B08_Solicitation_Attachment_1_Drawings_FRSP_Fredericksburg_Battlefield_Visitor_Center.pdf
PDF 4 MB Posted
- Attached to
- FIRE SUPPRESSION SYSTEM AT FREDERICKSBURG VC
- Solicitation number
- 140P4325R0028
About this file
These are fire suppression system construction drawings for the Fredericksburg Visitor Center at Fredericksburg & Spotsylvania National Military Park in Virginia. The drawings detail the installation of a comprehensive fire protection system including basement, first floor, and second floor sprinkler coverage with sidewall and upright sprinklers, a fire protection riser system, backflow preventer, fire department connection, and associated piping infrastructure. The project involves connecting to existing 16" and 8" public water mains via a 16"x6" tapping sleeve and installing a new 6" PVC underground fire main.
The drawings show detailed construction specifications including utility trenching, demolition of existing concrete sidewalks and brick pavers for pipe installation, tree protection measures, and restoration of disturbed areas. The fire suppression system must comply with International Fire Code 2024, NFPA 13 (sprinkler systems), NFPA 70 (electrical code), NFPA 72 (fire alarm code), and NPS RM-58 Structural Fire Management standards. Construction details include pipe sleeves through walls, valve boxes, tracer wire test stations, and specific requirements for protecting historic building elements during installation. The project includes coordination with existing utilities and requires specialized equipment clean before entering park lands to prevent invasive species introduction.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
QUALITY DESIGN CERTIFICATION
STATEREGION COUNTY
NAME OF PARK
TITLE OF PROJECTCROFT & ASSOCIATES -
PRIME:
REVISION
LOCATION WITHIN PARK
NATIONAL PARK SERVICE
SOUTHEAST REGIONAL OFFICE
UNITED STATES
DEPARTMENT OF THE INTERIOR
DRAWING NO.
PMIS/PKG NO.
SHEET
OF
RECOMMENDED:
Project Manager
APPROVED:
Superintendent
Date
Date
BOWMAN FIRE & LIFE
SAFETY, INC.
JOHNS CREEK, GEORGIA
SUB:
CROFT & ASSOCIATES
KENNESAW, GEORGIA
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
NORTHEAST SPOTSYLVANIA VIRGINIA
FREDERICKSBURG VISITOR CENTER
FREDRICKSBURG & SPOTSYLVANIA NATIONAL MILITARY PARK
NORTH
VICINITY MAP SCALE: 1" = 500'
CONSTRUCTION DOCUMENTS
FINAL DESIGN DRAWINGS
304830B
1 11
APPLICABLE CODES AND STANDARDS
· INTERNATIONAL FIRE CODE® (IFC) 2024 WITH APPENDICES
· 2022 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 13, STANDARD
FOR THE INSTALLATION OF SPRINKLER SYSTEMS
· 2022 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 70, NATIONAL
ELECTRICAL CODE
· 2022 NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 72, NATIONAL
FIRE ALARM AND SIGNALING CODE®
· NPS RM-58 STRUCTURAL FIRE MANAGEMENT DATED SEPTEMBER 2023
FIRE SUPPRESSION SYSTEM
Sheet List Table Sheet Number Sheet Title
G000 COVER SHEET
A101 BASEMENT RESTROOM PLAN
C001 GENERAL NOTES
C100 EXISTING CONDITIONS AND DEMOLITION PLAN
C101 UTILITY AND EROSION PLAN
C500 CONSTRUCTION DETAILS 1 OF 2
C501 CONSTRUCTION DETAILS 2 OF 2
FX101 BASEMENT FIRE PROTECTION PLAN
FX102 FIRST FLOOR FIRE PROTECTION PLAN
FX103 SECOND FLOOR FIRE PROTECTION PLAN
FX501 DETAILS - FIRE PROTECTION
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
NAME OF PARK
1/
/2
:2 1:
A
M
J.D
J.D
01/29/2025
L.C
1/
/2
:2 1:
A
M
GENERAL NOTESC001
FREDERICKSBURG VISITOR CENTER
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK 3 11
SITE NOTES
1. ACREAGE OF PROPERTY: ±3.58 ACRES (7779-91-1951), ±0.18 ACRES (7779-91-4739)
2. DISTURBED AREA: ±0.055 ACRES
3. USE : MUSEUM/STORAGE FACILITY
4. SIGNING AND STRIPING TO BE PROVIDED ACCORDING TO THE LOCAL SPECIFICATIONS.
5. SIGNAGE WILL BE PROVIDED TO MUTCD STANDARDS.
6. ON-SITE PARKING SHALL BE PROVIDED AND MAINTAINED THROUGHOUT CONSTRUCTION.
7. THERE ARE NO STATE WATERS ON SITE.
8. THERE ARE NO WETLANDS ON SITE.
9. THERE ARE NO KNOWN LANDFILLS ON SITE.
10. BOUNDARY AND TOPOGRAPHIC INFORMATION TAKEN FROM PATRIOT SURVEYING & INFRASTRUCTURE DATED JUNE 11 2024.
GRADING NOTES
BOUNDARY INFORMATION OBTAINED FROM PATRIOT SURVEYING & INFRASTRUCTURE. TOPOGRAPHIC INFORMATION OBTAINED FROM PATRIOT SURVEYING & INFRASTRUCTURE. EXISTING UTILITY LOCATIONS ARE SHOWN FOR INFORMATION PURPOSES ONLY. CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE EXACT LOCATIONS OF ALL UTILITIES AND FOR COORDINATING
HIS OPERATIONS WITH ALL UTILITIES WHICH CONFLICT WITH HIS WORK.
UNDERCUTTING IS REQUIRED IN ALL AREAS WHERE MATERIAL IS DETERMINED TO BE UNSUITABLE (BY A REGISTERED GEOTECHNICAL ENGINEER) FOR STRUCTURAL BACKFILL MATERIAL. ALL TREES, STUMPS, ROOTS, DEBRIS, AND OTHERWISE DELETERIOUS MATERIAL MAY NOT BE BURIED OR DISPOSED OF ON SITE. ALL SLOPES SHALL BE 3:1 MAXIMUM, UNLESS SPECIFIED OTHERWISE OR WITH WRITTEN APPROVAL FROM THE CONTRACTING OFFICER. STRIP TOPSOIL AND VEGETATION FROM ALL WORK AREAS PRIOR TO GRADING. COMPACT FILL TO 95% STD PROCTOR DENSITY. STOCKPILES TO BE COMPACTED
TO 90% SPD IN TOP 2' TO PREVENT INFILTRATION OF MOISTURE.
UTILITY DISCLAIMER:
INFORMATION REGARDING THE PRESENCE, SIZE, CHARACTER AND LOCATION OF EXISTING UNDERGROUND UTILITIES AND STRUCTURES SHOWN HEREON IS BASED ON INFORMATION READILY AVAILABLE AT THE TIME OF PLAN PREPARATION. THERE IS NO CERTAINTY OF THE ACCURACY OF THIS INFORMATION AND IT SHALL BE TAKEN INTO CONSIDERATION BY THOSE USING THIS DOCUMENT. THE LOCATION AND DISPOSITION OF UTILITIES SHOWN MAY BE INACCURATE AND UTILITIES AND STRUCTURES NOT SHOWN MAY BE ENCOUNTERED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING ALL UTILITIES AFFECTED BY HIS
WORK PRIOR TO BEGINNING ANY CONSTRUCTION OR LAND DISTURBANCE.
GENERAL CONSTRUCTION NOTES
1. ALL UTILITY LOCATIONS TO BE FIELD VERIFIED BY PROPER AGENCIES BEFORE BEGINNING CONSTRUCTION. INFORMATION
SHOWN SHOULD BE CONSIDERED APPROXIMATE. CONTRACTOR TO CONTACT ALL UTILITY COMPANIES TO HAVE UTILITIES
FIELD LOCATED BEFORE EXCAVATION OR DEMOLITION WORK BEGINS.
2. ALL WORK AND MATERIALS SHALL COMPLY WITH LOCAL REGULATIONS AND CODES OF O.S.H.A STANDARDS.
3. NECESSARY AND SUFFICIENT BARRICADES, LIGHTS, SIGNS AND OTHER TRAFFIC CONTROL MEASURES AS MAY BE
NECESSARY FOR THE PROTECTION AND SAFETY OF THE PUBLIC SHALL BE PROVIDED AND MAINTAINED THROUGHOUT THE
CONSTRUCTION PERIOD.
4. THE LOCATIONS OF EXISTING UNDERGROUND AND OVERHEAD UTILITIES ARE SHOWN IN AN APPROXIMATE WAY ONLY AND HAVE NOT BEEN INDEPENDENTLY VERIFIED BY THE OWNER OR CROFT AND ASSOCIATES. THE CONTRACTOR SHALL DETERMINE THE EXACT LOCATION OF ALL EXISTING UNDERGROUND AND OVERHEAD UTILITIES BEFORE COMMENCING WORK AND AGREES TO BE FULLY RESPONSIBLE FOR ANY AND ALL DAMAGES WHICH MIGHT BE OCCASIONED BY THE CONTRACTORS FAILURE TO EXACTLY LOCATE AND PRESERVE ANY AND ALL UNDERGROUND AND OVERHEAD UTILITIES.
5. FOR EXACT BUILDING DIMENSIONS SEE ARCHITECTURAL PLANS.
6. CONTRACTOR SHALL VERIFY ALL DIMENSIONS BEFORE BEGINNING CONSTRUCTION.
7. THE CONTRACTOR SHALL REFER TO THE PLUMBING / MECHANICAL PLANS FOR LOCATION & SIZE OF ROOF DRAINAGE, GAS
ELECTRICAL, SANITARY SEWER & WATER SYSTEM SERVICE LINE CONNECTIONS. MOST SERVICE CONNECTIONS BEGIN 5'
FROM BUILDING FACE.
8. THE CONTRACTOR SHALL SAW-CUT TO PROVIDE SMOOTH TRANSITIONS AT TIE-INS TO EXISTING EDGES OF PAVEMENT.
9. JOINTS OR SCORE MARKS ARE TO BE SHARP AND CLEAN WITHOUT SHOWING EDGES OF JOINT TOOL.
10. THE CONTRACTOR SHALL SAW-CUT TIE-INS AT EXISTING CURBS AS NECESSARY TO ENSURE SMOOTH TRANSITIONS. THE
CONTRACTOR SHALL SAW-CUT AND TRANSITION TO MEET EXISTING PAVEMENT AS NECESSARY AND AS DIRECTED BY THE
INSPECTOR TO ENSURE POSITIVE DRAINAGE (TYPICAL AT ALL INTERSECTIONS).
11. DIMENSIONS ON BUILDINGS ARE FOR GRADING PURPOSES ONLY AND ARE NOT TO BE USED TO LAYOUT FOOTINGS. REFER
TO THE STRUCTURAL DRAWINGS FOR FOUNDATION INFORMATION.
12. ALL FILL MATERIAL TO BE UTILIZED ON THE PROJECT SHALL BE FREE OF ORGANIC OR OTHERWISE DELETERIOUS MATERIALS AND COMPACTED TO MINIMUM DRY DENSITIES CORRESPONDING TO 95% OF MAXIMUM DRY DENSITY AS OBTAINED BY STANDARD PROCTOR, ASTM D698 AND AT LEAST 98% OF STANDARD PROCTOR WITHIN 1 FOOT BELOW PAVEMENT SUBGRADE. FILL SHALL BE PLACED IN LIFTS NOT TO EXCEED 6 INCHES IN COMPACTED FILL THICKNESS.
13. MAXIMUM SLOPE OF EMBANKMENT SHALL BE 3.0 FEET HORIZONTAL TO 1.0 FOOT VERTICAL.
14. PROPOSED CONTOUR INTERVALS ARE AS LABELED. ALL PROPOSED CONTOURS ARE FINISHED GRADE.
15. THE CONTRACTOR WILL INSURE THAT POSITIVE AND ADEQUATE DRAINAGE IS MAINTAINED AT ALL TIMES WITHIN THE
PROJECT LIMITS. NO SEPARATE PAYMENT WILL BE MADE AT ANY COSTS INCURRED TO COMPLY WITH THIS REQUIREMENT.
16. EXCESS EARTH CUT MATERIAL,IF ANY, SHALL BECOME THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE
REMOVED FROM THE SITE UNLESS OTHERWISE APPROVED TO BE PLACED ON SITE BY THE OWNERS REPRESENTATIVE.
17. THE CONTRACTOR SHALL PROVIDE ANY EXCAVATION AND MATERIAL SAMPLES NECESSARY TO CONDUCT REQUIRED SOIL
TESTS. ALL ARRANGEMENTS AND SCHEDULING FOR THE TESTING SHALL BE THE CONTRACTOR'S RESPONSIBILITY.
18. SOILS TESTING AND ON-SITE INSPECTION SHALL BE PERFORMED BY AN INDEPENDENT TESTING AGENCY.THE TESTING
AGENCY SHALL PROVIDE COPIES OF TEST REPORTS TO THE CONTRACTOR, AND THE OWNER'S REPRESENTATIVE. TESTING AGENCY SHALL PROMPTLY NOTIFY THE OWNER'S REPRESENTATIVE AND THE CONTRACTOR SHOULD WORK PERFORMED
BY THE CONTRACTOR FAIL TO MEET THESE SPECIFICATIONS.
GENERAL NOTES
1. OFF-STREET PARKING MUST BE PROVIDED AND MAINTAINED THROUGHOUT CONSTRUCTION.
2. CONTRACTOR SHALL FURNISH, INSTALL AND MAINTAIN ALL NECESSARY TRAFFIC BARRICADES AND WARNING SIGNAGE TO
THE SATISFACTION OF THE ROAD DEPARTMENT WHILE ROADWAY FRONTAGE IMPROVEMENTS ARE MADE.
3. ACCEPTANCE AND/OR SUBSEQUENT ACCEPTANCE OF THESE PLANS DOES NOT CONSTITUTE APPROVAL BY THE LOCAL
MUNICIPALITY OF ANY LAND DISTURBING ACTIVITY WITHIN WETLAND AREAS, JURISDICTIONAL WATERS OF THE STATE, AREAS OF THREATENED/ENDANGERED SPECIES, OR AREAS OF HISTORICAL SIGNIFICANCE. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO CONTACT THE APPROPRIATE REGULATORY AGENCY FOR APPROVALS.
4. ALL SILT BARRIERS MUST BE PLACED AS ACCESS IS OBTAINED DURING CLEARING. NO GRADING SHALL BE DONE UNTIL SILT BARRIER INSTALLATION IS CONSTRUCTED. SILT BARRIERS TO BE PLACED AS SHOWN AND/OR AS DIRECTED BY CONTRACTING OFFICER AND/OR LOCAL MUNICIPALITY INSPECTOR. NOTIFY INSPECTOR 24 HOURS PRIOR TO CONSTRUCTION. ALL EROSION AND SEDIMENTATION CONTROLS, AND TREE PROTECTION MEASURES SHALL BE INSTALLED PRIOR TO GRADING. ACCEPTED PLANS AND SUBSEQUENT ACCEPTED REVISIONS MUST BE PRESENT ON-SITE AT ALL TIMES.
304830B
01/29/2025
W
W W
G
G
E
E
E
E
E
E
G
G
G
G
UC
OM
UCOM
UCOM
UCOM
UCOM
UCOM
UCOM
UC
OM
UC
OM
UCOM
UCOM
UCOM
UCOM
UCOM
UCOM
UC
OM
W
W
UCOM
UCOM
UCOM
UCOM UCOM
UCOM
UCOM
UCOM
W
W
W
W
W
W
WW
E
E
E
E
E
E
E
E
E
W
S
S
S
S
S
5"
4"
LAFAYETTE BLVD
WILLIS STREET
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
NAME OF PARK
1/
/2
:2 1:
A
M
J.D
J.D
01/29/2025
C.J
1/
/2
:2 1:
A
M
EXISTING CONDITIONS AND
DEMOLITION PLANC100
4 11
FREDERICKSBURG VISITOR CENTER
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
LEGEND
EXISTING WATER LINE
EXISTING CONTOUR
BRICK PAVER HATCH
304830B
REMOVE ±5 LF OF FENCE
SAW CUT ASPHALT FOR TRENCH
REMOVE BRICK PAVERS
TREE TO BE REMOVED
TREE PROTECTION FENCE
TREE PROTECTION FENCE
REMOVE ±5 LF OF CURB
REMOVE ±20 SF OF CONCRETE SIDEWALK
SAW CUT ASPHALT FOR PIPE TRENCHING
PAVING TO BE REMOVED
STRUCTURE TO BE REMOVED
DEMOLITION NOTES:
1. TREE PROTECTION FENCE SHALL BE PLACED ALONG LIMITS OF DISTURBANCE
AROUND ANY LARGE TREES WHOSE TRUNK OR ROOTS MAY BE IMPACTED BY
STOCKPILING MATERIALS, OR BEING DRIVEN OVER REPEATEDLY THE ALONG
THE PERIMETER AND THROUGHOUT THE DISTURBED AREA.
2. INCLUDE MEASURES FOR ROOT PROTECTION DURING TRENCHING (GIVING
CLEAN CUTS TO LARGE ROOTS, KEEPING CUT ROOTS COVERED/ MOIST UNTIL
SOIL IS PUT BACK IN).
3. ALL VEHICLES, EQUIPMENT, TOOLS, ETC. MUST BE CLEAN BEFORE ENTERING
PARK LANDS TO PREVENT SPREAD OF NON-NATIVE, INVASIVE PLANTS AND
OTHER PESTS.
W
W W
G
G
E
E
E
E
E
E
G
G
G
G
UC
OM
UCOM
UCOM
UCOM
UCOM
UCOM
UCOM
UC
OM
UC
OM
UCOM
UCOM
UCOM
UCOM
UCOM
UCOM
UC
OM
W
W
UCOM
UCOM
UCOM
UCOM UCOM
UCOM
UCOM
UCOM
W
W
W
W
W
W
WW
E
E
E
E
E
E
E
E
E
W
LAFAYETTE BLVD
WILLIS STREET
F
F
F
F
F
F
F
F
F
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
NAME OF PARK
1/
/2
:2 1:
A
M
J.D
J.D
01/29/2025
C.J
1/
/2
:2 1:
A
M
UTILITY AND EROSION PLANC101
5 11
LEGEND
FIRE LINE
UTILITY NOTES:
1. BACKFILL MATERIAL FOR ALL UTILITY LINES SHALL CONSISTS
OF CLEAN SOIL FREE FROM ROCKS AND STONES, EXTENDING
AT LEAST 12" FROM THE OUTER EDGES OF THE WATER LINES.
2. CONTRACTOR SHALL AVOID THE DISTURBANCE OF ANY
EXISTING UTILITY LINE THAT IS NOT OTHERWISE NOTED AS
BEING DISTURBED DURING CONSTRUCTION.
3. 4-6" OF WEED SEED TOPSOIL SHOULD BE PLACE ON TOP OF
BACKFILL.
4. IF EROSION CONTROL MATTING/ BLANKETS ARE USED, USE
NATURAL FIBER PRODUCTS (NOT PLASTIC).
5. NPS APPROVED SEED MIXES SHOULD BE USED FOR
REVEGETATION.
6. ALL VEHICLES, EQUIPMENT, TOOLS, ETC. BEING CLEAN BEFORE
ENTERING PARK LANDS TO PREVENT SPREAD OF NON-NATIVE,
INVASIVE PLANTS AND OTHER PESTS.
WALL PENETRATION SEE DETAIL 3 ON
SHEET C500. SEE FIRE PROTECTION
PLANS FOR CONTINUATION
PROPOSED 6" PVC
UNDERGROUND FIRE MAIN
EXISTING 16" PUBLIC
WATER MAIN
EXISTING DROP INLET
EXISTING TRANSFORMER
EXISTING 8" PUBLIC
WATER MAIN
6" VALVE
F
VALVE
FREDERICKSBURG VISITOR CENTER
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
TAPPING SLEEVE
PROPOSED 16"X6"
TAPPING SLEEVE
LIMITS OF DISTURBANCE
LIMITS OF DISTURBANCE
EXISTING FENCE TO BE REMOVED AND
REPLACED FOR PROPOSED FIRE LINE
REPLACE PORTION OF CONCRETE SIDEWALK
304830B
SO
TS
SO
IP
TREE PROTECTION FENCE
PRACTICE DETAIL DESCRIPTIONMAP
SYMBOL
EROSION CONTROL LEGEND
CODE
REPLACE ASPHALT AND
CONCRETE CURB
TREE PROTECTION FENCE
PROPOSED ASPHALT
PROPOSED CONCRETE
PROPOSED PAVERS
AVOID CONFLICTS WITH EXISTING UTILITIES
DURING INSTALLATION OF FIRE LINE
REPLACE BRICK PAVERS
REPLACE BRICK PAVERS
01/29/2025
BOOKSTORE
DOMESTIC WATER LINE
cloveall Line cloveall Line cloveall Line cloveall Line
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
NAME OF PARK
1/
/2
:2 1:
A
M
J.D
J.D
01/29/2025
C.J
CONSTRUCTION DETAILS
1 OF 2C500
FREDERICKSBURG VISITOR CENTER
6 11FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
304830B
NOT TO SCALE
PIPE SLEEVE THROUGH GROUT WALL DETAIL
NOT TO SCALE
PIPE SLEEVE THROUGH WALL DETAIL
NOTES:
FOR INTERIOR WALLS AND BELOW GRADE GROUND TO
GROUND WALLS.
NOTES:
FOR INTERIOR WALLS AND BELOW GRADE
GROUND TO GROUND WALLS.
ANCHOR LUGS (MIN.3 REQ'D)
PIPE SLEEVE
FIRE RESISTANT SILICONE
FOAM SEALER
POURED CONCRETE OR C.M.U
WALL
CUT OPENING IN EXISTING
MASONRY WALL LARGER THAN
SLEEVE AND FORM & FILL WITH
EXPENSIVE TYPE GROUT
ESCUTCHEON PLATE ONE ONE
OR BOTH SIDES WHERE PIPE IS
EXPOSED
PIPE INSTALLATION WHERE
REQ'D
PIPE
PIPE SLEEVE
POURED CONCRETE OR C.M.U. WALL
ESCUTCHEON PLATE ONE ONE OR BOTH SIDES WHERE PIPING IS
EXPOSED
PIPE INSTALLATION WHERE REQ'D
PIPE
ANCHOR LUGS (MIN. 3 REQ'D)
FIRE RESISTANT SILICONE
FOAM SEALER
C500
C500
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
NAME OF PARK
1/
/2
:2 1:
A
M
J.D
J.D
01/29/2025
C.J
CONSTRUCTION DETAILS
2 OF 2C501
7 11FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
304830B
FREDERICKSBURG VISITOR CENTER
EXHIBIT
ROOM
BOILER
ROOM
STORAGE
ROOM
CONFERENCE
AREA
MENS
RESTROOM
WOMENS
RESTROOM
B01
B07 B06
B09
B05
B02 B03
B04
B08
UP
FX501
FIRE PROTECTION SYSTEM LEAD IN
PROVIDE UPRIGHT SPRINKLERS
FOR BOILER AND STORAGE
ROOM AREAS. COORDINATE
SPRINKLER PLACEMENT
AROUND OBSTRUCTIONS FROM
EXISTING EQUIPMENT
PROVIDE SIDEWALL
SPRINKLERS FED FROM
STORAGE ROOM FOR
CONFERENCE AREA PROVIDE SIDEWALL SPRINKLERS FED
FROM BOILER ROOM FOR EXHIBIT AREA
CONSTRUCT NEW FIRE SPRINKLER RISER
ROOM IN EXISTING WOMENS RESTROOM.
PROVIDE SIDEWALL SPRINKLERS FOR
WOMENS RESTROOM FED FROM NEW
SPRINKLER RISER ROOM. SEE A101
PROPOSED SPRINKLER MAIN
LOCATION.
PROPOSED SPRINKLER MAIN LOCATION. MAINTAIN
HEADROOM IN STAIRCASE. LOCATE SPRINKLER
MAIN TO MINIMIZE IMPACT ON EXISTING SPACE
PROVIDE SIDEWALL SPRINKLERS
FED FROM STORAGE ROOM FOR
MENS RESTROOM
TO FIRE DEPARTMENT CONNECTION
TO BACKFLOW PREVENTER TEST HEADER
LIGHT HAZARD
0.10 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
ORDINARY HAZARD, GROUP 1
0.15 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
FIRE PROTECTION LEGEND FIRE PROTECTION NOTES
1. SEE SHEET FX501 FOR FIRE PROTECTION SYSTEM NOTES
AND DETAILS.
2. PAINT ALL EXPOSED SPRINKLER PIPING TO MATCH THE
EXISTING ADJACENT CEILING OR WALL COLOR. PAINT
COLOR MUST BE APPROVED BY THE COR.
3. SPRINKLER PIPE MUST NOT PENETRATE THE CROWN
MOLDING UNLESS APPROVED BY THE COR IN ORDER TO
PRESERVE HISTORIC ELEMENTS OF THE BUILDING.
4. THE BUILDING IS A MUSEUM EXHIBIT SPACE. ALL
OBJECTS/ARTIFACTS MUST BE PROTECTED FROM
POTENTIAL DAMAGE DURING INSTALLATION - PROTECT IN
PLACE, TEMPORARILY REMOVE, ETC. THE CURATOR MUST
REVIEW ALL TYPES OF EQUIPMENT WELL IN ADVANCE OF
INSTALLATION SCHEDULE IN ORDER TO MITIGATE
VIBRATION. CURATOR MUST NOTIFY LENDERS OF FUTURE
CONSTRUCTION PROJECT AND COMPLY WITH THEIR
PREFERENCE TO PROTECT OBJECTS/ARTIFACTS. COSTS
MAY BE ASSOCIATED WITH MOVING OBJECTS. IF
OBJECTS/ARTIFACTS WILL BE PROTECTED IN PLACE,
DISPLAY CASES OR VENTS SHOULD BE SEALED TO CATCH
DUST. CASE INTERIORS SHOULD BE CLEANED BEFORE
REINSTALLING OBJECTS. IF UTILITY SERVICES SUCH AS
HVAC NEED TO TO BE OR ARE INADVERTENTLY
INTERRUPTED, A TEMPORARY SOLUTION NEEDS TO BE
FOUND.
FX101
1 BASEMENT FIRE PROTECTION PLAN
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
BOWMAN FIRE &
LIFE SAFETY, INC.
JOHNS CREEK,
GEORGIA
LOCATION WITHIN PARK
NAME OF PARK
1/
/2
3:
:5
PM BASEMENT FIRE
PROTECTION PLANFX101
01/29/2025
D. BROWN
H. SIMPSON
D. FISHER
8 11
304830B
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
SCALE: 1/4" = 1'-0"
0 2' 4' 8'
FREDERICKSBURG VISTOR CENTER
LECTURE
LOBBY
INFORMATION
EXHIBIT
ROOM
LIBRARY 102
UP
DN
FIRE PROTECTION SYSTEM RISER FROM BASEMENT
PROVIDE SIDEWALL SPRINKLERS
FROM LOBBY FOR LECTURE ROOM
PROVIDE SIDEWALL SPRINKLERS FROM
LOBBY FOR EXHIBIT AREA
PROPOSED SPRINKLER MAIN
LOCATION.
PROVIDE SIDEWALL SPRINKLERS
FROM LECTURE ROOM FOR LIBRARY
FIRE DEPARTMENT CONNECTION(2.5" NST CONNECTIONS)
PROPOSED SPRINKLER MAIN
LOCATION. PAINT SPRINKLER MAIN TO
MATCH EXISTING WALL FINISH.
PROVIDE SIDEWALL SPRINKLERS FROM
LOBBY FOR LOUNGE ROOM (102)
BACKFLOW PREVENTER TEST HEADER (2.5" NST CONNECTIONS)
FX501
LIGHT HAZARD
0.10 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
ORDINARY HAZARD, GROUP 1
0.15 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
FIRE PROTECTION LEGEND FIRE PROTECTION NOTES
1. SEE SHEET FX501 FOR FIRE PROTECTION SYSTEM NOTES
AND DETAILS.
2. PAINT ALL EXPOSED SPRINKLER PIPING TO MATCH THE
EXISTING ADJACENT CEILING OR WALL COLOR. PAINT
COLOR MUST BE APPROVED BY THE COR.
3. SPRINKLER PIPE MUST NOT PENETRATE THE CROWN
MOLDING UNLESS APPROVED BY THE COR IN ORDER TO
PRESERVE HISTORIC ELEMENTS OF THE BUILDING.
4. THE BUILDING IS A MUSEUM EXHIBIT SPACE. ALL
OBJECTS/ARTIFACTS MUST BE PROTECTED FROM
POTENTIAL DAMAGE DURING INSTALLATION - PROTECT IN
PLACE, TEMPORARILY REMOVE, ETC. THE CURATOR MUST
REVIEW ALL TYPES OF EQUIPMENT WELL IN ADVANCE OF
INSTALLATION SCHEDULE IN ORDER TO MITIGATE
VIBRATION. CURATOR MUST NOTIFY LENDERS OF FUTURE
CONSTRUCTION PROJECT AND COMPLY WITH THEIR
PREFERENCE TO PROTECT OBJECTS/ARTIFACTS. COSTS
MAY BE ASSOCIATED WITH MOVING OBJECTS. IF
OBJECTS/ARTIFACTS WILL BE PROTECTED IN PLACE,
DISPLAY CASES OR VENTS SHOULD BE SEALED TO CATCH
DUST. CASE INTERIORS SHOULD BE CLEANED BEFORE
REINSTALLING OBJECTS. IF UTILITY SERVICES SUCH AS
HVAC NEED TO TO BE OR ARE INADVERTENTLY
INTERRUPTED, A TEMPORARY SOLUTION NEEDS TO BE
FOUND.
FX102
1 FIRST FLOOR FIRE PROTECTION PLAN
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
BOWMAN FIRE &
LIFE SAFETY, INC.
JOHNS CREEK,
GEORGIA
LOCATION WITHIN PARK
NAME OF PARK
1/
/2
3:
:1
PM FIRST FLOOR FIRE
PROTECTION PLANFX102
01/29/2025
D. BROWN
H. SIMPSON
D. FISHER
9 11
304830B
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
SCALE: 1/4" = 1'-0"
LUNCH
OFFICE
CORRIDOR
OFFICEOFFICE
DN
FIRE PROTECTION SYSTEM RISER FROM
SECOND FLOOR. SPRINKLERS ON THIRD FLOOR
ARE TO BE PENDENT TYPE. LOCATE SPRINKLER
MAIN IN ATTIC.
PROVIDE SIDEWALL SPRINKLERS FROM
CORRIDOR FOR LIBRARY AND OFFICE
PROPOSED SPRINKLER MAIN
LOCATION. PAINT SPRINKLER MAIN TO
MATCH EXISTING WALL FINISH.
PROVIDE SIDEWALL SPRINKLERS FROM
CORRIDOR FOR LUNCH ROOM AND CLOSETS
LIGHT HAZARD
0.10 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
ORDINARY HAZARD, GROUP 1
0.15 GPM/SF OVER HYDRAULICALLY
MOST REMOTE 1,500 SF
FIRE PROTECTION LEGEND FIRE PROTECTION NOTES
1. SEE SHEET FX501 FOR FIRE PROTECTION SYSTEM NOTES
AND DETAILS.
2. PAINT ALL EXPOSED SPRINKLER PIPING TO MATCH THE
EXISTING ADJACENT CEILING OR WALL COLOR. PAINT
COLOR MUST BE APPROVED BY THE COR.
3. SPRINKLER PIPE MUST NOT PENETRATE THE CROWN
MOLDING UNLESS APPROVED BY THE COR IN ORDER TO
PRESERVE HISTORIC ELEMENTS OF THE BUILDING.
4. THE BUILDING IS A MUSEUM EXHIBIT SPACE. ALL
OBJECTS/ARTIFACTS MUST BE PROTECTED FROM
POTENTIAL DAMAGE DURING INSTALLATION - PROTECT IN
PLACE, TEMPORARILY REMOVE, ETC. THE CURATOR MUST
REVIEW ALL TYPES OF EQUIPMENT WELL IN ADVANCE OF
INSTALLATION SCHEDULE IN ORDER TO MITIGATE
VIBRATION. CURATOR MUST NOTIFY LENDERS OF FUTURE
CONSTRUCTION PROJECT AND COMPLY WITH THEIR
PREFERENCE TO PROTECT OBJECTS/ARTIFACTS. COSTS
MAY BE ASSOCIATED WITH MOVING OBJECTS. IF
OBJECTS/ARTIFACTS WILL BE PROTECTED IN PLACE,
DISPLAY CASES OR VENTS SHOULD BE SEALED TO CATCH
DUST. CASE INTERIORS SHOULD BE CLEANED BEFORE
REINSTALLING OBJECTS. IF UTILITY SERVICES SUCH AS
HVAC NEED TO TO BE OR ARE INADVERTENTLY
INTERRUPTED, A TEMPORARY SOLUTION NEEDS TO BE
FOUND.
FX103
1 SECOND FLOOR FIRE PROTECTION PLAN
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
BOWMAN FIRE &
LIFE SAFETY, INC.
JOHNS CREEK,
GEORGIA
LOCATION WITHIN PARK
NAME OF PARK
1/
/2
3:
:3
PM SECOND FLOOR FIRE
PROTECTION PLANFX103
01/29/2025
D. BROWN
H. SIMPSON
D. FISHER
10 11
304830B
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
SCALE: 1/4" = 1'-0"
FIRE PROTECTION NOTES
1. THE CONTRACTOR MUST DEVELOP SHOP DRAWINGS FOR A
HYDRAULICALLY DESIGNED SYSTEM BASED ON THESE DRAWINGS. THE
SYSTEM MUST BE A WET PIPE SYSTEM IN ACCORDANCE WITH NFPA 13, THE
SPECIFICATIONS, AND THE SCOPE OF WORK DOCUMENTS FOR THE AREAS
ON THESE DRAWINGS.
2. CONTRACTOR MUST PROVIDE ALL NECESSARY AUXILIARY DRAINS AND
INSPECTORS' TEST CONNECTIONS AS REQUIRED BY NFPA 13. INSPECTORS'
TEST CONNECTIONS MUST BE LOCATED AT THE MOST REMOTE BRANCH
LINE. INSPECTORS' TEST CONNECTIONS DRAINS MUST DISCHARGE TO A
SAFE LOCATION OUTSIDE THE BUILDING.
3. CONTRACTOR MUST PROVIDE ALL NECESSARY PIPE HANGERS AND
SUPPORTS AS REQUIRED BY NFPA 13.
4. THE FIRE ALARM SYSTEM IS AN EXISTING TO REMAIN SILENT KNIGHT
SK-5208 FIRE ALARM CONTROL UNIT. THE FIRE ALARM CONTROL PANEL IS
LOCATED IN THE BASEMENT BOILER ROOM (B03).
5. ALL WATERFLOW SWITCHES MUST BE CONNECTED TO THE FIRE ALARM
SYSTEM BY THE FIRE ALARM CONTRACTOR.
6. ALL VALVES CONTROLLING WATERFLOW TO THE SPRINKLER SYSTEM MUST
BE PROVIDED WITH TAMPER SWITCHES TO BE CONNECTED TO THE FIRE
ALARM SYSTEM BY THE FIRE ALARM CONTRACTOR.
7. ALL PENETRATIONS THROUGH FIRE-RESISTANT ASSEMBLIES MUST BE
PROTECTED BY A UL-LISTED THROUGH-PENETRATION FIRESTOP SYSTEM.
ALL PENETRATIONS THROUGH SMOKE PARTITIONS MUST BE SEALED WITH
NON-COMBUSTIBLE MATERIAL.
8. CONTRACTOR MUST BE RESPONSIBLE FOR AVOIDING ALL CONFLICTS WITH
LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS, CABLE TRAYS, CABLE
BUNDLES, CONDUIT, UTILITY PIPING AND ALL OTHER OBSTRUCTIONS
ENCOUNTERED.
9. CONTRACTOR MUST VERIFY ELEVATIONS AND LOCATIONS OF NEW
SPRINKLER PIPING AND EQUIPMENT PRIOR TO INSTALLATION.
10. CONTRACTOR MUST TAKE ALL NECESSARY MEASURES TO KEEP THE
PREMISES DRY AT ALL TIMES AND TO PREVENT WATER DAMAGE.
CONTRACTOR MUST REPAIR WATER DAMAGE RESULTING FROM THE WORK,
WHETHER INTENTIONAL OR NOT, AT NO COST TO, AND TO THE
SATISFACTION OF THE CONTRACTING OFFICER.
11. NEITHER THE CONTRACTING OFFICER NOR THE ENGINEER MUST BE
RESPONSIBLE FOR PROVIDING A SAFE WORKING PLACE FOR THE
CONTRACTOR, SUBCONTRACTORS, OR THEIR EMPLOYEES, OR ANY OTHER
INDIVIDUAL RESPONSIBLE TO THEM FOR THE WORK. THIS RESPONSIBILITY
RESTS SOLELY ON THE CONTRACTOR'S PROJECT SUPERINTENDENT.
12. ALL PIPING IN AREAS WITH SUSPENDED CEILINGS MUST BE CONCEALED
ABOVE CEILINGS. SPRINKLERS WILL BE SIDEWALL TYPE IN AREAS WITH
HARD CEILINGS WHERE POSSIBLE. PROVIDE UPRIGHT SPRINKLERS IN
AREAS WITH EXPOSED CEILINGS.
13. PAINT ALL EXPOSED EXTERIOR FIRE SUPPRESSION SYSTEM PIPES A COLOR
MATCHING ADJACENT WALL FINSHES AND AS APPROVED BY THE NPS COR.
FIRE SUPPRESSION SYSTEM PIPING MUST BE PAINTED WITH AN EPOXY
ENAMEL PAINT.
14. CONTROL VALVES MUST BE PLACED IN LOCATIONS ACCESSIBLE WITHOUT
THE USE OF A STEP LADDER WHEN POSSIBLE.
15. THE CONTRACTOR MUST VERIFY PIPING AND SPRINKLER LOCATIONS IN THE
FIELD PRIOR TO INSTALLATION.
16. ALL EXPOSED SPRINKLER HEADS MUST BE BRASS. CONCEALED HEADS
MUST BE USED WHERE POSSIBLE. COLOR OF CONCEALED HEAD COVER
PLATES MUST BE COORDINATED WITH THE CONTRACTING OFFICER AT
EACH LOCATION.
17. WHERE PRESENT, CONTRACTOR MUST AVOID DISTURBING CROWN
MOLDING.
18. FLOW TEST RESULTS, PERFORMED BY FISHER ENGINEERING ON 04/09/24:
49 PSI STATIC, 46 PSI AT 978 GPM. THE FLOW HYDRANT WAS LOCATED ON
WILLIS ST. THE TEST HYDRANT WAS LOACTED ON THE CORNER OF
LAFAYETTE BLVD & WILLIS ST.
19. BACKFLOW PREVENTER AND FIRE DEPARTMENT HOSE CONNECTION SIZE
AND THREAD PITCH MUST BE VERIFIED WITH A FIRE CODE OFFICAL PRIOR
TO INSTALLATION.
RISER ASSEMBLY
TO FIRE DEPARTMENT
CONNECTION WITH CHECK VALVE.
TO BACKFLOW PREVENTER TEST
HEADER WITH SUPERVISED OS&Y
VALVE (NORMALLY CLOSED).
PROVIDE 2" - 2 1/2" GATED HOSE
VALVES AT EXTERIOR
DOUBLE CHECK BACKFLOW
PREVENTER WITH TAMPER SWITCHES
BASEMENT FLOOR
MAIN DRAIN VALVE. PROVIDE TEST
AND DRAIN ASSEMBLY WITH
PRESSURE RELIEFE. PIPE TO
EXTERIOR OF BUILDING. PROVIDE
SPLASH BLOCK BELOW PIPE OUTLET.
WATERFLOW SWITCH
6-INCH INCOMING
WATER MAIN
TO SPRINKLER SYSTEM
GROUND LEVEL
FREE STANDING FIRE
DEPARTMENT CONNECTION
(2.5" NST CONNECTIONS)
BACKFLOW TEST HEADER (2.5" NST CONNECTIONS)
SCALE: 1" = 1'-0"
0 6" 1' 2'
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
TITLE OF SHEET
A/E FIRM:
PRIME:
BOWMAN FIRE &
LIFE SAFETY, INC.
JOHNS CREEK,
GEORGIA
LOCATION WITHIN PARK
NAME OF PARK
1/
/2
3:
:5
PM DETAILS - FIRE
PROTECTIONFX501
01/29/2025
D. BROWN
H. SIMPSON
D. FISHER
11 11
304830B
FREDERICKSBURG & SPOTSYLVANIA
NATIONAL MILITARY PARK
FX501
1 FIRE PROTECTION RISER DETAIL
FX501
2 FDC AND TEST HEADER
SCALE: 1" = 1'-0"
0 6" 1' 2'