1. Does the facility require to be built by exact dimensions of the desired slab location. The slab measures 10x 24. Answer No as long as we can accommodate the equipment planned for installation we can alter the recommended dimensions. 2. You have required a 12X20 as part of the SOW. Can we supply a 10X20 and still meet your interior space requirements. Answer 10'x20' should work well. The clean room will contain the following pieces of equipment (a) Dual Drawdown Table 48 W x 58 H x 49 D (b) Two.