B08_Attachment_2_-_GEWA_305342_-_Drawings.pdf

PDF 29 MB Posted

Attached to
George Washington Birthplace National Monument- RE
Solicitation number
140P4326R0013
Issued by

About this file

This is a comprehensive set of construction drawings and mechanical/electrical design documents for replacing the geothermal heating and cooling system at the Memorial House Museum located at George Washington Birthplace National Monument in Colonial Beach, Virginia.

The project involves demolishing the existing water source heat pump (WSHP) system with ground source condensing water loops and replacing it with a new system comprising: five water source heat pumps (WSHP-1 through WSHP-5B) rated at 1.5 to 3 tons, a new propane-fired boiler (Burnham X-206LP, 146 MBH output), a cooling tower (BAC VFL-024-12H, 24-ton capacity with basin heaters), five inline circulation pumps with variable frequency drives, expansion tanks, air separators, and side stream filtration. The new system will serve multiple zones across the basement, first floor, and second floor (attic) of the historic structure. Key requirements include disconnecting and removing existing refrigerant per EPA guidelines, reconfiguring existing ductwork and hot water coils to remain in service, providing new condensate drain lines to existing pumps, installing new thermostats and controls, and balancing both water and air systems. The electrical work requires new branch circuit wiring, safety switches, and variable frequency drive installations powered from the existing main distribution panel (120/240V, 1Ø, 200A). Construction must prioritize historic preservation by minimizing disturbance to historic fabric, using existing routing for conduit and wiring where feasible, and coordinating all penetrations with the Contracting Officer. The drawings indicate design-assist requirements with the electrical contractor responsible for preparing final electrical design documents based on mechanical equipment specifications and field conditions prior to installation.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

REPLACE THE GEOTHERMAL SYSTEM

AT THE MEMORIAL HOUSE MUSEUM

COLONIAL BEACH

VIRGINIA

SHEET SUB TITLE

NO.SHEET

1 CS COVER SHEET

2 SI1.0 PLAN

3 SI2.0 DETAILS

4 SI2.0 DETAILS

5 M0.1 MECHANICAL LEGEND AND NOTES

6 M1.0 MECHANICAL SITE PLAN

7 M2.0 MECHANICAL BASEMENT DEMOLITION FLOOR PLAN

8 M2.1 MECHANICAL BASEMENT NEW WORK FLOOR PLAN

9 M2.2 MECHANICAL LEVEL 1 FLOOR PLAN

10 M2.3 MECHANICAL LEVEL 2 FLOOR PLAN

11 M3.0 MECHANICAL FLOW DIAGRAM

12 M4.0 MECHANICAL SCHEDULE

13 M5.0 MECHANICAL DETAILS

14 M5.1 MECHANICAL DETAILS

15 M5.2 MECHANICAL DETAILS

16 M5.3 MECHANICAL DETAILS

17 E0.1 ELECTRICAL GENERAL NOTES

18 E1.0 ELECTRICAL SITE PLAN

19 E2.0 ELECTRICAL DEMOLITION FLOOR PLAN

20 E2.1 ELECTRICAL NEW WORK FLOOR PLAN

REPLACE GEOTHERMAL SYSTEM

2/9/2026

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M0.1

ELS

ELS

305342

114081

332MECHANICAL

LEGEND AND NOTES

1. REFER TO ALL DRAWINGS SPECIFICATION FOR GENERAL DESCRIPTION OF AREAS REQUIRING

DEMOLITION.

2. REFER TO CONSTRUCTION MANAGER'S INSTRUCTIONS FOR ALL EXISTING EQUIPMENT AND

MATERIALS THAT SHALL REMAIN THE PROPERTY OF THE OWNER.

3. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE OWNER, SHALL BECOME

THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM SITE AND LEGALLY

DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT SITE IS PROHIBITED.

4. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING DURING

DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE

SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY REPAIR DAMAGED PROPERTY TO

THE CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT

WINDBLOWN DUST.

5. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION. KEEP

UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES SERVING

OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM HARVARD FACILITIES. PROVIDE

TEMPORARY SERVICES AS REQUIRED.

6. THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL SYSTEM REMOVAL. NOT

EVERY ITEM OR COMPONENT OF A SYSTEM IS SHOWN.

7. THIS CONTRACTOR SHALL PROVIDE SHUT DOWN OF SERVICES (BOILERS, AHU, PUMPS, ETC.) AND

TRACING OF ALL PIPING WITHIN BASE BID.

HVAC DEMOLITION SPECIFICATION

1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL MX.XX AND P.XX SERIES

DRAWINGS.

2. DRAWINGS ARE DIAGRAMMATIC, DETERMINE EXACT LOCATIONS OF SYSTEMS AND COMPONENTS

IN FIELD.

3. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.

4. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

5. PROVIDE INFORMATION AND HARDWARE AS NECESSARY TO COORDINATE CONCRETE PADS AND

STEEL PLATFORMS REQUIRED FOR MECHANICAL WORK.

6. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING

REQUIREMENTS.

7. SHEETMETAL FITTINGS SHOWN ARE TO BE PROVIDED. NO SUBSTITUTES SHALL BE ALLOWED

WITHOUT PRIOR CONSENT FROM ARCHITECT/ENGINEER.

8. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND LEAKAGE

CLASSES.

9. RUN DUCTS AND PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS. ALL DUCTWORK SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO WALL AND UNDERSIDE

OF BEAMS AND JOISTS.

10. INSTALL THERMOSTATS AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT.

MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA.

11. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AND DUCTS

AND TRANSITIONS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST.

12. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY

AND PROVIDE DUCT TRANSITIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE

ALL DIMENSIONS BEFORE FABRICATION.

13. ACCESS PANELS SHALL BE PROVIDED TO CLEAN COILS AND SERVICE DAMPERS, HEATERS,

VALVES AND ALL CONCEALED MECHANICAL EQUIPMENT.

14. SUPPORT ALL EQUIPMENT, PIPING AND DUCTWORK FROM BUILDING STRUCTURE TO PROVIDE A

VIBRATION FREE INSTALLATION. PROVIDE TO GC A LIST OF ALL WEIGHTS AND METHODS OF

SUPPORT FOR COORDINATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

15. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.

16. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. CONTRACTOR SHALL INCREASE SIZE

FOR LINER IF APPLICABLE.

17. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, OTHER THAN SPECIFIC RENTED ITEMS

IDENTIFIED ON PLANS.

18. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.

19. ALL CONDENSATE DRAINLINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTSET.

20. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND AIR HANDLING

UNITS UNLESS INTERNALLY ISOLATED. ALL DUCTS TO BE GROUNDED ACROSS FLEXIBLE

CONNECTION WITH FLEXIBLE COPPER GROUNDING STRAPS.

21. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED FLAT

BLACK.

22. INSULATE PIPING AND DUCTWORK AS SPECIFIED: PERFORM TESTS SPECIFIED BEFORE

INSULATING.

23. PROVIDE HANGERS, CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS

NECESSARY TO PREVENT STRESS ON PIPING.

24. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.

25. PROVIDE AT LEAST THREE-ELBOW SWING FOR PIPE TAKE-OFFS TO TERMINAL EQUIPMENT AND

RISERS.

26. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT WIDTH)

WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT RADIUS ELBOW

WITH FULL LENGTH SPLITTER VANES PER SMACNA. MITERED (SQUARE) ELBOWS WITH TURNING

VANES MAY NOT BE SUBMITTED WITHOUT WRITTEN CONSENT FROM THE ARCHITECT/ENGINEER.

27. ISOLATION VALVES IN PIPING SYSTEMS ARE NOT SHOWN ON PLANS (FOR CLARITY) BUT ARE REQUIRED AT ALL PIPE BRANCHES AND CONNECTIONS TO EQUIPMENT REFER TO DETAIL SHEETS

AND FLOW DIAGRAMS.

28. PITCH PIPING 1 INCH IN 20 FEET MINIMUM IN DIRECTION OF FLOW, TO ALLOW FOR DRAINING

29. MANUAL DAMPERS ARE NOT SHOWN ON THE DRAWINGS IN ORDER FOR DRAWING CLARITY.

PROVIDE MANUAL ADJUSTABLE DAMPERS ON EACH LOW PRESSURE SUPPLY, RETURN, AND

EXHAUST DUCT TAKE OFF, AND AT EACH TAKE OFF TO REGISTERS, GRILLES AND DIFFUSERS.

30. PROVIDE CEILING ACCESS PANELS BELOW ALL EQUIPMENT LOCATED ABOVE CEILINGS. EXACT

SIZE AND LOCATION SHALL BE COORDINATED IN FIELD WITH ARCHITECT.

GENERAL NOTES

DN

UP

W

CO

MAV

AAV

PT

FM

S

OR

OR

OR

R w

PIPING LEGENDDUCTWORK

SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE

ROUND SUPPLY

DUCT UP

SUPPLY

DUCT UP

ROUND SUPPLY

DUCT DN

SUPPLY DUCT

DOWN

STANDARD RADIUS

ELBOW

( R = W )

SUPPLY/RETURN

EXHAUST

SPLIT TAKE-OFF

W/ BRANCH DAMPERS

SUPPLY

BULLHEAD SPLIT

SUPPLY

CEILING DUCT

GOOD FOR

RING DUCT

TAKEOFF TO

MTD DIFF/GRILLE

W/BRANCH TAKE-OFF

VOLUME DAMPER

CEILING DUCT

MTD DIFF/GRILLE

W/BRANCH TAKE-OFF

VOLUME DAMPER

OPEN END

DUCT W/VD &

1/2"x1/2" WMS

FLEXIBLE

DUCT

RISE/DROP

RISE/DROP

ROUND RETURN OR

EXHAUST

DUCT UP

RETURN/EXHAUST

DUCT UP

RETURN/EXHAUST

DUCT DOWN

ROUND RETURN OR

EXHAUST DUCT

DN

HORIZONTAL

OFFSET

SUPPLY/RETURN

/EXHAUST

RISE OR DROP

SUPPLY/RETURN/

EXHAUST

RING

DUCT

90° TAKE-OFF W/BRANCH TAKE-OFF

VOLUME DAMPER (VD IN LOW PRESSURE

SYSTEMS ONLY)

BULLHEAD CONVERGE

RETURN/EXHAUST

W/BRANCH TAKE-OFF

VOLUME DAMPER

SIDEWALL DUCT MTD

REGISTER/GRILLE

W/BRANCH TAKE-OFF

VOLUME DAMPER

SUPPLY CEILING

LINEAR DIFFUSER (W/

1" INTERNALLY LINED

SM PLENUM) BRANCH

CONN W/VD FOR

EVERY 4' OF LINEAR BOOT

BY LD

MFR

ROOF EXHAUST FAN

SHOWN ON ROOF

ROOF EXHAUST FAN

SHOWN ON FLOOR PLAN

RETURN OR EXHAUST

AIR FLOW

SUPPLY AIR FLOW

STANDARD 4-WAY BLOW

SUPPLY DIFFUSER

BLANKED FOR 3-WAY BLOW

SUPPLY DIFFUSER

BLANKED FOR 2-WAY BLOW

SUPPLY DIFFUSER

BLANKED FOR 1-WAY BLOW

SUPPLY DIFFUSER

DESIGN CFM

A(200)

PRESSURE TRANSMITTER

HUMIDISTAT

THERMOSTAT

SECTION DESIGNATION

SHEET NUMBER

DETAIL DESIGNATION

SHEET NUMBER

DIFFUSER, GRILLE,

REGISTER LETTER

DESIGNATOR

M.XX

M.XX

CARBON DIOXIDE SENSOR

FSD COMBINATION SMOKE/FIRE

DAMPER W/ACCESS DOOR

VD MANUAL VOLUME DAMPER

(OBD IN DIFFUSER)

ACD AUTOMATIC CONTROL DAMPER

W/ACCESS DOOR

SD AUTOMATIC SMOKE DAMPER

W/ACCESS DOOR

FD FIRE DAMPER W/ ACCESS DOOR

RH

VFD

C

C

C

VARIABLE FREQUENCY DRIVE

UNIT HEATERCABINET HEATER

COOLING COILREHEAT COIL

OPPOSED BLADE DAMPER

W/ MODULATING ACTUATOR

BACKDRAFT DAMPER

W/ TWO POSITION ACTUATOR

OPPOSED BLADE DAMPER

ROOF FAN

C

H

HEATING COILFILTER BANK

INLINE CENTRIFUGAL FAN

CENTRIFUGAL FAN

PUMP

UPBLAST CENTRIFUGAL FAN

EXPANSION TANK

AIR SEPARATOR

CHEMICAL FEED SYSTEM

AIR TERMINAL BOX

AAV

H

TEQUIPMENT TAGXX

CONNECT TO EXISTING

DISCONNECT FROM EXITING

CALL OUT SYMBOLS

C

P

°F DEGREES FAHRENHEIT

Ø DIAMETER

AAV AUTOMATIC AIR VENT

AC AIR CONDITIONING

ACC AIR COOLED CONDENSER UNIT

ACD AUTOMATIC CONTROL DAMPER

ACV AUTOMATIC CONTROL VALVE

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

ALT ALTERNATE ALUM ALUMINUM

AS AIR SEPARATOR

ATD AIR TERMINAL DEVICE

ATV ATMOSPHERIC VENT

AVG AVERAGE

BAS BUILDING AUTOMATION SYSTEM

BBD BOILER BLOW DOWN

BDD BACKDRAFT DAMPER

BF BOILER FEED WATER

BHP BRAKE HORSEPOWER

BLDG BUILDING

B BOILER

BOD BOTTOM OF DUCT

BOP BOTTOM OF PIPE

BSMT BASEMENT

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

CC COOLING COIL

CD CONDENSATE DRAIN

CFM CUBIC FEET PER MINUTE CH CHILLER

CHEM CHEMICAL FEED

CHW CHILLED WATER

CHWR CHILLED WATER RETURN

CHWS CHILLED WATER SUPPLY

CO CLEAN-OUT

CU CONDENSING UNIT

CUF CUBIC FEET

CUH CABINET UNIT HEATER

D DRAIN

DB DRY BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROL

DIA DIAMETER

DIFF DIFFUSER

DN DOWN

DWG DRAWING

DX DIRECT EXPANSION

(E) EXISTING

EA EACH

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EFF EFFICIENCY

ELEC ELECTRICAL

ELEV ELEVATION

ERU ENERGY RECOVERY UNIT

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

EUH ELECTRIC UNIT HEATER

EXH EXHAUST

EWT ENTERING WATER TEMPERATURE

EX EXHAUST

EXP EXPANSION

F FAN

FAS FIRE ALARM SYSTEM

FTR FINNED TUBE RADIATION

FCU FAN COIL UNIT

FCV FLOW CONTROL VALVE

FG FIBERGLASS

FLEX FLEXIBLE

FLR FLOOR FLRDR FLOOR DRAIN

FP FIRE PROTECTION

FPM FEET PER MINUTE

FT FEET

FT/SEC FEET PER SECOND

G GAS

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GC GENERAL CONTRACTOR

GND GROUND

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GRD GRADE (GROUND LEVEL)

GWB GYPSUM WALL BOARD

H HEIGHT

HB HOSE BIBB CONN W/CHAINED CAP

HC HEATING COIL

HCPD HANDICAPPED

HD HEAD

HP HORSEPOWER H

HR HOUR

HRC HEAT RECOVERY COIL - GLYCOL

HRU HEAT RECOVERY UNIT

HU HUMIDIFIER

HV HEATING & VENTILATING UNIT

HW HOT WATER

HWR HOT WATER RETURN

HWS HOT WATER SUPPLY

HX HEAT EXCHANGER

HZ HERTZ

ID INSIDE DIAMETER

IN INCHES

INSUL INSULATION

KW KILOWATT

KVA KILOVOLT AMPERE

L LENGTH

LAT LEAVING AIR TEMPERATURE

LB POUND

LD LINEAR DIFFUSER

LF LINEAR FEET

LVG LEAVING

LWT LEAVING WATER TEMPERATURE

ABRREVIATIONS

MAV MANUAL AIR VENT

MAX MAXIMUM

MBH THOUSAND BRITISH THERMAL

UNITS PER HOUR

MCA MINIMUM CIRCUIT AMPS

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MU MAKEUP WATER

N/A NOT APPLICABLE

NC NORMALLY CLOSED

NC NOISE CRITERIA

NO NORMALLY OPEN

NO. NOM NOMINAL

NTS NOT TO SCALE

OA OUTSIDE AIR

OB OCTAVE BAND

OD OUTSIDE DIAMETER

OBD OPPOSED BLADE DAMPER

OED OPEN END DUCT

OV OUTLET VELOCITY

P PUMP

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT

PD PRESSURE DROP PH PHASE

PH PERIMETER HEAT

PHC PREHEAT COIL

PHX PLATE HEAT EXCHANGER

PLBG PLUMBING

POS PROVIDED BY OTHER SECTION(S)

PRESS PRESSURE

PRIM PRIMARY

PSIA POUNDS PER SQUARE INCH

ABSOLUTE

PSID POUNDS PER SQUARE INCH

DIFFERENTIAL

PSIG POUNDS PER SQUARE INCH

GAUGE

PVC POLYVINYL CHLORIDE

R REHEAT

RA RETURN AIR

RD REFRIGERANT DISCHARGE

(HOT GAS)

REP REPRESENTATIVE

RET RETURN

RF RETURN FAN

RG RETURN GRILLE

R.H. RELATIVE HUMIDITY

RH REHEAT

RHC REHEAT COIL

RHP RADIANT HEATING PANEL

RL REFRIGERANT LIQUID

RLF RELIEF RR RETURN REGISTER

RM ROOM

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RV RETURN AIR VALVE/BOX

SA SUPPLY AIR

SATT SOUND ATTENUATOR

SCH SCHEDULE

SCR SCREEN

SD SMOKE DAMPER

SDET SMOKE DETECTOR

SF SUPPLY FAN

SFD COMBINATION AUTOMATIC SMOKE/FIRE

DAMPER WITH ACCESS DOOR

SM SHEETMETAL

SOV SOLENOID OPERATED VALVE

SP STATIC PRESSURE

SPECS SPECIFICATIONS

SQ SQUARE

SQFT SQUARE FEET

SS STAINLESS STEEL

STD STANDARD

STDBY STANDBY

STL STEEL

SUCT SUCTION

SUP SUPPLY

SV VARIABLE VOLUME SUPPLY

AIR TERMINAL BOX

TEMP TEMPERATURE

TOD TOP OF DUCT

TOP TOP OF PIPE

TSP TOTAL STATIC PRESSURE

TYP TYPICAL

UC UNDERCUT DOOR

UH UNIT HEATER

V VENT

VD VOLUME DAMPER

VEL VELOCITY

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VTR VENT THROUGH ROOF

VV SUPPLY VAV BOX

W WIDTH

W/ WITH

W/O WITHOUT

WB WET BULB TEMPERATURE

WG WATER GAUGE

WMS WIRE MESH SCREEN

GATE VALVE

BALL VALVE

BALL VALVE WITH HOSE BIBB, CAP & CHAIN (DRAIN

VALVES)

BUTTERFLY VALVE

BUTTERFLY VALVE WITH MEMORY STOP

(BALANCING VALVE)

GLOBE VALVE

PRESSURE REDUCING VALVE

CHECK VALVE

STRAINER W/BALL VALVE, HOSE BIBB & CAP (GATE

VALVE FOR STEAM)

SOLENOID VALVE

AUTOMATIC CONTROL VALVE, MODULATING

ACTUATOR

AUTOMATIC CONTROL VALVE, TWO POSITION

ACTUATOR

THREE WAY AUTOMATIC CONTROL VALVE,

MODULATING ACTUATOR

THREE WAY AUTOMATIC CONTROL VALVE, TWO

POSITION ACTUATOR

AUTOMATIC FLOW CONTROL VALVE (PRESSURE

INDEPENDENT)

COMBINATION FLOWMETER/SHUT OFF/BALANCING

VALVE (CIRCUIT SETTER)

FLOW MEASURING DEVICE

SAFETY RELIEF VALVE

UNION OR FLANGE (AS INDICATED BY PIPE SIZE -

SEE SPEC.)

END CAP

PRESSURE GAUGE WITH GAUGE CLOCK

PRESSURE/TEMPERATURE WELL

AUTOMATIC AIR VENT WITH ISOLATION VALVE

MANUAL AIR VENT

RISE (SINGLE LINE - PLAN VIEW)

DROP (SINGLE LINE - PLAN VIEW)

TOP TAKEOFF

BOTTOM TAKEOFF

PIPE BREAK (SINGLE LINE)

WATER METER DIAL TYPE

CLEAN-OUT FOR CONDENSATE DRAIN

DIRECTION OF FLOW IN PIPE

PITCH PIPE UP IN DIRECTION OF FLOW

PITCH PIPE DOWN IN DIRECTION OF FLOW

NEW WORK

SUPPLY LINES

RETURN LINES

DEMO LINE

DESIGNED:

DRAWN:

TECH REVIEW:

DATE:

J. SPECK

J. SPECK

J. SPECK

02/02/2026

SUB SHEET NO. DRAWING NO.

PKG.

NO.

SHEET

OF

PLAN

REPLACE GEOTHERMAL SYSTEM

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

10'-6"6'-0"18'-2"

4" 5'-10" 5'-10" 5'-10" 6'-0"

4"

5"

'-3

/4

2'

-7

5' -5

/4

2'

-7

4" 4"

G

AT

ES

GATE

2'-8 5/8"

'-6

EXISTING BUILDINGCOOLING TOWER 4'-1 1/4" W x 10' 11 3/4" L

EXISTING

TRANSFORMER

8" THICK WALL

8" THICK WALL

8" T

H

IC

K W

AL

L

8" T

H

IC

K W

AL

L

1' X 2' X 6" CONC. STEP

POST FLOOR FLANGE TYP.

5 7/8" X 5 7/8" - 13 REQ.

COOLING TOWER PIT

SCALE 1/8" = 1'-0"

NATIONAL MONUMENT

H200K-13 SLAB DRAIN 8" WIDE BY 13' 1-1/2" LONG

SLOPE 1/4" PER FT.

SLOPE 1/4" PER FT.

SL

O

PE

/4 " P

ER

F

T.

SL

O

PE

/4 " P

ER

F

T.

1. A 6" PERFORATED TILE SHALL RUN ALONG THE INSIDE OF THE

RETAINING WALL FOOTING. BACKFILL AROUND PIPE WITH 34"

STONE. WRAP STONE IN FILTER FABRIC AS SHOWN.

2. UTILIZE 4" BOTTOM KNOCK OUT IN TRENCH DRAIN AND

EXTEND A SOLID 4" PVC PIPE FROM THE TRENCH DRAIN TO

THE 6" PERFORATED PIPE.

3. ALLOW THE 6" PERFORATED PIPE TO PENETRATE THE

RETAINING WALL FOOTING NEAR THE DOUBLE SET OF GATES

AND TERMINATE 10' AWAY FROM RETAINING WALL WITH A

NDS-FWAS24-FLO PREFABRICATED DRY WELL KIT 24"DIA x 48".

SET WELL ON 4" THICK LAYER OF 34" STONE AND WRAP WELL

STRUCTURE IN FILTER FABRIC.

4. TOP TO HAVE A 6" SURFACE DRAIN INLET. RIM ELEVATION TO

MATCH SURROUNDING GRADE.

DRAINAGE NOTES:

CONCRETE PIER FOR FENCE POST (3 REQUIRED)

1. SET 8" DIA X 24" SONOTUBE AND FILL WITH CONCRETE.

2. SET CHAIN LINK FENCE POST FLOOR FLANGES AT TOP OF

CONCRETE WITH PIGTAIL OR L SHAPED BENT ANCHORS.

ELEVATION TO MATCH TOP OF RETAINING WALL.

3. TOOL A 12" RADIUS AROUND TOP EDGE OF CONCRETE.

4. REMOVE TOP 6" OF SONOTUBE ONCE CONCRETE HAS SET.

FENCE (BOTH SIDES)

FE

N

C E

(O N

E

SI

D E

O N

LY

N O

F

EN

C E

TH

IS

S

ID

E

H200K-13 SLAB DRAIN 8" WIDE BY 13' 1-1/2" LONG

4" KNOCK OUT TYP.

SI1.0

DRAWN:

TECH REVIEW:

DATE:

J. SPECK

J. SPECK

J. SPECK

02/02/2026

SUB SHEET NO. DRAWING NO.

PKG.

NO.

SHEET

OF

DETAILS

TURF

1/

2"

AV

G

COOLING

TOWER

8"

2' 0"

3/4" STONE

3/4" STONE

UNDISTURBED SOIL

FILTER FABRIC

12"

1" WEEP HOLE

3' O.C.

FILTER FABRIC

6" PERF.

PIPE

DIMPLED

DRAIN BOARD

8"

10" 8" 14"

8"

4"

6"5' 1-1/4"

UNDISTURBED SOIL

3/4" STONE

EXISTING BUILDING 10' 6"

1. COVER OVER ALL REBAR TO BE 2" MINIMUM ALL SIDES.

2. CONCRETE TO BE 4,000 P.S.I.

3. REINFORCING STEEL TO BE GRADE 60.

4. DRAIN PIPE TO BE 6" PERFORATED PVC.

5. LAPPING OF REBAR BE 18".

6. REBAR FOR EQUIPMENT PAD TO BE 2 LAYERS #4 BAR 12" O.C. EACH WAY.

7. REBAR FOR WALL TO BE #3 BAR 18" O.C. HORIZONTAL AND 16" O.C. VERTICAL BENT

INTO FOOTING AS SHOWN.

8. REBAR IN TOP OF FOOTING TO BE #4 BAR 12" O.C. EACH WAY.

9. REBAR IN BOTTOM OF FOOTING TO BE #4 BAR 14" O.C.

PIT

SCALE 1/8" = 1'-0"

EQUIPMENT PAD

SCALE 1/4" = 1'-0"

RETAINING WALL

SCALE 1/4" = 1'-0"

REPLACE GEOTHERMAL SYSTEM

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

6"

6" TYP.

SEE NOTE

NOTE:

CLEARANCE BETWEEN COOLING TOWER AND CONCRETE

WALL IS SHOWN AT 3'-0". VERIFY MINIMUM CLEARANCES

ONCE FINAL COOLING TOWER IS SELECTED AND ADJUST

DIMENSIONS ACCORDINGLY.

4' 1-1/4" X 10' 11 3/4"

SLAB TRENCH DRAIN:

H200K-13, 8" INTERNAL WIDTH

TRENCH DRAIN 39.37" LONG

WITH 3.94" INVERT. 479Q

DUCTILE IRON GRATE

4" PIPE FROM

TRENCH DRAIN

TO 6" PERF. PIPE

FINAL DIMENSION DETERMINED

AFTER TOWER IS SELECTED

TRENCH

DRAIN TYP

TRENCH

DRAIN TYP

SI2.0

DRAWN:

TECH REVIEW:

DATE:

J. SPECK

J. SPECK

J. SPECK

02/09/2026

SUB SHEET NO. DRAWING NO.

PKG.

NO.

SHEET

OF

DETAILS

REPLACE GEOTHERMAL SYSTEM

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

CHAIN LINK 2-1/2" (2 3/8" OD) X 6" WOODEN FENCE TO POST LINE ADAPTER (GALVANIZED PRESSED STEEL) CHAIN LINK FENCE 2-1/2" (2 3/8" OD) ROUND DOME EXTERNAL FENCE POST CAP (DIE CAST ALUMINUM)

TREATED 2 X 4 FASTENED TO ADAPTER WITH 1/4" X 1 1/2" HEAVY DUTY HEX HEAD WOOD FENCE LAG SCREWS

TREATED 1 X 6 FASTENED TO 2 X WITH 2" FLATHEAD STAINLESS STEEL SCREWS

CHAIN LINK 2-1/2" (2 3/8" OD) SS40 ROUND INDUSTRIAL FENCE PIPE TUBING (.13" WALL) (GALVANIZED STEEL)

CHAIN LINK 2-1/2" (2 3/8" OD) X 6" WOODEN FENCE TO POST LINE ADAPTER (GALVANIZED PRESSED STEEL)

TREATED 2 X 6 FASTENED TO ADAPTER WITH 1/4" X 1 1/2" HEAVY DUTY HEX HEAD WOOD FENCE LAG SCREWS

CHAIN LINK 2-1/2" (2 3/8" OD) X 6" WOODEN FENCE TO POST LINE ADAPTER (GALVANIZED PRESSED STEEL)

TREATED 2 X 8 FASTENED TO ADAPTER WITH 1/4" X 1 1/2" HEAVY DUTY HEX HEAD WOOD FENCE LAG SCREWS

CHAIN LINK FENCE 2-1/2" (2 3/8" OD) POST FLOOR FLANGE (GALVANIZED PRESSED STEEL) BOLTED TO TOP OF WALL

1/2" PIGTAIL OR L SHAPED BENT ANCHOR BOLTS W/ NUTS AND WASHERS (4 PER POST)

NOTE:

1. THREE CORNER POSTS WILL REQUIRE CHAIN LINK 2 1/2" (2 3/8 OD) X 6 WOODEN FENCE TO POST CORNER

ADAPTERS (GALVANIZED PRESSED STEEL) IN PLACE OF POST LINE ADAPTERS

2. THREE POSTS WILL REQUIRE CHAIN LINK 2 1/2" (2 3/8 OD) X 6 WOODEN FENCE TO POST END

ADAPTERS (GALVANIZED PRESSED STEEL) WHERE GATES ARE REQUIRED.

3. GATES WILL REQUIRE CHAIN LINK GATE HINGES ATTACHED TO FABRICATED GALVANIZED STEEL TUBULAR

FRAME. MOUNT TREATED 1 X 6 TO FRAME WITH STINLESS STEEL, SELF TAPING FLATHEAD SCREWS.

6'

" M

AX

SECTION OF FENCE AROUND EQUIPMENT PAD

SCALE 1/4" = 1'-0"

1/2" R

8" CONCRETE

RETAINING WALL

SI3.0

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M1.0

ELS

ELS

305342

114081

332MECHANICAL

SITE PLAN

MEMORIAL HOUSE

COOLING TOWER

CONDENSER WATER LINE

DRAIN LINE

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M2.0

ELS

ELS

305342

114081

(E) WSHP

(E) WSHP

(E) WSHP

(E) WSHP

(E) BOILER

NG

N G

N G

N G

CD

C D

C D

(E) WSHP

HOT WATER

RISERS UP

(E) SUPPLY/RETURN

FROM WELL FIELD

CH

CH

CH

CH

(E) HOT WATER COIL

(E) HOT WATER COIL

(E) DUCTWORK

(E) HOT WATER COIL

(E) SUPPLY/ RETURN

CONDENSER WATER

(E) SUPPLY/ RETURN

HOT WATER

(E) HOT WATER COIL

(E) REFRIGERANT

(E) CONDENSATE

(E) SUPPLY/ RETURN

HOT WATER

(E) SUPPLY/ RETURN

CONDENSER WATER

(E) DUCTWORK

(E) DUCTWORK

(E) DUCTWORK

(E) SUPPLY/ RETURN

HOT WATER

(E) SUPPLY/ RETURN

CONDENSER WATER

BASEMENT FLOOR PLAN

SHEET NOTES:

DISCONNECT LP PIPING FROM BOILER AND PREPARE FOR RECONNECTION. DEMOLISH BOILER, VENT, PUMPS, WIRING, AND

ACCESSORIES. CONCRETE PAD SHALL BE REUSED.

DISCONNECT DUCTWORK FROM WSHP. DUCTWORK AND HOT WATER COILS SHALL REMAIN. DEMOLISH WSHPs, ASSOCIATED PIPING, WIRING AND ACCESSORIES. RECLAIM AND VACATE ALL EXISTING REFRIGERANT PER EPA

GUIDELINES.

DEMOLISH REFRIGERANT AND CONDENSATE LINE FROM COMPRESSOR TO BLOWER UNIT LOCATED IN THE ATTIC.

DISCONNECT AND TEMPORARY CAP GROUND SOURCE CONDENSING WATER LOOP AT BUILDING ENTRANCE. DEMOLISH ALL CONDENSING WATER PIPING. REMOVE ALL HANGERS AND SUPPORTS ASSOCIATED WITH THE SYSTEM COMPONENTS.

DEMOLISH VISIBLE HOT WATER PIPING RISERS THAT LEADS TO SECOND FLOOR. HOT WATER DISTRIBUTION PIPING TO

COILS SHALL REMAIN.

GENERAL NOTES:

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.

CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.

DEMOLITION WORK

SCALE: 1/4" = 1'-0"

M2.0

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M2.1

ELS

ELS

305342

114081

NG

N G

N G

N G

REFRIGERANT

AND CONDENSATE

LINE FROM ATTIC

(E) SUPPLY/RETURN

FROM WELL FIELD

2" SUPPLY/RETURN

FROM COOLING

TOWER

CH

CH

CH

CH

WSHP-1

WSHP-4

WSHP-3 B-1

WSHP-5A

WSHP-2

P-5

P-1 P-2

(E) SUPPLY/ RETURN

HOT WATER

(E) SUPPLY/ RETURN

HOT WATER

ET-1

AS-1

SUPPLY/ RETURN

CONDENSER WATER

2" SUPPLY/ RETURN

FROM COOLING TOWER

SUPPLY/ RETURN

CONDENSER WATER

P-4 P-3

WSHP-1

WSHP-2

WSHP-4

WSHP-3

B-1

16x8

16x8

CH

CH

CH

CH

WSHP-5A

4" Ø EXHAUST

VENT

(E) HOT WATER COIL

(E) HOT WATER COIL

(E) DUCTWORK

(E) HOT WATER COIL

16x8

16x8 (E) HOT WATER COIL

(E) DUCTWORK

(E) DUCTWORK

(E) DUCTWORK

BASEMENT FLOOR PLAN

SHEET NOTES:

PROVIDE NEW BOILER. RECONNECT GAS LINE. PROVIDE NEW VENT AND RUN IN LOCATION OF EXISTING VENT AND DISCHARGE THROUGH EXISTING WINDOW OPENING. PROVIDE REQUIRED PIPING AND VALVES, REFER TO PIPING DIAGRAM.

PROVIDE NEW WSHPs. CLEAN EXISTING DUCTWORK AND RECONNECT WSHP. PROVIDE NEW RETURN DUCTWORK TO NEW FLOOR OPENING. CONNECT TO FLOOR GRILLE (GRILLE FURNISHED BY THE PARK). DO NOT REMOVE MORE FLOORING THAT NECESSARY TO INSTALL GRILLE. PROVIDE REQUIRED CONDENSER WATER PIPING AND VALVES, REFER TO PIPING DIAGRAM. EXISTING HOT WATER PIPING AND COILS TO REMAIN. RUN CONDENSATE DRAINS TO EXISTING CONDENSATE

PUMP.

NEW COOLING TOWER LINES SHALL BE DRILLED BELOW FOUNDATION WALL AND ENTER THE BUILDING THROUGH THE FLOOR. REINSTALL ANY BRICK WORK THAT WAS DISTURBED DURING INSTALLATION. REFER TO PIPING DIAGRAM FOR

REQUIRED VALVES AND PIPE ROUTING.

PROVIDE NEW PUMPS AND TANKS. REFER TO PIPING DIAGRAM.

RECONNECT GROUND SOURCE WATER LOOP TO NEW PIPING LOOP. REFER TO PIPING DIAGRAM. IF EXISTING WALL OPENINGS NEED TO INCREASE TO FIT NEW PIPING, REMOVE BRICKS THAT HAD BEEN NEWLY ADD. DISCUSS WITH COR

BEFORE MAKING PENETRATIONS.

BALANCE WATER AND AIR SYSTEM.

NEW WORK - PIPING

SCALE: 1/4" = 1'-0"

M2.1

GENERAL NOTES:

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.

CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.

NEW WORK - DUCTWORK

SCALE: 1/4" = 1'-0"

M2.1

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M2.2

ELS

ELS

305342

114081

ROOM D

ROOM C

ROOM B

ROOM A

HALL

T

T T

T

REFRIGERANT

AND CONDENSATE

LINE FROM ATTIC

T

T T

T

ROOM D

ROOM C

ROOM B

ROOM A

HALL

REFRIGERANT

AND CONDENSATE

LINE FROM ATTIC

FIRST FLOOR PLAN

NEW WORK

SCALE: 1/4" = 1'-0"

M2.2

DEMOLITION WORK

SCALE: 1/4" = 1'-0"

M2.2

SHEET NOTES:

DEMO EXISTING THERMOSTATS.

INSTALL NEW THERMOSTATS IN EXISTING LOCATION.

PROVIDE NEW RETURN DUCTWORK TO NEW FLOOR OPENING. CONNECT TO FLOOR GRILLES (GRILLES FURNISHED BY THE

PARK). DO NOT REMOVE MORE FLOORING THAT NECESSARY TO INSTALL GRILLE.

GENERAL NOTES:

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.

CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M2.3

ELS

ELS

305342

114081

UPPER HALL

ROOM F

ROOM E

ROOM H

ROOM G

WSHP-5B

T

26x24

REFRIGERANT

AND CONDENSATE

LINE FROM ATTIC

14x4

(TYP 4)

8x8

18x12

10x8 10x8

10x8

16x14

T

C D

CD REF

R

EF

UPPER HALL

ROOM F

ROOM E

ROOM H

ROOM G

(E)WSHP

SECOND FLOOR PLAN

NEW WORK

SCALE: 1/4" = 1'-0"

M2.3

DEMOLITION WORK

SCALE: 1/4" = 1'-0"

M2.3

SHEET NOTES:

DISCONNECT AND DEMOLISH WSHPs, ASSOCIATED REFRIGERANT PIPING, CONDENSATE, AND DUCTWORK. CEILING

GRILLES SHALL REMAIN.

DEMO THERMOSTAT.

HATCH OPENING TO ATTIC IS 28"x26" ALL EQUIPMENT WILL NEED TO FIT THROUGH EXISTING OPENING.

PROVIDE NEW WSHP WITH A NEW DRAIN PAN. PROVIDE NEW DUCTWORK PER FLOOR PLAN. CONNECT DUCTWORK TO EXISTING CEILING GRILLES. PROVIDE REQUIRED PIPING AND VALVES, REFER TO PIPING DIAGRAM.

INSTALL NEW THERMOSTATS IN EXISTING LOCATION.

CLEAN ALL DIFFUSERS.

BALANCE WATER AND AIR SYSTEM.

GENERAL NOTES:

1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.

CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M3.0

ELS

ELS

305342

114081

332MECHANICAL

FLOW DIAGRAM

BASEMENT

6' -3

/4

2" CTWR

2" CTWS

WHSP-5 B

LEVEL 2

WHSP-1

ROOM A

WHSP-2

ROOM B

WHSP-3

ROOM C

WHSP-4

ROOM D

LEVEL 1

LEVEL 2

ATTIC

2" CTWR

2" CTWS

(E) RETURN FROM WELL FIELD

(E) SUPPLY FROM WELL FIELD

B-1

MAKE-UP PRV

ADJUST TO 0.5 TO 1 PSI

MAXIMUM PRESSURE DROP

ACROSS AIR SEPARATOR

REDUCE TO SIZE

OF AIR SEPARATOR

N.C.

F

AAV (LARGE CAPACITY)

AAV

12"

TO 6" AFF

TO 6" AFF

ET-1

VFD

VFD

WATER

COLD

BACKFLOW

COUPON RACK

PT

LOCATE IN MECH ROOM AS

INSTRUCTED BY CHEMICAL

TREATMENT CONTRACTOR

AND OWNER.

1 X 1 TEE WITH

PLUGGED END

TYPICAL FOR 6

LOW

FLOW

BYPASS

CHEMICAL

FEED

2" CWS

TF

TF

2" CWR

P-5

WHSP-5A

LEVEL 2

CH EXISTING

HEATING COIL

CH EXISTING

HEATING COIL

CH EXISTING

HEATING COIL

CH EXISTING

HEATING COIL

2" H

W R

2" H

W S

REFRIGERANT LINE

SIZE PER MANUFACTURER'S

RECOMMENDATION

P-4

P-3

P-1

P-2

AS-1

CT-1

1-1/4"

HWR

1-1/4"

HWS

VFD

VFD

VFD

T

T

T

T

T

T

M

1" WATTS LF009

BACKFLOW

PREVENTER

RELIEF TO

INDIRECT

DRAIN

WATER METER

1" TO DCW TO

ADJACENT

BATHROOM

EXISTING GROUP LOOP

CIRCULATION PUMP

STRUCTURAL STEEL

SUPPORT BY

MANUFACTURER

CONCRETE PIT

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M4.0

ELS

ELS

305342

114081

332MECHANICAL

SCHEDULE

COOLING TOWER SCHEDULE

UNIT NO. LOCATION TYPE NO. OF CELLS TON/CELL NOMINAL

TONS

HEAT

REJECTION

CAPACITY

(MBH)

AMBIENT AIR

TEMP °F

(WB)

WATER TEMP (°F) WATER

FLOW

RATE

(GPM)

WATER

PRESSURE

DROP

(FT WC)

FAN DATA PUMP DATA BASIN DATA (EACH HEATER)

OBERATING

WEIGHT

(LBS)

MANUFACTURER

MODEL NUMBER

(BASIS OF DESIGN)

NOTESAIR FLOW

(CFM)

NO. OF

FANS PER

CELL

EXTERNAL

STATIC

PRESSURE

(IN WC)

MOTOR DATA ELECTRICAL

HP

ELECTRICAL SERVICE NO. OF

BASIN

HEATERS

AMBIENT

AIR TEMP °F

(DB)

BASIN

HEATER

POWER (kW)

ELECTRICAL SERVICE

INLET OUTLET RPM MAX BHP HP V PH HZ V PH HZ V PH HZ

CT-1 GRADE WATER 1 24 24 150 78 101 86 20 0.11 15430 1 - 5 5 240 1 60 0.33 240 1 60 1 0 3 240 1 60 4610 BAC

VFL-024-12H 1-3

1. PROVIDE FAN VFD

2. PROVIDE FACTORY CONTROL PANEL (FRANKLIN CONTROLS CTP3R-BYP010-P2/3)

3. PROVIDE MANUFACTURE STEEL FRAME. REFER TO VIBRATION ISOLATION SPECIFICATION.

EXPANSION TANK SCHEDULE

UNIT NO. LOCATION SERVICE

SYSTEM TEMP (°F)

SYSTEM PRESSURE AT

TANK LOCATION

(PSIG)

TANK PRESSURE

RATING (PSI)

TANK AIR

CHARGE

(PSIG)

TANK

AACCEPTANCE

VOLUME (GAL)

MANUFACTURER

MODEL NUMBER

(BASIS OF DESIGN)

NOTES

MIN MAX MIN MAX

ET-1 MECH RM CONDENSER

WATER 40 150 10 60 30 15 6.3 BELL & GOSSETT

D-15 1

1. ASME EXPANSION TANK WITH REPLACEABLE FULL ACCEPTANCE BLADDER

SIDE STREAM FILTER SCHEDULE

UNIT NO. LOCATION SERVICE

FLOW RATE

(GPM)

ELEC. DATA MANUFACTURER

MODEL NUMBER

(BASIS OF DESIGN)

NOTES

V PH HZ

SSF-1 COOLING

TOWER

COOLING TOWER

WATER 3 120 1 60 LAKOS

ILB-0037 1-2

1. ABV AUTOMATIC PURGE SYSTEM WITH BRASS 3/4" VALVE WITH REMOTE CONTROLLER 120-240V

2. SIZED FOR 15% FLOW OF THE CONDENSER WATER DESIGN FLOW (3 GPM)

AIR SEPARATOR SCHEDULE

UNIT NO. LOCATION SERVICE

FLOW RATE

(GPM)

PRESSURE

DROP (FT WC)

SIZE

DIA Ø" x H"

(INCHES)

CONNECTION SIZE

OPERATING

WEIGHT (LBS)

MANUFACTURER

MODEL NUMBER

(BASIS OF DESIGN)

NOTESINLET

(INCH)

OUTLET

(INCH)

AS-1 MECH RM CONDENSER

WATER 20 0.5 6-7/16"x12-3/16" 1 1 8.8 BELL & GOSSETT

EAS-1 1

1. BUILT IN STRAINER REQUIRED.

PUMP SCHEDULE

UNIT NO. LOCATION SERVICE PUMP

STYLE/TYPE

PUMP DATA FLUID DATA MOTOR DATA

WORKING

PRESSURE

(PSIG)

MANUFACTURER

MODEL NUMBER

(BASIS OF DESIGN)

NOTESWATER

FLOW RATE

(GPM)

HEAD

PRESURE

(FT WC)

NPSHR (FT

WC)

SHUT-OFF HEAD

PRESSURE

(FT WC)

PUMP

SPEED

(RPM)

IMPELLER

SIZE

(INCHES)

FLUID TEMP

(°F)

FLUID

TYPE % GLYCOL

MOTOR

SPEED

(RPM)

BHP HP DRIVE TYPE

ELECTRICAL SERVICE

V PH HZ

P-1 BASEMENT CONDENSER

WATER LOOP INLINE 15 10 2.67 10.3 1396 4 95 WATER 0 1800 0.064 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT

E-90 1

P-2 BASEMENT CONDENSER

WATER LOOP INLINE 15 10 2.67 10.3 1396 4 95 WATER 0 1800 0.064 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT

E-90 1

P-3 BASEMENT BOILERS INLINE 30 8 2.83 10.2 1387 4 180 WATER 0 1800 0.094 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT E-90 1

P-4 BASEMENT HOT WATER COILS INLINE 10 7 8.85 1200 4.125 180 WATER 0 3600 2 VFD 115/208-230 1 60 175 BELL & GOSSITT E-90E 1

P-5 BASEMENT COOLING TOWER INLINE 20 10 2.78 10.7 1423 4 95 WATER 0 1800 0.080 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT E-90 1

1. PROVIDE DISCONNECT SWITCH

BOILER SCHEDULE

UNIT NO. LOCATION SERVICE

OUTPUT

CAPACITY

(MBH)

INPUT MAX

(MBH)

MAX INLET

PRESSURE LP

"W.C.

MIN INLET

PRESSURE LP

"W.C.

WATER AIR ELECTRICAL SERVICE WORKING

PRESSURE

(PSIG)

MANUFACTURER

MODEL NUMBER

(BASIS OF DESIGN)

NOTES

GPM EWT (°F) LWT (°F) MAX PD (FT) % GLYCOL AIR INLET VENT SIZE FLA V PH HZ

B-1 MECH RM WSHP 146 175 14 11 30 140 110 2.2 0 - 6 12 120 1 60 50 BURNHAM

X-206LP 1

1. PROVIDE WITH PROPANE CONVERSION KIT

WATER SOURCE HEAT PUMP SCHEDULE

UNIT NO. LOCATION SERVICE NOM. TON ORIENTATION REFRIG. CFM BLOWER

HP

COMPRESSOR

QTY

AIR EXTERNAL

STATIC PRESSURE

(IN WC)

WATER FLOW

RATE (GPM)

WATER PRESSURE

DROP

(FT WC)

COOLING HEATING ELECTRICAL SERVICE

WEIGHT

(LBS)

DIMENSIONS

(WxDxH)

MANUFACTURER

MODEL NUMBER

(BASIS OF DESIGN)

NOTESEWT (°F) LWT (°F) EAT (°F) TC (MBH) SC (MBH) EER EWT (°F) LWT (°F) EAT (°F) HC (MBH) V PH HZ FLA MCA

WSHP-1 BASEMENT ROOM A 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH

CL015 1-4

WSHP-2 BASEMENT ROOM B 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH

CL015 1-4

WSHP-3 BASEMENT ROOM C 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH

CL015 1-4

WSHP-4 BASEMENT ROOM D 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH

CL015 1-4

WSHP-5A BASEMENT LEVEL 2 3 VERTICAL -

COMPRESSOR R-454B - 1/3 1 0.5 6.75 1.7 86 101 76/63.4 39.1 23.2 17.1 63 53 70 36.6 208-230 1 60 14.6 18.2 166 24"x26"x22" BOSCH

CP036 1-4

WSHP-5B ATTIC LEVEL 2 3 HORIZONTAL -

BLOWER R-454B 1150 1/2 - 0.5 - - 86 101 76/63.4 39.1 23.2 17.1 63 53 70 36.6 208-230 1 60 3.3 4.2 121 22"×20"×47" BOSCH

BIVA -36RCB 1-4

1. PROVIDE DRAIN PAN AND CONDENSATE PUMP (AS REQUIRED, IF DRAINING BY GRAVITY IS NOT FEASIBLE - BLUE DIAMOND MODEL MAXIBLUE, 23FT HEAD, 16.5 SUCTION LIFT, 208-230V).

2. PROVIDE HOSE KIT WITH ISOLATION VALVES, A STRAINER, BLOW DOWN VALVE, AND AUTO BALANCING VALVE

3. PROVIDE MANUFACTURE THERMOSTAT

4. COORDINATE SUPPLY AIR AND RETURN AIR DUCT CONNECTION ARRANGEMENT AND LEFT-/RIGHT-HAND MODEL TO MATCH LAYOUT SHOWN ON FLOOR PLAN FOR EACH APPLICATION PRIOR TO ORDERING.

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M5.0

ELS

ELS

305342

114081

332MECHANICAL

DETAILS

DO NOT USE ANY SCREWS,

BECAUSE THEY INTERFERE

WITH DAMPER BLADE(S).

FOR HANGING DUCT:

TRAPEZE DUCT OR

STRAP HANGER AROUND

DUCT COMPLETELY.

PROVIDE EXTRA LENGTH

TO AVOID "PINCHING"

OF INSULATION AT

CORNERS.

BUTT ENDS

& SEAL

PROVIDE LOCKING

QUADRANT ARM

STANDOFF

TYPICAL DUCT INSULATION & SUPPORTS NEAR

VOLUME DAMPERS

NOTES:

1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORE

THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.

2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.

3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA.

1"

MAX. 60" SEE NOTE c

ANGLE IRON

THREADED

HANGER ROD

UNISTRUT OR

HANGER

STRAP

OVER 60"

GALV. HANGER

SCALE:

DUCT HANGER SUPPORT

h = DUCT HEIGHT w = DUCT WIDTH h w

NO. OF VANES

EQUIVALENT DIAMETER = (w+h)/2

WITHIN 2 EQUIV. DIA.:

WHEN 2 ELBOWS ARE

NO. OF VANES

DEPICTED HERE:

EXAMPLE AT LEFT IS

O U

TS

ID

E R

AD

IU

S

IN

IN

C

H

ES

IN

SI

D E

R

AD

IU

S

O F

EL

BO

W

IN

IN

C

H

ES

N O

. 1 O

F

N O

. 2 O

F

N O

. 3 O

F

N O

. 2 O

F

N O

. 1 O

F

N O

. 1 O

F

NUMBER OF SPLITTERS

OF 3 VANES.

NO. 2 VANE OF A TOTAL

"NO. 2 OF 3" =

OF 3 VANES.

NO. 1 VANE OF A TOTAL

"NO. 1 OF 3" =

TERMINOLOGY:

= INSIDE RADIUS

= CENTERLINE RADIUS

R r rR r/w = 0.5 IS A SQUARE THROAT ELBOW!

FOR 1 ELBOW:

r/w >= 1.50

1.5 > r/w >= 0.70

0.7 > r/w >= 0.60

0.6 > r/w >= 0.55

HOWEVER, MINIMUM INSIDE RADIUS R SHOULD BE 2".

NOTE:

r/w RATIO:

RADIUS ELBOW AND SPLITTER VANE REQUIREMENTS

R=20" R=2" R=4-1/4" R=9-1/4"

SHORT RADIUS ELBOW SPLITTER VANE

QUANTITY AND SPACING

SPRAY ADHESIVE TO SEAL

EDGES. USE SAME ADHESIVE

AS USED ON DUCT LINER

FABRICATION BY DUCT LINER

MANUFACTURER SPECIFIED.

EDGE OF NOSE PIECES SHALL BE 1.5 INCHES

WIDE MINIMUM SO THAT TAKE-OFF FITTING

WILL SEAT PROPERLY.

(TYP. FOR 4)

PROVIDE SHEETMETAL

NOSE PIECES FOR

CLAMPING ENTIRE

EDGE OF EXPOSED

DUCTLINER.

(TYP. FOR 2)

EXPOSED EDGE OF

DUCT LINER (TYP.)

SINGLE LINE: PREFERRED

FITTINGS:

ALTERNATE FITTINGS

(SPACE LIMITATION):

SEE RECTANGULAR/ROUND

DUCT DETAIL AND DUCT

TAKEOFFS DETAILS

SEE RECTANGULAR/ROUND

DUCT DETAIL AND DUCT

TAKEOFFS DETAILS

ELBOW RADIUS

1.5D REFEREED

(ALTERNATE IS

1D)

ELBOW RADIUS

1.5D REFEREED

(ALTERNATE IS

1D)

PIPE ANCHOR DETAIL STRUCTURAL STEEL

SCALE: NTS

TYPE TAKE-OFF(CONICAL OR BELLMOUTH TYPE)

90° SPLITTER TAKE-OFF

W1

(CONVERGING & DIVERGING)

CONCENTRIC & ECCENTRIC TRANSITION

DUCT DOWN

45° ELBOW

W2

15° MAX

W

90° PARALLEL FLOW

TRANSITION TO ROUNDAT DUCT MAIN

SIDEWALL OUTLET

90° ROUND DUCT TAKE-OFF

D/W MIN D

AIR

FLOW

20° MAX

90° TAKE-OFF 90° CONICAL TAKE-OFF

20° MAX

R=D

90° OR 45° ELBOW

D

R

45° TAKE-OFF

1.5 x C

C

6" MIN

AIR

FLOW

AIR

FLOW

AIR

FLOW

AIR

FLOW

AIR

FLOW

AIR

FLOW

AIR

FLOW

AIR

FLOW

90° TURN

RECTANGULAR DUCT

NOTES:

1. TYPICAL FOR SUPPLY, RETURN, AND

EXHAUST DUCTWORK.

2. WHERE DUCT SIZE CHANGE OCCURS,

TRANSITION MAY NOT BE SHOWN ON

PLANS.

NOTES:

1. TYPICAL FOR SUPPLY,

RETURN, AND EXHAUST

DUCTWORK.

2. LOCATE THE CENTER

OF TAKE-OFFS FROM

DUCT MAINS AT THE

MIDPOINT OF THE SIDE

OF DUCT MAIN

("HEIGHT"/2)

3. SIZE A & B DIMENSIONS

ARE PROPORTIONAL TO

AIR QUANTITIES IN

EACH LEG SPLIT.

4. WHERE DUCT SIZE

CHANGE OCCURS,

TRANSITION MAY NOT

BE SHOWN ON PLANS.

5. IF W2 DOES NOT EQUAL

W1, MODIFY SHAPE OF

VANE EDGES TO

PROJECT TANGENT

PARALLEL TO DUCT

SIDES.

ROUND DUCT

BRANCH TAKE-OFF

L=1/4 W, 4" MIN.

RECTANGULAR DUCT

45° TAKE-OFF (TYP.)

AIR FOIL TURNING

VANES (TYP.)

PROVIDE VOLUME

DAMPERS DOWN-

STREAM OF EACH

SPLIT (TYP.)

SCALE:

ROUND DUCT FITTING DETAIL

SCALE:

RECTANGULAR DUCT FITTING DETAIL

TRANSITION (DIVERGING & CONVERGING)

SCALE:

DUCT SEALING DETAIL

RIGID TO FLEX AIR SEALING

AIR HANDLER AIR SEALING

RIGID DUCT AIR SEALING

FLEX TAKE-OFF FROM RIGID AIR SEALING

FLOOR BOOT AIR SEALING

SEAL JOINT BETWEEN BOOT AND CEILING

DRYWALL WITH UL-181 TAPE, MASTIC, OR

FIBERGLASS MESH AND MASTIC, OR CAULK -

COORDINATE WITH SUSTAINABLE

CONSULTANT FOR EXACT DETAILS AND

REQUIREMENTS

CEILING BOOT AIR SEALING

JOINT BETWEEN BOOT &

SUBFLOOR SEALED W/ MASTIC

OR FIBERGLASS MESH &

MASTIC OR CAULK

MASTIC (TYP.)

MASTIC (TYP.)

MASTIC

(TYP.)

MASTIC (TYP.)

MASTIC (TYP.)

MASTIC AND

SEAL ALL DUCT

JOINTS (TYP.)

SEALING AND SECURING EXPOSED

DUCTLINER7 5

TAPERED CONNECTION 45° ANGLE(IF MAIN DUCT

IS RECTANGULAR) OR CONICAL CONNECTION (IF

MAIN DUCT IS ROUND) L=1/4 W; 4"MIN

MAIN DUCT

VD

W

L

BRANCH DUCT

SUPPLY AIR

RETURN/EXHAUST AIR

LOW PRESSURE BRANCH TAKE-OFFS8

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M5.1

ELS

ELS

305342

114081

332MECHANICAL

DETAILS

SCALE:

TYPICAL HORIZONTAL DUCTED WSHP DETAIL

VALVES, ETC.

CONTROL VALVE, STRAINERS,

COMPONENTS INCLUDING

NOTE: INSULATE ALL PIPING

LINING

ACOUSTICAL

SEE SPECS

FLEX CONN

VIBRATION ISOLATION

REFER TO WATER COIL

DETAIL FOR PIPING AND

DRAIN REQUIREMENTS

DUCTED

RETURN AIR

FLEX CONNECTION

(TYP)

CONDENSER WATER

PIPES

EXISTING SUPPLY AIR

DUCTWORK

FILTER RACK WITH MERV-8 FILTER

WITH TIGHT-FITTING GASKET ON

DOOR TO FILTER ACCESS.

RETURN AIR DUCTWORK TO

FLOOR DIFFUSER

3 4" CONDENSATE DRAIN

TO CONDENSATE PUMP

PROVIDE 58"H x 22"W WALL

ACCESS PANEL FOR UNIT

ACCESS IF REQUIRED

INSTALL UNIT ON STEEL

FRAME/UNISTRUT PLATFORM

WITH DRAIN PAN BELOW

SCALE:

TYPICAL VERTICAL DUCTED WSHP DETAIL

X W x X H DUCTWORK

4"

SLAB

DUCTWORK INSULATION

PER SPECIFICATIONS

1-1/2" FLANGE

(TYP. 2)

FLOOR MOUNTED

GRILLE (EXISTING)

SHEET METAL PLENUM.

REFER TO FLOOR PLANS

FOR SIZE

FLOOR DIFFUSER PLENUM DETAIL

SCALE: NTS

3/4" DRAIN LINE VALVED W / CAP AND

CHAIN. LOCATE AT CENTER OF EACH

PLENUM BOX. FOR PLENUMS

INSTALLED ABOVE INACCESSIBLE

LOCATIONS (ELEC ROOMS, HARD

CEILINGS, ETC.) DRAIN LINE SHALL BE

RUN TO NEAREST MECHANICAL

SPACE.

1/2 W

1/2 W

W WW

CEILING

W

W

LINING

ALTERNATE METHOD FOR LOW CEILING CLEARANCE ONLY:

CEILING

(2xW) OR (3 FT) MIN

RETURN GRILLE

1" ACOUSTIC

CEILING PLENUM

PRIMARY METHOD

SUPPORT STRAP

RETURN GRILLE

SHEETMETAL

RETURN AIR

BOOT (NO

LINE OF

SIGHT) 1" ACOUSTICAL LINING

AREA OF OPENING=1/2

AREA OF GRILLE ON

BOTH ENDS, W=WIDTH

OF GRILLE

DIRECT BOOT

TERMINATION POINT

AWAY FROM FAN

DRIVEN EQUIPMENT

AND/OR TRANSFER

AIR OPENINGS IN

CEILING PLENUM

AREA OF

OPENING=AREA OF

GRILLE ON BOTH

SIDES W=WIDTH OF

GRILLE

RETURN AIR GRILLE WITH SOUND

ATTENUATION BOOT

NOTES:

1. CONTRACTOR SHALL INSTALL RETURN AIR BOOTS FOR ALL PLENUN RETURN AIR GRILLES UNLESS

NOTED OTHER WISE.

2. IF SPACE DOES NOT PERMIT FOR BOOT AS DETAILED ABOVE, THE CONTRACTOR SHALL SUBMIT

ALTERNATE DESIGN SUGGESTION(S) FOR APPROVAL, MAINTAINING NO LINE OF SIGHT BETWEEN

THE CEILING GRILLE OPENING AND THE OPEN END OF THE RETURN BOOT.

3. BOOT SHALL BE POSTIIONED SUCH THAT THE OPEN END IS PERPENDICULAR WITH ANY FULL

HEIGHT WALL TRANSFER OPENINGS OR TRANSFER DUCT OPENINGS.

EXISTING HOT WATER

COILS

DRAIN PAN

INSTALL WSHP ON

EXISTING WOODEN

STRUCTURE.

D = DUCT DIAMETER

= INSIDE BEND RADIUS

= CENTERLINE BEND RADIUS

R r Rr

D

AIR DEVICE SIZE

AS NOTED ON

PLANS

AIR DEVICE

NECK

SCREW AND

CLAMP

(TYPICAL)

SUPPORT ELBOW WITH TIE

R

R=DEPTH OF DUCT

FLEX CONN

ROUND DUCT

MAX OFFSET =

D/8"

MAX. OFFSET = D/8"

SUPPLY DIFFUSER

REGISTER (TYP.)

FLEX CONN. REFER

TO SPECS FOR

INSULATED TYPE

WHEN HEIGHT DOES NOT ALLOW FLEX CONN,

HARD-DUCT BUT BE SURE BRANCH IS 4" WIDER

THAN COLLAR TO ALLOW ALIGNMENT OF TERMINAL

WITHIN GRID WITHOUT FISHMOUTHING.

RECTANGULAR DUCT

RECTANGULAR DUCT

HARD CONNECTION WHERE

ALIGNMENT & SPACE

DICTATE ONLY

FLEX CONN

RECTANGULAR DUCT

ROUND DUCT

3D PREFERRED

1D MINIMUM

PROVIDE EQUALIZING GRID IF LESS THAN 3D

FLEXIBLE DUCT

DRAW BANDS SNUG

WITHOUT CRUSHING

FLEXIBLE DUCT

PROVIDE DURABLE

ELBOW SUPPORT

DIFFUSER/REGISTER DUCTWORK CONNECTIONS

NOTES:

1. DETAIL ALLOWS DUCTWORK TO BE INSTALLED BEFORE CEILING GRID THEN ALLOWS DIFFUSERS AND REGISTERS TO

BE POSITIONED INTO GRID.

2. PROVIDE INSULATED TRANSITION ROUND TO SQUARE INLET DIFFUSERS.

3. SECURE FLEXIBLE DUCT TO METAL DUCT WITH (2) STAINLESS STEEL CLAMPS OR NYLON TY-WRAPS TO INDIVIDUALLY

SECURE FLEXIBLE DUCT INNER SLEEVE AND OUTER SLEEVE. WHEN INSTALLED ON INSULATED SYSTEM SEAL INSULATION JOINT WITH VAPOR BARRIER MASTIC. PROVIDE NYLON TY-WRAP TOOL OR REUSABLE SS DRAW BANDS.

4. PROVIDE DUCT MOUNTED VOLUME DAMPER. AVOID NECK DAMPERS.

5. FLEXIBLE DUCTS SHALL BEND IN ONE DIRECTION ONLY WITH A MAXIMUM CHANGE IN DIFFERENCE OF 90 DEGREES.

6. UNLESS SHOWN OTHERWISE FLEXIBLE DUCT SIZE AND COLLAR OF TAP OFF SHALL BE SAME SIZE AS DIFFUSER NECK.

7. IF RUN-OUT LENGTH REQUIRES SEGMENT OF HARD DUCT, SIZE SHALL BE SAME AS DIFFUSER NECK. RUN-OUT TO

DIFFUSER SHALL BE AS STRAIGHT AS POSSIBLE.

8. INSTALL BENDS IN FLEXIBLE DUCTS WITH A MINIMUM CENTERLINE RADIUS EQUAL TO 1.5 DUCT DIAMETERS (r >= 1.5 x

D).

9. DO NOT EXCEED 6'-0" MAXIMUM LENGTH OF FLEX DUCT RECOMMENDED IN THE 2017 ASHRAE FUNDAMENTALS

HANDBOOK. INSTALL FLEX DUCT WITH NO MORE THAN 1/2" SAG PER FOOT.

DUCT WIDTH = 4" GREATER THAN NECK

/ COLLAR DIMENSION TO ALLOW FOR

CONNECTION W/O FISHMOUTHING

FILTER (MODIFY FRAME FOR

SIDE OR BOTTOM PULL IF

NECESSARY TO ALLOW

COORDINATION OF OTHER

CEILING SERVICES WITH

FILTER REMOVAL)

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M5.2

ELS

ELS

305342

114081

332MECHANICAL

DETAILS

NOTE: USE TFE TAPE ON ALL THREADED

JOINTS.

HIGHEST POINT IN SYSTEM

4 PIPE DIAMETERS (WITH 18"MAX)

REDUCER

1/4" BRASS NIPPLE

1/4" GAGE COCK

1/4" TYPE "L" COPPER TUBE

NOTE: USE TFE TAPE ON ALL THREADED

JOINTS.

HIGHEST POINT IN SYSTEM

4 PIPE DIAMETERS (WITH 18"MAX)

REDUCER

1/4" BRASS NIPPLE

1/4" GAGE COCK

FLOAT-TYPE AIR VENT

1/4" TUBE TO SCHRAEDER ADAPTER

1/4" TYPE "L" COPPER TUBE

SCALE:

TYPICAL PIPE INSULATION &

VALVE HANDLE EXTENSION

SCALE:

AUTOMATIC AIR VENT ASSEMBLY

MANUAL AIR VENT ASSEMBLY

BUTT & SEAL

JOINTS

CAP INSULATION. LEAVE

NO EXPOSED INSULATION

ANYWHERE

PROVIDE VALVE

EXTENSION KIT

TO ALLOW PROPER

INSULATION COVERAGE

TYPICAL FOR CHECK VALVES

AND BALANCING VALVES STRAINERS WITH BLOW-OFF.

TYPICAL FOR Y-BRANCH AND

TYPICAL FOR ALL VALVES

CASE

REMOVABLE

ENCLOSED IN

FIBERGLASS

BOARD.

CASE

REMOVABLE

CASE

REMOVABLE

NOTES:

1. INSULATION TO BE USED ON STEAM,

CONDENSATE RETURN, CHILLED WATER AND

CW MAKEUP PIPING. REFER TO INSULATION

SPEC FOR ADDITIONAL INSULATION FINISH ON

EXPOSED FITTINGS.

2. SEAL WATERTIGHT, ALL EXPOSED FIBERGLASS AND

WHERE TWO OR MORE PIECES OF INSULATION MEET.

INSULATION SHALL BE PER SPECIFICATION DENSITY

(EXCEPT AT HANGERS) AND THE SAME THICKNESS AS

THE ADJOINING PIPE INSULATION.

SCALE:

SCALE:

PIPE HANGER SUPPORT

VALVE & STRAINER INSULATION DETAIL

ADJUSTABLE HANGER

WITH ROLLER

LOCKING NUT

SUPPORT NUT INSULATION

PIPE

PIPE COVERING

PROTECTION

16 GA SADDLE

GALVANIZED

INSULATION

SHIELD 12"LONG.

NOTES:

1. SEE SPECIFICATION FOR HANGER SIZES.

2. PIPE 8" AND LARGER SHALL HAVE ROLLER SUPPORTED WITH DUAL RODS.

3. FOR CHW SERVICE OVER 3" REPLACE SADDLE WITH 12" LONG 14 GA SHIELD WITH RIGID

INSULATION BETWEEN PIPE AND SHIELD.

MIN.9 lb/cft

DENSITY RIGID

INSULATION AT

SHIELD

CLEVIS HANGER

(FOR 1/2" UP TO

HEAVY DUTY

& INCL. 3" PIPE)

(FOR 4" TO 6" PIPE)

INLINE PUMP

SCALE:

SCALE:

INLINE PUMP PIPING (EACH PUMP)

DIFF.

PRESSURE

SWITCH

DIFFERENTIAL PRESSURE SWITCH

CLOSED WATER SYSTEM PIPING SIZING CHART

PIPING SIZE

(INCHES)

FLOW

(GPM)

3/40 - 3.0

13.0 - 6.5

1-1/46.5 - 12

1-1/212 - 20

220 - 40

2-1/240 - 65

NOTE:

· MINIMUM PIPE SIZES UNLESS LARGER SIZES ARE INDICATED ON

DRAWINGS.

365 - 115

4115 - 240

NOTES:

1. SLOPE 1" PER FT

DOWN TO INSTRUMENT

2. TUBING ROUTING

SHALL AVOID HIGH

TEMPERATURE SWIRLS.

TUBING AND SUPPORTS

SHALL INCLUDE

PROVISIONS FOR

THERMAL EXPANSION.

3. FOR STAND DETAIL

SEE DWG. NO. FOR

MOUNTING DETAIL SEE

DWG. NO.

4. TUBING SHALL BE

SUPPORTED EVERY 5'-0"

WITH MILL GALVANIZED

STRUT & STAINLESS

STEEL TUBING CLAMPS.

5. IF UNABLE TO

SUPPORT TUBING

EVERY 5'-0",

INSTRUMENT TUBE

TRAY IS TO BE USED

WITH THE APPROPRIATE

TUBING CLAMPS.

1/2"MNPTx1/2"T SS CONN. COMPRESSION TYPE 1/2"ODx0.035 316SS SMLS TUBE

1/2"Tx1/2"Tx1/2"T TEE SS COMPRESSION TYPE

1/2" 3 VALVE MANIFOLD SS

1/2" BALL VALVE SS, 2000#

1/2"MNPT PLUG SS

1/2" TUBE UNION SS COMPRESSION TYPE7

ITEM MATERIAL

BILL OF MATERIALS

QTY PROVIDED BY

INSTALLER

INSTALLER

INSTALLER

INSTALLER

INSTALLER

INSTALLER

INSTALLERA/R

A/R

SCALE:

CLOSED WATER SYSTEM PIPING SIZING CHART

SCALE:

NC

3/4"

SHUNT FROM CHILLED OR

HOT WATER SUPPLY

RETURN

3/4"

5 GALLON FILTER

FEEDER TANK OR

OTHER SIZE AS

SPECIFIED ASME

RATED

TO CHILLED OR HOT

WATER RETURN

SHUT OFF/

BALANCING VALVE

WITH MEMORY STOP

SUPPLY

SCALE:

CHEMICAL FEED (FILTER FEEDER)

PT

1 X 1 TEE WITH PLUGGED END

TYPICAL FOR 6

NOTES:

1. TYPICAL FOR, CHILLED WATER AND HOT WATER.

LOCATE IN MECH ROOM AS INSTRUCTED BY CHEMICAL

TREATMENT CONTRACTOR AND OWNER.

BALL VALVE

RETURN MAIN

SUPPLY MAIN

SCALE:

COUPON RACK

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

M5.3

ELS

ELS

305342

114081

332MECHANICAL

DETAILS

TRENCH

SCALE:

FINISHED GRADE

NATIVE BACK FILL

INSTALL 6" BEDDING

BELOW PIPE AND 12"

ABOVE PIPE.

MINIMUM 18" WIDE.

MAINTAIN 6" MINIMUM

CLEARANCE TO EXISTING

PIPES

UNDISTURBED

EARTH

6"

12"

SHORE

TRENCH

PER OSHA

INSTALL PIPE

WITH A MINIMUM

OF 24" BURRY

3' -0

" M

AX

1'-6" MAX

FAN MOTOR

2" MPT DRAIN

10'-11 3/4"

5' -1

5/

8"

5'-11 5/8"

2" MPT OVERFLOW

1" MPT MAKE-UP

ACCESS

SPRAY PUMP

4" MPT DRAIN

4" BFW FLUID IN

4'-1 1/4"

DOOR

1/2" FPT VENT 1/2" FPT VENT

4" BFW FLUID OUT

WITH CAP

6' -3

/4

COOLING TOWER DETAIL

SCALE: NTS

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

ELS

ELS

305342

114081

332ELECTRICAL

GENERAL NOTES

GENERAL NOTES

1. DRAWINGS ARE CONCEPTUAL AND ARE INTENDED TO SHOW GENERAL SYSTEM

CONFIGURATION AND PERFORMANCE. NOT ALL NECESSARY DEVICES AND COMPONENTS

ARE SHOWN. PROVIDE ALL DEVICES AND COMPONENTS FOR A FULLY FUNCTIONAL SYSTEM.

2. CONTRACT DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND MUST BE USED IN

CONJUNCTION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. CONTRACTOR SHALL

COORDINATE ALL DRAWINGS AND SPECIFICATIONS PRIOR TO COMMENCING WORK.

QUESTIONS REGARDING DESIGN INTENT OR SYSTEM OPERATION SHALL BE PROMPTLY

BROUGHT TO ATTENTION OF THE COR.

3. INSTALL DEVICES AND SYSTEM WIRING TO AVOID DISTURBANCE TO HISTORIC FABRIC AND

TO AVOID VISUAL INTRUSION INTO PUBLIC VISITATION AREAS. HISTORIC PRESERVATION

SHALL BE TAKEN INTO ACCOUNT THROUGHOUT THE PROJECT.

4. USE EXISTING ROUTING FOR NEW FEEDERS AND BRANCH CIRCUITS WHENEVER POSSIBLE. IF

A PATH IS FOUND TO BE UNTENABLE, CONFIRM NEW ROUTING WITH THE COR. WIRING SHALL

BE INSTALLED WITHIN CONDUIT WHERE EXISTING PATHS INCLUDE CONDUIT.

5. USE EXISTING HOLES AND OPENINGS TO INSTALL CONDUIT AND CABLE. WHERE NO USABLE

PATH EXISTS, CUT NEW HOLES. COORDINATE SIZE AND LOCATIONS OF DRILLED HOLES AND

CUT OPENINGS WITH THE COR.

6. IT IS RECOMMENDED THAT THE CONTRACTOR VISIT AND BECOME FAMILIAR WITH THE SITE

PRIOR TO SUBMITTING BID.

7. THE TERM "REMOVE" MEANS DISCONNECT AND REMOVE THE DEVICE INCLUDING OUTLETS,

BRANCH CIRCUIT WIRING AND RACEWAY.

8. THE TERM “PROVIDE” MEANS FURNISH AND INSTALL, COMPLETE AND READY FOR USE.

9. THE TERM “CONTRACT DOCUMENTS” MEANS THE PROJECT MANUAL, DRAWINGS, ADDENDA,

SKETCHES AND OTHER DOCUMENTATION THAT DEFINE THE WORK.

10. ANY CONFLICTS BETWEEN SPECIFICATIONS AND DRAWINGS SHALL BE PROMPTLY BROUGHT

TO COR’S ATTENTION. THE CONTRACTOR SHALL NOT PROCEED WITH ANY WORK EXCEPT AT

THEIR OWN RISK, UNTIL CLARIFICATIONS OF CONFLICTS ARE ISSUED TO THE CONTRACTORS

BY THE COR.

11. WHERE DEVICES, WIRING, MOLDING, ETC. ARE TO BE REMOVED FROM EXISTING HISTORIC

FABRIC AND REMOVAL MAY NOT BE POSSIBLE WITHOUT DAMAGING EXISTING HISTORIC

FABRIC, NOTIFY COR PRIOR TO THE REMOVAL OF THE ITEM.

12. PROVIDE ENGRAVED, PHENOLIC NAMEPLATE PANELS, SAFETY SWITCHES, CABINETS, ETC,

TO IDENTIFY THE UNIT AND THE SOURCE PANEL AND CIRCUIT NUMBER.

13. ALL ELECTRICAL MATERIALS SHALL BE TEMPERATURE RATED FOR 90°C.

DESIGN ASSIST NOTES

1. ELECTRICAL WORK RELATED TO MECHANICAL SYSTEMS SHALL BE PROVIDED USING A

DESIGN-ASSIST APPROACH. ELECTRICAL CONTRACTOR SHALL PREPARE FINAL ELECTRICAL

DESIGN DOCUMENTS BASED ON MECHANICAL EQUIPMENT REQUIREMENTS, FIELD

CONDITIONS, AND APPLICABLE CODES. FINAL DESIGN SHALL BE SUBMITTED FOR ENGINEER

AND OWNER REVIEW PRIOR TO INSTALLATION. DRAWINGS INDICATE GENERAL INTENT ONLY

AND DO NOT REPRESENT A COMPLETE ELECTRICAL DESIGN.

2. CONTRACTOR SHALL VERIFY EXISTING ELECTRICAL CAPACITY AND INFRASTRUCTURE AND

NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH FINAL DESIGN.

3. ELECTRICAL CONTRACTOR SHALL COORDINATE POWER AND CONTROL WIRING

REQUIREMENTS WITH THE MECHANICAL CONTROLS CONTRACTOR AND EQUIPMENT

MANUFACTURERS.

4. CONTRACTOR SHALL VERIFY ALL MECHANICAL EQUIPMENT ELECTRICAL CHARACTERISTICS,

INCLUDING VOLTAGE, PHASE, MCA, MOCP, AND CONTROL REQUIREMENTS PRIOR TO FINAL

DESIGN.

E0.1

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

ELS

ELS

305342

114081

GATES

GATE RESTROOM BUILDING

COOLING TOWER

EXISTING

TRANSFORMER

EXISTING MAIN DISTRIBUTION

PANEL MDP: 120/240V, 1Ø

200A MCB

ELECTRICAL

SITE PLAN

MEMORIAL HOUSE

E1.0

EXISTING 1-PHASE

TRANSFORMER

NEW COOLING

TOWER

SITE PLAN

SCALE: 1/16" = 1'-0"

E1.0

MDP

SCALE: 1/4" = 1'-0"

E1.0

SHEET NOTES

1. NEW COOLING TOWER (CT-1): 208V,1Ø, FURNISHED AND SET-IN-PLACE BY ANOTHER

CONTRACTOR. THIS CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING TO NEMA

3R SAFETY SWITCHES AND POWER WIRING IN LFMC TO CT.

2. NEW COOLING TOWER PUMP. FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR.

THIS CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.

3. NEW HEAT BASIN, FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS

CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.

4. NEW CONTROL PANEL, FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS

CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.

5. NEW SIDE STREAM FILTER: 120V, 1Ø; FURNISHED AND SET-IN-PLACE BY ANOTHER

CONTRACTOR. THIS CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.

6. EXISTING PANEL MDP: PROVIDE NEW CIRCUIT BREAKERS FOR ALL REPLACEMENT & NEW

EQUIPMENT. PROVIDE NEW COVER DOOR WITH NAMEPLATE ON THE COVER TO IDENTIFY

THE PANEL & ELECTRICAL CHARACTERISTICS.

7. PROVIDE NEW WALL MOUNTED VARIABLE FREQUENCY DRIVES HAVING THE

CHARACTERISTICS RECOMMENDED BY THE COOLING TOWER MANUFACTURER.

COOLING TOWER PLAN

SCALE: 1/4" = 1'-0"

E1.0

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

ELS

ELS

305342

114081

(E) WSHP

(E) WSHP

(E) BOILER

(E) WSHP

EXISTING HOUSE PANEL DP-1:

120/240V, 1Ø

200A MCB

(E) HOT WATER

PUMPS (TYP 2)

(E) WSHP

UPPER HALL

ROOM F

ROOM E

ROOM H

ROOM G

(E)WSHP

DEMOLITION FLOOR PLAN

SHEET NOTES:

1. (5) WATER SOURCES HEAT PUMPS, (1) BLOWER FAN, A BOILER, AND (2) HOT WATER TO BE REMOVED BY ANOTHER CONTRACTOR. THIS CONTRACT SHALL DISCONNECT POWER WIRING AND REMOVE WIRING, CONDUIT AND DEVICES, BACK

TO PANEL HOUSE PANEL.

2. VERIFY THAT FEEDERS ARE DE-ENERGIZED AND DEVICES ARE OBSOLETE AND REMOVE WIRING, RACEWAY AND DEVICES.

NOTIFY THE COR IF A FEEDER AND ASSOCIATED DEVICES ARE FOUND TO BE FOR EQUIPMENT THAT IS IN-SERVICE: SEE

PHOTO P1.

BASEMENT

SCALE: 1/4" = 1'-0"

E2.0

E2.0

LEVEL 2

SCALE: 1/4" = 1'-0"

E2.0

DISTRIBUTION PANEL

SCALE: NTS

E2.0

DISTRIBUTION PANEL

SCALE: NTS

E2.0

MEMORIAL HOUSE

GEORGE WASHINGTON BIRTHPLACE

NATIONAL MONUMENT

HACE

ELS

ELS

305342

114081

EXISTING HOUSE PANEL DP-1:

120/240V, 1Ø

200A MCB

WSHP-1

WSHP-4

WSHP-3 B-1

WSHP-5A

WSHP-2

P-5

P-1 P-2

P-4 P-3

UPPER HALL

ROOM F

ROOM E

ROOM H

ROOM G

WSHP-5B

NEW WORK FLOOR PLAN

E2.1BASEMENT

SCALE: 1/4" = 1'-0"

E2.1

LEVEL 2

SCALE: 1/4" = 1'-0"

E2.1

SHEET NOTES

1. (4) NEW WATER SOURCE HEAT PUMPS (WSHP-1-4): 208V,1Ø, 10.1 MCA FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS CONTRACT SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM

PANEL, NEW SAFETY SWITCH AND POWER CONNECTIONS.

2. NEW WATER SOURCE HEAT PUMPS (WSHP-5A): 208V,1Ø, 18.2 MCA FURNISHED AND SET-IN-PLACE BY

ANOTHER CONTRACTOR. THIS CONTRACT SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM

PANEL, NEW SAFETY SWITCH AND POWER CONNECTIONS.

3. NEW BLOWER UNIT (WSHP-5B): 208V,1Ø, 4.2 MCA FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS CONTRACT SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM PANEL, NEW

SAFETY SWITCH AND POWER CONNECTIONS.

4. NEW BOILER: 120V, 1Ø, FURNSIHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS CONTRACT

SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM PANEL, NEW SAFETY SWITCH AND POWER

CONNECTIONS.

5. FIVE NEW PUMPS…