETE
FILLED). PAINT SAFETY YELLOW. SEE DETAIL 5/A3.1
32.02 6" DIAMETER STANDARD WEIGHT GALVANIZED STEEL PIPE BOLLARD
(CONCRETE FILLED). PAINT SAFETY YELLOW. SEE DETAIL 5/A3.1
DEMOLITION KEYNOTES (BY DIVISION)
DIVISION03
D03.01 DEMOLISH EXISTING PRECAST CONCRETE BOLLARD
DIVISION 10
D10.01 REMOVE EXISTING "NO TRESPASSING" SIGN AND SALVAGE TO BE
REINSTALLED IN NEW LOCATION
D10.02 REMOVE EXISTING "PARKING LOT #4" SIGN AND SALVAGE TO BE REINSTALLED
IN NEW LOCATION
DIVISION 32
D32.01 DEMOLISH EXISTING ROLLING SECURITY GATE AND ASSOCIATED
ACCESSORIES INCLUDING OPERATORS, CONTROLS AND ELECTRICAL WIRING.
D32.02 DEMOLISH EXISTING ROLLING GATE TRANSPONDER RECEIVER
D#.# jftacek Typewriter
NOTE: EXISTING OPERATOR CONTROLLER SHALL BE
CAREFULLY REMOVED AND PLACED ON A PALLET TO BE
GIVEN TO THE OWNER.
jftacek Typewriter jftacek Typewriter
FIRST FLOOR
0'-0"
LOWER LEVEL I
-13'-4"
12345
08.01
NO TRESPASSING
AUTHORIZED
PERSONNEL ONLY
BEYOND THIS POINT.
ALL PERSONS AND
VEHICLES ARE SUBJECT
TO SEARCH
VIOLATORS WILL BE
PROSECUTED
NO TRESPASSING
AUTHORIZED
PERSONNEL ONLY
BEYOND THIS POINT.
ALL PERSONS AND
VEHICLES ARE SUBJECT
TO SEARCH
VIOLATORS WILL BE
PROSECUTED
City of Bloomington Parking Lot #4 No Public Parking Bloomington Police Only
10.01
10.01
10.02
32.01 32.01
10.03
FIRST FLOOR
0'-0"
LOWER LEVEL I
-13'-4"
12345
D32.01
D03.01 D03.01
D10.01
D10.01 D10.02 D32.02
FIRST FLOOR
0'-0"
LOWER LEVEL I
-13'-4"
A3.1
/4
/8
4'-0"
4'-0"
/4
ALIGN
HIGH/SPEED
OVERHEAD
DOOR
/8
NEW METAL
CANOPY
± 5'-0"
ALIGN
ALIGN
3'-0"
O
P N
G
W
ID
T H
EDGE OF
(E) DRIVE
03.01
03.02
32.01
08.03
08.04
32.01
03.01
03.02
03.03
ENCLOSED OHD
GUIDE ENCLOSURE
O P
N G
W
ID
T
H
08.02
08.03
08.04
± 5'-0" 6"
3'-0"
S
LO
P E
CONCRETE
TO BE
CROWNED 1"
STANDARD
WEIGHT
GALVANIZED
STEEL PIPE
(CONCRETE
FILLED)
1" WASH
FINISHED GRADE
CLASS SI (3500
PSI) CONCRETE.
CONCRETE TO
BEAR ON
UNDISTURBED
MATERIAL ON
ALL SIDES
APPROVED
SUBGRADE
NOTES:
COLOR OF BOLLARD SHALL
BE YELLOW AND SHALL
BE PAINTED AS FOLLOWS:
A. SOLVENT CLEAN TO
REMOVE OIL, GREASE
AND OTHER
CONTAMINANTS.
B. APPLY METAL PRIMER
FOR GALVANIZED
SURFACES.
C. APPLY TWO FINISH COATS
OF APPROVE EXTERIOR
PAINT FOR METAL
SURFACES.
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
200 W. COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/2
/2
:3 :5
P
M A3.1
EXTERIOR
ELEVATIONS AND
DETAILS
GDK
JEB
02501052.001
Bloomington Police Garage Door and Ventilation Upgrades
City of Bloomington
305 S. East Street Bloomington, Illinois
03/17/2026
03/17/2026
BID SET
GDK
BID SET
SCALE: 1/4" = 1'-0"
EAST ELEVATION - PARKING DECK 0 2 4 8
SCALE: 1/4" = 1'-0"
EAST ELEVATION - PARKING DECK DEMOLITION 0 2 4 8
DEMOLITION KEYNOTES (BY DIVISION)
DIVISION03
D03.01 DEMOLISH EXISTING PRECAST CONCRETE BOLLARD
DIVISION 10
D10.01 REMOVE EXISTING "NO TRESPASSING" SIGN AND SALVAGE TO BE
REINSTALLED IN NEW LOCATION
D10.02 REMOVE EXISTING "PARKING LOT #4" SIGN AND SALVAGE TO BE REINSTALLED
IN NEW LOCATION
DIVISION 32
D32.01 DEMOLISH EXISTING ROLLING SECURITY GATE AND ASSOCIATED
ACCESSORIES INCLUDING OPERATORS, CONTROLS AND ELECTRICAL WIRING.
D32.02 DEMOLISH EXISTING ROLLING GATE TRANSPONDER RECEIVER
KEYNOTES (BY DIVISION)
DIVISION 00
DIVISION 03
03.01 6" PC CONCRETE SIDEWALK ON COMPACTED SLAB. CONCRETE SHALL BE
CLASS SI, 3500 PSI IN ACCORDANCE WITH SECTION 1020 OF THE STANDARD
SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION INDICATED IN TABLE
03.02 3/4" BITUMINOUS EXPANSION JOINT FILLER
03.03 INTREGAL CURB, MONOLITHIC WITH THE SIDE WALK AT 6" HIGH (OR AS
NECESSARY TO ACCOMODATE ADJACENT GRADE AND 6" WIDE. THE CURB
HEIGHT SHALL TAPER TO FOLLOW SLOPE OF ADJACENT GRADE.
DIVISION 08
08.01 HIGH-SPEED OVERHEAD DOOR
08.02 OVERHEAD DOOR CONTROLLER; COORDINATE LOCATION IN FIELD
08.03 HINGED GUIDE OPENING AREA
08.04 ENCLOSED OHD GUIDE ENCLOSURE
DIVISION 10
10.01 REINSTALL SALVAGED "NO TRESPASSING" SIGN. COORDINATE LOCATION IN
THE FIELD
10.02 REINSTALL SALVAGED "PARKING LOT #4" SIGN. COORDINATE LOCATION IN
THE FIELD
10.03 NEW METAL CANOPY
DIVISION 32
32.01 8" DIAMETER STANDARD WEIGHT GALVANIZED STEEL PIPE (CONCRETE
FILLED). PAINT SAFETY YELLOW. SEE DETAIL 5/A3.1
32.02 6" DIAMETER STANDARD WEIGHT GALVANIZED STEEL PIPE BOLLARD
(CONCRETE FILLED). PAINT SAFETY YELLOW. SEE DETAIL 5/A3.1
D#.#
SCALE: 3/8" = 1'-0"
SECTION @
ROLL-UP
SECURITY DOOR
SCALE: 3/4" = 1'-0"
HEAD DETAIL @
ROLL-UP
SECURTY
DOOR/CANOPY
SCALE: 1/2" = 1'-0"
PLAN DETAIL
SCALE: 1/2" = 1'-0"
PLAN DETAIL
0 1 2 4
0 1 2 4
0 21 40 1 2
SCALE: 3/4" = 1'-0"
BOLLARD DETAIL 0 1 2
SLOPE
G
DRILL HOLES IN CORNER OF OPENING
(1 1/2" DIA MIN). CUT EDGES TO HOLE.
DO NOT OVER-CUT CORNERS.
S1.1
A P
P R
O X
S
E E
M E
C H
D R
A W
IN
G
S
C O
O R
D W
L O
U V
E R
M F
R S
E E
M E
C H
D W
G S
S
E E
M E
C H
D W
G S
3'-6" MAX
2'-6" MAX
SEE 3/S1.1 FOR
EXTERIOR EQUIP PAD
T O
H E
A D
O F
N E
W O
P E
N
IN
G
M
IN
B
E L
O W
C O
R B
E L
DRILL HOLES IN CORNER OF
OPENING. CUT EDGES TO HOLE. DO
NOT OVER-CUT CORNERS.
PAINT ENDS OF EXPOSED REBAR
WITH RUST-INHIBITING PAINT- 2
COATS MIN.
(E) CORBEL
(E) PRECAST DOUBLE TEES
(E) CAST IN PLACE CONC FOUND WALL
A. THE STRUCTURAL ENGINEERING DESIGN IS BASED ON AND IN ACCORDANCE WITH THE FOLLOWING
CODE:
INTERNATIONAL BUILDING CODE - 2018
RISK CATEGORY = IV
B. UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS, THE STRUCTURAL DESIGN IS BASED ON
THE FOLLOWING TYPICAL UNIFORM LOADS:
DEAD LOADS FLOOR = 117 PSF. PRECAST, TOPPING, MISC
LIVE LOADS PARKING = 50PSF
PARKING = 2000LB POINT LOAD
SNOW LOADS Pg = 30 PSF Pbal = 30.2 PSF Ce = 1.0 I = 1.2 Ct = 1.2
WIND DESIGN DATA V (ULT) = 115 MPH
V (NOM) = 90 MPH
EXPOSURE CATEGORY = B
GCpi = (+/-)0.18
COMPONENTS AND CLADDING ULTIMATE WIND PRESSURES
EFFECTIVE ULTIMATE
ZONE WIND AREA (SF) WIND PRESSURE (PSF)
1 10 = +/- 49
100 = +/- 38
2 10 = +/- 64 100 = +/- 51
3 10 = +/- 87 100 = +/- 60
4 10 = +/- 31 50 = +/- 28 100 = +/- 26
5 10 = +/- 37 50 = +/- 32 100 = +/- 26
EARTHQUAKE DESIGN DATA
I = 1.5 Ss = 0.243 S1 = 0.104
SITE CLASS = D
SDS = 0.259
SD1 = 0.165
SEISMIC DESIGN CATEGORY = D
BASIC SEISMIC-FORCE-
RESISTING SYSTEM = PROPOSED CHANGES DO NOT AFFECT THE MAIN
VERTICAL OR LATERAL LOAD RESISTING SYSTEM
DESIGN CRITERIA:
A. ALL DETAILS, SECTIONS, AND PLAN NOTES SHOWN ON THE DRAWINGS ARE
INTENDED TO BE TYPICAL AND SHALL BE CONSTRUED TO APPLY TO SIMILAR
CONDITIONS ELSEWHERE.
B. THE CONTRACTOR SHALL FIELD CHECK AND VERIFY ALL EXISTING CONDITIONS
AND REPORT ANY DISCREPANCIES TO THE OWNER'S REPRESENTATIVE BEFORE
PROCEEDING WITH THE WORK.
C. THE EXISTING CONDITIONS INDICATED ON THE DRAWINGS ARE BASED ON
MATERIAL PROVIDED BY THE OWNER AND NO CLAIM IS MADE AS TO ITS
ABSOLUTE COMPLETENESS AND/OR ACCURACY PRIOR TO THE START OF
CONSTRUCTION OPERATIONS.
D. WHERE NEW CONSTRUCTION ABUTS OR INTEGRATES WITH EXISTING
CONSTRUCTION, THE CONTRACTOR SHALL VERIFY THAT THE EXISTING
CONDITIONS AND DIMENSIONS ARE CLOSE TO THOSE THAT HAVE BEEN
ASSUMED. IF THERE ARE ANY VARIANCES THAT WILL PREVENT THE WORK FROM
BEING COMPLETED IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS,
THEY SHALL BE REPORTED TO THE ENGINEER IMMEDIATELY UPON DISCOVERY.
THE ENGINEER SHALL ADVISE THE CONTRACTOR AS TO THE NECESSARY
MODIFICATIONS.
E. ALL LATERAL LOAD RESISTANCE AND STABILITY OF THE BUILDING IN THE
EXISTING STRUCTURE IS PROVIDED BY CAST-IN-PLACE CONCRETE FOUNDATIONS
WALLS IN EACH ORTHOGONAL DIRECTION. THE CONCRETE FLOOR SERVES AS
HORIZONTAL DIAPHRAGMS THAT DISTRIBUTE THE LATERAL WIND AND SEISMIC
FORCES HORIZONTALLY TO THE SHEAR WALLS. THE SHEAR WALLS CARRY THE
APPLIED LATERAL LOADS TO THE BUILDING FOUNDATION.
F. CONSTRUCTION MATERIAL SHALL BE SPREAD OUT IF PLACED ON FRAMED ROOF
OR FLOOR. LOAD SHALL NOT EXCEED THE DESIGN LIVE LOAD PER SQUARE FOOT.
G. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE
DESIGN INTENT FOR THE FINISHED STRUCTURE. THEY DO NOT INDICATE MEANS
OR METHODS OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION.
GENERAL CONSTRUCTION:
M A
X
M
IN
C L R
#4 AT 12" OC EA WAY
MIN
6"
EQUIPMENT PER
MECHANICAL -ANCHORAGE TO
SLAB PER MECHANICAL MFR
GRADE PER CIVIL
#4 HORIZ AT 16" OC W/
STD HOOK EA END
#4 VERT AT 12" OC W/ STD
HOOK AT TOP AS SHOWN
COMPACTED DRAINAGE ROCK
8"8"
TWO-POUR OPTION
SINGLE POUR OPTION
www.f-w.com Engineers | Architects | Surveyors | Scientists
GROUP
DATE:
DRAWN:
REVIEWED:
SHEET TITLE:
SHEET NUMBER:
PROJECT NO.:
PROJECT:
200 W. COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
ISSUE:
# DATE: DESCRIPTION:
DESIGNED:
/1
/2
:2 :4
A
M S1.1
GENERAL NOTES,
DETAILS, AND PLAN
JPG
PMH
02501052.001
Bloomington Police Garage Door And Ventilation Upgrades
City of Bloomington
305 S East Street Bloomington, IL
03/06/2026
03/18/2026
BID SET
JPG
BID SET
NORTH
PLAN
SCALE: 1/4" = 1'-0"
ENLARGED LOWER LEVEL 1 DEMOLITION PLAN
SCALE: 1/2" = 1'-0"
SECTION AT LOUVER OPENING
GENERAL NOTES
SCALE: 3/4" = 1'-0"
CONC EQUIP PAD/ FROST WALL
BID SET
03/17/2026
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
GENERAL
INFORMATION
M0.1
TMG
TMG
DRR
PROJECT:
DATE:
PROJECT NO.:
City Of Bloomington
Bloomington Police Garage Door And Ventilation Upgrades
305 S. East Street Bloomington, Illinois
03/17/2026
02501052.001
DESCRIPTION:DATE:#
ISSUE:
BID SET
03/17/2026
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
200 WEST COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
BD BOILER BLOW DOWN
CD CONDENSATE DRAIN
CWS CONDENSER WATER SUPPLY
HCWSDUAL TEMPERATURE SUPPLY
HPS HIGH PRESSURE STEAM
HRS HEAT RECOVERY SUPPLY
HTWSHIGH TEMP WATER SUPPLY
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
LS LOOP SUPPLY
MPS MEDIUM PRESSURE STEAM
PD PUMP DISCHARGE
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
CHR CHILLED WATER RETURN
CWR CONDENSER WATER RETURN
HCWRDUAL TEMPERATURE RETURN
HPR HIGH PRESSURE STEAM CONDENSATE RETURN
HRR HEAT RECOVERY RETURN
HTWRHIGH TEMP WATER RETURN
HWR HOT WATER RETURN
LPR LOW PRESSURE STEAM CONDENSATE RETURN
LR LOOP RETURN
MPR MEDIUM PRESSURE STEAM CONDENSATE RETURN
ABOVE CEILING/AC AIR CONDITIONER
OA OUTDOOR AIR
ACC AIR COOLED CONDENSER
AF AIR FILTER
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AMS AIR MEASURING STATION
AS AIR SEPARATOR
AV AUTOMATIC AIR VENT
B BOILER
BAS BUILDING AUTOMATION SYSTEM
BDD BACKDRAFT DAMPER
BFC BELOW FINISHED CEILING
BFP BACKFLOW PREVENTION DEVICE
BJ BETWEEN JOISTS
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTUH BRITISH THERMAL UNITS PER HOUR
CA COMPRESSED AIR
CBS COUNTER BALANCED SHUTTER
CC COOLING COIL
CF CEILING / CIRCULATING FAN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CNV CONVECTOR
COND CONDENSATE
CP CONDENSATE PUMP
CRAC COMPUTER ROOM AIR CONDITIONER
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CW DOMESTIC COLD WATER
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DC DRY COOLER
DN DOWN
DP DIFFERENTIAL PRESSURE
DS DUCT SILENCER
EA EXHAUST AIR
EBB ELECTRIC BASEBOARD HEATER
EF EXHAUST FAN
EG EXHAUST GRILLE (LESS DAMPER)
EHC ELECTRIC HEATING COIL
EL ELEVATION
ER EXHAUST REGISTER
ERV ENERGY RECOVERY VENTILATOR
ET EXPANSION TANK
FA FRESH AIR
FD FIRE DAMPER
FDC FLEXIBLE DUCT CONNECTION
FFA FROM FLOOR ABOVE
FFB FROM FLOOR BELOW
FPC FLEXIBLE PIPE CONNECTION
FPT FAN POWERED AIR TERMINAL
FT FINNED TUBE RADIATION
GF GAS FURNACE
GIH GRAVITY INTAKE HOOD
GPM GALLONS PER MINUTE
GR GLYCOL RETURN
GS GLYCOL SUPPLY
GUH GAS UNIT HEATER
HU HUMIDIFIER
HC HEATING COIL
HCWR DUAL TEMPERATURE RETURN
HCWS DUAL TEMPERATURE SUPPLY
HP HEAT PUMP
HPR HIGH PRESSURE STEAM RETURN
HPS HIGH PRESSURE STEAM SUPPLY
HRC HEAT RECOVERY COIL
HS HUMIDITY SENSOR
HWP HOT WATER PUMP
HWR HOT WATER RETURN
LOW PRESSURE STEAM SUPPLY
LOW PRESSURE STEAM RETURN
KITCHEN HOOD -COMMERCIAL
HEAT EXCHANGER
HOT WATER SUPPLY
LPS
LPR
KH
HX
HWS
THOUSANDS OF BTU PER HOUR
MOTORIZED DAMPER
MAKEUP AIR UNIT
MIXED AIR
MBH
MD
MAU
MA
OBD OPPOSED BLADE DAMPER
P PUMP
PBD PARALLEL BLADE DAMPER
PRV PRESSURE RELIEF VALVE
PS PRESSURE SWITCH
PSI POUNDS PER SQUARE INCH
PTAC
RA RETURN AIR
RF RETURN AIR FAN
RG RETURN GRILLE (LESS DAMPER)
RH ROOF HOOD
RHC REHEAT COIL
RLFA RELIEF AIR
RPZ REDUCED PRESSURE BFP
RR RETURN REGISTER (WITH DAMPER)
RTU ROOFTOP AIR HANDLING UNIT
SA SUPPLY AIR
SAS SELF-ACTING SHUTTER
SD SUPPLY DIFFUSER/SMOKE DAMPER
SF SUPPLY FAN / SQUARE FOOT
SFD SMOKE/FIRE DAMPER
SG SUPPLY GRILLE
SR SUPPLY REGISTER
TCAC TEMP. CONTROL AIR COMPRESSOR
TCAD TEMP. CONTROL AIR DRYER
TDV TRIPLE DUTY VALVE
TFA TO FLOOR ABOVE
TFB TO FLOOR BELOW
TOD TOP OF DUCT
TOP TOP OF PIPE
UC UNIT COOLER
UFD UNDERFLOOR DUCT
UH UNIT HEATER
UV UNIT VENTILATOR
VAV VARIABLE AIR VOLUME TERMINAL
VD VOLUME DAMPER
VFD VARIABLE FREQUENCY DRIVE
AUTOMATIC AIR VENT
TEMPERATURE SENSOR/SWITCH
PRESSURE GAUGE
THERMOMETER
PIPE ANCHOR
PIPE GUIDES
MANUAL AIR VENT
FLOW SENSOR/SWITCH
PIPE EXPANSION JOINT
PIPE UNION
CONCENTRIC REDUCER
ECCENTRIC REDUCER
WYE STRAINER
WYE STRAINER W/DRAIN VALVE
DIRECTION OF FLOW
STEAM BUCKET TRAP
STEAM F&T TRAP
BACKFLOW PREVENTER
PIPE TURNING UP
PIPE TURNING DOWN
TEE OFF TOP
TEE OFF BOTTOM
PIPE TEE
PIPE CAP
PLAN 90 DEGREE ELBOW
PLAN 45 DEGREE ELBOW
PIPING SYSTEM (SOLID LINE)
PIPING SYSTEM (DASHED LINE)
MOTORIZED SHUTTER
NOT TO SCALE
MS
NTS
GENERAL
HYDRONIC VENTILATION
GENERAL NOTES
COMMON REQUIREMENTS DEMOLITION
DESIGN CONDITIONS
DUCTWORK REQUIREMENTS
UFT UNDERFLOOR FAN TERMINAL
HRV HEAT RECOVERY VENTILATOR (SENSIBLE)
EUH ELECTRIC UNIT HEATER
ESP EXTERNAL STATIC PRESSURE
ISP INTERNAL STATIC PRESSURE
TSP TOTAL STATIC PRESSURE
PUMP
PC PLUMBING CONTRACTOR
EC ELECTRICAL CONTRACTOR
GC GENERAL CONTRACTOR
FLEXIBLE PIPE CONNECTOR
FCU FAN COIL UNIT
AL ALUMINUM
VRP VERTICAL RADIANT PANEL
WAC WINDOW / WALL AIR CONDITIONER
DAC DOOR AIR CURTAIN
DH DEHUMIDIFIER
DOAS DEDICATED OUTDOOR AIR SYSTEM
DSU DUCTLESS SPLIT UNIT
DX DX COOLING COIL
ERP ELECTRIC RADIANT PANEL
GRH GAS RADIANT HEATER
L LOUVER
PDH POOL ROOM DEHUMIDIFIER
PACKAGED TERMINAL AIR CONDITIONER
RP RADIANT PANEL
S1 12x12
EQUIPMENT TYPE
EQUIPMENT MARK
SHEET #
DETAIL #
AIRFLOW IN CFM
THROAT SIZE
MECHANICAL EQUIPMENT TAG
AIR TERMINAL DESIGNATION
KEYNOTE
DETAIL OR SECTION MARK
POINT OF NEW CONNECTION
CAP EXISTING PIPE OR DUCT
BOLD TEXT INDICATES PROPOSED ITEM
ITALIC TEXT INDICATES EXISTING ITEM
NEW
PRESSURE/TEMPERATURE PLUG
AHU-1
GUARD LOCKABLE GUARD WHERE INDICATED
EQUIPMENT TO BE CONTROLLED
GUARD
TEMP
HUMID
CO ELEMENT TO BE MONITORED
LOCKABLE GUARD WHERE INDICATED
HUMIDISTAT
THERMOSTAT
SENSOR
SUPPLY DIFFUSER/REGISTER
RETURN REGISTER/GRILLE
EXHAUST REGISTER/GRILLE
DIFFUSER AIRFLOW PATTERN IF
OTHER THAN 4-WAY BLOW
FLEXIBLE BRANCH RUNOUT TO SUPPLY
DIFFUSER, 36" MAX LENGTH
CEILING RETURN REGISTER WITH LINED
DUCT FOR SOUND ATTENUATION OPEN
TO CEILING PLENUM
FLEXIBLE DUCT CONNECTION TO
EQUIPMENT OR BETWEEN DUCTS
VOLUME DAMPER
MOTORIZED DAMPER
FIRE DAMPER
SMOKE DAMPER
COMBINATION FIRE/SMOKE DAMPER
SUPPLY AIR DUCT TOWARDS
SUPPLY AIR DUCT AWAY
RETURN/OUTDOOR AIR DUCT TOWARDS
RETURN/OUTDOOR AIR DUCT AWAY
TRANSFER AIR
MECHANICAL EQUIPMENT INSTALLATION
PRESSURE SENSOR/SWITCH
EXHAUST AIR DUCT TOWARDS
EXHAUST AIR DUCT AWAY
TJ THROUGH JOISTS
CHS CHILLED WATER SUPPLY
CO2
3-WAY CONTROL VALVE
ANGLE GATE VALVE
ANGLE GLOBE VALVE
BALANCING/SHUTOFF VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
CALIBRATED BALANCING VALVE
CONTROL VALVE
EXPANSION VALVE
GATE VALVE
GLOBE VALVE
QUICK OPEN VALVE
SAFETY RELIEF VALVE
SOLENOID VALVE
VACUUM RELIEF VALVE
GAS COCK
PLUG VALVE
PRESSURE REDUCING VALVE (WATER)
PRESSURE REGULATOR (GAS)
PIPE SLOPE ARROW
WALL SWITCH
H
S
T
CFM
F
P
T
12x8Φ FLAT OVAL DUCT
12"ø ROUND DUCT
12x8 RECTANGULAR DUCT
AHU
M METER
MC MECHANICAL CONTRACTOR
SYMBOLS LEGEND
NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS
ABBREVIATIONS
LINE STYLE INDICATES DEMOLISHED ITEM
A. VERIFY EXACT SIZE AND LOCATION OF EXISTING UTILITIES PRIOR TO START OF DEMOLITION
WORK
B. RELOCATE, REMOVE, AND ADJUST ALL MECHANICAL AND ELECTRICAL ITEMS AS REQUIRED TO
ACCOMPLISH SCOPE OF NEW WORK
C. EXISTING MECHANICAL ITEMS ARE SHOWN IN SCHEMATIC FORM BASED UPON EXISTING
CONSTRUCTION DOCUMENTS AND/OR FIELD INVESTIGATION
D. REMOVE EXISTING PIPING AND DUCTWORK BACK TO LAST ACTIVE SERVICE AND CAP
E. FIXTURES AND EQUIPMENT INDICATED TO BE REUSED OR SALVAGED SHALL REMAIN THE
PROPERTY OF THE OWNER AND BE STORED IN A LOCATION AS DIRECTED BY OWNER'S
REPRESENTATIVE
F. IN LOCATIONS WHERE EXISTING CONSTRUCTION IS REMOVED AND NO ADDITIONAL
CONSTRUCTION IS INDICATED, PATCH EXISTING CONSTRUCTION TO MATCH ADJACENT SURFACES
AND FINISHES
G. CONNECTIONS TO, AND SHUTDOWNS OF, EXISTING SYSTEMS SHALL BE COORDINATED WITH
OWNER'S REPRESENTATIVE TO ALLOW MINIMUM INTERFERENCE WITH OWNER'S OPERATION AND
DOWNTIME OF EXISTING UTILITIES. CONTRACTOR SHALL SUBMIT TO OWNER FOR REVIEW AND
APPROVAL THE PROPOSED PHASING PLAN FOR CONNECTING NEW SERVICES TO EXISTING
A. THIS FACILITY HAS BEEN DESIGNATED A "SMOKE-FREE" ENVIRONMENT. NO MECHANICAL
VENTILATION PROVISIONS HAVE BEEN MADE TO ACCOMMODATE TOBACCO USAGE BY THE BUILDING
OCCUPANTS
B. ALL MECHANICAL SYSTEMS SHALL BE INSTALLED TO THE SATISFACTION OF THE LOCAL CODE
AUTHORITIES HAVING JURISDICTION
C. EVERY ATTEMPT HAS BEEN MADE TO COORDINATE THE ROUTING OF DUCTWORK WITHIN THE CLEAR
STRUCTURAL SPACE. ACTUAL LOCATION OF ALL STRUCTURAL MEMBERS HOWEVER CAN NOT BE
DETERMINED UNTIL FABRICATION DRAWINGS ARE SUBMITTED FOR REVIEW. WHERE POSSIBLE,
REFRAIN FROM PREFABRICATING DUCTWORK DESIGNATED FOR INSTALLATION UNTIL FRAMING IS IN
PLACE AND ACTUAL STRUCTURAL CONDITIONS CAN BE FIELD VERIFIED.
A. INSTALL EQUIPMENT TO ALLOW MAXIMUM POSSIBLE HEADROOM UNLESS SPECIFIC MOUNTING
HEIGHTS ARE INDICATED
B. INSTALL EQUIPMENT LEVEL AND PLUMB, PARALLEL AND PERPENDICULAR TO OTHER BUILDING
SYSTEMS AND COMPONENTS IN EXPOSED INTERIOR SPACES, UNLESS OTHERWISE INDICATED
C. INSTALL HVAC EQUIPMENT TO FACILITATE SERVICE, MAINTENANCE, AND REPAIR OR REPLACEMENT
OF COMPONENTS. CONNECT EQUIPMENT FOR EASE OF REMOVAL, WITH MINIMUM INTERFERENCE
TO OTHER INSTALLATIONS
D. ALL MECHANICAL EQUIPMENT WITH THE EXCEPTION OF AIR HANDLING UNITS, SUPPORTED FROM
FLOOR STRUCTURE SHALL BE MOUNTED ON 4" THICK CONCRETE HOUSEKEEPING PADS UNLESS
NOTED OTHERWISE. AIR-HANDLING UNITS SHALL BE MOUNTED ON 6" THICK CONCRETE
HOUSEKEEPING PADS TO ACCOMMODATE PROPER TRAPPING OF THE CONDENSATE DRAIN
E. AIR FILTERS SHALL BE REPLACED IN ALL AIR HANDLING EQUIPMENT EMPLOYING SUCH PRIOR TO
FINAL COMPLETION AND OWNER OCCUPANCY
F. THE INSTALLING CONTRACTOR ASSUMES FULL RESPONSIBILITY FOR ALL MECHANICAL EQUIPMENT PUT INTO OPERATION PRIOR TO THE INSTALLATION OF A WORKING CONTROL SYSTEM, TESTING, AND BALANCING, AND SUBSTANTIAL COMPLETION. ALL RETURN AND EXHAUST DUCT OPENINGS
SHALL BE COVERED WITH ROLL TYPE FILTER MEDIA DURING SUCH TEMPORARY OPERATION.
OPERATION OF THE MECHANICAL EQUIPMENT PRIOR TO FINAL COMPLETION SHALL NOT IMPACT THE
EQUIPMENT WARRANTY. MINIMUM 1-YEAR FROM SUBSTANTIAL COMPLETION UNLESS SPECIFIED
OTHERWISE
G. PROVIDE FLEXIBLE DUCT CONNECTION BETWEEN MOTOR DRIVEN MECHANICAL UNITS AND SHEET
METAL SUPPLY, OUTDOOR AIR, EXHAUST, AND/OR RETURN AIR DUCTWORK CONNECTIONS
H. PROVIDE FLEXIBLE PIPE CONNECTION BETWEEN MOTOR DRIVEN MECHANICAL UNITS AND
CONNECTING PIPING
I. BASIS OF DESIGN MECHANICAL EQUIPMENT IS AS SCHEDULED ON THE DRAWINGS. INSTALLING CONTRACTOR ASSUMES RESPONSIBILITY FOR COORDINATING PHYSICAL SPACE REQUIREMENTS OF
EQUIVALENT CAPACITY MECHANICAL EQUIPMENT DEEMED ACCEPTABLE BY THE ENGINEER
J. MECHANICAL EQUIPMENT FACTORY FINISH DAMAGED DURING THE COURSE OF CONSTRUCTION
SHALL BE RESTORED TO ORIGINAL CONDITION PRIOR TO FINAL ACCEPTANCE
A. DUCTWORK IS SHOWN IN SCHEMATIC FORM. ALL REQUIRED DUCT RISERS AND DROPS TO ALLOW GENERAL ROUTING DEPICTED MAY NOT BE SHOWN. PROVIDE OFFSETS AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO AVOID INTERFERENCE WITH OTHER TRADES AND FIELD CONDITIONS. EXACT LOCATION OF THE DUCTWORK MAY VARY ACCORDING TO THE COORDINATED SPACE REQUIREMENTS.
EACH TRADE SHALL BE TOTALLY RESPONSIBLE FOR COORDINATION WITH OTHER TRADES. NOTIFY
ENGINEER OF CONDITIONS REPRESENTING SIGNIFICANT CHANGES TO THE DESIGNED ROUTING
B. COMPLY WITH NFPA 90A, "INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS," UNLESS
OTHERWISE INDICATED
C. COMPLY WITH NFPA 90B, "INSTALLATION OF WARM AIR HEATING AND AIR CONDITIONING SYSTEMS,"
UNLESS OTHERWISE INDICATED
D. FABRICATE RECTANGULAR DUCTS, ELBOWS, TRANSITIONS, OFFSETS, BRANCH CONNECTIONS, AND OTHER CONSTRUCTION WITH GALVANIZED, SHEET STEEL, ACCORDING TO SMACNA'S "HVAC DUCT
CONSTRUCTION STANDARDS--METAL AND FLEXIBLE." COMPLY WITH REQUIREMENTS FOR METAL
THICKNESS, REINFORCING TYPES AND INTERVALS, TIE-ROD APPLICATIONS, AND JOINT TYPES AND
INTERVALS
E. COORDINATE SIZE, QUANTITY, AND LOCATION OF ALL OPENINGS REQUIRED FOR DUCT AND PIPE
PENETRATIONS THROUGH WALLS, FLOORS, AND ROOFS, WITH CONTRACTOR RESPONSIBLE FOR
ROUGH FRAMING. COORDINATE LOCATION OF AIR INTAKES WITH EXHAUST AND PLUMBING VENTS SO
THAT INTAKES ARE A MINIMUM OF 10 FEET FROM EXHAUST OPENINGS OR PLUMBING VENTS
F. INSTALL DUCTS IN LONGEST LENGTH POSSIBLE AND FEWEST POSSIBLE JOINTS. INSTALL FABRICATED
FITTINGS FOR CHANGES IN DIRECTIONS, CHANGES IN SIZE AND SHAPE, AND CONNECTIONS
G. INSTALL DUCTS, UNLESS OTHERWISE INDICATED, VERTICALLY AND HORIZONTALLY, PARALLEL AND PERPENDICULAR TO BUILDING LINES; AVOID DIAGONAL RUNS UNLESS SPECIFICALLY INDICATED ON
DRAWINGS
H. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF CEILING MOUNTED DEVICES. COORDINATE MECHANICAL CEILING DEVICES SUCH AS DIFFUSERS AND REGISTERS WITH
LIGHT FIXTURES, SPEAKERS, SPRINKLER HEADS, ETC.
I. ELECTRICAL EQUIPMENT SPACES: ROUTE DUCTWORK TO AVOID PASSING THROUGH TRANSFORMER
VAULTS AND ELECTRICAL EQUIPMENT SPACES AND ENCLOSURES. AVOID ROUTING DUCTWORK
DIRECTLY ABOVE ELECTRICAL EQUIPMENT UNLESS SPECIFICALLY INDICATED ON THE MECHANICAL
DRAWINGS
J. NON-FIRE-RATED PARTITION PENETRATIONS: WHERE DUCTS PASS THROUGH INTERIOR PARTITIONS
AND ARE EXPOSED TO VIEW IN MECHANICAL ROOMS, CONCEAL SPACE BETWEEN CONSTRUCTION
OPENING AND DUCT OR DUCT INSULATION WITH SHEET METAL FLANGES OF SAME METAL THICKNESS
AS DUCT. OVERLAP OPENING ON FOUR SIDES BY AT LEAST 1-1/2 INCHES UNLESS INDICATED
OTHERWISE
K. FIRE-RATED PARTITION PENETRATIONS: WHERE DUCTS PASS THROUGH INTERIOR PARTITIONS, INSTALL APPROPRIATELY RATED FIRE DAMPER. FIRE DAMPER INSTALLATION MUST STRICTLY ADHERE
TO MANUFACTURER'S WRITTEN INSTRUCTIONS
L. PROVIDE MANUAL VOLUME-CONTROL BALANCING DAMPER AT ALL BRANCH DUCTS AND AT ALL OTHER
LOCATIONS REQUIRED FOR A COMPLETE AND BALANCEABLE AIR DISTRIBUTION SYSTEM
M. BALANCE ENTIRE AIR DISTRIBUTION SYSTEM TO AIRFLOW QUANTITIES INDICATED ON MECHANICAL
DRAWINGS
N. FLEXIBLE DUCTWORK SHALL BE ALLOWED ONLY IN POSITIVE PRESSURE APPLICATIONS AT SUPPLY BRANCH RUNOUTS TO DIFFUSERS ABOVE ACCESSIBLE CEILINGS. FLEXIBLE DUCTWORK SHALL NOT EXCEED 36" IN LENGTH. 90 DEGREE TURNS SHALL ONLY BE ALLOWED IF RETAINING BANDS EQUAL TO THERMAFLEX "FLEX-FLOW" ARE EMPLOYED. UNDER NO CIRCUMSTANCES SHALL FLEXIBLE DUCTWORK
BE ALLOWED IN NEGATIVE PRESSURE APPLICATIONS
HVAC DESIGN LOAD CALCULATIONS ARE BASED ON THE FOLLOWING CLIMATE DATA:
CITY AND STATE: BLOOMINGTON, IL
WINTER OUTDOOR AMBIENT DB: -3 SUMMER OUTDOOR AMBIENT DB/WB: 91.8/75.6
MECHANICAL SYSTEMS HAVE BEEN DESIGNED BASED UPON THE 2018 INTERNATIONAL MECHANICAL CODE, 2021 INTERNATIONAL ENERGY CONSERVATION CODE, NATIONAL FIRE PROTECTION (NFPA)
STANDARDS, AND AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND AIR-CONDITIONING
ENGINEERS (ASHRAE) ACCEPTED STANDARDS AND PRACTICES
http://www.f-w.com
ADG
02A
030A
020D020C
020A
A
D
M1.34
M2.1PHOTO
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
LOWER LEVEL 1
PLAN
M1.1
TMG
TMG
DRR
PROJECT:
DATE:
PROJECT NO.:
City Of Bloomington
Bloomington Police Garage Door And Ventilation Upgrades
305 S. East Street Bloomington, Illinois
03/17/2026
02501052.001
DESCRIPTION:DATE:#
ISSUE:
BID SET
03/17/2026
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
200 WEST COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
ROOM INDEX
A STAIR
B STAIR
D STAIR
01 PARKING
02 LOBBY
02A GRAPHICS AND FORENSICS
03 SECURE FORMS STORAGE
04 QUARTERMASTER STORAGE
05 PATROL SUPPLIES / STORAGE
06 EVIDENCE DROP
07 VESTIBULE
08 REPORT WRITING
09 UNASSIGNED
010 JANITOR SUPPLIES
011 FEMALE LOCKERS
011A TOILET / SHOWER
012 EVALUATION
013 VENDING
014 BRIEFING
015 PHYSICAL TRAINING
016 LONG TERM EVIDENCE STORAGE
017 VESTIBULE
018 MALE LOCKERS
019 UNASSIGNED
020 LABORATORY
020A STORAGE
020B OFFICE
020C BLOOD DRYING ROOM
020D BLOOD DRYING ROOM
021 VESTIBULE
022 HALL
023 JANITOR CLOSET
024 TOILET / SHOWER
025 S.W.A.T.
025A ARMORY
026 INTERVIEW
027 INTERVIEW
028 TOILET
029 VESTIBULE
030 VEHICLE SALLYPORT
030A DECONTAMINATION
031 CORRIDOR
032 CORRIDOR
033 CORRIDOR
034 CORRIDOR
0 4 8 16
1 SCALE:
LOWER LEVEL 1 PLAN
1/8"=1'-0" NORTH
109A
107A
125A
138A
138137
A
D
EF
M2.1
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
FIRST FLOOR PLAN
M1.2
TMG
TMG
DRR
PROJECT:
DATE:
PROJECT NO.:
City Of Bloomington
Bloomington Police Garage Door And Ventilation Upgrades
305 S. East Street Bloomington, Illinois
03/17/2026
02501052.001
DESCRIPTION:DATE:#
ISSUE:
BID SET
03/17/2026
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
200 WEST COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
0 4 8 16
1 SCALE:
FIRST FLOOR PLAN
1/8"=1'-0" NORTH
ROOM INDEX
A STAIR
B STAIR
C STAIR
D STAIR
100 VESTIBULE
101 PUBLIC LOBBY
102 MEDIA
103 FINGERPRINTING
104 PUBLIC WAITING
105 CLOSET
106 SECRETARY / RECEPTION
107 WORKROOM
107A STORAGE
108 COFFEE BAR
109 CHIEF
109A CLOSET
110 CONFERENCE
111 ASSISTANT CHIEF
112 OPERATIONS CAPTAIN
113 DISPATCH CENTER
114 COFFEE BAR
115 ADMINISTRATION TOILET
116 STORAGE
117 PATROL LIEUTENANT
118 FIELD TRAINING
119 DISPATCH SUPERVISOR
120 PATROL LIEUTENANT
121 PATROL LIEUTENANT
122 PATROL LIEUTENANT
123 CONFERENCE
124 STORAGE
125 STAFF
125A PUBLIC RECEPTION
125B DESK SERGEANT
126 RECORDS
127 EVIDENCE STORAGE
127A EVIDENCE PROCESSING
127B VAULT
128 PATROL SERGEANT
129 VENDING LOUNGE
130 VENDING
131 JANITOR
132 WOMEN
133 MEN
134 COMPUTER EQUIPMENT
135 DATA ENTRY
136 STORAGE
137 CRIME PREVENTION
138 D.A.R.E. OFFICERS
138A WORK ROOM
139 OFFICE
140 MEN
141 WOMEN
142 INTERVIEW
143 CORRIDOR
144 CORRIDOR
145 CORRIDOR
146 CORRIDOR
147 CORRIDOR
0302030
029A
M1.3
3'-0"
34x30
24x30 INTAKE LOUVER WITH NORMALLY
OPEN MOTORIZED DAMPER, 750 CFM
EMERGENCY PUSHBUTTON CLOSES
MOTORIZED DAMPERS
IN SUPPLY DUCT AND INTAKE LOUVER AND
CUTS POWER TO MAU-1. REFER TO
ELECTRICAL DRAWINGS
EXISTING 3" ELECTRICAL CONDUITS
FROM BELOW GRADE PROTECTED BY
EXISTING BOLLARDS
CENTERLINE OF TEE ABOVE
48x22 OVAL FABRIC DISPERSION DUCTWORK BETWEEN TEE LEGS
SE
R
VI
C
E C
LE
AR
AN
C
E
MAU
34x30 ELBOW WITH
TURNING VANES
LOWER LEVEL 1
FIRST FLOOR
PAVED SURFACE
MAU
9' -8
8"
FI
EL
D V
ER
IF
Y
56'-0"
NOMINAL LENGTH, FIELD VERIFY
x3
30x34 ELBOW WITH
TURNING VANES
SUPPORT
DUCTWORK FROM
FLOOR SLAB
48x22 OVAL FABRIC DISPERSION DUCTWORK BETWEEN TEE LEGS
EXISTING CONDUITS AND
SPRINKLER PIPING
FABRIC DUCTWORK TO BE PROVIDED WITH INTERNAL FRAMEWORK
TENSIONING SYSTEM AND SUPPORTED BY CABLE FROM DECK
STRUCTURE. FABRIC COLOR TO BE GRAY. MANUFACTURER IS
RESPONSIBLE FOR THE DESIGN OF PERFORATIONS OR NOZZLES
REQUIRED TO DELIVER 11,020 CFM (APPROXIMATELY 197 CFM PER FOOT
OF LENGTH). BASIS OF DESIGN MANUFACTURER: DUCTSOX
5 MOTORIZED
DAMPER
2' -2
- REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
ENLARGED LOWER
LEVEL 1 PLAN AND
SECTION
M1.3
TMG
TMG
DRR
PROJECT:
DATE:
PROJECT NO.:
City Of Bloomington
Bloomington Police Garage Door And Ventilation Upgrades
305 S. East Street Bloomington, Illinois
03/17/2026
02501052.001
DESCRIPTION:DATE:#
ISSUE:
BID SET
03/17/2026
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
200 WEST COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
ROOM INDEX
KEY NOTES
A STAIR
B STAIR
D STAIR
01 PARKING
02 LOBBY
02A GRAPHICS AND FORENSICS
03 SECURE FORMS STORAGE
04 QUARTERMASTER STORAGE
05 PATROL SUPPLIES / STORAGE
06 EVIDENCE DROP
07 VESTIBULE
08 REPORT WRITING
09 UNASSIGNED
010 JANITOR SUPPLIES
011 FEMALE LOCKERS
011A TOILET / SHOWER
012 EVALUATION
013 VENDING
014 BRIEFING
015 PHYSICAL TRAINING
016 LONG TERM EVIDENCE STORAGE
017 VESTIBULE
018 MALE LOCKERS
019 UNASSIGNED
020 LABORATORY
020A STORAGE
020B OFFICE
020C BLOOD DRYING ROOM
020D BLOOD DRYING ROOM
021 VESTIBULE
022 HALL
023 JANITOR CLOSET
024 TOILET / SHOWER
025 S.W.A.T.
025A ARMORY
026 INTERVIEW
027 INTERVIEW
028 TOILET
029 VESTIBULE
030 VEHICLE SALLYPORT
030A DECONTAMINATION
031 CORRIDOR
032 CORRIDOR
033 CORRIDOR
034 CORRIDOR
1. 6"Ø STEEL BOLLARD FILLED WITH
CONCRETE. TOP OF BOLLARD
APPROXIMATELY 48" ABOVE PAVED
SURFACE
2. EXISTING 6"Ø STEEL BOLLARDS
3. CONCRETE EQUIPMENT PAD EXTENDING
6" BEYOND MAKEUP AIR UNIT IN ALL
DIRECTIONS. FIELD DETERMINE PAD
HEIGHT IN FIELD
4. DUCT SUPPORTS FABRICATED FROM
GALVANIZED STEEL SHAPES
5. PREFABRICATED MAXIMUM SECURITY
BAR GRILLE. VERTICAL AND
HORIZONTAL 1/2" STEEL BARS WELDED
TO TO MINIMUM 3/16" THICK STEEL
SLEEVE. SECURE SLEEVE TO CONCRETE
WALL WITH FASTENERS LOCATED ON
THE "SECURE SIDE" OF OPENING
6. INSTALL LOUVER AT NEW OPENING IN
EXISTING CONCRETE EXTERIOR WALL.
REFER TO ARCHITECTURAL DRAWINGS.
LOUVER EQUIVALENT TO RUSKIN MODEL
EME720, 56% FREE AREA, 0.25"
PRESSURE DROP, SANDSTONE COLOR.
750 CFM
7. INTERLOCK OPERATION OF MAKEUP AIR
UNIT WITH EXISTING CARBON MONOXIDE
SENSORS AS FOLLOWS: UPON CARBON
MONOXIDE CONCENTRATION
EXCEEDING SETPOINT (25 PPM) , THE
MAU-1 DISCHARGE MOTORIZED DAMPER
WITHIN THE GARAGE AND INTAKE
MOTORIZED DAMPER AT THE UNIT MOVE
TO THE FULLY OPEN POSITION. MAU-1
SUPPLY FAN IS ENERGIZED WHEN BOTH
DAMPERS PROVE OPEN AND EXISTING
EXHAUST FAN EF-8 IS ENERGIZED. THE
SYSTEM REMAINS OPERATING FOR A
PERIOD OF 10 MINUTES (ADJUSTABLE)
AFTER CARBON MONOXIDE
CONCENTRATION FALLS BELOW 15 PPM
(ADJUSTABLE)
8. "INSULATE" EXTERIOR DUCTWORK FOR
THE PURPOSE OF IMPACT RESISTANCE
AND PROTECTION OF SHEET METAL
COMPONENTS PER SPECIFICATIONS
9. 18x18 ACCESS DOOR. REFER TO
SPECIFICATIONS
0 4 8 16
1 SCALE:
ENLARGED LOWER LEVEL 1 PLAN
1/4"=1'-0" NORTH
0 4 8 16
2 SCALE:
SECTION THROUGH LOWER LEVEL 1 PARKING GARAGE
1/4"=1'-0" NORTH
LOWER LEVEL 2
LOWER LEVEL 1
FIRST FLOOR
EF
REMOVE EXISTING
EXHAUST FAN EF-7
FIELD VERIFY EXACT DIMENSION
FOR NEW ADAPTER CURB
2'-8 12"3"
FIELD VERIFY
EXHAUST INLET
LOUVER
EXHAUST INLET
LOUVER
REVISE CONTROLS SUCH THAT EXHAUST FAN
OPERATES CONTINUOUSLY AS IN NOT ACTIVATED
BY EXISTING CARBON MONOXIDE SENSORS
2' -6
1'-0"
STEEL
SECURITY
BARS
SHEET METAL CLOSURE ANGLE
ALL SIDE OF DUCT AND BOTH
SIDES OF WALL
SILICONE SEALANT TYPICAL
FILL VOID WITH EXPANDING FOAM
AND TRIM NEATLY AT OPENING
TREATED WOOD BLOCKING OR
STEEL BLOCKING AS REQUIRED
MINIMUM 1/2"Øx5" HEX HEAD
"TAPCON" LAG SCREWS OR
EQUIVALENT
JACKETING TAPE ABOUT PERIMETER
FOAM "INSULATION" PER
SPECIFICATIONS
"INSULATION" JACKETING
PER SPECIFICATIONS
FILL VOID WITH EXPANDING FOAM
REVIEWED:
DESIGNED:
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
MECHANICAL
DETAILS AND
SCHEDULES
M2.1
TMG
TMG
DRR
PROJECT:
DATE:
PROJECT NO.:
City Of Bloomington
Bloomington Police Garage Door And Ventilation Upgrades
305 S. East Street Bloomington, Illinois
03/17/2026
02501052.001
DESCRIPTION:DATE:#
ISSUE:
BID SET
03/17/2026
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
200 WEST COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
0 1 2 4
1 SCALE:
SECTION THROUGH NORTHEAST EXHAUST SHAFT
1/2"=1'-0"
FAN SCHEDULE
MARK MANUFACTURER MODEL TYPE DRIVE SERVICE CFM ESP
(IN. W.C.)
FAN
MOTOR
BHP
SONES DAMPER
ROOF
OPENING ELECTRICAL DATA PHYSICAL DATA
REMARKS
L
(IN.)
W
(IN.)
HP/
WATTS V/PH FLA MCA MOP L
(IN.)
W
(IN.)
H
(IN.)
WT
(LB.)
EF7 GREENHECK CUE-099-VG UPBLAST DIRECT GARAGE VENTILATION 750 0.5 0.14 8.1 15.5 15.5 0.25 208/1 2.1 2.6 15 25 25 38 53
NOTES:
MAKEUP AIR UNIT SCHEDULE
MARK MANUFACTURER MODEL LOCATION SERVICE
FAN FILTER ELECTRICAL DATA PHYSICAL DATA
REMARKS
CFM ESP
(IN. W.C.)
BHP HP MERV THICK.
(IN.)
V/PH FLA MCA MOCP L
(IN.)
W
(IN.)
H
(IN.)
WT.
(LB.)
MAU1 GREENHECK MSX-P125-H32-D3 WEST LOT VEHICLE EXHAUST SYSTEM 11020 1.5 7.21 10 8 2 208/3 39 60 110 52 49 1270
NOTES: PROVIDE UNIT WITH LOUVERED INTAKE, MOTORIZED INLET DAMPER, AND DIRECT DRIVE FAN
4 SCALE:
PROPOSED LOCATION OF MAKEUP AIR UNIT
NONE
A
D
C B
E
A. 3" ELECTRICAL CONDUITS FROM BELOW
GRADE AND THROUGH WALL INTO
GARAGE
B. STEEL BOLLARD FILLED WITH CONCRETE
C. LOCATION OF NEW 34x30 DUCT
PENETRATION THROUGH WALL
D. LOCATION OF NEW 24x30 WALL
PENETRATION TO ACCOMMODATE
LOUVER
E. MATERIAL STORAGE AND RACKING TO BE
RELOCATED BY THE CITY OF
BLOOMINGTON
IN WIDTH AND/OR DEPTH
SMALL DOUBLE VANE ELBOW
USE FOR ELBOWS UP TO 36"
4.
3.
1.
2.
1"R
NOTES:
ALL SQUARE OR RECTANGULAR ELBOWS FOR POSITIVE PRESSURE
DUCTS (SUPPLY) SHALL HAVE ONE OF THE TWO TYPES OF TURNING
VANES SHOWN ABOVE. SINGLE VANE ELBOWS WILL NOT BE PERMITTED.
VANES SHALL BE CONSTRUCTED, SUPPORTED AND FASTENED AS
RECOMMENDED BY SMACNA.
TURNING VANES NOT ALLOWED IN NEGATIVE PRESSURE DUCTS
(RETURN OR EXHAUST).
ALL ELBOWS SHALL BE RADIUS UNLESS SPACE LIMITATIONS REQUIRE
SQUARE OR RECTANGULAR ELBOWS AND/OR THERE IS AN OUTLET OR
TAKE-OFF WITHIN 5D ON THE DOWNSTREAM SIDE OF THE ELBOW.
LARGE DOUBLE VANE ELBOW
USE FOR ELBOWS 36" OR
WIDER AND ANY DEPTH
2 1/4"2 1/4"
3 1/ 4"
2 1/4" R
4 1/2" R
45° 45°
SIDE VIEW
TYPICAL ELBOW
FRONT VIEW
DEPTH (D)
WIDTH (W)
1/
8" 1 1/8"
1 1/8"
45°
45° 2"R
3 SCALE:
TURNING VANE DETAIL
NONE 2 SCALE:
DUCT WALL PENETRATION
3/4"=1'-0"
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
GENERAL
INFORMATION
E0.1
TLA
KMT
WRK
PROJECT:
DATE:
PROJECT NO.:
City Of Bloomington
Bloomington Police Garage Door And Ventilation Upgrades
305 S. East Street Bloomington, Illinois
03/17/2026
02501052.001
DESCRIPTION:DATE:#
ISSUE:
BID SET
03/17/2026
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
200 WEST COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
CONDUIT - CAPPED
CABLE TRAY
SEALING FITTING
EXPANSION FITTING
CONDUIT FITTING (CONDULET)
JUNCTION BOX
CONDUIT - FLEXIBLE
SPECIAL PURPOSE RECEPTACLE - FLOOR MOUNTED
SPECIAL PURPOSE RECEPTACLE - CEILING MOUNTED
SPECIAL PURPOSE RECEPTACLE - MOUNTED 18" AFF
CEILING FAN
QUADRUPLEX RECEPTACLE - FLOOR MOUNTED
DUPLEX RECEPTACLE - FLUSH FLOOR MOUNTED
SINGLE RECEPTACLE - MOUNTED 18" AFF
QUADRUPLEX RECEPTACLE - MOUNTED 18" AFF
LIGHTING CONTROLLER
POLE MOUNTED SITE LIGHTING - QUAD HEAD
TOGGLE SWITCH - MOUNTED 48" AFF
a
PHOTOCELL
CONDUIT - CONTINUED
CONDUIT - TURNING UP
CONDUIT - EXPOSED
CONDUIT - TURNING DOWN
REVISION CALL-OUT
ROOM NUMBER
FEEDER CALL-OUT
KEYED NOTE
GENERAL SYMBOLS
UTILITY KILOWATT-HOUR METER
DUPLEX RECEPTACLE - EMERGENCY POWER - MOUNTED 18" AFF
DUPLEX RECEPTACLE - CEILING MOUNTED
DUPLEX RECEPTACLE - SPLIT WIRED - MOUNTED 18" AFF
DUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER
DUPLEX RECEPTACLE (NEMA 5-20R) - MOUNTED 18" AFF
MAGNETIC STARTER
COMBINATION STARTER
SAFETY SWITCH - FUSIBLE
SAFETY SWITCH - NON-FUSIBLE
EQUIPMENT - MOTOR
POLE MOUNTED SITE LIGHTING - TRIPLE HEAD
POLE MOUNTED SITE LIGHTING - DUAL HEAD
POLE MOUNTED SITE LIGHTING - SINGLE HEAD
EXIT SIGN - DUAL FACE, WALL MOUNTED
EXIT SIGN - DUAL FACE, CEILING MOUNTED
EXIT SIGN - SINGLE FACE, WALL MOUNTED
BRANCH CIRCUIT PANELBOARD - FLUSH MOUNTED
DISTRIBUTION PANELBOARD OR SWITCHBOARD
MOTOR CONTROL CENTER
BRANCH CIRCUIT PANELBOARD - SURFACE MOUNTED
T
CONTROL PANEL
TRANSFORMER
POWER SYMBOLS
LUMINAIRE - SURFACE MOUNTED
OPEN INDUSTRIAL LUMINAIRE
RECESSED DOWNLIGHT - CEILING MOUNTED
LIGHTING SYMBOLS
RECESSED LUMINAIRE CONNECTED TO THE
EMERGENCY POWER SYSTEM OR BALLAST/DRIVER
JUNCTION BOX - EMERGENCY POWER
FOOD SERVICE EQUIPMENT DESIGNATION
HAND DRYER
WIRING AND CONDUITS
NEW EQUIPMENT (TYPICAL)
EXISTING EQUIPMENT (TYPICAL)
DEMOLITION EQUIPMENT (TYPICAL)
PUSH BUTTON
WALL MOUNT BRACKET (TYPICAL)
LUMINAIRE TYPE
PANEL NAME
LUMINAIRE - RECESSED (REFER TO LUMINAIRE SCHEDULE)
CONNECTED FOR NIGHT LIGHT USE
1LP-1a NL
CIRCUIT NUMBER AND SWITCH LEG (LUMINAIRES
ARE CONTROLLED BY LOCAL SWITCH UNLESS
DESIGNATION GIVEN)
A a
WALL MOUNTED LUMINAIRE
CEILING MOUNTED DAYLIGHT SENSOR
a
AHU
J
J
B
M
F
H
PC
DL
VFD
GWH1
MECHANICAL EQUIPMENT CALL-OUT: REFER TO
THE EQUIPMENT DATA SCHEDULE FOR DETAILS
PLUMBING EQUIPMENT CALL-OUT: REFER TO THE
EQUIPMENT DATA SCHEDULE FOR DETAILS
###A#G
CONDUIT - UP AND DOWN
(CHANGE IN ELEVATION)
CONDUIT - CONCEALED BELOW
SLAB OR GRADE
CONDUIT - CONCEALED IN
SUSPENDED CEILING OR WALL
T POLE MOUNTED TRANSFORMER
GROUND BAR
AC
QUADRUPLEX RECEPTACLE - MOUNTED 6" ABOVE COUNTER
AC
J FLOOR BOX - SEE SPECS OR KEYED NOTES ON PLAN
FOR DETAILS
PP
POWER POLE
OPEN INDUSTRIAL LUMINAIRE EMERGENCY
POWER SYSTEM OR BALLAST/DRIVER
SURFACE MOUNTED DOWNLIGHT
RECESSED ADJUSTABLE/WALLWASH - CEILING MOUNTED
LINEAR PENDANT
PENDANT
TRACK LIGHTING
EXIT SIGN WITH EMERGENCY LIGHT
ARROW INDICATES DIRECTION OF EXIT
EXIT SIGN - SINGLE FACE, CEILING MOUNTED
ARROW INDICATES DIRECTION OF EXIT
EMERGENCY LIGHT
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOROS
CEILING MOUNTED DUAL TECHNOLOGY VACANCY SENSOR
a
VS
LC1
LRP
INV
LIGHTING RELAY PANEL
INVERTER
b LOWER CASE LETTER DENOTES LTG. SWITCH GROUP
2 DOUBLE-POLE SINGLE-THROW (DPST)
3 3-WAY
4 4-WAY
B PUSHBUTTON
D DIMMER (WALL BOX TYPE)
K KEY OPERATED
M MANUAL MOTOR STARTER
P PILOT LIGHT T TIMER
TT THERMAL TRIP SWITCH
WP WEATHER PROOF
OS WALL BOX OCCUPANCY SENSOR
OS2 WALL BOX OCCUPANCY SENSOR FOR TWO LEVEL
SWITCHING
VS WALL BOX VACANCY SENSOR
LV LOW VOLTAGE SWITCH
TC TEACHER ENTRY STATION
TE TEACHER ENTRY STATION
MC MOMENTARY CONTACT
GFI GROUND FAULT CIRCUIT INTERRUPTER
SS SURGE SUPPRESSOR (ISOLATED GROUND TYPE)
WP WEATHERPROOF
H HOSTPITAL GRADE
TP TAMPER PROOF
D DEDICATED
USB STANDARD DUPLEX WITH 2 USB PORTS
VFD VARIABLE FREQUENCY DRIVE
a LOWER CASE LETTER DENOTES LTG. SWITCH GROUP a LOWER CASE LETTER DENOTES LTG. SWITCH GROUP a LOWER CASE LETTER DENOTES LTG. SWITCH GROUP
QUADRUPLEX RECEPTACLE - CEILING MOUNTED
SYMBOLS LEGEND
NOTE: NOT ALL SYMBOLS ARE USED IN CONSTRUCTION DOCUMENTS.
FIRE ALARM SYMBOLS
SPECIAL SYSTEMS SYMBOLS
CONTROL DEVICE - DOOR HOLD OPEN
ADDRESSABLE INTERFACE MODULE
SUPERVISORY SWITCH - DRY-PIPE PRESSURE SWITCH
MANUAL PULL STATION - MOUNTED 46" AFF
MAIN CONTROL PANEL (FACP)
SHUNT TRIP PUSH BUTTON - MOUNTED 46" AFF
NOTIFICATION APPLIANCE (CEILING)
THERMAL (HEAT) DETECTOR
SMOKE DETECTOR
DUCT DETECTOR HOUSING AND SAMPLING TUBE
P
R
CARBON MONOXIDE DETECTOR - WALL MOUNTED AT 18" AFF
CEILING MOUNTED COMBINATION VOICE EVACUATION
SPEAKER AND STROBE
FCP
F
S
F C
F
CO
D
H
DP
SUPERVISORY SWITCH - TAMPER SWITCHTS
SUPERVISORY SWITCH - WATER FLOW SWITCHWF
NOTIFICATION APPLIANCE MOUNTED 80" AFF OR 6" FROM
CEILING WHICHEVER IS LOWER
NOTIFICATION APPLIANCE - STROBE ONLY
MOUNTED 80" AFF
C
C
C
RTS REMOTE TEST SWITCH
COMBINATION VOICE EVACUATION SPEAKER AND STROBE
MOUNTED 80" AFF
ACCP ACCESS CONTROL CONTROL PANEL
DVR DVR AND RACK
CARD READER - MOUNTED 48" AFF WITH 3/4" CONDUITCR
ES ELECTRIC STRIKE WITH 3/4" CONDUIT
ML ELECTRO-MAGNETIC LOCK WITH 3/4" CONDUIT
VM VIDEO MONITOR, FLAT SCREEN LCD WITH 3/4" CONDUIT
DC DOOR STATUS SWITCH WITH 3/4" CONDUIT
MS MOTION DETECTOR WITH 3/4" CONDUIT
PS POWER SUPPLY FOR PTZ CAMERA WITH 3/4" CONDUIT
PS4 4-CHANNEL CAMERA POWER SUPPLY WITH 3/4" CONDUIT
INDOOR FIXED CAMERA WITH 3/4" CONDUIT
TV TV OUTLET WITH 3/4" CONDUIT - MOUNTED 18" AFF
HANDICAP DOOR OPERATORS - SEE ARCHITECTURALS WITH 3/4" CONDUIT
GB GLASS BREAK SENSOR WITH 3/4" CONDUIT
V VOLUME CONTROLLER - MOUNTED 48" AFF WITH 3/4" CONDUIT
S CEILING MOUNTED SPEAKER
WALL MOUNTED SPEAKER
IMS INTERCOM MASTER STATION
I INTERCOM REMOTE STATION
DOOR BELL PUSH BUTTON
DB DOOR BELL
NOTIFICATION APPLIANCE WITH STROBE MOUNTED
80" AFF OR 6" FROM CEILING WHICHEVER IS LOWER
P PEDESTAL MOUNT
S HIGH SECURITY
G GENERAL USE
PTZ PAN TILT ZOOM
WP WEATHERPROOF
K WITH KEY PAD
CANDELA VALUE AS SHOWN MINIMUM
C CHIME
H HORN
LF LOW FREQUENCY
CANDELA VALUE AS SHOWN MINIMUM
CANDELA VALUE AS SHOWN MINIMUM
CANDELA VALUE AS SHOWN MINIMUM
C CHIME
H HORN
LF LOW FREQUENCY
CANDELA VALUE AS SHOWN MINIMUM
C CHIME
H HORN
LF LOW FREQUENCY
C CONTROL
M MONITORING
S SIGNALING
V SOLENOID VALVE
R RATE OF RISE ONLY
F FIXED TEMPERATURE
L LINE TYPE FIXED TEMPERATURE CABLE
ALL HEAT DETECTORS SHALL BE 135°, COMBINATION TYPE
UNLESS INDICATED OTHERWISE.
P PHOTOELECTRIC
PL PLENUM SMOKE DETECTOR
S SOUNDER BASE
LF LOW FREQUENCY TONE PER NFPA72 18.4.5.3
FCP F/A MAIN CONTROL PANEL
FSA FIRE SYSTEM ANNUNCIATOR
FTR F/A TRANSPONDER OR TRANSMITTER
ESR ELEVATOR STATUS RECALL
FRP F/A RELAY PANEL
FAC F/A COMMUNICATOR
FPS FIRE ALARM ANNUNCIATION CIRCUIT POWER SUPPLY
S
S
S 75
CEILING MOUNTED VOICE EVACUATION SPEAKER
VOICE EVACUATION SPEAKER MOUNTED 80" AFFS
S
DRAWN:
SHEET TITLE:
SHEET NUMBER:
FIELD BOOK NO.:
GENERAL
INFORMATION AND
SCHEDULES
E0.2
TLA
KMT
WRK
PROJECT:
DATE:
PROJECT NO.:
City Of Bloomington
Bloomington Police Garage Door And Ventilation Upgrades
305 S. East Street Bloomington, Illinois
03/17/2026
02501052.001
DESCRIPTION:DATE:#
ISSUE:
BID SET
03/17/2026
GROUP
www.f-w.com Engineers | Architects | Surveyors | Scientists
200 WEST COLLEGE AVENUE, SUITE 301
NORMAL, ILLINOIS 61761
(309) 663-8436 / info@f-w.com
(E) EXISTING (ALSO COVERED BY TEXT
WEIGHT)
(F) FUTURE
(PART) PARTIAL CIRCUIT
(R) RELOCATE
2S1W TWO SPEED, SINGLE WINDING
2S2W TWO SPEED, DOUBLE WINDING
A AMPERES
AC 6" ABOVE…