B08_Attachment_3_-_Drawings_Reference_Only.pdf

PDF 4 MB Posted

Attached to
Eisenhower National Historic Site Federal contract opportunity
Solicitation number
140P4226Q0005
Issued by
Department of the Interior National Park Service Northeast Region

About this file

Summary

This is a set of fire protection construction drawings for the Eisenhower National Historic Site, dated March 3, 2022, prepared by the U.S. Department of the Interior, Northeast Regional Office. The drawings provide comprehensive technical specifications for installing dry pipe sprinkler suppression systems to replace existing fire protection equipment at Farm 1 Barn and Farm 2 Show Barn at the historic site. The scope includes detailed plans, sections, details, and equipment schedules for two separate dry sprinkler systems with nitrogen generators serving approximately 263 gallons (Farm 1) and 424 gallons (Farm 2) of system volume. Both systems utilize quick-response sprinkler heads in various configurations (upright, pendent, and horizontal sidewall types) at specified 5.6 K-factor ratings and temperature ratings of 155°F and 200°F, with a combined total of 244 sprinkler heads across both buildings.

The technical drawings (Sheets F2-F9) include lower-level floor plans, upper-level demolition plans, building sections, details, site plans, staging plans, and system riser diagrams. Key equipment specifications indicate use of existing 6-inch water services with backflow preventers, Viking brand dry valve assemblies for Farm 1, and Tyco nitrogen generators for both locations. The drawings establish detailed hydraulic calculations showing design densities of 0.12 and 0.13 gallons per minute per square foot for light hazard occupancies, with system safety factors of 6.5 PSI. Installation requirements mandate compliance with NFPA 13 standards, coordination with the contracting officer prior to pipe installation, appropriate drain placement for complete system drainage, and intermediate temperature-rated sprinkler heads in mechanical and electrical spaces. Contractor staging areas are defined on aerial photographs, and detailed construction specifications address penetrations, hangers, connections, and testing protocols.

View the file

Other files for this federal contract opportunity

Other files attached to Eisenhower National Historic Site, newest first.
File Type Posted
Site_Visit_Sign_In-EISE_Fire_Suppression_Repairs_0002.pdf PDF
B08_Attachment_7_-_140P4226Q0005_Project_Experience_0002.docx DOCX document
Sol_140P4226Q0005_Amd_0002.pdf PDF
Sol_140P4226Q0005_Amd_0001.pdf PDF
Sol_140P4226Q0005.pdf PDF
B08_Attachment_1_-_EISE_Barns_Fire_Suppression_Repairs_SOW_V_2.pdf PDF
B08_Attachment_6_-_Q_A_Document.xlsx XLSX spreadsheet
B03_Attachment_4_-_WD_PA20260073.pdf PDF
B08_Attachment_2_-_Specifications_Reference_Only.pdf PDF
B08_Attachment_5_-_Subcontracting_Percentage_Worksheet.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

R

O

A

D

P

U

M

P

I

N

G

R

O

B

E

R

T

A

F

A

M

A

D

E

I

S

E

N

H

O

W

E

R

BUS

M

A

R

S

H

C

R

E

E

K

FARM #2

W

I

L

L

O

U

G

H

B

Y

FARM #4

S

T

A

T

I

N

A

D

S

C

O

T

T

R

O

A

D

R

O

C

K

FARM

#1

R

E

D

R

O

A

D

R

U

N

W

A

Y

E

I

S

E

N

H

O

W

E

D

I

V

E

R

I

D

G

E

W

E

S

T

C

N

F

E

D

E

R

A

T

E

A

V

E

E

M

M

I

T

S

B

U

G

A

D

FARM #3

P

I

L

Z

E

S

U

N

T

A

V

E

A

D

VISITOR CENTER

HEADQUARTERS &

GETTYSBURG N.M.P.

M

I

L

L

E

R

S

T

O

W

N

R

O

A

D

BUS

TO

V.C.

LEGEND

HQ.

GETTYSBURG N.M.P.

INFORMATION CENTER

PARK HEADQUARTERS

VISITOR CENTER

RANGER STATION

CREEK OR RIVER

UNPAVED ROAD

PARK BOUNDARY

STATE LINE

HQ.

SCALE OF

MILES

10 0 10

PENNSYLVANIA

V

I

R

G

I

N

I

A

W

E

S

T

P

E

N

N

S

Y

L

V

A

N

I

A

MARYLAND

PENNSYLVANIA

M

O

N

O

C

A

C

Y

I

V

E

R

CHESAPEAKE

BALTIMORE

FREDERICK

P

O

T

O

M

A

C

V

I

R

G

I

N

I

A

70S

R

I

V

E

R

M

A

R

Y

L

A

N

D

70N

BAY

MARYLAND

PENNSYLVANIA

YORK

HARRISBURG

SITE

HISTORIC

NATIONAL

EISENHOWER

HAGERSTOWN

T

U

R

N

P

I

K

E

GETTYSBURG

EISENHOWER NATIONAL HISTORIC SITE

B

A

R

N

HOUSE

L

O

A

F

I

N

G

S

H

E

D

HOUSE

C

R

I

B

C

O

R

N

B

A

R

N

PROJECT SITE

FARM 1 BARN

PROJECT SITE

FARM 2

SHOW BARN

M S N

D R A W I N G S F I R E

P R O T E C T I O N F

F I R E

P R O T E C T I O N

C O V E R

S H E E T D W G

P M

PROJECT SITE

FARM 1 BARN

PROJECT SITE

FARM 2

SHOW BARN

3/3/2022

AC - AIR COMPRESSOR

ACC - ACCESS

ACV - ALARM CHECK VALVE

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

ALT - ALTERNATE

AHJ - AUTHORITY HAVING

JURISDICTION

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECTURAL

ASSY - ASSEMBLY

ATS - AUTOMATIC TRANSFER SWITCH

BLDG - BUILDING

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BTWN - BETWEEN

CFCI - CONTRACTOR FURNISHED

CONTRACTOR INSTALLED

CL - CENTERLINE

CLG - CEILING

CONN - CONNECTION / CONNECT

CONTR - CONTRACTOR

CORR - CORRIDOR

CU - COPPER

D - DRAIN LINE

DCBP - DOUBLE CHECK

BACKFLOW PREVENTER

DDBP - DOUBLE DETECTOR

BACKFLOW PREVENTER

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DN - DOWN

DSPR - DRY SPRINKLER PIPE

DWG - DRAWING

EA - EACH

ELEV - ELEVATION

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EXT - EXTERIOR

F - FIRE SUPPLY

FACP - FIRE ALARM CONTROL PANEL

FDC - FIRE DEPARTMENT CONNECTION

FDV - FIRE DEPARTMENT VALVE

FHC - FIRE HOSE CABINET

FHR - FIRE HOSE RACK

FLR - FLOOR

FMG - FACTORY MUTUAL GLOBAL

FPC - FIRE PUMP CONTROLLER

FPTH - FIRE PUMP TEST HEADER

FS - FLOW SWITCH

FT - FEET

FTG - FOOTING

FVC - FIRE VALVE CABINET

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GPM - GALLONS PER MINUTE

HD - HUB DRAIN

IBC - INTERNATIONAL BUILDING CODE

ID - INSIDE DIAMETER

IE - INVERT ELEVATION

IFC - INTERNATIONAL FIRE CODE

IN - INCHES

JP - JOCKEY PUMP

JPC - JOCKEY PUMP CONTROLLER

L - LENGTH

LBS - POUNDS

MAX - MAXIMUM

MEZZ - MEZZANINE

MFR - MANUFACTURER

MIN - MINIMUM

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

NC - NORMALLY CLOSED

NFPA - NATIONAL FIRE PROTECTION

ASSOCIATION

NO - NORMALLY OPEN

NOM - NOMINAL

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OC - ON CENTER

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED

CONTRACTOR INSTALLED

OFOI - OWNER FURNISHED

OWNER INSTALLED

PIV - POST INDICATOR VALVE

PLBG - PLUMBING

PRESS - PRESSURE

PRV - PRESSURE REDUCING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSIG - POUNDS PER SQUARE INCH

GAUGE

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH-IN

RPM - REVOLUTIONS PER MINUTE

RPBP - REDUCED PRESSURE ZONE

BACKFLOW PREVENTER

RV - RELIEF VALVE

SCH - SCHEDULE

SHT - SHEET

SPEC - SPECIFICATION

SPR - SPRINKLER

SQ - SQUARE

S/S - STAINLESS STEEL

STRU - STRUCTURAL / STRUCTURE

TEMP - TEMPERATURE

TC - TEST CELL

TOB - TOP OF BEAM

TOD - TOP OF DECK

TOJ - TOP OF JOIST

TOS - TOP OF SLAB / TOP OF STEEL

TYP - TYPICAL

UBC - UNIFORM BUILDING CODE

UFC - UNIFORM FIRE CODE

UNO - UNLESS NOTED OTHERWISE

V - VALVE

VEL - VELOCITY

VESDA - VERY EARLY SMOKE

DETECTION APPARATUS

VOL - VOLUME

W - WIDTH

W/ - WITH

W/O - WITHOUT

ABBREVIATIONS

FIRE PROTECTION SYMBOLS AND ABBREVIATIONS

SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO

NOT APPLY TO THIS PROJECT.

FIRE PROTECTION SYMBOLS

SPRINKLER PIPE TEXT

(TOP INDICATES PIPE SIZE)

(BOTTOM INDICATES

CENTER TO CENTER PIPE

LENGTH)

FIRE HOSE CABINET

SPRINKLER ZONE

BOUNDARY

PIPE HANGER

FHC

PIPE SIZE

PIPE LENGTH

PUMP (FLOOR PLAN)

PUMP (FLOW DIAGRAM)

ECCENTRIC REDUCER

CONCENTRIC REDUCER

TEE UP

TEE DOWN

ELBOW UP

ELBOW DOWN

SUPERVISED BUTTERFLY

VALVE

SHUTOFF VALVE (SUPERVISED)

CHECK VALVE

PIPE CAP OR FLUSHING

CONNECTION

PIPE SLEEVE

PRESSURE GAUGE

(WITH GAUGE VALVE)

FLOW SWITCH

FIRE SUPPLYF

DRY SPRINKLER PIPE

DSPR

PREACTION SPRINKLER PIPEPSPR

CLEAN AGENT SYSTEMCA

WATER SERVICEW

VALVE IN VERTICAL

REDUCED PRESSURE

BACKFLOW PREVENTER

(RPBP)

DOUBLE CHECK

BACKFLOW PREVENTER

(DCBP)

SUPERVISED OS&Y VALVE

SUPERVISED POST

INDICATOR VALVE (PIV)

ALARM CHECK VALVE

INSPECTOR'S TEST AND

DRAIN ASSEMBLY

INSPECTOR'S TEST

ASSEMBLY

ROOFTOP TEST HEADER

FIRE DEPARTMENT VALVE

STORZ CONNECTION

FLUSH MOUNTED CONNECTION

WALL MOUNTED

CONNECTION

DRY PIPE VALVE ASSEMBLY

PREACTION VALVE ASSEMBLY

DELUGE VALVE ASSEMBLY

SPRINKLER ZONE CONTROL

VALVE ASSEMBLY

FIRE HOSE RACK

FHR

FIRE VALVE CABINET

FVC

EXISTING VALVE CABINET

EVC

BUTTERFLY VALVE

DRAIN LINED

SPRINKLER PIPESPR

SHEET SYMBOLS

A/15B-6

SPECIALTY ITEMS

(I.E. GAUGE FILTER, ETC.)

REFER TO EQUIPMENT LIST

M-1

ROOM NAME & NUMBER

DESIGNATION

SECTION DESIGNATION.

-TOP INDICATES SECTION NUMBER,

-BOTTOM INDICATES ON WHICH

SHEET SECTION APPEARS

MATCHLINE

DESIGNATION

DETAIL REFERENCE.

-TOP INDICATES SECTION NUMBER,

-BOTTOM INDICATES ON WHICH

SHEET SECTION APPEARS

REVISION REFERENCE.

REFER TO SHEET REVISION

BLOCK

SHEET KEYNOTE REFERENCE

PLAN CONTINUATION REFERENCE.

-BOTTOM INDICATES ON WHICH

SHEET CONTINUATION APPEARS

CONSTRUCTION BULLETIN

REVISION NUMBER

SCHEDULED EQUIPMENT DESIGNATION.

-TOP INDICATES EQUIPMENT

ABBREVIATION

-BOTTOM INDICATES EQUIPMENT

NUMBER

REFER TO EQUIPMENT SCHEDULES

ELEVATION DESIGNATION.

REFERENCE OFFICIAL

PROJECT DATUM

EQ

POINT OF NEW

CONNECTION TO EXISTING

REFER

M-1

M-1

DETAIL REFERENCE.

-TOP INDICATES SECTION NUMBER,

-BOTTOM INDICATES ON WHICH

SHEET SECTION APPEARS

ROOM NAME

HALFTONE LIGHT LINE

INDICATES EXISTING WORK

HEAVY DASHED LINE WITH

HATCH INDICATES

EXISTING WORK TO BE

DEMOLISHED

HEAVY LINE INDICATES

NEW WORK

HYDRAULIC ZONE

BOUNDARY

CLEAN AGENT EXTINGUISHING

SYSTEM

CAES

DELUGE SPRINKLER SYSTEMDELS

HANGER SPACING

STEEL PIPE*

N/A

1"

12-0

12-0

15-0

2"

15-0

15-0

3"

15-0

15-0

4"

15-0

5"

15-0

6"

15-0

8"

15-0

*EXCEPT THREADED LIGHTWALL PIPE

REFER TO DRAWING SPRINKLER HEAD LEGEND FOR TYPE

DRY PENDENT SPRINKLER

SPRINKLER HEAD SYMBOLS

WHITE 5.6 200° F 27

FINISH K-FACTOR TEMP. QTY.SPRINKLER TYPESYMBOL

DRY HORIZONTAL SIDEWALL SPRINKLER WHITE 5.6 155° F 7

QR

RESPONSE

QR

UPRIGHT SPRINKLER WHITE 5.6 200° F 197

QR

WHITE 5.6 155° F 13 QRDRY PENDENT SPRINKLER WITH ESCUTCHEON

TR1

DV1

BR1

BFD

UG

FIRE PROTECTION EQUIPMENT

1 EXISTING 6" WATER SERVICE

BACKFLOW PREVENTER WITH BUTTERFLY VALVES & TAMPER SWITCHES

(N.O.)

FDC BYPASS BUTTERFLY VALVE WITH TAMPER SWITCH (N.C.)

4 FDC CHECK VALVE

5 EXISTING FDC TO REMAIN

EXISTING 6" BUTTERFLY VALVE WITH TAMPER SWITCH (N.O.) TO BE REUSED

7 EXISTING 6" VIKING DRY VALVE ASSEMBLY TO BE REUSED

6" BUTTERFLY VALVE WITH TAMPER SWITCH (N.O.)

4" BUTTERFLY VALVE WITH TAMPER SWITCH (N.O.)

10 4" VIKING DRY VALVE ASSEMBLY

NITROGEN GENERATOR CABINET WITH INTEGRATED COMPRESSOR RATED

FOR 800 GALLON SPRINKLER SYSTEM (ECS PGEN-10 IS BASIS OF DESIGN)

S117

C11

C01

M110

S101S102S103

S105

S106

S107

S113

S108

S123

S114

S115S116

S119S120S121S122

S124

C05

C02

C03

C04

S104

C06

C07

C08

S110S111S112 S109

S118

R125

S126

C09

C10

C12

C13

C14

C15 C16

TR1 DV1 BR1

BFD UG

S125

F2

GENERAL NOTESKEY NOTES

LEGEND

DRY PENDENT SPRINKLER 0

QTY.SPRINKLER TYPESYMBOL

HORIZONTAL SIDEWALL SPRINKLER 7

UPRIGHT SPRINKLER 78

13DRY PENDENT SPRINKLER WITH ESCUTCHEON

1. INSTALLATION OF SPRINKLER SYSTEM SHALL BE IN ACCORDANCE

WITH NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS.

2. CONTRACTOR SHALL NOT INSTALL PIPE PRIOR TO COORDINATION

WITH CONTRACTING OFFICER.

3. SPRINKLERS IN LIGHT HAZARD OCCUPANCIES SHALL BE OF THE

QUICK-RESPONSE TYPE.

4. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS

OVER 4 FEET WIDE, SUCH AS DUCTS, DECKS, OPEN GRATE FLOORING,

CUTTING TABLES, AND OVERHEAD DOORS.

5. SPRINKLER SYSTEMS SHALL BE INSTALLED WITH THE APPROPRIATE

AMOUNT AND LOCATIONS OF DRAINS TO FACILITATE FULL DRAINING

OF THE SPRINKLER SYSTEM.

6. PROVIDE INTERMEDIATE TEMPERATURE RATED SPRINKLER HEADS IN

ALL MECHANICAL, ELECTRICAL OR SIMILAR BACK OF HOUSE SPACES

WHERE AMBIENT TEMPERATURE ARE HIGHER THAN NORMAL

COMMON SPACE ENVIRONMENTS, UNLESS NOTED OTHERWISE.

7. PROVIDE THE APPROPRIATE HYDRAULIC NAMEPLATES AT THE BASE

OF EACH SYSTEM RISER. NAMEPLATES SHALL INCLUDE LOCATION OF

REMOTE AREA, NUMBER OF SPRINKLERS FLOWING, DESIGN DENSITY,

AND REQUIRED GPM AND PSI AT THE BASE OF EACH SYSTEM RISER

OR CONTROL VALVE ASSEMBLY.

8. NO SERVICE SHALL BE INTERRUPTED WITHOUT WRITTEN PERMISSION

FROM THE CONTRACTING OFFICER.

9. WHERE DEMOLITION WORK INTERFERES WITH OWNER'S USE OF

PREMISES, SCHEDULE WORK THROUGH CONTRACTING OFFICER TO

MINIMIZE INCONVENIENCE TO OWNER. OWNER MUST APPROVE

SCHEDULE BEFORE CONTRACTOR BEGINS ANY SUCH WORK.

10. REMODEL OF SPACE IDENTIFIED ON DRAWINGS REQUIRES THAT

COORDINATION OCCUR BETWEEN FIRE PROTECTION CONTRACTOR

AND OWNER. AT THE END OF EACH WORK DAY, SPRINKLER FITTER

MUST COORDINATE WITH OWNER SO THE FIRE PROTECTION SYSTEM

IS RE-ACTIVATED FOR EACH NIGHT.

11. REFER TO SPECIFICATION 21 1314 - AUTOMATIC FIRE SPRINKLER

SYSTEM FOR ADDITIONAL INFORMATION.

12. FIRE PROTECTION CONTRACTOR SHALL HAVE APPROVED

SPRINKLER SUBMITTAL DRAWINGS FROM ARCHITECT AND ENGINEER

PRIOR TO STARTING INSTALLATION ON THIS PROJECT. ANY WORK

THAT HAS BEEN INSTALLED PRIOR TO RECEIVING THE APPROVALS

MAY BE REMOVED, AT THE CONTRACTORS EXPENSE.

13. AREAS OF WOOD FRAMING SHALL BE CONSIDERED COMBUSTIBLE

OBSTRUCTED IF THE BEAM SPACING IS LESS THAN 15'-0” ON CENTER.

THESE AREAS SHALL BE LIMITED TO 130 SQ/FT MAXIMUM SPACING.

F5

GENERAL NOTES

KEY NOTES

LEGEND

1. INSTALLATION OF SPRINKLER SYSTEM SHALL BE IN ACCORDANCE

WITH NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS.

2. CONTRACTOR SHALL NOT INSTALL PIPE PRIOR TO COORDINATION

WITH CONTRACTING OFFICER.

3. SPRINKLERS IN LIGHT HAZARD OCCUPANCIES SHALL BE OF THE

QUICK-RESPONSE TYPE.

4. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS

OVER 4 FEET WIDE, SUCH AS DUCTS, DECKS, OPEN GRATE FLOORING,

CUTTING TABLES, AND OVERHEAD DOORS.

5. SPRINKLER SYSTEMS SHALL BE INSTALLED WITH THE APPROPRIATE

AMOUNT AND LOCATIONS OF DRAINS TO FACILITATE FULL DRAINING

OF THE SPRINKLER SYSTEM.

6. PROVIDE INTERMEDIATE TEMPERATURE RATED SPRINKLER HEADS IN

ALL MECHANICAL, ELECTRICAL OR SIMILAR BACK OF HOUSE SPACES

WHERE AMBIENT TEMPERATURE ARE HIGHER THAN NORMAL

COMMON SPACE ENVIRONMENTS, UNLESS NOTED OTHERWISE.

7. PROVIDE THE APPROPRIATE HYDRAULIC NAMEPLATES AT THE BASE

OF EACH SYSTEM RISER. NAMEPLATES SHALL INCLUDE LOCATION OF

REMOTE AREA, NUMBER OF SPRINKLERS FLOWING, DESIGN DENSITY,

AND REQUIRED GPM AND PSI AT THE BASE OF EACH SYSTEM RISER

OR CONTROL VALVE ASSEMBLY.

8. NO SERVICE SHALL BE INTERRUPTED WITHOUT WRITTEN PERMISSION

FROM THE CONTRACTING OFFICER.

9. WHERE DEMOLITION WORK INTERFERES WITH OWNER'S USE OF

PREMISES, SCHEDULE WORK THROUGH CONTRACTING OFFICER TO

MINIMIZE INCONVENIENCE TO OWNER. OWNER MUST APPROVE

SCHEDULE BEFORE CONTRACTOR BEGINS ANY SUCH WORK.

10. REMODEL OF SPACE IDENTIFIED ON DRAWINGS REQUIRES THAT

COORDINATION OCCUR BETWEEN FIRE PROTECTION CONTRACTOR

AND OWNER. AT THE END OF EACH WORK DAY, SPRINKLER FITTER

MUST COORDINATE WITH OWNER SO THE FIRE PROTECTION SYSTEM

IS RE-ACTIVATED FOR EACH NIGHT.

11. REFER TO SPECIFICATION 21 1314 - AUTOMATIC FIRE SPRINKLER

SYSTEM FOR ADDITIONAL INFORMATION.

12. FIRE PROTECTION CONTRACTOR SHALL HAVE APPROVED

SPRINKLER SUBMITTAL DRAWINGS FROM ARCHITECT AND ENGINEER

PRIOR TO STARTING INSTALLATION ON THIS PROJECT. ANY WORK

THAT HAS BEEN INSTALLED PRIOR TO RECEIVING THE APPROVALS

MAY BE REMOVED, AT THE CONTRACTORS EXPENSE.

13. AREAS OF WOOD FRAMING SHALL BE CONSIDERED COMBUSTIBLE

OBSTRUCTED IF THE BEAM SPACING IS LESS THAN 15'-0” ON CENTER.

S101

S102

S103

S104

S105

S106

S107

S108

S128

S124

S125

S129

S126

S130

S127

S109

S110

S111

S112

S113

S114

S115

S116

S117

S118

S119

S120

S121

S122

M101

M102

M103

M105

M107 M108

M109

M110 M111 M112

M113

M114

M106

TR1

S202

S201

S204

S203

S206

S205

R208

S207

S210

S209

S212

S211

S214

S213

S216

S215

S218

S217

S220

S219

S222

S223

S224

S225

S226

S227

S228

S229

S230

S231

S232

S234

S235

S236

S237

S221

S238

S239

S240

M201

M202 M203

M204 M205

M206

M207

M208

M209

M210

M213

M214

M215

M216

M217 M218

M115

M116

M117

M219

M211

M222

M220

M212

S208

R229 R226

R223

S123

M104

RA1

A1

RA2

A2

RA3

A3

RA4

A4

RA5

A5

RA6

A6

A7

BFD

UG

RN1 RN2

RN3

RN4

S233

M221

X1

X2

S241

R241

F5

F5

F5

F4

DV1

FIRE PROTECTION EQUIPMENT

1 EXISTING 6" WATER SERVICE

BACKFLOW PREVENTER WITH BUTTERFLY VALVES & TAMPER SWITCHES

(N.O.)

FDC BYPASS BUTTERFLY VALVE WITH TAMPER SWITCH (N.C.)

4 FDC CHECK VALVE

5 EXISTING FDC TO REMAIN

6 EXISTING 6" VIKING DRY VALVE ASSEMBLY TO BE REUSED

SKID-MOUNTED NITROGEN GENERATOR WITH INTEGRATED COMPRESSOR

(TYCO NG-1 1000 IS BASIS OF DESIGN)

BFD

UG

TR1

DRY PENDENT SPRINKLER 26

QTY.SPRINKLER TYPESYMBOL

HORIZONTAL SIDEWALL SPRINKLER 0

UPRIGHT SPRINKLER 119

0DRY PENDENT SPRINKLER WITH ESCUTCHEON

1. INSTALLATION OF SPRINKLER SYSTEM SHALL BE IN ACCORDANCE

WITH NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS.

2. CONTRACTOR SHALL NOT INSTALL PIPE PRIOR TO COORDINATION

WITH CONTRACTING OFFICER.

3. SPRINKLERS IN LIGHT HAZARD OCCUPANCIES SHALL BE OF THE

QUICK-RESPONSE TYPE.

4. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS

OVER 4 FEET WIDE, SUCH AS DUCTS, DECKS, OPEN GRATE FLOORING,

CUTTING TABLES, AND OVERHEAD DOORS.

5. SPRINKLER SYSTEMS SHALL BE INSTALLED WITH THE APPROPRIATE

AMOUNT AND LOCATIONS OF DRAINS TO FACILITATE FULL DRAINING

OF THE SPRINKLER SYSTEM.

6. PROVIDE INTERMEDIATE TEMPERATURE RATED SPRINKLER HEADS IN

ALL MECHANICAL, ELECTRICAL OR SIMILAR BACK OF HOUSE SPACES

WHERE AMBIENT TEMPERATURE ARE HIGHER THAN NORMAL

COMMON SPACE ENVIRONMENTS, UNLESS NOTED OTHERWISE.

7. PROVIDE THE APPROPRIATE HYDRAULIC NAMEPLATES AT THE BASE

OF EACH SYSTEM RISER. NAMEPLATES SHALL INCLUDE LOCATION OF

REMOTE AREA, NUMBER OF SPRINKLERS FLOWING, DESIGN DENSITY,

AND REQUIRED GPM AND PSI AT THE BASE OF EACH SYSTEM RISER

OR CONTROL VALVE ASSEMBLY.

8. NO SERVICE SHALL BE INTERRUPTED WITHOUT WRITTEN PERMISSION

FROM THE CONTRACTING OFFICER.

9. WHERE DEMOLITION WORK INTERFERES WITH OWNER'S USE OF

PREMISES, SCHEDULE WORK THROUGH CONTRACTING OFFICER TO

MINIMIZE INCONVENIENCE TO OWNER. OWNER MUST APPROVE

SCHEDULE BEFORE CONTRACTOR BEGINS ANY SUCH WORK.

10. REMODEL OF SPACE IDENTIFIED ON DRAWINGS REQUIRES THAT

COORDINATION OCCUR BETWEEN FIRE PROTECTION CONTRACTOR

AND OWNER. AT THE END OF EACH WORK DAY, SPRINKLER FITTER

MUST COORDINATE WITH OWNER SO THE FIRE PROTECTION SYSTEM

IS RE-ACTIVATED FOR EACH NIGHT.

11. REFER TO SPECIFICATION 21 1314 - AUTOMATIC FIRE SPRINKLER

SYSTEM FOR ADDITIONAL INFORMATION.

12. FIRE PROTECTION CONTRACTOR SHALL HAVE APPROVED

SPRINKLER SUBMITTAL DRAWINGS FROM ARCHITECT AND ENGINEER

PRIOR TO STARTING INSTALLATION ON THIS PROJECT. ANY WORK

THAT HAS BEEN INSTALLED PRIOR TO RECEIVING THE APPROVALS

MAY BE REMOVED, AT THE CONTRACTORS EXPENSE.

13. AREAS OF WOOD FRAMING SHALL BE CONSIDERED COMBUSTIBLE

OBSTRUCTED IF THE BEAM SPACING IS LESS THAN 15'-0” ON CENTER.

SCALE:

SCALE:

NOT TO SCALE

FIRE DEPARTMENT CONNECTION W/ FULL FLOW BYPASS

SCALE:

NOT TO SCALE

EXTERIOR WALL PENETRATION - BELOW GRADE

SCALE:

NOT TO SCALE

EXTERIOR WALL PENETRATION - ABOVE GRADE

SCALE:

NOT TO SCALE

PIPE THROUGH INTERIOR WALL

SCALE:

NOT TO SCALE

DRY PIPE VALVE ASSEMBLY

SCALE:

NOT TO SCALE

EXTERIOR DRAIN THROUGH WALL

SCALE:

SCALE:

NOT TO SCALE

SIDE SCREW PIPE HANGER

SCALE:

NOT TO SCALE

VERTICAL SCREW PIPE HANGER

PIPE

WATERSTOP SLEEVE

SEAL PENETRATION

AT EACH SIDE

PIPE

WATERSTOP SLEEVE

SEAL PENETRATION

AT EACH SIDE

CHROME SPLIT WALL PLATE

GWB CEILING

WOOD JOIST

LISTED WOOD SCREW

ALL THREAD ROD

HANGER RING

WOOD JOIST

LISTED WOOD SCREW

ALL THREAD ROD

HANGER RING

F I R

E

M

A I N

WATER SOURCE

SUPERVISED OS&Y

SHUTOFF VALVES

NOT TO SCALE

DOUBLE CHECK BACKFLOW PREVENTER

THREADED ROD

FOR TWO HOLE

NOTES:

1. PRESSURE REDUCING BACKFLOW IS ONLY LISTED FOR

INSTALLATION IN THE HORIZONTAL POSITION.

2. COORDINATE LOCATION WITH PLUMBING CONTRACTOR.

FOR PLUMBERS

FROM FIRE

PROTECTION

SYSTEM

REFER TO ARCHITECTURAL

DRAWINGS FOR FLOOR TYPE

AND DIMENSIONS

BYPASS FOR FORWARD FLOW

TEST OF BACKFLOW PREVENTER

CHECK VALVE

TO FIRE DEPARTMENT

CONNECTION

ROUTE BALL DRIP TO

DISCHARGE TO EXTERIOR.

SUPERVISED SHUTOFF

VALVE W/ TAMPER,

NORMALLY CLOSED

PROVIDE SUPPORT AS

REQUIRED

BUILDING

SPACE

BELOW

GRADE

THUNDERLINE CORPORATION. USE 316 SS NUTS AND BOLTS.

"LINK-SEAL" MODULAR WALL AND CASING SEAL BY(1)

NOTES:

(2)

(3)

BETWEEN PIPE AND OPENING WITHOUT SLEEVE. SIZE OPENING

FOR CORE DRILLED HOLE, INSTALL "LINK-SEAL" SEAL

AS RECOMMENDED BY SEAL MANUFACTURER.

FOR LINED PIPE, EXTEND LINING TO SEAL AT BOTH

SIDES.

BUILDING

SPACE

ABOVE

GRADE

NOTE:

REFER TO SPECIFICATION FOR ADDITIONAL INFORMATION.

BACKING MATERIAL

SEALANT

PIPE

REFER TO ARCHITECTURAL

DRAWINGS FOR WALL TYPE

AND DIMENSIONS

NOTE:

1. WHERE WALL IS FIRE RATED, PROVIDE A LISTED PENETRATION ASSEMBLY.

2. PROVIDE PLASTIC WALL PLATES OVER PENETRATIONS WHEN EXPOSED TO

VIEW.

F I R

E

M

A I N

DRY PIPE SPRINKLER

SYSTEM VALVE

ASSEMBLY

UL 2125 LISTED,

FLOOR MOUNTED

AIR COMPRESSOR

REFER TO

ARCHITECTURAL

DRAWINGS FOR WALL

AND FLOOR TYPE AND

DIMENSIONS

SUPERVISED SHUTOFF

VALVE W/ TAMPER

SWITCH

AIR MAINTENANCE

DEVICE

SUPERVISED SHUTOFF

VALVE W/ TAMPER

SWITCH TO ISOLATE

SYSTEM DURING

TESTING

HUB DRAIN

(REFER TO PLUMBING

DRAWING FOR

LOCATION)

AUXILIARY DRAIN

PROVIDE SUPPORT AS

REQUIRED

TO DRAIN LOCATION

GALVANIZED

THREADED 45° ELBOW

SEAL PENETRATION

AT EACH SIDE

90° ELBOW

INTERIOR FLOOR

EXTERIOR

DRAIN RISER

CHROME SPLIT WALL PLATE

GALVANIZED PIPE

REFER TO ARCHITECTURAL

DRAWINGS FOR WALL AND FLOOR

TYPES AND DIMENSIONS.

WATERSTOP SLEEVE

LOCATE 18"-36" ABOVE

FINISHED GRADE

SEAL PENETRATION

AT EACH SIDE

PROVIDE SPLASH BLOCK TO

LOCATIONS W/ EXPOSED SOIL

SYSTEM PIPING

VALVE (NORMALLY OPEN)

VALVE (NORMALLY CLOSED)

ROUTE DRAIN TO AN

APPROVED LOCATION

PROVIDE WITH SMALLEST

SPRINKLER HEAD ORIFICE ON

DRY SYSTEM FOR TESTING

WHEN REQUIRED BY NFPA

STANDARDS

2" PIPE

THREADED REDUCER

THREADED REDUCER

NOT TO SCALE

LOW POINT DRAIN

LISTED WOOD SIDE SCREW

ALL THREAD ROD

HANGER RING

WOOD JOIST

EISENHOWER HOME

BARN

RECEPTION CENTER

GUEST HOUSE

FARM 1 BARN CONTRACTOR

STAGING AREA

LIMITS OF FARM 1 BARN

CONSTRUCTION/STAGING AREA

CHAIN LINK CONSTRUCTION

FENCE BY CONTRACTOR

EXTENDED BETWEEN

PERMANENT PARK FENCES

SHOW BARN

LOAFING BARN

SELF FEEDER

MATERNITY BARN

HERDSMAN'S HOME

(PARK HEADQUARTERS)

CHAIN LINK CONSTRUCTION

FENCE BY CONTRACTOR

EXTENDED BETWEEN

PERMANENT PARK FENCES

FARM 2 BARN CONTRACTOR

STAGING AREA

LIMITS OF FARM 2 BARN

CONSTRUCTION/STAGING AREA

0 25 50 100 Feet 0 30 60 120 Feet

BFD

UG

TEST

CONTINUES TO

SHOW BARN

WATER METER

GATE VALVE

GATE VALVE

CONTINUES

TO FARM 3

6" WATER SERVICE

HYDRANT

6" WATER MAIN

6" WATER MAIN

6" WATER MAIN

6" WATER MAIN

GENERAL NOTES

KEY NOTES

LEGEND

1. INSTALLATION OF SPRINKLER SYSTEM SHALL BE IN ACCORDANCE

WITH NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS.

2. CONTRACTOR SHALL NOT INSTALL PIPE PRIOR TO COORDINATION

WITH CONTRACTING OFFICER.

3. SPRINKLERS IN LIGHT HAZARD OCCUPANCIES SHALL BE OF THE

QUICK-RESPONSE TYPE.

4. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS

OVER 4 FEET WIDE, SUCH AS DUCTS, DECKS, OPEN GRATE FLOORING,

CUTTING TABLES, AND OVERHEAD DOORS.

5. SPRINKLER SYSTEMS SHALL BE INSTALLED WITH THE APPROPRIATE

AMOUNT AND LOCATIONS OF DRAINS TO FACILITATE FULL DRAINING

OF THE SPRINKLER SYSTEM.

6. PROVIDE INTERMEDIATE TEMPERATURE RATED SPRINKLER HEADS IN

ALL MECHANICAL, ELECTRICAL OR SIMILAR BACK OF HOUSE SPACES

WHERE AMBIENT TEMPERATURE ARE HIGHER THAN NORMAL

COMMON SPACE ENVIRONMENTS, UNLESS NOTED OTHERWISE.

7. PROVIDE THE APPROPRIATE HYDRAULIC NAMEPLATES AT THE BASE

OF EACH SYSTEM RISER. NAMEPLATES SHALL INCLUDE LOCATION OF

REMOTE AREA, NUMBER OF SPRINKLERS FLOWING, DESIGN DENSITY,

AND REQUIRED GPM AND PSI AT THE BASE OF EACH SYSTEM RISER

OR CONTROL VALVE ASSEMBLY.

8. NO SERVICE SHALL BE INTERRUPTED WITHOUT WRITTEN PERMISSION

FROM THE CONTRACTING OFFICER.

9. WHERE DEMOLITION WORK INTERFERES WITH OWNER'S USE OF

PREMISES, SCHEDULE WORK THROUGH CONTRACTING OFFICER TO

MINIMIZE INCONVENIENCE TO OWNER. OWNER MUST APPROVE

SCHEDULE BEFORE CONTRACTOR BEGINS ANY SUCH WORK.

10. REMODEL OF SPACE IDENTIFIED ON DRAWINGS REQUIRES THAT

COORDINATION OCCUR BETWEEN FIRE PROTECTION CONTRACTOR

AND OWNER. AT THE END OF EACH WORK DAY, SPRINKLER FITTER

MUST COORDINATE WITH OWNER SO THE FIRE PROTECTION SYSTEM

IS RE-ACTIVATED FOR EACH NIGHT.

11. REFER TO SPECIFICATION 21 1314 - AUTOMATIC FIRE SPRINKLER

SYSTEM FOR ADDITIONAL INFORMATION.

12. FIRE PROTECTION CONTRACTOR SHALL HAVE APPROVED

SPRINKLER SUBMITTAL DRAWINGS FROM ARCHITECT AND ENGINEER

PRIOR TO STARTING INSTALLATION ON THIS PROJECT. ANY WORK

THAT HAS BEEN INSTALLED PRIOR TO RECEIVING THE APPROVALS

MAY BE REMOVED, AT THE CONTRACTORS EXPENSE.

13. AREAS OF WOOD FRAMING SHALL BE CONSIDERED COMBUSTIBLE

OBSTRUCTED IF THE BEAM SPACING IS LESS THAN 15'-0” ON CENTER.

BFD

TEST

UG

1. INSTALLATION OF SPRINKLER SYSTEM SHALL BE IN ACCORDANCE

WITH NFPA 13, INSTALLATION OF SPRINKLER SYSTEMS.

2. CONTRACTOR SHALL NOT INSTALL PIPE PRIOR TO COORDINATION

WITH CONTRACTING OFFICER.

3. SPRINKLERS IN LIGHT HAZARD OCCUPANCIES SHALL BE OF THE

QUICK-RESPONSE TYPE.

4. SPRINKLERS SHALL BE INSTALLED UNDER FIXED OBSTRUCTIONS

OVER 4 FEET WIDE, SUCH AS DUCTS, DECKS, OPEN GRATE FLOORING,

CUTTING TABLES, AND OVERHEAD DOORS.

5. SPRINKLER SYSTEMS SHALL BE INSTALLED WITH THE APPROPRIATE

AMOUNT AND LOCATIONS OF DRAINS TO FACILITATE FULL DRAINING

OF THE SPRINKLER SYSTEM.

6. PROVIDE INTERMEDIATE TEMPERATURE RATED SPRINKLER HEADS IN

ALL MECHANICAL, ELECTRICAL OR SIMILAR BACK OF HOUSE SPACES

WHERE AMBIENT TEMPERATURE ARE HIGHER THAN NORMAL

COMMON SPACE ENVIRONMENTS, UNLESS NOTED OTHERWISE.

7. PROVIDE THE APPROPRIATE HYDRAULIC NAMEPLATES AT THE BASE

OF EACH SYSTEM RISER. NAMEPLATES SHALL INCLUDE LOCATION OF

REMOTE AREA, NUMBER OF SPRINKLERS FLOWING, DESIGN DENSITY,

AND REQUIRED GPM AND PSI AT THE BASE OF EACH SYSTEM RISER

OR CONTROL VALVE ASSEMBLY.

8. NO SERVICE SHALL BE INTERRUPTED WITHOUT WRITTEN PERMISSION

FROM THE CONTRACTING OFFICER.

9. WHERE DEMOLITION WORK INTERFERES WITH OWNER'S USE OF

PREMISES, SCHEDULE WORK THROUGH CONTRACTING OFFICER TO

MINIMIZE INCONVENIENCE TO OWNER. OWNER MUST APPROVE

SCHEDULE BEFORE CONTRACTOR BEGINS ANY SUCH WORK.

10. REMODEL OF SPACE IDENTIFIED ON DRAWINGS REQUIRES THAT

COORDINATION OCCUR BETWEEN FIRE PROTECTION CONTRACTOR

AND OWNER. AT THE END OF EACH WORK DAY, SPRINKLER FITTER

MUST COORDINATE WITH OWNER SO THE FIRE PROTECTION SYSTEM

IS RE-ACTIVATED FOR EACH NIGHT.

11. REFER TO SPECIFICATION 21 1314 - AUTOMATIC FIRE SPRINKLER

SYSTEM FOR ADDITIONAL INFORMATION.

12. FIRE PROTECTION CONTRACTOR SHALL HAVE APPROVED

SPRINKLER SUBMITTAL DRAWINGS FROM ARCHITECT AND ENGINEER

PRIOR TO STARTING INSTALLATION ON THIS PROJECT. ANY WORK

THAT HAS BEEN INSTALLED PRIOR TO RECEIVING THE APPROVALS

MAY BE REMOVED, AT THE CONTRACTORS EXPENSE.

13. AREAS OF WOOD FRAMING SHALL BE CONSIDERED COMBUSTIBLE

OBSTRUCTED IF THE BEAM SPACING IS LESS THAN 15'-0” ON CENTER.

F0 - FIRE PROTECTION - COVER SHEET
Sheets and Views
Layout1
F1 - FIRE PROTECTION - SYMBOLS AND ABBREVIATIONS
Sheets and Views
Layout1
PLOT
F2 - FIRE PROTECTION - FARM 1 BARN LOWER LEVEL PLAN
Sheets and Views
Layout1
PLOT
F3 - FIRE PROTECTION - FARM 1 BARN UPPER LEVEL DEMOLITION PLAN
Sheets and Views
Layout1
F4 - FIRE PROTECTION - FARM 2 SHOW BARN PLAN
Sheets and Views
Layout1
PLOT
F5 - FIRE PROTECTION - BUILDING SECTIONS
Sheets and Views
Layout1
PLOT
F6 - FIRE PROTECTION - DETAILS
Sheets and Views
FIRE PROTECTION DETAILS
PLOT
F7 - FIRE PROTECTION - STAGING PLAN
Sheets and Views
Staging Plan
VIEW
F8 - FIRE PROTECTION - FARM 1 BARN SITE PLAN
Sheets and Views
Layout1
PLOT
F9 - FIRE PROTECTION - FARM 2 SHOW BARN SITE PLAN
Sheets and Views
Layout1
PLOT