B08_Solicitation_Attachment_1_Scope_of_Work.docx
DOCX document 29 KB Posted
- Attached to
- LOWELL NHP_FIRE SUPPRESSION MAINTENANCE AND REPAIR Federal contract opportunity
- Solicitation number
- 140P4326Q0065
About this file
This is a Scope of Work document for fire alarm and fire sprinkler system maintenance and repair services at Lowell National Historical Park in Lowell, Massachusetts. The Contractor must provide all labor, materials, tools, transportation, and supervision to inspect, test, maintain, and repair fire alarm and water-based fire suppression systems across four designated park facilities: Boott Mill Complex, Maintenance Facility, Park Headquarters, and Mogan Cultural Center. All work must comply with applicable National Fire Protection Association standards (NFPA 20, 25, 70, and 72). The contract structure includes three Competitive Line Item Numbers (CLINs) spanning a base year plus two optional 12-month extensions: Annual Inspections & Maintenance (firm-fixed-price), Monthly Fire Pump Testing (firm-fixed-price), and Service Calls/Repairs/Additional Work (time and materials).
Key service requirements include performing annual NFPA-compliant inspections with main drain tests, alarm verification, control valve inspection and lubrication, device testing, detector cleaning, flow and tamper switch testing, and fire pump operational testing. Monthly fire pump testing must be conducted per NFPA 25 standards with minimum 10-minute run times. Service calls for troubleshooting and minor repairs are priced on a time and materials basis, with different rates for weekday (8 AM–5 PM) and weekend/holiday calls. The Contractor must maintain 24/7 service availability with 4-hour response times and complete repairs within 48 hours when feasible. All inspection reports are due within two weeks of service and must document deficiencies and corrective actions. Security restrictions include no modifications to historic structures without approval, no contact with historic materials without authorization, and escort requirements in sensitive areas. The solicitation includes an organized site visit scheduled for September 9, 2026, at 10:00 AM ET at the Maintenance Facility (220 Aiken Street, Lowell, MA 01854).
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P4326Q0065_Amd_0001.pdf | ||
| Sol_140P4326Q0065.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Scope of Work Fire Alarm and Fire Sprinkler System Maintenance and Repair Lowell National Historical Park Lowell, Massachusetts
Table of Contents
1.0 Background
2.0 Scope
3.0 Objectives
4.0 Tasks
5.0 Delivery
6.0 Government-Furnished Property
7.0 Security
8.0 Place of Performance
9.0 Period of Performance
10.0 Restrictions
11.0 Definitions
1.0 BACKGROUND
Lowell National Historical Park, established in 1978, preserves and interprets resources associated with Lowell’s role in the 19th-century American Industrial Revolution while contributing to the city’s ongoing revitalization.
The Contractor shall provide all labor, materials, tools, transportation, and supervision necessary to perform inspection, testing, maintenance, and repair of fire alarm and water-based fire suppression systems at designated park facilities.
Purpose of Contract To ensure all fire alarm and fire suppression systems are fully operational and compliant with applicable codes, including those established by the National Fire Protection Association (NFPA), thereby protecting park resources, staff, and visitors.
Applicable standards include:
· NFPA 25 – Water-Based Fire Protection Systems
· NFPA 20 – Fire Pumps
· NFPA 72 – Fire Alarm Systems
· NFPA 70 – National Electrical Code
CLIN Structure
| Service |
| Base Year |
| Option Yr 1 |
| Option Yr 2 |
| Annual Inspections & Maintenance |
| 00010 |
| 00040 |
| 00070 |
| Monthly Fire Pump Operation |
| 00020 |
| 00050 |
| 00080 |
Service Calls (Weekdays)/ (Weekends/Holidays) / Repairs / Additional Work
| 00030 |
| 00060 |
| 00090 |
2.0 SCOPE
The park’s fire protection systems vary in size and complexity, including wet, dry, pre-action, and fire pump-supported systems.
Contractor shall inspect, test, maintain, fasten down and repair:
· Fire alarm control panels and devices
· Detection systems (smoke, heat, pull stations)
· Notification systems (horns, strobes)
· Water-based fire suppression systems Alarm signals are transmitted to:
· Municipal fire department (via wireless master box)
· Third-party monitoring service Exclusions:
· Halon systems
· Backflow preventer testing
3.0 OBJECTIVES
Ensure all systems are fully functional and compliant with NFPA 20, 25, 70, and 72 through routine inspection, testing, maintenance, and repair.
4.0 TASKS
4.1 General Requirements
· Provide scheduled inspections, emergency service, and repairs
· Maintain 24/7 service availability
· Respond to service calls within 4 hours
· Complete repairs within 48 hours, when feasible
· Submit written service reports to the COR after each visit
· Maintain active insurance throughout contract duration
4.2 Annual Inspection and Testing (Firm-Fixed-Price)
Contractor shall perform:
· Main drain tests (record static/residual pressures)
· Alarm verification (local and remote transmission)
· Inspection and lubrication of all control valves
· Testing of all initiating and notification devices
· Detector cleaning and sensitivity checks
· Flow switch and tamper switch testing
· Fire pump and jockey pump operational testing
· Pump capacity (flow) testing per manufacturer specs All systems shall be restored to normal operation upon completion.
4.3 Monthly Fire Pump Testing (Firm-Fixed-Price)
· Conduct monthly no-flow test per NFPA 25
· Run pump for minimum of 10 minutes
· Verify automatic start function
· Record performance and deficiencies via e-mail.
4.4 Service Calls (Time & Materials)
Includes troubleshooting and minor repairs such as:
· Alarm “trouble” conditions
· Device replacement (detectors, batteries, switches)
· Wiring and system diagnostics
· Resetting municipal fire alarm connections Pricing Parameters:
· Weekday calls (8 AM–5 PM): $_________ Per Hour
· Weekend/holiday calls: $_________ Per Hour If unresolved, follow-up service call required.
4.5 Repairs / Additional Work (Time & Materials)
· Repairs/Additional work requires prior approval
· Contractor shall submit written quotes
· Work invoiced against T&M Not-to-Exceed Ceiling amount for current year. Repairs/Additional work will be invoiced at the appropriate hourly rate, based on when the work is being completed (Weekday/Weekend/Holiday).
5.0 DELIVERY
· Inspection reports due within 2 weeks of service
· Reports must include deficiencies and corrective actions
· Contractor shall maintain digital records accessible to the Government
6.0 GOVERNMENT-FURNISHED PROPERTY
None. Contractor shall provide all equipment and materials.
7.0 SECURITY
· Contractor shall coordinate access through COR
· Escort required in sensitive areas
· No contact with historic materials without approval
· No smoking, food, or drink unless authorized
· No modification to historic fabric without COR approval
8.0 PLACE OF PERFORMANCE
Services shall be performed at:
· Boott Mill Complex (115 John St.)
· Maintenance Facility (220 Aiken St.)
· Park Headquarters (67 Kirk St.)
· Mogan Cultural Center (40 French St.)
(Existing system details remain as provided)
9.0 PERIOD OF PERFORMANCE
· Base Year: 12 months
· Two (2) optional 12-month extensions
10.0 RESTRICTIONS
· No wireless system modifications permitted
· No drilling or alteration of historic structures without approval
· No personal audio devices
· No unauthorized interaction with artifacts
11.0 DEFINITIONS
Annual Inspection:
Full NFPA-compliant inspection of fire alarm and suppression systems.
Service Call:
Minor repair or troubleshooting.
Repairs / Additional Work:
Repairs or Additional Work not included in service calls.