The project involves demolishing the existing water source heat pump (WSHP) system with ground source condensing water loops and replacing it with a new system comprising: five water source heat pumps (WSHP-1 through WSHP-5B) rated at 1.5 to 3 tons, a new propane-fired boiler (Burnham X-206LP, 146 MBH output), a cooling tower (BAC VFL-024-12H, 24-ton capacity with basin heaters), five inline circulation pumps with variable frequency drives, expansion tanks, air separators, and side stream filtration. The new system will serve multiple zones across the basement, first floor, and second floor (attic) of the historic structure. Key requirements include disconnecting and removing existing refrigerant per EPA guidelines, reconfiguring existing ductwork and hot water coils to remain in service, providing new condensate drain lines to existing pumps, installing new thermostats and controls, and balancing both water and air systems. The electrical work requires new branch circuit wiring, safety switches, and variable frequency drive installations powered from the existing main distribution panel (120/240V, 1Ø, 200A). Construction must prioritize historic preservation by minimizing disturbance to historic fabric, using existing routing for conduit and wiring where feasible, and coordinating all penetrations with the Contracting Officer. The drawings indicate design-assist requirements with the electrical contractor responsible for preparing final electrical design documents based on mechanical equipment specifications and field conditions prior to installation.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
REPLACE THE GEOTHERMAL SYSTEM
AT THE MEMORIAL HOUSE MUSEUM
COLONIAL BEACH
VIRGINIA
SHEET SUB TITLE
NO.SHEET
1 CS COVER SHEET
2 SI1.0 PLAN
3 SI2.0 DETAILS
4 SI2.0 DETAILS
5 M0.1 MECHANICAL LEGEND AND NOTES
6 M1.0 MECHANICAL SITE PLAN
7 M2.0 MECHANICAL BASEMENT DEMOLITION FLOOR PLAN
8 M2.1 MECHANICAL BASEMENT NEW WORK FLOOR PLAN
9 M2.2 MECHANICAL LEVEL 1 FLOOR PLAN
10 M2.3 MECHANICAL LEVEL 2 FLOOR PLAN
11 M3.0 MECHANICAL FLOW DIAGRAM
12 M4.0 MECHANICAL SCHEDULE
13 M5.0 MECHANICAL DETAILS
14 M5.1 MECHANICAL DETAILS
15 M5.2 MECHANICAL DETAILS
16 M5.3 MECHANICAL DETAILS
17 E0.1 ELECTRICAL GENERAL NOTES
18 E1.0 ELECTRICAL SITE PLAN
19 E2.0 ELECTRICAL DEMOLITION FLOOR PLAN
20 E2.1 ELECTRICAL NEW WORK FLOOR PLAN
REPLACE GEOTHERMAL SYSTEM
2/9/2026
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M0.1
ELS
ELS
305342
114081
332MECHANICAL
LEGEND AND NOTES
1. REFER TO ALL DRAWINGS SPECIFICATION FOR GENERAL DESCRIPTION OF AREAS REQUIRING
DEMOLITION.
2. REFER TO CONSTRUCTION MANAGER'S INSTRUCTIONS FOR ALL EXISTING EQUIPMENT AND
MATERIALS THAT SHALL REMAIN THE PROPERTY OF THE OWNER.
3. ITEMS OF VALUE WHICH ARE NOT DIRECTED TO BE RETURNED TO THE OWNER, SHALL BECOME
THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM SITE AND LEGALLY
DISPOSED OF. STORAGE OR SALE OF ITEMS ON THE PROJECT SITE IS PROHIBITED.
4. PROTECTION: ENSURE THE SAFE PASSAGE OF PERSONS IN AND AROUND THE BUILDING DURING
DEMOLITION. PREVENT INJURY TO PERSONS AND DAMAGE TO PROPERTY. PROVIDE ADEQUATE
SHORING AND BRACING TO PREVENT COLLAPSE. IMMEDIATELY REPAIR DAMAGED PROPERTY TO
THE CONDITION BEFORE BEING DAMAGED. TAKE EFFECTIVE MEASURES TO PREVENT
WINDBLOWN DUST.
5. UTILITIES: MAINTAIN ALL UTILITIES EXCEPT THOSE REQUIRING REMOVAL OR RELOCATION. KEEP
UTILITIES IN SERVICE AND PROTECT FROM DAMAGE. DO NOT INTERRUPT UTILITIES SERVING
OCCUPIED AREAS WITHOUT FIRST OBTAINING PERMISSION FROM HARVARD FACILITIES. PROVIDE
TEMPORARY SERVICES AS REQUIRED.
6. THESE DRAWINGS ARE DIAGRAMMATIC ONLY AND REFLECT OVERALL SYSTEM REMOVAL. NOT
EVERY ITEM OR COMPONENT OF A SYSTEM IS SHOWN.
7. THIS CONTRACTOR SHALL PROVIDE SHUT DOWN OF SERVICES (BOILERS, AHU, PUMPS, ETC.) AND
TRACING OF ALL PIPING WITHIN BASE BID.
HVAC DEMOLITION SPECIFICATION
1. GENERAL NOTES, SYMBOLS LIST AND DETAILS ARE APPLICABLE TO ALL MX.XX AND P.XX SERIES
DRAWINGS.
2. DRAWINGS ARE DIAGRAMMATIC, DETERMINE EXACT LOCATIONS OF SYSTEMS AND COMPONENTS
IN FIELD.
3. COORDINATE WORK OF THIS SECTION WITH THAT OF OTHER SECTIONS.
4. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
5. PROVIDE INFORMATION AND HARDWARE AS NECESSARY TO COORDINATE CONCRETE PADS AND
STEEL PLATFORMS REQUIRED FOR MECHANICAL WORK.
6. COORDINATE ROOF PENETRATIONS WITH WORK OF OTHER SECTIONS AND WITH FLASHING
REQUIREMENTS.
7. SHEETMETAL FITTINGS SHOWN ARE TO BE PROVIDED. NO SUBSTITUTES SHALL BE ALLOWED
WITHOUT PRIOR CONSENT FROM ARCHITECT/ENGINEER.
8. REFER TO SPECIFICATIONS FOR DUCTWORK CONSTRUCTION CLASSES, SEAL, AND LEAKAGE
CLASSES.
9. RUN DUCTS AND PIPING CONCEALED, UNLESS SPECIFIED OTHERWISE, AND CLEAR OF CEILING INSERTS. ALL DUCTWORK SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO WALL AND UNDERSIDE
OF BEAMS AND JOISTS.
10. INSTALL THERMOSTATS AT LOCATIONS SHOWN ON PLANS OR AS DIRECTED BY ARCHITECT.
MOUNTING HEIGHT AFF SHALL COMPLY WITH ADA.
11. ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN PIPING AND DUCTS
AND TRANSITIONS AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST.
12. VERIFY ALL EQUIPMENT CONNECTIONS WITH MANUFACTURER'S CERTIFIED DRAWINGS. VERIFY
AND PROVIDE DUCT TRANSITIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND COORDINATE
ALL DIMENSIONS BEFORE FABRICATION.
13. ACCESS PANELS SHALL BE PROVIDED TO CLEAN COILS AND SERVICE DAMPERS, HEATERS,
VALVES AND ALL CONCEALED MECHANICAL EQUIPMENT.
14. SUPPORT ALL EQUIPMENT, PIPING AND DUCTWORK FROM BUILDING STRUCTURE TO PROVIDE A
VIBRATION FREE INSTALLATION. PROVIDE TO GC A LIST OF ALL WEIGHTS AND METHODS OF
SUPPORT FOR COORDINATION. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
15. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH NEC, AND DIVISION 26 SPECIFICATIONS.
16. INTERNAL AIR FLOW DIMENSIONS ARE SHOWN FOR DUCTS. CONTRACTOR SHALL INCREASE SIZE
FOR LINER IF APPLICABLE.
17. ALL MATERIALS AND EQUIPMENT SHALL BE NEW, OTHER THAN SPECIFIC RENTED ITEMS
IDENTIFIED ON PLANS.
18. DIFFUSER SIZES SHOWN ARE NECK SIZES; REGISTER AND GRILLE SIZE ARE NOMINAL.
19. ALL CONDENSATE DRAINLINES SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTSET.
20. PROVIDE FLEXIBLE CONNECTIONS ON ALL DUCTS CONNECTING TO FANS AND AIR HANDLING
UNITS UNLESS INTERNALLY ISOLATED. ALL DUCTS TO BE GROUNDED ACROSS FLEXIBLE
CONNECTION WITH FLEXIBLE COPPER GROUNDING STRAPS.
21. THE INSIDE OF DUCTWORK VISIBLE THROUGH A GRILLE OR DIFFUSER SHALL BE PAINTED FLAT
BLACK.
22. INSULATE PIPING AND DUCTWORK AS SPECIFIED: PERFORM TESTS SPECIFIED BEFORE
INSULATING.
23. PROVIDE HANGERS, CLAMPS, OFFSETS, EXPANSION JOINTS, ANCHORS AND GUIDES AS
NECESSARY TO PREVENT STRESS ON PIPING.
24. PROVIDE VENTS AT HIGH POINTS IN PIPING SYSTEMS AND DRAIN VALVES AT LOW POINTS.
25. PROVIDE AT LEAST THREE-ELBOW SWING FOR PIPE TAKE-OFFS TO TERMINAL EQUIPMENT AND
RISERS.
26. ELBOWS IN DUCT SYSTEMS SHALL BE FULL RADIUS (CENTERLINE RADIUS = 1.5 DUCT WIDTH)
WHERE SPACE PERMITS. WHERE LIMITED CLEARANCE OCCURS, PROVIDE SHORT RADIUS ELBOW
WITH FULL LENGTH SPLITTER VANES PER SMACNA. MITERED (SQUARE) ELBOWS WITH TURNING
VANES MAY NOT BE SUBMITTED WITHOUT WRITTEN CONSENT FROM THE ARCHITECT/ENGINEER.
27. ISOLATION VALVES IN PIPING SYSTEMS ARE NOT SHOWN ON PLANS (FOR CLARITY) BUT ARE REQUIRED AT ALL PIPE BRANCHES AND CONNECTIONS TO EQUIPMENT REFER TO DETAIL SHEETS
AND FLOW DIAGRAMS.
28. PITCH PIPING 1 INCH IN 20 FEET MINIMUM IN DIRECTION OF FLOW, TO ALLOW FOR DRAINING
29. MANUAL DAMPERS ARE NOT SHOWN ON THE DRAWINGS IN ORDER FOR DRAWING CLARITY.
PROVIDE MANUAL ADJUSTABLE DAMPERS ON EACH LOW PRESSURE SUPPLY, RETURN, AND
EXHAUST DUCT TAKE OFF, AND AT EACH TAKE OFF TO REGISTERS, GRILLES AND DIFFUSERS.
30. PROVIDE CEILING ACCESS PANELS BELOW ALL EQUIPMENT LOCATED ABOVE CEILINGS. EXACT
SIZE AND LOCATION SHALL BE COORDINATED IN FIELD WITH ARCHITECT.
GENERAL NOTES
DN
UP
W
CO
MAV
AAV
PT
FM
S
OR
OR
OR
R w
PIPING LEGENDDUCTWORK
SINGLE LINE DOUBLE LINE SINGLE LINE DOUBLE LINE
ROUND SUPPLY
DUCT UP
SUPPLY
DUCT UP
ROUND SUPPLY
DUCT DN
SUPPLY DUCT
DOWN
STANDARD RADIUS
ELBOW
( R = W )
SUPPLY/RETURN
EXHAUST
SPLIT TAKE-OFF
W/ BRANCH DAMPERS
SUPPLY
BULLHEAD SPLIT
SUPPLY
CEILING DUCT
GOOD FOR
RING DUCT
TAKEOFF TO
MTD DIFF/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
CEILING DUCT
MTD DIFF/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
OPEN END
DUCT W/VD &
1/2"x1/2" WMS
FLEXIBLE
DUCT
RISE/DROP
RISE/DROP
ROUND RETURN OR
EXHAUST
DUCT UP
RETURN/EXHAUST
DUCT UP
RETURN/EXHAUST
DUCT DOWN
ROUND RETURN OR
EXHAUST DUCT
DN
HORIZONTAL
OFFSET
SUPPLY/RETURN
/EXHAUST
RISE OR DROP
SUPPLY/RETURN/
EXHAUST
RING
DUCT
90° TAKE-OFF W/BRANCH TAKE-OFF
VOLUME DAMPER (VD IN LOW PRESSURE
SYSTEMS ONLY)
BULLHEAD CONVERGE
RETURN/EXHAUST
W/BRANCH TAKE-OFF
VOLUME DAMPER
SIDEWALL DUCT MTD
REGISTER/GRILLE
W/BRANCH TAKE-OFF
VOLUME DAMPER
SUPPLY CEILING
LINEAR DIFFUSER (W/
1" INTERNALLY LINED
SM PLENUM) BRANCH
CONN W/VD FOR
EVERY 4' OF LINEAR BOOT
BY LD
MFR
ROOF EXHAUST FAN
SHOWN ON ROOF
ROOF EXHAUST FAN
SHOWN ON FLOOR PLAN
RETURN OR EXHAUST
AIR FLOW
SUPPLY AIR FLOW
STANDARD 4-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 3-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 2-WAY BLOW
SUPPLY DIFFUSER
BLANKED FOR 1-WAY BLOW
SUPPLY DIFFUSER
DESIGN CFM
A(200)
PRESSURE TRANSMITTER
HUMIDISTAT
THERMOSTAT
SECTION DESIGNATION
SHEET NUMBER
DETAIL DESIGNATION
SHEET NUMBER
DIFFUSER, GRILLE,
REGISTER LETTER
DESIGNATOR
M.XX
M.XX
CARBON DIOXIDE SENSOR
FSD COMBINATION SMOKE/FIRE
DAMPER W/ACCESS DOOR
VD MANUAL VOLUME DAMPER
(OBD IN DIFFUSER)
ACD AUTOMATIC CONTROL DAMPER
W/ACCESS DOOR
SD AUTOMATIC SMOKE DAMPER
W/ACCESS DOOR
FD FIRE DAMPER W/ ACCESS DOOR
RH
VFD
C
C
C
VARIABLE FREQUENCY DRIVE
UNIT HEATERCABINET HEATER
COOLING COILREHEAT COIL
OPPOSED BLADE DAMPER
W/ MODULATING ACTUATOR
BACKDRAFT DAMPER
W/ TWO POSITION ACTUATOR
OPPOSED BLADE DAMPER
ROOF FAN
C
H
HEATING COILFILTER BANK
INLINE CENTRIFUGAL FAN
CENTRIFUGAL FAN
PUMP
UPBLAST CENTRIFUGAL FAN
EXPANSION TANK
AIR SEPARATOR
CHEMICAL FEED SYSTEM
AIR TERMINAL BOX
AAV
H
TEQUIPMENT TAGXX
CONNECT TO EXISTING
DISCONNECT FROM EXITING
CALL OUT SYMBOLS
C
P
°F DEGREES FAHRENHEIT
Ø DIAMETER
AAV AUTOMATIC AIR VENT
AC AIR CONDITIONING
ACC AIR COOLED CONDENSER UNIT
ACD AUTOMATIC CONTROL DAMPER
ACV AUTOMATIC CONTROL VALVE
ADJ ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE ALUM ALUMINUM
AS AIR SEPARATOR
ATD AIR TERMINAL DEVICE
ATV ATMOSPHERIC VENT
AVG AVERAGE
BAS BUILDING AUTOMATION SYSTEM
BBD BOILER BLOW DOWN
BDD BACKDRAFT DAMPER
BF BOILER FEED WATER
BHP BRAKE HORSEPOWER
BLDG BUILDING
B BOILER
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BSMT BASEMENT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CC COOLING COIL
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE CH CHILLER
CHEM CHEMICAL FEED
CHW CHILLED WATER
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
CO CLEAN-OUT
CU CONDENSING UNIT
CUF CUBIC FEET
CUH CABINET UNIT HEATER
D DRAIN
DB DRY BULB TEMPERATURE
DDC DIRECT DIGITAL CONTROL
DIA DIAMETER
DIFF DIFFUSER
DN DOWN
DWG DRAWING
DX DIRECT EXPANSION
(E) EXISTING
EA EACH
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EFF EFFICIENCY
ELEC ELECTRICAL
ELEV ELEVATION
ERU ENERGY RECOVERY UNIT
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EUH ELECTRIC UNIT HEATER
EXH EXHAUST
EWT ENTERING WATER TEMPERATURE
EX EXHAUST
EXP EXPANSION
F FAN
FAS FIRE ALARM SYSTEM
FTR FINNED TUBE RADIATION
FCU FAN COIL UNIT
FCV FLOW CONTROL VALVE
FG FIBERGLASS
FLEX FLEXIBLE
FLR FLOOR FLRDR FLOOR DRAIN
FP FIRE PROTECTION
FPM FEET PER MINUTE
FT FEET
FT/SEC FEET PER SECOND
G GAS
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GC GENERAL CONTRACTOR
GND GROUND
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GRD GRADE (GROUND LEVEL)
GWB GYPSUM WALL BOARD
H HEIGHT
HB HOSE BIBB CONN W/CHAINED CAP
HC HEATING COIL
HCPD HANDICAPPED
HD HEAD
HP HORSEPOWER H
HR HOUR
HRC HEAT RECOVERY COIL - GLYCOL
HRU HEAT RECOVERY UNIT
HU HUMIDIFIER
HV HEATING & VENTILATING UNIT
HW HOT WATER
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HX HEAT EXCHANGER
HZ HERTZ
ID INSIDE DIAMETER
IN INCHES
INSUL INSULATION
KW KILOWATT
KVA KILOVOLT AMPERE
L LENGTH
LAT LEAVING AIR TEMPERATURE
LB POUND
LD LINEAR DIFFUSER
LF LINEAR FEET
LVG LEAVING
LWT LEAVING WATER TEMPERATURE
ABRREVIATIONS
MAV MANUAL AIR VENT
MAX MAXIMUM
MBH THOUSAND BRITISH THERMAL
UNITS PER HOUR
MCA MINIMUM CIRCUIT AMPS
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MU MAKEUP WATER
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NC NOISE CRITERIA
NO NORMALLY OPEN
NO. NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OB OCTAVE BAND
OD OUTSIDE DIAMETER
OBD OPPOSED BLADE DAMPER
OED OPEN END DUCT
OV OUTLET VELOCITY
P PUMP
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP PH PHASE
PH PERIMETER HEAT
PHC PREHEAT COIL
PHX PLATE HEAT EXCHANGER
PLBG PLUMBING
POS PROVIDED BY OTHER SECTION(S)
PRESS PRESSURE
PRIM PRIMARY
PSIA POUNDS PER SQUARE INCH
ABSOLUTE
PSID POUNDS PER SQUARE INCH
DIFFERENTIAL
PSIG POUNDS PER SQUARE INCH
GAUGE
PVC POLYVINYL CHLORIDE
R REHEAT
RA RETURN AIR
RD REFRIGERANT DISCHARGE
(HOT GAS)
REP REPRESENTATIVE
RET RETURN
RF RETURN FAN
RG RETURN GRILLE
R.H. RELATIVE HUMIDITY
RH REHEAT
RHC REHEAT COIL
RHP RADIANT HEATING PANEL
RL REFRIGERANT LIQUID
RLF RELIEF RR RETURN REGISTER
RM ROOM
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RV RETURN AIR VALVE/BOX
SA SUPPLY AIR
SATT SOUND ATTENUATOR
SCH SCHEDULE
SCR SCREEN
SD SMOKE DAMPER
SDET SMOKE DETECTOR
SF SUPPLY FAN
SFD COMBINATION AUTOMATIC SMOKE/FIRE
DAMPER WITH ACCESS DOOR
SM SHEETMETAL
SOV SOLENOID OPERATED VALVE
SP STATIC PRESSURE
SPECS SPECIFICATIONS
SQ SQUARE
SQFT SQUARE FEET
SS STAINLESS STEEL
STD STANDARD
STDBY STANDBY
STL STEEL
SUCT SUCTION
SUP SUPPLY
SV VARIABLE VOLUME SUPPLY
AIR TERMINAL BOX
TEMP TEMPERATURE
TOD TOP OF DUCT
TOP TOP OF PIPE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UC UNDERCUT DOOR
UH UNIT HEATER
V VENT
VD VOLUME DAMPER
VEL VELOCITY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VTR VENT THROUGH ROOF
VV SUPPLY VAV BOX
W WIDTH
W/ WITH
W/O WITHOUT
WB WET BULB TEMPERATURE
WG WATER GAUGE
WMS WIRE MESH SCREEN
GATE VALVE
BALL VALVE
BALL VALVE WITH HOSE BIBB, CAP & CHAIN (DRAIN
VALVES)
BUTTERFLY VALVE
BUTTERFLY VALVE WITH MEMORY STOP
(BALANCING VALVE)
GLOBE VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
STRAINER W/BALL VALVE, HOSE BIBB & CAP (GATE
VALVE FOR STEAM)
SOLENOID VALVE
AUTOMATIC CONTROL VALVE, MODULATING
ACTUATOR
AUTOMATIC CONTROL VALVE, TWO POSITION
ACTUATOR
THREE WAY AUTOMATIC CONTROL VALVE,
MODULATING ACTUATOR
THREE WAY AUTOMATIC CONTROL VALVE, TWO
POSITION ACTUATOR
AUTOMATIC FLOW CONTROL VALVE (PRESSURE
INDEPENDENT)
COMBINATION FLOWMETER/SHUT OFF/BALANCING
VALVE (CIRCUIT SETTER)
FLOW MEASURING DEVICE
SAFETY RELIEF VALVE
UNION OR FLANGE (AS INDICATED BY PIPE SIZE -
SEE SPEC.)
END CAP
PRESSURE GAUGE WITH GAUGE CLOCK
PRESSURE/TEMPERATURE WELL
AUTOMATIC AIR VENT WITH ISOLATION VALVE
MANUAL AIR VENT
RISE (SINGLE LINE - PLAN VIEW)
DROP (SINGLE LINE - PLAN VIEW)
TOP TAKEOFF
BOTTOM TAKEOFF
PIPE BREAK (SINGLE LINE)
WATER METER DIAL TYPE
CLEAN-OUT FOR CONDENSATE DRAIN
DIRECTION OF FLOW IN PIPE
PITCH PIPE UP IN DIRECTION OF FLOW
PITCH PIPE DOWN IN DIRECTION OF FLOW
NEW WORK
SUPPLY LINES
RETURN LINES
DEMO LINE
DESIGNED:
DRAWN:
TECH REVIEW:
DATE:
J. SPECK
J. SPECK
J. SPECK
02/02/2026
SUB SHEET NO. DRAWING NO.
PKG.
NO.
SHEET
OF
PLAN
REPLACE GEOTHERMAL SYSTEM
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
10'-6"6'-0"18'-2"
4" 5'-10" 5'-10" 5'-10" 6'-0"
4"
5"
'-3
/4
2'
-7
5' -5
/4
2'
-7
4" 4"
G
AT
ES
GATE
2'-8 5/8"
'-6
EXISTING BUILDINGCOOLING TOWER 4'-1 1/4" W x 10' 11 3/4" L
EXISTING
TRANSFORMER
8" THICK WALL
8" THICK WALL
8" T
H
IC
K W
AL
L
8" T
H
IC
K W
AL
L
1' X 2' X 6" CONC. STEP
POST FLOOR FLANGE TYP.
5 7/8" X 5 7/8" - 13 REQ.
COOLING TOWER PIT
SCALE 1/8" = 1'-0"
NATIONAL MONUMENT
H200K-13 SLAB DRAIN 8" WIDE BY 13' 1-1/2" LONG
SLOPE 1/4" PER FT.
SLOPE 1/4" PER FT.
SL
O
PE
/4 " P
ER
F
T.
SL
O
PE
/4 " P
ER
F
T.
1. A 6" PERFORATED TILE SHALL RUN ALONG THE INSIDE OF THE
RETAINING WALL FOOTING. BACKFILL AROUND PIPE WITH 34"
STONE. WRAP STONE IN FILTER FABRIC AS SHOWN.
2. UTILIZE 4" BOTTOM KNOCK OUT IN TRENCH DRAIN AND
EXTEND A SOLID 4" PVC PIPE FROM THE TRENCH DRAIN TO
THE 6" PERFORATED PIPE.
3. ALLOW THE 6" PERFORATED PIPE TO PENETRATE THE
RETAINING WALL FOOTING NEAR THE DOUBLE SET OF GATES
AND TERMINATE 10' AWAY FROM RETAINING WALL WITH A
NDS-FWAS24-FLO PREFABRICATED DRY WELL KIT 24"DIA x 48".
SET WELL ON 4" THICK LAYER OF 34" STONE AND WRAP WELL
STRUCTURE IN FILTER FABRIC.
4. TOP TO HAVE A 6" SURFACE DRAIN INLET. RIM ELEVATION TO
MATCH SURROUNDING GRADE.
DRAINAGE NOTES:
CONCRETE PIER FOR FENCE POST (3 REQUIRED)
1. SET 8" DIA X 24" SONOTUBE AND FILL WITH CONCRETE.
2. SET CHAIN LINK FENCE POST FLOOR FLANGES AT TOP OF
CONCRETE WITH PIGTAIL OR L SHAPED BENT ANCHORS.
ELEVATION TO MATCH TOP OF RETAINING WALL.
3. TOOL A 12" RADIUS AROUND TOP EDGE OF CONCRETE.
4. REMOVE TOP 6" OF SONOTUBE ONCE CONCRETE HAS SET.
FENCE (BOTH SIDES)
FE
N
C E
(O N
E
SI
D E
O N
LY
N O
F
EN
C E
TH
IS
S
ID
E
H200K-13 SLAB DRAIN 8" WIDE BY 13' 1-1/2" LONG
4" KNOCK OUT TYP.
SI1.0
DRAWN:
TECH REVIEW:
DATE:
J. SPECK
J. SPECK
J. SPECK
02/02/2026
SUB SHEET NO. DRAWING NO.
PKG.
NO.
SHEET
OF
DETAILS
TURF
1/
2"
AV
G
COOLING
TOWER
8"
2' 0"
3/4" STONE
3/4" STONE
UNDISTURBED SOIL
FILTER FABRIC
12"
1" WEEP HOLE
3' O.C.
FILTER FABRIC
6" PERF.
PIPE
DIMPLED
DRAIN BOARD
8"
10" 8" 14"
8"
4"
6"5' 1-1/4"
UNDISTURBED SOIL
3/4" STONE
EXISTING BUILDING 10' 6"
1. COVER OVER ALL REBAR TO BE 2" MINIMUM ALL SIDES.
2. CONCRETE TO BE 4,000 P.S.I.
3. REINFORCING STEEL TO BE GRADE 60.
4. DRAIN PIPE TO BE 6" PERFORATED PVC.
5. LAPPING OF REBAR BE 18".
6. REBAR FOR EQUIPMENT PAD TO BE 2 LAYERS #4 BAR 12" O.C. EACH WAY.
7. REBAR FOR WALL TO BE #3 BAR 18" O.C. HORIZONTAL AND 16" O.C. VERTICAL BENT
INTO FOOTING AS SHOWN.
8. REBAR IN TOP OF FOOTING TO BE #4 BAR 12" O.C. EACH WAY.
9. REBAR IN BOTTOM OF FOOTING TO BE #4 BAR 14" O.C.
PIT
SCALE 1/8" = 1'-0"
EQUIPMENT PAD
SCALE 1/4" = 1'-0"
RETAINING WALL
SCALE 1/4" = 1'-0"
REPLACE GEOTHERMAL SYSTEM
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
6"
6" TYP.
SEE NOTE
NOTE:
CLEARANCE BETWEEN COOLING TOWER AND CONCRETE
WALL IS SHOWN AT 3'-0". VERIFY MINIMUM CLEARANCES
ONCE FINAL COOLING TOWER IS SELECTED AND ADJUST
DIMENSIONS ACCORDINGLY.
4' 1-1/4" X 10' 11 3/4"
SLAB TRENCH DRAIN:
H200K-13, 8" INTERNAL WIDTH
TRENCH DRAIN 39.37" LONG
WITH 3.94" INVERT. 479Q
DUCTILE IRON GRATE
4" PIPE FROM
TRENCH DRAIN
TO 6" PERF. PIPE
FINAL DIMENSION DETERMINED
AFTER TOWER IS SELECTED
TRENCH
DRAIN TYP
TRENCH
DRAIN TYP
SI2.0
DRAWN:
TECH REVIEW:
DATE:
J. SPECK
J. SPECK
J. SPECK
02/09/2026
SUB SHEET NO. DRAWING NO.
PKG.
NO.
SHEET
OF
DETAILS
REPLACE GEOTHERMAL SYSTEM
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
CHAIN LINK 2-1/2" (2 3/8" OD) X 6" WOODEN FENCE TO POST LINE ADAPTER (GALVANIZED PRESSED STEEL) CHAIN LINK FENCE 2-1/2" (2 3/8" OD) ROUND DOME EXTERNAL FENCE POST CAP (DIE CAST ALUMINUM)
TREATED 2 X 4 FASTENED TO ADAPTER WITH 1/4" X 1 1/2" HEAVY DUTY HEX HEAD WOOD FENCE LAG SCREWS
TREATED 1 X 6 FASTENED TO 2 X WITH 2" FLATHEAD STAINLESS STEEL SCREWS
CHAIN LINK 2-1/2" (2 3/8" OD) SS40 ROUND INDUSTRIAL FENCE PIPE TUBING (.13" WALL) (GALVANIZED STEEL)
CHAIN LINK 2-1/2" (2 3/8" OD) X 6" WOODEN FENCE TO POST LINE ADAPTER (GALVANIZED PRESSED STEEL)
TREATED 2 X 6 FASTENED TO ADAPTER WITH 1/4" X 1 1/2" HEAVY DUTY HEX HEAD WOOD FENCE LAG SCREWS
CHAIN LINK 2-1/2" (2 3/8" OD) X 6" WOODEN FENCE TO POST LINE ADAPTER (GALVANIZED PRESSED STEEL)
TREATED 2 X 8 FASTENED TO ADAPTER WITH 1/4" X 1 1/2" HEAVY DUTY HEX HEAD WOOD FENCE LAG SCREWS
CHAIN LINK FENCE 2-1/2" (2 3/8" OD) POST FLOOR FLANGE (GALVANIZED PRESSED STEEL) BOLTED TO TOP OF WALL
1/2" PIGTAIL OR L SHAPED BENT ANCHOR BOLTS W/ NUTS AND WASHERS (4 PER POST)
NOTE:
1. THREE CORNER POSTS WILL REQUIRE CHAIN LINK 2 1/2" (2 3/8 OD) X 6 WOODEN FENCE TO POST CORNER
ADAPTERS (GALVANIZED PRESSED STEEL) IN PLACE OF POST LINE ADAPTERS
2. THREE POSTS WILL REQUIRE CHAIN LINK 2 1/2" (2 3/8 OD) X 6 WOODEN FENCE TO POST END
ADAPTERS (GALVANIZED PRESSED STEEL) WHERE GATES ARE REQUIRED.
3. GATES WILL REQUIRE CHAIN LINK GATE HINGES ATTACHED TO FABRICATED GALVANIZED STEEL TUBULAR
FRAME. MOUNT TREATED 1 X 6 TO FRAME WITH STINLESS STEEL, SELF TAPING FLATHEAD SCREWS.
6'
" M
AX
SECTION OF FENCE AROUND EQUIPMENT PAD
SCALE 1/4" = 1'-0"
1/2" R
8" CONCRETE
RETAINING WALL
SI3.0
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M1.0
ELS
ELS
305342
114081
332MECHANICAL
SITE PLAN
MEMORIAL HOUSE
COOLING TOWER
CONDENSER WATER LINE
DRAIN LINE
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M2.0
ELS
ELS
305342
114081
(E) WSHP
(E) WSHP
(E) WSHP
(E) WSHP
(E) BOILER
NG
N G
N G
N G
CD
C D
C D
(E) WSHP
HOT WATER
RISERS UP
(E) SUPPLY/RETURN
FROM WELL FIELD
CH
CH
CH
CH
(E) HOT WATER COIL
(E) HOT WATER COIL
(E) DUCTWORK
(E) HOT WATER COIL
(E) SUPPLY/ RETURN
CONDENSER WATER
(E) SUPPLY/ RETURN
HOT WATER
(E) HOT WATER COIL
(E) REFRIGERANT
(E) CONDENSATE
(E) SUPPLY/ RETURN
HOT WATER
(E) SUPPLY/ RETURN
CONDENSER WATER
(E) DUCTWORK
(E) DUCTWORK
(E) DUCTWORK
(E) SUPPLY/ RETURN
HOT WATER
(E) SUPPLY/ RETURN
CONDENSER WATER
BASEMENT FLOOR PLAN
SHEET NOTES:
DISCONNECT LP PIPING FROM BOILER AND PREPARE FOR RECONNECTION. DEMOLISH BOILER, VENT, PUMPS, WIRING, AND
ACCESSORIES. CONCRETE PAD SHALL BE REUSED.
DISCONNECT DUCTWORK FROM WSHP. DUCTWORK AND HOT WATER COILS SHALL REMAIN. DEMOLISH WSHPs, ASSOCIATED PIPING, WIRING AND ACCESSORIES. RECLAIM AND VACATE ALL EXISTING REFRIGERANT PER EPA
GUIDELINES.
DEMOLISH REFRIGERANT AND CONDENSATE LINE FROM COMPRESSOR TO BLOWER UNIT LOCATED IN THE ATTIC.
DISCONNECT AND TEMPORARY CAP GROUND SOURCE CONDENSING WATER LOOP AT BUILDING ENTRANCE. DEMOLISH ALL CONDENSING WATER PIPING. REMOVE ALL HANGERS AND SUPPORTS ASSOCIATED WITH THE SYSTEM COMPONENTS.
DEMOLISH VISIBLE HOT WATER PIPING RISERS THAT LEADS TO SECOND FLOOR. HOT WATER DISTRIBUTION PIPING TO
COILS SHALL REMAIN.
GENERAL NOTES:
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.
DEMOLITION WORK
SCALE: 1/4" = 1'-0"
M2.0
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M2.1
ELS
ELS
305342
114081
NG
N G
N G
N G
REFRIGERANT
AND CONDENSATE
LINE FROM ATTIC
(E) SUPPLY/RETURN
FROM WELL FIELD
2" SUPPLY/RETURN
FROM COOLING
TOWER
CH
CH
CH
CH
WSHP-1
WSHP-4
WSHP-3 B-1
WSHP-5A
WSHP-2
P-5
P-1 P-2
(E) SUPPLY/ RETURN
HOT WATER
(E) SUPPLY/ RETURN
HOT WATER
ET-1
AS-1
SUPPLY/ RETURN
CONDENSER WATER
2" SUPPLY/ RETURN
FROM COOLING TOWER
SUPPLY/ RETURN
CONDENSER WATER
P-4 P-3
WSHP-1
WSHP-2
WSHP-4
WSHP-3
B-1
16x8
16x8
CH
CH
CH
CH
WSHP-5A
4" Ø EXHAUST
VENT
(E) HOT WATER COIL
(E) HOT WATER COIL
(E) DUCTWORK
(E) HOT WATER COIL
16x8
16x8 (E) HOT WATER COIL
(E) DUCTWORK
(E) DUCTWORK
(E) DUCTWORK
BASEMENT FLOOR PLAN
SHEET NOTES:
PROVIDE NEW BOILER. RECONNECT GAS LINE. PROVIDE NEW VENT AND RUN IN LOCATION OF EXISTING VENT AND DISCHARGE THROUGH EXISTING WINDOW OPENING. PROVIDE REQUIRED PIPING AND VALVES, REFER TO PIPING DIAGRAM.
PROVIDE NEW WSHPs. CLEAN EXISTING DUCTWORK AND RECONNECT WSHP. PROVIDE NEW RETURN DUCTWORK TO NEW FLOOR OPENING. CONNECT TO FLOOR GRILLE (GRILLE FURNISHED BY THE PARK). DO NOT REMOVE MORE FLOORING THAT NECESSARY TO INSTALL GRILLE. PROVIDE REQUIRED CONDENSER WATER PIPING AND VALVES, REFER TO PIPING DIAGRAM. EXISTING HOT WATER PIPING AND COILS TO REMAIN. RUN CONDENSATE DRAINS TO EXISTING CONDENSATE
PUMP.
NEW COOLING TOWER LINES SHALL BE DRILLED BELOW FOUNDATION WALL AND ENTER THE BUILDING THROUGH THE FLOOR. REINSTALL ANY BRICK WORK THAT WAS DISTURBED DURING INSTALLATION. REFER TO PIPING DIAGRAM FOR
REQUIRED VALVES AND PIPE ROUTING.
PROVIDE NEW PUMPS AND TANKS. REFER TO PIPING DIAGRAM.
RECONNECT GROUND SOURCE WATER LOOP TO NEW PIPING LOOP. REFER TO PIPING DIAGRAM. IF EXISTING WALL OPENINGS NEED TO INCREASE TO FIT NEW PIPING, REMOVE BRICKS THAT HAD BEEN NEWLY ADD. DISCUSS WITH COR
BEFORE MAKING PENETRATIONS.
BALANCE WATER AND AIR SYSTEM.
NEW WORK - PIPING
SCALE: 1/4" = 1'-0"
M2.1
GENERAL NOTES:
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.
NEW WORK - DUCTWORK
SCALE: 1/4" = 1'-0"
M2.1
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M2.2
ELS
ELS
305342
114081
ROOM D
ROOM C
ROOM B
ROOM A
HALL
T
T T
T
REFRIGERANT
AND CONDENSATE
LINE FROM ATTIC
T
T T
T
ROOM D
ROOM C
ROOM B
ROOM A
HALL
REFRIGERANT
AND CONDENSATE
LINE FROM ATTIC
FIRST FLOOR PLAN
NEW WORK
SCALE: 1/4" = 1'-0"
M2.2
DEMOLITION WORK
SCALE: 1/4" = 1'-0"
M2.2
SHEET NOTES:
DEMO EXISTING THERMOSTATS.
INSTALL NEW THERMOSTATS IN EXISTING LOCATION.
PROVIDE NEW RETURN DUCTWORK TO NEW FLOOR OPENING. CONNECT TO FLOOR GRILLES (GRILLES FURNISHED BY THE
PARK). DO NOT REMOVE MORE FLOORING THAT NECESSARY TO INSTALL GRILLE.
GENERAL NOTES:
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M2.3
ELS
ELS
305342
114081
UPPER HALL
ROOM F
ROOM E
ROOM H
ROOM G
WSHP-5B
T
26x24
REFRIGERANT
AND CONDENSATE
LINE FROM ATTIC
14x4
(TYP 4)
8x8
18x12
10x8 10x8
10x8
16x14
T
C D
CD REF
R
EF
UPPER HALL
ROOM F
ROOM E
ROOM H
ROOM G
(E)WSHP
SECOND FLOOR PLAN
NEW WORK
SCALE: 1/4" = 1'-0"
M2.3
DEMOLITION WORK
SCALE: 1/4" = 1'-0"
M2.3
SHEET NOTES:
DISCONNECT AND DEMOLISH WSHPs, ASSOCIATED REFRIGERANT PIPING, CONDENSATE, AND DUCTWORK. CEILING
GRILLES SHALL REMAIN.
DEMO THERMOSTAT.
HATCH OPENING TO ATTIC IS 28"x26" ALL EQUIPMENT WILL NEED TO FIT THROUGH EXISTING OPENING.
PROVIDE NEW WSHP WITH A NEW DRAIN PAN. PROVIDE NEW DUCTWORK PER FLOOR PLAN. CONNECT DUCTWORK TO EXISTING CEILING GRILLES. PROVIDE REQUIRED PIPING AND VALVES, REFER TO PIPING DIAGRAM.
INSTALL NEW THERMOSTATS IN EXISTING LOCATION.
CLEAN ALL DIFFUSERS.
BALANCE WATER AND AIR SYSTEM.
GENERAL NOTES:
1. THESE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL TRANSITIONS, OFFSETS, ETC.
CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND PROVIDE ALL NECESSARY FITTINGS TO COMPLETE THE INTENT OF THE DRAWINGS. ANY DISCREPANCIES BETWEEN DRAWINGS AND FIELD CONDITIONS SHALL BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION. CONTRACTOR MAY LOCATE MECHANICAL EQUIPMENT DIFFERENTLY THAN SHOWN ON DRAWINGS DUE TO CONFLICTS, AS LONG AS FUNCTION AND/OR APPEARANCE ARE NOT AFFECTED.
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M3.0
ELS
ELS
305342
114081
332MECHANICAL
FLOW DIAGRAM
BASEMENT
6' -3
/4
2" CTWR
2" CTWS
WHSP-5 B
LEVEL 2
WHSP-1
ROOM A
WHSP-2
ROOM B
WHSP-3
ROOM C
WHSP-4
ROOM D
LEVEL 1
LEVEL 2
ATTIC
2" CTWR
2" CTWS
(E) RETURN FROM WELL FIELD
(E) SUPPLY FROM WELL FIELD
B-1
MAKE-UP PRV
ADJUST TO 0.5 TO 1 PSI
MAXIMUM PRESSURE DROP
ACROSS AIR SEPARATOR
REDUCE TO SIZE
OF AIR SEPARATOR
N.C.
F
AAV (LARGE CAPACITY)
AAV
12"
TO 6" AFF
TO 6" AFF
ET-1
VFD
VFD
WATER
COLD
BACKFLOW
COUPON RACK
PT
LOCATE IN MECH ROOM AS
INSTRUCTED BY CHEMICAL
TREATMENT CONTRACTOR
AND OWNER.
1 X 1 TEE WITH
PLUGGED END
TYPICAL FOR 6
LOW
FLOW
BYPASS
CHEMICAL
FEED
2" CWS
TF
TF
2" CWR
P-5
WHSP-5A
LEVEL 2
CH EXISTING
HEATING COIL
CH EXISTING
HEATING COIL
CH EXISTING
HEATING COIL
CH EXISTING
HEATING COIL
2" H
W R
2" H
W S
REFRIGERANT LINE
SIZE PER MANUFACTURER'S
RECOMMENDATION
P-4
P-3
P-1
P-2
AS-1
CT-1
1-1/4"
HWR
1-1/4"
HWS
VFD
VFD
VFD
T
T
T
T
T
T
M
1" WATTS LF009
BACKFLOW
PREVENTER
RELIEF TO
INDIRECT
DRAIN
WATER METER
1" TO DCW TO
ADJACENT
BATHROOM
EXISTING GROUP LOOP
CIRCULATION PUMP
STRUCTURAL STEEL
SUPPORT BY
MANUFACTURER
CONCRETE PIT
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M4.0
ELS
ELS
305342
114081
332MECHANICAL
SCHEDULE
COOLING TOWER SCHEDULE
UNIT NO. LOCATION TYPE NO. OF CELLS TON/CELL NOMINAL
TONS
HEAT
REJECTION
CAPACITY
(MBH)
AMBIENT AIR
TEMP °F
(WB)
WATER TEMP (°F) WATER
FLOW
RATE
(GPM)
WATER
PRESSURE
DROP
(FT WC)
FAN DATA PUMP DATA BASIN DATA (EACH HEATER)
OBERATING
WEIGHT
(LBS)
MANUFACTURER
MODEL NUMBER
(BASIS OF DESIGN)
NOTESAIR FLOW
(CFM)
NO. OF
FANS PER
CELL
EXTERNAL
STATIC
PRESSURE
(IN WC)
MOTOR DATA ELECTRICAL
HP
ELECTRICAL SERVICE NO. OF
BASIN
HEATERS
AMBIENT
AIR TEMP °F
(DB)
BASIN
HEATER
POWER (kW)
ELECTRICAL SERVICE
INLET OUTLET RPM MAX BHP HP V PH HZ V PH HZ V PH HZ
CT-1 GRADE WATER 1 24 24 150 78 101 86 20 0.11 15430 1 - 5 5 240 1 60 0.33 240 1 60 1 0 3 240 1 60 4610 BAC
VFL-024-12H 1-3
1. PROVIDE FAN VFD
2. PROVIDE FACTORY CONTROL PANEL (FRANKLIN CONTROLS CTP3R-BYP010-P2/3)
3. PROVIDE MANUFACTURE STEEL FRAME. REFER TO VIBRATION ISOLATION SPECIFICATION.
EXPANSION TANK SCHEDULE
UNIT NO. LOCATION SERVICE
SYSTEM TEMP (°F)
SYSTEM PRESSURE AT
TANK LOCATION
(PSIG)
TANK PRESSURE
RATING (PSI)
TANK AIR
CHARGE
(PSIG)
TANK
AACCEPTANCE
VOLUME (GAL)
MANUFACTURER
MODEL NUMBER
(BASIS OF DESIGN)
NOTES
MIN MAX MIN MAX
ET-1 MECH RM CONDENSER
WATER 40 150 10 60 30 15 6.3 BELL & GOSSETT
D-15 1
1. ASME EXPANSION TANK WITH REPLACEABLE FULL ACCEPTANCE BLADDER
SIDE STREAM FILTER SCHEDULE
UNIT NO. LOCATION SERVICE
FLOW RATE
(GPM)
ELEC. DATA MANUFACTURER
MODEL NUMBER
(BASIS OF DESIGN)
NOTES
V PH HZ
SSF-1 COOLING
TOWER
COOLING TOWER
WATER 3 120 1 60 LAKOS
ILB-0037 1-2
1. ABV AUTOMATIC PURGE SYSTEM WITH BRASS 3/4" VALVE WITH REMOTE CONTROLLER 120-240V
2. SIZED FOR 15% FLOW OF THE CONDENSER WATER DESIGN FLOW (3 GPM)
AIR SEPARATOR SCHEDULE
UNIT NO. LOCATION SERVICE
FLOW RATE
(GPM)
PRESSURE
DROP (FT WC)
SIZE
DIA Ø" x H"
(INCHES)
CONNECTION SIZE
OPERATING
WEIGHT (LBS)
MANUFACTURER
MODEL NUMBER
(BASIS OF DESIGN)
NOTESINLET
(INCH)
OUTLET
(INCH)
AS-1 MECH RM CONDENSER
WATER 20 0.5 6-7/16"x12-3/16" 1 1 8.8 BELL & GOSSETT
EAS-1 1
1. BUILT IN STRAINER REQUIRED.
PUMP SCHEDULE
UNIT NO. LOCATION SERVICE PUMP
STYLE/TYPE
PUMP DATA FLUID DATA MOTOR DATA
WORKING
PRESSURE
(PSIG)
MANUFACTURER
MODEL NUMBER
(BASIS OF DESIGN)
NOTESWATER
FLOW RATE
(GPM)
HEAD
PRESURE
(FT WC)
NPSHR (FT
WC)
SHUT-OFF HEAD
PRESSURE
(FT WC)
PUMP
SPEED
(RPM)
IMPELLER
SIZE
(INCHES)
FLUID TEMP
(°F)
FLUID
TYPE % GLYCOL
MOTOR
SPEED
(RPM)
BHP HP DRIVE TYPE
ELECTRICAL SERVICE
V PH HZ
P-1 BASEMENT CONDENSER
WATER LOOP INLINE 15 10 2.67 10.3 1396 4 95 WATER 0 1800 0.064 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT
E-90 1
P-2 BASEMENT CONDENSER
WATER LOOP INLINE 15 10 2.67 10.3 1396 4 95 WATER 0 1800 0.064 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT
E-90 1
P-3 BASEMENT BOILERS INLINE 30 8 2.83 10.2 1387 4 180 WATER 0 1800 0.094 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT E-90 1
P-4 BASEMENT HOT WATER COILS INLINE 10 7 8.85 1200 4.125 180 WATER 0 3600 2 VFD 115/208-230 1 60 175 BELL & GOSSITT E-90E 1
P-5 BASEMENT COOLING TOWER INLINE 20 10 2.78 10.7 1423 4 95 WATER 0 1800 0.080 0.25 VFD 115/208-230 1 60 175 BELL & GOSSITT E-90 1
1. PROVIDE DISCONNECT SWITCH
BOILER SCHEDULE
UNIT NO. LOCATION SERVICE
OUTPUT
CAPACITY
(MBH)
INPUT MAX
(MBH)
MAX INLET
PRESSURE LP
"W.C.
MIN INLET
PRESSURE LP
"W.C.
WATER AIR ELECTRICAL SERVICE WORKING
PRESSURE
(PSIG)
MANUFACTURER
MODEL NUMBER
(BASIS OF DESIGN)
NOTES
GPM EWT (°F) LWT (°F) MAX PD (FT) % GLYCOL AIR INLET VENT SIZE FLA V PH HZ
B-1 MECH RM WSHP 146 175 14 11 30 140 110 2.2 0 - 6 12 120 1 60 50 BURNHAM
X-206LP 1
1. PROVIDE WITH PROPANE CONVERSION KIT
WATER SOURCE HEAT PUMP SCHEDULE
UNIT NO. LOCATION SERVICE NOM. TON ORIENTATION REFRIG. CFM BLOWER
HP
COMPRESSOR
QTY
AIR EXTERNAL
STATIC PRESSURE
(IN WC)
WATER FLOW
RATE (GPM)
WATER PRESSURE
DROP
(FT WC)
COOLING HEATING ELECTRICAL SERVICE
WEIGHT
(LBS)
DIMENSIONS
(WxDxH)
MANUFACTURER
MODEL NUMBER
(BASIS OF DESIGN)
NOTESEWT (°F) LWT (°F) EAT (°F) TC (MBH) SC (MBH) EER EWT (°F) LWT (°F) EAT (°F) HC (MBH) V PH HZ FLA MCA
WSHP-1 BASEMENT ROOM A 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH
CL015 1-4
WSHP-2 BASEMENT ROOM B 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH
CL015 1-4
WSHP-3 BASEMENT ROOM C 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH
CL015 1-4
WSHP-4 BASEMENT ROOM D 1.5 VERTICAL R-454B 500 1/3 1 0.72 3.5 11.9 86 101 76/63.4 15.4 11.8 13.6 63 53 70 16.6 208-230 1 60 8.6 10.1 146 21.5"x21.5"x33" BOSCH
CL015 1-4
WSHP-5A BASEMENT LEVEL 2 3 VERTICAL -
COMPRESSOR R-454B - 1/3 1 0.5 6.75 1.7 86 101 76/63.4 39.1 23.2 17.1 63 53 70 36.6 208-230 1 60 14.6 18.2 166 24"x26"x22" BOSCH
CP036 1-4
WSHP-5B ATTIC LEVEL 2 3 HORIZONTAL -
BLOWER R-454B 1150 1/2 - 0.5 - - 86 101 76/63.4 39.1 23.2 17.1 63 53 70 36.6 208-230 1 60 3.3 4.2 121 22"×20"×47" BOSCH
BIVA -36RCB 1-4
1. PROVIDE DRAIN PAN AND CONDENSATE PUMP (AS REQUIRED, IF DRAINING BY GRAVITY IS NOT FEASIBLE - BLUE DIAMOND MODEL MAXIBLUE, 23FT HEAD, 16.5 SUCTION LIFT, 208-230V).
2. PROVIDE HOSE KIT WITH ISOLATION VALVES, A STRAINER, BLOW DOWN VALVE, AND AUTO BALANCING VALVE
3. PROVIDE MANUFACTURE THERMOSTAT
4. COORDINATE SUPPLY AIR AND RETURN AIR DUCT CONNECTION ARRANGEMENT AND LEFT-/RIGHT-HAND MODEL TO MATCH LAYOUT SHOWN ON FLOOR PLAN FOR EACH APPLICATION PRIOR TO ORDERING.
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M5.0
ELS
ELS
305342
114081
332MECHANICAL
DETAILS
DO NOT USE ANY SCREWS,
BECAUSE THEY INTERFERE
WITH DAMPER BLADE(S).
FOR HANGING DUCT:
TRAPEZE DUCT OR
STRAP HANGER AROUND
DUCT COMPLETELY.
PROVIDE EXTRA LENGTH
TO AVOID "PINCHING"
OF INSULATION AT
CORNERS.
BUTT ENDS
& SEAL
PROVIDE LOCKING
QUADRANT ARM
STANDOFF
TYPICAL DUCT INSULATION & SUPPORTS NEAR
VOLUME DAMPERS
NOTES:
1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORE
THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES.
2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION.
3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA.
1"
MAX. 60" SEE NOTE c
ANGLE IRON
THREADED
HANGER ROD
UNISTRUT OR
HANGER
STRAP
OVER 60"
GALV. HANGER
SCALE:
DUCT HANGER SUPPORT
h = DUCT HEIGHT w = DUCT WIDTH h w
NO. OF VANES
EQUIVALENT DIAMETER = (w+h)/2
WITHIN 2 EQUIV. DIA.:
WHEN 2 ELBOWS ARE
NO. OF VANES
DEPICTED HERE:
EXAMPLE AT LEFT IS
O U
TS
ID
E R
AD
IU
S
IN
IN
C
H
ES
IN
SI
D E
R
AD
IU
S
O F
EL
BO
W
IN
IN
C
H
ES
N O
. 1 O
F
N O
. 2 O
F
N O
. 3 O
F
N O
. 2 O
F
N O
. 1 O
F
N O
. 1 O
F
NUMBER OF SPLITTERS
OF 3 VANES.
NO. 2 VANE OF A TOTAL
"NO. 2 OF 3" =
OF 3 VANES.
NO. 1 VANE OF A TOTAL
"NO. 1 OF 3" =
TERMINOLOGY:
= INSIDE RADIUS
= CENTERLINE RADIUS
R r rR r/w = 0.5 IS A SQUARE THROAT ELBOW!
FOR 1 ELBOW:
r/w >= 1.50
1.5 > r/w >= 0.70
0.7 > r/w >= 0.60
0.6 > r/w >= 0.55
HOWEVER, MINIMUM INSIDE RADIUS R SHOULD BE 2".
NOTE:
r/w RATIO:
RADIUS ELBOW AND SPLITTER VANE REQUIREMENTS
R=20" R=2" R=4-1/4" R=9-1/4"
SHORT RADIUS ELBOW SPLITTER VANE
QUANTITY AND SPACING
SPRAY ADHESIVE TO SEAL
EDGES. USE SAME ADHESIVE
AS USED ON DUCT LINER
FABRICATION BY DUCT LINER
MANUFACTURER SPECIFIED.
EDGE OF NOSE PIECES SHALL BE 1.5 INCHES
WIDE MINIMUM SO THAT TAKE-OFF FITTING
WILL SEAT PROPERLY.
(TYP. FOR 4)
PROVIDE SHEETMETAL
NOSE PIECES FOR
CLAMPING ENTIRE
EDGE OF EXPOSED
DUCTLINER.
(TYP. FOR 2)
EXPOSED EDGE OF
DUCT LINER (TYP.)
SINGLE LINE: PREFERRED
FITTINGS:
ALTERNATE FITTINGS
(SPACE LIMITATION):
SEE RECTANGULAR/ROUND
DUCT DETAIL AND DUCT
TAKEOFFS DETAILS
SEE RECTANGULAR/ROUND
DUCT DETAIL AND DUCT
TAKEOFFS DETAILS
ELBOW RADIUS
1.5D REFEREED
(ALTERNATE IS
1D)
ELBOW RADIUS
1.5D REFEREED
(ALTERNATE IS
1D)
PIPE ANCHOR DETAIL STRUCTURAL STEEL
SCALE: NTS
TYPE TAKE-OFF(CONICAL OR BELLMOUTH TYPE)
90° SPLITTER TAKE-OFF
W1
(CONVERGING & DIVERGING)
CONCENTRIC & ECCENTRIC TRANSITION
DUCT DOWN
45° ELBOW
W2
15° MAX
W
90° PARALLEL FLOW
TRANSITION TO ROUNDAT DUCT MAIN
SIDEWALL OUTLET
90° ROUND DUCT TAKE-OFF
D/W MIN D
AIR
FLOW
20° MAX
90° TAKE-OFF 90° CONICAL TAKE-OFF
20° MAX
R=D
90° OR 45° ELBOW
D
R
45° TAKE-OFF
1.5 x C
C
6" MIN
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
AIR
FLOW
90° TURN
RECTANGULAR DUCT
NOTES:
1. TYPICAL FOR SUPPLY, RETURN, AND
EXHAUST DUCTWORK.
2. WHERE DUCT SIZE CHANGE OCCURS,
TRANSITION MAY NOT BE SHOWN ON
PLANS.
NOTES:
1. TYPICAL FOR SUPPLY,
RETURN, AND EXHAUST
DUCTWORK.
2. LOCATE THE CENTER
OF TAKE-OFFS FROM
DUCT MAINS AT THE
MIDPOINT OF THE SIDE
OF DUCT MAIN
("HEIGHT"/2)
3. SIZE A & B DIMENSIONS
ARE PROPORTIONAL TO
AIR QUANTITIES IN
EACH LEG SPLIT.
4. WHERE DUCT SIZE
CHANGE OCCURS,
TRANSITION MAY NOT
BE SHOWN ON PLANS.
5. IF W2 DOES NOT EQUAL
W1, MODIFY SHAPE OF
VANE EDGES TO
PROJECT TANGENT
PARALLEL TO DUCT
SIDES.
ROUND DUCT
BRANCH TAKE-OFF
L=1/4 W, 4" MIN.
RECTANGULAR DUCT
45° TAKE-OFF (TYP.)
AIR FOIL TURNING
VANES (TYP.)
PROVIDE VOLUME
DAMPERS DOWN-
STREAM OF EACH
SPLIT (TYP.)
SCALE:
ROUND DUCT FITTING DETAIL
SCALE:
RECTANGULAR DUCT FITTING DETAIL
TRANSITION (DIVERGING & CONVERGING)
SCALE:
DUCT SEALING DETAIL
RIGID TO FLEX AIR SEALING
AIR HANDLER AIR SEALING
RIGID DUCT AIR SEALING
FLEX TAKE-OFF FROM RIGID AIR SEALING
FLOOR BOOT AIR SEALING
SEAL JOINT BETWEEN BOOT AND CEILING
DRYWALL WITH UL-181 TAPE, MASTIC, OR
FIBERGLASS MESH AND MASTIC, OR CAULK -
COORDINATE WITH SUSTAINABLE
CONSULTANT FOR EXACT DETAILS AND
REQUIREMENTS
CEILING BOOT AIR SEALING
JOINT BETWEEN BOOT &
SUBFLOOR SEALED W/ MASTIC
OR FIBERGLASS MESH &
MASTIC OR CAULK
MASTIC (TYP.)
MASTIC (TYP.)
MASTIC
(TYP.)
MASTIC (TYP.)
MASTIC (TYP.)
MASTIC AND
SEAL ALL DUCT
JOINTS (TYP.)
SEALING AND SECURING EXPOSED
DUCTLINER7 5
TAPERED CONNECTION 45° ANGLE(IF MAIN DUCT
IS RECTANGULAR) OR CONICAL CONNECTION (IF
MAIN DUCT IS ROUND) L=1/4 W; 4"MIN
MAIN DUCT
VD
W
L
BRANCH DUCT
SUPPLY AIR
RETURN/EXHAUST AIR
LOW PRESSURE BRANCH TAKE-OFFS8
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M5.1
ELS
ELS
305342
114081
332MECHANICAL
DETAILS
SCALE:
TYPICAL HORIZONTAL DUCTED WSHP DETAIL
VALVES, ETC.
CONTROL VALVE, STRAINERS,
COMPONENTS INCLUDING
NOTE: INSULATE ALL PIPING
LINING
ACOUSTICAL
SEE SPECS
FLEX CONN
VIBRATION ISOLATION
REFER TO WATER COIL
DETAIL FOR PIPING AND
DRAIN REQUIREMENTS
DUCTED
RETURN AIR
FLEX CONNECTION
(TYP)
CONDENSER WATER
PIPES
EXISTING SUPPLY AIR
DUCTWORK
FILTER RACK WITH MERV-8 FILTER
WITH TIGHT-FITTING GASKET ON
DOOR TO FILTER ACCESS.
RETURN AIR DUCTWORK TO
FLOOR DIFFUSER
3 4" CONDENSATE DRAIN
TO CONDENSATE PUMP
PROVIDE 58"H x 22"W WALL
ACCESS PANEL FOR UNIT
ACCESS IF REQUIRED
INSTALL UNIT ON STEEL
FRAME/UNISTRUT PLATFORM
WITH DRAIN PAN BELOW
SCALE:
TYPICAL VERTICAL DUCTED WSHP DETAIL
X W x X H DUCTWORK
4"
SLAB
DUCTWORK INSULATION
PER SPECIFICATIONS
1-1/2" FLANGE
(TYP. 2)
FLOOR MOUNTED
GRILLE (EXISTING)
SHEET METAL PLENUM.
REFER TO FLOOR PLANS
FOR SIZE
FLOOR DIFFUSER PLENUM DETAIL
SCALE: NTS
3/4" DRAIN LINE VALVED W / CAP AND
CHAIN. LOCATE AT CENTER OF EACH
PLENUM BOX. FOR PLENUMS
INSTALLED ABOVE INACCESSIBLE
LOCATIONS (ELEC ROOMS, HARD
CEILINGS, ETC.) DRAIN LINE SHALL BE
RUN TO NEAREST MECHANICAL
SPACE.
1/2 W
1/2 W
W WW
CEILING
W
W
LINING
ALTERNATE METHOD FOR LOW CEILING CLEARANCE ONLY:
CEILING
(2xW) OR (3 FT) MIN
RETURN GRILLE
1" ACOUSTIC
CEILING PLENUM
PRIMARY METHOD
SUPPORT STRAP
RETURN GRILLE
SHEETMETAL
RETURN AIR
BOOT (NO
LINE OF
SIGHT) 1" ACOUSTICAL LINING
AREA OF OPENING=1/2
AREA OF GRILLE ON
BOTH ENDS, W=WIDTH
OF GRILLE
DIRECT BOOT
TERMINATION POINT
AWAY FROM FAN
DRIVEN EQUIPMENT
AND/OR TRANSFER
AIR OPENINGS IN
CEILING PLENUM
AREA OF
OPENING=AREA OF
GRILLE ON BOTH
SIDES W=WIDTH OF
GRILLE
RETURN AIR GRILLE WITH SOUND
ATTENUATION BOOT
NOTES:
1. CONTRACTOR SHALL INSTALL RETURN AIR BOOTS FOR ALL PLENUN RETURN AIR GRILLES UNLESS
NOTED OTHER WISE.
2. IF SPACE DOES NOT PERMIT FOR BOOT AS DETAILED ABOVE, THE CONTRACTOR SHALL SUBMIT
ALTERNATE DESIGN SUGGESTION(S) FOR APPROVAL, MAINTAINING NO LINE OF SIGHT BETWEEN
THE CEILING GRILLE OPENING AND THE OPEN END OF THE RETURN BOOT.
3. BOOT SHALL BE POSTIIONED SUCH THAT THE OPEN END IS PERPENDICULAR WITH ANY FULL
HEIGHT WALL TRANSFER OPENINGS OR TRANSFER DUCT OPENINGS.
EXISTING HOT WATER
COILS
DRAIN PAN
INSTALL WSHP ON
EXISTING WOODEN
STRUCTURE.
D = DUCT DIAMETER
= INSIDE BEND RADIUS
= CENTERLINE BEND RADIUS
R r Rr
D
AIR DEVICE SIZE
AS NOTED ON
PLANS
AIR DEVICE
NECK
SCREW AND
CLAMP
(TYPICAL)
SUPPORT ELBOW WITH TIE
R
R=DEPTH OF DUCT
FLEX CONN
ROUND DUCT
MAX OFFSET =
D/8"
MAX. OFFSET = D/8"
SUPPLY DIFFUSER
REGISTER (TYP.)
FLEX CONN. REFER
TO SPECS FOR
INSULATED TYPE
WHEN HEIGHT DOES NOT ALLOW FLEX CONN,
HARD-DUCT BUT BE SURE BRANCH IS 4" WIDER
THAN COLLAR TO ALLOW ALIGNMENT OF TERMINAL
WITHIN GRID WITHOUT FISHMOUTHING.
RECTANGULAR DUCT
RECTANGULAR DUCT
HARD CONNECTION WHERE
ALIGNMENT & SPACE
DICTATE ONLY
FLEX CONN
RECTANGULAR DUCT
ROUND DUCT
3D PREFERRED
1D MINIMUM
PROVIDE EQUALIZING GRID IF LESS THAN 3D
FLEXIBLE DUCT
DRAW BANDS SNUG
WITHOUT CRUSHING
FLEXIBLE DUCT
PROVIDE DURABLE
ELBOW SUPPORT
DIFFUSER/REGISTER DUCTWORK CONNECTIONS
NOTES:
1. DETAIL ALLOWS DUCTWORK TO BE INSTALLED BEFORE CEILING GRID THEN ALLOWS DIFFUSERS AND REGISTERS TO
BE POSITIONED INTO GRID.
2. PROVIDE INSULATED TRANSITION ROUND TO SQUARE INLET DIFFUSERS.
3. SECURE FLEXIBLE DUCT TO METAL DUCT WITH (2) STAINLESS STEEL CLAMPS OR NYLON TY-WRAPS TO INDIVIDUALLY
SECURE FLEXIBLE DUCT INNER SLEEVE AND OUTER SLEEVE. WHEN INSTALLED ON INSULATED SYSTEM SEAL INSULATION JOINT WITH VAPOR BARRIER MASTIC. PROVIDE NYLON TY-WRAP TOOL OR REUSABLE SS DRAW BANDS.
4. PROVIDE DUCT MOUNTED VOLUME DAMPER. AVOID NECK DAMPERS.
5. FLEXIBLE DUCTS SHALL BEND IN ONE DIRECTION ONLY WITH A MAXIMUM CHANGE IN DIFFERENCE OF 90 DEGREES.
6. UNLESS SHOWN OTHERWISE FLEXIBLE DUCT SIZE AND COLLAR OF TAP OFF SHALL BE SAME SIZE AS DIFFUSER NECK.
7. IF RUN-OUT LENGTH REQUIRES SEGMENT OF HARD DUCT, SIZE SHALL BE SAME AS DIFFUSER NECK. RUN-OUT TO
DIFFUSER SHALL BE AS STRAIGHT AS POSSIBLE.
8. INSTALL BENDS IN FLEXIBLE DUCTS WITH A MINIMUM CENTERLINE RADIUS EQUAL TO 1.5 DUCT DIAMETERS (r >= 1.5 x
D).
9. DO NOT EXCEED 6'-0" MAXIMUM LENGTH OF FLEX DUCT RECOMMENDED IN THE 2017 ASHRAE FUNDAMENTALS
HANDBOOK. INSTALL FLEX DUCT WITH NO MORE THAN 1/2" SAG PER FOOT.
DUCT WIDTH = 4" GREATER THAN NECK
/ COLLAR DIMENSION TO ALLOW FOR
CONNECTION W/O FISHMOUTHING
FILTER (MODIFY FRAME FOR
SIDE OR BOTTOM PULL IF
NECESSARY TO ALLOW
COORDINATION OF OTHER
CEILING SERVICES WITH
FILTER REMOVAL)
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M5.2
ELS
ELS
305342
114081
332MECHANICAL
DETAILS
NOTE: USE TFE TAPE ON ALL THREADED
JOINTS.
HIGHEST POINT IN SYSTEM
4 PIPE DIAMETERS (WITH 18"MAX)
REDUCER
1/4" BRASS NIPPLE
1/4" GAGE COCK
1/4" TYPE "L" COPPER TUBE
NOTE: USE TFE TAPE ON ALL THREADED
JOINTS.
HIGHEST POINT IN SYSTEM
4 PIPE DIAMETERS (WITH 18"MAX)
REDUCER
1/4" BRASS NIPPLE
1/4" GAGE COCK
FLOAT-TYPE AIR VENT
1/4" TUBE TO SCHRAEDER ADAPTER
1/4" TYPE "L" COPPER TUBE
SCALE:
TYPICAL PIPE INSULATION &
VALVE HANDLE EXTENSION
SCALE:
AUTOMATIC AIR VENT ASSEMBLY
MANUAL AIR VENT ASSEMBLY
BUTT & SEAL
JOINTS
CAP INSULATION. LEAVE
NO EXPOSED INSULATION
ANYWHERE
PROVIDE VALVE
EXTENSION KIT
TO ALLOW PROPER
INSULATION COVERAGE
TYPICAL FOR CHECK VALVES
AND BALANCING VALVES STRAINERS WITH BLOW-OFF.
TYPICAL FOR Y-BRANCH AND
TYPICAL FOR ALL VALVES
CASE
REMOVABLE
ENCLOSED IN
FIBERGLASS
BOARD.
CASE
REMOVABLE
CASE
REMOVABLE
NOTES:
1. INSULATION TO BE USED ON STEAM,
CONDENSATE RETURN, CHILLED WATER AND
CW MAKEUP PIPING. REFER TO INSULATION
SPEC FOR ADDITIONAL INSULATION FINISH ON
EXPOSED FITTINGS.
2. SEAL WATERTIGHT, ALL EXPOSED FIBERGLASS AND
WHERE TWO OR MORE PIECES OF INSULATION MEET.
INSULATION SHALL BE PER SPECIFICATION DENSITY
(EXCEPT AT HANGERS) AND THE SAME THICKNESS AS
THE ADJOINING PIPE INSULATION.
SCALE:
SCALE:
PIPE HANGER SUPPORT
VALVE & STRAINER INSULATION DETAIL
ADJUSTABLE HANGER
WITH ROLLER
LOCKING NUT
SUPPORT NUT INSULATION
PIPE
PIPE COVERING
PROTECTION
16 GA SADDLE
GALVANIZED
INSULATION
SHIELD 12"LONG.
NOTES:
1. SEE SPECIFICATION FOR HANGER SIZES.
2. PIPE 8" AND LARGER SHALL HAVE ROLLER SUPPORTED WITH DUAL RODS.
3. FOR CHW SERVICE OVER 3" REPLACE SADDLE WITH 12" LONG 14 GA SHIELD WITH RIGID
INSULATION BETWEEN PIPE AND SHIELD.
MIN.9 lb/cft
DENSITY RIGID
INSULATION AT
SHIELD
CLEVIS HANGER
(FOR 1/2" UP TO
HEAVY DUTY
& INCL. 3" PIPE)
(FOR 4" TO 6" PIPE)
INLINE PUMP
SCALE:
SCALE:
INLINE PUMP PIPING (EACH PUMP)
DIFF.
PRESSURE
SWITCH
DIFFERENTIAL PRESSURE SWITCH
CLOSED WATER SYSTEM PIPING SIZING CHART
PIPING SIZE
(INCHES)
FLOW
(GPM)
3/40 - 3.0
13.0 - 6.5
1-1/46.5 - 12
1-1/212 - 20
220 - 40
2-1/240 - 65
NOTE:
· MINIMUM PIPE SIZES UNLESS LARGER SIZES ARE INDICATED ON
DRAWINGS.
365 - 115
4115 - 240
NOTES:
1. SLOPE 1" PER FT
DOWN TO INSTRUMENT
2. TUBING ROUTING
SHALL AVOID HIGH
TEMPERATURE SWIRLS.
TUBING AND SUPPORTS
SHALL INCLUDE
PROVISIONS FOR
THERMAL EXPANSION.
3. FOR STAND DETAIL
SEE DWG. NO. FOR
MOUNTING DETAIL SEE
DWG. NO.
4. TUBING SHALL BE
SUPPORTED EVERY 5'-0"
WITH MILL GALVANIZED
STRUT & STAINLESS
STEEL TUBING CLAMPS.
5. IF UNABLE TO
SUPPORT TUBING
EVERY 5'-0",
INSTRUMENT TUBE
TRAY IS TO BE USED
WITH THE APPROPRIATE
TUBING CLAMPS.
1/2"MNPTx1/2"T SS CONN. COMPRESSION TYPE 1/2"ODx0.035 316SS SMLS TUBE
1/2"Tx1/2"Tx1/2"T TEE SS COMPRESSION TYPE
1/2" 3 VALVE MANIFOLD SS
1/2" BALL VALVE SS, 2000#
1/2"MNPT PLUG SS
1/2" TUBE UNION SS COMPRESSION TYPE7
ITEM MATERIAL
BILL OF MATERIALS
QTY PROVIDED BY
INSTALLER
INSTALLER
INSTALLER
INSTALLER
INSTALLER
INSTALLER
INSTALLERA/R
A/R
SCALE:
CLOSED WATER SYSTEM PIPING SIZING CHART
SCALE:
NC
3/4"
SHUNT FROM CHILLED OR
HOT WATER SUPPLY
RETURN
3/4"
5 GALLON FILTER
FEEDER TANK OR
OTHER SIZE AS
SPECIFIED ASME
RATED
TO CHILLED OR HOT
WATER RETURN
SHUT OFF/
BALANCING VALVE
WITH MEMORY STOP
SUPPLY
SCALE:
CHEMICAL FEED (FILTER FEEDER)
PT
1 X 1 TEE WITH PLUGGED END
TYPICAL FOR 6
NOTES:
1. TYPICAL FOR, CHILLED WATER AND HOT WATER.
LOCATE IN MECH ROOM AS INSTRUCTED BY CHEMICAL
TREATMENT CONTRACTOR AND OWNER.
BALL VALVE
RETURN MAIN
SUPPLY MAIN
SCALE:
COUPON RACK
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
M5.3
ELS
ELS
305342
114081
332MECHANICAL
DETAILS
TRENCH
SCALE:
FINISHED GRADE
NATIVE BACK FILL
INSTALL 6" BEDDING
BELOW PIPE AND 12"
ABOVE PIPE.
MINIMUM 18" WIDE.
MAINTAIN 6" MINIMUM
CLEARANCE TO EXISTING
PIPES
UNDISTURBED
EARTH
6"
12"
SHORE
TRENCH
PER OSHA
INSTALL PIPE
WITH A MINIMUM
OF 24" BURRY
3' -0
" M
AX
1'-6" MAX
FAN MOTOR
2" MPT DRAIN
10'-11 3/4"
5' -1
5/
8"
5'-11 5/8"
2" MPT OVERFLOW
1" MPT MAKE-UP
ACCESS
SPRAY PUMP
4" MPT DRAIN
4" BFW FLUID IN
4'-1 1/4"
DOOR
1/2" FPT VENT 1/2" FPT VENT
4" BFW FLUID OUT
WITH CAP
6' -3
/4
COOLING TOWER DETAIL
SCALE: NTS
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
ELS
ELS
305342
114081
332ELECTRICAL
GENERAL NOTES
GENERAL NOTES
1. DRAWINGS ARE CONCEPTUAL AND ARE INTENDED TO SHOW GENERAL SYSTEM
CONFIGURATION AND PERFORMANCE. NOT ALL NECESSARY DEVICES AND COMPONENTS
ARE SHOWN. PROVIDE ALL DEVICES AND COMPONENTS FOR A FULLY FUNCTIONAL SYSTEM.
2. CONTRACT DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND MUST BE USED IN
CONJUNCTION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. CONTRACTOR SHALL
COORDINATE ALL DRAWINGS AND SPECIFICATIONS PRIOR TO COMMENCING WORK.
QUESTIONS REGARDING DESIGN INTENT OR SYSTEM OPERATION SHALL BE PROMPTLY
BROUGHT TO ATTENTION OF THE COR.
3. INSTALL DEVICES AND SYSTEM WIRING TO AVOID DISTURBANCE TO HISTORIC FABRIC AND
TO AVOID VISUAL INTRUSION INTO PUBLIC VISITATION AREAS. HISTORIC PRESERVATION
SHALL BE TAKEN INTO ACCOUNT THROUGHOUT THE PROJECT.
4. USE EXISTING ROUTING FOR NEW FEEDERS AND BRANCH CIRCUITS WHENEVER POSSIBLE. IF
A PATH IS FOUND TO BE UNTENABLE, CONFIRM NEW ROUTING WITH THE COR. WIRING SHALL
BE INSTALLED WITHIN CONDUIT WHERE EXISTING PATHS INCLUDE CONDUIT.
5. USE EXISTING HOLES AND OPENINGS TO INSTALL CONDUIT AND CABLE. WHERE NO USABLE
PATH EXISTS, CUT NEW HOLES. COORDINATE SIZE AND LOCATIONS OF DRILLED HOLES AND
CUT OPENINGS WITH THE COR.
6. IT IS RECOMMENDED THAT THE CONTRACTOR VISIT AND BECOME FAMILIAR WITH THE SITE
PRIOR TO SUBMITTING BID.
7. THE TERM "REMOVE" MEANS DISCONNECT AND REMOVE THE DEVICE INCLUDING OUTLETS,
BRANCH CIRCUIT WIRING AND RACEWAY.
8. THE TERM “PROVIDE” MEANS FURNISH AND INSTALL, COMPLETE AND READY FOR USE.
9. THE TERM “CONTRACT DOCUMENTS” MEANS THE PROJECT MANUAL, DRAWINGS, ADDENDA,
SKETCHES AND OTHER DOCUMENTATION THAT DEFINE THE WORK.
10. ANY CONFLICTS BETWEEN SPECIFICATIONS AND DRAWINGS SHALL BE PROMPTLY BROUGHT
TO COR’S ATTENTION. THE CONTRACTOR SHALL NOT PROCEED WITH ANY WORK EXCEPT AT
THEIR OWN RISK, UNTIL CLARIFICATIONS OF CONFLICTS ARE ISSUED TO THE CONTRACTORS
BY THE COR.
11. WHERE DEVICES, WIRING, MOLDING, ETC. ARE TO BE REMOVED FROM EXISTING HISTORIC
FABRIC AND REMOVAL MAY NOT BE POSSIBLE WITHOUT DAMAGING EXISTING HISTORIC
FABRIC, NOTIFY COR PRIOR TO THE REMOVAL OF THE ITEM.
12. PROVIDE ENGRAVED, PHENOLIC NAMEPLATE PANELS, SAFETY SWITCHES, CABINETS, ETC,
TO IDENTIFY THE UNIT AND THE SOURCE PANEL AND CIRCUIT NUMBER.
13. ALL ELECTRICAL MATERIALS SHALL BE TEMPERATURE RATED FOR 90°C.
DESIGN ASSIST NOTES
1. ELECTRICAL WORK RELATED TO MECHANICAL SYSTEMS SHALL BE PROVIDED USING A
DESIGN-ASSIST APPROACH. ELECTRICAL CONTRACTOR SHALL PREPARE FINAL ELECTRICAL
DESIGN DOCUMENTS BASED ON MECHANICAL EQUIPMENT REQUIREMENTS, FIELD
CONDITIONS, AND APPLICABLE CODES. FINAL DESIGN SHALL BE SUBMITTED FOR ENGINEER
AND OWNER REVIEW PRIOR TO INSTALLATION. DRAWINGS INDICATE GENERAL INTENT ONLY
AND DO NOT REPRESENT A COMPLETE ELECTRICAL DESIGN.
2. CONTRACTOR SHALL VERIFY EXISTING ELECTRICAL CAPACITY AND INFRASTRUCTURE AND
NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH FINAL DESIGN.
3. ELECTRICAL CONTRACTOR SHALL COORDINATE POWER AND CONTROL WIRING
REQUIREMENTS WITH THE MECHANICAL CONTROLS CONTRACTOR AND EQUIPMENT
MANUFACTURERS.
4. CONTRACTOR SHALL VERIFY ALL MECHANICAL EQUIPMENT ELECTRICAL CHARACTERISTICS,
INCLUDING VOLTAGE, PHASE, MCA, MOCP, AND CONTROL REQUIREMENTS PRIOR TO FINAL
DESIGN.
E0.1
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
ELS
ELS
305342
114081
GATES
GATE RESTROOM BUILDING
COOLING TOWER
EXISTING
TRANSFORMER
EXISTING MAIN DISTRIBUTION
PANEL MDP: 120/240V, 1Ø
200A MCB
ELECTRICAL
SITE PLAN
MEMORIAL HOUSE
E1.0
EXISTING 1-PHASE
TRANSFORMER
NEW COOLING
TOWER
SITE PLAN
SCALE: 1/16" = 1'-0"
E1.0
MDP
SCALE: 1/4" = 1'-0"
E1.0
SHEET NOTES
1. NEW COOLING TOWER (CT-1): 208V,1Ø, FURNISHED AND SET-IN-PLACE BY ANOTHER
CONTRACTOR. THIS CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING TO NEMA
3R SAFETY SWITCHES AND POWER WIRING IN LFMC TO CT.
2. NEW COOLING TOWER PUMP. FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR.
THIS CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.
3. NEW HEAT BASIN, FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS
CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.
4. NEW CONTROL PANEL, FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS
CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.
5. NEW SIDE STREAM FILTER: 120V, 1Ø; FURNISHED AND SET-IN-PLACE BY ANOTHER
CONTRACTOR. THIS CONTRACTOR SHALL PROVIDE BRANCH CIRCUITS WIRING.
6. EXISTING PANEL MDP: PROVIDE NEW CIRCUIT BREAKERS FOR ALL REPLACEMENT & NEW
EQUIPMENT. PROVIDE NEW COVER DOOR WITH NAMEPLATE ON THE COVER TO IDENTIFY
THE PANEL & ELECTRICAL CHARACTERISTICS.
7. PROVIDE NEW WALL MOUNTED VARIABLE FREQUENCY DRIVES HAVING THE
CHARACTERISTICS RECOMMENDED BY THE COOLING TOWER MANUFACTURER.
COOLING TOWER PLAN
SCALE: 1/4" = 1'-0"
E1.0
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
ELS
ELS
305342
114081
(E) WSHP
(E) WSHP
(E) BOILER
(E) WSHP
EXISTING HOUSE PANEL DP-1:
120/240V, 1Ø
200A MCB
(E) HOT WATER
PUMPS (TYP 2)
(E) WSHP
UPPER HALL
ROOM F
ROOM E
ROOM H
ROOM G
(E)WSHP
DEMOLITION FLOOR PLAN
SHEET NOTES:
1. (5) WATER SOURCES HEAT PUMPS, (1) BLOWER FAN, A BOILER, AND (2) HOT WATER TO BE REMOVED BY ANOTHER CONTRACTOR. THIS CONTRACT SHALL DISCONNECT POWER WIRING AND REMOVE WIRING, CONDUIT AND DEVICES, BACK
TO PANEL HOUSE PANEL.
2. VERIFY THAT FEEDERS ARE DE-ENERGIZED AND DEVICES ARE OBSOLETE AND REMOVE WIRING, RACEWAY AND DEVICES.
NOTIFY THE COR IF A FEEDER AND ASSOCIATED DEVICES ARE FOUND TO BE FOR EQUIPMENT THAT IS IN-SERVICE: SEE
PHOTO P1.
BASEMENT
SCALE: 1/4" = 1'-0"
E2.0
E2.0
LEVEL 2
SCALE: 1/4" = 1'-0"
E2.0
DISTRIBUTION PANEL
SCALE: NTS
E2.0
DISTRIBUTION PANEL
SCALE: NTS
E2.0
MEMORIAL HOUSE
GEORGE WASHINGTON BIRTHPLACE
NATIONAL MONUMENT
HACE
ELS
ELS
305342
114081
EXISTING HOUSE PANEL DP-1:
120/240V, 1Ø
200A MCB
WSHP-1
WSHP-4
WSHP-3 B-1
WSHP-5A
WSHP-2
P-5
P-1 P-2
P-4 P-3
UPPER HALL
ROOM F
ROOM E
ROOM H
ROOM G
WSHP-5B
NEW WORK FLOOR PLAN
E2.1BASEMENT
SCALE: 1/4" = 1'-0"
E2.1
LEVEL 2
SCALE: 1/4" = 1'-0"
E2.1
SHEET NOTES
1. (4) NEW WATER SOURCE HEAT PUMPS (WSHP-1-4): 208V,1Ø, 10.1 MCA FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS CONTRACT SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM
PANEL, NEW SAFETY SWITCH AND POWER CONNECTIONS.
2. NEW WATER SOURCE HEAT PUMPS (WSHP-5A): 208V,1Ø, 18.2 MCA FURNISHED AND SET-IN-PLACE BY
ANOTHER CONTRACTOR. THIS CONTRACT SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM
PANEL, NEW SAFETY SWITCH AND POWER CONNECTIONS.
3. NEW BLOWER UNIT (WSHP-5B): 208V,1Ø, 4.2 MCA FURNISHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS CONTRACT SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM PANEL, NEW
SAFETY SWITCH AND POWER CONNECTIONS.
4. NEW BOILER: 120V, 1Ø, FURNSIHED AND SET-IN-PLACE BY ANOTHER CONTRACTOR. THIS CONTRACT
SHALL PROVIDE NEW BRANCH CIRCUIT WIRING FROM PANEL, NEW SAFETY SWITCH AND POWER
CONNECTIONS.
5. FIVE NEW PUMPS…