Bid_#2026-36_-_Drawing-Plans_-_Bloomington_Fire_Station_#4_Kitchen_Remodel.pdf
PDF 11 MB Posted
- Attached to
- Bloomington Fire Station #4 Kitchen Remodel
- Solicitation number
- Bid #2026-36
- Issued by
- Mclean County, Illinois
About this file
This document comprises the construction drawing package for Bid #2026-36, the Bloomington Fire Station #4 Kitchen Remodel project in Bloomington, Illinois, involving the City of Bloomington and architectural/engineering firm Dewberry Architects Inc. The project scope includes renovation of an existing kitchen at 1705 S Morris Avenue, consisting of removal of a non-load bearing wall, relocation of gas and utility lines, installation of a new residential-grade kitchen exhaust hood, replacement of kitchen cabinets, countertops, and flooring materials, interior wall painting, and window blind replacement. The project site encompasses 216 square feet of kitchen space within the fire station. Sealed bids are due via the City's e-Procurement Portal by Wednesday, March 25, 2026, at 10:00 am CST. The construction documents are issued for permit and bid as of February 23, 2026, and include detailed architectural, mechanical, electrical, plumbing, and fire protection drawings prepared by licensed professionals with expirations through August 2027.
The project documents specify materials and equipment selections including a Whirlpool residential-grade gas range, GE refrigerators, Manitowac ice maker, luxury vinyl tile flooring (Mohawk brand), Formica plastic laminate cabinetry, Wilsonart quartz countertops, stainless steel corner guards, and a Whirlpool kitchen exhaust hood with internal blower. The construction is estimated to occur within a fully sprinklered Type IIIB construction fire station building originally constructed in 1990. All work must comply with the 2024 International Building Code, 2014 Illinois Plumbing Code, 2020 National Electrical Code, and other applicable standards. The project requires coordination across multiple trades and adherence to fire-rated wall penetration requirements. Per City ordinance, a project labor agreement may be required for public works projects exceeding $50,000, though terms cannot exceed Illinois Prevailing Wage Act standards and cannot mandate union membership.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT SITE
6 POINTS ROAD
S M
O R
R
IS
A V
E
NOT IN CONTRACT
WORK AREA
PROJECT SCOPE
THE PROJECT CONSISTS OF THE
RENOVATION OF AN EXISTING KITCHEN.
THE PROJECT REMOVES AN EXISTING
NON-LOAD BEARING WALL, RELOCATES
THE EXISTING GAS LINE FOR A NEW GAS
RANGE, PROVIDES A NEW RESIDENTIAL
GRADE KITCHEN EXHAUST HOOD.
RELOCATE WATER, SEWER AND POWER
TO THE ISLAND AND POWER AND DATA
FOR THE TV. REPLACE EXISTING
KITCHEN CABINETS, COUNTERTOPS AND
FLOORING MATERIALS. PAINT INTERIOR
WALLS AND REPLACE EXISTING BLINDS
ON ALL WINDOWS.
OWNER
ARCHITECTURAL
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079
309.282.8000
IL DESIGN FIRM
#184000358-0001
INTERIOR DESIGN
Dewberry Architects Inc.
401 Southwest Water Street Suite 701 Peoria, IL 61602-1585
309.282.8000
IL DESIGN FIRM
#184000358-0001
MEPFP
Dewberry Engineers Inc.
401 Southwest Water Street Suite 701 Peoria, IL 61602-1585
309.282.8000
IL. REG.#184005007-0006
PROJECT NUMBERBLOOMINGTON FIRE STATION #4 KITCHEN
REMODEL
1705 S MORRIS AVE
BLOOMINGTON, ILLINOIS 61701
ISSUE FOR PERMIT & BID | 02/23/2026
BLOOMINGTON FIRE
DISTRICT
50190534
Scale: N.T.S.
AERIAL SITE MAP
Scale: 3/32" = 1'-0"
WORK AREA DIAGRAM
SS IOE NFO ALR P E ND GE IS NN EE EC RI L 062.077973
KRISTIE HAINES
DATE: 02/23/2026
EXP: 11/30/2027
DATE: 02/23/2026
EXP: 11/30/2027Exp Date:
Seal Date: 02/23/2026 11/30/2027
DATE: 10/30/2025
EXPIRES: 8/31/2027
DATE: 2/23/2026
EXPIRES: 8/31/2027
Carla Murillo Textbox Bid #2026-36
A101
SIM
APC-X
8' - 0"
A
X#XX 1HR
SF01
Area Name
150 SF
FIRST FLOOR
100' - 0"
ROOM NAME
A101
SIM
GB-01
View Name
1/A101Scale:1/8" = 1'-0"
A101
SIM
CALLOUT
BUILDING/WALL
SECTION
DETAIL SECTION
ROOM TAG
CEILING TAG
DOOR / BORROWED
LITE TAG
WINDOW TAG
WALL TAG
FURNITURE,
CASEWORK, &
EQUIPMENT TAG
REVISION TAG
KEYNOTE TAG00 00 00.A1
AREA TO BE
ENLARGED
SHEET REF.
PLAN / DETAIL REF.
SECTION REF.
SHEET REF.
DETAIL REF.
SHEET REF.
LEVEL LINE
AREA SQUARE
FOOTAGE
ROOM NUMBER
EXTERIOR
ELEVATION
INTERIOR
ELEVATION
ELEVATION REF.
SHEET REF.A101
A101
1 ELEVATION REF.
SHEET REF.
VIEW NAME
VIEW SCALE
VIEW DESIGNATION
VIEW REF/SHEET REF
WHERE VIEW IS REFERENCED
VIEW TITLE
AREA TAG
CEILING TYPE
CEILING HEIGHT
(ABOVE FINISH FLOOR)
LEVEL NAME
LEVEL ELEVATION
GRID LINE
NORTH INDICATOR
GRID NUMBER OR
LETTER
INDICATES PLAN NORTH
INDICATES TRUE NORTH
A101
SPOT ELEVATION
SYMBOL
ANNOTATION LEGEND
PT-X
RB-X
CPT-X
NOTES: 22
ROOM NAME
ROOM FINISH TAG
ROOM NUMBER
WALL FINISH
BASE FINISH
FLOOR FINISH
FINISH NOTES
FLOOR MOUNTED WATER CLOSET
WALL MOUNTED TANKLESS WATER CLOSET
FLOOR MOUNTED TANKLESS WATER CLOSET
TOILET PARTITIONS
LOCKERS
LOCKER
COUNT
GRAB BAR
WALL MOUNTED URINAL
NEW WALL
EXISTING WALL
EXISTING WALL TO BE DEMOLISHED
NEW DOOR
EXISTING DOOR
EXISTING DOOR TO BE DEMOLISHED
WALL MOUNTED LAVATORY
COUNTER MOUNTED LAVATORY
ELECTRIC WATER COOLER
DRAFTING LEGEND
ALUMINUM
BATT INSULATION
CMU (CONCRETE MASONRY UNIT)
CONCRETE
DRAINAGE MESH
EARTH (BACKFILL)
EARTH (UNDISTURBED)
FACE BRICK
FINISHED WOOD
2x WOOD BLOCKING
1x WOOD BLOCKING
GRAVEL
GYPSUM BOARD
PLASTER
PLYWOOD
RIGID INSULATION
SAND/GROUT
SPRAY FOAM INSULATION
STEEL
STONE
MATERIAL LEGEND
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:5
A
M
INDEX
SS
BK
SS
02/23/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
G-001
AB ANCHOR BOLT
ACST ACOUSTIC(AL)
ADDL ADDITIONAL
ADDN ADDITION
ADH ADHESIVE
ADJ ADJACENT, ADJOINING,
ADJUSTABLE
AED AUTOMATED EXTERNAL
DEFIBRILLATOR
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ANCH ANCHOR
ANOD ANODIZE(D)
AP ACCESS PANEL
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
ASPH ASPHALT
AUTO AUTOMATIC
AVE AVERAGE
AWT ACOUSTICAL WALL TREATMENT
BAL SHT BALANCE SHEET
BC BRICK COLOR
BCS BABY CHANGING STATION
BD BOARD
BG BUMPER GUARD
BITUM BITUMINOUS
BLDG BUILDING
BLKG BLOCKING (WOOD)
BOT BOTTOM
BRDG BRIDGING
BRG BEARING
BRK PV BRICK PAVERS
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT UP ROOFING
CAB CABINET
CB CHALKBOARD
CC CUBICLE CURTAIN
CCT CUBICLE CURTAIN TRACK
CFCI CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CFMF COLD-FORMED METAL FRAMING
CG CORNER GUARD
CH COAT HOOK
CIP CONC CAST-IN-PLACE CONCRETE
CJ CONTROL JOING, CONSTRUCTION
JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEAN OUT, CASED OPENING
COL COLUMN
COMB COMBINATION, COMBINED
COMP COMPRESSIBLE
COMPT COMPARTMENT
CONC CONCRETE
CONC CTG CONCRETE COATING
COND CONDITION
CONT CONTINUOUS
CONTR CONTRACTOR
CORR CORRIDOR
CPRS COMPRESSIBLE
CPT CARPET
CR CLOSET ROD
CRL CRASH RAIL
CRS COLD-ROLLED STEEL
CTR CENTER(S)
CUH CABINET UNIT HEATER
CUV CABINET UNIT VENTILATOR
CW CURTAINWALL
D DEEP, DEPTH, PENNY NAIL
DC DISPLAY CASE
DET DETAIL
DETN DETENTION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DP DECORATIVE PANEL
DR DOOR
DS DOWNSPOUT
DWG DRAWING(S)
EHD ELECTRIC HAND DRYER
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EMBED EMBEDMENT
EMER EMERGENCY
EPDM ETHYLENE PROPYLENE DIENE
MONOMER
EQ EQUAL
EQUIP EQUIPMENT
ES EXPOSED STRUCTURE
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
FAB FABRIC
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FHC FIRE HOSE CABINET
FIN FINISH
FLASH FLASHING
FLP FLOOR PATTERN
FLR FLOOR
FRP FIBER REINFORCED PLASTIC
FTG FOOTING
FURG C FURRING CHANNEL
FURN FURNACE
FWC FABRIC WALLCOVERING
GA GAGE, GAUGE
GALV GALVANIZED
GB GRAB BAR
GFRC GLASS-FIBER REINFORCED
CONCRETE
GL GLASS
GL BLK GLASS BLOCK
GLZ CMU GLAZED CONCRETE MASONRY UNIT
GRFG GLASS-FIBER REINFORCED GYPSUM
GT GROUT
GWH GAS FIRED WATER HEATER
GYP BD GYPSUM WALL BOARD
H HIGH, HATCH (ROOF)
HB HOSE BIB
HDNR HARDENER
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HORIZ HORIZONTAL
HR HANDRAIL
HT HEIGHT
HTG HEATING
HVAC HEATING, VENTILATING, AND AIR
CONDITIONING
ID INSIDE DIAMETER, INSIDE
DIMENSION
IF INSIDE FACE
INCL INCLUDED
INSUL INSULATION
INT INTERIOR
INV INVERT
JT JOINT
KD KNOCKED DOWN
KOP KNOCK OUT PANEL
L LONG, ANGLE
LAM LAMINATE(D)
LAV LAVATORY
LH LEFT HAND
LINO LINOLEUM
LKR LOCKER
LL LIVE LOAD, LOW LEVEL
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LVL LEVEL
LVR LOUVER
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MARKERBOARD
MBH MOB/BROOM HOLDER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MI MIRROR
MIN MINIMUM, MINUTE
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODEL, MODULE, MODULAR
MSB MOP SERVICE BASIN
MT MOUNT
MTL METAL
NDU NEEDLE DISPOSAL UNIT
NIC NOT IN CONTRACT, NOISE ISOLATION
CLASS
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER, OUTSIDE
DIMENSION
OF OUTSIDE FACE
OFCI OWNER FURNISHED CONTRACTOR
INSTALLED
OFD OVERFLOW DRAIN
OFOI OWNER FURNISHED OWNER
INSTALLED
OH OVERHEAD
OH DR OVERHEAD DOOR
OP OPERABLE PARTITION
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OS OVERFLOW SCUPPER
PC PORTLAND CEMENT, POINT
OF CURVE, POLYCARBONATE
PCC PRECAST CONCRETE
PERIM PERIMETER
PJ PROJECTOR
PL PLATE, PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PS PROJECTION SCREEN
PSF POUNDS PER SQUARE FOOT
PT PAINT
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER &
RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVC POLYVINYL CHLORIDE
PVG PAVING
R RISER, RADIUS, THERMAL
RESISTANCE (R-VALUE)
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN, ROAD
REF REFERENCE, REFRIGERATOR
REINF REINFORCE
REQD REQUIRED
RF RESILIENT FLOORING
RFG ROOFING
RFM REMOVABLE FLOOR MAT
RH RIGHT HAND
RO ROUGH OPENING
RS ROLLER SHADE
RSF RESINOUS FLOORING
RST REINFORCING STEEL
RTF RESILIENT TILE FLOORING
RV ROOF VENT, ROOF VENTILATOR
SC SEALED CONCRETE
SCHED SCHEDULE
SCR SHOWER CURTAIN ROD
SCWD SOLID CORE WOOD DOOR
SD SOAD DISPENSER
SECT SECTION
SF STOREFRONT
SH SHINGLES, SINGLE HUNG (WINDOW)
SHT SHEET
SHTHG SHEATHING
SHV SHELVING
SLNT SEALANT
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT
SOG SLAB ON GRADE
SPCG SPACING
SPEC SPECIFICATION
SPKR SPEAKER
SQ SQUARE
SS SERVICE SINK , SOLID SURFACING
SST STAINLESS STEEL, SHOWER SEAT
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STL LNTL STEEL LINTEL
STL PL STEEL PLATE
STL RF DK STEEL ROOF DECK
STL TR STEEL TRUSS
STN STAIN
STRUCT STRUCTURAL
SUSP SUSPEND
SV SHEET VINYL
SWP SHEET WALL PROTECTION
SYMM SYMMETRICAL
SYNTH SYNTHETIC
T TILE, TREAD
T&G TONGUE AND GROOVE
T/S TUB/SHOWER
TB TOWEL BAR, TACKBOARD
TC TOILET COMPARTMENT
TD TRENCH DRAIN
TER TERRAZZO
THK THICK
TOB TOP OF BEAM
TOC TOP OF CONCRETE, TOP OF CURB
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF SLAB, TOP OF STEEL
TOW TOP OF WALL
TPH TOILET PAPER HOLDER
TR TOWEL RACK
TS TUBE STEEL, TRANSITION STRIP
UNO UNLESS NOTED OTHERWISE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W WIDE, WEST
WC WALL COVERING
WD WOOD, WOOD DOOR
WDW WINDOW
WP WALL PATTERN, WATERPROOFING
WT WEIGHT, WINDOW TREATMENT
WWF WELDED WIRE FABRIC
STANDARD ABBREVIATIONS
SHEET INDEX
SHEET NO. SHEET NAME
GENERAL
G-000 COVER
G-001 INDEX
G-002 CODE PLAN
ARCHITECTURAL
AD-111 FIRST FLOOR DEMOLITION PLAN & RCP
A-111 FIRST FLOOR ANNOTATION & DIMENSION PLAN
A-112 FIRST FLOOR RCP AND FINISH PLAN
A-411 INTERIOR ELEVATIONS
A-421 INTERIOR CASEWORK DETAILS
FIRE PROTECTION
F-111 FIRST FLOOR DEMO & NEW WORK PLANS - FIRE PROT
PLUMBING
P-001 PLUMBING SYMBOLS, ABBREVIATIONS & NOTES
PD-111 UNDER & FIRST FLOOR DEMO PLANS - PLUMBING
P-111 UNDER & FIRST FLOOR NEW WORK PLANS - PLUMBING
P-301 DETAILS & RISER DIAGRAMS - PLUMBING
MECHANICAL
M-001 MECHANICAL SYMBOLS, ABBREVIATIONS & NOTES
M-111 FIRST FLOOR PLAN DEMO & NEW WORK PLANS - MECH
ELECTRICAL
E-001 ELECTRICAL SYMBOLS, ABBREVIATIONS, & NOTES
E-110 FIRST FLOOR PLANS - ELECTRICAL
E-111 FIRST FLOOR PLANS - ELECTRICAL
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
ISSUE FOR COST ESTIMATE 02/12/26
1 ISSUE FOR PERMIT & BID 02/23/26
1 1
2 2
SB SB
SHADED REGION
IS NOT IN
CONTRACT
470 SF
LOUNGE
52 SF
WATCH
OFFICE
209 SF
DINING
216 SF
KITCHEN
MECH
HALL
STORAGE
APPARATUS
BUSINESS
3033 SF / 100 SF
= ACTUAL OCCUPANTS
239 = ALLOWABLE = 36" / .15"
(1) 36" DOOR(S) | 36" EGRESS CAPACITY
= ACTUAL OCCUPANTS
239 = ALLOWABLE = 36" / .15"
(1) 36" DOOR(S) | 36" EGRESS CAPACITY
BUSINESS
980 SF / 100 SF
= ACTUAL OCCUPANTS
239 = ALLOWABLE = 36" / .15"
(1) 36" DOOR(S) | 36" EGRESS CAPACITY
= ACTUAL OCCUPANTS
239 = ALLOWABLE = 36" / .15"
(1) 36" DOOR(S) | 36" EGRESS CAPACITY
= ACTUAL OCCUPANTS
239 = ALLOWABLE = 36" / .15"
(1) 36" DOOR(S) | 36" EGRESS CAPACITY
DORMITORY /
TRAINING
TOILET
TOILET
STORAGE
LOCKERS
UTILITY
MECH
HOSE TOWER
PATH 1 (5)
PATH 2 (6)
FE
BUSINESS
92 SF / 100 SF
BUSINESS
648 SF / 100 SF
PATH 3 (16)PATH 4 (15)
PATH 5 (7)
Diagonal Down
PATH
AREA OF SPACE/AREA PER OCCUPANT
OCCUPANT LOAD
OCCUPANCY USE TYPE
TRAVEL DISTANCE
1-HR FIRE RATED WALL (EXISTING TO REMAIN)
2-HR FIRE RATED WALL (EXISTING TO REMAIN)
NUMBER OF OCCUPANTS GOING THROUGH AN
EGRESS DOOR
DOOR PANEL SIZE
SMOKE PARTITIONS (EXISTING TO REMAIN)
Area Name
150 SF / 150 SF
= ACTUAL OCCUPANTS
= ALLOWABLE = 34" / .15"
(2) 36" DOOR(S) | 34" EGRESS CAPACITY
CODE PLAN LEGEND
FIRE EXTINGUISHER - WALL MOUNTEDFE
MAX. NUMBER OF OCCUPANTS ALLOWED PER
CODE THROUGH AN EGRESS DOOR
DOOR EGRESS
CAPACITY
BUILDING CODE SYNOPSIS
BUILDING CODE: 2024 INTERNATIONAL BUILDING CODE
EXISTING BUILDING
CODE: 2024 INTERNATIONAL EXISTING BUILDING CODE
ACCESSIBILITY: 2009 ANSI A117.1 ACCESSIBLE AND USABLE BUILDINGS & FACILITIES
2010 ADA
PLUMBING: 2014 ILLINOIS PLUMBING CODE
FIRE PREVENTION: 2018 INTERNATIONAL FIRE CODE
MECHANICAL: 2018 INTERNATIONAL MECHANICAL CODE
ELECTRICAL: 2020 NATIONAL ELECTRICAL CODE (NEC)
ENERGY: 2024 ILLINOIS COMMERCIAL STRETCH ENERGY CODE
ORIGINAL BUILDING CONSTRUCTED: 1990
USE GROUP CLASSIFICATION:
1 STORY FIRE STATION (IBC SECTION 302.1):
OCCUPANCIES: BUSINESS (B)
EXISTING BUILDING CONSTRUCTION TYPE (IBC TABLE 601):
TYPE IIIB
FIRE SUPPRESSION:
SCOPE OF WORK AREA FULLY SPRINKLERED
BUILDING DESCRIPTION:
FIRE SEPARATION:
FIRE RESISTANCE RATINGS (TABLE 601):
PRIMARY STRUCTURAL FRAME = 0 HOUR
BEARING WALLS
EXTERIOR = 2 HOUR
INTERIOR = 0 HOUR
NONBEARING WALLS & PARTITIONS
EXTERIOR = 0 HOUR (BASED ON TABLE 602)
NONBEARING WALLS & PARTITIONS
INTERIOR = 0 HOUR
FLOOR CONSTRUCTION AND
ASSOCIATED SECONDARY MEMBERS = 0 HOUR
ROOF CONSTRUCTION AND
ASSOCIATED SECONDARY MEMBERS = 0 HOUR
FIRE- RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION
DISTANCE (TABLE 602):
30'-0" OR MORE = 0 HOUR
EGRESS:
MINIMUM NUMBER OF EXITS OR ACCESS TO EXITS REQUIRED PER STORY (TABLE 1006.3.2)
OCCUPANT LOAD PER STORY
1-500 OCCUPANTS = 2 EXITS
501-1,000 OCCUPANTS = 3 EXITS
OCCUPANT LOAD FIRST FLOOR = 49
ACTUAL NUMBER OF EXITS PROVIDED:
FIRST FLOOR = 5 EXITS
COMMON PATH OF EGRESS TRAVEL - WITH SPRINKLER SYSTEM (TABLE 1006.2.1)
OCCUPANCY B = 100 FEET
EXIT ACCESS TRAVEL DISTANCE - WITH SPRINKLER SYSTEM (TABLE 1017.2)
OCCUPANCY B = 300 FEET
CORRIDOR FIRE RESISTANCE RATING (TABLE 1020.1)
OCCUPANCY B = 0 HOUR WITH SPRINKLER SYSTEM
MAXIMUM DEAD ENDS (SECTION 1020.4)
OCCUPANCY B = 50 FEET WITH AUTOMATIC SPRINKLER SYSTEM
APPLICABLE CODES:
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:5
A
M
CODE PLAN
SS
BK
SS
02/23/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
G-002
Scale: 3/16" = 1'-0"
FIRST FLOOR - CODE PLAN
- Paths - Egress Path Schedule
PATH NAME PATH LENGTH
PATH 1
PATH 1 35' - 5"
35' - 5"
PATH 2
PATH 2 47' - 11"
47' - 11"
PATH 3
PATH 3 63' - 0"
63' - 0"
PATH 4
PATH 4 70' - 8"
70' - 8"
PATH 5
PATH 5 35' - 8"
35' - 8"
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
REMOVE EXISTING WALL
AND PASS THRU
REMOVE EXISTING GAS
RANGE, GAS LINE TO BE
RELOCATED.
REMOVE EXISTING SINK
IN ITS ENTIRETY
REMOVE EXISTING
DISHWASHER
REMOVE EXISTING WALL
CABINETS, BASE
CABINETS AND
COUNTERTOP
REMOVE EXISTING
REFRIGERATORS
STORAGE
MECH
OFFICE
APPARATUS
LOUNGE
WATCH
KITCHEN
HALL
DINING
NOT IN CONTRACT
REMOVE EXISTING
TRANSITION STRIP.
SAW CUT EXISTING FLOOR SLAB FOR
NEW PIPING PENETRATIONS, REFER
TO PLUMBING DRAWINGS FOR
LOCATIONS
BASE BID: REMOVE
EXISTING FLOOR TILE,
PREP FLOOR FOR
RECEIVING NEW FLOOR
FINISH
REMOVE EXISTING WALL SECTIONS AS REQUIRED FOR
NEW ELECTRICAL AND PLUMBING SERVICES, REFER
TO ELEC. PLUMB. DWGS. PATCH AND REPAIR
LOCATIONS AS REQUIRED.
REMOVE EXISTING WALL SECTIONS AS REQUIRED FOR
NEW ELECTRICAL AND PLUMBING SERVICES, REFER
TO ELEC. PLUMB. DWGS. PATCH AND REPAIR
LOCATIONS AS REQUIRED.
1. VISIT SITE AND VERIFY EXISTING CONDITIONS PRIOR TO BID SUBMISSION.
DISCREPANCIES BETWEEN CONSTRUCTION INDICATED ON DRAWINGS AND
ACTUAL SITE CONDITIONS SHALL BE BROUGHT TO ARCHITECT’S ATTENTION
IMMEDIATELY IN WRITING.
2. DEMOLISHED ITEMS NOT INDICATED TO BE “DELIVERED TO OWNER” OR “TO BE
RELOCATED” SHALL BE REMOVED FROM SITE AS SOON AS POSSIBLE UNLESS THEY
ARE TO BE USED FOR REQUIRED PATCHING AND INFILLING OF EXISTING
CONSTRUCTION THAT IS TO REMAIN. NO OTHER DEMOLISHED ITEMS SHALL BE
STORED ON SITE.
3. DEMOLISHED ITEMS NOTED AS “DELIVER TO OWNER” OR “TO BE RELOCATED”
SHALL BE REMOVED OR DISASSEMBLED IN SUCH A MANNER THAT WILL NOT
DAMAGE THE ITEM AND PREVENT IT FROM BEING RELOCATED. REPAIR OR
REPLACE SUCH ITEMS, IF DAMAGED. NOTIFY OWNER’S REPRESENTATIVE
IMMEDIATELY IF DAMAGE HAS OCCURRED, AND SUBMIT A REPAIR SOLUTION TO
ARCHITECT FOR REVIEW.
4. TEMPORARILY STORE ITEMS INDICATED AS “DELIVER TO THE OWNER” IN ONSITE
LOCATION, DESIGNATED BY THE OWNER. OWNER SHALL MOVE ITEM(S), AS
NECESSARY, TO NOT HINDER OR DELAY PERFORMANCE OF WORK IN AREA.
5. TEMPORARILY STORE ITEMS INDICATED AS “TO BE RELOCATED” IN LOCATION
ONSITE AND PROTECT ITEMS FROM DAMAGE PRIOR TO INSTALLATION IN NEW
LOCATION.
6. ITEMS INDICATED “TO REMAIN” THAT ARE DAMAGED DURING THE PERFORMANCE
OF THE DEMOLITION WORK. SUCH DAMAGE SHALL BE REPORTED TO OWNER’S
REPRESENTATIVE IMMEDIATELY, AND SUBMIT A REPAIR SOLUTION TO ARCHITECT
FOR REVIEW.
7. COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTION WORK IN EACH AREA
OF DEMOLITION. EXISTING CONSTRUCTION IN AREAS ADJACENT TO DEMOLITION
WORK SHALL BE PATCHED AND REPAIRED TO MATCH ORIGINAL EXISTING
CONDITION AS REQUIRED TO PROVIDE FOR NEW CONSTRUCTION WORK IN AREA
OF DEMOLITION.
8. ITEMS INDICATED TO BE REMOVED BY OWNER SHALL BE COMPLETED PRIOR TO
COMMENCEMENT OF WORK.
9. AT LOCATIONS WHERE A PORTION OF EXISTING CONSTRUCTION IS TO BE
REMOVED AND PREPARED FOR NEW INFILL CONSTRUCTION, OR AN OPENING IN A
WALL, ROOF, OR FLOOR IS CREATED BY DEMOLITION WORK, CONSTRUCT INFILL
WITH SAME MATERIALS AND METHOD OF CONSTRUCTION AS EXISTING ADJACENT
CONSTRUCTION, UNLESS NOTED OTHERWISE. SEE ARCHITECTURAL DRAWINGS
FOR INFILL CONSTRUCTION. INFILL CONSTRUCTION SHALL SMOOTHLY BUTT
ADJACENT SURFACES AND MATCH THE FINISH, U.N.O.
10. AT LOCATIONS WHERE AN ITEM IS TO BE REMOVED FROM A SURFACE THAT IS TO
REMAIN, PATCH AND REPAIR EXISTING SURFACE TO MATCH EXISTING ADJACENT
SURFACE, UNLESS INDICATED OTHERWISE.
11. EXISTING ITEMS ANCHORED TO CONSTRUCTION THAT IS INDICATED TO BE
DEMOLISHED SHALL BE CONSIDERED A PART OF DEMOLISHED CONSTRUCTION
AND SHALL BE DEMOLISHED WITH THE INDICATED CONSTRUCTION, UNLESS
NOTED OTHERWISE.
12. IN CONDITIONS WHERE A WALL OR FLOOR FINISH IS DEMOLISHED CREATING A
DISSIMILAR ELEVATION IN ADJACENT FLOOR FINISHES, INSTALL AN APPROVED
LEVELING MATERIAL TO BRING LOWER FLOOR FINISH ELEVATION UP TO AN
ELEVATION FLUSH WITH ADJACENT FLOOR.
13. CONSTRUCT TEMPORARY DUST PARTITIONS TO CONTAIN DEMOLITION WORK AND
PREVENT CONSTRUCTION DUST FROM ENTERING ADJACENT EXISTING
CONSTRUCTION. SUBMIT LOCATIONS OF THESE PARTITIONS FOR APPROVAL BY
OWNER’S REPRESENTATIVE. PARTITION LOCATIONS SHALL NOT IMPEDE OR
HINDER EMERGENCY EGRESS FROM BUILDING. REFER TO SPECIFICATIONS FOR
CONSTRUCTION OF DUST PARTITIONS.
14. RETAIN DEMOLISHED MATERIALS AS NEEDED FOR INFILLING OPENINGS IN
EXISTING CONSTRUCTION SO THAT FINISH MATERIALS WILL PROPERLY ALIGN
WITH EXISTING AND MATCH THE EXISTING FINISH. IF DEMOLISHED MATERIALS ARE
NOT SALVAGEABLE, NOTIFY OWNER’S REPRESENTATIVE, SO THAT ALTERNATE
SOLUTIONS MAY BE DETERMINED.
15. IF EXISTING CONSTRUCTION IS REVEALED NOT CONSTRUCTED OR FINISHED IN A
MANNER THAT MATCHES ADJACENT SURFACES, PATCH AREA AS NECESSARY
WITH APPROPRIATE MATERIALS AND METHODS OF CONSTRUCTION TO MATCH
EXISTING ADJACENT FINISH, OR PREPARE SURFACE FOR INSTALLATION OF NEW
FINISH. CONTACT OWNER’S REPRESENTATIVE AS SOON AS POSSIBLE SO THAT
CONCEALED CONSTRUCTION MAY BE IDENTIFIED AND SCOPE OF POSSIBLE
ADDITIONAL WORK DETERMINED.
16. WHEN EXISTING SURFACE IS INDICATED TO BE “PATCHED AND REPAIRED” OR
“PREPARED” TO RECEIVE NEW FINISH MATERIAL, PROVIDE A CONSTRUCTION
SURFACE THAT IS CAPABLE OF RECEIVING NEW FINISH MATERIAL.
17. WHEN THE TERM ‘ENTIRETY’ IS DIRECTED TO A SPECIFIC ITEM OR ASSEMBLY,
DEMOLISH AND REMOVE IDENTIFIED ITEM AND ASSOCIATED CONSTRUCTION
PERTINENT TO THE ITEM, INCLUDING, BUT NOT LIMITED TO UNDERGROUND AND
CONCEALED CONSTRUCTION, SUCH AS FOOTINGS AND FOUNDATIONS, SEWER,
PLUMBING, AND ELECTRICAL WORK. THIS DEMOLITION WORK SHALL BE
COORDINATED WITH PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS.
DEMOLITION PLAN GENERAL NOTES
REMOVE EXISTING SOFFITS
ABOVE CABINETS
NOT IN CONTRACT
REMOVE EXISTING 1'X4' LIGHT
FIXTURES IN LOUNGE, DINING ROOM,
AND OFFICE. REPLACE WITH NEW
LIGHT FIXTURES. REFER TO
ELECTRICAL DWGS.
REMOVE EXISTING CEILING
AND LIGHT FIXTURES
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:0
A
M
FIRST FLOOR
DEMOLITION
PLAN & RCP
SS
BK
SS
02/23/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
AD-111
Scale: 1/4" = 1'-0" A1
FIRST FLOOR DEMOLITION PLAN
Scale: 1/4" = 1'-0" D1
FIRST FLOOR DEMOLITION RCP
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
APPARATUS
STORAGE
MECH
112 OFFICE
LOUNGE
WATCH
KITCHEN
HALL
DINING
A-411
D1
D
B5
A-411
B1
D5
NOT IN CONTRACT
RELOCATED TV
4 LOCKABLE
SHIFT PANTRY
CABINETS A-411 B
2'x2' BASE CABINET, COUNTERTOP AND COFFEE
STATION
A-411A
A-411
A2
0" - 0"
0" - 0"
CG-2
CG-2
CG-1
CG-2
CG-2
CG-1
RS-1
RS-1
RS-1
RS-1
RS-1
RS-1
TV
COFF
RNGE
ICE
REFREF
1. SEE ROOM FINISH PLANS AND INTERIOR ELEVATIONS FOR WALL FINISHES.
2. SEE INTERIOR ELEVATIONS FOR CASEWORK MATERIAL FINISH.
3. ALL NEW WALL PENETRATIONS MUST BE SEALED AGAINST THE PASSAGE OF
SMOKE. ALL NEW WALL PENETRATIONS THROUGH A FIRE RATED WALLS MUST BE
SEALED TO MAINTAIN THE SPECIFIED RATING. FIRE RATED WALLS MUST BE
VERIFIED BY THE CONTRACTOR IN THE FIELD.
4. ALL ROOM NAMES AND NUMBERS INDICATED ON THE DRAWINGS SHALL BE USED
FOR THE PROGRAMMING OF ALL SYSTEMS.
5. FURNISH AND INSTALL FIRE-RETARDANT-TREATED WOOD BLOCKING OR METAL
BACKING PLATE IN STEEL STUD PARTITIONS FOR PROPER ANCHORAGE OF WALL
ATTACHED ITEMS; I.E. TOILET ACCESSORIES, TOILET PARTITIONS, CASEWORK,
MILLWORK, WALL-MOUNTED FIXTURES, MARKERBOARDS, TACKBOARDS, DOOR
STOPS, AUDIO VISUAL BRACKETS, ETC.
6. GYPSUM BOARD AND PLASTER SURFACES SHALL BE ISOLATED WITH CONTROL
JOINTS WERE INDICATED ON DRAWINGS AND/OR AS DESCRIBED IN THE
SPECIFICATIONS.
7. INCLUDE OWNER-FURNISHED AND INSTALLED ITEMS AND OWNER FURNISHED AND
CONTRACTOR INSTALLED ITEMS IN THE CONSTRUCTION SCHEDULE, AND
COORDINATE WITH OWNER TO ACCOMMODATE THESE ITEMS.
8. ARCHITECTURAL FINISH FLOOR ELEVATION 0’-0” EQUALS ACTUAL SITE REFERENCE
ELEVATION OF FINISH FLOOR 0'-0".
FLOOR PLAN GENERAL NOTES
1. AT ALL LOCATIONS WHERE GYPSUM BD. MEETS CMU THE GYPSUM BD IS TO BE
FINSHED WITH A J-BEAD AND THE JOINT IS TO HAVE A CONTINUOUS BEAD OF
SEALANT UNLESS OTHERWISE NOTED.
2. REFER TO M.E.P. DRAWINGS FOR ADDITIONAL INFORMATION ON MECHANICAL,
ELECTRICAL, AND PLUMBING WORK.
ANNOTATION PLAN GENERAL NOTES
1. REFER TO CODE PLANS FOR GRAPHIC REPRESENTATION AND UL DESIGNS OF
RATED AND SMOKE PARTITIONS.
2. FINAL WALL PREP REQUIREMENTS BASED ON FINISH SHOWN IN THE ROOM FINISH
SCHEDULE AND WITH THE SPECIFICATIONS.
3. REFER TO DETAIL PLANS AND SECTIONS FOR FURTHER DESCRIPTION OF
INTERIOR PARTITIONS.
INTERIOR PARTITION GENERAL NOTES
VIF
8' - 0"
6' - 4 1/2"
NOT IN CONTRACT
C.T. EDGE
2' - 0"
C O
U N
T E
R T
O P
E D
G E
"4
10' - 8"
COUNTERTOP EDGE
7' - 0"
CENTERED ON WALL
LINE OF BASE
CABINETRY BELOW
1. REFER TO CODE PLANS FOR GRAPHIC REPRESENTATION AND U.L. DESIGNS OF
RATED WALLS AND SMOKE PARTITIONS.
2. EXTEND PARTITIONS TO UNDERSIDE OF STRUCTURE/DECK, U.N.O.
3. FINAL WALL PREP REQUIREMENTS ARE BASED ON FINISH SHOWN IN ROOM FINISH
SCHEDULE AND WITH THE SPECIFICATIONS.
4. DIMENSIONS ARE ACTUAL AND ARE TO FACE OF WALL, FACE OF CONCRETE
WALLS, FACE OF FRAMES OR CENTERLINE OF COLUMNS, UNLESS NOTED
OTHERWISE.
DIMENSION PLAN GENERAL NOTES
METAL STUD
S411-S
WALL MATERIAL
IDENTIFIER
WALL WIDTH
# OF LAYERS (GYP BD, CEMENT
BOARD, WOOD) ON SIDE 1
# OF LAYERS (GYP BD, CEMENT
BOARD, WOOD) ON SIDE 2
WALL HEIGHT IDENTIFIER
OTHER MODIFIERS
TAG LEADER
MATERIALS: M = MASONRY S = METAL STUD C = C-H STUD F = FURRING
M6-Y
WALL HEIGHT IDENTIFIER
OTHER MODIFIERS
TAG LEADER
CMU
SHOWS A ROUNDED VALUE FOR THE WIDTH OF THE STRUCTURAL PORTION
OF THE WALL.
WALL MATERIAL IDENTIFIER & WIDTH:
SHOWS A VALUE FOR THE NUMBER OF LAYERS OF GYP BD ON EACH SIDE OF THE
STUD. A '0' INDICATES ZERO LAYERS OF GYP BD. WHERE A WALL ONLY HAS GYP
BD ON ONE SIDE, IT IS ALWAYS ON THE EXPOSED SIDE.
# OF GYP BD LAYERS ON SIDE 1 & 2:
(METAL STUD WALL ONLY)
- (DASH) = TO STRUCTURE
A = TO 6" ABOVE CEILING OR ONE FULL COURSE ABOVE CEILING (CMU)
B = TO CEILING
C = PARTIAL HEIGHT (SEE PLANS/ELEVATIONS FOR WALL HEIGHT)
C1 = PARTIAL HEIGHT SUPPORT WALL (UNDER RAISED STOREFRONT SYSTEMS)
WALL HEIGHT IDENTIFIER:
A = SPRAY FOAM INSULATION BEHIND METAL STUD
B = PROVIDE WOOD BLOCKING (INDICATE LOCATION)
F = FIRE RATED WALL (COORDINATE WITH CODE COMPLIANCE PLAN FOR
RATING AND UL DESIGNATION)
M = PREFINISHED BREAK METAL
O = OMIT SOUND ATTENUATION BLANKET IN WALL
P = PANELING (WOOD VENEER)
R = IMPACT RESISTANT GYPSUM BOARD
T = WALL TILE WITH TILE BACKER BOARD
S = STONE VENEER
V = FIBER CEMENT SIDING
X = STEEL SUPPORT STRUCTURE
OTHER MODIFIERS:
F1: 7/8" METAL FURRING CHANNEL W/ 5/8" GYP BD (1 1/2" ACTUAL)
F2: 1 1/2" METAL FURRING CHANNEL W/ 5/8" GYP BD (2 1/8" ACTUAL)
F3: 2 1/2" METAL STUD W/ 5/8" GYP BD ONE SIDE (3 1/8" ACTUAL)
M2: 2" CMU SOAP (1 5/8" ACTUAL)
M4: 4" CMU (3 5/8" ACTUAL)
M6: 6" CMU (5 5/8" ACTUAL)
M8: 8" CMU (7 5/8" ACTUAL)
S1: 1 5/8" METAL STUD
S2: 2 1/2" METAL STUD
S3: 3 5/8" METAL STUD
S4: 4" METAL STUD
S6: 6" METAL STUD
S8: 8" METAL STUD
C3: 2 1/2" C-H STUD
C4: 4" C-H STUD
P8
WALL MATERIAL
IDENTIFIER
WALL WIDTH TAG LEADER
PRECAST
P8: 8" PRECAST
P12: 12" PRECAST
WALL MATERIAL
IDENTIFIER
WALL WIDTH
INTERIOR PARTITION LEGEND
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:0
A
M
FIRST FLOOR
ANNOTATION &
DIMENSION PLAN
SS
BK
SS
02/23/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
A-111 Scale: 3/8" = 1'-0"
A1
FIRST FLOOR ANNOTATION PLAN
Scale: 3/8" = 1'-0" D1
FIRST FLOOR DIMENSION PLAN
EQUIPMENT SCHEDULE
TAG DESCRIPTION MANUF. MODEL RESPONSIBILITY
RNGE RANGE WHIRLPOOL WEG750H0H OFCI
REF REFRIGERATOR GE GTS19KYNRFS OFCI
REF REFRIGERATOR GE GTS19KYNRFS OFCI
ICE ICE MAKER MANITOWAC
ICE
UYF0240A-161 OFOI
COFF COFFEE MAKER PER OWNER OFOI
TV TELEVISION PER OWNER OFOI
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
J
PNT-1
RB-1
EXIST
MECH
PNT-1,
U.N.O.
RB-1
LVT-1
KITCHEN
PNT-1,
U.N.O.
RB-1
LVT-1
DINING
PNT-1,
U.N.O.
EXIST
EXIST
LOUNGE
PNT-1
RB-1
LVT-1
WATCH
PNT-1,
U.N.O.
EXIST
EXIST
OFFICE
PNT-2
PNT-2 PNT-2
WT-1
PNT-2
PNT-2
PNT-2 PNT-2
PNT-2
EXISTING FLOORING TO REMAINLVT-1
EXISTING TILE
TO REMAIN
EXISTING TILE
TO REMAIN
INSTALL NEW FLAT T-
MOULD TRANSITION STRIP
DEPENDENT ON
CONDITIONS OF CARPET
EDGE AFTER DEMO.
COUNTERTOP TO BE CUT AROUND
RANGE. COORDINATE DIMENSION
WITH OPCI APPLIANCE.
1. SEE SPECIFICATION SECTIONS FOR ADDITIONAL INFORMATION.
2. FINISH INDICATES ENTIRE SURFACE, U.N.O.
3. ALL WALLS TO BE PAINTED PNT-1, U.N.O. ALL ACCENT WALLS TO BE PAINTED PNT-2,
U.N.O.
4. ALL HOLLOW FRAMES TO BE PAINTED PNT-4 U.N.O. ALL HOLLOW METAL DOORS TO
BE PAINTED PNT-5 U.N.O.
5. REFER TO FINISH PLANS, INTERIOR ELEVATIONS, REFLECTED CEILING PLANS, AND
DETAILS FOR PAINT COLOR LOCATIONS.
6. WHERE ANY DISCREPANCIES BETWEEN THE FINISH PLANS, ELEVATIONS AND
SPECIFICATIONS OCCUR, ARCHITECT WILL DETERMINE FINISH.
7. FOR ALL CONCRETE FLOOR SLAB AREAS TO RECEIVE FLOORING MATERIAL,
INCLUDE 1/8" SKIM COAT AS REQUIRED FOR MATERIAL INSTALLATION.
8. PROVIDE TRANSITION STRIPS AT ALL LOCATIONS WHERE TRANSITIONS. BETWEEN
DISSIMILAR FLOORING FINISHES OR HEIGHTS OCCUR. SEE SPECIFICATIONS.
9. PROVIDE RESILIENT BASE AT ALL WALLS AND ALL CASEWORK UNLESS NOTED
OTHERWISE.
10. ANY AREA NOTED AS CMU, CONCRETE OR UNFINISHED/ SEALED SHALL HAVE
CLEARLY STRUCK JOINTS OR RUBBED SURFACE TO PROVIDE A BLEMISH-FREE
SURFACE.
11. REFER TO COVER SHEET FOR SCOPE ALTERNATE DETAILS.
FINISH PLAN GENERAL NOTES
PT-X
RB-X
CPT-X
COMMENTS: 22
ROOM NAME
INTERIOR FINISH LEGEND
FLOOR FINISH TRANSITION TAG
ROOM FINISH TAGWALL FINISH
BASE FINISH
FLOOR FINISH
NOTES (IF
APPLICABLE)
ACCENT WALL MATERIAL / COLOR
XXX
XXXXXX
BID ALTERNATE #2
NOT IN CONTRACT
KITCHEN EXHAUST
CENTERED ON RANGE BELOW
EXISTING HEADER
AT @ 7'-0" AFF
GYP
7' - 0"
" 4' - 2"
GYP
8' - 0"
GYP
8' - 0"
GYP
8' - 10"
NOT IN CONTRACT
NOT IN CONTRACT
2' - 0"
2' - 0" 4' - 8" 4' - 8"
LINE OF KITCHEN
ISLAND BELOW
EQ EQ
A6
A-112
Sim
C.J.
RECESSED LIGHT FIXTURE
RECESSED LIGHT FIXTURE
GYPSUM BOARD CEILING
ROLLER SHADE
SURFACE MOUNTED LIGHT FIXTURE
NOTE: FOR MEPFP DEVICES, REFER TO MEPFP DRAWINGS.
APC-X
8' - 0"
CEILING TYPE
CEILING HEIGHT
CEILING LEGEND
1. REFLECTED CEILING PLAN GENERAL NOTES APPLY TO ALL REFLECTED CEILING
PLAN SHEETS.
2. ELECTRICAL AND MECHANICAL FIXTURES AND DEVICES ARE SHOWN FOR
REFERENCE AND TO COORDINATE PLACEMENT. REFER TO ENGINEERING
DRAWINGS FOR INFORMATION REGARDING TYPE AND OTHER FIXTURE AND
DEVICE INFORMATION.
3. GYPSUM CEILINGS & SOFFITS TO BE PAINTED, COLOR: PNT-3, U.N.O.
4. CEILING HEIGHTS SHOWN ON REFLECTED CEILING PLANS ARE FROM FINISHED
FLOOR OF PLAN SHOWN.
5. SEE ELECTRICAL LIGHTING PLANS FOR EMERGENCY LIGHT FIXTURE LOCATIONS.
6. CONTRACTOR TO COORDINATE CEILING FIXTURE LOCATIONS WITH ABOVE-
CEILING WORK TO AVOID CONFLICTS.
7. CONTROL JOINTS SHOWN IN GYPSUM BOARD SOFFITS SHALL CONTINUE ON
VERTICAL SURFACE OF SAME SOFFIT. SPACE CONTROL JOINTS NO MORE THAN
25'-0" O.C. ARCHITECT TO VERIFY JOINT LOCATIONS PRIOR TO INSTALLATION.
8. ELECTRICAL AND MECHANICAL FIXTURES AND DEVICES ARE SHOWN FOR
REFERENCE AND TO COORDINATE PLACEMENT. REFER TO ENGINEERING
DRAWINGS FOR INFORMATION REGARDING TYPE AND OTHER FIXTURE AND
DEVICE INFORMATION.
9. SUBMIT A REFLECTED CEILING PLAN COORDINATION DRAWING TO ARCHITECT
AFTER COORDINATING LAYOUT WITH OTHER TRADES PRIOR TO COMMENCING
CEILING WORK.
10. ALL SUSPENDED CEILING SYSTEMS SHALL BE SUPPORTED FROM STRUCTURE
ABOVE.
CEILING PLAN GENERAL NOTES
GYP BOARD ON METAL STUDS AT 16" OC
CORNER BEAD, TYP.
METAL STUDS AT 16" OC,
ANCHOR TO STRUCTURE
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:0
A
M
FIRST FLOOR
RCP AND FINISH
PLAN
SS/JB
BK
SS
02/23/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
A-112Scale: 3/8" = 1'-0" A1
FIRST FLOOR FINISH PLAN
FINISH LIST
FINISH COMMENTS
CORNER GUARDS (CG)
CG-1 STAINLESS STEEL CORNER GUARDS, 3'H (CUT IN FIELD AS NEEDED
TO FIT), 1.5" WING LENGTH. INSTALL AT 4" AFF (ABOVE RUBBER
BASE).
CG-2 STAINLESS STEEL CORNER GUARDS, 6'H, 2" WING LENGTH. INSTALL
AT 4" AFF (ABOVE RUBBER BASE).
LUXURY VINYL TILE
LVT-1 MOHAWK, HEAVY AND HEAVY, LINEATE, COLOR: 948 FIGURED, SIZE:
9"x59", 5 MM THICK. INSTALL BRICK ASHLAR.
PAINT (PNT)
PNT-1 SHERWIN WILLIAMS; SW 7015 REPOSE GRAY
PNT-2 SHERWIN WILLIAMS; SW 9170 ACIER
PNT-3 SHERWIN WILLIAMS; SW 7007 CEILING BRIGHT WHITE
PNT-4 SHERWIN WILLIAMS; SW 6258 TRICORN BLACK
PNT-5 TO MATCH EXISTING RED
PLASTIC LAMINATE (PLAM)
PLAM-1 FORMICA, FINNISH OAK 118, MATTE (58)
PLAM-2 FORMICA, BRUSHED STAINLESS STEEL M2178
QUARTZ (QTZ)
QTZ-1 WILSONART, QUARTZ, COLOR: BODEGA Q1022, 2CM THICK
QTZ-2 BID ALTERNATE #3: DALTILE, ONE QUARTZ SURFACES, CARRARA
PISA OQ96 POLISHED, 2 CM THICK
RESILIENT BASE(RB)
RB-1 JOHNSONITE TARKETT, 4" RUBBER COVE BASE, COLOR: BLACK 40
ROLLER SHADES (RS)
RS-1 REFER TO SPECIFICATIONS
STAINLESS STEEL (SST)
SST-1 BID ALTERNATE #5: REFER TO SPECIFICATIONS
WALL TILE (WT)
WT-1 DALTILE, SYNCHRONIC, COLOR: WHITE SY30 TEXTURED, SIZE: 18" x 36".
WOOD (WD)
WD-1 BID ALTERNATE #1: STAIN TO MATCH PLAM-1
Scale: 3/8" = 1'-0" D1
FIRST FLOOR REFLECTED CEILING PLAN
Scale: 1" = 1'-0" A6
GYP BD SOFFIT
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
QTZ-1
PLAM-1
2' - 0"
RB-1
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
8' - 0"
2' - 9" 5' - 3"
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
C1
A-421
PLAM-1
1' - 2"
CUTOUT AT REAR
MILLWORK PANEL, REFER
TO SECTION FOR MORE
DETAIL. CENTER CUTOUT
AT REAR PANEL.
FILLER 2' - 0" 2' - 0"
6" FILLER
2' - 3"3' - 6"3' - 0"1' - 3"
FILLER
WT-1 (BACKSPLASH)
QTZ-1(COUNTERTOP)
PLAM-1
PLAM-1
A3
A-421
Sim
RB-1
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
3' - 0" 1"
2' - 0" 2' - 0" 2' - 0" 2' - 0" 1"
FILLER
1' - 0"
1"
3' - 0" 2' - 0" 3' - 0"
WT-1
(BACKSPLASH)
PLAM-1
QTZ-1
(COUNTERTOP)
PLAM-1
A4
A-421
Sim
C2
A-421
RB-1
LOCKABLE
PANTRY CABINETS
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
D5
A-421
Sim
QTZ-1
PLAM-1
RB-1
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
REFER TO
PLUMB. DWGS.
A1
A-421
Sim
FILLER
1' - 6" 2' - 0" 3' - 0"WATER FILTER
CABINET
TRASH NICHE,
PLAM-2 LINED
ELECTRICAL
OUTLET -
REFER TO
ELEC. SHEETS
RB-1
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
PLAM-1
QTZ-1 (COUNTERTOP)
PLAM-1
END PANEL
CEILING MOUNTED
KITCHEN EXHAUST.
REFER TO MECH. SHEETS
D6
A-421
Sim
CEILING MOUNTED
KITCHEN EXHAUST.
REFER TO MECH. SHEETS
ELECTRICAL
OUTLET - REFER TO ELEC. SHEETS
PLAM-1 END PANEL
QTZ-1
RB-1
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
INTERIOR VERTICAL
DIVIDERS FOR PAN
STORAGE
2' - 0" 2' - 6" +/- 2' - 0"
FILLER
CEILING MOUNTED
KITCHEN EXHAUST.
REFER TO MECH.
SHEETS
ELECTRICAL
OUTLET - REFER
TO ELEC. SHEETS
A2
A-421
Sim
PLAM-1
QTZ-1
RB-1
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
QTZ-1
COORDINATE DIM. WITH OPCI APPLIANCE
FILLER (1-3/4" WIDE MAXIMUM FILLER PER SIDE) IF OPENING
IS LARGER THAN 3-1/2" ADD ANOTHER 3" TO CASEWORK UNIT.
ADJUSTABLE SHELVES
HINGED DOOR
BACKSPLASH
SINK (DASHED)
PANEL
DRAWER, ALL EQUAL U.N.O.
PULL
BASE AS SCHEDULED
WIDTH OF UNITS, SEE
CASEWORK ELEVATIONS
OUTLET
B A
S E
HEIGHT OF CABINET,
SEE CASEWORK
ELEVATIONS
FINISHED END PANEL
THIS IS AN INFORMATIONAL LEGEND AND IS INTENDED
ONLY TO IDENTIFY THE COMPONENTS OF THE
CASEWORK ON SUBSEQUENT DRAWINGS.
ELEVATED CASEWORK LEGEND
/A5 A-421 /C3 A-421
./C6 A-421
/C4 A-421
LOCK
1. DETAILS ARE INTENDED TO SHOW DESIGN INTENT AND DIMENSIONAL
INFORMATION. ACTUAL CASEWORK FABRICATION MUST MEET OR EXCEED
STANDARDS REFERENCED IN THE SPECIFICATIONS.
2. FINISH ALL EXPOSED SURFACES.
3. SEE PLUMBING DRAWINGS FOR PLUMBING FIXTURES, TRAPS, AND ALL OTHER
MISCELLANEOUS ITEMS TO BE FURNISHED AND INSTALLED.
4. FIELD VERIFY ALL DIMENSIONS BEFORE FABRICATING CASEWORK.
5. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
6. COUNTERTOPS ARE 1.25" WITH 4" INTEGRAL BACKSPLASH AND RETURNS, UNLESS
NOTED OTHERWISE.
7. UNLESS NOTED OTHERWISE, BASE CABINETS SHALL BE 23" DEEP, ALL UPPER
CABINETS SHALL BE 12" DEEP AND ALL TALL STORAGE UNITS SHALL BE 24" DEEP.
PROVIDE FILLERS AND FINISHED END PANELS AS REQUIRED.
8. AT LOCATIONS WHERE CASEWORK COVERS CLEANOUTS, EMERGENCY VALVES OR
ELECTRICAL/DATA BOXES PROVIDE REMOVABLE ACCESS PANEL INSIDE
CLASSROOM.
9. AT CASEWORK WHERE ELECTRICAL OUTLETS ARE SPECIFICALLY NOTED INSIDE
CABINETS, OUTLETS TO BE FLUSH MOUNTED ON INSIDE FACE OF CASEWORK
PANEL.
10. PROVIDE CONTINUOUS SEALANT AT GAPS BETWEEN BACKSPLASH AND WALL -
COLOR TO BE CLEAR.
11. ALL LAMINATE WOOD GRAIN TO RUN VERTICAL - TYPICAL FOR BASE AND UPPER
CABINETS.
12. ELECTRICAL OUTLETS ARE SHOWN AS THEY RELATE TO CASEWORK.
COORDINATE LOCATIONS WITH ELECTRICAL DRAWINGS.
13. PROVIDE LOCKS AT ALL CABINETS, KEYED ALIKE PER ROOM, UNLESS NOTED
OTHERWISE.
14. REFER TO SHEET E-110 FOR EQUIPMENT SCHEDULE.
CASEWORK GENERAL NOTES
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:0
A
M
INTERIOR
ELEVATIONS
JB
BMK
SS
02/23/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
A-411Scale: 1/2" = 1'-0" A2
KITCHEN ELEVATION - COFFEE COUNTER
Scale: 1/2" = 1'-0" D5
KITCHEN ELEVATION - NORTH
Scale: 1/2" = 1'-0"
D1
KITCHEN ELEVATION - SOUTH
Scale: 1/2" = 1'-0" D3
KITCHEN ELEVATION - WEST
Scale: 1/2" = 1'-0" A1
KITCHEN ISLAND - ADA SINK
Scale: 1/2" = 1'-0" B1
KITCHEN ISLAND - NORTH
Scale: 1/2" = 1'-0"
B3
KITCHEN ISLAND - SIDE
Scale: 1/2" = 1'-0" B5
KITCHEN ISLAND - SOUTH
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
BASE CABINET W/
THREE DRAWERS
DRAWER
DRAWER
CABINET HARDWARE
SEE SPEC.
COUNTERTOP AND
SQUARE EDGE
U.N.O. ON ELEV.
BACKSPLASH
PER ELEV.
/2
/2
1/2" 5/8"
VARIES
(SEE PLAN)
S P
L A
S H
W H
E R
E I N
D
IC
A T
E D
B A
C K
S P
L A
S H
S
ID
E
S P
L A
S H
P E
R E
L E
V (P
R O
V
ID
E F
U L L
D
IM
P
E R
E L E
V
DRAWER
BASE AS SCHEDULED
BASE CABINET W/
DRAWER &
ADJUSTABLE SHELF
DRAWER
COUNTERTOP AND
SQUARE EDGE
U.N.O. ON ELEV.
BACKSPLASH
PER ELEV.
CABINET HARDWARE
SEE SPEC.
RECESSED
STANDARDS
D
IM
P
E R
E L E
V
W H
E R
E I N
D
IC
A T
E D
B A
C K
S P
L A
S H
S
ID
E
S P
L A
S H
P
R
E L
E V
(P
R O
V
ID
E
F
U L
L S
P L A
S H
/2
/2
5/8"1/2"
VARIES
(SEE PLAN)
M
IN
BASE AS SCHEDULED
PROVIDE WOOD
BLOCKING AS
REQ'D. (TYP.)
3/4" 1' - 2" 1"
CABINET HARDWARE
AS SCHED.
RECESSED STANDARDS
R E
F E
L E
V F
O R
H E
IG
H
T
UPPER CABINET W/
ADJUSTABLE SHELVES
UNDERCABINET LIGHTING -
REFER TO ELECTRICAL
DRAWINGS
FINISHED CEILING -
REFER TO RCP
VANITY SINK - SET IN
BED OF SILCONE
SEALANT REF. MECH.
BACKSPLASH
PER ELEV.
COUNTERTOP AND SQUARE
EDGE U.N.O. ON ELEV.
5/8"
VARIES
(SEE PLAN)
S P
L A
S H
W H
E R
E I N
D
IC
A T
E D
B A
C K
S P
L A
S H
S
ID
E
S P
L A
S H
P E
R E
L E
V (P
R O
V
ID
E F
U L L
D
IM
P
E R
E L E
V
CABINET WITH 180 DEGREE
SWINGING DOORS
1/2"
BASE AS SCHEDULED
FIXED PANELDRAWER
DRAWER
/2
/2
DRAWER
ADJUSTABLE SHELVES
CABINET HARDWARE
AS SCHEDULED
BASE AS SCHEDULED
PROVIDE APRON DTL.
(ADA COMPLAINT)
BASE AS SCHEDULED
SINK; REFER TO
PLUMBING DWGS
BACKSPLASH WATERFALL
EDGE; MATERIAL NOTED
ON ELEVATION
APRON
SURFACE MATERIAL OVER
3/4" SUBSTRATE, FINISH
IDENTIFIED IN ELEVATIONS.
MAX.
7 3/4"
C L R
M
IN
1/2"
2' - 0"
D
IM
P
E R
E L E
V
.8" MIN.
FAUCET, REFER TO
PLUMB. DWGS
BASE CABINET W/ DRAWER
& DIVIDERS, REFER TO
ELEVATION FOR QTY.
DRAWER
COUNTERTOP AND
SQUARE EDGE
U.N.O. ON ELEV.
CABINET HARDWARE
SEE SPEC.
PLAM DIVIDER PANEL
D
IM
P
E R
E L E
V
/2
/2
1/2" 2' - 0"
M
IN
BASE AS SCHEDULED
BASE AS SCHEDULED
BACKSPLASH, PER ELEV.
COUNTERTOP, REFER TO ELEVATION FOR FINISH.
CABINET HARDWARE, REFER TO SPECIFICATIONS
CABINET DOOR
BASE CABINET WITH REV-A-SHELF PULL
OUT BLIND CORNER KITCHEN CABINET
ORGANIZER MODEL # 5PSP-18-CR
BACKSPLASH - SEE
ELEVATION FOR FINISH
FINISHED CEILING
ADJUSTABLE SHELVES
COUNTERTOP - SEE
ELEVATION FOR FINISH
FIXED SHELF
UNDERCABINET LIGHTING -
REFER TO ELECTRICAL
DRAWINGS
1' - 2"
Level 0
0' - 0"
FIRST FLOOR
0' - 0"
ADJUSTABLE SHELVING
OPENING FOR OUTLET -
COORDINATE WITH
ELECTRICAL DRAWINGS
OPENING FOR PLUMBING/
ELECTRICAL COORDINATE
WITH MEP DRAWINGS
SEE PLAN
2' - 0"
OPENING
BASE AS SCHEDULED
PLAM ALL EXPOSED SURFACES
COUNTERTOP WITH SQUARE EDGE
1/2"
FINISHED BACK PANEL
COUNTERTOP AND
SQUARE EDGE
U.N.O. ON ELEV.
BACKSPLASH
PER ELEV.
CABINET HARDWARE
SEE SPEC.
D
IM
P
E R
E L E
V
W H
E R
E I N
D
IC
A T
E D
B A
C K
S P
L A
S H
S
ID
E
S P
L A
S H
P
R
E L
E V
(P
R O
V
ID
E
F
U L
L S
P L A
S H
5/8"
(SEE PLAN)
BASE AS SCHEDULED
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:0
A
M
INTERIOR
CASEWORK
DETAILS
JB
BMK
SS
02/23/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
A-421
Scale: 1" = 1'-0" C3
CASEWORK DTL - BASE CABINET (3 DRAWERS)
Scale: 1" = 1'-0"
C4
CASEWORK DTL - BASE CABINET WITH DRAWER
Scale: 1" = 1'-0" C6
CASEWORK DTL - UPPER CABINET
Scale: 1" = 1'-0" A5
CASEWORK DTL - SINK CABINET
Scale: 1" = 1'-0"
A4
CASEWORK DTL - PANTRY CABINET
Scale: 1" = 1'-0" A1
CASEWORK DTL - ADA SINK
Scale: 1" = 1'-0"
A2
CASEWORK DTL - BASE CABINET WITH DIVIDERS
Scale: 1" = 1'-0" A3
CASEWORK DTL - BLIND CORNER CABINET
Scale: 1" = 1'-0" C2
CASEWORK DTL - ADJUSTABLE SHELVING
Scale: 1" = 1'-0"
C1
CASEWORK DTL - MICROWAVE CABINET
Scale: 1" = 1'-0" D6
CASEWORK DTL - TRASH NICHE
Scale: 1" = 1'-0"
D5
CASEWORK DTL - BASE CABINET
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
F
TS
FLOW SWITCH
HOSE END DRAIN VALVEHED
TEMPERATURE SENSOR
PRESSURE GAUGE
MANUAL DAMPER
MECHANICAL SYMBOLS
FIRE DAMPER
HUMIDISTAT
SYMBOL DESCRIPTION
H
GAS COCK
GAS PRESSURE REGULATING VALVE
CO2
CARBON MONOXIDE SENSOR
T THERMOSTAT/TEMPERATURE SENSOR
MOTOR OPERATED DAMPERM
DUCTWORK SYMBOLS
SMOKE DAMPER
FD
SD
X = SECTION DETAIL NUMBER
XX = SHEET REFERENCE
X
XX
X = CALLOUT DETAIL NUMBER
XX = SHEET REFERENCE
X
XX
GENERAL
CONNECT TO EXISTING
DIRECTION OF AIR FLOW
VENTURI FLOW METER
BUTTERFLY VALVE
BACKFLOW PREVENTER
1/8" PIPE SLOPE AS NOTED
PRESSURE REGULATING VALVE
PIPE REDUCER OR INCREASER
CONTROL VALVE (3-WAY)
MECHANICAL SYMBOLS
DIRECTION OF FLOW
GATE VALVE
BALANCING VALVE
GLOBE VALVE
Y-STRAINER
PIPE CAP OR PLUG
CHECK VALVE
UNION
PIPE CONTINUES
SYMBOL DESCRIPTION
CONTROL VALVE (2-WAY)
ELBOW UP
ELBOW DOWN
TOP TAKE-OFF
BOTTOM TAKE-OFF
BALL VALVE
BFP
SUPPLY AIR DEVICE
EXHAUST AIR DEVICE
RETURN AIR DEVICE
EQUIPMENT TAG
XXX = TYPE X = NUMBER
(SEE SCHEDULE)
XXX
X
AIR DEVICE TAG
X = TAG XX = CFM
(SEE SCHEDULE)
X
XX
AIR DEVICE SYMBOLS
WALL AIR DEVICE (SUPPLY/RETURN)
SA
TO SPACE
SQUARE ELBOW (WITH TURNING VANES)
RADIUS ELBOW (1.5 DIA. UNLESS NOTED)
SQUARE TO SQUARE/ROUND DUCT 90 DEGREE TAKEOFF
ROUND TO ROUND DUCT 90 DEGREE TAKEOFF
TRANSITION
RECTANGULAR ELBOW UP (SUPPLY)
RECTANGULAR ELBOW DN (SUPPLY)
ROUND ELBOW UP (SUPPLY)
ROUND ELBOW DN (SUPPLY)
VAV BOX (SIZE MAY VARY)
45 DEGREE DUCT TRANSITION UP/DN
FLEX DUCT
LINEAR SLOT CEILING AIR DEVICE
LINEAR SLOT WALL AIR DEVICE
CO
CARBON DIOXIDE SENSOR
GENERAL NOTES
1. NOT ALL SYMBOLS AND ABBREVIATIONS SHOWN ON THIS DRAWING MAY
BE USED FOR THIS PROJECT.
2. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS NECESSARY
FOR THE INSTALLATION OF THE WORK AND FOR ALL CERTIFICATES OF
INSPECTION AND APPROVAL REQUIRED BY THE AUTHORITIES HAVING
JURISDICTION. NO WORK IS TO PROCEED WITHOUT BUILDING
DEPARTMENT PERMIT.
3. THE CONTRACTOR SHALL MAINTAIN SUCH INSURANCE AS WILL PROTECT
HIMSELF AND/OR THE OWNER FROM DIRECT, ASSUMED AND CONTINGENT
LIABILITY FROM CLAIMS FOR DAMAGES, FOR PERSONAL INJURIES,
INCLUDING DEATH, AND/OR DAMAGE TO PROPERTY, WHICH MAY ARISE
FROM OPERATION UNDER HIS CONTRACT WHETHER SUCH OPERATIONS
BE BY HIMSELF, OR ANY SUB-CONTRACTOR, OR ANYONE DIRECTLY
EMPLOYED BY EITHER OF THEM.
4. THE MECHANICAL CONTRACTOR SHALL BE FAMILIAR WITH ALL CONTRACT
DOCUMENTS FOR ALL TRADES AND COORDINATE WITH OTHER
CONTRACTORS.
5. WHEN CONFLICTS OCCUR IN THE SPECIFICATIONS OR ON THE DRAWINGS
OR BETWEEN EITHER, PROVIDE THE ITEM OF GREATER QUANTITY OR
HIGHER COST, UNLESS WRITTEN INSTRUCTIONS FROM THE OWNER OR
ENGINEER ARE PROVIDED TO RESOLVE THE SPECIFIC CONFLICT.
6. THE GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION, AS
SPECIFIED, ARE PART OF THIS CONTRACT.
7. THE MECHANICAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL
AND PLUMBING REQUIREMENTS WITH THE ELECTRICAL AND PLUMBING
CONTRACTORS.
8. MECHANICAL WORK SHALL BE IN ACCORDANCE WITH APPLICABLE
FEDERAL, STATE AND LOCAL CODES, AND STANDARDS.
9. THE CONTRACTOR WILL BE HELD TO HAVE VISITED THE PREMISES PRIOR
TO SUBMITTING THEIR BID AN TO HAVE THOROUGHLY EXAMINED ALL
EXISTING CONDITIONS INCLUDING ENTRANCE AND EXIT FACILITIES,
HOURS PERMITTED BY THE BUILDING FOR THE TRANSPORTATION OF
EQUIPMENT AND MATERIALS, AS WELL AS THE CONTRACTOR SATISFIED
THEMSELVES AS TO THE CONDITIONS AND WORK SHOWN ON THE PLANS
OF THE ARCHITECT WHICH WOULD IN ANY MANNER AFFECT THE WORK
UNDER THEIR CONTRACT AND ITS COMPLETION DATE. NO LATER CLAIM
FOR EXTRA COMPENSATION FOR WORK WHICH COULD HAVE BEEN
FORESEEN BY SUCH VISIT OR INVESTIGATION SHALL BE RECOGNIZED.
SUBMISSION OF A BID SHALL BE CONSTRUED AS EVIDENCE THAT SUCH A
VISIT HAD OCCURRED. THE CONTRACTOR SHALL EXAMINE ALL EXISTING
STRUCTURAL CONDITIONS, TAKE ALL NECESSARY MEASUREMENTS FOR
THEIR WORK AT THE SITE AND SHALL VERIFY ALL DIMENSIONS GIVEN ON
THE DRAWINGS OF THE WORK AND THE REFERENCE DRAWINGS.
10. THE SCOPE OF WORK SHALL INCLUDE PROVIDING VENTILATING FOR THE
PREMISES IN ACCORDANCE WITH THESE DRAWINGS AND
SPECIFICATIONS. DRAWINGS AND SPECIFICATIONS INDICATE GENERAL
ARRANGEMENT OF SYSTEMS AND WORK INCLUDED IN THIS CONTRACT,
WORK SHALL CONSIST OF FURNISHING ALL ASPECTS NECESSARY FOR
AND INCIDENTAL TO THE EXECUTION AND COMPLETION OF FULLY
FUNCTIONAL HVAC SYSTEMS INDICATED ON THE DRAWINGS AND
SPECIFIED HEREIN.
11. MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
12. DO NOT SCALE THIS DRAWING FOR EXACT DIMENSIONS. MECHANICAL
DRAWINGS ARE DIAGRAMMATIC ONLY AND ARE BASED ON ONE
MANUFACTURER'S EQUIPMENT. THEY ARE NOT INTENDED TO SHOW
EVERY ITEM IN ITS EXACT LOCATION, THE EXACT DIMENSIONS, OR ALL
THE DETAILS OF THE EQUIPMENT OR DEVICES. THE CONTRACTOR SHALL
VERIFY THE ACTUAL DIMENSIONS OF THE EQUIPMENT PROPOSED TO
ENSURE THAT THE EQUIPMENT WILL FIT IN THE AVAILABLE SPACE; FINAL
ROUTING OF DUCTWORK, PIPING AND EQUIPMENT LOCATIONS SHALL BE
DETERMINED IN THE FIELD. ADDITIONAL OFFSETS, ELBOWS, ETC., SHALL
BE PROVIDED AND INSTALLED WITHOUT ADDITIONAL COST TO THE
OWNER.
13. IN ORDER TO DEFINE REQUIREMENTS FOR CAPACITY, QUALITY,
FUNCTION, SIZE, GAUGES AND GRADES, THESE MATERIAL
SPECIFICATIONS DESIGNATE MANUFACTURERS, BRANDS, AND OTHER
PERTINENT DATA DESCRIBING PRODUCTS THAT CONFORM TO THIS
PROJECT'S REQUIREMENTS, MATERIALS OR PRODUCTS SPECIFIED BY
NAME OF MANUFACTURER, BRAND OR TRADE NAME OR CATALOG
REFERENCE SHALL BE THE BASIS OF THE BID AND FURNISHED UNDER
THIS CONTRACT. SHOULD THE CONTRACTOR WISH TO PROVIDE AN
ALTERNATE PIECE OF EQUIPMENT HE SHALL BEAR ALL BURDEN OF
RESPONSIBILITY GUARANTEEING SUBSTITUTE UNIT IS EQUAL IN ALL
ASPECTS OF PERFORMANCE, DIMENSIONS ETC. WHERE TWO OR MORE
MATERIALS OR PRODUCTS ARE NAMED, THE CHOICE OF THESE SHALL BE
OPTIONAL WITH THE BIDDER, THE BIDDER SHALL SUBMIT HIS BID BASED
ON THE MATERIAL AND PRODUCTS LISTED IN THIS SPECIFICATION.
14. THE MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL
INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE MECHANICAL WORK
COMPLETE AND READY FOR OPERATION.
15. THE CONTRACTOR SHALL GUARANTEE ALL WORK PERFORMED AND
MATERIALS INSTALLED BY HIM TO BE FREE FROM INHERENT DEFECTS,
AND SHALL REPAIR OR REPLACE ANY DEFECTIVE MATERIALS OR
WORKMANSHIP, FREE OF COST TO OWNER, FOR A PERIOD OF ONE (1)
YEAR FROM THE DATE OF ACCEPTANCE BY THE OWNER. ANY DAMAGE OR
LOSS, EXCLUSIVE OF BUILDING CONTENTS DUE TO SUCH DEFECTS WILL
ALSO BE MADE GOOD AT CONTRACTOR'S EXPENSE. DEFECTS WILL BE
REMEDIED AND DAMAGES OR LOSSES WILL BE MADE GOOD WITHIN A
REASONABLE TIME, AS SPECIFIED IN NOTICE BY THE OWNER.
16. ANY LOSS OF, OR DAMAGE TO ANY EQUIPMENT, OR MATERIALS SUPPLIED
BY THE CONTRACTOR, OR BY OWNER FOR INSTALLATION SHALL BE THE
SOLE RESPONSIBILITY OF THIS CONTRACTOR, UNTIL SUCH TIME AS
COMPLETED JOB HAS BEEN APPROVED AND ACCEPTED BY THE OWNER. IF
LOSS, OR DAMAGE SHOULD OCCUR NO CLAIM MAY BE MADE AGAINST THE
OWNER, NOR SHALL COMPLETION DATES BE AFFECTED BY SUCH LOSS,
OR DAMAGE.
17. THE MECHANICAL CONTRACTOR SHALL FURNISH TO THE GENERAL
CONTRACTOR ALL INFORMATION REQUIRED FOR SETTING OF WALL, ROOF
AND PARTITION OPENINGS FOR MECHANICAL WORK.
18. ALL EXTERIOR OPENINGS TO BE PROPERLY CAULKED AND SEALED WITH A
SEALANT OF HIGH QUALITY AND LONG LIFE, TO PREVENT INFILTRATION OF
OUTSIDE AIR INTO CONDITIONED SPACE.
19. CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS OF THE
EQUIPMENT, DUCTWORK IN 3/8" SCALE, PIPING, TEMPERATURE CONTROLS
AND PROVIDE CUTS OF COMPONENTS TO BE FURNISHED BY HIM. ALL
ITEMS SHALL BE SUBMITTED THE ENGINEER FOR HIS APPROVAL. NO
WORK SHALL PROCEED WITHOUT APPROVED SHOP DRAWINGS.
20. CONTRACTOR SHALL FURNISH "AS BUILT" RECORD DRAWINGS AND
OPERATING AND MAINTENANCE INSTRUCTIONS AT THE COMPLETION OF
THE INSTALLATION. DRAWINGS SHALL SHOW:
A. ALL NEW ELECTRICAL AND MECHANICAL WORK INSTALLED
B. MODIFICATIONS AND ADDITIONS TO ORIGINAL DESIGN
C. DIMENSIONAL INFORMATION NECESSARY TO LOCATE BURIED OR
UNDERGROUND PIPING/UTILITIES
21. TEMPORARY WORK TO KEEP NORMAL BUILDING SERVICES IN OPERATION
SHALL BE PART OF THIS CONTRACT. COORDINATE WITH BUILDING
MANAGEMENT AND OBTAIN PERMISSION FOR ANY ALTERATIONS
AFFECTING BUILDING. COORDINATE ALL BUILDING SHUTDOWNS AND
RELOCATIONS OF EXISTING SYSTEMS WITH OWNER. DO NOT PROCEED
WITH WORK AFFECTING BUILDING SYSTEMS AND OPERATION WITHOUT
WRITTEN APPROVAL.
22. CONTRACTOR SHALL COORDINATE HIS WORK WITH ARCHITECT'S
DRAWINGS, LIGHTING, AND WORK OF ALL OTHER TRADES. CONTRACTOR
SHALL PROVIDE ADDITIONAL DUCTWORK TO MAINTAIN CEILING HEIGHTS
AND AVOID WORK OF OTHER TRADES AND EXISTING CONDITIONS, AS
PART OF HIS BASE BID.
23. FIELD OBSERVATION OF EXISTING SYSTEM AND CONDITIONS WAS
ATTAINED VIA LIMITED FIELD SURVEYS. ONLY SYSTEMS AND CONDITIONS
CLEARLY VISIBLE AT THE TIME OF SURVEY ARE SHOWN. CONTRACTOR
SHALL VERIFY EXACT LOCATION OF CONNECTION OF NEW WORK TO
EXISTING.
24. CONTRACTOR TO PROVIDE PRIME AND FINISH PAINTING AS REQUIRED.
25. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING AND/OR
DISPOSING OF ALL ITEMS THAT ARE NOT NECESSARY IN THE COMPLETION
OF THE PROJECT AND SHALL CLEAN THE AREA OF CONSTRUCTION AFTER
THE COMPLETION OF THE PROJECT.
26. WHERE EXISTING EQUIPMENT IS TO BE RELOCATED, EXTREME CARE
SHALL BE TAKEN TO PREVENT DAMAGE DURING THE REMOVAL AND
REINSTALLATION. WHERE DAMAGE OCCURS, THE EQUIPMENT SHALL BE
REPLACED OR REPAIRED TO THE SATISFACTION OF THE ARCHITECT, AT
NO ADDITIONAL COST TO THE OWNER.
27. PROVIDE COMPLETE ACCESS TO ALL NEW OR RELOCATED AIR HANDLING
UNITS, TERMINAL DEVICES, HEATING COILS, AND FANS AND NOTIFY
ENGINEER OF ANY CONFLICTS PRIOR TO INSTALLATION.
GENERAL NOTES - CONTINUEDGENERAL NOTES - MECHANICAL HVAC
1. MECHANICAL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOCATIONS OF
DIFFUSERS, REGISTERS AND GRILLES.
3. SUPPORTS FOR DUCT, FANS, ETC. SHALL BE DIRECTLY FROM BUILDING
STRUCTURE, SUSPENDING ANY OF THE ABOVE FROM ONE ANOTHER IS
PROHIBITED.
4. INSULATE THE BACKS OF ALL DIFFUSERS UNLESS NOTED OTHERWISE.
5. PROVIDE ALL NECESSARY DUCT TRANSITIONS FROM THE INDICATED DUCT
SIZE TO THE ACTUAL EQUIPMENT DUCT COLLAR SIZE.
6. INSTALL EACH FAN WITH THE FAN MOTOR AND DRIVE ORIENTED TO ALLOW
ACCESS.
7. ALL DUCTWORK DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS.
DUCTWORK SIZES SHOWN DO NOT ACCOUNT FOR DUCTWORK LINER OR
INSULATION WRAP THICKNESS.
8. IN FINISHED AREAS, INSTALL ALL DUCTWORK AT THE MAXIMUM ELEVATION
POSSIBLE. PROVIDE ALL FITTINGS, TRANSITIONS AND MATERIALS
REQUIRED TO ACHIEVE MAXIMUM ELEVATION. COORDINATE ALL WORK
WITH OTHER TRADES PRIOR TO THE START OF WORK TO AVOID
CONFLICTS. THIS EXCLUDES ALL DUCT NECESSARY TO KEEP EQUIPMENT
AND DAMPERS ACCESSIBLE FOR MAINTENANCE.
9. THE CONTRACTOR SHALL SEAL ALL LEAKS IN NEW DUCTWORK AND
EXISTING DUCTWORK TO REMAIN. THE CONTRACTOR SHALL CAP AND
SEAL ALL UNUSED TAPS AND OPENINGS IN THE EXISTING DUCTWORK.
10. PROVIDE SCREWED ON ENGRAVED BLACK LAMICOLD SHEET NAMEPLATES
FOR EQUIPMENT, INSTRUMENTS, GAUGES, CONTROL SWITCHES ETC.
A
54321
B
C
D
E
F
SCALE
APPROVED BY
CHECKED BY
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
REVISIONS
SEAL
KEY PLAN
Dewberry Architects Inc.
132 North York Street Suite 2C Elmhurst, IL 60126-3079 309.282.8000
IL DESIGN FIRM #184000358-0001
/2
/2
:0
:4
A
M
MECHANICAL
SYMBOLS,
ABBREVIATIONS
& NOTES
KHH
JRF
KHH
02/12/2026
50190534
B L
O O
M
IN
G T
O N
F
IR
E S
T A
T
IO
N
K
IT
C
H E
N R
E M
O D
E L
B L O
O M
IN
G
T O
N F
IR
E
D
IS
T R
IC
T
IS
S
U E
F O
R P
E R
M
IT
B
ID
S
M O
R R
IS
A
V E
B L O
O M
IN
G
T O
N
IL
L
IN
O
IS
M-001
ABBREVIATIONS - MECHANICAL
(D) DEMOLISH
(E) EXISTING
(R) REMOVE
ADJ ADJUSTABLE
AF AIRFLOW
ARCH ARCHITECTURAL
CONN CONNECTION
CONT CONTROLS
DIA DIAMETER
DN DOWN
DWG DRAWING
DWH DOMESTIC WATER HEATER
EA EXHAUST AIR
EF EXHAUST FAN
ELEC ELECTRICAL
ESP EXTERNAL STATIC PRESSURE
ETC ETCETERA
F DEGREES FAHRENHEIT
FLA FULL LOAD AMPS
FP FAN POWERED
GC GENERAL CONTRACTOR
HP HORSEPOWER
IN INCH
KEF KITCHEN EXHAUST FAN
MCA MINIMUM CIRCUIT AMPS
MFGR MANUFACTURER
MOCP MAXIMUM OVERCURRENT PROTECTION
N NEW OR NORTH
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OS OCCUPANCY SENSOR
P/I PROVIDE AND INSTALL
PD PRESSURE DROP
QTY QUANTITY
SP STATIC PRESSURE
TYP TYPICAL
V OR VOLT VOLTAGE
VEL VELOCITY
VF VENTILATION FAN
W WIDTH OR WATTS
NO. DESCRIPTION DATE
75% Construction Documents 02/04/26
95% Construction Documents 02/09/26
ISSUE FOR COST ESTIMATE 02/12/26
1 ISSUE FOR PERMIT & BID 02/23/26
SS IOE NFO ALR P E ND GE IS NN EE EC RI L 062.077973
KRISTIE HAINES
DATE: 02/23/2026
EXP: 11/30/2027
KH
6ø 1
2 3
KITCHEN RANGE HOOD SCHEDULE
TAG KITCHEN…