The document is an electrical design drawing for a fire alarm system replacement project at Offutt Air Force Base. The solicitation (FA460025Q0056) involves replacing fire alarm control panels and devices in three buildings (Buildings 123, 441, and 584) with specific equipment requirements. The project involves removing existing faulty panels and installing new Notifier NFS-320 and Simplex 4007 fire alarm control panels with associated devices, including testing and documentation.
Key dates include a site visit on 24 July 2025 at 1300 CST, with questions due by 30 July 2025 at 1:00 PM CST. The offer submission deadline is 06 August 2025 at 10:00 AM CST. The solicitation notes that funds are not currently available, and the government reserves the right to cancel the solicitation. Contact points are SrA Javier Contreras and Casey Hupton from the Department of the Air Force Air Combat Command. The project requires careful preparation, equipment installation, system testing, and comprehensive documentation of the fire alarm system upgrades.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text
AutoCAD SHX Text
LEGEND, ABBREVIATIONS,
AutoCAD SHX Text
ELECTRICAL SYMBOLS
AutoCAD SHX Text
ELECTRICAL ABBREVIATIONS AND SYMBOLS LEGEND
AutoCAD SHX Text
ABBREVIATIONS
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text
AFF
AutoCAD SHX Text
LIGHTING
AutoCAD SHX Text
SUBSCRIPT 'E' ADJACENT TO ANY DEVICE INDICATES EXISTING.
AutoCAD SHX Text E
AutoCAD SHX Text
(ER)
AutoCAD SHX Text
ELECTRIC WATER COOLER
AutoCAD SHX Text
EWC
AutoCAD SHX Text
GROUND FAULT INTERRUPTER
AutoCAD SHX Text
GFI
AutoCAD SHX Text
EXISTING TO BE RELOCATED.
AutoCAD SHX Text
SUBSCRIPT (ER) ADJACENT TO ANY DEVICE INDICATES
AutoCAD SHX Text
HAND-OFF-AUTO
AutoCAD SHX Text
HOA
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
HT
AutoCAD SHX Text
MANUFACTURED
AutoCAD SHX Text
MFD
AutoCAD SHX Text
MANUFACTURING
AutoCAD SHX Text
MFG
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MFR
AutoCAD SHX Text
MOUNT
AutoCAD SHX Text
MT
AutoCAD SHX Text
MOUNTING
AutoCAD SHX Text
MTG
AutoCAD SHX Text
MOUNTED
AutoCAD SHX Text
MTD
AutoCAD SHX Text
NON-FUSED
AutoCAD SHX Text
NF
AutoCAD SHX Text
OVERHEAD ELECTRICAL
AutoCAD SHX Text
OHE
AutoCAD SHX Text
PUSHBUTTON
AutoCAD SHX Text
PS
AutoCAD SHX Text
POLYVINYL CHLORIDE
AutoCAD SHX Text
PVC
AutoCAD SHX Text
SUBSCRIPT (R) ADJACENT TO ANY DEVICE INDICATES THE
AutoCAD SHX Text (R)
AutoCAD SHX Text
RIGID GALVANIZED STEEL
AutoCAD SHX Text
RGS
AutoCAD SHX Text
RELOCATED POSITION OF AN EXISTING DEVICE.
AutoCAD SHX Text
BREAKER
AutoCAD SHX Text
BKR
AutoCAD SHX Text
TELEPHONE TERMINAL BOARD
AutoCAD SHX Text
TTB
AutoCAD SHX Text
TELEPHONE TERMINAL CABINET
AutoCAD SHX Text
TTC
AutoCAD SHX Text
UNDERGROUND ELECTRICAL
AutoCAD SHX Text
UGE
AutoCAD SHX Text
UNDERGROUND TELEPHONE
AutoCAD SHX Text
UGT
AutoCAD SHX Text
WEATHERPROOF
AutoCAD SHX Text
WP
AutoCAD SHX Text
CROSS-HATCHING INDICATES REMOVAL
AutoCAD SHX Text
ELECTRICAL DISTRIBUTION
AutoCAD SHX Text
ELECTRICAL DISTRIBUTION
AutoCAD SHX Text
MOTOR CONTROL & MOTOR
AutoCAD SHX Text
SPECIAL SYSTEMS
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
CONTROL EQUIPMENT
AutoCAD SHX Text
2' X 4' FLUORESCENT TROFFER. LETTER DENOTES FIXTURE TYPE.
AutoCAD SHX Text
1' X 4' FLUORESCENT TROFFER. LETTER DENOTES FIXTURE TYPE.
AutoCAD SHX Text J
AutoCAD SHX Text
FIXTURE MOUNTING HEIGHT.
AutoCAD SHX Text
LETTER/NUMBER DENOTES FIXTURE TYPE. REFER TO DRAWINGS FOR
AutoCAD SHX Text
1' X 4' SURFACE OR PENDANT MOUNTED FLUORESCENT FIXTURE.
AutoCAD SHX Text J
AutoCAD SHX Text
TYPE. REFER TO DRAWINGS FOR FIXTURE MOUNTING HEIGHT.
AutoCAD SHX Text
WALL MOUNTED FLUORESCENT FIXTURE. LETTER/NUMBER DENOTES FIXTURE
AutoCAD SHX Text J
AutoCAD SHX Text
FLUORESCENT STRIP FIXTURE. LETTER DENOTES FIXTURE TYPE. REFER
AutoCAD SHX Text
TO DRAWINGS FOR FIXTURE MOUNTING HEIGHT.
AutoCAD SHX Text
RECESSED, SURFACE OR PENDANT MOUNTED FLUORESCENT, H.I.D. OR
AutoCAD SHX Text
INCANDESCENT FIXTURE. LETTER DENOTES FIXTURE TYPE. REFER TO
AutoCAD SHX Text
DRAWINGS FOR MOUNTING DETAILS AND MOUNTING HEIGHT.
AutoCAD SHX Text
BATTERY POWERED EMERGENCY LIGHT FIXTURE. REFER TO FIXTURE
AutoCAD SHX Text
SCHEDULE ON DRAWINGS FOR FIXTURE TYPE. REFER TO DRAWINGS FOR
AutoCAD SHX Text
FIXTURE MOUNTING HEIGHT.
AutoCAD SHX Text
WALL MOUNTED EXIT SIGN. PROVIDE DIRECTIONAL ARROWS AS SHOWN
AutoCAD SHX Text
ON DRAWINGS. REFER TO FIXTURE SCHEDULE FOR FIXTURE TYPE. REFER
AutoCAD SHX Text
TO DRAWINGS FOR MOUNTING HEIGHT. (DARKENED PORTION OF FIXTURE
AutoCAD SHX Text
INDICATES ILLUMINATED FACES.)
AutoCAD SHX Text
CEILING MOUNTED EXIT SIGN. PROVIDE DIRECTIONAL ARROWS AS SHOWN
AutoCAD SHX Text
ON DRAWINGS. REFER TO FIXTURE SCHEDULE FOR FIXTURE TYPE.
AutoCAD SHX Text
(DARKENED PORTION OF FIXTURE INDICATES ILLUMINATED FACES.)
AutoCAD SHX Text
LETTER DENOTES FIXTURE TYPE. REFER TO DRAWING FOR MOUNTING HEIGHT.
AutoCAD SHX Text
WALL MOUNTED FLUORESCENT, H.I.D. OR INCANDESCENT FIXTURE.
AutoCAD SHX Text S
AutoCAD SHX Text
SINGLE POLE SWITCH
AutoCAD SHX Text
THREE WAY SWITCH
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
DIMMER SWITCH
AutoCAD SHX Text D
AutoCAD SHX Text S
AutoCAD SHX Text
MOTION DETECTOR SWITCH
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text
THERMAL ELEMENT SWITCH
AutoCAD SHX Text
TE
AutoCAD SHX Text S
AutoCAD SHX Text
20A, 125V DOUBLE DUPLEX CONVENIENCE OUTLET (NEMA 5 - 20R)
AutoCAD SHX Text
20A, 125V DUPLEX CONVENIENCE OUTLET (NEMA 5 - 20R)
AutoCAD SHX Text
20A, 125V DUPLEX CONVENIENCE OUTLET - CEILING AND FLOOR
AutoCAD SHX Text
PIGTAIL DENOTES CONNECTION TO EQUIPMENT
AutoCAD SHX Text
JUNCTION BOX - CEILING, FLOOR, AND WALL MOUNTING
AutoCAD SHX Text
DATA OUTLET AND COVERPLATE, FLUSH MOUNTED AT 18" AFF
AutoCAD SHX Text
TELEPHONE OUTLET AND COVERPLATE, FLUSH MOUNTED AT 18" AFF
AutoCAD SHX Text C
AutoCAD SHX Text F
AutoCAD SHX Text C
AutoCAD SHX Text F
AutoCAD SHX Text
SPECIAL PURPOSE OUTLET, TYPE AS NOTED ON DRAWINGS
AutoCAD SHX Text
MOUNTED (NEMA 5 - 20R)
AutoCAD SHX Text D
AutoCAD SHX Text
TELEPHONE TERMINAL BOARD OR TERMINAL CABINET - SIZE AND TYPE
AutoCAD SHX Text
AS INDICATED (TTB OR TTC).
AutoCAD SHX Text
BRANCH CIRCUIT HOMERUN TO PANEL (NUMBER OF ARROWS INDICATES
AutoCAD SHX Text
NUMBER OF CIRCUITS. NUMBER OF TICK MARKS INDICATES NUMBER OF WIRES)
AutoCAD SHX Text
(NUMBER 12AWG, MINIMUM, UNLESS OTHERWISE NOTED). IF NO TICK MARKS
AutoCAD SHX Text
ARE SHOWN, ASSUME 3- NUMBER 12 AWG IN 1/2" CONDUIT.
AutoCAD SHX Text
CONDUIT AND WIRE CONCEALED. NUMBER OF TICK MARKS INDICATES
AutoCAD SHX Text
NUMBER OF WIRES (NUMBER 12AWG MINIMUM, UNLESS OTHERWISE NOTED) IF
AutoCAD SHX Text
NO TICK MARKS ARE SHOWN, ASSUME 3-NUMBER 12 IN 1/2" CONDUIT.
AutoCAD SHX Text
CONDUIT RISER UP
AutoCAD SHX Text
CONDUIT RISER DOWN
AutoCAD SHX Text
INDICATES BUSH AND CAP
AutoCAD SHX Text
CONDUIT SEAL FITTING FOR HAZARDOUTS AREAS
AutoCAD SHX Text
CONDUIT STUBBED UP 6" AFF AND CAPPED
AutoCAD SHX Text
LIGHTING AND APPLIANCE PANEL
AutoCAD SHX Text
MOTOR CONTROL CENTER OR SWITCHBOARD
AutoCAD SHX Text
POWER PANEL (DISTRIBUTION TYPE)
AutoCAD SHX Text
TRANSFORMER
AutoCAD SHX Text T
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
FUSIBLE SWITCH
AutoCAD SHX Text M
AutoCAD SHX Text
ELECTRONIC KWH/DEMAND METER. SEE DRAWINGS AND SPECIFICATIONS
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
MOTOR - HORSEPOWER AS INDICATED ON DRAWINGS
AutoCAD SHX Text
NON-FUSED DISCONNECT SWITCH, ASSUME 30A/3P UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
FUSED DISCONNECT SWITCH, FUSE SIZE AS NOTED ON DRAWINGS, ASSUME
AutoCAD SHX Text
30A/3P UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
COMBINATION FVNR MAGNETIC MOTOR STARTER WITH HOA SELECTOR
AutoCAD SHX Text
SWITCH AND NON-FUSED DISCONNECT SWITCH, ASSUME NEMA SIZE 1 STARTER
AutoCAD SHX Text
AND 30A/3P SWITCH UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
COMBINATION FVNR MAGNETIC MOTOR STARTER WITH HOA SELECTOR SWITCH
AutoCAD SHX Text
AND FUSED DISCONNECT SWITCH, ASSUME NEMA SIZE 1 STARTER AND 30A/3P
AutoCAD SHX Text
SWITCH UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
FVNR MAGNETIC MOTOR STARTER WITH HOA SELECTOR SWITCH, ASSUME NEMA
AutoCAD SHX Text
SIZE 1 STARTER UNLESS OTHERWISE NOTED.
AutoCAD SHX Text
HAND-OFF-AUTO SELECTOR SWITCH
AutoCAD SHX Text H.O.A.
AutoCAD SHX Text
START/STOP PUSH BUTTON
AutoCAD SHX Text
3 POSITION PUSH BUTTON
AutoCAD SHX Text
CONTROL PANEL - INTEGRAL PART OF OR FURNISHED WITH
AutoCAD SHX Text
DESIGNATED EQUIPMENT
AutoCAD SHX Text
LOCK-OUT PUSH BUTTON
AutoCAD SHX Text
FIRE ALARM MANUAL PULL STATION
AutoCAD SHX Text
FIRE ALARM HORN/STROBE UNIT
AutoCAD SHX Text
FIRE ALARM BELL
AutoCAD SHX Text
FIRE ALARM FLASHING STROBE LIGHT
AutoCAD SHX Text
FIRE ALARM COMBINATION BELL AND FLASHING LIGHT
AutoCAD SHX Text
POST SUPERVISORY VALVE CONTACTS
AutoCAD SHX Text
SUPERVISORY VALVE CONTACTS
AutoCAD SHX Text
WATER FLOW SWITCH
AutoCAD SHX Text
COMBINATION DETECTOR/DOOR HOLD OPEN DEVICE
AutoCAD SHX Text
SMOKE DETECTOR
AutoCAD SHX Text
HEAT DETECTOR - COMBINATION RATE OF RISE AND FIXED TEMPERATURE
AutoCAD SHX Text
DUCT SMOKE DETECTOR
AutoCAD SHX Text
FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
FIRE ALARM TRANSFER PANEL
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text P
AutoCAD SHX Text S
AutoCAD SHX Text F
AutoCAD SHX Text
FS
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text D
AutoCAD SHX Text
FACP
AutoCAD SHX Text
FATP
AutoCAD SHX Text
VOLUME CONTROL FOR SPEAKER
AutoCAD SHX Text
SOUND DISTRIBUTION RACK
AutoCAD SHX Text
MICROPHONE
AutoCAD SHX Text
SDR
AutoCAD SHX Text
FIRE ALARM
AutoCAD SHX Text
FIRE ALARM HORN
AutoCAD SHX Text F
AutoCAD SHX Text B
AutoCAD SHX Text C
AutoCAD SHX Text G
AutoCAD SHX Text K
AutoCAD SHX Text L
AutoCAD SHX Text M
AutoCAD SHX Text M1
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text M
AutoCAD SHX Text
VC
AutoCAD SHX Text M
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
UNLESS OTHERWISE NOTED
AutoCAD SHX Text
PROJECT GENERAL NOTES
AutoCAD SHX Text
FOR TYPE.
AutoCAD SHX Text
GRND
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
EXISTING. THE LOCATIONS OF EXISTING EQUIPMENT AND DEVICES
AutoCAD SHX Text
WERE OBTAINED FROM PREVIOUS DRAWINGS AND SITE VISITS. THE
AutoCAD SHX Text
LOCATIONS OF EXISTING EQUIPMENT AND DEVICES ARE SHOWN FOR THE
AutoCAD SHX Text
CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE INFORMATION
AutoCAD SHX Text
VERIFICATION OF ALL EXISTING CONDITIONS PRIOR TO SUBMITTING
AutoCAD SHX Text
THE PROJECT BID. NO ADDITIONAL COMPENSATION WILL BE ALLOWED
AutoCAD SHX Text
FOR CHANGES WHICH OCCUR AFTER BIDS ARE SUBMITTED WHICH ARE
AutoCAD SHX Text
A RESULT OF EXISTING CONDITIONS. SITE VISITS PRIOR TO SUBMISSION
AutoCAD SHX Text
THE CONTRACTOR MUST FIELD VERIFY EXISTING CIRCUITING PRIOR
AutoCAD SHX Text
TO COMMENCING ANY WORK. ALL BIDS MUST INCORPORATE THIS
AutoCAD SHX Text
DEVICES SHOWN WITH CROSS HATCHING AND/OR SO NOTED SHALL
AutoCAD SHX Text
BE REMOVED. ALL OTHER DEVICES SHALL BE RELOCATED, SHALL
AutoCAD SHX Text
REMAIN, OR SHALL BE ABANDONED AS SHOWN, OR AS FOLLOWS:
AutoCAD SHX Text
DEVICES SHALL BE COMPLETELY REMOVED FROM WALLS
AutoCAD SHX Text
THAT ARE ALSO SHOWN TO BE REMOVED. DEVICES SHOWN
AutoCAD SHX Text
TO BE REMOVED ON DRYWALL OR PLASTER TYPE WALLS THAT
AutoCAD SHX Text
ARE TO REMAIN SHALL HAVE THE WALL SURFACE PATCHED TO
AutoCAD SHX Text
MATCH THE EXISTING FINISH. FLUSH TYPE DEVICES SHOWN TO BE
AutoCAD SHX Text
REMOVED ON CONCRETE OR BRICK TYPE WALLS THAT ARE TO
AutoCAD SHX Text
REMAIN SHALL HAVE THE DEVICES REMOVED AND BOXES
AutoCAD SHX Text
CONDUITS SHALL BE COMPLETELY REMOVED FROM WALLS THAT
AutoCAD SHX Text
ARE ALSO SHOWN TO BE REMOVED. CONCEALED CONDUITS MAY BE
AutoCAD SHX Text
AND BOXES THAT ARE SURFACE MOUNTED AND NO LONGER REQUIRE
AutoCAD SHX Text
THE CONDUCTORS FOR DEVICES SHOWN TO BE REMOVED SHALL BE
AutoCAD SHX Text
DISCONNECTED AND REMOVED BACK TO THE PANEL OR BACK TO
AutoCAD SHX Text
THE NEXT DEVICE SHOWN TO REMAIN OR AS REQUIRED BY ACTUAL
AutoCAD SHX Text
CIRCUITING. ACTUAL CIRCUITING MUST BE DETERMINED IN THE FIELD.
AutoCAD SHX Text
REFER TO ARCHITECTURAL DRAWINGS FOR WALL REMOVAL AND WALL
AutoCAD SHX Text
THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.
AutoCAD SHX Text
ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE
AutoCAD SHX Text
REMOVED FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR.
AutoCAD SHX Text
THE OWNER WILL OCCUPY PORTIONS OF THE FACILITY THROUGHOUT
AutoCAD SHX Text
CONSTRUCTION. ELECTRICAL SYSTEMS TO OCCUPIED PORTIONS OF THE
AutoCAD SHX Text
FACILITY MUST REMAIN IN OPERATION. THE ELECTRICAL CONTRACTOR
AutoCAD SHX Text
MUST COORDINATE ALL PHASING REQUIREMENTS WITH THE GENERAL
AutoCAD SHX Text
CONTRACTOR AND THE OWNER, AND MUST PROVIDE ALL NECESSARY
AutoCAD SHX Text
DEVICES, EQUIPMENT, WIRE, CONDUIT, AND CONNECTIONS TO ENSURE
AutoCAD SHX Text
PHASING AND OWNER OCCUPANCY REQUIREMENTS ARE SATISFIED. ALL
AutoCAD SHX Text
BIDS SHOULD INCORPORATE THIS REQUIREMENT. NO ADDITIONAL
AutoCAD SHX Text
COMPENSATION WILL BE ALLOWED FOR ISSUES AND CHANGES WHICH
AutoCAD SHX Text
ALL BIDS SHOULD INCORPORATE THIS REQUIREMENT. NO ADDITIONAL
AutoCAD SHX Text
COMPENSATION WILL BE ALLOWED FOR CHANGES WHICH OCCUR AS
AutoCAD SHX Text
A RESULT OF EXISTING CIRCUITING. CONTINUITY OF CIRCUITING SHALL
AutoCAD SHX Text
BE MAINTAINED FOR ALL EXISTING CIRCUITS AS REQUIRED. CONTRACTOR
AutoCAD SHX Text
SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT, DEVICES AND
AutoCAD SHX Text
CONNECTIONS TO ENSURE CIRCUIT CONTINUITY TO ALL NEW AND EXISTING
AutoCAD SHX Text
OCCUR AS A RESULT OF PHASING AND OWNER OCCUPANCY
AutoCAD SHX Text
REQUIREMENTS.
AutoCAD SHX Text 8.
AutoCAD SHX Text 7.
AutoCAD SHX Text 6.
AutoCAD SHX Text 5.
AutoCAD SHX Text 4.
AutoCAD SHX Text
EQUIPMENT.
AutoCAD SHX Text
TYPE.
AutoCAD SHX Text
PROVIDED WITH BLANK COVER PLATES.
AutoCAD SHX Text
ABANDONED IN WALLS THAT ARE TO REMAIN. ALL CONDUITS
AutoCAD SHX Text
ACTIVE CIRCUITS SHALL BE REMOVED.
AutoCAD SHX Text
GENERAL DEMOLITION NOTES:
AutoCAD SHX Text 3.
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
OF BIDS MUST BE FULLY COORDINATED WITH THE OWNER.
AutoCAD SHX Text
REQUIREMENT.
AutoCAD SHX Text
ALL OF THE DEVICES SHOWN ON THE DEMOLITION PLANS ARE
AutoCAD SHX Text
SHOWN IS NOT GUARANTEED. THE CONTRACTOR IS RESPONSIBLE FOR THE
AutoCAD SHX Text
UNLESS OTHERWISE NOTED. PATCH ALL EXISTING SURFACES AFTER
AutoCAD SHX Text
A DEDICATED NEUTRAL CONDUCTOR IS REQUIRED FOR ALL DIMMABLE
AutoCAD SHX Text
LAYOUT AND CIRCUITING TO REMAIN.
AutoCAD SHX Text
IN ROOMS WHERE NO FIXTURES ARE SHOWN, THE EXISTING LIGHTING
AutoCAD SHX Text
DEVICE INSTALLATION, AS REQUIRED. REFER TO THE PROJECT
AutoCAD SHX Text
SPECIFICATION FOR CUTTING AND PATCHING REQUIREMENTS. REFER
AutoCAD SHX Text
WHERE 3 LAMP OR 4 LAMP FLUORESCENT FIXTURES ARE SHOWN
AutoCAD SHX Text
WITHIN A ROOM OR AREA TO BE CONTROLLED BY TWO SWITCHES
AutoCAD SHX Text
(OR TWO SETS OF 3-WAY SWITCHES), CONNECT THE OUTSIDE LAMPS
AutoCAD SHX Text
OF EACH FIXTURE TO ONE SWITCH AND CONNECT THE INSIDE LAMP(S)
AutoCAD SHX Text
OF EACH FIXTURE TO THE SECOND SWITCH. SWITCH DESIGNATIONS
AutoCAD SHX Text
ARE SHOWN IN THESE ROOMS TO ASSIST THE CONTRACTOR IN THE
AutoCAD SHX Text
TO ARCHITECTURAL DRAWINGS FOR WALL TYPES.
AutoCAD SHX Text
COMPLETION OF THE WORK.
AutoCAD SHX Text
CIRCUITS.
AutoCAD SHX Text 9.
AutoCAD SHX Text 8.
AutoCAD SHX Text 7.
AutoCAD SHX Text
REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT
AutoCAD SHX Text
COORDINATE THE INSTALLATION OF ALL RECESSED LIGHTING FIXTURES
AutoCAD SHX Text
WITH ACTUAL CEILING TYPES. REFER TO ARCHITECTURAL FINISH
AutoCAD SHX Text
SUPPORT ALL RECESSED AND PENDANT MOUNTED FIXTURES FROM
AutoCAD SHX Text
STRUCTURE IN ACCORDANCE WITH APPLICABLE BUILDING CODE
AutoCAD SHX Text
ROUTE ALL WIRE AND CONDUIT CONCEALED UNLESS OTHERWISE
AutoCAD SHX Text
NOTED. PATCH ALL EXISTING SURFACES AFTER WIRE AND CONDUIT
AutoCAD SHX Text
INSTALLATION, AS REQUIRED. REFER TO THE SPECIFICATION FOR
AutoCAD SHX Text
CUTTING AND PATCHING REQUIRMENTS. ALL COSTS ASSOCIATED WITH
AutoCAD SHX Text
ABOVE REQUIREMENTS MUST BE INCLUDED IN THE PROJECT BID.
AutoCAD SHX Text
FLUSH MOUNT ALL NEW WIRING DEVICES IN NEW OR EXISTING SURFACES,
AutoCAD SHX Text
GENERAL LIGHTING NOTES:
AutoCAD SHX Text
LOCATION OF ALL CEILING MOUNTED DEVICES.
AutoCAD SHX Text
COORDINATE THE INSTALLATION OF LIGHTING FIXTURES
AutoCAD SHX Text
WITH ALL OTHER TRADES.
AutoCAD SHX Text
SCHEDULES FOR ADDITIONAL DETAILS.
AutoCAD SHX Text
REQUIREMENTS. SUSPENDED CEILING MOUNTING SYSTEMS SHALL
AutoCAD SHX Text 6.
AutoCAD SHX Text 5.
AutoCAD SHX Text 4.
AutoCAD SHX Text 3.
AutoCAD SHX Text 1.
AutoCAD SHX Text 2.
AutoCAD SHX Text
BOX AROUND RECESSED LIGHTING FIXTURES AS REQUIRED SO THAT
AutoCAD SHX Text
THERMAL INSULATION, ETC AND LIGHTING FIXTURES ARE MAINTAINED.
AutoCAD SHX Text
FULLY COORDINATE ALL REQURIEMENTS WITH THE GENERAL CONTRACTOR.
AutoCAD SHX Text
ALL CODE REQUIRED CLEARANCES BETWEEN COMBUSTIBLE MATERIALS,
AutoCAD SHX Text
TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
CEILINGS, AND FLOORS TO MAINTAIN CODE REQUIRED RATINGS. REFER
AutoCAD SHX Text
SEAL AROUND ALL CONDUIT AND CABLE PENETRATIONS THROUGH WALLS,
AutoCAD SHX Text
FULLY COORDINATE ALL REQUIREMENTS WITH THE GENERAL CONTRACTOR.
AutoCAD SHX Text
REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES AND RATINGS.
AutoCAD SHX Text
IN RATED CEILINGS SO ALL CODE REQUIRED RATINGS ARE MAINTAINED.
AutoCAD SHX Text
PROVIDE ENCLOSURES OVER RECESSED LIGHTING FIXTURES INSTALLED
AutoCAD SHX Text 10.
AutoCAD SHX Text 12.
AutoCAD SHX Text 11.
AutoCAD SHX Text
NOT BE USED TO SUPPORT FIXTURES OR RACEWAYS.
AutoCAD SHX Text
DISTRIBUTION OF OWNER FURNISHED TELEPHONE, DATA, AND SOUND
AutoCAD SHX Text
NECESSARY SLEEVES THROUGH WALLS AND FLOORS TO ALLOW FOR THE
AutoCAD SHX Text
IN ADDITION TO THOSE SHOWN ON THE DRAWINGS, PROVIDE ALL
AutoCAD SHX Text
LOADS. CAREFULLY REVIEW CIRCUITING TICK MARKS, AND PROVIDE
AutoCAD SHX Text
NEUTRAL AND GROUND CONDUCTORS, TO SERVE COMPUTER EQUIPMENT
AutoCAD SHX Text
MANY OF THE CIRCUITS SHOWN ARE PROVIDED WITH DEDICATED
AutoCAD SHX Text
REFER TO ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
WALLS, CEILINGS AND FLOORS TO MAINTAIN CODE REQUIRED RATINGS.
AutoCAD SHX Text
SEAL AROUND ALL CONDUIT AND CABLE PENETRATIONS THROUGH
AutoCAD SHX Text
SYSTEM CABLING. COORDINATE REQUIREMENTS WITH THE OWNER.
AutoCAD SHX Text
ALL NECESSARY CONDUCTORS.
AutoCAD SHX Text 7.
AutoCAD SHX Text 6.
AutoCAD SHX Text 5.
AutoCAD SHX Text
FULLY COORDINATE ALL REQUIREMENTS WITH THE MECHANICAL AND
AutoCAD SHX Text
AND CONTACTS TO ENSURE PROPER SYSTEM CONTROL FUNCTIONS.
AutoCAD SHX Text
CONTRACTOR, PROVIDE ALL NECESSARY AUXILIARY COMPONENTS
AutoCAD SHX Text
FOR ALL HVAC CONTROL DEVICES PROVIDED BY THE ELECTRICAL
AutoCAD SHX Text
CONTRACTOR.) COORDINATE DEVICE REQUIREMENTS WITH ACTUAL
AutoCAD SHX Text
EQUIPMENT. (CONTROL WIRING TO BE PROVIDED BY MECHANICAL
AutoCAD SHX Text
TO ENSURE SATISFACTORY OPERATION OF ALL SYSTEMS AND
AutoCAD SHX Text
DEVICES (I.E. STARTERS, SWITCHES, CONTACTS, ETC.) REQUIRED
AutoCAD SHX Text
THE MECHANICAL AND CONTROLS CONTRACTORS. PROVIDE ALL
AutoCAD SHX Text
FULLY COORDINATE THE LOCATION OF ALL HVAC EQUIPMENT WITH
AutoCAD SHX Text
INCLUDE PATCHING AND REFINISHING OF EXISTING SURFACES TO
AutoCAD SHX Text
FULLY COORDINATE INSTALLATION WITH EXISTING CONDITIONS, AND
AutoCAD SHX Text
MOUNTED AND ALL WIRE AND CONDUIT IS TO BE ROUTED CONCEALED.
AutoCAD SHX Text
UNLESS OTHERWISE NOTED, ELECTRICAL DEVICES ARE TO BE FLUSH
AutoCAD SHX Text
FULLY COORDINATE THE INSTALLATION OF ALL ELECTRICAL DEVICES
AutoCAD SHX Text
GENERAL POWER & AUXILIARY SYSTEMS NOTES:
AutoCAD SHX Text
CONTROLS CONTRACTORS.
AutoCAD SHX Text
ACCOMODATE THIS REQUIREMENT.
AutoCAD SHX Text
EQUIPMENT.
AutoCAD SHX Text 4.
AutoCAD SHX Text 3.
AutoCAD SHX Text
WITH THE WORK OF OTHER TRADES.
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
PROJECT GENERAL ELECTRICAL NOTES:
AutoCAD SHX Text E0.1
AutoCAD SHX Text
LOCATE PHOTOCELL DEVICES FOR CONTROL OF EXTERIOR LIGHTING
AutoCAD SHX Text
FIXTURES, ON THE ROOF AT A LOCATION WHICH CANNOT BE SEEN
AutoCAD SHX Text
FROM GRADE LEVEL.
AutoCAD SHX Text 13.
AutoCAD SHX Text Disposal and testing will be handled by Offutt AFB.
AutoCAD SHX Text PCBs unless the individual ballast says "No PCB".
AutoCAD SHX Text DOT packaging requirements of 1A2 a metal drum marked 1A2.
AutoCAD SHX Text to a main base location each time a packaged volume reaches or exceeds
AutoCAD SHX Text Environmental Flight, 294-4087.
AutoCAD SHX Text and each container will have provided hazardous waste label affixed
AutoCAD SHX Text packaging must be marked 4G.
AutoCAD SHX Text waste and will be containerized in original boxes or other fiberboard box
AutoCAD SHX Text Drums will be delivered to Offutt's 90-day storage facility (Bldg 457).
AutoCAD SHX Text Ballasts saying "No PCB" will be containerized separately from the rest.
AutoCAD SHX Text All ballasts will be handled, containerized, and treated as containing
AutoCAD SHX Text
10. All ballasts will be collected in an open top drum meeting
AutoCAD SHX Text 55 gallons, i.e., 3 boxes of 4 foot tubes in original containers.
AutoCAD SHX Text Boxes will be delivered as specified by the Contracting Officer
AutoCAD SHX Text to one end. Labels provided by 55 CES/CEVC, AutoCAD SHX Text Any openings and/or folded seams will be taped over with duct tape
AutoCAD SHX Text meeting Department of Transportation (DOT) 4G packing requirements, i.e., AutoCAD SHX Text
9. Fluorescent Light Tubes removed and discarded are a hazardous
AutoCAD SHX Text Air Force Base
AutoCAD SHX Text Offutt
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
COORDINATION
AutoCAD SHX Text
DESIGN FIRM
AutoCAD SHX Text Project Manager
AutoCAD SHX Text Date
AutoCAD SHX Text Designer
AutoCAD SHX Text Drafter
AutoCAD SHX Text
BY/DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text Facility Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text
ALTER / REPAIR
AutoCAD SHX Text
RENOVATE BAND
AutoCAD SHX Text
BLDG. 123
AutoCAD SHX Text
SGBP 94-0005 A3 (R)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GL
AutoCAD SHX Text
RS
AutoCAD SHX Text 9-6-95
AutoCAD SHX Text
AS
AutoCAD SHX Text
PHASE 3
OFF-B-5760
AutoCAD SHX Text
AND AUXILIARY SYSTEMS
AutoCAD SHX Text
FIRST FLOOR POWER & AUXILIARY SYSTEMS PLAN
AutoCAD SHX Text 8'
AutoCAD SHX Text 4'
AutoCAD SHX Text 2'
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
AutoCAD SHX Text
PLAN
AutoCAD SHX Text
FIRST FLOOR POWER
AutoCAD SHX Text E2.2
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text D
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text H
AutoCAD SHX Text +48"
AutoCAD SHX Text +48"
AutoCAD SHX Text
GFI
AutoCAD SHX Text F
AutoCAD SHX Text +48"
AutoCAD SHX Text F
AutoCAD SHX Text +48"
AutoCAD SHX Text
GFI
AutoCAD SHX Text H
AutoCAD SHX Text
GFI
AutoCAD SHX Text +48"
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
LB-10,12
AutoCAD SHX Text
LB-4
AutoCAD SHX Text
LB-6
AutoCAD SHX Text
LB-2
AutoCAD SHX Text
LB-12
AutoCAD SHX Text
LB-8,10,12
AutoCAD SHX Text
LB-18
AutoCAD SHX Text
LB-11
AutoCAD SHX Text L1-4
AutoCAD SHX Text L1-2,4,6
AutoCAD SHX Text L1-8
AutoCAD SHX Text
OUTLET LOCATIONS UNLESS
AutoCAD SHX Text
TYPICAL FOR ALL DATA/TELEPHONE
AutoCAD SHX Text
OTHERWISE NOTED
AutoCAD SHX Text
LB-7,9,11
AutoCAD SHX Text
LB-9,11
AutoCAD SHX Text L1-17
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
,TYPICAL FOR ALL TELEPHONE
AutoCAD SHX Text
OUTLET LOCATION UNLESS OTHERWISE
AutoCAD SHX Text
NOTED
AutoCAD SHX Text L1-20
AutoCAD SHX Text
AutoCAD SHX Text
FACP
AutoCAD SHX Text
AutoCAD SHX Text L1-6
AutoCAD SHX Text
FATP
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
STUB ABOVE ACCESSSIBLE CEILING. BUSH CONDUIT END.
AutoCAD SHX Text
ROUTE A 3/4" CONDUIT FROM TELEPHONE OUTLET BOX CONCEALED AND
AutoCAD SHX Text
END.
AutoCAD SHX Text
CONCEALED AND STUB ABOVE ACCESSIBLE CEILING. BUSH CONDUIT
AutoCAD SHX Text
ROUTE A 1" CONDUIT FROM TELEPHONE/DATA OUTLET BOX
AutoCAD SHX Text
HEIGHT TO TOP OF J-BOX SHALL BE 72".
AutoCAD SHX Text
24" X 24" X 6" SOUND SYSTEM J-BOX WITH HINGED DOOR. MOUNTING
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MECHANICAL CONTRACTOR.
AutoCAD SHX Text
ELECTRIC WATER HEATER. FULLY COORDINATE ALL REQUIREMENTS WITH
AutoCAD SHX Text
240VAC, 2 POLE, 60AMP, 100,000 AIC NON-FUSED DISCONNECT SWITCH FOR
AutoCAD SHX Text
MECHANICAL CONTRACTOR.
AutoCAD SHX Text
RECEPTACLE FOR WATER COOLER. FULLY COORDINATE REQUIREMENTS WITH
AutoCAD SHX Text
TO SOUND SYSTEM J-BOX IN STORAGE ROOM 102. FULLY COORDINATE THE
AutoCAD SHX Text
ROUTE 4 1/4" CONDUITS CONCEALED IN FLOOR CONCRETE FROM FLOOR BOX
AutoCAD SHX Text
AutoCAD SHX Text
MOUNT RECEPTACLE 6" ABOVE RAMP AT LOCATION SHOWN.
AutoCAD SHX Text
FLUSH ACCESS HATCH OR APPROVED EQUAL FOR MICROPHONE FLOOR BOXES.
AutoCAD SHX Text
FIRST FLOOR POWER & AUXILIARY SYSTEMS PLAN NOTES:
AutoCAD SHX Text
WALKER RFB4 MULTISERVICE STEEL RECESSED FLOOR BOX WITH RAKM11
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
2-#8 AND 1-#10 GRND IN 3/4" CONDUIT.
AutoCAD SHX Text
AT EACH LOCATION SHOWN, PROVIDE AND INSTALL A BLANK
AutoCAD SHX Text
INSTALLATION OF FLOOR BOXES WITH THE GENERAL CONTRACTOR AND
AutoCAD SHX Text
PROVIDE ALL NECESSARY ADJUSTMENTS FOR A FINISHED SYSTEM.
AutoCAD SHX Text
AT EACH LOCATION SHOWN, PROVIDE AND INSTALL A STEEL CITY CATALOG
AutoCAD SHX Text
CAT. NO. 664 CONCEALED SERVICE FLOOR BOX, OR APPROVED EQUAL, COMPLETE
AutoCAD SHX Text
WITH 2-20A, 125V DUPLEX RECEPTACLES AND 2 RECEPTACLE FACEPLATES
AutoCAD SHX Text
(CAT. NO. 664 RP). PROVIDE EACH FLOOR BOX WITH A CONCEALED SERVICE
AutoCAD SHX Text
TOP (CAT. NO. 664CST, COLOR AS DIRECTED BY CONTRACTING OFFICER). FULLY
AutoCAD SHX Text
COORDINATE THE INSTALLATION OF FLOOR BOXES WITH THE GENERAL CONTRACTOR
AutoCAD SHX Text
AND PROVIDE ALL NECESSARY ADJUSTMENTS FOR A FINISHED SYSTEM.
AutoCAD SHX Text
AutoCAD SHX Text
WORK NOT IN THIS CONTRACT (NIC)
AutoCAD SHX Text
WORK IN THIS CONTRACT
AutoCAD SHX Text
WORK BY PHASE 3
AutoCAD SHX Text
WORK BY PHASE 2
AutoCAD SHX Text
SEE ARCHITECTURAL GENERAL NOTES FOR DESCRIPTION
AutoCAD SHX Text
THIS PROJECT IS PHASE 3 OF A THREE PHASE PROJECT.
AutoCAD SHX Text
OF WORK WHICH IS INCLUDED IN THIS PHASE.
AutoCAD SHX Text
AA
AutoCAD SHX Text F
AutoCAD SHX Text
AA
AutoCAD SHX Text
AA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text
AA
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AutoCAD SHX Text M
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
%%UPRACTICE ROOM
AutoCAD SHX Text
%%ULOBBY
AutoCAD SHX Text
%%UFOYER
AutoCAD SHX Text
%%UCLOSET
AutoCAD SHX Text
MEN'S
AutoCAD SHX Text
%%UTOILET
AutoCAD SHX Text
%%USTORAGE
AutoCAD SHX Text
%%UTOILET
AutoCAD SHX Text
WOMEN'S
AutoCAD SHX Text
JANITOR
AutoCAD SHX Text
UP
AutoCAD SHX Text
%%UALCOVE
AutoCAD SHX Text
%%UCOATS
AutoCAD SHX Text
%%UOFFICE
AutoCAD SHX Text
%%USTORAGE
AutoCAD SHX Text
RAMP DOWN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UAUDITORIUM
AutoCAD SHX Text
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text Air Force Base
AutoCAD SHX Text Offutt
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
COORDINATION
AutoCAD SHX Text
DESIGN FIRM
AutoCAD SHX Text Project Manager
AutoCAD SHX Text Date
AutoCAD SHX Text Designer
AutoCAD SHX Text Drafter
AutoCAD SHX Text
BY/DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text Facility Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text
ALTER / REPAIR
AutoCAD SHX Text
RENOVATE BAND
AutoCAD SHX Text
BLDG. 123
AutoCAD SHX Text
SGBP 94-0005 A3 (R)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GL
AutoCAD SHX Text
RS
AutoCAD SHX Text 9-6-95
AutoCAD SHX Text
AS
AutoCAD SHX Text
PHASE 3
AutoCAD SHX Text
AND AUXILIARY SYSTEMS
AutoCAD SHX Text
SECOND FLOOR POWER
AutoCAD SHX Text
SECOND FLOOR POWER & AUXILIARY SYSTEMS PLAN
AutoCAD SHX Text 8'
AutoCAD SHX Text 4'
AutoCAD SHX Text 2'
AutoCAD SHX Text
SCALE
AutoCAD SHX Text
AutoCAD SHX Text
PLAN
AutoCAD SHX Text E2.3
AutoCAD SHX Text
AutoCAD SHX Text +48"
AutoCAD SHX Text
AutoCAD SHX Text +48"
AutoCAD SHX Text L1-14,16,18
AutoCAD SHX Text L1-15
AutoCAD SHX Text L1-13,15
AutoCAD SHX Text L1-18
AutoCAD SHX Text L1-16
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text
TE
AutoCAD SHX Text S
AutoCAD SHX Text
TE
AutoCAD SHX Text M
AutoCAD SHX Text L1-22
AutoCAD SHX Text L1-23
AutoCAD SHX Text
AutoCAD SHX Text
, TYPICAL FOR ALL
AutoCAD SHX Text
TELEPHONE OUTLET
AutoCAD SHX Text
LOCATIONS UNLESS
AutoCAD SHX Text
OTHERWISE NOTED.
AutoCAD SHX Text
%%UFVBR 6.2
AutoCAD SHX Text
%%UEF-1
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text
%%UFVBR 12.2
AutoCAD SHX Text L1-21
AutoCAD SHX Text L1-24
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
STUB ABOVE ACCESSSIBLE CEILING. BUSH CONDUIT END.
AutoCAD SHX Text
ROUTE A 3/4" CONDUIT FROM TELEPHONE OUTLET BOX CONCEALED AND
AutoCAD SHX Text
SECOND FLOOR POWER & AUXILIARY SYSTEMS PLAN NOTES:
AutoCAD SHX Text
225A, MCB TYPE, 3 PHASE, 208Y/120V, 22,000AIC PANEL 'L1'. SEE ONE
AutoCAD SHX Text
LINE DIAGRAM AND PANEL SCHEDULE FOR ADDITIONAL DETAILS. ( PROVIDED BY PHASE 2)
AutoCAD SHX Text
J-BOX FOR CONNECTION OF TEMPERATURE CONTROLS. COORDINATE ALL
AutoCAD SHX Text
DETAILS WITH MECHANICAL AND CONTROLS CONTRACTORS.
AutoCAD SHX Text
LUTRON GP24-1204M-20, OR APPROVED EQUAL, DIMMER CABINET 'DC' WITH
AutoCAD SHX Text
200A, 22,000AIC MAIN BREAKER. SEE ONE LINE DIAGRAM AND DIMMER
AutoCAD SHX Text
CABINET SCHEDULE FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
4' X 4' TELEPHONE BACKBOARD. COORDINATE ALL REQUIREMENTS WITH OFFUTT
AutoCAD SHX Text
AIR FORCE BASE COMMUNICATIONS DEPARTMENT. SEE TELEPHONE SYSTEM
AutoCAD SHX Text
RISER DIAGRAM FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text
AA
AutoCAD SHX Text H
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
(BOX PROVIDED BY PHASE 2)
AutoCAD SHX Text
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
%%UUPPER AUDITORIUM
AutoCAD SHX Text
PRACTICE
AutoCAD SHX Text
%%UROOM
AutoCAD SHX Text
%%UROOM
AutoCAD SHX Text
PRACTICE
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
%%ULIBRARY
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
%%UCHASE
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%UROOM
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
REMOVABLE
AutoCAD SHX Text
RAILING
AutoCAD SHX Text
SECTIONS
AutoCAD SHX Text
WORK BY PHASE 3
AutoCAD SHX Text
WORK IN THIS CONTRACT
AutoCAD SHX Text
WORK BY PHASE 2
AutoCAD SHX Text
WORK NOT IN THIS CONTRACT (NIC)
AutoCAD SHX Text
SEE ARCHITECTURAL GENERAL NOTES FOR DESCRIPTION
AutoCAD SHX Text
THIS PROJECT IS PHASE 3 OF A THREE PHASE PROJECT.
AutoCAD SHX Text
OF WORK WHICH IS INCLUDED IN THIS PHASE.
AutoCAD SHX Text F.E.C.
AutoCAD SHX Text Air Force Base
AutoCAD SHX Text Offutt
AutoCAD SHX Text
OFFICE
AutoCAD SHX Text
SIGNATURE
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
COORDINATION
AutoCAD SHX Text
DESIGN FIRM
AutoCAD SHX Text Project Manager
AutoCAD SHX Text Date
AutoCAD SHX Text Designer
AutoCAD SHX Text Drafter
AutoCAD SHX Text
BY/DATE
AutoCAD SHX Text
REVISION
AutoCAD SHX Text
SHEET TITLE
AutoCAD SHX Text
OF
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
PROJECT TITLE
AutoCAD SHX Text Facility Number
AutoCAD SHX Text Project Number
AutoCAD SHX Text Drawing Number
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text N
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text M
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text
ALTER / REPAIR
AutoCAD SHX Text
RENOVATE BAND
AutoCAD SHX Text
BLDG. 123
AutoCAD SHX Text
SGBP 94-0005 A3 (R)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
GL
AutoCAD SHX Text
RS
AutoCAD SHX Text 9-6-95
AutoCAD SHX Text
AS
AutoCAD SHX Text
PHASE 3