B08_SOL_Attachment_1_-_GWMP_Deficiency_Description_and_Pricing_Sheet_(2).xlsx
XLSX spreadsheet 73 KB Posted
- Attached to
- ARHO - Fire Monitoring Federal contract opportunity
- Solicitation number
- 140D0424Q0621
About this file
This document appears to be a detailed description of fire protection system deficiencies and associated repair/maintenance costs for buildings located along the George Washington Memorial Parkway (GWMP). The deficiencies include items such as the need for 5-year internal pipe examinations, pressure gauge replacements, hydrostatic testing, identification signage, fire alarm system upgrades, and heat detector replacements. The total estimated net cost for addressing these deficiencies across multiple GWMP facilities is $0.00.
The document is related to a federal contract opportunity with Solicitation Number 140D0424Q0621 for "ARHO - Fire Monitoring" issued by the Department of the Interior Departmental Offices Interior Business Center. The contract appears to be for fire and intrusion monitoring with minor repairs at the GWMP facilities.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140D0424Q0621_Amd_0003.pdf | ||
| B08_SOL_ARHO_Fire_Intrusion_Monitoring_-Amendment_3_FE_0003.pdf | ||
| B08_SOL_-_Attachment_1_-140D0424Q0621_0002.pdf | ||
| Attachment_2_-_Pictures_0002.pdf | ||
| B08_SOL_ARHO_Fire_Intrusion_Monitoring_-Amendment_2_FE_0002.pdf | ||
| Sol_140D0424Q0621_Amd_0002.pdf | ||
| B08_SOL_ARHO_Fire_Intrusion_Monitoring_-Amendment_1_FE_0001.pdf | ||
| B08_SOL_Attachment_2_-_SCLS_Form_(2)_0001.docx | DOCX document | |
| Sol_140D0424Q0621_Amd_0001.pdf | ||
| B08_SOL_Attachment_1_-_GWMP_Deficiency_Description_and_Pricing_Sheet_0001.xlsx | XLSX spreadsheet | |
| B08_SOL_Attachment_2_-_SCLS_Form_(1).docx | DOCX document | |
| B08_SOL_ARHO_Fire_Intrusion_Monitoring_FE.pdf | ||
| Sol_140D0424Q0621.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GWMP - 2023
DEFICIENCY COST ESTIMATE
GEORGE WASHINGTON MEMORIAL PARKWAY (GWMP)
Annual
ITM
Date FMSS Bldg # System Asset
| # | Building Name | Deficiency Description | |
| (NOTE: Deficiencies in red are repeat deficiencies which were also cited from ITM performed last year) | Nature of Deficiency | NFPA Reference Standard, Section | RAC |
Work
| Type | Qty | Material Cost | Labor Cost | SubTotal Cost | SubTotal NET Cost | Total NET Cost | |||||||
| 05/12/ | |||||||||||||
| 2023 | 26424 | 1254332 | Great Falls Visitor Center | No difificencies noted. | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 05/12/ | |||||||||||||
| 2023 | 85780 | ????? | Visitor Center Snack Bar | No difificencies noted. | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
05/12/ 2023 26492 1559075 Parkway Maintenance Hq Perform 5-year internal pipe examination of the fire sprinkler system, including alarm/check valves and fire department connection. Cost is per system/zone. FP 25, 13.4.1.2, 13.4.2.1,
| 14.2.1 | FM/DM | |||||||
| Serious | 1 | |||||||
| 05/12/ 2023 | 26492 | 1559075 | Parkway Maintenance Hq | Replace two (2) pressure gauges as part of 5-year maintenance. | FP | 25, | ||
| 5.3.2 | FM/DM | |||||||
| Minor | 2 | |||||||
| 05/12/ 2023 | 26492 | 1559075 | Parkway Maintenance Hq | 5 year hydrostatic test of fire department connection (FDC) piping is due. Perform hydrostatic test of the system as required. | FP | 25, | ||
| 6.3.2.1 | FM/DM | |||||||
| Minor | 1 | |||||||
| 05/12/ 2023 | 26492 | 1559075 | Parkway Maintenance Hq | Provide identification sign for the fire department connection (FDC). FDC is currently not provided with an identification sign. | FP | 25, | ||
| 13.7.1 | FM/DM | |||||||
| Minor | 1 | |||||||
| 05/12/ 2023 | 26492 | 1562544 | Parkway Maintenance Hq | All fifteen (15) heat detectors are 15 years old and are required to be replaced. Heat detectors were tested for integrity and reported to panel. | FA | 72, | ||
| 14.4.3.2 | FM/EM | |||||||
| Serious | 15 | |||||||
| 05/12/ 2023 | 26492 | 1562544 | Parkway Maintenance Hq | The fire alarm control panel in this building is a conventional "Cerberus Pyrotronics System 3" panel. Fire alarm devices report to NPS Dispatch as zones with generic descriptions. The NPS document “National Capital Region Fire Protection Systems Requirements” requires all fire alarm control panels to be addressable type, so that fire alarm devices are programmed as individual points (instead of zones). Install an addressable fire alarm system. | FA | 72, 14.4.3.2 | FM/CR | |
| Serious | 1 |
05/12/ 2023 26493 ???? BLDG #2 Auto & Equipment Repair No fire alarm or sprinkler system preseent in this building. N/A N/A N/A N/A N/A N/A N/A
| 05/12/ 2023 | 26495 | 384441 | BLDG #4 Grounds Operation Storage | Investigate integrity of fire alarm system monitoring. Outside monitoring station failed to receive signals from the fire alarm control panel during testing. Cost is for service call to determine the extent of corrective action. | FA | 72, | |
| 14.4.3.2 | FM/EM | ||||||
| Critical | 1 |
| 05/08/ | ||||||
| 2023 | 26496 | 384441 | BLDG #5-6 Grounds Operation Bldg | Perform 5-year internal pipe examination of the fire sprinkler system, including alarm/check valves and fire department connection. Cost is per system/zone. | FP | 25, |
13.4.1.2, 13.4.2.1,
| 14.2.1 | FM/DM | |||||
| Serious | 1 | |||||
| 05/08/ | ||||||
| 2023 | 26496 | 384441 | BLDG #5-6 Grounds Operation Bldg | Replace (up to 4) pressure gauges as part of 5-year maintenance. | FP | 25, |
| 5.3.2 | FM/DM | |||||
| Minor | 1 | |||||
| 05/08/ | ||||||
| 2023 | 26496 | 384441 | BLDG #5-6 Grounds Operation Bldg | 5 year hydrostatic test of fire department connection (FDC) piping is due. Perform hydrostatic test of the system as required. | FP | 25, |
| 13.8.5 | FM/DM | |||||
| Minor | 1 | |||||
| 05/08/ | ||||||
| 2023 | 26496 | 384441 | BLDG #5-6 Grounds Operation Bldg | Provide identification sign for the fire department connection (FDC). FDC is currently not provided with signage. | FP | 25, |
| 13.7.1 | FM/DM | |||||
| Minor | 1 | |||||
| 05/08/ | ||||||
| 2023 | 26496 | 384441 | BLDG #5-6 Grounds Operation Bldg | Provide an identification tag for the fire sprinkler control valve. Control valve currently not provided with an identification tag. | FP | 25, |
| 13.3.2.2 | FM/LMSF | |||||
| Minor | 1 |
05/12/ 2023 26497 384441 BLDG #7 Roads & Bridges-Tree No deficiencies noted. N/A N/A N/A N/A N/A N/A N/A
05/12/ 2023 26498 384369 BLDG #8 B&U Signs Perform 5-year internal pipe examination of the fire sprinkler system, including alarm/check valves and fire department connection. Cost is per system/zone. FP 25, 13.4.1.2 13.4.2.1
| 14.2.1 | FM/DM | |||||||
| Serious | 1 | |||||||
| 05/12/ 2023 | 26498 | 384369 | BLDG #8 B&U Signs | Replace (up to 4) pressure gauges as part of 5-year maintenance. | FP | 25, | ||
| 5.3.2 | FM/DM | |||||||
| Minor | 4 | |||||||
| 05/12/ 2023 | 26498 | 384369 | BLDG #8 B&U Signs | Wet sprinkler system is not piped outside, which means a main drain test could not be prefromed. Cost is for an inspection to determine the extent of corrective action required. | FP | 25, | ||
| 6.3.2.1 | FM/DM | |||||||
| Serious | 1 | |||||||
| 05/12/ 2023 | 26498 | 384369 | BLDG #8 B&U Signs | Hydraulic nameplate is missing from each of the two (2) sprinkler risers. Provide a hydraulic nameplate for each as required. | FP | 25, | ||
| 5.2.7 | FM/DM | |||||||
| Minor | 2 | |||||||
| 05/12/ 2023 | 26498 | 384441 | BLDG #8 B&U Signs | Replace/repair valve water flow switch. Valve water flow switch failed to report to panel when tested. | FP | 13, | ||
| 6.9.2.1 | FM/EM | |||||||
| Critical | 1 | |||||||
| 05/12/ 2023 | 26498 | 384441 | BLDG #8 B&U Signs | Replace/repair valve tamper switch. Valve tamper switch failed to report to panel when tested. | FP | 25, | ||
| 13.3.2.2 | FM/EM | |||||||
| Critical | 2 | |||||||
| 05/12/ 2023 | 26498 | 384441 | BLDG #8 B&U Signs | All sixteen (16) heat detectors are 15 years old and are required to be replaced. Heat detectors were tested for integrity and reported to panel. | FA | 72, | ||
| 14.4.3.2 | FM/EM | |||||||
| Serious | 16 | |||||||
| 05/12/ 2023 | 26498 | 384441 | BLDG #8 B&U Signs | Replace two (2) 12V, 7A batteries serving the fire alarm control panel. Batteries are over five years old and should be replaced. | FA | 72, | ||
| 14.4.3.2 | FM/DM | |||||||
| Serious | 2 | |||||||
| 05/12/ 2023 | 26498 | 384441 | BLDG #8 B&U Signs | The fire alarm control panel in this building is a conventional "Cerberus Pyrotronics System 3" panel. Fire alarm devices report to NPS Dispatch as zones with generic descriptions. The NPS document “National Capital Region Fire Protection Systems Requirements” requires all fire alarm control panels to be addressable type, so that fire alarm devices are programmed as individual points (instead of zones). Install an addressable fire alarm system. Cost is for system replacement, which covers Buildings #4 through #9 at the GWMP Maintenance Yard. | FA | 72, 14.4.3.2 | FM/CR | |
| Serious | 1 |
| 05/11/ | ||||||
| 2023 | 26499 | Unknown | BLDG #9 President Park/White House | Perform 5-year internal pipe examination of the fire standpipe system, including alarm/check valves and fire department connection. Cost is per system/zone. | FP | 25, |
13.4.1.2 13.4.2.1
| 14.2.1 | FM/DM | |||||
| Serious | 1 | |||||
| 05/11/ | ||||||
| 2023 | 26499 | Unknown | BLDG #9 President Park/White House | Replace (up to 4) pressure gauges as part of 5-year maintenance. | FP | 25, |
| 5.3.2 | FM/DM | |||||
| Minor | 2 | |||||
| 05/11/ | ||||||
| 2023 | 26499 | Unknown | BLDG #9 President Park/White House | Provide identification sign for the fire department connection (FDC). FDC is currently not provided with signage. | FP | 25, |
| 13.7.1 | FM/DM | |||||
| Minor | 1 | |||||
| 05/11/ | ||||||
| 2023 | 26499 | Unknown | BLDG #9 President Park/White House | Hydraulic nameplate is missing from the sprinkler riser. Provide a hydraulic nameplate as required. | FP | 25, |
| 5.2.7 | FM/DM | |||||
| Minor | 2 | |||||
| 05/11/ | ||||||
| 2023 | 26499 | Unknown | BLDG #9 President Park/White House | 5 year hydrostatic test of fire department connection (FDC) piping is due. Perform hydrostatic test of the system as required. | FP | 25, |
| 6.3.2.1 | FM/DM | |||||
| Minor | 1 | |||||
| 05/11/ | ||||||
| 2023 | 26499 | Unknown | BLDG #9 President Park/White House | Provide a spare sprinkler cabinet with a minimum of 6 sprinkler heads and a matching wrench. Spare sprinkler cabinet is currently not provided at this location. | FP | 25, |
| 5.4.1.5 | FM/LMSF | |||||
| Minor | 1 | |||||
| 05/11/ | ||||||
| 2023 | 26499 | Unknown | BLDG #9 President Park/White House | All fifteen (15) heat detectors are 15 years old and are required to be replaced. Heat detectors were tested for integrity and reported to panel. | FA | 72, |
| 14.4.3.2 | FM/EM | |||||
| Serious | 15 |
| 05/12/ | ||||||
| 2023 | 26842 | 316838 | Turkey Run Headquarters-Admin (TRHQ) | Repair/replace notification appliance located "Inside Women's Room by the Lobby (strobe)". Device failed to activate when tested. | FA | 72, |
| 14.4.3.2 | FM/EM | |||||
| Serious | 2 | |||||
| 05/12/ | ||||||
| 2023 | 26842 | 316838 | Turkey Run Headquarters-Admin (TRHQ) | Replace two (2) 12V, 7A batteries serving the fire alarm control panel. Batteries failed the load test. | FA | 72, |
| 14.4.3.2 | FM/DM | |||||
| Serious | 2 |
| 05/14/ | ||||||
| 2023 | 26843 | 224834 | USPP HQ Building | Perform 5-year internal pipe examination of the fire sprinkler system, including alarm/check valves and fire department connection. Cost is per system/zone. | FP | 25, |
13.4.1.2, 13.4.2.1,
| 14.2.1 | FM/DM | ||||||
| Serious | 2 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 1562547 | USPP HQ Building | Replace four (4) pressure gauges as part of 5-year maintenance. | FP | 25, | |
| 5.3.2 | FM/DM | ||||||
| Minor | 5 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 224834 | USPP HQ Building | 5 year hydrostatic test of fire department connection (FDC) piping is due. Perform hydrostatic test of the system as required. | FP | 25, | |
| 6.3.2.1 | FM/DM | ||||||
| Minor | 1 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 1562547 | USPP HQ Building | Perform a 3-year leak test and full flow trip test of the dry pipe sprinkler system. Cost is per system/zone. | FP | 25, 13.4.4.2.9 | FM/DM |
| Serious | 1 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 1562547 | USPP HQ Building | Provide identification sign for the fire department connection (FDC). FDC is currently not provided with signage. | FP | 25, | |
| 13.7.1 | FM/DM | ||||||
| Minor | 1 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 1562547 | USPP HQ Building | Provide an identification tag for the fire sprinkler control valve. Control valve currently not provided with an identification tag. | FP | 25, | |
| 13.3.2.2 | FM/LMSF | ||||||
| Minor | 2 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 1562547 | USPP HQ Building | Replace dry-type sprinkler heads, or send representative samples for testing. Dry-type sprinkler heads were noted to be over 10 years old. Cost is for dry-type sprinkler head replacement. Number of sprinkler heads that require replacement is estimated in the quantity column. | FP | 25, 5.3.1.1.1.6 | FM/EM |
| Serious | 20 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 1562547 | USPP HQ Building | Replace two (2) 12V, 18A outdated batteries serving the fire alarm control panel. Batteries are outdated as they have been in use for over 5 years. | FA | 72, | |
| 14.4.3.2 | FM/DM | ||||||
| Serious | 2 | ||||||
| 05/14/ | |||||||
| 2023 | 26843 | 318474 | USPP HQ Building | System was not tested due to main fire alarm control panel being out of service. Cost is for service call to determine extent of corrective action. | FA | 72, 14.4.3.2 | FM/EM |
| Serious | 1 |
| 05/14/ | |||||||||||
| 2023 | 26869 | ????? | TR-IRRM Ranger Building | No fire alarm or sprinkler systems on site need to move from list | NA | NA | NA | NA | N/A | N/A | N/A |
| 05/11/ 2023 | 27173 | (need asset #) | Clara Barton House | Repair/replace smoke detector. Smoke detector failed to activate alarm/report to the fire alarm control panel when tested. | FA | 72, | |
| 14.4.3.2 | FM/EM | ||||||
| Serious | 2 | ||||||
| 05/11/ 2023 | 27173 | (need asset #) | Clara Barton House | Replace/repair the manual pull station. Manual pull station failed to operate when tested. | FA | 72, | |
| 14.4.3.2 | FM/EM | ||||||
| Serious | 1 | ||||||
| 05/11/ 2023 | 27173 | (need asset #) | Clara Barton House | Perform 5-year internal pipe examination of the fire standpipe system, including alarm/check valves and fire department connection. Cost is per system/zone. | FP | 25, |
13.4.1.2 13.4.2.1
| 14.2.1 | FM/DM | ||||||
| Serious | 1 | ||||||
| 05/11/ 2023 | 27173 | (need asset #) | Clara Barton House | Replace 2 (two) pressure gauges as part of 5-year maintenance. | FP | 25, | |
| 5.3.2 | FM/DM | ||||||
| Minor | 2 | ||||||
| 05/11/ 2023 | 27173 | (need asset #) | Clara Barton House | 5 year hydrostatic test of fire department connection (FDC) piping is due. Perform hydrostatic test of the system as required. | FP | 25, | |
| 6.3.2.1 | FM/DM | ||||||
| Minor | 1 | ||||||
| 05/11/ 2023 | 27173 | (need asset #) | Clara Barton House | Replace two (2) 12V, 7A batteries serving the fire alarm control panel. Batteries are over five years old and should be replaced. | FA | 72, | |
| 14.4.3.2 | FM/DM | ||||||
| Serious | 2 |
| 05/14/ 2023 | 16756 | ????? | Fort Hunt Maintinance Building | Perform immediate investigation of fire alarm system outage. Fire alarm system is currently out of service, due to not having power. Cost is for a service call to determine the extent of corrective action. | FA | 25, | |
| 5.1.1.2 | FM/EM | ||||||
| Critical | 1 |
05/14/ 2023 27278 ????? USPP - Fort Hunt Stable No alarm system is present. Existing heat detectors should be removed. NA NA NA NA N/A N/A N/A
| 05/14/ 2023 | 39662 | ????? | Fort Hunt Trailer | System was not tested due to main fire alarm control panel being out of service. Cost is for service call to determine extent of corrective action. | FA | 72, 14.4.3.2 | FM/EM | |
| Serious | 1 |
05/18/ 2023 85785 ????? Wahsington Sailing Marina - Indigo Landing & Afterdeck Site is leased and responsible for its own inspections. NA NA NA NA N/A N/A N/A
05/18/ 2023 85787 ????? Wahsington Sailing Marina - Office Site is leased and responsible for its own inspections. NA NA NA NA N/A N/A N/A
| 05/11/ 2023 | 90327 | ????? | Columbia Island Marina Office | Access to a manual pull station in the kitchen is being obstructed by a shelf. Clear a path to the pull station. | FA | 72, | |
| 17.15.9.2 | FM/LMSF | ||||||
| Minor | NA | N/A | N/A | N/A |
PROJECT SUBTOTALS $0.00 $0.00 $0.00 $0.00
PROJECT TOTALS $0.00
Inspection and Testing of the Fire Protection and Life Safety Systems NCR Region August 9, 2022