UPS

Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications.

APPLICATIONS

• DataCenters
• NetworkOperationsCenters
• IndustrialProcessControlFacilities
• InternetHousingSites
• SemiconductorManufacturing
• Banks&FinancialMarkets
• PowerGenerationPlants
• Hospitals&TestingLaboratories
• Emergency911ResponseCenters
• 10yeardesignlife@25˚C
• AbsorbentGlassMat(AGM)technology
forefficientgasrecombinationofup
to99%andfreedomfromelectrolyte

maintenance.

• PatentedLongLifeAlloyhavingthe
lowestcalciumlevelsintheindustry-
minimizinggridgrowth,reducinggassing,

and extending battery life.

• PatentedULRecognizedFlame-
arrestingventsineachcellforsafetyand

long life.

• Designedwiththesamerecombination,
thermalrunawayprevention,gassing
andflameretardantcharacteristicsofthe
Bellcore4228compliantDynastyTelecom

products.

• Flameretardantpolypropylenecaseand
covercompliantwithUL94-V2
• Thermallyweldedcase-to-coverbondto
eliminateleakage.
• Canbeoperatedinanyorientation.
Upright,sideorendmounting

recommended.

• Notrestrictedforairtransport-Complies
withIATA/ICAOSpecialProvisionsA67.
• Notrestrictedforsurfacetransport-
Classifiedasnon-hazardousmaterial
asrelatedtoDOT-CFRTitle49parts

171-189.

• Notrestrictedforwatertransport-
Classifiedasnon-hazardousmaterialper
IMDGAmendment27.

* Nominal 20 hr rate to 1.75 VPC in Ampere-Hours.

FEATURES & BENEFITS

TECHNICAL DATA

Voltage AH

20 hr*

Constant Power Discharge Ratings - Watts per Cell @ +77°F (+25°C) Weight

Operating Time (in minutes) to 1.67 Volts per Cell 5 10 15 20 30 40 50 60 90 lbs kg

12 26.0 172 117 90.9 75.4 57.2 46.5 39.3 34.1 24.6 21.0 10.0 12 34.6 290 193 148 120 88.9 71.1 59.4 51.1 36.1 27.3 12.4 12 53.8 373 261 206 169 127 102 85.1 73.3 51.9 40.0 18.0 12 78.6 546 385 300 245 183 147 123 106 75.0 58.4 26.5 12 93.2 619 440 350 289 216 173 144 123 85.9 67.4 30.5 12 103 716 506 400 328 244 195 162 139 97.2 75.8 34.4 12 141.2 771 593 488 411 317 258 218 189 135 100.0 45.0 12 149 875 657 537 451 343 277 231 198 139 100.0 45.0 6 199 938 747 620 530 410 335 283 245 174 72.0 33.0

E

B

A

D

C

F

.3

.8

0.25 6.42

0.64 16.18

0.18 4.67

0.50 12.62

.2

.5

.5

.7

1/4-20 UNC

.3

.6

.1

.1

1.13 28.70

1/4-20 UNC

3.50 89.0

.7

.0

.1

.1

1/4-20 UNC

.3

.3

1.22 31.10

.1

.1

1/4-20 UNC

.3

.3

1.22 31.10

.1

.1

1/4-20 UNC

.3

.7

0.98 24.9

.1

.2

Battery Termination

A B C D E F

6.54 (166.2)

6.45 (163.7)

5.17 (131.3)

5.07 (128.8)

6.37 (161.7)

6.86 (174.3)

7.76 (197.1)

7.54 (191.4)

5.19 (131.9)

5.02 (127.6)

6.52 (165.7)

6.80 (172.7)

9.0 (228.6)

8.86 (225.1)

5.48 (139.2)

5.31 (134.8)

7.89 (200.3)

8.07 (205.1)

10.27 (260.9)

10.17 (258.4)

6.83 (173.4)

6.65 (168.9)

7.89 (200.3)

8.01 (203.5)

12.04 (305.8)

11.95 (303.5)

6.83 (173.4)

6.65 (168.9)

7.94 (201.6)

8.06 (204.8)

13.42 (340.9)

12.75 (323.7)

6.80 (172.7)

6.54 (166.0)

8.40 (213.2)

8.52 (216.4)

13.57 (344.7)

12.74 (323.6)

6.80 (172.7)

6.63 (168.4)

10.81 (274.5)

10.93 (277.7)

12.63 (320.8)

12.51 (317.8)

6.97 (177.0)

6.83 (173.4)

8.82 (224.0)

8.94 (227.2)

.6

.6

0.75 19.0

.1

.7

#10-32 UNF

.6

.1

0.87 22.2

.1

.7

#10-32 UNF

Operating Temperature Range with temperature compensation

Discharge:-40˚F(-40˚C)to+160˚F(+71˚C)
Charge:-10˚F(-23˚C)to+140˚F(+60˚C)

Nominal Operating Temperature Range +74˚F (23˚C) to +80˚F (27˚C)

Recommended Maximum Charging Current Limit C20/5 amperes @ 20hr rate

Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit (6.75 to 6.90 per 6V unit)

Maximum AC Ripple (Charger) 0.5%RMSor1.5%P-Poffloatchargevoltagerecommendedforbestresults.
Maxvoltageallowed=1.4%RMS(4%P-P)Maxcurrentallowed=C/20@20hr.rate
Self Discharge Batterycanbestoredupto6monthsat77°F(25°C)beforeafresheningchargeisrequired.
Batteriesstoredattemperaturesgreaterthan77°F(25°C)willrequirerechargesoonerthan
batteriesstoredatlowertemperatures.Self-DischargeandInventoryControlfordetails.

Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77˚F (25˚C) (7.20 to 7.40 VDC per 6V unit.)

Terminal: Flag 0.22 in. clearance hole to accept 0.1875 in. or 10-32 bolt

Terminal: Inserted Threaded copper alloy insert terminal to accept 10-32 UNF bolt 1⁄4-20 UNC bolt

Terminal Hardware Annual Retorque 32 in.-lbs (3.48 N-m) (UPS12-100MR)

Terminal Hardware Initial Torque:

Inserted Terminal

40in.-lbs.(4.5N-m)
30in.-lbs.(3.4N-m
110in.-lbs.(12.4N-m)

SPECIFICATIONS

DIMENSIONS

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 157 114 87.5 72.1 54.9 45.0 41.5 38.5 33.7 24.0

1.70 168 115 89.6 74.4 56.5 46.0 42.1 38.9 33.8 24.4

1.67 172 117 90.9 75.4 57.2 46.5 42.6 39.3 34.1 24.6

1.65 174 118 91.5 75.9 57.6 46.9 42.9 39.7 34.5 24.8

1.60 179 119 92.5 76.8 58.3 47.4 43.4 40.1 34.8 25.0

End Point

Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

.083 .25 .5 .75 1 2 3 5 8 10 12 20 24 72 100

1.90 50.8 32.9 32.9 17.1 13.8 8.29 6.04 3.95 2.61 2.15 1.82 1.14 0.96 0.34 0.24

1.85 63.2 38.1 38.1 18.6 15.0 8.99 6.56 4.30 2.84 2.33 1.98 1.24 1.05 0.37 0.26

1.80 71.8 41.6 41.6 20.3 16.1 9.42 6.83 4.46 2.95 2.42 2.05 1.28 1.08 0.38 0.27

1.75 85.5 45.7 45.7 21.4 17.0 9.74 6.99 4.54 3.00 2.45 2.08 1.30 1.10 0.39 0.28

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 273 182 140 115 85.7 68.8 62.7 57.6 49.7 35.0

1.70 284 188 144 117 87.1 69.8 63.6 58.4 50.3 35.7

1.67 290 193 148 120 88.9 71.1 64.7 59.4 51.1 36.1

1.65 294 196 149 122 90.0 71.8 65.3 60.0 51.5 36.4

1.60 297 200 152 124 91.0 72.5 65.9 60.5 51.9 36.6

End Point Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

1 2 3 5 8 10 12 20 24 72

1.85 22.8 13.0 9.08 5.70 3.76 3.10 2.64 1.64 1.38 0.47

1.80 24.2 13.6 9.46 5.91 3.90 3.21 2.72 1.69 1.41 0.48

1.75 25.4 14.1 9.80 6.11 4.00 3.28 2.79 1.73 1.45 0.49

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 341 243 193 162 123 99.0 90.3 83.0 71.5 50.6

1.70 366 253 200 166 125 100 91.1 83.6 71.8 50.4

1.67 373 261 206 169 127 102 92.6 85.1 73.3 51.9

1.65 378 262 205 170 128 102 93.3 85.7 73.8 52.1

1.60 391 265 207 172 129 103 94.0 86.3 74.2 52.3

End Point Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

1 2 3 5 8 10 12 20 24 72

1.85 32.6 19.1 13.6 8.68 5.79 4.72 4.01 2.51 2.12 0.73

1.80 34.8 20.3 14.4 9.20 6.12 5.00 4.24 2.65 2.23 0.76

1.75 36.7 21.1 19.9 9.43 6.25 5.05 4.28 2.69 2.27 0.77

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 493 360 281 232 175 141 129 119 103 73.5

1.70 525 379 293 240 179 144 131 120 104 74.0

1.67 546 385 300 245 183 147 134 123 106 75.0

1.65 564 395 302 247 183 147 134 124 107 76.2

1.60 579 402 306 250 186 150 137 126 109 77.7

End Point Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

1 2 3 5 8 10 12 20 24 72

1.85 48.3 28.1 19.9 12.6 8.36 6.82 5.79 3.62 3.05 1.05

1.80 51.1 29.3 20.7 13.1 8.84 7.23 6.13 3.83 3.22 1.08

1.75 52.7 30.1 21.2 13.4 9.16 7.46 6.32 3.93 3.30 1.10

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 534 410 327 272 205 165 150 138 119 84.3

1.70 596 425 337 280 211 169 154 141 121 84.9

1.67 619 440 350 289 216 173 157 144 123 85.9

1.65 638 455 358 296 220 175 159 145 124 86.5

1.60 669 471 367 302 223 177 161 147 126 87.6

End Point Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

1 2 3 5 8 10 12 20 24 72

1.85 53.0 31.8 22.9 14.8 10.6 8.73 7.38 4.56 3.84 1.29

1.80 58.8 34.5 24.6 15.7 10.1 8.35 7.09 4.39 3.69 1.32

1.75 62.6 36.3 25.8 16.4 11.0 8.98 7.57 4.66 3.92 1.34

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 612 470 374 310 232 186 169 155 134 94.7

1.70 678 490 388 323 241 193 176 161 138 96.6

1.67 716 506 400 328 244 195 177 162 139 97.2

1.65 740 515 403 332 247 197 179 164 140 98.1

1.60 767 530 411 337 249 199 180 165 140 99.2

End Point Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

1 2 3 5 8 10 12 20 24 72

1.85 56.2 33.7 24.4 15.7 10.8 8.85 7.56 4.8 4.06 1.38

1.80 62.1 36.5 26.1 16.7 11.4 9.38 8.00 5.03 4.23 1.43

1.75 67.9 39.2 27.8 17.6 11.9 9.73 8.26 5.17 4.35 1.46

Model Cells per Unit

Maximum Discharge Current (AMPS)

Short Circuit Current (AMPS @ 0.1 sec)

Ohms Impedance 60 Hz (Ω)

6 500 1750 0.0060

6 500 2500 0.0060

6 600 3000 0.0045

6 800 3600 0.0040

6 800 4200 0.0030

6 800 5100 0.0025

6 800 5000 0.0023

6 800 5000 0.0023

3 800 4350 0.0012

SPECIFICATIONS

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 655 527 443 382 300 247 227 210 183 132

1.70 740 573 470 400 310 253 233 215 187 134

1.67 771 593 488 411 317 258 237 218 189 135

1.65 799 614 497 419 321 261 239 220 191 137

1.60 838 640 513 429 325 264 241 222 193 138

End Point Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

1 2 3 5 8 10 12 20 24 72

1.85 80.8 48.4 34.8 22.4 15.0 12.3 10.5 6.66 5.64 1.93

1.80 86.4 51.3 36.7 23.4 15.6 12.7 10.8 6.88 5.82 1.99

1.75 91.0 53.5 38.2 24.4 16.2 13.1 11.1 7.06 5.98 2.03

End Point Volts/Cell

Constant Power Discharge Ratings - Watts Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in minutes)

5 10 15 20 30 40 45 50 60 90

1.75 728 564 471 406 318 261 239 221 191 136

1.70 833 626 511 433 332 269 246 226 195 138

1.67 875 657 537 451 343 277 252 231 198 139

1.65 912 683 550 462 349 280 255 234 201 141

1.60 959 701 560 468 353 283 258 237 203 143

End Point Volts/Cell

Constant Current Discharge Ratings - Amps Per Cell @ +77°F (+25°C) Operating Time to End Point Voltage (in hours)

1 2 3 5 8 10 12 20 24 72

1.85 82.7 49.5 35.6 22.9 15.0 12.6 10.9 7.05 5.98 2.00

1.80 89.6 53.1 38.1 24.4 15.9 13.2 11.3 7.29 6.18 2.07

1.75 98.9 57.0 40.3 25.5 16.5 13.6 11.7 7.46 6.31 2.11