B08_Attachment_2_-_Drawings_WRST_248940_Glennallen_3Mar2025.pdf
PDF 16 MB Posted
- Attached to
- WRST 248940 - Deficient Water Treatment System
- Solicitation number
- 140P2025R0007
About this file
This file is a comprehensive set of architectural and engineering drawings for the replacement of a deficient water treatment system at the Glennallen Facility within Wrangell-St. Elias National Park and Preserve in Alaska. The project involves constructing a new 1,271 square-foot water treatment facility with multiple functional areas including a vehicle bay, process room, and chemical storage room, designed to meet 2021 International Building Code standards. The facility will include key components such as water storage tanks, distribution pumps, chemical dosing systems, greensand filters, oxidation and flocculation tanks, and associated utility infrastructure.
The technical drawings provide detailed specifications for structural, mechanical, electrical, and process systems, including foundation plans, utility layouts, SCADA control panel designs, and piping schematics. The facility is designed with specific considerations for Alaska's environmental conditions, featuring a V-B construction type, frost protection measures, and specialized equipment for water treatment processes. The project includes provisions for temporary water system operations during construction, with specific requirements for potable water system modifications, chemical dosing, and compliance with drinking water system regulations, including NSF standards and Alaska Department of Environmental Conservation guidelines.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HQ.
3 3
CAN.U.S.
CHISTOCHINA
GULKANA
GAKONA
GLENNALLEN
COPPER
CENTER
NABESNA
JUNCTION
TONSINA
CHITINA
GULKANA
AIRPORT
WILLOW
LAKE
STRELNA
CHOKOSNA
KENNECOTT
McCARTHY
MAY
CREEK
DAN
CREEK
CHITINA RIVER
BR
EM
NE
R RIVER
MILES LAKE
TONGASS
NATIONAL
FORESTMALASPINA
GLACIER
BAGLEY ICE FIELD
YAHTSE
GLACIER
BERING
GLACIER
JEFFERIES
GL
AC
IER
MILES
GLACIER
MOUNT
ST.ELIAS
MARTIN
RIVER
GLACIER
CAPE
YAKATAGA ICY
BAY
YAKUTAT
BAY
LOGAN GLACIER
MT.WRANGELL
MT.
SANFORD
MT.
DRUM
C H
IS
A N A R
IV
E R
PTARMIGAN
LAKE
ROCKLAKE
RUSSELL
GLACIER
BARNARD
GLACIER
JAKES
BAR
NABESNA
GLACIER
C A N A D A
U N
IT
E D
S
TA
TE
S
Y U K O N
TE
R R
ITO
R Y
A
LA
S K A
YAKUTAT
SEWARD
GLACIER
SINONA
LODGE
TO
TOK
SLANA
TO DELTA
JUNCTION
TO
ANCHORAGE
TO
VALDEZ
TETLIN
INDIAN
RESERVATION
KLUANE
NATIONAL
PARK
TETL
IN
NATI
ONA
L
WILD
LIFE
PRE
SERV
E
GUYOT
GLACIER
CHUGACH
NATIONAL
FOREST
C O P P E R
RI
VE
R
BREMNER
GLACIER
CREEK
REEVE FIELD
TANADA
LAKE
COPPER
LAKE
NABESNA ROAD
DUFFYS
TAVERN
FAIRBANKS
CHUGACH MOUNTAINS
WRANGELL
MO
UN
TAI
NS
NUTZOTIN MOUNTAINS
PROJECT
LOCATIONS
WRANGELL-
ST.
ELIAS
NATIONAL
PARK
PRESERVE
GULF
OF
ALASKA
BERING
SEA
FAIRBANKS
ANCHORAGE
PRINCE
RUPERT
WHITEHORSE
JUNEAU
KODIAK
YU
K O N
RI
VE
R
C A N A D A
U N
ITE
D
S T A
TE
S
Y U K O N
A L A S K A
VALDEZ
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
UNITED STATES
TITLE OF DRAWING
OF
DEPARTMENT OF THE INTERIOR
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
LOCATION WITHIN PARK
NAME OF PARK
WRANGELL ST. ELIAS NATIONAL PARK & PRESERVE
REGION BOROUGH STATE
ALASKA - ALASKA
WRANGELL-ST. ELIAS NATIONAL PARK AND RESERVE
PRESERVE AND WILDERNESS
PARK AND WILDERNESS
PRESERVE
PARK/PRESERVE/WILDERNESS
/ LANDING STRIP
UNPAVED ROAD
PAVED ROAD
PARK HEADQUARTERS
RANGER STATION
PARK
AIRPORT
RIVER
PARK
BOUNDARY
CONTIGUOUS BOUNDARY
LEGEND
HQ.
SCALE OF KILOMETERS
SCALE OF MILES
15 0 15
15 0
20 25
15 30
ALASKA
REGION 0
SCALE OF MILES
250 250
PMIS
REPLACE DEFICIENT WATER TREATMENT SYSTEM WRST
8/
/2
4:
:5
P
M B
IM
.0
W
R S
T R ep la ce W at er
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r vt
REPLACE DEFICIENT VC/HQ WATER TREATMENT
SYSTEM WRST
248940
CONSTRUCTION DOCUMENTS
248940
PROJECT
LOCATIONS
GLENNALLEN
GLENNALLEN, ALASKA
GL
NO DESCRIPTION DATE 1 63
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF8/
/2
4:
:0
P
M B
IM
.0
W
R S
T R ep la ce W at er
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r vt
Author
Checker
Designer
G1.1
- GL
SHEET INDEX
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
SHEET INDEX
GENERAL
ARCHITECTURAL
CIVIL
STRUCTURAL
PROCESS
MECHANICAL
ELECTRICAL
INSTRUMENTATION & CONTROLS LEGEND
SHEET SHEET NAME
E0.1- GL LEGEND, SCHEDULES , AND LOAD CALCULATIONS
E1.1- GL ELECTRICAL SITE PLAN - GLENNALLEN
E2.1- GL LIGHTING PLA
E2.2- GL POWER AND SIGNAL PLAN
E3.1- GL POWER ONE-LINE DIAGRAM
E3.2- GL ELECTRICAL DETAILS
M0.1- GL MECHANICAL LEGEND AND ABBREVIATIONS
M0.2- GL MECHANICAL SCHEDULES
M0.3- GL MECHANICAL SCHEDULES
M1.1- GL PLUMBING
M2.1- GL FIRST FLOOR HEATING
M3.1- GL FIRST FLOOR VENTILATION
M4.1- GL SCHEMATICS & DETAILS
M4.2- GL DETAILS
IC0.1 INSTRUMENTATION & CONTROLS LEGEND
IC0.2 PROCESS CONTROL NETWORK DIAGRAM
IC1.1- GL PROCESS CONTROL RISER DIAGRAM GLENNALLEN
IC1.2- GL PROCESS CONTROL EQUIPMENT PLAN GLENNALLEN
IC2.1- GL SCADA PANEL SCP - ENCLOSURE LAYOUT GLENNALLEN
IC2.2- GL SCADA PANEL SCP - PANEL LAYOUT GLENNALLEN
IC2.3- GL SCADA PANEL SCP - THREE-LINE POWER GLENNALLEN
IC2.4- GL SCADA PANEL SCP - CONTROL POWER GLENNALLEN
IC2.5- GL SCADA PANEL SCP - PLC INPUTS/OUTPUTS GLENNALLEN
IC4.1- GL CHEMICAL DOSING JBOX - ENCLOSURE LAYOUT GLENNALLEN
IC4.2- GL CHEMICAL DOSING JBOX - SCHEMATIC DETAIL GLENNALLEN
IC5.1 SCHEMATIC DETAILS TYPICAL ANALOG AND DIGITAL I/O
IC5.2 SCHEMATIC DETAILS TYPICAL VFD
IC5.3 SCHEMATIC DETAILS TYPICAL FVNR
PI0.1- GL LEGENDS AND ABBREVIATIONS
PI1.1- GL PRETREATMENT P&ID
PI1.2- GL DISTRIBUTION P&ID
P1.0- GL PROCESS DESIGN CRITERIA
P1.1- GL PROCESS EQUIPMENT PLAN
P1.2- GL PROCESS PIPING PLAN
P1.3- GL PIPING ISOMETRIC
P1.4- GL PROCESS ELEVATIONS
P1.5- GL WATER STORAGE TANK T-10-1 DETAILS
P1.6- GL PROCESS DETAILS
P1.7- GL PROCESS DETAILS
S0.1 SYMBOLS
S0.2 GENERAL NOTES
S0.3 SPECIAL INSPECTION
S1.1 GLENNALLEN WTF FOUNDATION PLAN
S1.2 COPPER CENTER HQ FOUNDATION PLAN
S2.1 GLENNALLEN WTF FOUNDATION DETAILS
S2.2 GLENNALLEN WTF PILASTER & BOLLARD DETAILS
S2.3 GLENNALLEN WTF TRENCH & SUMP DETAILS
S2.4 COPPER CENTER HQ DETAILS
S2.5 GLENNALLEN CANOPY DETAILS
A0.1 ABBREVIATIONS AND SYMBOLS LEGEND
A1.1- HQ FLOOR PLAN
A2.1- GL FLOOR PLAN
A2.2- GL ROOF PLAN AND DETAILS
A3.1- GL EXTERIOR ELEVATIONS & SECTIONS, WALL SECTION
A4.1- GL DETAILS
C1.0- HQ NOTES, LEGEND , AND ABBREVIATIONS
C1.1- HQ EXISTING CONDITIONS AND DEMOLITION
C2.0- HQ SITE PLAN
C3.0- HQ DETAILS
C3.1- HQ DETAILS
C3.2- HQ DETAILS
C1.0- GL NOTES, LEGEND, AND ABBREVIATIONS
C2.0- GL EXISTING CONDITIONS AND DEMOLITION
C3.0- GL SITE LAYOUT
C3.1- GL UTILITY LAYOUT
C3.2- GL UTILITY PROFILES
C4.0- GL DETAILS
C4.1- GL DETAILS
C4.2- GL DETAILS
G1.0 - HQ COVER SHEET
G1.1 SHEET INDEX
G1.2 - HQ CODE STUDY
2 63
CODE STUDY - COPPER CENTER HEAD QUARTERS
REFERENCED CODES AND STANDARDS
INTERNATIONAL BUILDING CODE (IBC) 2021 EDITION
INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2021 EDITION
INTERNATIONAL MECHANICAL CODE (IMC) 2021 EDITION
INTERNATIONAL FUEL GAS CODE (IFGC) 2021 EDITION
INTERNATIONAL FIRE CODE (IFC) 2021 EDITION
UNIFORM PLUMBING CODE (IAPMO) 2018 EDITION
NFPA 70 NATIONAL ELECTRICAL CODE 2017 EDITION
NATIONAL ELECTRICAL SAFETY CODE 2017 EDITION
INTERNATIONAL RESIDENTIAL CODE 2021 EDITION
ASHRAE 90.1 2016 EDITION
NEC 2020 EDITION
INTERNATIONAL PRIVATE SEWAGE DISPOSAL CODE 2021 EDITION
NFPA 101 LIFE SAFETY CODE
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
NPS AUTOMATED CONTROLS STANDARDS
NPS REFERENCE MANUAL 58
EXISTING BUILDING ALTERATION LEVEL
LEVEL 2 (IEBC, 603)
OCCUPANCY CLASSIFICATION
OCCUPANCY
VEHICLE AND WORK BAYS S-2
TREATMENT BAY F-1
EXISTING BUILDING SPRINKLERED
BUILDING DESCRIPTION
CONSTRUCTION TYPE V-B
ALLOWABLE HEIGHT 40 FT (TABLE 504.3)
ACTUAL HEIGHT 21' - 2 1/2" COMPLIES
ALLOWABLE STORIES (IBC, TABLE 504.4)
F-1 1 S-2 2
ACTUAL STORIES 1 COMPLIES
ALLOWABLE AREA (IBC, TABLE 506.2)
F-1 8,500 SF
S-2 13,500 SF
ACTUAL BUILDING AREA (GROSS)
F-1 720 SF COMPLIES
S-2 360 SF COMPLIES
GROSS BUILDING AREA 1,080 SF
FIRE RESISTANCE RATINGS
PRIMARY STRUCTURAL FRAME 0 HOURS
BEARING WALLS 0 HOURS
NONBEARING WALLS AND PARTITIONS 0 HOURS
FLOOR CONSTRUCTION 0 HOURS
ROOF CONSTRUCTION 0 HOURS
OCCUPANT LOAD CALCULATIONS
OCCUPANCY OCCUPANCY EXIT
FACILITY ROOM CLASS AREA (SF) FACTOR (OLF) OCCUPANCY REQ'D REMARKS
GARAGE/ UTILITY
VEHICLE AND WORK BAYS S3 720 SF 300 2 1
TREATMENT BAY F2 360 SF 200 2 1
TOTAL BUILDING OCC: 4
OTHER REQUIREMENTS
MAXIMUM TRAVEL DISTANCE TO EXIT DISTANCE (IBC, TABLE 1017.2)
F-1 200 FT COMPLIES
S-2 300 FT COMPLIES
CODE STUDY - GLENNALLEN
REFERENCED CODES AND STANDARDS
INTERNATIONAL BUILDING CODE (IBC) 2021 EDITION
INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2021 EDITION
INTERNATIONAL MECHANICAL CODE (IMC) 2021 EDITION
INTERNATIONAL FUEL GAS CODE (IFGC) 2021 EDITION
INTERNATIONAL FIRE CODE (IFC) 2021 EDITION
UNIFORM PLUMBING CODE (IAPMO) 2018 EDITION
NFPA 70 NATIONAL ELECTRICAL CODE 2017 EDITION
NATIONAL ELECTRICAL SAFETY CODE 2017 EDITION
INTERNATIONAL RESIDENTIAL CODE 2021 EDITION
ASHRAE 90.1 2016 EDITION
NEC 2020 EDITION
INTERNATIONAL PRIVATE SEWAGE DISPOSAL CODE 2021 EDITION
NFPA 101 LIFE SAFETY CODE
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS
NPS AUTOMATED CONTROLS STANDARDS
NPS REFERENCE MANUAL 58
OCCUPANCY CLASSIFICATION
OCCUPANCY
WATER TREATMENT AREA F-1 (IBC 306.2)
TRUCK STORAGE AREA S-2 (IBC 311.3)
OCCUPANCY SEPARATION NON-SEPARATED OCCUPANCIES (508.3)
BUILDING DESCRIPTION
CONSTRUCTION TYPE V-B
ALLOWABLE HEIGHT 40 FT (TABLE 504.3)
ACTUAL HEIGHT 16'-4" COMPLIES
ALLOWABLE STORIES (IBC, TABLE 504.4)
F-1 1 S-2 2
ACTUAL STORIES 1 COMPLIES
ALLOWABLE AREA (IBC, TABLE 506.2)
F-1 8,500 SF
S-2 13,500 SF
ACTUAL BUILDING AREA (GROSS)
F-1 712 SF COMPLIES
S-2 560 SF COMPLIES
GROSS BUILDING AREA 1,271 SF
FIRE RESISTANCE RATINGS
PRIMARY STRUCTURAL FRAME 0 HOURS
BEARING WALLS 0 HOURS
NONBEARING WALLS AND PARTITIONS 0 HOURS
FLOOR CONSTRUCTION 0 HOURS
ROOF CONSTRUCTION 0 HOURS
OCCUPANT LOAD CALCULATIONS (IBC, TABLE 1004.5)
OCCUPANCY OCCUPANCY EXIT
ROOM CLASS AREA (SF) FACTOR (OLF) OCCUPANCY REQ'D REMARKS
101 VEHICLE BAY S-2 88 200 GROSS 1 1
102 PROCESS ROOM F-1 712 100 GROSS 8 1
103 STORAGE ROOM S-2 472 500 GROSS 1 1
TOTAL BUILDING OCC: 10
OTHER REQUIREMENTS
MAXIMUM TRAVEL DISTANCE TO EXIT DISTANCE (IBC, TABLE 1017.2)
F-1 200 FT
S-2 300 FT
ACTUAL TRAVEL DISTANCE 50'-6" COMPLIES
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF8/
/2
4:
:0
P
M B
IM
.0
W
R S
T R ep la ce W at er
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r vt
M.BARTOLOME
B. KLUG
D. ZIEMER
G1.2
- GL
CODE STUDY
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
3 63
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
2/5 /20
7:
:15
A M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-C
V-
GL
EN
NA
LL
EN
.dw g U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023
GENERAL CONSTRUCTION NOTES ABBREVIATIONS
1. EXISTING CONDITIONS AND UTILITIES DERIVED FROM
WRANGELL-ST.ELIAS NATIONAL PARK & PRESERVE PROJECT:
GLENNALLEN MAINTENANCE FACILITY: WATER AND SEWER
IMPROVEMENTS. DRAWING NO 190 / 80,127A, DATED 2013. CONTRACTOR
SHALL VERIFY SITE CONDITIONS BEFORE CONSTRUCTION.
2. EXISTING SEPTIC SYSTEM BASED ON PROJECT STATED IN NOTE 1, AND
ADEC PLAN REVIEW D5039. CONTRACTOR SHALL VERIFY CONDITION OF
UTILITY BEFORE CONSTRUCTION.
3. LOCATIONS OF EXISTING UTILITIES ARE APPROXIMATE ONLY. THE
CONTRACTOR SHALL VERIFY LOCATIONS BY OBTAINING UTILITY
LOCATES PRIOR TO BEGINNING CONSTRUCTION. COORDINATE UTILITY
RELOCATION WITH NATIONAL PARK SERVICES. EXERCISE CAUTION
DURING EXCAVATION.
4. VERIFY HORIZONTAL AND VERTICAL LOCATIONS OF ALL UTILITIES
ENCOUNTERED DURING CONSTRUCTION. RECORD LOCATIONS AND
CHANGES TO UTILITIES IN SURVEY NOTES AND ON AS BUILT DRAWINGS.
5. VERIFY INVERTS AND LOCATIONS OF ALL UTILITY CONNECTION POINTS
PRIOR TO INSTALLING PIPE. REPORT DISCREPANCIES FROM PLANS
IMMEDIATELY TO THE ENGINEER OF RECORD.
6. ELEVATIONS SHOWN ARE TO PIPE INVERT OR FINISH GROUND SURFACE,
UNLESS NOTED OTHERWISE.
7. DIMENSIONS SHOWN ARE TO FACE OF BUILDING, OR OUTSIDE EDGE OF
PIPE UNLESS NOTED OTHERWISE.
8. RESTORE ALL DISTURBED PROPERTY OUTSIDE OF WORK LIMITS TO
ORIGINAL CONDITIONS
9. DEWATERING MAY BE REQUIRED FOR ALL EXCAVATIONS THAT
PENETRATE THE GROUND WATER SURFACE. WATER RESULTING FROM
CONTRACTOR'S DEWATERING EFFORT MAY NOT BE PUMPED OR
OTHERWISE DIVERTED INTO EXISTING STORM DRAINS UNLESS
REQUIRED PERMITS ARE OBTAINED BY THE CONTRACTOR. UNDER NO
CIRCUMSTANCES WILL THE CONTRACTOR BE ALLOWED TO DIVERT
WATER FROM THE EXCAVATION ONTO ROADWAYS. CONTRACTOR SHALL
PROVIDE DISPOSAL SITE FOR EXCESS WATER AND SHALL BE
RESPONSIBLE FOR ALL NECESSARY PERMITS AND APPROVALS.
10. THE CONTRACTOR SHALL FOLLOW NATIONAL PARK SERVICE
REGULATIONS FOR NOISE, HOURS OF OPERATIONS, AND DUST CONTROL.
11. THE AUTOCAD FILE FOR THIS SITE PLAN WILL BE PROVIDED TO THE
CONSTRUCTION SURVEYOR. THE SURVEYOR SHALL INFORM THE
ENGINEER OF ANY DISCREPANCIES IMMEDIATELY.
12. MINIMIZE OFF-SITE VEHICLE TRACKING OF SEDIMENTS, SWEEP SITE
ENTRANCE AND EXIT DURING CONSTRUCTION WHEN SOILS
ACCUMULATE TO DEPTHS GREATER THAN ONE-FOURTH INCH. WATER
EXPOSED SOILS AS NECESSARY TO CONTROL GENERATION OF DUST.
CONSTRUCTION ACTIVITIES SHALL BE MONITORED ON A DAILY BASIS TO
DETERMINE IF TRACKING OF DIRT AND DEBRIS ONTO THE ADJACENT
ROADWAYS HAS OCCURRED. ANY NECESSARY CLEANUP SHALL BE
ACCOMPLISHED ON A DAILY BASIS.
13. THE CONTRACTOR SHALL PROVIDE CONTROLS TO LIMIT SEDIMENT
DISCHARGE DUE TO SOIL EROSION. THESE CONTROLS SHALL INCLUDE
REGULAR SWEEPING OF STREETS ADJACENT TO THE SITE THAT
ACCUMULATE SITE SOILS. ADDITIONAL CONTROLS MAY BE REQUIRED IF
THESE MEASURES PROVE INADEQUATE. THE CONTRACTOR SHALL
IMPLEMENT A STORM WATER POLLUTION PREVENTION PLAN (SWPPP).
14. REVISIONS THAT ALTER THE REVIEWED AND APPROVED DESIGN INTENT
REFLECTED IN THIS SET OF SIGNED CONSTRUCTION DRAWINGS MUST BE
APPROVED BY THE ENGINEER OF RECORD.
15. KEEP SITE FREE OF LITTER
R
I
C
H
A
R
D
S
O
N
H
W
Y
R I C
H A
R D
S O
N
H
W Y
GLENN HWY
GLENNALLEN
COPPERVILLE
TAZLINA
PROJECT
LOCATION
LOCATION
PROJECT
G
L
E
Y
GLENNALLEN CAMPUS
NTS
VICINITY MAP: PROJECT AREA
NTS
LEGEND
ADEC - ALASKA DEPT. OF ENVIRONMENTAL CONSERVATION
ARFS - AS REQUIRED FOR SAFETY
AWWA - AMERICAN WATER WORKS ASSOCIATION
BLM - BUREAU OF LAND MANAGEMENT
CMP - CORRUGATED METAL PIPE
CO - CLEANOUT
DIAM. - DIAMETER
EL - ELEVATION
GPD - GALLONS PER DAY
FT - FOOT
H - HORIZONTAL
HDPE - HIGH DENSITY POLYETHYLENE
IBC - INTERNATIONAL BUILDING CODE
IN - INCH
INV - INVERT
LC - LEVELING COURSE
LF - LINEAR FEET
MIN - MINIMUM
NFS - NON-FROST SUSCEPTIBLE
NPS - NATIONAL PARK SERVICE
NSF - NATIONAL SANITATION FOUNDATION
NTS - NOT TO SCALE
OD - OUTSIDE DIAMETER
OSHA - OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
PE - POLYETHYLENE
PSI - POUND PER SQUARE INCH
PVC - POLYVINYL CHLORIDE
S - SEWER
SDR - STANDARD DIMENSION RATIO
SF - SQUARE FOOT
TYP - TYPICAL
WTP - WATER TREATMENT PLANT
PROPOSED EXISTING DESCRIPTION
BUILDING OUTLINE
FENCE
CULVERT
WATER
VALVE
SANITARY SEWER
LEACH FIELD BOUNDARY
CLEANOUT
EDGE OF GRAVEL
BOLLARD
POWER POLE
GEOTECHNICAL TEST PIT LOCATION
C1.0-
NOTES, LEGEND, AND
ABBREVIATIONS
REMOVE AND STORE PROPANE TANK. COORDINATE
WITH OWNER/SUPPLIER FOR NEW LOCATION.
REMOVE WATER TREATMENT
PLANT STRUCTURE. PROTECT
WATER WELL IN PLACE
REMOVE ~30 LF OF WATER DISTRIBUTION PIPE
(2" SUPPLY AND 2" RETURN POLYETHYLENE PIPE IN
6" CARRIER PIPE WRAPPED WITH 3" INSULATION)
REMOVE ~45 LF OF SEWER PIPE AND CLEANOUT.
(4" HDPE WITH 4" INSULATION IN 12" HDPE JACKER)
REMOVE ~40 LF OF 1" HDPE SEASONAL WATER LINE
TRAIL CREW BLDG. PARK STAFF WILL
RELOCATE. NOT IN CONTRACTORS SCOPE
REMOVE ~10 LF OF SEWER PIPE
APPROXIMATE LIMITS OF PROPOSED
LEACH FIELD EXCAVATION
EXISTING CLEANOUT TO REMAIN
EXISTING SEPTIC TANK TO REMAIN
EXISTING SEWER PIPE TO REMAIN
EXISTING LEACH FIELD TO REMAIN
EXISTING CLEANOUT TO REMAIN
REMOVE ~55 LF OF SEWER PIPE.
(4" HDPE WITH 4" INSULATION IN 12" HDPE JACKER)
CUT AND CAP ABANDONED PIPE AND FITTING
CAP ABANDONED PIPE
SHEET
PMIS/PKG NO.
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
4/1 6/2
4 3
:53 :09
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-D
M-
GL
EN
NA
LL
EN
.dw g U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023
NOTES:
1. EXISTING CONDITIONS SHOWN ARE COMPILED FROM
"AS-CONSTRUCTED" DRAWINGS FOR THE GLENNALLEN MAINTENANCE
FACILITY, DATED 2013; DESIGN DRAWINGS FOR THE GLENNALLEN
INTERAGENCY EMPLOYEE HOUSING PROJECT, DATED 1994; AND THE
BLM'S GLENNALLEN ADMINISTRATIVE SITE, EXISTING SITE CONDITIONS
SURVEY, WHICH WAS COMPILED FROM FIELD SURVEY AND DESIGN
DRAWINGS.
2. EXISTING DEPTHS OF BURY:
- 1" HDPE SEASONAL WATER LINE IS BURIED AT ~12"
- 4"x12" ARCTIC INSULATED SEWER PIPE IS BURIED AT ~4 FT TO 5 FT
- 6"x12" ARCTIC INSULATED WATER DISTRIBUTION LINE AT ~3FT TO 5FT
- EXISTING DEPTHS OF BURY PER DESIGN INFORMATION AND IS NOT
CONFIRMED.
C2.0-
EXISTING CONDITIONS
AND DEMOLITION
A B C
PROPOSED
WTP
TRAIL CREW BUILDING RELOCATED BY PARK STAFF, NOT IN CONTRACTORS SCOPE
TRAIL
CREW
BLDG.
20' MIN
PROPOSED LEACH FIELD EXPANSION
SITE GRADING AND FINISHED FLOOR, SEE NOTE 4 AND 5. GRADE
TO DRAIN AROUND BUILDING, DO NOT DIRECT STORMWATER
TOWARDS OTHER STRUCTURES OR DRIVING SURFACES.
CONTRACTOR STAGING AND LAYDOWN
PROPOSED SEPTIC TANK
BOLLARDS, SEE ARCHITECTURAL FOR LAYOUT.
INSTALL PER DETAIL 2/C4.2
200' WELL RADIUS
PROPANE TANK, GRADE GROUND
BELOW TANK LOCATION TO BE
LEVEL. TANK SHALL BE PLACED
ON CONCRETE BLOCKS
16'
3'
SHEET
PMIS/PKG NO.
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
4/1 7/2
4 1
2:2 2:0
9 P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-S
I-G
LE
NN
AL
LE
N_
V2 .dw g U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023
C3.0-
SITE LAYOUT
NOTES:
1. PROPOSED WATER TREATMENT PLANT (WTP) WILL BE PLACED PER THE
EXISTING WELL LOCATION. CONTRACTOR SHALL FIND CLEAR SPACE
BETWEEN FENCE AND BUILDING AND PROVIDE INFORMATION TO NPS
PROJECT MANAGER BEFORE CONSTRUCTION TO DETERMINE IF FENCE
WILL BE IMPACTED.
2. ORIENTATION OF PROPOSED BUILDING SHALL MATCH ORIENTATION OF
EXISTING BUILDING.
3. SEE STRUCTURAL SHEETS FOR SUBGRADE IMPROVEMENTS FOR
PROPOSED WTP.
4. CONTRACTOR SHALL MEASURE FINISH FLOOR OF EXISTING WTP
BEFORE DEMOLITION AND REPORT ELEVATION TO ENGINEER PRIOR TO
DEMOLITION.
4.1. PROPOSED FINISH FLOOR SHALL BE SET TO ALLOW THE GROUND
IMMEDIATELY ADJACENT TO THE FOUNDATION TO BE SLOPED AWAY
FROM THE BUILDING AT A SLOPE OF NOT LESS THAN 5-PERCENT
FOR A MINIMUM DISTANCE OF 10 FEET MEASURED PERPENDICULAR
TO THE FACE OF THE WALL. (2021 IBC 1804.4)
4.2. SEE SHEET C3.1. CONTRACTOR SHALL SURVEY AND MEASURE
INVERT OF EXISTING SEWER CLEANOUT AT CONNECTION POINT.
FINISH FLOOR OF PROPOSED WTP WILL BE SET TO ACCOMODATE
NEW PIPE SLOPE AND CONNECTION TO SEWER CATCH BASIN AS
SHOWN IN 3/C4.1. COORDINATE WITH ENGINEER.
5. GRAVEL DRIVEWAY SHALL EXTEND FROM EXISTING GRAVEL ACCESS
ROAD TO BUILDING ENTRANCE AND GARAGE DOOR. COMPACT GRAVEL
TO 95% TO CREATE A FIRM, STABLE SURFACE. RESTORE OTHER
DISTURBED AREA AROUND THE BUILDING TO ORIGINAL CONDITION.
6. SITE CONCRETE SHALL CONFORM TO SPECIFICATION 03 30 00.
A B C
50LF 1" HDPE SEASONAL WATER
SERVICE, ~12" BURY DEPTH,
SLOPE TO DRAIN
50LF 4x12 ARCTIC PIPE, SEE DETAIL 1/C4.0
CONNECTION TO BUILDING,
SEE DETAIL 3/C4.1
40LF 6x12 ARCTIC PIPE (2" HDPE SUPPLY
AND 2" HDPE RETURN SERVICE)
SEE DETAIL 2/C4.0
EXISTING CLEANOUT
TO REMAIN
SINGLE CLEANOUT WITH
45-DEGREE BEND,
SEE DETAIL 5/C4.0
45-DEGREE BEND
90-DEGREE BEND
10' MIN.
10' MIN.
TRAIL CREW BLDG.
17'
PROPANE TANK,
SEE MECHANICAL
LEACH FIELD - FOUR 24-FT LONG LATERALS
CONSTRUCTED OF INFILTRATOR CHAMBERS.
SEE DETAILS ON C4.1
24'
~11.3'
DOUBLE CLEANOUT,
SEE DETAIL 5/C4.0
~8 LF 4x12 ARCTIC
PIPE @ 2.0% MIN.,
SEE DETAIL 1/C4.0
DISTRIBUTION BOX,
SEE DETAIL 4/C4.0
TWO RUNS OF ~6LF
4x12 ARCTIC PIPE, SEE DETAIL 1/C4.0
USE DOUBLE WYE OR DISTRIBUTION BOX TO
COMBINE SEWER LINES AND CONNECT TO EXISTING
20'
9.4'
~10 LF 4x12 ARCTIC PIPE @ 2.0% MIN., SEE DETAIL 1/C4.0
45° BEND
DISTRIBUTION BOX,
SEE DETAIL 4/C4.0
11'
EXISTING POWER POLE,
PROTECT IN PLACE
SINGLE CLEANOUT,
SEE DETAIL 5/C4.0
SINGLE CLEANOUT WITH 45-DEGREE
BEND, SEE DETAIL 5/C4.0
GROUND EL≈1444.0
INV≈1439.75
50LF 4x12 ARCTIC PIPE @10.1%
SEE DETAIL 1/C4.0
EXISTING CLEANOUT
GROUND EL≈1447.5
INV≈1444.8
24LF 4x12 ARCTIC PIPE @ 1.7%
SEE DETAIL 1/C4.0
10LF 4x12 ARCTIC PIPE @ 2.7%
SEE DETAIL 1/C4.0
1,000 GALLON PE
SEPTIC TANK,
SEE C4.2
EXISTING SEPTIC
TANK TO REMAIN
CONNECT TO
EXISTING SERVICE
GROUND EL≈1443.0
INV≈1438.8
CAP LINE
CAP LINE
SHEET
PMIS/PKG NO.
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
8/2 6/2
4 3
:14 :16
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-U
T-
GL
EN
NA
LL
EN
_V 2.d wg U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023
LEACH FIELD NOTES:
1. CONTRACTOR SHALL EXCAVATE 6-FT BELOW BOTTOM OF PROPOSED
LEACH FIELD TO DETERMINE IF A CONFINING LAYER IS PRESENT,
DOCUMENT FINDINGS, AND REPORT TO ENGINEER.
2. THE PROPOSED LEACH FIELD SHALL COVER A MINIMUM OF 270 SF.
3. CONTRACTOR SHALL DOCUMENT INSTALLATION OF PROPOSED LEACH
FIELD AND SEWER PIPE MODIFICATIONS WITH AS-BUILT NOTES,
ELEVATIONS, AND PHOTOS. DOCUMENTATION SHALL BE DELIVERED TO
ENGINEER ONCE CONSTRUCTION IS COMPLETE FOR RECORD
DRAWINGS.
4. THE CAPACITY OF EXISTING LEACH FIELD IS 511 GPD PER 2013 DESIGN
DOCUMENTS. EXISTING SYSTEM WAS APPROVED BY ADEC (PLAN
REVIEW NO.: 8037). PROPOSED LEACH FIELD WILL ADD 182 GPD
CAPACITY TO SYSTEM, PROVIDING A TOTAL CAPACITY OF 693 GPD.
5. DO NOT CONSTRUCT PROPOSED LEACH FIELD UNDER DRIVEWAYS.
WTP UTILITY NOTES:
1. SLOPE SEWER PIPE AT 2-PERCENT.
CONTRACTOR SHALL DETERMINE INVERT
ELEVATION OF EXISTING SEWER AT
CLEANOUT BEFORE CONSTRUCTING NEW
SEWER CONNECTION. MAINTAIN MAXIMUM
COVER OVER SEWER SERVICE FOR AS
MUCH OF THE RUN AS POSSIBLE. RECORD
INVERT ELEVATIONS AND DEPTH OF COVER
AT HORIZONTAL AND VERTICAL CHANGES.
CONTACT ENGINEER IF 4-FT COVER
CANNOT BE MAINTAINED.
C3.1
WTP UTILITIES
1"=10'
C3.1
SEPTIC TANK AND LEACH FIELD
1"=10'
C3.1-
UTILITY LAYOUT
SEPTIC TANK AND SEWER NOTES:
1. GROUND AND PIPE ELEVATIONS COLLECTED BY NPS STAFF.
CONTRACTOR TO LOCATE EXISTING PIPES AND VERIFY CONNECTION
ELEVATIONS BEFORE EXCAVATION AND INSTALLATION.
2. CONTRACTOR SHALL DOCUMENT INSTALLATION OF PROPOSED SEWER
SERVICE RE-ROUTE AND SEPTIC TANK WITH AS-BUILT NOTES,
ELEVATIONS, AND PHOTOS. DOCUMENTATION SHALL BE DELIVERED TO
ENGINEER ONCE CONSTRUCTION IS COMPLETE FOR RECORD DRAWINGS.
EXISTING 4" SEWER PIPE IN
ARCTIC INSULATION
EXISTING CLEANOUT,
INSTALL CONCRETE
COLLAR PER DETAIL 5/C4.0
GROUND EL≈1447.5
INV≈1444.8
SINGLE CLEANOUT AND
CONCRETE COLLAR PER
DETAIL 5/C4.0
GROUND EL≈1444.0
INV≈1439.75
SINGLE CLEANOUT PER
DETAIL 5/C4.0
CONNECT TO EXISTING
SERVICE WITH WYE
GROUND EL≈1443.0
INV≈1438.8
L F
X
A
R C
T
IC
P
IP
E
.1
10LF 4X12 ARCTIC PIPE @ 2.7%
24LF 4X12 ARCTIC PIPE @ 1.7%
EXISTING 4" SEWER PIPE IN
ARCTIC INSULATION
FINISHED GRADE =
EXISTING GROUND
NOTE:
1. CONTRACTOR SHALL VERIFY EXISTING PIPE ELEVATIONS AT
CONNECTION POINTS BEFORE BEGINNING INSTALLATION.
2. SLOPES OF EXISTING PIPES IS ASSUMED BASED ON GRADE OF
EXISTING GROUND.
3. A MINIMUM OF 10-FT OF PIPE IMMEDIATELY UPSTREAM OF SEPTIC
TANK SHALL BE SLOPED AT 1-2%.
T
L
E
A
C
F
I E
L
D
S
FROM WTP
1,000
GALLON
PE SEPTIC
TANK
DOUBLE CLEANOUT PER
DETAIL 5/C4.0
DISTRIBUTION BOX PER
DETAIL 4/C4.0
CONNECT TO EXISTING
SEWER SERVICE, INSTALL
DISTRIBUTION BOX PER
DETAIL 4/C4.0
45° BEND
~10-FT~8-FT
F
R
M
T
P
A
D
M
E
C
H
A
N
I
S
O
P
24-FT
4X12
ARCTIC
PIPE,
2% MIN.
4X12
ARCTIC
PIPE,
2% MIN.
LEACH FIELD
CHAMBERS
LEACH FIELD, SEE
DETAILS ON C4.1
FINISHED GRADE =
EXISTING GROUND
EXISTING 4" SEWER PIPE IN
ARCTIC INSULATION
FLOW FROM WTP
EXISTING 4" SEWER PIPE IN
ARCTIC INSULATION
CONNECT TO EXISTING
SERVICE AT EXISTING
CLEANOUT, INSTALL
CONCRETE COLLAR PER
DETAIL 5/C4.0
SINGLE CLEANOUT AND
CONCRETE COLLAR PER
DETAIL 5/C4.0
FINISHED GRADE =
EXISTING GROUND
45° BEND
SINGLE CLEANOUT AND
CONCRETE COLLAR PER
DETAIL 5/C4.0, AND 45° BEND
NOTE:
1. CONTRACTOR SHALL MEASURE DEPTH OF EXISTING SEWER AT
EXISTING CLEANOUT BEFORE CONSTRUCTION OF WTP BEGINS.
2. FINISH FLOOR ELEVATION OF WTP SHALL BE SET TO OBTAIN THE
MINIMUM SLOPE AND COVER OF THE PROPOSED SEWER SERVICE
CONNECTION FROM THE EXISTING CLEANOUT TO THE WTP. SEE
NOTE 4 ON C3.0 AND THE UTILITY NOTES WITH 1/C3.1
~50-FT
4X12 ARCTIC
PIPE, 2% MIN.
SEE DETAIL 3/C4.1
FOR CONNECTION
TO BUILDING
SHEET
PMIS/PKG NO.
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
8/2 6/2
4 3
:11 :59
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-U
T-
GL
EN
NA
LL
EN
_V 2.d wg U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023
C3.2
WTP CONNECTION - PROFILE
NTP
C3.2-
UTILITY PROFILES
C3.2
LEACH FIELD - PROFILE
NTP
C3.2
SEPTIC TANK - PROFILE
NTP
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
4/1 6/2
4 3
:53 :18
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-D
T-
GL
EN
NA
LL
EN
.dw g U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023
4" HDPE, SDR 17 OR 11
POLYURETHANE INSULATION12" OD THIN WALL HDPE
OUTER JACKET
C4.0
SEWER LINE - 4x12 ARCTIC PIPE
NTS
6" HDPE, SDR 17 CARRIER PIPE
3" THICK POLYURETHANE INSULATION
60 MIL PE OUTER JACKET
C4.0
WATER LINE - 6x12 ARCTIC PIPE
NTS
2" HDPE RETURN LINE
2" HDPE SUPPLY LINE
12"
6" MIN.
6"
4.
0'
M
IN
IM
U
M (O
R A
S N
O
TE
D
6" GRAVEL, COMPACTED TO 95%
CLEAN NATIVE
MATERIAL
COMPACTED TO
90%
ACCESS ROADS,
DRIVING SURFACES
OUTSIDE OF VEHICLE
MANEUVERING AREAS
RESTORE TO ORIGINAL CONDITION
O.D.
ARCTIC PIPE
AS REQUIRED FOR
SAFETY BY OSHA
BEDDING, 2" MINUS CLASSIFIED MATERIAL
EXCAVATE AS REQUIRED TO
REMOVE ALL UNSUITABLE MATERIAL
NOTE: COMPACT BOTTOM OF TRENCH
C4.0
UTILITY TRENCH SECTION
NTS
C4.0
DISTRIBUTION BOX
NTS
NOTES:
1. PRECAST OR PREMANUFACTURED DISTRIBUTION BOX SUITABLE FOR COMMERCIAL
APPLICATIONS THAT MEETS THE MINIMUM DIMENSIONS NOTED IN THIS DETAIL.
2. DISTRIBUTION BOX SHALL BE INSTALLED LEVEL. MANUFACTURER SUPPLIED
"LEVELERS" MAY ONLY BE USED IF THE DIAMETER OF INLET AND OUTLET PIPES IS
NOT DECREASED.
INLET
2' T
YP
4.0' MINIMUM
(OR AS NOTED)
4x12 ARCTIC PIPE PER 1/C4.0
45° BEND
45° WYE
2' T
YP
4.0' MINIMUM
(OR AS NOTED)
4x12 ARCTIC PIPE PER 1/C4.0
45° BEND
45° WYE
4x12 ARCTIC PIPE PER 1/C4.0
45° BEND
SINGLE CLEANOUT DOUBLE CLEANOUT
C4.0
CLEANOUT
NTS
TRACER WIRE, INSTALL FOR SEWER AND WATER PIPES
DETAILSC4.0-
EJIW 1574 CLEANOUT BOX
AND COVER, OR EQUIVALENT
6" MIN.
6" MIN.
6" MIN.
2"
ADJACENT GROUND
4" MIN. CONCRETE, 4000 PSI
CLEANOUT COVER AND
CONCRETE COLLAR
NOTE: CLEANOUTS WITHIN DRIVE AREAS
SHALL BE SET RECESSED INTO ADJACENT
GROUND WITH CONCRETE COLLAR
CONCRETE COLLAR -
PLAN VIEW
EJIW 1574 CLEANOUT BOX
AND COVER, OR EQUIVALENT
CLEAN NATIVE MATERIAL
COMPACTED TO 95%
AutoCAD SHX Text 9"
AutoCAD SHX Text 14"
AutoCAD SHX Text 5.5"
AutoCAD SHX Text 3.5"
AutoCAD SHX Text 4.5"
AutoCAD SHX Text 1"
AutoCAD SHX Text 9.5"
AutoCAD SHX Text
CLEANOUT CAP
AutoCAD SHX Text
CLEANOUT CAP
INCOMING
FLOW
4-IN RIGID BOARD
INSULATION OVER LEACH
FIELD DISTRIBUTION PIPES DISTRIBUTION BOX,
SEE DETAIL 4/C4.0
INSPECTION PIPE, TYP
24'
~11.3'
INFILTRATOR CHAMBERS
SHEET
PMIS/PKG NO.
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
4/1 6/2
4 3
:53 :18
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-D
T-
GL
EN
NA
LL
EN
.dw g U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023
C4.1
LEACH FIELD - TYPICAL SECTION
NTS
EXISTING GROUND
UNDISTURBED EARTH
DO NOT PLACE MATERIAL WITHIN CHAMBER
NATIVE SOIL AT BOTTOM OF LEACH
FIELD, DO NOT COMPACT
AS REQUIRED FOR
SAFETY BY OSHA
4-FT MINIMUM
NOTES:
1. ANY SOIL AT BOTTOM OF LEACH FIELD THAT IS COMPACTED SHALL BE DISTURBED, DUG, AND REPOSITIONED
SO THAT NATIVE SOIL IS NOT COMPACTED BEFORE PLACING INFILTRATOR CHAMBERS. KEEP EQUIPMENT AND
VEHICLES OUT OF LEACH FIELD.
2. MOUND SOIL OVER LEACH ABOVE ABOVE EXISTING ELEVATION SO THAT STORMWATER WILL DRAIN AWAY AND
AROUND LEACH FIELD
3. BASIS OF DESIGN: INFILTRATOR CHAMBER DIMENSIONS ARE 34" W x 53" L x 12" H
4. INSTALL SEPARATOR FABRIC PER ADEC ONSITE WASTEWATER SYSTEM INSTALLATION MANUAL (JANUARY 2016).
FINISHED GRADE, MOUND SOIL
TO DRAIN OVER LEACH FIELD
AS REQUIRED FOR
SAFETY BY OSHA
INSPECTION PIPE, TYP
SEPARATOR FABRIC
" M
IN
12"
C4.1
INSPECTION PIPE
NTS
SEPARATOR FABRIC
FINISHED GRADE
REMOVABLE CAP
REFLECTIVE TAPE
4" SOLID WALL PVC PIPE
4" PERF. PVC (1/2" DIAM. PERFORATIONS)
INFILTRATOR CHAMBER
C4.1
BUILDING CONNECTION
NTS
DETAILSC4.1-
C4.1
LEACH FIELD - PLAN
NTS
1-FT
4-FT
4-IN RIGID BOARD INSULATION
4-IN RIGID BOARD INSULATION
C4.1
4X12 ARCTIC PIPE
INSTALL WATERTIGHT AND FLEXIBLE
PIPE TO MANHOLE CONNECTION AT
PENETRATION. SEAL WITH
POLYURETHANE SPRAY IN FOAM
NOTE:
CIVIL SCOPE DETAILS CONNECTION TO CONCRETE WASTEWATER "CATCH BASIN". ALL OTHER WORK
SHOWN IN OTHER DISCIPLINE'S DRAWINGS
TO CONNECTION WITH EXISTING
PIPE AND LEACH FIELD
EXISTING GROUND
2% MINIMUM TO
CONNECTION
45° BEND
2 FT PIPE BETWEEN FITTINGS.GROUT FLOOR TO DRAIN
ARCTIC BOOT CONNECTION FASTENED PER MANUFACTURERS INSTRUCTIONS
5LF @ 5% MINIMUM
STUB PIPE 2-INCH MINIMUM
INTO CATCH BASIN
FINISHED GRADE
INSTALL SINGLE CLEANOUT,
SEE 5/C4.0
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF
248940
4/1 6/2
4 3
:53 :18
P M
J:\
\63
7-
\65
CA
D\ Sh ee tF ile s\G
L - G len na lle n\S
C2 0-
CS
-D
T-
GL
EN
NA
LL
EN
.dw g U
SE
R:
NC
ON
W
AY
GL
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
N.CONWAY
N.CONWAY
L.CHMIELOWSKI
12/01/2023 11
DETAILSC4.2-
ANCHORS, (TYP OF 6)
CABLE, (TYP OF 3)
SLOPE TO DRAIN SLOPE TO DRAIN
24-IN MANWAY WITH
INSULATED FROST LID
COMPACTED BACKFILL
MUST BE MOUNDED
4-IN TO 6-IN TO ALLOW
FOR SETTLEMENT
ARFS
BACKFILL WITH EXCAVATED MATERIAL,
COMPACT TO 90%
FILL TANK 1/2 FULL OF WATER
PRIOR TO BACKFILLING
SEPTIC TANK FOUNDATION MUST BE
THOROUGHLY COMPACTED NON-FROST
SUSCEPTIBLE MATERIAL
2-FT MINIMUM
1,000 GALLON
PE TANK
NOTE:
1. ANCHORS SHALL BE SEATED AND PROOF
LOADED TO 120% OF DESIGN LOAD.
4-IN ARCTIC SEWER PIPE
FROM EXISTING SYSTEM
FLEXIBLE LOW PRESSURE COUPLING WITH 2 EACH
SCREW CLAMPS TO PROVIDE SMOOTH
TRANSITION (TYP OF 2)
BACKFILL IN 12" LIFTS,
COMPACT TO 90%
NOTE:
1. 1,000 GALLON, TWO COMPARTMENT POLYETHYLENE SEPTIC
TANK MANUFACTURED IN COMPLIANCE WITH 18 AAC AND
APP. H OF THE UNIFORM PLUMBING CODE.
2. SEPTIC TANK MUST BE INSTALLED LEVEL.
3. SOLID PIPE WITH NO JOINTS TO SPAN 10 FEET FROM INLET
AND OUTLET OF TANK
END VIEW
PROFILE
4-IN SEWER PIPE TO LEACH FIELD,
SEE 3/C3.0 FOR INSULATION
24-IN MANWAYS
WITH INSULATED
FROST LIDS
4-IN URETHANE INSULATION, 30 PSI
MINIMUM COMPRESSIVE STRENGTH
4-IN URETHANE INSULATION, 30 PSI
MINIMUM COMPRESSIVE STRENGTH
4-IN PVC INLET TEE
4-IN PVC TEE WITH EFFLUENT FILTER
RATED FOR 700 GPD MINIMUM
2-FT MINIMUM
C4.2
SEPTIC TANK INSTALLATION
NTS
SLOPE TO DRAIN
FINISH
GRADE
6" DIA SCHEDULE 40
STEEL PIPE FILLED WITH
CONCRETE AND PAINTED
(SEE NOTE 1)
CONCRETE
2"
4.0'
18"
3000 PSI
CONCRETE
4.0'
6"
NOTE:
1. POSTS SHALL BE PRIMED AND RECEIVE TWO COATS MINIMUM
OF DARK GREEN POWDER COAT PAINT IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS. TOPCOAT WITH TWO
C4.2
STEEL BOLLARD
NTS
4"
YELLOW
REFLECTORIZED
STRIPPING
COATS OF POLYURETHANE ENAMEL PAINT, YELLOW IN
COLOR.
SYMBOLS LEGEND
ROOM DESIGNATION
WALL TYPE
DOOR DESIGNATION
GRIDLINE
EQUIPMENT DESIGNATION
EXTERIOR ELEVATION DESIGNATION
WINDOW / LOUVER DESIGNATION
DETAIL DESIGNATION
REVISION DESIGNATION
BUILDING SECTION DESIGNATION
PLAN KEYNOTE
INTERIOR ELEVATION DESIGNATION
BREAK LINE
NORTH ARROW / PLAN NORTH
DATUM DESIGNATION
TITLE DESIGNATION
XX
XX
1 VIEW NAME 1
A101
SHT_NO
DET_NO
A101
X'XX" AFF CEILING HEIGHT DESIGNATION
XXXX
RM NO
ROOM NAME
XXXX
FURNITURE DESIGNATION
XXx
WALL SECTION DESIGNATION
XX
DET_NO
SHT_NO
SIM
LEVEL NAME
ELEVATION
GRAPHIC SCALE
XXXX
DET_NO
SHT_NO
SIM
DET_NO
SHT_NO
SIM
DET_NO
SHT_NO
SIM
DETAIL SECTION DESIGNATION
4 80
ABBREVIATIONS LEGEND
AB ANCHOR BOLT
ABS ACRYLONITRILE BUTADIENE STYRENE
ABV ABOVE
A/C AIR CONDITIONING
AC ASPHALTIC CONCRETE
ACP ACOUSTICAL CEILING PANEL
AD AREA DRAIN
ADDL ADDITIONAL
ADF ACCESSIBLE DRINKING FOUNTAIN
ADJ ADJACENT
AFF ABOVE FINISH FLOOR
AFS ABOVE FINISH SLAB
AGGR AGGREGATE
ALUM ALUMINUM
ALT ALTERNATE
ANOD ANODIZED
APPROX APPROXIMATE
ARCH ARCHITECTURAL
A
B
BBQ BARBEQUE
BD BOARD
BFF BELOW FINISH FLOOR
BKBD BACK BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOD BOTTOM OF DECK
BOT F BOTTOM FACE
BOT BOTTOM
BR BEDROOM
BRG BEARING
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CER CERAMIC
CFCI CONTRACTOR FURNISHED /
CONTRACTOR INSTALLED
CG CORNER GUARD
CMPST COMPOSITE
CI CAST IRON
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
COND CONDITION
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUE/CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COP COPPER
CORR CORRIDOR
CPT CARPET
CSK COUNTERSINK
CT CERAMIC TILE
CTR CENTER
CUH CABINET UNIT HEATER
CULT CULTURED
CW COLD WATER PIPING
D
D DEEP/DEPTH
DBL DOUBLE
DEG DEGREE
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DR DOOR
DS DOWNSPOUT
DSP DRY STANDPIPE
DW DISHWASHER
DWG DRAWING
DWR DRAWER
E
E EAST
EA EACH
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELAST ELASTOMERIC
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
EPB ELECTRICAL PANEL BOARD
EPDM ETHYLENE PROPYLENE DIENE MONOMER
ES EACH SIDE
EQ EQUAL
EQUIP EQUIPMENT
EOS EDGE OF SLAB
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXP EXPOSED
EXPN EXPANSION
EXT EXTERIOR
(E) EXISTING
F FAHRENHEIT
FA FIRE ALARM
FAB FABRICATE
FB FLAT BAR
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISH FLOOR
FF & E FURNITURE, FIXTURES AND
EQUIPMENT
FGL FIBERGLASS
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLG FLOORING
FLR FLOOR
FLUOR FLUORESCENT
FLR SK FLOOR SINK
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FP FIRE PROOF
FR FRAME
FRP FIBERGLASS REINFORCED
PLASTIC
FRT FIRE RETARDANT
FRZ FREEZER
FT FEET
FTD FACIAL TISSUE DISPENSER
FTG FOOTING
FURG FURRING
FUT FUTURE
G NATURAL GAS
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GEN GENERAL
GFGI GOVERNMENT FURNISHED /
GOVERNMENT INSTALLED
GFRG GLASSFIBER REINFORCED GYPSUM
GFRC GLASSFIBER REINFORCED CONCRETE
GL GLASS/GLAZING
GLU LAM GLUE LAMINATED WOOD
GPM GALLONS PER MINUTE
GRAN GRANITE
GSB GYPSUM SHEATHING BOARD
GTV GATE VALVE
GWT GLAZED WALL TILE
GYP GYPSUM
GWB GYPSUM WALL BOARD
H HIGH
HB HOSE BIBB
HC HOLLOW CORE
HCP HANDICAPPED
HD HEAD
HDBD HARDBOARD
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HORIZ HORIZONTAL
HS HAND SINK
HT HEIGHT
HVAC HEATING, VENTILATION AND
AIR CONDITIONING
HW HOT WATER
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
F
G
H
I
ID INSIDE DIAMETER
INCL INCLUDED
IMP INSULATED METAL PANEL
IN INCH
INFO INFORMATION
INSUL INSULATION/INSULATED
INT INTERIOR
INV INVERT
J-BOX JUNCTION BOX
JAN JANITOR
JST JOIST
JT JOINT
KD KNOCK DOWN
KIT KITCHEN
KO KNOCK-OUT
KW KILOWATT
KWH KILOWATT HOUR
L LENGTH
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LB POUND
LBF/SF POUNDS PER SQUARE FOOT
LDG LANDING
LF LINEAR FOOT
LH LEFT HAND
LKR LOCKER
LLV LONG LEG VERTICAL
LOC LOCATION
LT LIGHT
LR LIVING ROOM
LVR LOUVER
M METER
M2 SQUARE METER
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MBR MASTER BEDROOM
MC MEDICINE CABINET
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE
MI MIRROR
MID MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
MLDG MOULDING
MM MILLIMETER
MO MASONRY OPENING
MOD MODULE
MP METAL PANEL
MR MOISTURE RESISTANT
MTD MOUNTED
MTL METAL
MTG MOUNTING
MULL MULLION
MUN MUNTIN
MW MICROWAVE
N NORTH
NFS NON-FROST SUSCEPTIBLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OVERALL
OBS OBSCURE
OC ON CENTER
OD OUTSIDE DIAMETER
OF/CI OWNER FURNISHED / CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED / OWNER INSTALLED
OFD OVERFLOW DRAIN
OH OVER HANG
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
OVHD OVER HEAD
J
K
L
M
N
O
P
PA PUBLIC ACCESS
PC PIECE
PCC PRECAST CONCRETE
PEND PENDANT
PERIM PERIMETER
PH PENTHOUSE
PLAS PLASTER
PLBG PLUMBING
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PNL PANEL
PR PAIR
PROP PROPERTY
PREFAB PREFABRICATE
PT PAINT
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER
AND RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT
QT QUARRY TILE
R RISER
R RADIUS
RA RETURN AIR
RB RUBBER BASE
RB HK ROBE HOOK
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REF REFRIGERATOR
REFL REFLECTED
REG REGISTER
REINF REINFORCE
RECS RECOMMENDATIONS
REQD REQUIRED
RESIL RESILIENT
REST REST ROOM
REV REVISION
RTF RUBBER TILE FLOOR
RFG ROOFING
RLG RAILING
RH RIGHT HAND
RND ROUND
RM ROOM
RO ROUGH OPENING
RWL RAIN WATER LEADER
S SOUTH
SA SUPPLY AIR
SAB SOUND ATTENUATION BLANKET
SB SPLASH BLOCK
SC SOLID CORE
SCHED SCHEDULE
SCD SEAT COVER DISPENSER
SCP SCUPPER
SCR SHOWER CURTAIN ROD
SCRN SCREEN
SD SMOKE DETECTOR
SECT SECTION
SED SEE ELECTRICAL DRAWINGS
SF SQUARE FEET
SHT SHEET
SHR SHOWER
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SL SLOPE
SLDG SLIDING
SLNT SEALANT
SM SHEET METAL
SND SANITARY NAPKIN DISPENSER
SNDU SANITARY NAPKIN DISPOSAL UNIT
SPC SPACING
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SQ SQUARE
SSD SEE STRUCTURAL DRAWINGS
SST STAINLESS STEEL
SMD SEE MECHANICAL DRAWINGS
SMLS SEAMLESS
SS SOLID SURFACE
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STR STRINGERS
STRUCT STRUCTURAL
SURR SURROUND
SUSP SUSPENDED
SVCE SERVICE
SW SWITCH
SYMM SYMMETRICAL
SYS SYSTEM
Q
R
S
T
T TREAD
TB TOWEL BAR
TBD TO BE DETERMINED
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
T&G TONGUE AND GROOVE
THRES THRESHOLD
THRU THROUGH
THK THICKNESS
TK BD TACK BOARD
TMPD TEMPERED
TOC TOP OF CURB
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF SLAB
TOW TOP OF WALL
TPD TOILET PAPER DISPENSER
TPH TOILET PAPER HOLDER
TS TUBE STEEL
TSH TOWEL SHELF
TSTAT THERMOSTAT
TV TELEVISION
TYP TYPICAL
TLT TOILET
UBC UNIFORM BUILDING CODE
UC UNDERCUT
UNGD UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UNFIN UNFINISHED
UNO UNLESS OTHERWISE NOTED
UR URINAL
VAR VARIES
VB VALVE BOX
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VOL VOLUME
VP VENEER PLASTER
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WIDE
W/ WITH
WC WALL COVERING
WCLR WATER COOLER
WD WOOD
WDSP WASTE DISPOSER
WDW WINDOW
WF WIDE FLANGE
WGL WIRED GLASS
WH WATER HEATER
W/O WITHOUT
WP WATERPROOF / WATERPROOFING
WR WATER REPELLENT
WSCT WAINSCOT
WSP WET STAND PIPE
WT WEIGHT
WWF WELDED WIRE FABRIC
U
V
W
MATERIALS LEGEND
CONCRETESAND, MORTAR, PLASTER,
TILE, BACKER BOARD
EARTH (UNCLASSIFIED FILL)
CLASSIFIED COMPACTED
FILL
INSULATION - PANEL
GYPSUM BOARD
PLYWOOD
INSULATION - BATT
ACOUSTIC CEILING PANEL
STEEL
ALUMINUM
GLAZING, GLASS
CARPET
FLOORING - CERAMIC TILE
OR RESILIENT
INSULATION - UNDERSLAB
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF8/
/2
4:
:5
P
M B
IM
.0
W
R S
T R ep la ce W at er
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r vt
M.BARTOLOME
J.DOUGHERTY
D.ZIEMER
A0.1
ABBREVIATIONS AND
SYMBOLS LEGEND
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST 12 63
A3.1- GL
A3.1- GL
A3.1- GL
A3.1- GL
1 3
A
CC
A3.1- GL
A3.1- GL
A
101A
101B
A
2'
1"
3'
/2
A
A
A
Bi
B B
B
40' - 0"
VEHICLE BAY
PROCESS ROOM
CHEMICAL
STORAGE
A
3"
20' - 0" 20' - 0"
B
5'
6'
5'
/2
3'
/2
2'
/2
10"
FP1
FP2
FP3
A4.1- GL
FP6
FP7
FP7
5' - 0"
5' - 1 1/2" 10' - 11 3/4"
FP2
3'
5' - 1 7/16"
5' - 4 1/2" 3' - 6 1/2"
/2
102B
5' - 0"
FP5
FP8
C
C C
CC
C
FP4
FP4
FP4
A3.1- GL
A2.1- GL
A4.1- GL
FP9
FP10
A2.1- GL 3
A2.1- GL 4
1"
6' - 0"
2' - 0"
FP4
1'
1'
PER SCHEDULEPER SCHEDULEPER SCHEDULE
P E
R S
C H
E D
U
LE
P E
R S
C H
E D
U
LE
P E
R S
C H
E D
U
LE
FINISH FLOOR
OS F/F N F
PER SCHEDULE
P E
R S
C H
E D
U
LE
3' - 0" 6" 2' - 0" 6"
3'
3'
6"
WALL TYPE A
STRUCTURAL MEMBER, SEE
METAL BUILDING PACKAGE
FOR SIZE AND SPACING
GIRT, SEE METAL
BUILDING PACKAGE FOR
SIZE AND SPACING
6" INSULATED METAL PANEL
WALL TYPE B(i)
5/8" GYPSUM, EACH SIDE
3 5/8" METAL STUD @ 24" O.C. TO
UNDERSIDE OF STRUCTURE ABOVE
ROOF TYPE A
STRUCTURAL MEMBER, SEE
METAL BUILDING PACKAGE
FOR SIZE AND SPACING
GIRT, SEE METAL BUILDING
PACKAGE FOR SIZE AND SPACING
6" INSULATED METAL PANEL
i - INSULATION WHERE INDICATED
2" STANDING-SEAM METAL
ROOFING
WALL TYPE C
3 5/8" METAL STUD @ 24" O.C.
6" INSULATED METAL PANEL
1/2" SHEATHING
FRP PANEL (INTERIOR SIDE OF
ROOM 103 ONLY)
FLOOR PLAN NOTES
1. REFERENCE ELEVATION: ALL ELEVATIONS NOTED ON THIS PLAN CORRESPOND TO REFERENCE
ELEVATION [0’-0”] FOR THIS FLOOR LEVEL. DEVIATIONS AND VARIANCES IN THIS ELEVATION MAY
EXIST, AS INDICATED. UPPER FLOOR ELEVATIONS TO BE NOTED ACCORDINGLY. NOTE: THIS
ASSISTS AND ESTABLISHES NOTED VERTICAL CONTROL AT ALL FLOOR PLANS, REGARDLESS TO
FLOOR LEVEL.
2. WALL TAGS CONTAINING THE SUFFIX 'i' SHALL HAVE STUDS FILLED WITH R-13 BATT INSULATION.
GENERAL ARCHITECTURAL NOTES
1. IT IS THE INTENT THAT ALL CONSTRUCTION SHALL CONFORM TO THE 2021 INTERNATIONAL
BUILDING CODE AND THE LATEST AMENDMENTS AND ORDINAINCES. TO THE BEST OF OUR BELIEF, THESE PLANS ARE IN COMPLIANCE WITH THE APPLICABLE ACCESSIBILITY GUIDELINES. IF
SOMETHING IS DEPICTED THAT APPEARS TO BE AT VARIANCE WITH CODE/STANDARDS, PROMPTLY
NOTIFY THE GOVERNMENT IN WRITING.
2. DIMENSIONING (UNLESS NOTED OTHERWISE):
a.TO FACE OF STUD AT METAL STUDS AND TO FACE OF FINISH AT CONCRETE CONSTRUCTION b.DIMENSIONS NOTED AS "CLEAR" ARE CRITICAL MINIMUMS DIMENSIONED FROM FACE-OF-FINISH
TO FACE-OF-FINISH
3. CONTRACTOR TO VERIFY ALL EQUIPMENT AND MATERIAL SIZES AND PROVIDE ADEQUATE
CLEARANCE AS REQUIRED, BEFORE PROCEEDING WITH THE WORK
WALL ASSEMBLY, TYPE - Bi, SEE A2.1
CONTINUOUS METAL STUD
6" INSULATED METAL PANEL
STRUCTURE BELOW PER MFR
FILL GAPS BETWEEN WALL ASSEMBLY
AND IMPS WITH SEALANT
METAL STUD, CUT AT STRUCTURE
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
CB
APPROXIMATE
LOCATION OF
SEISMIC BRACINGS
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF8/
/2
4:
:5
P
M B
IM
.0
W
R S
T R ep la ce W at er
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r vt
M.BARTOLOME
J.DOUGHERTY
D.ZIEMER
A2.1-
GL
FLOOR PLAN
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
A2.1- GL
1 FLOOR PLAN
SCALE OF FEET
DOOR SCHEDULE
DOOR OR BORROWED LITE FRAME
GLAZING
TYPE
FIRE
RATING
(MINUTES) REMARKSOPENING TYPE
SIZE
MAT FINISH MAT FINISHWIDTH HEIGHT
101A OS 11' - 10" 12' - 0" ISTL FF STL
101B F/F 5' - 0" 7' - 0" IHM PAINT IHM PAINT PAIR
102A N 3' - 0" 7' - 0" HM PAINT HM PAINT SG
102B F 3' - 0" 7' - 0" IHM PAINT IHM PAINT
103A F 3' - 0" 7' - 0" HM PAINT IHM PAINT
DOOR TYPES
FP1 OVERHEAD SECTIONAL DOOR TRACK ABOVE
FP2 TRENCH DRAIN, SEE MECHANICAL FOR ADDITIONAL INFORMATION
FP3 7'-0" WHEEL STOP. REFER TO SPECIFICATION 321713. FINAL LOCATION TO BE DETERMINED
BY NPS REP IN FIELD
FP4 BOLLARDS, SEE STRUCTURAL AND CIVIL
FP5 CONTINUOUS GIRTS
FP6 EDGE OF CANOPY ABOVE
FP7 SEISMIC BRACING
FP8 WORKTABLE WITH SINK, SEE SPEC SECTION 12 35 00
FP9 TRENCH DRAIN TO BE COVERED WITH PLATE
FP10 ALTERNATING TREAD DEVICE WITH 30" X 30" MINIMUM PLATFORM
XX KEYED NOTES
A2.1- GL
2 WALL CONNECTION - PLAN
SCALE A
SCALE A
SCALE OF INCHES
12 6 12
SCALE B
SCALE B
NOT TO SCALE A2.1- GL
3 INTERIOR ELEVATION AT WELL OPENING4
A2.1 - GL
VIEW AT DOOR 102B
NOT TO SCALE SCALE A
13 63
A3.1- GL
A3.1- GL
A3.1- GL
A3.1- GL
1 3
A
C
A3.1- GL
A3.1- GL 2
B
6" 20' - 0" 20' - 0"
6"
6"
6"
5' - 0"
1" / 12" 1" / 12"
2" / 12" 2" / 12"
1" / 12"
P E
A K
P E
A K
A2.2- GL
A2.2- GL
A2.2- GL
A2.2- GL SIM
A2.2- GL
SIM
A2.2- GL
SIM
A2.2- GL
SIM
FLUE UP THROUGH ROOF.
SEE 1 / M4.1-GL
A3.1- GL
A2.2- GL
A2.2- GL
A2.2- GL
A2.2- GL
A2.1- GL 3
2CLOSER STRIPS
METAL CLOSURE SET
IN BUTYL SEALANT
ROOF TYPE A, SEE A2.1
ROOF PANEL CLIP BY MFR
TWO-PART FOAMED-
IN-PLACE URETHANE
PERLINS PER MFR
C
SECONDARY FRAMING & RAKE ANGLE
CONTINUOUS BUTYL SEALANT W/
MARRIAGE BEAD TO PANEL FACE
CONTINUOUS BUTYL SEALANT
12 GA. STAINLESS STEEL HIDDEN
FASTENER CLIP (1 PER PANEL, PER
SUPPORT) SET CLIP IN BUTYL SEALANT
CAP TRIM W/ POP RIVET @ 8" O.C.
(SEALANT BETWEEN INTERIOR AND
EXTERIOR CAP TRIMS)
STANDING SEAM TRIM SUPPORT
RAKE FASCIA
FIELD CUT PANEL AS NEEDED FOR
PROPER LAYOUT REQUIREMENTS
B.O. DECK AT EAVE
14' - 0"
INSIDE CLOSURE STRIP W/ 1"
x 3/16" BUTYL TAPE SEALANT
AT TOP AND BOTTOM
LOW EAVE TRIM
FIELD-FILL W/ COMPRESSIBLE
INSULATION
IMP ROOF ASSEMBLY
NOTE: HOT STACKS
HAVE THIMBLES.
CL
WATERTIGHT FLASHING
ROOF PENETRATION
FRAMING PER MFR
4"
2" STANDING-SEAM
METAL ROOFING
3X2X1/4 HSS PER STRUCT
2X2 ANGLE PER STRUCT
1/8" POP RIVETS
AT 12" O.C.
RAKE TRIM
FIELD CUT AND BEND
PANEL UP 1 1/2"
1/4" BENT PLATE PER STRUCT
2" STANDING-SEAM
METAL ROOFING
3X2X1/4 HSS
PER STRUCT
1 1/2" METAL ROOF
DECK PER STRUCT
1/8" RIVETS AT 12" O.C.
RIDGE COVER
3X2X1/4 HSS PER STRUCT
1 1/2" METAL ROOF
DECK PER STRUCT
NON-SKINNING BUTYL
SEALANT ON THE TOP OF
PANEL'S MALE LEG
NON-SKINNING BUTYL
SELAND APPLIED ON SIDE
OF PANEL'S MALE LEGAND
TIED INTO BUTYL TAPE
FASTENERS AS REQUIRED
NON-SKINNING BUTYL TAPE
SHEET METAL
TRIM CLEAT
EAVE FLASHING
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF8/
/2
4:
:5
P
M B
IM
.0
W
R S
T R ep la ce W at er
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r vt
J.LI
J.DOUGHERTY
D.ZIEMER
A2.2-
GL
ROOF PLAN AND DETAILS
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
1/4" = 1'-0"A2.2- GL
4 ROOF PLAN
A2.2- GL
8 ROOF PEAK DETAIL
A2.2- GL
7 ROOF RAKE DETAIL
A2.2- GL
6 EAVE DETAIL
A2.2- GL
5 ROOF PENETRATION DETAIL
A2.2- GL
3 CANOPY RAKE DETAIL
A2.2- GL
2 CANOPY PEAK DETAIL
A2.2- GL
1 CANOPY EAVE DETAIL
SCALE OF FEET
SCALE A
SCALE OF INCHES
12 6 12
SCALE B
SCALE OF INCHES
SCALE C
SCALE A SCALE C
SCALE C
SCALE C
SCALE B
SCALE B
SCALE B
SCALE B
14 63
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
AC B
4" / 1 2"
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
1" / 12"1" / 12"
1" / 12"
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
1 3
1" / 12"1" / 12"
1" / 12"
2" / 12" 2" / 12"
8'
6'
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
A CB
4" / 12"
2'
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
1 3
1" / 12" 1" / 12"
A2.2- GL
A2.2- GL
VEHICLE BAY
PROCESS ROOM
A2.2- GL
SIM
A4.1- GL
A4.1- GL
A4.1- GL
SIM
A4.1- GL
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
A CB
FP3
A4.1- GL
A2.2- GL
A4.1- GL
VEHICLE BAY
CANOPY. SEE A2.2 AND S2.5
FIRST FLOOR
0' - 0"
B.O. DECK AT EAVE
14' - 0"
C
A4.1- GL
A4.1- GL
A2.2- GL
SIM
A4.1- GL
A2.2- GL
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF8/
/2
4:
:5
P
M B
IM
6 0
.0
W
R S
T R ep la ce W at e r
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r v t
J.LI
J.DOUGHERTY
D.ZIEMER
A3.1-
GL
EXTERIOR ELEVATIONS &
SECTIONS, WALL SECTION
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
3/16" = 1'-0"A3.1- GL
4 WEST ELEVATION
3/16" = 1'-0"A3.1- GL
7 SOUTH ELEVATION
3/16" = 1'-0"A3.1- GL
6 NORTH ELEVATION
3/16" = 1'-0"A3.1- GL
3 EAST ELEVATION
3/16" = 1'-0"A3.1- GL
5 LONGITUDINAL SECTION
3/16" = 1'-0"A3.1- GL
2 CROSS SECTION
A3.1- GL
1 SECTION AT EXTERIOR MAN DOOR
4 0 4 128
SCALE OF FEET
SCALE A
SCALE OF FEET
2 0 2 4
SCALE B
SCALE A
SCALE A
SCALE ASCALE A
SCALE A
SCALE A SCALE B
15 63
MACHINE SCREW WITH COUNTER SINK
HEAD, TAP HSS
4" TYPE V RIGID INSULATION
3/8" X 14" X 4" BENT STEEL PLATE- PAINT
3/8" X 4" STEEL PLATE
INSULATED SECTIONAL OVERHEAD DOOR
1/4" FILLET SKIP WELD- EACH SIDE
C6 X 10.5 STEEL CHANNEL
JAMB FLASHING W/ POP RIVETS
FIRST FLOOR
0' - 0"
C
WEATHERSEAL
INSULATED SECTIONAL
OVERHEAD DOOR AND TRACK
2" THERMALLY BROKEN
THRESHOLD- FILL WITH
RIGID INSULATION BELOW
WALL ASSEMBLY BEYOND
UNDER SLAB RIGID
INSULATION
DAMP PROOFING
THICKENED EDGE SLAB,
REFER TO 5/S2.1
BOLLARDS BEYOND W/ FULL
HEIGHT PLASTIC SLEEVE
EXTEIROR
BOLLARD FOOTING
BEYOND PER CIVIL.
C
WALL ASSEMBLY:TYPE A
TUBE STEEL HEADER- REFER TO
STRUCTURAL
4" TYPE V RIGID INSULATION
BENT STEEL PLATE- PAINT
INSULATED SECTIONAL OVERHEAD DOOR
PRE-FINISHED METAL TRIM
MACHINE SCREW WITH
COUNTER SINK HEAD, TAP HSS
STRUT BRACKET PER MANUFACTURER
3/8" X 4" STEEL PLATE
1/4" FILLET SKIP WELD- EACH SIDE
FIRST FLOOR
0' - 0"
C
THERMALLY BROKEN THRESHOLD -
FILL WITH RIGID INSULATION BELOW
IHM DOOR AS SCHEDULED
IHM FRAME AS SCHEDULED
UNDERSLAB RIGID INSULATION
DAMP PROOFING
THICKENED EDGE SLAB,
REFER TO 1/S2.1 AND 2/S2.1
STRUCTURAL MEMBER BEYOND
IMP BEYOND
CANOPY FOOTING BEYOND
PER 1/S2.5 AND 2/S2.5
C
6" INSULATED METAL PANEL, TYP
INSULATED EXTERIOR DOOR
INSULATED METAL FRAME, FASTEN TO
SHIM AND C CHANNEL. OVERLAP GAP
BETWEEN STRUCTURE AND METAL
PANEL WITH FRAME BY 1 INCH MINIMUM
STRUCTURE BEYOND
1' - 4"
SHEET METAL FLASHING
2" STANDING-SEAM
METAL ROOF PANELS
HEADER PER IMP MFR
METAL TRIM, POP RIVETED PER IMP MFR'S
RECOOMENDATIONS, PREFINISHED TO
MATCH IMP SEALANT1/8" RIVETS AT 8" O.C. - SET IN
CONTINUOUS SELANT TAPE
SEALANT
METAL ROOF DECK. SEE STRUCT.
CANOPY STRUCTURE. SEE STRUCT.
C
6" INSULATED METAL PANEL, TYP
INSULATED EXTERIOR DOOR
INSULATED METAL FRAME, FASTEN TO
SHIM AND C CHANNEL. OVERLAP GAP
BETWEEN STRUCTURE AND METAL
PANEL WITH FRAME BY 1 INCH MINIMUM
HEADER PER IMP MFR
STEEL CAP TRIM - HEM EDGES,
PREFINISHED TO MATCH IMP
WALL ASSEMBLY, SEE A2.1
SLOTTED DEFLECTION TRACK
J TRIM
ROOF PURLINS PER BLDG MFR
INSULATION WHERE INDICATED
ROOF TYPE A, SEE A2.1
12GA STAINLESS STEEL HIDDEN FASTENER CLIP
(1) PER PANEL, PER SUPPORT) SET CLIP IN BUTYL
SEALANT
(2) 1/4" HEX HEAD FASTENERS W/O WASHER
TRANSITION FLASHING
BUTYL TAPE SEALANT AT TOP AND BOTTOM
BASE TRIM W/ POP RIVETS
CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
CONTINUOUS BUTYL
SEALANT BOTH SIDES
OF TRIM
TRANSITION FLASHING
FIRST FLOOR
0' - 0"
CONTINUOUS BUTYL SEALANT
BOTH SIDES OF TRIM W/ MARRIAGE
BEAD TO VERTICAL PANEL JOINT
STEEL BASE ANGLE
CONCRETE ANCHOR
FASTENING CLIP WITH (2) 1/4" -
14 HWH BI - METAL FASTENERS
*PRE-DRILLING REQUIRED
BASE FLASHING
METAL FLASHING, EXTEND 6"
BELOW GRADE
DAMP
PROOFING
SHEET
PMIS/PKG NO.
DRAWING NO.
187491
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF8/
/2
4:
:5
P
M B
IM
.0
W
R S
T R ep la ce W at er
S ys te m
/W R
S T
_1
7-
7_
C E
N T
R A
L_ A
R C
H .r vt
J.LI
J.DOUGHERTY
D. ZIEMER
A4.1-
GL
DETAILS
WRANGELL-ST. ELIAS NATIONAL PARK & PRESERVE12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
1 1/2" = 1'-0"A4.1- GL
5 EXTERIOR SECTIONAL DOOR JAMB
1 1/2" = 1'-0"A4.1- GL
4 EXTERIOR SECTIONAL DOOR THRESHOLD
1 1/2" = 1'-0"A4.1- GL
6 EXTERIOR SECTIONAL DOOR HEAD DETAIL
A4.1- GL
7 EXTERIOR MAN DOOR THRESHOLD
A4.1- GL
9 EXTERIOR MAN DOOR HEAD DETAIL
A4.1- GL
8 EXTERIOR MAN DOOR JAMB DETAIL
A4.1- GL
3 DEFLECTION TRACK DETAIL
A4.1- GL
2 WALL TO ROOF CONNECTION DETAIL
A4.1- GL
1 BASE DETAIL
SCALE OF INCHES
12 6 12SCALE A
SCALE A
SCALE A
SCALE A
SCALE A
SCALE A
SCALE A SCALE A
SCALE A
SCALE A
16 63
SYMBOLS
NORTH ARROW
GRID LINE
GRID BUBBLE
SOIL
GENERAL SYMBOLS
OPENING IN FLOOR OR WALL
A
M/E
DIMENSION PER
ARCHITECT
DIMENSION PER MECHANICAL OR
ELECTRICAL
CONNECTORS
CONCRETE ANCHOR BOLT
PLAN SECTION
DRILL IN CONCRETE ANCHOR
(X'-X") TOP OF FOOTING RELATIVE TO DATUM
[X'-X"] TOP OF WALL OR BEAM ELEVATION
ELEVATION RELATIVE TO DATUM
WORK POINT
DIRECTION OF SPAN
LIMIT OF SPAN
SLOPE
SURFACE - SLOPE UP
SURFACE - SLOPE DOWN
SURFACE - SLOPE TWO WAYS
SURFACE - STEPPED
SURFACE - STEPPED AND SLOPED
CONCRETE SYMBOLS
F1 FOOTING TYPE PER SCHEDULE
CONCRETE OVER STEEL FLOOR DECK-
LONGITUDINAL
CONCRETE OVER STEEL FLOOR DECK-
TRANSVERSE
CONCRETE WALL IN SECTION
CONCRETE CURB/PARTIAL HEIGHT
WALL
CONCRETE WALL BELOW THIS LEVEL
CHANGE OF SLAB THICKNESS
STEEL SYMBOLS
DETAIL IDENTIFIERS
DETAIL LABEL
SCALE
SHEET NUMBER WHERE
DETAIL / SECTION /
ELEVATION IS SHOWN
NUMBER OF
DETAIL
INDICATES
DIRECTION OF
CUTTING PLANE
SEE 1 / S201
FOR ADD'L INFO
SHEET NUMBER
WHERE DRAWN
SECTION / DETAIL / ELEVATION
NUMBER
NUMBER OF SECTION
NUMBER OF
ELEVATION
DETAILELEVATION
SECTIONTEXT NOTATION
S402
S402
SHEET NUMBER
WHERE DETAIL /
SECTION / ELEVATION
IS SHOWN
BEAM/GIRDER
BRACING
COLUMN
DIAGONAL BRACING
BEAM/COLUMN SPLICE
STEEL IN CROSS SECTION
BOLT
NAIL
DETAIL NUMBER
X'-X" TOP OF SLAB RELATIVE TO DATUM
S402
S204
TITLE
1/8" = 1'-0"
X"
X"
X
A K
AF AL
T S
TA
E O
49 TH
S
JASON E KWIATKOWSKI
No. CE 118884
REG IST ER E D P R O F ES S I O NA L E NG IN
EER
SHEET
PMIS/PKG NO.
DRAWING NO.
187491GL
SUB SHEET NO.DESIGNED:
CADD:
TECH REVIEW:
DATE:
TITLE OF SHEET
OF 63
12-01-202311
/2 6/
0:
:3
A
M C
:\U se rs \jk w ia tk ow sk i\D oc um en ts
\W R
S T
_G le na lle n_ M od
_R
_S tr uc tu ra l_
C en tr al
_j kw ia tk ow sk iQ V
7Q C
.r vt
SC
JK
SC
S0.1
SYMBOLS
WRANGELL - ST. ELIAS NATIONAL PARK & PRES.12/01/2023
248940
REPLACE DEFICIENT VC/HQ WATER
TREATMENT SYSTEM WRST
RND ROUND
RO ROUGH OPENING
RTN RETURN
SBN SHEAR WALL BOUNDARY
NAILING
SC SLIP CRITICAL
SCHED SCHEDULE
SECT SECTION
SHT SHEET
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SOG SLAB ON GRADE
SPC SPACE, SPACED, SPACING
SPEC SPECIFICATION
SRPE STEEL REINFORCED
POLYETHYLENE
SQ SQUARE
SS STAINLESS STEEL
SSH SHORT SLOTTED HOLE
STAG STAGGER, STAGGERED
STD STANDARD
STIFF STIFFENER
STIR STIRRUP
STL STEEL
STRUC STRUCTURAL
SUPP SUPPORT
SYM SYMMETRICAL, SYMMETRY
SW SHEAR WALL
T/ TOP OF
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TEMP TEMPERATURE
THK THICK, THICKNESS
THRU THROUGH
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TR THREADED ROD
TRANS TRANSVERSE
TYP TYPICAL
TWS THREADED WELDED STUD
UON UNLESS OTHERWISE NOTED
VERT VERTICAL
W WIDTH, WIDE FLANGE
w/ WITH
WD WOOD
WHS WELDED HEADED STUD
W/O WITHOUT
WP WORK POINT
WT WEIGHT
WWR WELDED WIRE
REINFORCEMENT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
L LENGTH, ANGLE
LB, # POUND
LF LINEAL FOOT
LL LIVE LOAD
LLBB LONG LEGS BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATION, LOCATE
LONGIT LONGITUDINAL
LP…