This document is a set of construction drawings for the Kyles Landing Sewer Renovation project at Buffalo National Riverway in Newton County, Arkansas. The comprehensive drawing set includes 18 sheets covering various technical aspects of the project, such as site layout, topographic survey, site access, erosion control, sanitary sewer details, site removals, electrical diagrams, and equipment specifications.
The drawings detail the replacement of existing sewer infrastructure, including two septic tanks, a lift station, distribution pipes, and a drain field. The project involves precise site grading, installation of underground utilities, and careful environmental considerations, as evidenced by erosion control and site restoration plans. The electrical drawings include one-line diagrams, control logic for pumps, and ground rod and conduit details. The site is located in a forested area with an access road, and the drawings provide extensive technical specifications for each component of the sewer system renovation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6225B0001_Amd_0001.pdf | ||
| B11_Site_Visit_Attendence_0001.pdf | ||
| Sol_140P6225B0001.pdf | ||
| B08_Solicitation_-_Attachment_3_-_Wage_Determination.pdf | ||
| B08_Solicitation_-_Attachment_1_-_Specifications.pdf | ||
| B08_Solicitation_-_Attachment_4_-_Limitations_on_Subcontracting.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TITLE OF PROJECT
BUFFALO NATIONAL RIVERWAY
80062
NATIONAL
SERVICE
PARK LOCATION WITH PARK
KYLES LANDING SEWER RENOVATION
NAME OF PARK
REGION COUNTY STATE
ARKANSASNEWTONMIDWEST
G
ROAD
WORK
AHEAD
LIFT STATION / VALVE VAULT
STA 4+21.50
RIM ELEV 910.87
INVERT IN 6" (NE) 906.93
INVERT OUT 2" (SW) 907.91
BOTTOM OF WET WELL 902.59
SEPTIC TANK #2
STA 4+34.12
RIM ELEV 910.87
INVERT IN 6" (NE) 907.24
INVERT OUT 6" (SW) 907.00
SEPTIC TANK #1
STA 4+45.93
RIM ELEV 910.87
INVERT IN 6" (NE) 907.53
INVERT OUT 6" (SW) 907.29
6" DOUBLE
CLEANOUT
6" 45° PIPE
BEND
DISTRIBUTING VALVE W/ 30" ENCLOSURE
STA 11+42.83
RIM ELEV 999.52
INV IN 2" (SE) 996.46
INV OUT 1 14"(4) 994.31
2" HDPE, HDD
2" HDPE, HDD
EXISTING GROUND
EXISTING GROUND
EX.
UNDERGROUND
POWER
EX. SANITARY SEWER
(TO BE ABANDONED)
6" 45° PIPE
BEND
EX. UNDERGROUND
POWER
EX. WATER
SERVICE
EX. TELEPHONE
EX. UNDERGROUND
POWER
EX. WATER
SERVICE
2' M
IN.
BURY DEPTH
2' M
IN.
BURY DEPTH
2" AIR RELEASE
VALVE W/ ENCLOSURE
4 - 1 14" DISTRIBUTION PIPES
KVA
3Ø, 4W 208/120V
LP100
CONDUIT RUN BETWEEN DEVICES CONCEALED IN
NON-ARCHITECTURALLY FINISHED AREAS OR UNDER FLOOR
SLAB. CONDUIT AND CONDUCTOR SIZES SHALL BE THE SAME
AS THE HOMERUN FOR THE CIRCUIT.
1. THIS IS A STANDARD ELECTRICAL SYMBOLOGY SHEET. NOT ALL SYMBOLS MAY BE USED ON
THIS PROJECT.
2. SCREENING OR SHADING OF WORK IS USED TO INDICATE EXISTING COMPONENTS OR TO
DE-EMPHASIZE PROPOSED IMPROVEMENTS TO HIGHLIGHT SELECTED TRADE WORK. REFER
TO CONTEXT OF EACH SHEET FOR USAGE.
3. SEE P&ID LEGEND SHEET FOR PROJECT-SPECIFIC EQUIPMENT SYMBOLS, EQUIPMENT
ABBREVIATIONS, AND PIPING SYSTEM ABBREVIATIONS.
CURRENT TRANSFORMER (CT)
VOLTAGE TRANSFORMER (VT, PT, OR CPT)
UTILITY WATT-HOUR METER PER UTILITY REQUIREMENTS
GROUND
LIGHTNING ARRESTER
DIGITAL METERING PACKAGE
LOW VOLTAGE SURGE PROTECTIVE DEVICE
CONTROL PANEL WITH DISCONNECT SWITCH INTEGRAL OR
PROVIDED WITH ASSOCIATED EQUIPMENT
MOTOR/LOAD CONTROLLER AND
SEPARATELY MOUNTED MOTOR/LOAD CONTROLLER
WITH SHORT CIRCUIT PROTECTION AND DISCONNECT
PLUG-IN RECEPTACLE STRIP, QUANTITY AND SPACING OF
RECEPTACLES AS NOTED OR SPECIFIED
SWITCHBOARD OR PANELBOARD; NAME, VOLTAGE, PHASE,
NUMBER OF WIRES WHEN INDICATED
CONDUIT TAG OR CIRCUIT NUMBER - WIRE AND
CONDUIT SIZE AS SPECIFIED IN CIRCUIT SCHEDULE
ON THE SHEETS
CONDUIT STUBBED OUT AND CAPPED
CIRCUIT CONTINUATION
NON-MOTOR LOAD WITH DESIGN KVA, KW, OR AMP
SIMPLEX RECEPTACLE
SEPARATELY MOUNTED COMBINATION MOTOR STARTER
OR CONTROLLER; SEE ELECTRICAL ONE - LINE DIAGRAM
OR SCHEDULE FOR DESCRIPTION
NON-FUSED SWITCH, CURRENT RATING, AND
NUMBER OF POLES AS NOTED (3 POLE UON)
MCCB
ICCB
LVP
MCP
GROUND ROD
GROUND CABLE
SPECIAL-PURPOSE RECEPTACLE AS DEFINED ON PLANS
DUPLEX RECEPTACLE
WALL SWITCH
SINGLE-FACED CEILING OR WALL-MOUNTED EXIT LIGHT; DIRECTIONAL
ARROWS (IF REQUIRED) AS INDICATED ON PLANS
DOUBLE-FACED CEILING OR WALL-MOUNTED EXIT LIGHT; DIRECTIONAL
ARROWS (IF REQUIRED) AS INDICATED ON PLANS
EMERGENCY LIGHT, REMOTE MOUNTED HEAD
EMERGENCY LIGHT, NUMBER OF ATTACHED HEADS SHOWN
CIRCUIT HASH MARKS (WHEN INDICATED); LONG, SHORT,
SINGLE DOT, AND DOUBLE DOT REPRESENT PHASE, NEUTRAL,
EQUIPMENT GROUND, AND ISOLATED EQUIPMENT GROUND,
RESPECTIVELY. #12 IN 3/4" CONDUIT UNLESS OTHERWISE
INDICATED.
GROUND FAULT PROTECTION
CIRCUIT RUN BETWEEN DEVICES EXPOSED IN
NON-ARCHITECTURALLY FINISHED AREAS; CONCEALED IN
ARCHITECTURALLY FINISHED AREAS. CONDUIT AND
CONDUCTOR SIZES SHALL BE THE SAME AS THE HOMERUN FOR
THE CIRCUIT.
CONDUIT TURNING DOWN
CONDUIT TURNING UP
PANELBOARD (LESS THAN 250V)
PANELBOARD (250V TO 600V)
JUNCTION OR PULL BOX
CONTROL PANEL INTEGRAL OR PROVIDED WITH ASSOCIATED
EQUIPMENT
INSTRUMENTATION/CONTROL DEVICE
PUSHBUTTON
SELECTOR SWITCH
3-PHASE, 4-WIRE GROUNDED WYE CONNECTION
TRANSFORMER
TRANSFER SWITCH, CURRENT RATING, AND
NUMBER OF POLES AS NOTED
GENERATOR
MOTOR WITH DESIGN HORSEPOWER
(WHEN INDICATED)
NON-FUSED SAFETY SWITCH, 30A, 3P, X INDICATES AMP
RATING GREATER THAN 30A
MEDIUM VOLTAGE CIRCUIT BREAKER
FUSIBLE SWITCH, CURRENT RATING, FUSE RATING,
AND QUANTITY AS NOTED (3 POLE UON)
FUSED CUTOUT, CURRENT RATING, FUSE RATING,
AND QUANTITY AS NOTED
FUSE, RATING, AND NUMBER OF FUSES AS NOTED
SEPARATELY MOUNTED CIRCUIT BREAKER; SEE
ELECTRICAL ONE - LINE DIAGRAM OR SCHEDULE FOR
DESCRIPTION
MAGNETIC MOTOR STARTER AND
SEPARATELY MOUNTED COMBINATION MAGNETIC
MOTOR STARTER
TYPES:
A - MAGNETIC STARTER NEMA SIZE
B - STARTER TYPE
C - CONTROL DIAGRAM OR CONTROLS
SCHEDULE NUMBER (IF REQUIRED)
D - CONTROLLER TYPE
ATS - AUTOMATIC
MTS - MANUAL
X - INDICATES LUMINAIRE TYPE PER LUMINAIRE SCHEDULE
Y - INDICATES CIRCUIT NUMBER FROM PANELBOARD
Z - INDICATES CONTROLLING SWITCH (IF REQUIRED)
NL - NIGHT LIGHT UNSWITCHED
X - INDICATES TYPE
RECESSED FLOOR MOUNTED BOX, QUANTITY AND TYPE OF
RECEPTACLES AS INDICATED
CORD AND PLUG CONNECTION
MOLDED CASE
INSULATED CASE
LOW VOLTAGE POWER
MOTOR CIRCUIT PROTECTOR
(RATING PER CONNECTED
LOAD)
NONE
FVR
2S
RVAT
FULL VOLTAGE NON-REVERSING (FVNR)
FULL VOLTAGE REVERSING
TWO SPEED
REDUCED VOLTAGE AUTO TRANSFORMER
VFD
SS
CONT
VARIABLE FREQUENCY DRIVE
SOLID STATE
CONTACTOR
NONE
K P L
DM
MC
T
SINGLE POLE
DOUBLE POLE
THREE-WAY
FOUR-WAY
KEY SWITCH
PILOT LIGHT
LIGHTED HANDLE
DIMMING
MOMENTARY CONTACT
TIMER
Y - INDICATES CONTROLLING SWITCH (IF REQUIRED)
PHOTOCELL
TIME CLOCK
ELECTRICAL EQUIPMENT ENCLOSURE: SWITCHBOARD,
MOTOR CONTROL CENTER, CONTROL PANEL, TRANSFORMER
OR OTHER EQUIPMENT AS INDICATED. ESTIMATED SIZE AS
INDICATED. WHEN USED X INDICATES EQUIPMENT TYPE.
ATS
CP
MTS
MCC
UPS
VFD
SB
SG
T
AUTOMATIC TRANSFER SWITCH
CONTROL PANEL
MANUAL TRANSFER SWITCH
MOTOR CONTROL CENTER
UNINTERRUPTIBLE POWER SUPPLY
VARIABLE FREQUENCY DRIVE
SWITCHBOARD
SWITCHGEAR
TRANSFORMER
SAFETY SWITCH, 3P, X INDICATES AMP RATING GREATER
THAN 30A, Y INDICATES FUSE SIZE
LOW VOLTAGE CIRCUIT BREAKER (CB). RATING AND NO. OF
POLES AS SHOWN. WHEN SPECIFIC TYPE, OTHER THAN
MCCB, IS REQUIRED, X INDICATES TYPE.
SEPARATELY MOUNTED MOTOR STARTER OR CONTROLLER; SEE
ELECTRICAL ONE-LINE DIAGRAM OR SCHEDULE FOR
DESCRIPTION.
L S I G A
TRIP UNIT:
LONG TIME PICKUP
SHORT TIME PICKUP
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
ARC FLASH MAINTENANCE
WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, ALL OR PARTIAL EMERGENCY
(INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)
CEILING/PENDANT MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, ALL OR PARTIAL
EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)
WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED
CEILING/PENDANT MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED
WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED
CEILING/PENDANT/BOLLARD MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED
CEILING/PENDANT/BOLLARD MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED,
EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)
WALL MOUNTED FLOOD LUMINAIRE, LAMP TYPE AS SPECIFIED
POLE/STANCHION MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED
POLE/STANCHION MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED,
EMERGENCY (INTERNAL OR EXTERNAL POWER SOURCE AS INDICATED)
POLE/STANCHION MOUNTED FLOOD LUMINAIRE, LAMP TYPE AS SPECIFIED
WALL MOUNTED LUMINAIRE, LAMP TYPE AS SPECIFIED, EMERGENCY (INTERNAL
OR EXTERNAL POWER SOURCE AS INDICATED)
LIGHTING CONTROL OCCUPANCY SENSOR, WALL MOUNTED, X INDICATES
SPECIFIC TYPE AS SPECIFIED
LIGHTING CONTROL OCCUPANCY SENSOR, CEILING MOUNTED, X INDICATES
SPECIFIC TYPE AS SPECIFIED
or
TWO RECEPTACLES IN 2-GANG BOX UNDER COMMON COVER
PLATE
or
X - INDICATES TYPE
GFCI
IG
TR
PLH
PLD
USB
SPD
AC
WP
WPI
Y - INDICATES CONTROLLING SWITCH (IF REQUIRED)
GROUND FAULT CIRCUIT INTERRUPTER
ISOLATED GROUND
TAMPER RESISTANT
PLUG LOAD HALF CONTROLLED (*)
PLUG LOAD DUAL CONTROLLED (*)
PLUG LOAD FULL CONTROLLED (*)
USB CHARGING STATION
SURGE PROTECTIVE DEVICE
ABOVE COUNTER
WEATHERPROOF
WEATHERPROOF IN-USE
HOMERUN TO PANEL
SINGLE PHASE: 2#12, 1#12G IN 3/4"C
THREE PHASE: 3#12, 1#12G IN 3/4"C
UNLESS OTHERWISE NOTED, CONDUCTOR
SIZE IS FOR ENTIRE CIRCUIT
CONDUIT CONNECTION TO EQUIPMENT
INTERLOCK; X INDICATES TYPE
E - ELECTRICAL
M - MECHANICAL
K - KEY
ROOM/AREA LIGHTING CONTROL TYPE,
SEE LIGHTING CONTROL SCHEDULE FOR REQUIREMENTS
LOW VOLTAGE DIGITAL WALL SWITCH, NUMBER INDICATES QUANTITY OF
PUSH BUTTONS PER SINGLE GANG PLATE, LETTER INDICATES CONTROL
ZONE WHEN SHOWN
MANUAL MOTOR STARTER
X - INDICATES TYPE
HP
TE
FT
HORSEPOWER RATED
HORSEPOWER RATED WITH THERMAL ELEMENT
HORSEPOWER RATED WITH FUSETRON FUSE
Y - INDICATES SWITCH TYPE
NONE
R
TOGGLE SWITCH TYPE
ROTAR SWITCH TYPE
or
(#X)
(#X)
INDICATES THAT ALL OR PART OF THE CIRCUIT MAY
BE ROUTED IN DUCT BANK OR UNDERGROUND
INDICATES THAT ALL OR PART OF THE CIRCUIT MAY
BE ROUTED IN CABLE TRENCH
INDICATES THAT ALL OR PART OF THE CIRCUIT MAY
BE ROUTED IN CABLE TRAY
PLF
(*) REFER TO PLUG LOAD CONTROL DETAIL #9 ON SHEET 00-E503.
WALL MOUNTED TELEPHONE OUTLET
WALL MOUNTED DATA OUTLET - SCADA
WALL MOUNTED DATA OUTLET - NPS IT
RECESSED FLOOR MOUNTED TELEPHONE OUTLET
RECESSED FLOOR MOUNTED DATA OUTLET - SCADA
RECESSED FLOOR MOUNTED DATA OUTLET - NPS IT
DOOR CONTACT
ROUGH-IN FOR FUTURE PROXIMITY CARD READER
ROUGH-IN FOR A FUTURE REQUEST TO EXIT PUSH
BUTTON
X
Y X
OROR
SV OR
ELECTRICAL CONNECTION
NO ELECTRICAL CONNECTION
NORMALLY OPEN TIME DELAY RELAY CONTACT WITH TIME DELAY ON
CLOSING AFTER COIL IS ENERGIZED
NORMALLY CLOSED TIME DELAY RELAY CONTACT WITH TIME DELAY ON
OPENING AFTER COIL IS ENERGIZED
NORMALLY OPEN TIME DELAY RELAY CONTACT WITH TIME DELAY
ON OPENING AFTER COIL IS DE-ENERGIZED
NORMALLY CLOSED TIME DELAY RELAY CONTACT WITH TIME
DELAY ON CLOSING AFTER COIL IS DE-ENERGIZED
SOLENOID VALVE
CONTROL/RELAY COIL; X INDICATES TYPE,
Y INDICATES LOOP NO. WHEN USED
TYPES:
NORMALLY OPEN CONTACT (N.O.)
NORMALLY CLOSED CONTACT (N.C.)
NORMALLY OPEN TEMPERATURE SWITCH;
CLOSE ON RISING TEMPERATURE
NORMALLY CLOSED TEMPERATURE SWITCH;
OPEN ON RISING TEMPERATURE
NORMALLY OPEN FLOW SWITCH; CLOSE ON INCREASING FLOW
NORMALLY CLOSED FLOW SWITCH;
OPEN ON INCREASING FLOW
NORMALLY OPEN LEVEL SWITCH, CLOSE ON RISING LEVEL
NORMALLY CLOSED LEVEL SWITCH, OPEN ON RISING LEVEL
NORMALLY OPEN PRESSURE SWITCH, CLOSE ON INCREASING
PRESSURE
NORMALLY CLOSED PRESSURE SWITCH, OPEN ON INCREASING
PRESSURE
NORMALLY OPEN LIMIT SWITCH, CLOSE ON REACHING LIMIT
NORMALLY CLOSED LIMIT SWITCH, OPEN ON REACHING LIMIT
FIELD WIRING EXTERNAL TO CONTROL PANEL
TYPES:
INTERLOCK; X INDICATES TYPE
NORMALLY CLOSED PUSHBUTTON, MOMENTARY CONTACT UNLESS
OTHERWISE NOTED
NORMALLY OPEN PUSHBUTTON, MOMENTARY CONTACT UNLESS
OTHERWISE NOTED
3 POSITION SELECTOR SWITCH, MAINTAINED CONTACTS; UNLESS
OTHERWISE NOTED, 2-POSITION SIMILAR
OOX
XOO
HAND AUTO
OFF
CR
DP
LC
M
E - ELECTRICAL
M - MECHANICAL
K - KEY
MICROPROCESSOR (PLC, RTU, ETC.) OUTPUT
MICROPROCESSOR (PLC, RTU, ETC.) INPUT
RTM
OL
RUN TIME METER
THERMAL OVERLOAD ELEMENT
THERMAL OVERLOAD RELAY CONTACT. WHEN SHOWN X INDICATES
QUANTITY.
(X)
AND
SUBSCRIPT:
HEAT DETECTOR
X
FAA FIRE ALARM ANNUNCIATOR
PRESSURE SWITCH
TAMPER SWITCH
FLOW SWITCH
X
SUBSCRIPT:
X
SPOT AND DUCT SMOKE DETECTOR, X INDICATES TYPE
FLASHING LIGHT
HORN/SPEAKER
BELL
FIRE ALARM MANUAL PULL STATIONF
FIRE ALARM CONTROL PANELFACP
I P D
R/C R/F R F
HORN/SPEAKER AND FLASHING LIGHT COMBINATION UNIT
SUBSCRIPT:
FLAME DETECTOR
X
IR
UV
DOOR HOLDER
EXTERIOR LOCATION HIGH POWER SPEAKER ARRAY (HSPA)
TXT
LOCAL OPERATING CONSOLELOC
MNCP MASS NOTIFICATION SYSTEM CONTROL PANEL
COMBINATION SPEAKER/STROBE NOTIFICATION APPLIANCEM
M
M
SPEAKER NOTIFICATION APPLIANCE
STROBE NOTIFICATION APPLIANCE
MS CEILING MOUNTED SPEAKER
MS WALL MOUNTED SPEAKER
MFCP COMBINATION MASS NOTIFICATION/FIRE ALARM CONTROL PANEL
COMBINATION MASS NOTIFICATION/FIRE ALARM STROBE
NOTIFICATION APPLIANCE
MF
MF
MF
COMBINATION MASS NOTIFICATION/FIRE ALARM SPEAKER
NOTIFICATION APPLIANCE
COMBINATION MASS NOTIFICATION/FIRE ALARM STROBE
NOTIFICATION APPLIANCE
LENS:
FIRE ALARM - CLEAR
MASS NOTIFICATION - AMBER
F
F
F
CPT
CONTROL POWER TRANSFORMER (CPT)
TEXT MESSAGE DISPLAY UNIT
CONTROL RELAY
DEFINITE PURPOSE RELAY
LIGHTING CONTACTOR
MOTOR STARTER
PC
TC
TR
PHOTOCELL
TIME CLOCK
TIMING RELAY
INFRARED
ULTRAVIOLET
RATE COMPENSATION
COMBINATION RATE OF RISE AND FIXED TEMP
RATE OF RISE FIXED
IONIZATION
PHOTOELECTRIC
FIRE OR SMOKE DAMPER
PS
TS
FS OR
OR
OR
F
F BELL/SPEAKER AND FLASHING LIGHT COMBINATION UNIT
E ALARM HORN AND FLASHING LIGHT COMBINATION UNIT
E ALARM BELL AND FLASHING LIGHT COMBINATION UNIT
E ALARM FLASHING LIGHT
E ALARM HORN
E ALARM BELL
X
X
LENS COLORS:
PUSH TO TEST INDICATING LIGHT, X INDICATES LENS COLOR
INDICATING LIGHT, X INDICATES LENS COLOR
R - RED
G - GREEN
B - BLUE
Y - YELLOW
W - WHITE
A - AMBER
X Y
X Y
X Y
RPS FIRE ALARM REMOTE POWER SUPPLY
IN OR ABOVE CEILING DATA OUTLET INTENDED TO SERVICE A
FUTURE CEILING MOUNTED WIRELESS ACCESS POINT (FUTURE, NIC)
DC
ISR - INSTRINSICALLY SAFE RELAY
ALT - ALTERNATOR
CP - CONTROL PANEL
CU - COPPER
GND - GROUND
MFR - MANUFACTURER
PB - PUSH BUTTON
1-3/8"
BODY
8 1/8"
8 7/8"
9"
7 1/8"
3/8
CAST IRON
COVER
9 3 /4"
3/
4"
" B
FG
R
HIGH ALARM BEACON
ALARM SILENCE PB
R
G
RTM
OFF
HAND AUTO
OOX
XOO
R
G
RTM
OFF
HAND AUTO
OOX
XOO
H N
| Sheets and Views |
| G0 COVER.dwg - Layout1 |
| G1 LEGEND - Layout1 |
| G2 ABBR - Layout1 |
| C1 TOPO - Layout1 |
| C2 SITE - Layout1 |
| C3 EC - Layout1 |
| C4 DEMO - Layout1 |
| C5 ACCESS - Layout1 |
| C6 P&P - Layout1 |
| C7 DETAILS - Layout1 |
| C8 DETAILS - Layout1 |
| C9 DETAILS - Layout1 |
| C10 DETAILS - Layout1 |
| E1 - Layout1 |
| E2 - Layout1 |
| E3 - Layout1 |
| E4 - Layout1 |
| E5 - Layout1 |
File details come from the government source that posted it. Updated .